Hvac&R Optimisation – Ventilation and Air

Total Page:16

File Type:pdf, Size:1020Kb

Hvac&R Optimisation – Ventilation and Air PART 1 OF 2 HVAC&R MODULE 85 HVAC&R Skills OPTIMISATION Workshop – VENTILATION AND AIR FLOW Over the next few months, we will be giving readers an insight into an ever-evolving topic of HVAC&R Optimisation. First up, we will discuss energy consumption reduction approaches involving air flows and ventilation systems – more specifically, economy cycle strategy. months, O/A can be used to provide cooling ECONOMY CYCLE for spaces, with or without the assistance of AC Economy cycle is a strategy that uses outside air compressors, thereby reducing the system energy DID YOU KNOW? directly for space cooling, with the aim to reduce consumption. Economy cycle allows for a the energy consumption by reducing operation of When outdoor conditions are not suitable, typically 15–20 per cent reduction of energy AC equipment. This strategy provides the added due to high temperature and/or humidity, the consumption of AC compressors benefit of improved IAQ by significantly increasing economy cycle must be disabled and the AHU must and improved IAQ. outside air ventilation rates during periods of mild revert to minimum O/A. The economy cycle must weather. also be disabled during Fire Mode Operation, which is an important consideration when retrofitting. to inadequate maintenance. When they fail, PRINCIPLES The economy cycle is one of the energy saving the HVAC system consumes more energy than AND EQUIPMENT: control strategies normally included in HVAC necessary. Common reasons for failures of existing PULLOUT DDC system controllers or BMSs. economy cycles include: For most parts of Australia, the ambient outside air often has a lower enthalpy (total energy) than the Often, existing economy cycles have been • Malfunctioning sensors air within conditioned spaces in buildings (except set up incorrectly and/or they have failed due (especially humidity sensors) for the hot and humid northern regions). In such conditions, air returned from the occupied space can be exhausted (rather than being returned) 100% and the lower enthalpy O/A can be used as open Spill air Return air S/A, reducing the operation of AC systems and reducing energy consumption, see Figure 15. When an AHU operates in cooling mode, it M typically cools S/A to 12–13°C (for CHW systems) Damper Return air or 8–9°C (for DX systems). During mild weather open M damper conditions, cooling requirements can be satisfied closed with a higher temperature of S/A, sometimes even as high as 20°C. It should be noted that in such situations, the ability of AC systems to dehumidify is significantly diminished and this optimisation strategy will not be viable where humidity control 100% Supply air is paramount. This is not the case for typical office open M Supply air fan type buildings where the space relative humidity activated can typically drift between 40–60 per cent (or Damper even to 35–65 per cent for brief periods) without open Energy Saving Tip significant discomfort. Don’t use relative humidity of outside air Taking into account the typical S/A temperatures alone as a justification noted above, as well as typical climate conditions Essential criteria for activation of economy cycle: for disabling economy for the southern part of Australia during the cooler • Call for cooling activated cycle – also consider • Outside air has less total energy (enthalpy) than return air absolute humidity • Outside and internal air temperature and relative of outside air PROUDLY SPONSORED BY humidity are both within operational limits (dew point criteria) Figure 15: Activated economy cycle. September 2015 | www.hvacrnation.com.au | HVAC&R Nation | 15 ➲ HVAC&R Skills Worskhop • The economy cycle is only used when O/A temperature is close to Often, existing economy cycles S/A temperature (12- 13°C). Such a strategy severely restricts the use of economy cycle (reduces its operating hours) as it only operates when have been set up incorrectly and/or O/A temperature is close to the off-coil S/A temperature. • O/A temperature is lower than R/A temperature. This approach overlooks they have failed due to inadequate the fact that sometimes even warmer O/A, rather than R/A (but much drier, lower humidity) can be utilised for the economy cycle. maintenance. When they fail, the A contributing factor to the under-utilisation of the economy cycle is HVAC system consumes more energy inappropriate space temperature set points and ranges. Optimised control strategies and control parameters should take into account both the than necessary. minimisation of the use of AC compressors and the comfort of occupants. OPPORTUNITY • Failed dampers or damper actuators resulting in discomfort FOR OPTIMISATION • Building pressurisation issues Typical control strategies (as described above) in place for economy cycles are not optimised. As such, they either operate within overly-restrictive conditions • Deactivated due to high energy consumption. or