www.hi-velocity.com LV-Z Series Installation Manual

Includes: LV-Z Series Coils Product Specifications Wiring and WEG Settings Specifications & Sizing

From the Manufacturers of Hi-Velocity SystemsTM www.hi-velocity.com Module-LVZ-Series-Fan-Coil-Installation-061616 Table of Contents

Setting up your LV-Z System - Pg. 4 Unit Selection, Quality Assurance

Fan Coil Placement - Pgs. 5 Placement, Unit Configuration, Clearances

Water Cooling Module (WCM) - Pg 6

Hot Water Coil (HWC) Add-on - Pg 6

Electric Strip Heater (ESH) - Pg. 7

Return Air - Pg. 7 Return Cutout Dimensions, Return Air Base, Filter Rack

Hi-Velocity Air Purification System Pg. 8 Hi-Velocity Air Purification System, HE PS Dimensions

User Guide Pg 8 IAQ, Filter Maintenance, System Efficiency

Installation Check List - Pg. 8

PSB Circuit Board & WEG Drive - Pgs. 9-16 PSB Board, WEG Drive, PSB Wiring Diagram, Extended WIring Diagrams

Trouble Shooting - Pgs. 17-24 Motor Running Too Fast, Motor Running Too Slow, Motor Not Running, 24V Clg, 24V Htg., Outdoor Unit, Short Cycling

Appendix Pages - Pgs. 25-26 LV-Z Fan Coil Specifications (Standard & Metric, Quick Product Sizing Guide)

Warranty Information - Pg. 27

-2- © 1995-2020 Energy Saving Products Ltd. Module LVZ LV-Z Series Fan Coil Installation (3/28)

The LV-Z System By Energy Saving Products Ltd.

All Product LV-Z Fan Coil Sizing on Pg. 26 Specs Pg. 25

Heating Options Cooling Options

Hot Water Coil Water Coil Module

Electric Strip Coil

Other Options

Return Air Hi-Velocity Air Purification System

-3- © 1995-2020 Energy Saving Products Ltd. Module LVZ LV-Z Series Fan Coil Installation (4/28)

When sizing an LV-Z fan coil for a residential system, it Sweat water connections are 3/4” for the LV-Z 1050 and 1” for is necessary to have an accurate heat loss/gain done for the the LV-Z 1750. All lines should be piped so as not to restrict use structure. This will ensure the proper equipment is used for of the access panels, filter section, or electrical enclosure. cooling and heating. A heat loss/gain is done for each room, with all rooms added together to find the total BTUH load for Refer to the back of this manual for all specifications, the building. With the total load known, the appropriate fan coil measurements, etc. can be chosen from Pg. 25. Fan coils are to be located indoors, however, attic, crawl space and garage conditions are fully acceptable. The can be positioned in a Horizontal, Hi-Boy, or Counterflow position IMPORTANT: The LV-Z Fan Coil is not and can be suspended from the ceiling or placed directly on to be used for temporary heating or the floor. cooling during the construction of When potential for gravity flow of the hot water exists, spring the structure. If used in this capacity check valves may be needed on both the supply and return lines. all warranties will be null and void.

Fan coil units specified in this section shall be designed as a closed loop hydronic fan coil system, with published BTUH ratings and entering water temperatures between 110°F and Please read the ENTIRE manual before 190°F. The system shall allow for heating, DX or beginning installation as this will help avoid cooling, and applications with electric coil back- ups. Entering water temperature and BTUH outputs shall match mistakes that may cost time and money. performances listed on Pg. 25.

