Hybrid Ring/Radial Final Circuits

Total Page:16

File Type:pdf, Size:1020Kb

Hybrid Ring/Radial Final Circuits PE NICEIC OCTober 2015:Layout 1 06/08/2015 15:13 Page 1 TECHNICAL ADVICE taking you step by step through procedures and requirements for electrical installations Hybrid ring/radial final circuits ICEIC is sometimes asked whether a ring Ring circuit cable (installed rating 20 A min) final circuit has to be Nsupplied directly from Ring !nal circuit a protective device in the distribution board or consumer unit, or whether it is permitted to supply the two ends of the Junction box (or possibly double-pole switch or contactor) rated at 30/32 A min ring via a dedicated radial circuit Cable connected to 30/32 A overcurrent protective device Radial circuit cable cable, as shown in Fig. 1, in consumer unit (installed rating 30/32 A min) thereby forming a hybrid L OUT N ring/radial circuit. OUT This question can arise where, for example, the contractor wishes to Consumer unit make use of a redundant radial circuit cable previously installed for another Fig 1 Typical ring final circuit supplied via a radial circuit cable, purpose (such as a cooker circuit) to forming a hybrid ring/radial circuit supply a ring final circuit, or where a Periodic Inspection of an existing hybrid circuit, the ‘single point of of the socket-outlets ( I⌬n ≤ 30 mA) in installation reveals such an supply’ is the point at which the two accordance with Regulation 411.3.3. arrangement. ends of the ring part of the circuit are Also, if any part of the circuit cable connected to the radial part (that is, at The same question may also arise is concealed in a wall or partition, it the junction box, switch or contactor as where the contractor wishes to control must be provided with additional labelled in Fig 1). a ring final circuit by means of a switch protection by an RCD ( I⌬n ≤ 30 mA) as for functional purposes, or possibly by A hybrid ring/radial final circuit must required by Regulations 522.6.202 means of a contactor, controlled by an be arranged to meet all the relevant and 522.6.203. emergency stop push button (such as requirements of BS 7671 , as amended, in a teaching situation), the supply the main ones of which are Cable sizing with regard to being brought to the switch or summarised as follows. normal load and overload contactor via a dedicated radial circuit The current-carrying capacity ( Iz) of cable. Protection against electric the cable in the radial part of the circuit shock The answer is that it is permissible must be not less than 30 A or 32 A, to to form a hybrid ring/radial circuit, even As for any other final circuit, the match the circuit overcurrent though BS 7671 defines a ring final requirements of Chapter 41 for electric protective device rating ( In) of 30 A or circuit as ‘ A final circuit arranged in the shock protection have to be met, 32 A. Where the protective device is a form of a ring and connected to a including those of Section 411 for earth semi-enclosed (rewireable) fuse, Iz single point of supply’. For such a fault loop impedance ( Zs) and, where must not be less than In divided by applicable, RCD additional protection 0.725. Regulation 433.1.202 refers. PE NICEIC OCTober 2015:Layout 1 06/08/2015 15:13 Page 2 TECHNICAL ADVICE The ring part of the circuit must ring parts of the circuit. These voltage 10 mA, the circuit will require a high meet the same overload protection drops added together make up the integrity protective conductor requirements as for any other ring total voltage drop in the circuit. This connection in accordance with final circuit, which is usually achieved may mean, for example, that the Regulation Group 543.7. through compliance with Regulation maximum allowable length of the ring 433.1.204. part of the circuit will be less than that Electrical Testing Despite the non-conventional form for a ring final circuit connected For verification of the hybrid of a hybrid ring/ radial circuit, the total directly to the distribution board. ring/radial circuit, the circuit details and test results for each part of the load current ( Ib) to be supplied by the Protective conductor in the ring overall circuit, the radial and the ring circuit, making due allowance for any