have excessive operation, both of which leads to energy wastage. Significant energy savings can be realised by optimising existing Economy cycles are typically beneficial in the following ambient conditions: settings, or retrofitting HVAC systems to incorporate economy cycles. • Temperature: 10–20°C Figure 15 shows the use of the O/A economy cycle as a first stage of cooling, • Enthalpy: < 52 kJ/kg when O/A conditions are favourable. • Dew point: < 12°C. Minimum required information In order to maximise the operating hours of the economy cycle, The minimum information required for an economy cycle program includes: it should be enabled when the O/A temperature: • Return Air (R/A) temperature and enthalpy (based on temperature • is lower than the zone cooling set point temperature and humidity) • is below the R/A temperature • A temperature and enthalpy (based on temperature and humidity) • Control strategy eg lock-out conditions • has a dew point below 12°C or an enthalpy which is at least 10 kJ/kg below the R/A enthalpy. • Control parameters eg O/A conditions This is the most efficient control strategy. • Conditions for activation • Economy cycle enabling time. The source of O/A should be located away from polluted air (loading docks, traffic, etc) and preferably on the southern or eastern side of the building Minimum required equipment to maximise economy cycle operation potential. The minimum equipment required for the economy cycle program includes: • Field sensors (outdoor and R/A temperature and humidity) ENERGY SAVING POTENTIAL, • DDC controllers COSTS, BENEFITS AND RISKS • Economy cycle software The economy cycle is typically a very cost-effective HVAC energy efficiency • O/A and relief air dampers (of adequate size) and motorised improvement; however, it does require some investment in sensors, motorised dampers, filters and possibly ductwork modifications. The economy cycle modulating actuators (see Figure 15) immediately reduces the energy consumption of the HVAC system by reducing • O/A inlet, exhaust air outlet and ducts sized to accommodate its load, as well as improving IAQ. This strategy can save up to 20 per cent 100 per cent O/A. of energy consumed by AC compressors. A mixed air temperature sensor is very useful for this strategy. Modern BMSs If a building has smoke hazard management, most of the infrastructure can now also use weather data feeds from the internet for more accurate is probably already in place and only new controls would be needed. and reliable data. CURRENT PRACTICE TIPS Many HVAC systems that are controlled by a DDC or BMS either do not have In cooling mode, a higher space temperature an economy cycle installed/ enabled or it is underutilised due to an inefficient 1 control strategy and/or inappropriate control parameters/limits. set point increases the use of economy cycle. Typical control strategies that lead to reduced opportunities for saving energy Economy cycle often runs together with regular include: 2 mechanical cooling, reducing the heat load • The economy cycle is used when O/A temperature is lower than the on the mechanical HVAC equipment. air temperature set point for the economy cycle (16-19°C), which is cooler air than the space temperatures. As such, the AC load is reduced. Don’t use outdoor Relative Humidity (RH) The disadvantage of this strategy is that it restricts the operation of 3 as a control criterion for an economy cycle – the economy cycle at higher ambient temperatures. This represents a diminished opportunity for energy conservation, especially in systems it’s irrelevant. Instead, use enthalpy, absolute where the enthalpy of the O/A is monitored and the O/A is only used humidity or dew point instead. when it has lower enthalpy than R/A. PROUDLY SPONSORED BY 16 | HVAC&R Nation | www.hvacrnation.com.au | September 2015 HVAC&R Skills Worskhop Figure 16: Air plenum of AHU showing motorised O/A and R/A volume control dampers. The economy cycle, or the use of O/A for AC, can also form part of a mixed- mode HVAC design (eg automated opening/closing of windows, dampers, DID YOU KNOW? or any other O/A provision). When implementing economy cycle or other For new installations, the use of economy cycles is mandated in Section J HVAC optimisation strategies to existing systems, of the NCC. it is important to ensure that the original design intent The economy cycle is not typically suitable for applications where a narrow for Fire Mode Operation is not altered in any manner control band for both space temperature and RH is required (eg museums, without consultation with the relevant authorities. art galleries, laboratories, clean rooms, etc). GETTING STARTED The total benefits arising from the use of economy cycle can include: The economy cycle is one of the energy saving control strategies • Reduced energy cost normally included in HVAC DDC system controllers or BMS packages. • Reduced CO₂ emissions The control strategy has often been set up incorrectly and/or has failed due to inadequate maintenance.