Quality Assurance Fan coil units shall be a total system complete with heating, cooling and air filtration, with the possibility of control and fresh air make up. The fan coil must be Fan Coils factory manufactured, assembled and tested. The LV-Z fan coil is manufactured with a direct drive, permanently lubricated motor that is mounted within the blower. All equipment furnished under this specification shall All LV-Z fan coils are single side access. The blower assembly comply with the standards set out by the following standards can be easily slid out by removing the electrical box and then organizations: removing the three mounting bolts that attach the blower to CSA Canadian Standards Association the center plate. CE European Conformity

UL Underwriters Laboratories Disclaimer The fan coil units shall be designed, rated, and approved by CSA/UL. Energy Saving Products Ltd. reserves the right to discontinue, make changes to, and add improvements upon its products at any time without public notice or obligatiion. The descriptions The fan coil units shall have pre-wired controls consisting of and specifications contained in this manual were in effect at a 24V transformer, printed circuit board and variable frequency printing. Some illustrations may not be applicable to your unit. drive. The circuit board shall be capable of providing heating, cooling and constant fan. Motors shall be 3 phase with published amp draws.

-4- © 1995-2020 Energy Saving Products Ltd. Module LVZ LV-Z Series Fan Coil Installation (5/28)

Placement Hanging the Fan Coil Unit When installing the fan coil, keep these points in mind:

- Serviceability and access to the unit. Quite often, the best location for the fan coil unit is suspended from the ceiling of the , in the horizontal - Maximizing usable floor space. position (Fig. 03). This will allow for more floor space in the - Location of heating/cooling source to the fan coil. room, and will minimize the work needed to connect to the fan coil unit.

As previously stated, the fan coil can be positioned in many different orientations. When placed in the Hi-Boy position, The Hi-Velocity fan coil can be suspended in any position, supply air is fed from the top of the unit (Fig. 01). When placed using most industry standard hanging support systems. in the Counterflow position, supply air is fed downwards from Redi-Rod, All Thread, C-Channel or Unistrut are some of the unit (Fig. 02). the building code acceptable hanging systems. Use these in conjunction with spring or rubber isolators to ensure a sturdy Fig. 01 - Hi-Boy hanging support system. These isolators will absorb most of the vibrations generated by the fan coil system, eliminating any sound transfer. Fig. 02 - Counterflow Securing the Fan Coil to the Hanging System

In most cases, fastening the hanging system near the corners of the outside cabinet of the fan coil will be acceptable. However, in some cases, brackets may be needed to secure the fan coil to the hanging system.

Clearances Clearance is only needed on the access side of the units. However, ensure that there is a small space between the unit and any other surface to prevent vibration transfer. In order to maintain and service the fan coil unit, the minimum clearances required on the access side are (Table 01).

Table 01 – Fan Coil Clearances

Fig. 03 - Horizontal installation Unit Inches LV-Z 1050* 22” LV-Z 1750 32” *Add an additional 4” for Electric Strip Coils (not available for the LV-Z 1750)

Refrigerant Cooling Module Due to the size of the RCM/RPM-E Cooling Modules and the high volume of air produced by the LV-Z fan coil Unit, the use of the RCM/RPM-E coils with the LV-Z fan coil is not advised. For cooling needs, a third party blow through coil such as an A-Frame or N-Frame coil is suitable.

-5- © 1995-2020 Energy Saving Products Ltd. Module LVZ LV-Z Series Fan Coil Installation (6/28)

Fig. 07 - Hot Water Coil easily slides into the fan coil Water Coil Module (WCM/WM) The water coil comes as a module and must be installed in the vertical position on the return air side of the fan coil. The WCM/ WM come supplied with two L mounting brackets for connection to the fan coil (Fig. 06). For WCM/WM dimensional information and sweat water connection sizes refer to the manual shipped with the coil, also available on our website. Piping the WCM/WM

When the potential for gravity flow of the hot water exists, check valves may be needed on both the supply and return lines. Figs. 08 and 09 give an example of this. All lines should be piped so as not to restrict access to the front panels, filter section, or electrical enclosure. Size your supply and return lines according to Table 02. Table 02 – WCM/WM pipe sizing Zone BTUH Pipe Size Pipe Size Heat loss up to 40 feet 40 – 100 feet

5 3 0 - 35,000 ⁄8” ⁄4”

