Ventilative Cooling in a School Building: Evaluation of the Measured Performances

Total Page:16

File Type:pdf, Size:1020Kb

Ventilative Cooling in a School Building: Evaluation of the Measured Performances fluids Article Ventilative Cooling in a School Building: Evaluation of the Measured Performances Hilde Breesch * , Bart Merema and Alexis Versele Department of Civil Engineering, Katholieke Universiteit Leuven, Construction Technology Cluster, Sustainable Building, Technology Campus Ghent, 9000 Ghent, Belgium; [email protected] (B.M.); [email protected] (A.V.) * Correspondence: [email protected]; Tel.: +32-9-331-6592 Received: 26 August 2018; Accepted: 18 September 2018; Published: 23 September 2018 Abstract: The test lecture rooms on Katholieke Universiteit Leuven (KU Leuven) Ghent Technology Campus (Belgium) are a demonstration case of Annex 62: Ventilative Cooling of the International Energy Agency’s Energy in Buildings and Communities programme (IEA EBC). The building is cooled by natural night ventilation and indirect evaporative cooling (IEC). Thermal comfort and the performances of ventilative cooling are evaluated. Long-term measurements of internal temperatures, occupancy, opening of windows and IEC were carried out in the cooling season of 2017. The airflow rates through the windows in cross- and single-sided ventilation mode were measured by both tracer gas concentration decay and air velocity measurements. In addition, the air flow pattern is visualized by measuring air temperatures in the room. The results show that good thermal summer comfort was measured except during heat waves and/or periods with high occupancy. Both nighttime ventilation and IEC operate very well. IEC can lower the supply temperature by day significantly compared to the outdoor temperature. The Air Changes Rates (ACR) of the night ventilation greatly depends on wind direction and velocity. The air temperature profile showed that the air is cooled down in the whole lecture but more in the upper zone. The extensive data monitoring system was important to detect malfunctions and to optimize the whole building performance. Keywords: ventilative cooling; nearly zero-energy buildings (nZEB); school building; measurements; thermal comfort 1. Introduction In the recently approved second recast of the Energy Performance of Buildings Directive (EPBD) [1], the member states of the European Union committed themselves to develop a sustainable, competitive, secure, and decarbonized energy system by 2050. An important aspect to achieve this goal is to find a cost-efficient equilibrium between decarbonizing energy supplies and reducing final energy consumption of the building stock. While the first recast of the EPBD [2] required that from 2020, all new buildings in the European Union have to be nearly zero-energy buildings (nZEB), this second recast focusses on renovation strategies. An average renovation rate of 3% annually towards nZEB, where nearly means cost effective, is needed [1]. One of the major new challenges in these highly insulated and airtight buildings is the increased need for cooling and the risk on overheating not only during summer but all year round. In addition, this cooling demand depends less on the outdoor temperature and more on the internal and solar heat gains [3]. A shift is noticed from reduction in heating to reduction in cooling demand. As a consequence, conceptual and building technical measures as well as energy efficient cooling systems are needed in these nZEB buildings to guarantee good thermal comfort all year round. Ventilative cooling is an example of an energy efficient cooling method that can contribute to achieve the goal Fluids 2018, 3, 68; doi:10.3390/fluids3040068 www.mdpi.com/journal/fluids Fluids 2018, 3, 68 2 of 14 of the 2nd recast of the EPBD and was extensively studied within IEA EBC Annex 62 [4]. Ventilative cooling is defined as “the application of the cooling capacity of the outdoor air flow by ventilation to reduce or even eliminate the cooling loads and/or the energy use by mechanical cooling in buildings, while guaranteeing a comfortable thermal environment” [3]. Ventilative cooling strategies depend on the indoor-outdoor temperature difference. For temperate outdoor conditions, i.e., mean outdoor 2 to 10 ◦C lower than indoor temperature, an increased airflow rate by day and night is recommended. For hot and dry, i.e., indoor–outdoor temperature difference between −2 ◦C and +2 ◦C, only the airflow rate during nighttime, i.e., night ventilation, is maximized. Extra natural cooling, like evaporative cooling and earth-to-air-heat-exchanger, or mechanical cooling can be provided to reduce the air intake temperature during daytime [3]. Santamouris and Kolokotska [5] reviewed the state of the art technologies for passive cooling including ventilative cooling and concluded that “the efficiency of the proposed passive cooling systems is found to be high while their environmental quality is excellent. Expected energy savings may reach 70% compared to a conventional air conditioned building”. Night ventilation was found to be very effective to reduce the