part of the circuit diversity, must still be no greater than parts, should be recorded separately the 30 A or 32 A rating of the circuit Except where the circuit protective on the appropriate schedule protective device. Thus, for example, conductor in the ring part of the circuit contained in the NICEIC Electrical the floor area served by the circuit is formed by a metal covering (such as Installation Certificate for Small should be no greater than would be a metallic cable sheath) or enclosure Installations not exceeding 100 A, as the case if an ordinary ring final circuit (such as metal conduit) containing all shown in Fig 2, or where appropriate having the same protective device the conductors of the ring, the on an EIC. protective conductor must be run in rating was installed instead of the Use of a standard circuit might hybrid circuit. the form of a ring, as required by Regulation 543.2.9. Both ends of the be easier Accessibility of connections protective conductor ring must be It will be appreciated from this As is required for all electrical connected to the earthing terminal at article that the use of a hybrid connections, the connections the origin of the ring (that is, the ring/radial circuit arrangement can between the radial and ring parts of junction box, switch or contactor in involve significant design effort. As an the circuit (in the junction box, switch Fig 1). alternative, for household and similar installations, installers should consider or contactor in Fig 1) must be arranged Earthing for equipment having to be accessible throughout the life of the use of the standard ring or radial high protective conductor socket-outlet circuit arrangements the installation for inspection, testing currents and maintenance (Regulation 132.12 shown in Appendix 15 of BS 7671 , for refers). If the circuit is intended to supply which tables of maximum cable length one or more items of equipment are given in the NICEIC Site Guide for Voltage drop where it is known or reasonably to be Electrical Installations . Account must be taken of the expected that the total protective voltage drops in both the radial and conductor current is likely to exceed ) This certificate is not valid k r if the serial number has DCN8/ o w been defaced or altered e h t g n i r ELECTRICAL INSTALLATION CERTIFICATE FOR SMALL INSTALLATIONS NOT EXCEEDING 100 A e d r o CIRCUIT DETAILS TEST RESULTS n o s 1 n r d Circuit impedances Circuit designation 7 RCD Circuit o o i Overcurrent protective devices 6 r Insulation resistance e t Maximum 4 7 h RCD y e t c g conductors: csa t operating p x S i e ( ) e b i d n r s W i B Test n measured d e t d i r m t m Z ) e n a times n e i ) y t n l u f i * To be completed only where this consumer unit is remote from 1 o u v e 1 b e All circuits D button e h r 7 Ring final circuits only o c o m w g c earth fault loop 7 m n I d c t r BS (EN) d p 6 cpc e r Live s y i r u , n 6 f P i i t t t o n e 7 p t s Line/ Neutral Line/Earth Neutral/Earth e i Line/Line i the origin of the installation. operation t e c 7 (measured end to end) (At least one column d o n t g m at 5 I e c - a p i i o c impedance, Z at I A b u s S . t r r n e e n t n S s x r i e r a D x m c to be completed) e T e e B e t D r e p m n r Record details of the circuit supplying this consumer unit in the a f o r a i B p p ( p i (if applicable) e a u y m e u y e r r e h r f i o a y 1 n 2 s c O s M b t M p T C R ( T p ( o R N S bold box. 2 2 c l (mm ) (mm ) (s) (mA) (Line) (Neutral) (cpc) (R 1 + R 2) R2 (M ) (M ) (M ) (M ) ( ) ( ) (ms) (ms) ( ) (A) (kA) (W) W W W W W a * n i g i 1 r Hybrid circuit: Radial supplying ring A B NA NA NA NA NA O Ring A B NA NA Lighting circuit A B NA NA NA NA NA ) e t a Shower circuit A B NA NA NA NA NA t s Recording the results in this way will permit R 1+R 2 values to be recorded for the radial part of the circuit and the loop values to be recorded for the ring part. Note: The recorded earth fault loop impedance (Z s) value for the ring includes the radial part of the circuit. Fig 2 An example of the Circuit Details and Test Results recorded on the Electrical Installation Certificate for small installations not exceeding 100 A G For other guidance and publications please see the NICEIC website.