Recommended publications
  • HVAC Controls (DDC/EMS/BAS) Evaluation Protocol
    Chapter 19: HVAC Controls (DDC/EMS/BAS) Evaluation Protocol The Uniform Methods Project: Methods for Determining Energy Efficiency Savings for Specific Measures Created as part of subcontract with period of performance September 2011 – December 2014 Jeff Romberger SBW Consulting, Inc. Bellevue, Washington NREL Technical Monitor: Charles Kurnik NREL is a national laboratory of the U.S. Department of Energy Office of Energy Efficiency & Renewable Energy Operated by the Alliance for Sustainable Energy, LLC This report is available at no cost from the National Renewable Energy Laboratory (NREL) at www.nrel.gov/publications. Subcontract Report NREL/SR-7A40-63167 November 2014 Contract No. DE-AC36-08GO28308 Chapter 19: HVAC Controls (DDC/EMS/BAS) Evaluation Protocol The Uniform Methods Project: Methods for Determining Energy Efficiency Savings for Specific Measures Created as part of subcontract with period of performance September 2011 – December 2014 Jeff Romberger SBW Consulting, Inc. Bellevue, Washington NREL Technical Monitor: Charles Kurnik Prepared under Subcontract No. LGJ-1-11965-01 NREL is a national laboratory of the U.S. Department of Energy Office of Energy Efficiency & Renewable Energy Operated by the Alliance for Sustainable Energy, LLC This report is available at no cost from the National Renewable Energy Laboratory (NREL) at www.nrel.gov/publications. National Renewable Energy Laboratory Subcontract Report 15013 Denver West Parkway NREL/SR-7A40-63167 Golden, CO 80401 November 2014 303-275-3000 • www.nrel.gov Contract No. DE-AC36-08GO28308 NOTICE This report was prepared as an account of work sponsored by an agency of the United States government. Neither the United States government nor any agency thereof, nor any of their employees, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or represents that its use would not infringe privately owned rights.
    [Show full text]
  • Smart Buildings: Using Smart Technology to Save Energy in Existing Buildings
    Smart Buildings: Using Smart Technology to Save Energy in Existing Buildings Jennifer King and Christopher Perry February 2017 Report A1701 © American Council for an Energy-Efficient Economy 529 14th Street NW, Suite 600, Washington, DC 20045 Phone: (202) 507-4000 • Twitter: @ACEEEDC Facebook.com/myACEEE • aceee.org SMART BUILDINGS © ACEEE Contents About the Authors ..............................................................................................................................iii Acknowledgments ..............................................................................................................................iii Executive Summary ........................................................................................................................... iv Introduction .......................................................................................................................................... 1 Methodology and Scope of This Study ............................................................................................ 1 Smart Building Technologies ............................................................................................................. 3 HVAC Systems ......................................................................................................................... 4 Plug Loads ................................................................................................................................. 9 Lighting ..................................................................................................................................
    [Show full text]
  • Hvac Controls Introduction
    Invensys Building Systems ON-LINE VERSION HVAC CONTROLS INTRODUCTION Pop-up Definitions in this Online Document • Terms that are blue, italic, and underlined, are provided with pop-up definitions, which can be accessed through blue “question mark” symbols located in the outside margin. • To open a definition, simply double-click the “question mark” symbol that is most in line with the term. • To close the definition, click the “close” box in the upper-left of the window. • These terms are also defined in the glossary of this document. Invensys Building Systems HVAC CONTROLS INTRODUCTION Printed in U.S.A. 3/01 F-26962 Copyright Notice The confidential information contained in this document is provided solely for use by Invensys Building Systems employees, licensees, and system owners, and is not to be released to, or reproduced for, anyone else. Neither is it to be used for unauthorized reproduction of an Invensys control system or any of its components. All specifications are nominal and may change as design improvements occur. Invensys Building Systems shall not be liable for damages resulting from misapplication or misuse of its products. Invensys Building Systems 1354 Clifford Avenue (Zip 61111) P.O. Box 2940 Loves Park, IL 61132-2940 United States of America © Invensys Building Systems 2001 Invensys, PopTop, and DuraDrive are trademarks of Invensys plc and its subsidiaries and affiliates. ii Invensys Building Systems Table of Contents Preface........................................................................................................