cooling demand in office buildings and improve thermal summer comfort regardless the climatic conditions [5]. In free floating buildings, amongst others [6–10] monitored that night ventilation can decrease the next day peak internal temperature up to 3 ◦C. In addition, the climatic cooling potential of buildings with night ventilation in Europe was evaluated by Artmann et al. [11]. A very significant climatic cooling potential was found in Northern Europe; a significant in central and Eastern Europe but series of warmer nights can occur. As a consequence, night ventilation may not be sufficient to guarantee good thermal comfort during these periods [11]. Santamouris and Kolokotska [5] also concluded, based on amongst others [12–14], that “indirect evaporative cooling techniques can be low energy solutions for medium and large buildings where passive cooling techniques cannot reach the required comfort conditions”. However, these systems require fan energy, which can be up to 20% less due to lower air velocities [5]. Kolokotroni and Heiselberg [15] give amongst other things, insight in the limitations and barriers to ventilative cooling. The most important are the impact of global warming and heat island effect [6,16,17] noise and pollution [18]. It is expected that the average cooling potential of night ventilation will decrease significantly with regionally varying implications. In Northern Europe, the risk of thermal discomfort in buildings that use exclusively night ventilation is increased while in Central Europe the periods with low night cooling potential are becoming more frequent [19]. Appropriate control is also a requirement to guarantee good thermal comfort. To ensure that the required window opening on a regular basis, the night ventilation strategy should be integrated to the office buildings energy management system [5]. The test lecture rooms of KU Leuven Ghent Technology Campus, which are studied in this paper, were one the demonstration cases of IEA EBC Annex 62: Ventilative Cooling [20]. Natural night ventilation and indirect evaporative cooling techniques are applied. This paper aims to evaluate thermal comfort in this nZEB school building and to discuss the performances of its ventilative cooling systems. First, a description of the building, its systems, and more specifically the ventilative cooling and control strategies are presented. Afterwards, the measurement setup for the evaluation of air flow rates, operation of ventilative cooling and thermal comfort is shown. Section3 presents the results of the measurements and finally the conclusions and lessons learned are presented. 2. Materials and Methods This paragraph describes the building, its systems and the ventilative cooling as well as the measurement setup. Fluids 2018, 3, 68 3 of 14 2.1. Building Description 2.1.1. Building and Use The nZEB school building is realized at the technology campus Ghent of KU Leuven (Belgium) on top of an existing university building. The building contains four zones (see Figure1): two large lecture roomsFluids 2018 (1), 3, andx FOR (2),PEER a REVIEW staircase (3) and a technical room (4). The lecture rooms have a3 floor of 14 area of about 140 m2, a volume of 380 m3. The lecture rooms are designed as identical zones with a different thermal mass.The nZEB The lowerschool building room has is realized a brick at externalthe technology wall camp withus exterior Ghent of insulation KU Leuven while(Belgium) the upper room hason atop lightweight of an existing timber university frame building. external The wall building with contains the same fourU zones-value. (see Both Figure lecture 1): two rooms large have a lecture rooms (1) and (2), a staircase (3) and a technical room (4). The lecture rooms have a floor area concrete slab floor. This results in a light (2nd floor) and a medium (1st floor) thermal mass according of about 140 m2, a volume of 380 m3. The lecture rooms are designed as identical zones with a different to EN ISOthermal 13790 mass. [21 The]. lower room has a brick external wall with exterior insulation while the upper room Tablehas1 a shows lightweight the building timber frame properties. external The wall school with the building same U is-value. designed Both andlecture constructed rooms have according a −1 to the Passiveconcrete slab House floor. standard.This results Thisin a light means (2nd floor) that and the a air medium tightness (1st floor)n50 thermalis lower mass than according 0.6 h and the U-valuesto EN ISO of 13790 the envelope[21]. parts are maximum 0.15 W/m2 K. The windows are constructed Table 1 shows the building properties. The school building is designed and constructed with triple glazing and have a g-value of 0.52. The window-to-wall ratio is 26.5% on both façades. according to the Passive House standard. This means that the air tightness n50 is lower than 0.6 h−1 The window-to-floorand the U-values ratio of the is 13%.envelope The parts windows are maximum are equipped 0.15 W/ withm2 K.internal The windows and externalare constructed solar shading. The externalwith triple solar glazing shading and have are a moveable g-value of 0.52.
