KEY DESIGN CRITERIA 1. 10% of all new and renovated spaces shall be designed to accommodate bariatric patients, visitors, and guests. 2. A minimum of 1 Bariatric Toilet shall be provided for every 4 Bariatric Exam Rooms per floor. 3. Locate Bariatric Toilets in proximity of Bariatric Exam rooms and along the same accessible path. 4. Water Closets shall be floor mount, rear discharge type with 1,000# static load minimum. 5. Grab bars and Lavatory shall have reinforced supports with a design weight of 500# minimum. 6. A minimum 6'-0" diameter turning space shall be provided within the toilet room. 7. Bariatric Toilets are not considered to be ADA accessible due to the varying clear floor space requirements. 8. All wall accessories shall be located in compliance with ADAAG requirements. 9. Finishes shall follow those listed for Public Toilet Rooms and be coordinated with the CC Room Finish Schedule. 10. The travel path to all Bariatric Rooms shall be maintained as follows: Corridors: 5'-0" minimum (6'-0" preferred) Maintain a minimum 45" clear at all constrictions along path(s) to destination Doorways: 45" minimum (48" preferred)
5" 9'-0" 5"
6'-0"dia. TURNING SPACE WALLS TO BE FULL HT. AND HAVE STC OF 47 MINIMUM 2'-0"
A
D B DOCUMENT HOLDER
C
4070
OTHER FEATURES:
2'-0" 1. CERAMIC/PORCELAIN TILE CHANGE BABY FLOOR AND BASE. 5"5" 4" 4'-4" 8'-0" 3'-4" 5" 5" 4'-0"w. DOOR/FRAME
FLOOR PLAN 1 SCALE: 1/4" = 1'-0" 02'4' 8'
Cleveland Clinic BARIATRIC TOILET TEMPLATE: REVISED 6/27/2011 BARIATRIC TOILET Copyright © 2010 Cleveland Clinic, All Rights Reserved Room Templates GFI, 48" FA DL
4070
NC
NC BABY CHANGE BABY
MEP PLAN 2 SCALE: 1/4" = 1'-0" 02'4' 8'
L.E.D. DOWNLIGHT OS
FULL HEIGHT
PARTITIONS BABY CHANGE BABY
PUBLIC TOILETS: RECESSED LIGHT COVE WITH STAGGERED STRIP FLUORESCENT FIXTURE CLINICAL TOILETS: USE 1 x 4 LIGHT FIXTURE WITH NO BULKHEAD REFLECTED CEILING PLAN 3 SCALE: 1/4" = 1'-0" 02'4' 8'
Cleveland Clinic BARIATRIC TOILET TEMPLATE: REVISED 6/27/2011 BARIATRIC TOILET Copyright © 2010 Cleveland Clinic, All Rights Reserved Room Templates LIGHT COVE ONLY OCCURS IN PUBLIC TOILET LOCATIONS
4'-0"
1'-0" 4'-0"
6" x 12" TILE BASE (TYP.) BARIATRIC TOILET A SCALE: 1/4" = 1'-0" 02'4' 8'
CL
ROBE HOOK
8" 1'-0" 6'-8" 4'-0" 4'-0" 1'-6" 3'-6" 7"
BARIATRIC TOILET B SCALE: 1/4" = 1'-0" 02'4' 8'
Cleveland Clinic BARIATRIC TOILET TEMPLATE: REVISED 6/27/2011 BARIATRIC TOILET Copyright © 2010 Cleveland Clinic, All Rights Reserved Room Templates 3'-6" 1'-0" 1'-6"
7" 3'-0"
BARIATRIC TOILET C SCALE: 1/4" = 1'-0" 02'4' 8'
1'-0" x 1'-0" WALL TILE
CL
3'-0" 3'-0" 1'-0" 2'-10" 3'-4" max. 3'-4"
2'-0" 2'-0"
BARIATRIC TOILET D SCALE: 1/4" = 1'-0" 02'4' 8'
Cleveland Clinic BARIATRIC TOILET TEMPLATE: REVISED 6/27/2011 BARIATRIC TOILET Copyright © 2010 Cleveland Clinic, All Rights Reserved Room Templates 4" 1/2" PARTICLE BOARD W/ PLASTIC LAMINATE FACES AND 2mm ABS EDGES (TYPICAL) 7" 4 1/2"
2"
1'-0" 7"
1'-0" 2"
DOCUMENT HOLDER SCALE: 1 1/2"= 1'-0"
Cleveland Clinic BARIATRIC TOILET TEMPLATE: REVISED 6/27/2011 BARIATRIC TOILET Copyright © 2010 Cleveland Clinic, All Rights Reserved Room Templates