3 35,001 - 70,000 ⁄4” 1” Fig. 08 - Hot water tank: Side take-offs 1 70,001 - 140,000 1” 1 ⁄4” H Fig. 06 - Mounting Brackets SUPPLY

Domestic C RETURN hot water mixing valve (optional)

Fan Coil Domestic cold water C H

Dual SUPPLY Purpose hot water tank RETURN

Fig. 09 - Hot water tank: Without side take-offs Hot Water Coil Add-on The Hot Water Coil Add-on is easily installed in the LV-Z fan H SUPPLY coil. With heating, condensate is not a consideration and the coil Domestic RETURN hot water C can be mounted on the supply side of the blower (Fig. 07). mixing valve (optional) With the removal of the front panels, the coil can be slid in place on the supply side of the blower. For Hot Water Coil Fan Coil dimensional information refer to our website. Domestic cold water C H

Dual Piping the Hot Water Coil Purpose hot water Figs. 08 and 09 illustrate typical pipe runs from a dual purpose tank hot water tank to a fan coil. These drawings are only for reference as all piping has to be run according to local code.

-6- © 1995-2020 Energy Saving Products Ltd. Module LVZ LV-Z Series Fan Coil Installation (7/28)

Once the placement of the return has been decided, the Electrical Strip Heater (ESH) return air knockout(s) can be marked and cut (Fig. 10). The pre- The Electrical Strip Heater slides into the fan coil, on the measured guide cuts on the fan coil should always be used; this supply side of the blower (Fig. 07). Once the front access doors will guarantee maximum airflow across the coil. have been removed, the ESH can be slid into place.

The ESH is labeled with a directional airflow sticker; when Return Air Base (Optional) placing the ESH the sticker shall be in the direction of the air flow. Currently, the ESH is only available for use with the LV-Z Energy Saving Products manufactures a return air base that 1050. matches up to the fan coil units.

Wiring the Electrical Strip Heater All return air bases come acoustically lined with half-inch Before wiring in the ESH, make sure all power sources are sound absorbing insulation. disconnected. The wiring diagram is on the inside of the ESH front panel, or refer to Pg. 10. Use only wires suitable for 167ºF (75ºC); wires shall be sized according to local electrical code. Table 04 – Return Air Base dimensions Use only class 2 wiring for the Control Circuit connections A B C D between the heater terminal 1, terminal 2 and the zone valve 1 3 1 1 RA-70/1050 22 ⁄2” 21 ⁄4” 18 ⁄2” 19 ⁄2” terminals. Please note, the ESH must be wired to a dedicated 1 3 1 1 breaker, separate from the fan coil. RA-1750 22 ⁄2” 21 ⁄4” 24 ⁄2” 26 ⁄2”

For Electrical Strip Heater Specifications, please refer to the Fig. 11 – Return Air Base manual shipped with the coil, also available on our website: 1” Flanged in www.hi-velocity.com for Fan Coil Return Air Placement The return air duct is not supplied with the LV-Z Fan Coil System. It is to be supplied and installed by the contractor. The return air and fresh air make-up ducts are to be installed according to local building code. Return Air Cutout All LV-Z fan coils are shipped with the return air knockouts pre-measured for multiple configurations. Table 03 contains the pre-measured dimensions for the return air knockouts.

Table 03 – Return Air Cutout Dimensions Model Dimensions LV-Z 1050 141/2” X 131/2” LV-Z 1750 21” X 177/8”

Fig. 10 - Return air cutout Filter Rack (Optional)

Available from Energy Saving Products is a 3” (76mm) Filter Rack. Filters are 1”(25mm) thick Merv 3, and the filter medium is approximately 14% efficient. Any after market filter may be used with the Hi-Velocity Filter Rack. (See Dimensions Below)

Table 05– Filter Rack Dimensions Length Width Depth Filter Opening LV-Z 1050 181/2” 191/2” 3” 11/8” LV-Z 1750 241/4” 261/2” 3” 11/8”