Recommended publications
  • Guide to Understanding Condensation
    Guide to Understanding Condensation The complete Andersen® Owner-To-Owner™ limited warranty is available at: www.andersenwindows.com. “Andersen” is a registered trademark of Andersen Corporation. All other marks where denoted are marks of Andersen Corporation. © 2007 Andersen Corporation. All rights reserved. 7/07 INTRODUCTION 2 The moisture that suddenly appears in cold weather on the interior We have created this brochure to answer questions you may have or exterior of window and patio door glass can block the view, drip about condensation, indoor humidity and exterior condensation. on the floor or freeze on the glass. It can be an annoying problem. We’ll start with the basics and offer solutions and alternatives While it may seem natural to blame the windows or doors, interior along the way. condensation is really an indication of excess humidity in the home. Exterior condensation, on the other hand, is a form of dew — the Should you run into problems or situations not covered in the glass simply provides a surface on which the moisture can condense. following pages, please contact your Andersen retailer. The important thing to realize is that if excessive humidity is Visit the Andersen website: www.andersenwindows.com causing window condensation, it may also be causing problems elsewhere in your home. Here are some other signs of excess The Andersen customer service toll-free number: 1-888-888-7020. humidity: • A “damp feeling” in the home. • Staining or discoloration of interior surfaces. • Mold or mildew on surfaces or a “musty smell.” • Warped wooden surfaces. • Cracking, peeling or blistering interior or exterior paint.
    [Show full text]
  • A Comprehensive Review of Thermal Energy Storage
    sustainability Review A Comprehensive Review of Thermal Energy Storage Ioan Sarbu * ID and Calin Sebarchievici Department of Building Services Engineering, Polytechnic University of Timisoara, Piata Victoriei, No. 2A, 300006 Timisoara, Romania; [email protected] * Correspondence: [email protected]; Tel.: +40-256-403-991; Fax: +40-256-403-987 Received: 7 December 2017; Accepted: 10 January 2018; Published: 14 January 2018 Abstract: Thermal energy storage (TES) is a technology that stocks thermal energy by heating or cooling a storage medium so that the stored energy can be used at a later time for heating and cooling applications and power generation. TES systems are used particularly in buildings and in industrial processes. This paper is focused on TES technologies that provide a way of valorizing solar heat and reducing the energy demand of buildings. The principles of several energy storage methods and calculation of storage capacities are described. Sensible heat storage technologies, including water tank, underground, and packed-bed storage methods, are briefly reviewed. Additionally, latent-heat storage systems associated with phase-change materials for use in solar heating/cooling of buildings, solar water heating, heat-pump systems, and concentrating solar power plants as well as thermo-chemical storage are discussed. Finally, cool thermal energy storage is also briefly reviewed and outstanding information on the performance and costs of TES systems are included. Keywords: storage system; phase-change materials; chemical storage; cold storage; performance 1. Introduction Recent projections predict that the primary energy consumption will rise by 48% in 2040 [1]. On the other hand, the depletion of fossil resources in addition to their negative impact on the environment has accelerated the shift toward sustainable energy sources.