Recommended publications
  • TRUE DC Isolators for PV Systems N Market-Leading Design N 2, 4, 6 & 8 Pole Versions Available N Max
    SI TRUE DC Solar Isolator Brighter Solutions AC vs DC Safe Switching As any electrician is aware the nature of DC switching has to be considered with care because on disconnection an arc can occur that is more arduous than that produced with an AC load because there is no zero point on DC. The nature of this arc means that design considerations have to be made within the switch in order to quench this phenomenon; that not only includes significant contact gaps with high speed of operation, but also thermal transmissive materials. What must be considered is that any AC isolator is predominantly designed with materials chosen such that the load will be AC. This means that the load supply will be a 50/60Hz sine wave, whether it be 230VAC or 400VAC, etc. When switching AC it should be remembered that the nature of the load supply will always pass through ØVAC twice in every cycle and therefore although loads can be ardu- ous in type the supply is self-extinguishing. By that we mean that even if the isolator switches at peak load and an arc is formed between contacts, the action of the supply reducing to ØV means that the load will tend to zero and the arc will be extinguished. DC load, on the other hand, is always there and unless the load becomes zero, the power being pulled through the contacts will always be the same. So if the load is 500VDC 25A it will be 500V 25A now, in 1s , in 1min, in 1hour – that is constant.
    [Show full text]
  • Lecture 5: Electrical Supply and Distribution
    Lecture 5: Electrical Supply and Distribution 5.1 Single Phase Electric Power There is only one phase, i.e. the current flows through only one wire and there is one return path called neutral line to complete the circuit. Single-phase comes to the home with two wires: active and neutral. The neutral wire is connected to earth (water pipe, earth stake, etc.) at the switchboard. Single-phase distribution is used when loads are mostly lighting and heating, with few large electric motors. Single-phase power is: Able to supply ample power for smaller customers, including homes and small, non- industrial businesses. Adequate for running motors up to about 10kw; a single-phase motor draws significantly more current than the equivalent 3-phase motor, making 3-phase power a more efficient choice for industrial applications. 5.2 Three Phase Electric Power It is the Polyphase system where three phases are send together from the generator to the load. Each phase are having a phase difference of 120°, i.e. 120° angle electrically. Therefore, from the total of 360°, three phases are equally divided into 120° each. The power in three-phase system is continuous as all the three phases are involved in generating the total power. Three-phase has four wires: three actives (called phases) and one neutral. The neutral wire is earthed at the switchboard. 3-phase power is: Common in large businesses, as well as industry and manufacturing. Large domestic installations sometimes have three-phase because it distributes the total load in a way that ensures that the current in each phase is lower.
    [Show full text]
  • B4 Building Works Standard Specifications
    THE REPUBLIC OF UGANDA MINISTRY OF WORKS AND TRANSPORT STANDARD SPECIFICATIONS (DRAFT) August 2012 B4 BUILDING WORKS BUILDING B4 FOREWORD The mission of the Ministry of Works and Transport (MoWT) is to promote an adequate, safe and well maintained works and transport infrastructure and services so as to effectively contribute to the socio-economic development of the country. In exercising this mission and in discharging its responsibilities, the Ministry is issuing a series of Design Manuals, Guidelines, Codes and Standards, of which the “Standard Specifications for Building Works” is one part thereof. The Standard Specifications for Building Works will be a nationally recognized document which will serve as a standard reference for the preparation of specifications for works to be undertaken on building construction projects. The major benefits to be gained in applying this document are the harmonization of professional practice in the building construction in Uganda and curtailment of informal developments so as to ensure well-planned, well- maintained, safe, cost effective and decent building developments and human settlements throughout the country. The Standard Specifications will be periodically updated and new editions issued to cater for the dynamic technological developments in the construction industry. Abraham Byandala Minister of Works and Transport August 2012 Ministry of Works and Transport Standard Specifications for Building Works General Table of Contents Part 1: Architectural, Structural and General Works Part 2: Building Sanitation Part 3: Electrical Services Ministry of Works and Transport i Standard Specifications for Building Works TABLE OF CONTENTS PART 1. ARCHITECTURAL, STRUCTURAL and GENERAL WORKS Page 1.0 GENERAL MATTERS ...................................................................................................... 2 1.1 General Conditions of Contract ..............................................................................