    [Show full text]
  • Energy Saving of Central Air-Conditioning and Control System Caseb Study: Nanchang Hongkelong Supermarket
    Energy Saving of Central Air-Conditioning and Control System Caseb Study: Nanchang Hongkelong Supermarket Thesis Yizhou He Degree Programme in Industrial Management Accepted ___.___._____ __________________________________ SAVONIA UNIVERSITY OF APPLIED SCIENCES, BUSINESS AND ENGINEERING, VARKAUS Degree Programme Industrial Engineering and Management Author He Yizhou Title of Project Energy saving of central air-conditioning and control system Case study: Nanchang Hongkelong Supermarket Type of Project Date Pages Final Project 13/10/2010 6 2+8 Academic Supervisor Company Supervisor Company Harri Heikura Zheng Jun HKLS Abstract In China, with the rapid development of economiy, the resources are consumed very seriously. Compared with the developed countries, China’s energy consumption for unit GDP production is more than 6 to 10 times and the energy consumption for unit product production is 50% higher than in the developed countries. Therefore, China is increasing emphasis on energy conservation and is also increasing the awareness of energy saving and environmental protection. In energy saving measures, the one that reduces energy consumption of the central air conditioning is very important. Because in industrial and commercial buildings, central air conditioning system is a very important part of infrastructure and it is widely used. It takes a large proportion in industrial production and the total daily energy consumption of buildings. In industry, central air-conditioning energy consumption accounts for over 40% of the total energy consumption. In this thesis, the problem and the cause of the problem were found according to the research of the specific practical problem of the traditional energy saving system. Based on the theory of intelligent building management system (IBMS) and energy-saving central air-conditioning inverter, a means of vector control can be adopted to achieve the integrated use of the technology and a solution to improve the Central Air Conditioner equipment and improve HVAC energy saving control system can be found.
    [Show full text]
  • Intelligent Thermal Control Method for Small-Size Air Conditioning System
    Intelligent Thermal Control Method for Small-Size Air Conditioning System Hung-Wen Lin1, Min-Der Wu1, Guan-Wen Chen1 and Ying Xuan Tan2 1Green Energy and Research Laboratories, Industrial Technology Research Institute, Hsinchu, Taiwan 2Department of Mechanical Engineering, University of Malaya, Kuala Lumpur, Malaysia Keywords: HVAC, Least Enthalpy Difference Theory, Energy Saving. Abstract: To decrease the energy consumption and maintaining the comfort of the area, a great deal of work has been done on HVAC control algorithms. A control system with the least enthalpy difference theory applied is proposed in this paper. By using the indoor air temperature and relative humidity as the feedback of the control system, the temperature set for the air conditioner is able to satisfy the indoor thermal comfort. The simulation and experimental results of this controller have shown positive energy saving while maintaining indoor thermal comfort. 1 INTRODUCTION “Adaptive Algorithm” which requires an additional parameter which is the expected residence time of the Due to the significant increase of energy consumption occupants for each zone to be controlled (Dimitris, in buildings, energy saving strategies have become Evangelos, John and Odysseus, 2014). An the first priority in energy policies in most countries occupancy-based feedback control algorithm for around the world. In 2006, United States of America variable-air volume HVAC systems that is applicable had used about 35% of the total energy for HVAC to the under-actuated case in which multiple rooms systems (US EIA, 2017). About 50% of the world’s share the same HVAC equipment was implemented. total electrical energy is consumed by HVAC systems Despite the inability to condition rooms (Fagan, Refai and Tachwali, 2007).