    [Show full text]
  • Initial Start-Up When Starting up the Cooler Refrigeration System for the First Time, the Following Events Occur
    SEQUENCE OF OPERATION COOLERS AND FREEZERS COOLERS All standard units are equipped with an adjustable thermostat located on the lower right hand side of the evaporator coil, on the inside of the walk-in. All units are set at the factory to the temperature requested by the customer. Minor adjustments in operating temperature may be made to suit your needs by a qualified refrigeration technician. Polar King recommends that you do not set the temperature colder than required, as this will cause unnecessary power consumption. Recommended temperature for a cooler ranges from +34° to +37° F, unless specified otherwise for special applications. Refrigeration - Initial Start-Up When starting up the cooler refrigeration system for the first time, the following events occur. The operating sequence is as follows: (1) Thermostat calls for refrigerant. (2) Liquid line solenoid valve opens, allowing refrigerant to flow. (3) Pressure control makes the control circuit and the condensing unit operates. (4) When the room thermostat is satisfied, the liquid line solenoid will close, and the compressor will pump down and turn off. (Fan on unit cooler will continue to run.) These units are designed for application conditions 33°F and above. CAUTION: DO NOT SET A COOLER BELOW 32°F OR DAMAGE MAY OCCUR. Defrost Defrost is accomplished during refrigeration off cycle. Four defrost cycles per day are programmed at the factory (4 a.m., 10 a.m., 4 p.m., and 10:00 p.m.). It may be necessary to change the defrost cycle times to fit your work schedule. The interior temperature may rise slightly during the defrost cycle.
    [Show full text]
  • Disparities in Ammonia, Temperature, Humidity, and Airborne Particulate Matter Between the Micro-And Macroenvironments of Mice in Individually Ventilated Caging
    Journal of the American Association for Laboratory Animal Science Vol 49, No 2 Copyright 2010 March 2010 by the American Association for Laboratory Animal Science Pages 177–183 Disparities in Ammonia, Temperature, Humidity, and Airborne Particulate Matter between the Micro-and Macroenvironments of Mice in Individually Ventilated Caging Matthew D Rosenbaum,1 Susan VandeWoude,2 John Volckens,3 and Thomas E Johnson3,* Animal room environmental parameters typically are monitored with the assumption that the environment within the cage closely mirrors the room environment. This study evaluated that premise by examining macro- (room) and microenvi- ronmental (cage) parameters in individually ventilated cages housing mice with variable amounts of bedding over a period of 17 d without cage changes. Intracage ammonia levels remained within recommended human guidelines but were higher than room levels, confirming that microisolation caging is efficient at preventing ammonia generated from animal waste from escaping into the room. Humidity and temperature within cages were consistently higher than room levels. Particles in the room predominantly consisted of fine particles (diameter less than 2.5 µm), presumably from the ambient atmosphere; some of these particles were found in the cage microenvironment. In addition, mouse activity within cages produced larger particles, and these particles contributed to substantially higher aerosol mass concentrations within the cage. These findings demonstrate that, although cage and room environmental parameters differ, knowledge of room environmental conditions can be used to predict certain conditions within the cage. This association is relevant in that typical animal care standard operat- ing procedures rely on room measurements, not intracage measurements, which arguably are more important for assessing animal welfare.