    [Show full text]
  • A Practical Guide to the 17Th Edition of the Wiring Regulations
    A Practical Guide to the 17th Edition of the Wiring Regulations This page intentionally left blank A Practical Guide to the 17th Edition of the Wiring Regulations Christopher Kitcher AMSTERDAM • BOSTON • HEIDELBERG • LONDON NEW YORK • OXFORD • PARIS • SAN DIEGO SAN FRANCISCO • SINGAPORE • SYDNEY • TOKYO Newnes is an imprint of Elsevier Newnes is an imprint of Elsevier The Boulevard, Langford Lane, Oxford OX5, 1GB, UK 30 Corporate Drive, Suite 400, Burlington, MA 01803 First edition 2010 Copyright © 2010, Christopher Kitcher. Published by Elsevier Ltd. All rights reserved The right of Christopher Kitcher to be identified as the author of this work has been asserted in accordance with the Copyright, Design and Patents Act 1988. No part of this publication may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying, recording, or any information storage and retrieval system, without permission in writing from the publisher. Details on how to seek permission, further information about the Publisher’s permissions policies and our arrangements with organizations such as the Copyright Clearance Center and the Copyright Licensing Agency, can be found at our website: www.elsevier.com/permissions. This book and the individual contributions contained in it are protected under copyright by the Publisher (other than as may be noted herein). Notices Knowledge and best practice in this field are constantly changing. As new research and experience broaden our understanding, changes in research methods, professional practices, or medical treatment may become necessary. Practitioners and researchers must always rely on their own experience and knowledge in evaluating and using any information, methods, compounds, or experiments described herein.
    [Show full text]
  • Answer the Purpose: 4
    Page 26 1. CONDUCTORS Conductors are defined as materials that easily allow the flow of _________. Metals are _______ conductors while insulators are ______ . The 2 common metals used for conductors in the electrical trade are: ___________ and ______________. Aluminium has become more prevalent for larger C.S.A. conductors as it is cheaper and lighter but more brittle than copper. Current/ Copper/ Aluminium Thermoplastic-sheathed cable (TPS) consists of an outer toughened sheath of polyvinyl chloride (PVC) (the thermoplastic element) covering one or more individual cables which are PVC insulated annealed copper conductors. It is a commonly used type of wiring for residential and light commercial construction in many countries. The flat version of the cable with two insulated conductors and an uninsulated earth conductor all within the outer sheath is referred to as twin and earth. In mainland Europe, a round equivalent is more common. Flat cables (or festoon cables) are made in PVC and Neoprene and are used as trailing cables for cranes, open filed conveyors and shelve service devices. Flat cables offer the advantages of extremely small bending radius’s, high flexibility and minimum wastage of space. Thermoplastic-sheathed cable (TPS) consists of an outer toughened sheath of polyvinyl chloride (PVC) (the thermoplastic element) covering one or more individual cables which are PVC insulated annealed copper conductors. It is a commonly used type of wiring for residential and light commercial construction in many countries. The flat version of the cable with two insulated conductors and an uninsulated earth conductor all within the outer sheath is referred to as twin and earth.