    [Show full text]
  • Load Shedding - Phase II & III: Concept Development and Prototype Design for Passenger Rail Equipment
    U.S. Department of Transportation Office of Research, Federal Railroad Development and Technology Administration Washington , DC 20590 Load Shedding - Phase II & III: Concept Development and Prototype Design for Passenger Rail Equipment u . tlffllr'ILUcmtN!ftke ,...,,...,.,.rt:WrrdtJ/Rm: PROC-- lS -lOIIIII~ MM • M0081JSj',HW n.i -rl••-otU.INO'I~ LtS ·IIOC8USSIM r~~,fft'IC"'t'"'""" ,.OI - Dlsatltlllp.iS U, -lopu,11~0 II -lOl-'c-0111 __ _ ..., -~Hollf!IW!fo .. ~lo&kllll lq,i,alTo, 00--- DOT/FRA/ORD-20/30 Final Report | July 2020 NOTICE This document is disseminated under the sponsorship of the Department of Transportation in the interest of information exchange. The United States Government assumes no liability for its contents or use thereof. Any opinions, findings and conclusions, or recommendations expressed in this material do not necessarily reflect the views or policies of the United States Government, nor does mention of trade names, commercial products, or organizations imply endorsement by the United States Government. The United States Government assumes no liability for the content or use of the material contained in this document. NOTICE The United States Government does not endorse products or manufacturers. Trade or manufacturers' names appear herein solely because they are considered essential to the objective of this report. Form Approved REPORT DOCUMENTATION PAGE OMB No. 0704-0188 The public reporting burden for this collection of information is estimated to average 1 hour per response, including the time for reviewing instructions, searching existing data sources, gathering and maintaining the data needed, and completing and reviewing the collection of information. Send comments regarding this burden estimate or any other aspect of this collection of information, including suggestions for reducing the burden, to Department of Defense, Washington Headquarters Services, Directorate for Information Operations and Reports (0704-0188), 1215 Jefferson Davis Highway, Suite 1204, Arlington, VA 22202-4302.
    [Show full text]
  • Best Practices in HVAC Controls
    Best Practices in HVAC Controls An overview of best practices, lessons learned and guidelines for optimizing HVAC controls to achieve significant energy and cost savings. Publication Date: June 2012 Advanced Energy I Best Practices in HVAC Digital Controls I June 2012 1 TABLE OF CONTENTS EXECUTIVE SUMMARY ............................................................................................................................... 4 OVERVIEW ................................................................................................................................................... 5 Using Controls to Manage Energy ............................................................................................................. 5 Commissioning/Re-Commissioning/Retro-commissioning ........................................................................ 5 Test Adjust and Balance ............................................................................................................................ 6 Assess Your In-House Expertise ............................................................................................................... 6 Research Options for Contracted Assistance ............................................................................................ 7 PHASE 1: COLLECT INFORMATION AND MAKE A MONITORING PLAN ............................................... 8 Create a Project Team and Select a Building ............................................................................................ 8 Facility Background
    [Show full text]
  • An Introduction to Energy Efficient HVAC Controls
    An Introduction to Energy Efficient HVAC Controls Course No: M02-053 Credit: 2 PDH J. Paul Guyer, P.E., R.A., Fellow ASCE, Fellow AEI Continuing Education and Development, Inc. 22 Stonewall Court Woodcliff Lake, NJ 07677 P: (877) 322-5800 [email protected] An Introduction to Energy Efficient HVAC Controls J. Paul Guyer, P.E., R.A. Paul Guyer is a registered civil engineer, mechanical engineer, fire protection engineer and architect with 35 years of experience designing buildings and related infrastructure. For an additional 9 years he was a principal staff advisor to the California Legislature on capital outlay and infrastructure issues. He is a graduate of Stanford University and has held numerous national, state and local offices with the American Society of Civil Engineers, Architectural Engineering Institute and National Society of Professional Engineers. © J. Paul Guyer 2015 1 CONTENTS 1. GENERAL 2. HUMIDITY CONTROL 3. SIMULTANEOUS HEATING AND COOLNG 4. MECHANICAL VENTILATION CONTROL 5. ENERGY CONSERVATION CONTROL SCHEMES 6. AUTOMATIC CONTROL DAMPERS 7. VARIABLE AIR VOLUME SYSTEM FAN CONTROL 8. FIRE AND SMOKE DETECTION AND PROTECTION CONTROLS 9. GAS-FIRED AIR-HANDLING UNIT CONTROL. 10. COOLING TOWER AND WATER-COOLED CONDENSER SYSTEM CONTROLS 11. CENTRAL CONTROL AND MONITORING SYSTEMS 12. ENERGY METERING 13. DDC HARDWARE REQUIREMENTS 14. DDC SOFTWARE REQUIREMENTS (This publication is adapted from sources produced by the United States government which are in the public domain, are authorized for unlimited distribution, and are not copyrighted.) © J. Paul Guyer 2015 2 1. GENERAL. This discussion covers automatic temperature and humidity controls, space pressurization controls, safety controls, and energy monitoring and central supervisory control systems.