-7- © 1995-2020 Energy Saving Products Ltd. Module LVZ LV-Z Series Fan Coil Installation (8/28)

Hi-Velocity Air Purification System

System Efficiency/Performance

B A big misconception that people have is that by turning off the when they leave home, they save on cooling costs. This is not necessarily true as the system will need to run A C longer and harder when pulling the house down to temperature Easily installed on any Hi-Velocity or existing HVAC System, after being shut off for a large amount of time. Keeping the the HE PS gives consumers unsurpassed indoor air quality. The temperature within a small range when there are no loads from HE PS will work at the airflow rates of the LV-Z 1050 only. For 3 human use will result in less overall energy consumption. stage filtration on the LV-Z 1750, we recommend using the HE PS 1750. Three powerful technologies in one Air Purification System:

• Electrostatic MERV-13 Filter Removes Allergens • Photo-Catalytic Oxidation destroys toxic chemicals Installation Checklist and eliminates household odors • Ultraviolet Light Kills Disease Germs on Contact Ensure that all electrical connections are tight, and that any packing or shipping restraints are removed from both the fan coil, and the outdoor unit. With the power to the condensing unit off, check the for normal operation and proper airflow from all vents. Do not run the fan coil without a filter in place.

Observe the system pressures during the initial start-up and charging of the system. Refer to the outdoor or indoor coil manufacturer’s charging guidelines. Check the voltage and amp LV-Z User Guide draw of both the fan coil, and the outdoor unit. The voltages must be within 10% of the rating plate data. If more than 10% Indoor Air Quality (IAQ) is noted, contact your local electrical company. Check that the amp draws of both units are within the information printed on Ensure that there is always a filter in place and check every the unit rating plates. month to ensure that the filter is clean. The amount of time between filter changes and cleaning will be dependant upon the living habits of the homeowner. With a clean , you not only have cleaner air to breathe, but you will also help maintain unit efficiency, as well as increase the operating life of the unit.

Filter Maintenance In the event of difficulty during the start- The 1” Merv 3 filtering medium supplied by Energy Saving up procedure, please refer to the trouble Products Ltd. can be cleaned and re-used. If the filter needs shooting flow charts (Pgs. 17-24) to cleaning, the system should first be shut down and the filter removed. Once out of the unit, the filter can be vacuumed on the assist you in determining the problem. pink side and washed on the white side. Once the filter has been vacuumed, cleaned, and completely dried, it can be replaced in the unit. Note that the pink side of the filter faces the blower and the white side towards the return air. A filter can generally be cleaned a few times, if re-used too often it will restrict airfow.

-8- © 1995-2020 Energy Saving Products Ltd. Module LVZ LV-Z Series Fan Coil Installation (9/28)

PSB Circuit Board

The LV-Z Series Fan Coil utilizes a dual function Circuit Board. This circuit board makes zoning simple and easy, eliminating the need for by-pass dampers and dump zones. It also makes adjustment to airflow quick with the use of trim pots for direct control.

Auxiliary Relay VDC Control Fan Delay 0 - 10v Operation Mode Fan Adjustment Pressure Sensor Terminals (Heating) Method On/Off Switch DC Output Indicator Trimpots Indicator Light