    [Show full text]
  • JUNE, 2020 Implementation Guide Implementation Guide
    BUILDING INSPECTION BOOKLET JUNE, 2020 Implementation Guide Implementation Guide TABLE OF CONTENTS Foreward ............................................................................................................................................................3 Disclaimer ......................................................................................................................................................... 4 1.0 PROJECT DETAILS ...........................................................................................................................5 2.0 DESCRIPTION OF WORKS...........................................................................................................5 3.0 PROJECT TEAM .................................................................................................................................5 3.1 DEVELOPERS TEAM ...................................................................................................................5 3.2 CONSULTANTS TEAM ............................................................................................................... 6 3.3 CONTRACTORS TEAM .............................................................................................................. 7 4.0 BUILDING ARCHITECTURE ........................................................................................................ 8 4.1 BUILDING ARCHITECTURE FOR CLASS A AND B BUILDINGS .......................... 8 4.2 BUILDING ARCHITECTURE FOR CLASS C BUILDINGS .........................................19
    [Show full text]
  • EDS 05-2010 Main Substation Feeder and Ring Main Unit Protection
    Document Number: EDS 05-2010 Version: 4.0 Date: 02/12/2015 ENGINEERING DESIGN STANDARD EDS 05-2010 VALIDITY BEFORE USE BEFORE VALIDITY MAIN SUBSTATION FEEDER AND RING MAIN UNIT S PROTECTION SETTINGS (LPN) Network(s): LPN Summary: This standard describes the protection settings for main substation feeders and ring main units in the LPN area. Owner: Kevin Burt Date: 02/12/2015 ADER MUST CONFIRM IT CONFIRM MUST ADER Approved By: Barry Hatton Approved Date: 08/01/2015 This document forms part of the Company’s Integrated Business System and its requirements are mandatory throughout UK Power Networks. Departure from these requirements may only be taken with the written approval of the Director of Asset Management. If you have any queries about this document please contact the author or owner of the current issue. Applicable To UK Power Networks External All UK Power Networks G81 Website Asset Management Contractors RE THE DOCUMENT, LED Capital Programme ICPs/IDNOs Connections Meter Operators HSS&TT Network Operations UK Power Networks Services Other THIS IS AN UNCONTROL AN IS THIS Document Number: EDS 05-2010 Version: 4.0 Date: 02/12/2015 E Revision Record Version 4.0 Review Date 08/01/2019 Date 02/12/2015 Author Kevin Burt Why has the document been updated – Periodic review What has changed – No content changes Document transferred onto a new template and rules applied S VALIDITY BEFORE US BEFORE VALIDITY S Version 3.2 Review Date 09/11/2015 Date 04/09/2012 Author Lee Strachan Document reviewed for publishing on G81 website Version 3.1 Review Date 09/11/2015 Date 25/08/2011 Author Chris Anderson Reclassified from EI to EDS Version 3.0 Review Date 09/11/2015 Date 19/08/2010 Author David G Edwards IT CONFIRM MUST ADER Rebranded, reviewed and review date extended Version 2.0 Review Date Date 30/10/2006 Author David G Edwards TLF ratings and revised ACB protection settings added Tables (6A and 11A) Version 1.0 Review Date Date 07/04/2004 Author David G Edwards Original, based on Protection Standard Number E 7/6 P 6/1 revision 4.
    [Show full text]
  • Pdf Grade 11 Physics Week 6 Lesson 2
    Ministry of Education Secondary Engagement Programme Grade 11 Physics WEEK 6 Lesson 2 Topic: Electricity Sub-topic: Electricity in Home Objective: Given information and with the aid of diagrams, students will: i. discuss the reasons for using parallel connections of domestic appliances; ii. explain the purpose of a fuse or circuit breaker and the earth wire; iii. select a fuse or circuit breaker of suitable current rating for a given appliance; iv. state the adverse effects of connecting electrical appliances to an incorrect or fluctuating voltage supply. Content: Distributing electricity Electrical energy is most efficiently generated and distributed using alternating current. Most Caribbean countries, and also the USA, utilize an a.c. frequency of 60 Hz. A few territories use a frequency of 50 Hz. Minimizing Power Loss When current travels along a wire, the wire becomes hot and heat energy is lost to the atmosphere. Power is lost according to the formula P = I2 R where P is the power lost, I is the current in the wire and R is the resistance of the wire To minimize power loss, two approaches are used in distribution systems. i. Keep the resistance (R) of the conducting wires as small as possible. The transmission wires, therefore, have larger diameters, since thick wires have less resistance per unit length than thin wires. ii. A second approach is to use small currents in the wires. To achieve this, the power is sent at very high voltages. Household electric circuits Parallel wiring 68 Ministry of Education Secondary Engagement Programme Grade 11 Physics Parallel wiring is used in household circuits rather than series connections so that appliances can be controlled individually without affecting other devices.