    [Show full text]
  • Automation and Control of HVAC Systems - So, Albert T.P
    CONTROL SYSTEMS, ROBOTICS AND AUTOMATION - Vol. XVIII - Automation and Control of HVAC Systems - So, Albert T.P. AUTOMATION AND CONTROL OF HVAC SYSTEMS So, Albert T.P. Asian Institute of Intelligent Buildings, and Department of Building & Construction, City University of Hong Kong Keywords: Heating, ventilation, air-conditioning, control, intelligent, monitoring, sensor, building, automation, management. Contents 1. Introduction 2. Conventional HVAC Control and Automation 2.1. Indoor Air Quality 2.2. Sensors in HVAC Systems 2.3. HVAC Systems 2.4. Conventional HVAC Control 2.4.1 A Control Example 2.4.2 Principles of PID Control 2.4.3 Programmable Logic Control 2.4.4 Actuators 2.4.5 Direct Digital Control 2.5. HVAC Automation 2.5.1 The Networks 2.5.2 Building Automation 3. Advanced HVAC Control 3.1. System Modeling 3.2. Digital Control 3.3. Multivariable Control 3.4. System Identification and Adaptive Control 3.5. Robust Control 3.6. Expert System based Control 3.7. Artificial Neural Network based Control 3.8. Fuzzy Logic based Control 3.9. Computer Vision based Control 3.10 Comfort based Control 4. ConclusionsUNESCO – EOLSS Glossary Bibliography SAMPLE CHAPTERS Biographical Sketch Summary The building services industry can, in general, be regarded as a more classical industry. The pace of advancement of technology in the field of building and construction, in particular, building services, is relatively slower compared with that of the electronics and control industries or information technology. Fortunately, research and development works on HVAC control have been substantial over the past two decades. Some achievements ©Encyclopedia of Life Support Systems (EOLSS) CONTROL SYSTEMS, ROBOTICS AND AUTOMATION - Vol.
    [Show full text]
  • Section 15950 - Hvac Controls and Sequence of Operations
    SECTION 15950 - HVAC CONTROLS AND SEQUENCE OF OPERATIONS City of San Diego, CWP Guidelines PART 1 -- GENERAL 1.1 WORK OF THIS SECTION A. The WORK of this Section includes providing equipment and devices required for a complete HVAC control system, including electrical devices, and the following: 1. Control system consisting of thermostats, control valves, dampers and operators, indicating devices, interface equipment and other apparatus and accessories required to operate mechanical systems, and to perform functions indicated. 2. Pneumatic automatic temperature control systems with electric accessories. 3. Sequence of operations for the HVAC equipment indicated. 1.2 RELATED SECTIONS A. The WORK of the following Sections applies to the WORK of this Section. Other Sections of the Specifications, not referenced below, shall also apply to the extent required for proper performance of this WORK. 1. Section 11000 Equipment General Provisions 2. Section 15000 Piping Components 3. Section 15050 Vibration Isolation 4. Section 15410 Plumbing Piping 5. Section 15550 Water Tube Boilers and Accessories 6. Section 15750 Packaged Equipment 7. Section 15855 Air Handling and Moving Equipment 8. Section 15880 Air Distribution Devices and Accessories 9. Section 15990 Testing, Adjusting and Balancing 1.3 CODES A. The WORK of this Section shall comply with the current editions of the following codes as adopted by the City of San Diego Municipal Code: 1. Uniform Mechanical Code 1.4 SPECIFICATIONS AND STANDARDS A. Except as otherwise indicated, the current editions of the following apply to the WORK of this Section: 1. AMCA 500 Test Methods for Louvers, Dampers and Shutters 2. ANSI/ASME B16.22 Wrought Copper and Copper Alloy Solder Joint Pressure Fittings HVAC CONTROLS AND SEQUENCE [FEBRUARY 1991] OF OPERATIONS [CONTRACT NO.]-[CONTRACT NAME] 15950-1 3.