T’Stat Connections

Emergency 24v Pump Timer Condenser/Zone Disconnect Auto-Reset on/off Switch Valve Connections Fuse Features: • If you wish to have the timer cycle operate at a specific • Wiring the circuit board is a quick and simple task. time of day, simple turn off power to the fan coil unit for ten • Clearly labeled connections. seconds at that time and then turn the power back on. • No additional relays typically required. • If you do not need to use the timer, move the jumper • When the PSB is set to “Auto”, it allows for automatic airflow header from the On pins to the Off pins and it will be disabled. adjustments, according to the static pressure of the supply air, • Circuit board is equipped with an emergency disconnect making zoning a breeze. feature. If there’s an emergency this feature will de-energizing • “Manual” mode allows for direct speed control of the fan all fan speeds and connected equipment. anywhere from 0-100% capability. LV-Zs come standard in • For this emergency disconnect feature to be active a Manual Mode. jumper header must be remove from the pins located close • Fan speeds in both functions are individually set for cooling, to the emergency disconnect terminal strip. heating and constant fan using the three trim pots located on • A fan delay is programmed into the circuit board. This the PSB. delay will prevent the fan from starting for 20 seconds on • Circuit board is capable of controlling , dual purpose cooling, 30 seconds on heating, and purge for 30 seconds on hot water heaters, heat pumps, and geothermal systems, as well shut-down. This delay is beneficial in certain applications to as our manufactured slide-in electric strip heaters (ESH). give the heating or cooling equipment a “head start” before the fan turns on. • The circuit board is also designed to send control signals to cooling sources such as condensing units, , heat pumps and geothermal systems. Function: • Circuit board features an auxiliary relay with dry contacts • Manages input power and through the use of a transformer connections, so that any applications requiring 24v, 120v, it supply 24vac to additional equipment. 230v or dry contacts (boilers, hot water heaters, heat pumps & • Organizes all thermostat inputs and prioritizes them ) can be automatically started when there’s a call for accordingly. heat. • Sends a 0-10vdc output to the VFD, dependent on how fast • Circulator timer chip is provided to prevent water stagnation it wants the fan to run. in potable water systems and to provide pump rotor protection for water source heating and cooling.

-9- © 1995-2020 Energy Saving Products Ltd. Module LVZ LV-Z Series Fan Coil Installation (10/28)

WEG Variable Frequency Drive

The LV-Z Series Fan Coil utilizes a WEG Variable Frequency Drive to run its 3-phase motor. The WEG VFD is a reliable and robust motor control that will provide many years of issue free operation.

Features: • Purposely oversized to ensure increased reliability and higher efficiencies at peak load • Features inherent with VFD allows for minimum power consumption at reduced loads (<100w average for constant fan speed) • Error code read out allows for easy drive analysis in the event of a VFD fault • Programmable drive parameters allow for acceleration and deceleration speed to be adjusted if necessary • Digital display makes motor speed references simple • Large heat sink allows for excellent heat dissipation in high ambient environments

Function: • Takes single phase input (110v or 200-240v) and converts it to 3 phase output for the fan motor • Fan speed is determined by the PSB circuit board which provides a 0-10vdc output to control the VFD Read-Only Parameters: Parameter Function Range Unit Description P002 Motor Frequency Output 0 to 66 Hz Indicates the VFD Output Frequency in Hertz

P003 Motor Current Output 0 to 1.5 x Inom A Indicates the VFD Output Current in Amperes P004 DC Link Voltage 0 to 524 V Indicates the VFD DC Link Voltage in Volts P007 Motor Voltage Output 0 to 240 V Indicates the VFD Output Voltage in Volts Indicates the Heat Sink Temp in Celsius. The VFD P008 Heatsink Temperature 25 to 110 ºC Overtemp Protection (E04) acts when Heatsink Temperature reaches 103 ºC P014 Last Fault 00 to 41 EXX Indicates the Code of the last occurred Fault P015 Second Fault Occurred 00 to 41 EXX Indicates the Code of the 2nd last occurred Fault P016 Third Fault Occurred 00 to 41 EXX Indicates the Code of the 3rd last occurred Fault

Fault Messages: Display Description E00 Output Overcurrent/Short-Circuit E01 DC Link Overvoltage Other Messages: E02 DC Link Undervoltage E04 Inverter Overtemperature Display Description rdy Inverter is ready to be enabled E05 Output Overload (I x t function) Power supply voltage is too low for the inverter operation Sub E06 External Fault (undervoltage) E08 CPU Error (watchdog) dcb Inverter in DC braking mode E09 Program Memory Error (checksum) EPP Inverter is loading factory setting E24 Programming Error E31 Keypad (HMI) Communication Fault 97 E41 Self-Diagnosis Error 97