    [Show full text]
  • At the Request of the District, Environmental Control Systems, Inc, the District's Environmental Risk Engineers, Visited Charl
    Environmental Control Systems, Inc. Indoor Air Quality Investigation Charles F. Patton Middle School Executive Summary At the request of the district, Environmental Control Systems, Inc, the district’s environmental risk engineers, visited Charles F. Patton Middle School to visually assess surfaces and test the air quality in various regions of the school building. This process was completed on Wednesday, November 21 during the regular school day when school was in session. Upon their professional inspection and review, Environmental Control Systems concluded that there is no evidence of mold at Charles F. Patton Middle School. Below is a summary of the report provided by Environmental Control Systems, Inc. You may view the complete report by clicking here. Indoor Air Quality Investigation Report Summary - November 21, 2018 1. Currently, there are no EPA, CDC or OSHA regulations or standards for airborne mold contaminants, therefore, there are no quantitative health-based guidelines, values, or thresholds for acceptable, tolerable, or normal concentrations for airborne fungi spores. 2. Generally speaking, indoor mold types should be similar to, and airborne concentrations should be no greater than, those found outdoors and in non-complaint areas. 3. According to the EPA, there is no practical way to eliminate all mold and mold spores in an indoor environment. Spores can be found almost anywhere and can grow on virtually any substance, providing moisture is present. 4. Mold may begin growing indoors when mold spores land on wet surfaces. There are many types of mold, but none of them will grow without water. At the time of this investigation, there was no condensation on any horizontal or vertical surfaces as all surfaces were equal to or higher than room temperature.
    [Show full text]
  • Understanding Residential Occupant Cooling Behaviour Through Electricity Consumption in Warm-Humid Climate
    Article Understanding Residential Occupant Cooling Behaviour through Electricity Consumption in Warm-Humid Climate Kumar Biswajit Debnath *, David P Jenkins, Sandhya Patidar and Andrew D Peacock School of Energy, Geoscience, Infrastructure and Society (EGIS), Heriot-Watt University, Edinburgh EH14 4AS, UK; [email protected] (D.P.J.); [email protected] (S.P.); [email protected] (A.D.P.) * Correspondence: [email protected] Received: 21 March 2020; Accepted: 15 April 2020; Published: 19 April 2020 Abstract: According to the India Energy Security Scenario 2047, the number of residential air conditioner (A/C) units may increase seven-fold by 2037 as compared to 2017. Also, the related energy consumption might increase four times in the next two decades, according to India’s National Cooling Action Plan. Therefore, the study of occupant cooling behaviour is essential to reduce and manage the significant electricity demand, helping to formulate and implement climate- specific cooling policies, and to adopt low-energy and low-cost technologies at mass-market scale. The study aims to analyse residential electricity consumption in order to investigate occupant behaviour, especially for thermal comfort by using space cooling and mechanical ventilation technologies. Among the five climate zones in India, this study focuses on the occupant behaviour in a warm-humid climate using Auroville as a case study, where climate analysis of the past 30 years demonstrated progression towards unprecedented warmer weather in the last five years. In this study, electricity consumption data from 18 households (flats) were monitored for seven months (November 2018–June 2019).
    [Show full text]
  • The Empirical Analysis Model on Identifying Sick Building Syndrome in Hot Humid Tropical Buildings
    Civil Engineering and Architecture 9(1): 52-73, 2021 http://www.hrpub.org DOI: 10.13189/cea.2021.090105 The Empirical Analysis Model on Identifying Sick Building Syndrome in Hot Humid Tropical Buildings Nurrahmi Kartikawati1, Erni Setyowati2,*, Djoko Indrosaptono2 1Doctoral Program of Architecture and Urbanism, Engineering Faculty of Diponegoro University, Semarang, 50275, Indonesia 2Department of Architecture, Engineering Faculty of Diponegoro University, Semarang, 50275, Indonesia Received November 9, 2020; Revised December 22, 2020; Accepted January 20, 2021 Cite This Paper in the following Citation Styles (a): [1] Nurrahmi Kartikawati, Erni Setyowati, Djoko Indrosaptono , "The Empirical Analysis Model on Identifying Sick Building Syndrome in Hot Humid Tropical Buildings," Civil Engineering and Architecture, Vol. 9, No. 1, pp. 52 - 73, 2021. DOI: 10.13189/cea.2021.090105. (b): Nurrahmi Kartikawati, Erni Setyowati, Djoko Indrosaptono (2021). The Empirical Analysis Model on Identifying Sick Building Syndrome in Hot Humid Tropical Buildings. Civil Engineering and Architecture, 9(1), 52 - 73. DOI: 10.13189/cea.2021.090105. Copyright©2021 by authors, all rights reserved. Authors agree that this article remains permanently open access under the terms of the Creative Commons Attribution License 4.0 International License Abstract A tropical hot humid climate provides high 1. Introduction humidity that influences the occupant’s comfort. This study highlights a comparison of physical measurements One of the remarkable things in occupancy is the indoor and perceptions related to thermal comfort, indoor air comfort aspect and the occupant’s health. The comfort quality, and sick building syndrome (SBS) in tropical and health of the residents are inseparable from thermal humid climate buildings.