    [Show full text]
  • IET Wiring Regulations BS 7671 18Th Edition
    — IET Wiring regulations BS 7671 18th edition Transient overvoltage protection 4 IET WIRING REGULATIONS BS 7671 18TH EDITION — The IET Wiring Regulations require all new electrical system designs and installations, as well as alterations and additions to existing installations, to be assessed against transient overvoltage risk and, where necessary, protected using appropriate surge protection measures (in the form of Surge Protection Devices SPDs). TRANSIENT OVERVOLTAGE PROTECTION - INTRODUCTION 3 — Transient overvoltage protection Introduction Based on the IEC 60364 series, the 18th Edition of BS 7671 Wiring regulations covers the electrical installation of buildings including the use of surge protection. The 18th Edition of BS 7671 applies to the design, In order to observe the Ligntning Protection Zone LPZ erection and verification of electrical installations, concept within BS 7671 and BS EN 62305, all other and also to additions and alterations to existing incoming metallic service lines, such as data, signal installations. Existing installations that have and telecommunications lines, are also a potential been installed in accordance with earlier editions route through which transient overvoltages to of BS 7671 may not comply with the 18th edition damage equipment. As such all such lines will require in every respect. This does not necessarily appropriate SPDs. mean that they are unsafe for continued use or require upgrading. BS 7671 clearly points the reader back to BS EN 62305 and BS EN 61643 for specific guidance. This is A key update in the 18th Edition relates to covered extensively in the Furse guide to BS EN 62305 Sections 443 and 534, which concern protection of Protection Against Lightning.
    [Show full text]
  • Overload Protection of an RCCB Or Switch in an LV Assembly to BS EN 61439-3
    Bringing power to life. Overload protection of an RCCB or switch in an LV assembly to BS EN 61439-3 BS 7671: 2018 IET Wiring Regulations 18th Edition specifies requirements for overload protection of an RCCB or switch in an LV assembly, Regulations 536.4.3.2, 536.4.5 and 536.4.202 refer. This bulletin provides BEAMA member’s guidance for RCCB and switch overload protection however; individual manufacturer’s instructions must be followed, particularly the rated current of the related assembly circuit Inc (A) which must be stated in the documentation supplied with the LV assembly e.g. distribution board or consumer unit. The rated current in the assembly circuit Inc (A) of the switch or RCCB shall be derived from one of the following two methods in diagrams 1 and 2. In both methods, circuits shall be designed so that a small overload of long duration is unlikely to occur. 1. Be greater than or equal to the sum of the rated current of all outgoing circuit OCPDs1 e.g. MCBs, fuses; see diagram 1. Diagram 1 I n1 or In 1 or Inc2 In 1 Inc2 In 3 + I n4 + In5 + In6 + In7 Inc2 or or Inc2 In3In4In5In6In7 In3In4In5In6In7 Inc2 = Rated current of a circuit (A) stated = Circuit-breaker by the assembly manufacturer which may be lower than the = Fuse unenclosed rated current marked on the device (switch disconnector Supplied from upstream 100 A BS 88-3 or BS 1361 cut-out supply fuse or RCCB) due to grouping & internal = Isolating switch / disconnector enclosure temperature etc.