    [Show full text]
  • Optimal Co-Scheduling of HVAC Control and Battery Management for Energy-Efficient Buildings Considering State-Of-Health Degradation
    Optimal Co-Scheduling of HVAC Control and Battery Management for Energy-Efficient Buildings Considering State-of-Health Degradation Tiansong Cui1, Shuang Chen1, Yanzhi Wang2, Qi Zhu3, Shahin Nazarian1 and Qi Zhu Shahin Nazarian Massoud Pedram Massoud Pedram1 University of California, Riverside University of Southern California University of Southern California Riverside, CA, USA Los Angeles, CA, USA Los Angeles, CA, USA 1Department of Electrical Engineering, University of Southern California, USA [email protected] [email protected] [email protected] 2Department of Electrical Engineering & Computer Science, Syracuse University, Syracuse, USA 3Department of Electrical and Computer Engineering, University of California, Riverside, USA 1{tcui, shuangc, shahin, pedram}@usc.edu, [email protected], [email protected] Abstract— The heating, ventilation and air conditioning (HVAC) sys- Although both HVAC control and battery management mechanisms tem accounts for half of the energy consumption of a typical building. are well researched, there has been little work on formulating the inter- Additionally, the need for HVAC changes over hours and days as does actions between the two aspects and addressing them together. In the the electric energy price. Level of comfort of the building residents is, building management system, the demand side scheduling of HVAC however, a primary concern, which tends to overwrite pricing. Dynamic control depends on the availability of battery storage and the price HVAC control under a dynamic energy pricing model while meeting an of grid electricity, while the supply side scheduling of battery stor- acceptable level of residents’ comfort is thus critical to achieving energy age requires the knowledge of HVAC demand [5].
    [Show full text]
  • Design and Control of Hydronic Radiant Cooling Systems
    Design and Control of Hydronic Radiant Cooling Systems By Jingjuan Feng A dissertation submitted in partial satisfaction of the requirements for the degree of Doctor of Philosophy in Architecture in the Graduate Division of the University of California, Berkeley Committee in charge: Professor Stefano Schiavon, Chair Professor Gail Brager Professor Edward Arens Professor Francesco Borrelli Spring 2014 PhD Dissertation, Dept. of Architecture, https://escholarship.org/uc/item/6qc4p0fr UC Berkeley 2014 Design and Control of Hydronic Radiant Cooling Systems © 2014 By Jingjuan Feng PhD Dissertation, Dept. of Architecture, https://escholarship.org/uc/item/6qc4p0fr UC Berkeley 2014 ABSTRACT Design and Control of Hydronic Radiant Cooling Systems by Jingjuan Feng Doctor of Philosophy in Architecture University of California, Berkeley Professor Stefano Schiavon, Chair Improving energy efficiency in the Heating Ventilation and Air conditioning (HVAC) systems in buildings is critical to achieve the energy reduction in the building sector, which consumes 41% of all primary energy produced in the United States, and was responsible for nearly half of U.S. CO2 emissions. Based on a report by the New Building Institute (NBI), when HVAC systems are used, about half of the zero net energy (ZNE) buildings report using a radiant cooling/heating system, often in conjunction with ground source heat pumps. Radiant systems differ from air systems in the main heat transfer mechanism used to remove heat from a space, and in their control characteristics when responding to changes in control signals and room thermal conditions. This dissertation investigates three related design and control topics: cooling load calculations, cooling capacity estimation, and control for the heavyweight radiant systems.
    [Show full text]