    [Show full text]
  • Sick Building Syndrome by WHO.Pdf
    Sick building syndrome By: World Health Organization Regional Office for Europe Summary Sick Building Syndrome (SBS) describes a medical condition where people in a building suffer from symptoms of illness or feel unwell for no apparent reason. The symptoms tend to increase in severity with the time people spend in the building, and improve over time or even disappear when people are away from the building. Sick Building Syndrome results in substantial disruption of people's work performance and personal relationships, and considerable loss of productivity. Sick Building Syndrome is wide spread and may occur in offices, apartment houses, nurseries and schools, resulting in substantial costs to the community. Even though the cause effect relations are unclear it is possible to remedy buildings with SBS problems, and for new buildings the chances of avoiding SBS problems are also good. Local Government actions can be both for implementing curative measures and for taking preventive actions. These measures and actions range from simple to radical. In recent years it has become apparent that occupants of buildings suffer a number of relatively minor illnesses where there is no apparent cause, yet it has been established that these are caused in some way by the building. The symptoms are varying degrees of irritation of the eyes, nose, throat or skin plus general symptoms such as lethargy and headaches. Because these illnesses may happen in the building or elsewhere, it was initially difficult to show that they could be caused by the building. While these symptoms may seem trivial at first sight, together they are a substantial problem.
    [Show full text]
  • Enthalpy of Neutralization
    Enthalpy of Neutralization Introduction Energy changes always accompany chemical reactions. If energy, in the form of heat, is liberated the reaction is exothermic and if energy is absorbed the reaction is endothermic. Thermochemistry is concerned with the measurement of the amount of heat evolved or absorbed. The heat (or enthalpy) of neutralization (∆H) is the heat evolved when an acid and a base react to form a salt plus water. Eq. 1 HNO2(aq) + NAOH(aq) → NaNO2(aq) + H2O(l) + Q Q in the above equation is -∆H and is expressed in kJ/mol of water. Neutralization reactions are generally exothermic and thus ∆H is negative. Heat measurements are performed by carrying out the reaction in a special container called a calorimeter. The heat (Q) given off by the neutralization reaction is absorbed by the reaction solution and the calorimeter. Both the solution and calorimeter increase in temperature due to the absorbed heat and this increase can be measured with a thermometer. ∆H is negative if heat is evolved and positive if heat is absorbed. Eq. 2 -∆Hneutralization = QSolution + QCalorimeter To evaluate the calorimeter constant (also known as its heat capacity) in J/oC, one adds a known mass of hot water to a known mass of cold water which is in the calorimeter. Heat (Q) is lost by the hot water and is absorbed by the cold water and the calorimeter. Thus the heat absorbed by the calorimeter is the heat lost by the hot water minus the heat gained by the cold water. QHot water = QCold water + QCalorimeter Eq.