    [Show full text]
  • The Testing of Electrical Installations
    2014 HellermannTyton South Africa Compliance Testers Compliance Test Kits TCTRP TCTDT TCTCDK Description Analogue Digital Digital Kit Kit Kit DMM TBM811 - - Clamp Meter - TBM3030 TBM3030 Insulation Tester T1800 T1851 T1151 Earth Resistance T1805 T1820 T1120 Loop Tester T1825 T1825 T1125 ELCB Tester TEL1TLB TEL1TLB TEL1TLB Phase Rotation T860 T887 T890 Foam TCTRPFM TCTDTFM TCTCDKFM Case TCTCS TCTCS TCTCS Refer to pages 19-24 for Technical Specifications Compliance Combination Tester Model T419 | T89 All the above testers featured in a single lightweight compliance combination tester • Continuity (Low OHM) • Insulation (50/100/250/500/1000 V) • Loop impedance • Earth resistance (resistivity) • ELCB (sensitivity & time) • RS232 Interface or USB • Frequency/Voltage • Phase Rotation • 350 Memory Locations Johannesburg Durban Cape Town Port Elizabeth i (011) 879-6620 (031) 569-9900 (021) 594-7100 (041) 408-2400 Index 1. WHAT IS AN ELECTRICAL INSTALLATION? 1 2. WHO IS RESPONSIBLE? 1 3. HOW CAN A LAYMAN KNOW IF THE INSTALLATION IS SAFE? 1 4. WHERE TO OBTAIN A CERTIFICATE OF COMPLIANCE? 1 5. WHAT MUST BE DONE BEFORE ISSUING A CERTIFICATE OF COMPLIANCE? 1 6. WHAT ELECTRICAL TEST MUST BE CARRIED OUT? 1 Tests to be done 7. CONTINUITY OF ALL BONDING CONDUCTORS 1/2 8. RESISTANCE OF EARTH CONTINUITY CONDUCTOR 2 9. CONTINUITY OF RING CIRCUIT (IF APPLICABLE) 4 10. ISOLOCK TESTER 5 11. EARTH LOOP IMPEDANCE TEST: MAIN SWITCH 4/6 12. ELEVATED VOLTAGE ON NEUTRAL 10 13. EARTH ELECTRODE RESISTANCE (IF REQUIRED) 10 14. INSULATION RESISTANCE 14 15. VOLTAGE (MAIN DB) NO LOAD 14 16. VOLTAGE (MAIN DB) ON LOAD 14 17. VOLTAGE AT AVAILABLE LOAD (WORST CONDITION) 14 18.
    [Show full text]
  • International Electrical Standards & Regulations
    International electrical standards & regulations AN OVERVIEW OF ELECTRICAL INSTALLATIONS Introduction to the installations world he world of electrical installations knowledge of the wiring suited to your specific Tis not always straightforward. regulations and standards requirements in terms of Working on an international project which are applicable in electrical installations and electrical engineers are often bewildered the specific country. communication networks. by the extensive amount of electrical This document compares Continuous innovation standards and wiring regulations which the basic framework No less than 1 800 determines their decisions. of the standards. people are dedicated Therefore, it is essential full-time to research and Rely on the world’s Detailed knowledge for the design engineer development. On average, leading specialist of the wiring rules to obtain more detailed Legrand invests 5% of its As one of the world The purpose of this information by contacting sales each year in R&D. leading specialists document is to clearly the appropriate standards in wiring accessories, present the most and building regulations Sustainable Legrand actively participate frequently encountered organisations. Development: a priority to the elaboration of the sets of wiring rules, For many years, installation standards showing the main One of the most complete the Legrand Group at international (IEC), technical characteristics offer of the market has drawn strength regional (NEC) and local of each set of installation 130 000 catalogue items! from its values to ensure levels. Thus, the technical and main accessories For you, the wealth profitable, sustainable expertise of the Legrand standards. Obviously, on of the Legrand Group’s and responsible growth people makes it possible any given project, it is catalogue offer is the in its business.
    [Show full text]