    [Show full text]
  • Lab #4: Temperature and Thermal Equilibrium
    Temperature and Thermal Equilibrium 1 Physics 123, Fall 2012 Name Lab #4: Temperature and Thermal Equilibrium Temperature and Temperature Scales Temperature is one of the most familiar and fundamental thermodynamic quantities. We have an intuitive feel for temperature, e.g. hot versus cold objects. However, a precise measurement depends on the establishment of a relative temperature scale, based on the change in some physical property of a material as it is heated or cooled over some temperature range. Thus a thermometer may be based on the length of a metal rod, the height of a column of mercury, or the volume of a gas under pressure. In addition, the electrical current carried by certain materials can change with temperature, and thus it is possible to use electronic devices to measure temperature. The familiar Fahrenheit and Celsius scales are just two of many temperature scales set up by early investi- gators of heat and thermodynamics. Both of these scales were set up by taking two fixed points of reliable, easily reproducible temperatures. The Celsius scale was originally based on the freezing point and boiling points of water, 0 ◦C and 100 ◦C, respectively. You will measure temperatures in terms of the Celsius scale. Thermometers In these exercises, you will experiment with two types of thermometers, investigating how the tempera- ture of a substance is affected when it interacts with an environment or another substance at a different temperature. You will use both the familiar glass bulb thermometer and a thermistor. In a glass bulb thermometer, the liquid (alcohol) expands when heated and contracts when cooled, so that the length of the column of liquid can be used to measure changes in temperature.
    [Show full text]
  • Thermodynamic Temperature
    Thermodynamic temperature Thermodynamic temperature is the absolute measure 1 Overview of temperature and is one of the principal parameters of thermodynamics. Temperature is a measure of the random submicroscopic Thermodynamic temperature is defined by the third law motions and vibrations of the particle constituents of of thermodynamics in which the theoretically lowest tem- matter. These motions comprise the internal energy of perature is the null or zero point. At this point, absolute a substance. More specifically, the thermodynamic tem- zero, the particle constituents of matter have minimal perature of any bulk quantity of matter is the measure motion and can become no colder.[1][2] In the quantum- of the average kinetic energy per classical (i.e., non- mechanical description, matter at absolute zero is in its quantum) degree of freedom of its constituent particles. ground state, which is its state of lowest energy. Thermo- “Translational motions” are almost always in the classical dynamic temperature is often also called absolute tem- regime. Translational motions are ordinary, whole-body perature, for two reasons: one, proposed by Kelvin, that movements in three-dimensional space in which particles it does not depend on the properties of a particular mate- move about and exchange energy in collisions. Figure 1 rial; two that it refers to an absolute zero according to the below shows translational motion in gases; Figure 4 be- properties of the ideal gas. low shows translational motion in solids. Thermodynamic temperature’s null point, absolute zero, is the temperature The International System of Units specifies a particular at which the particle constituents of matter are as close as scale for thermodynamic temperature.
    [Show full text]
  • Impacts of Room Temperature on the Performance of a Portable Propane Air Conditioner Nomenclature
    Impacts of room temperature on the performance of a portable propane air conditioner Ahmad Sharifian1, Jeri Tangalajuk Siang2 1,2Computational Engineering and Science Research Centre (CESRC), School of Mechanical and Electrical Engineering, Faculty of Health, Engineering and Science, University of Southern Queensland, Toowoomba, Australia. Email of corresponding author: [email protected] Abstract The performance of a portable propane air conditioner system, in which the temperatures of the air passing over the condenser and evaporator are equal, has been experimentally investigated under different room temperatures and refrigerant charge levels. The research has been carried out in a range of room temperatures from 20°C to 35°C and in undercharge, standard charge and overcharge conditions. The results show that, at higher room temperatures, the refrigerant temperature in all parts of the system, the density of the refrigerant at the inlet and outlet of the condenser, mass of the refrigerant in the compressor, the mass flow rate of the refrigerant and the cooling capacity of the system in either the undercharge or full charge condition, the specific cooling capacity of the undercharge system, the useful work of the compressor, and the maximum pressure of the refrigerant increase. The increase in room temperature decreases the density of the refrigerant at the inlet and outlet of the capillary tube, the mass of the refrigerant in the capillary tube, the refrigerant subcooling at the inlet of the capillary tube, the maximum velocity of the refrigerant and the coefficient of performance. In addition, the increase in room temperature at overcharge condition causes an increase in the mass flow rate, cooling capacity and specific cooling capacity to a maximum value followed by their decrease.
    [Show full text]