-10- © 1995-2020 Energy Saving Products Ltd. Module LVZ LV-Z Series Fan Coil Installation (11/28)

LV-Z Fan Coil - PSB Wiring Diagram U

O

W W

Y Y R R R C F S / C G C D C 1 2 2 1 C o B T E F R i E O - H O M ------E - - O Y F S E S F 2 2 P 2 R 2 2 T 2 A E E H L 2 I 4 4 4 4 I 4 E R E 4 H

R R Z R R E B I ( S ( C N O C M O E O I E V V V V V G V S S A O I U Y N O G O A A A A R A T S A R R O T T T E P R H C C C C G C T M N C N

P

S N A O S S S S I A T E T L D U D O T WEG CONTROLLER WEG CONTROLLER C S C C C O I O T I T I P T 200-240 V N 1 R Y E N N A M A S S A Y O O O U S E S U 10-120 V

Parameter I Parameter P W T W G G G

E T G P ( S T R T M M M T O T D R U A L L

D I C A T Value Value A I E E P P A R S M M M I L VFD VFD U T E T E A S G G O U T U E L E H

C N O O O N G C F S S E I E N T

T V E O O S A B A N N T N O E T T N E H A C N H O E N A A N E R P P T AC AC E O E G L G T N S C S A I O

E E N E W I I W T I T N L ) )

0 0 G C I

I O I

G S T N + +

T

N - - C P G S E Red Red H DUCT DUCT

Black Black A A E POWER POWER Equipment Equipment TMOSPHERIC PRESSURE TMOSPHERIC PRESSURE D Ground Ground )

PRESSURE 1 2 3 4 5 6 7 8 9 10 11 12 PRESSURE 1 2 3 4 5 6 7 8 9 10 11 12

A Y W F F W Y A L/L1 N/L2 U V W PE L/L1 N/L2 U V W PE A C R N L Z Z 2 1 3 1 2 A 2 1 2 4 - U - - - - - A - - - - A - A MOT MOT - - L F F X N V C H H C 2 2 I R R A U U U I E N 4 4 G G INPUT INPUT OR LEADS PLUG OR LEADS PLUG O E E O L E E (3 PHASE) (3 PHASE) C X X X U E I A A V V N N BK BK A E E I I I T T T A A L L L O D V D R Z Z R I I I I I C C WH WH O U N N A E E A A E E Y A R N T G N G R R L

C O L S S H T P Y S Y Y S

R R O U T T ( A ( E U

I I W W A A M T C N N N N G A T

T T P

O 1 2 O O G

G T M TRIM POTS (COOLING, HEA TRIM POTS (COOLING, HEA E T A T A THERMOST THERMOST : : U C ) ) I M R R O N U U 2 2 T O M M 208-240/1/50-60 1 M G N 4 4 N N N J5 J5 A A O

10-120/1/50-60

I I V V

R

N

T T 200-240v POWER CABLE 1 C C G G O/B O/B L L W2 W1 W2 W1 Y1 Y2 Y1 Y2 D D R R N A A 10-127v POWER CABLE

E E L L 2 2 C C Y Y L C J7 J7 4 4

A T LED LED O O C O L2 L2 V V FZ FZ AND CONST AND CONST Y I L U U P O A A U2 U2 O FZ FZ E T T C C F F N F F AN AN S P P N S O O W1 W1 24v OUTPUT 24v OUTPUT E U R6 R6 U U U HEA HEA D T T H H W2 W2 T T T T P P

R7 Y2 R7 Y2 COOL COOL U U C C ANT ANT T T Y1 Y1

R8 R8

TING, TING, LED LED

L1 L1 F F Red Wire (+) Wire Red Red Wire (+) Wire Red C C G G AN) AN) J8 J8 R R

H L H H H + + 0-10 VDC 0-10 VDC 0-10

E

4 3 1 2

J

OFF MAN OFF MAN OFF

OFF D U

D M P E Y T M L O L W A U

- -

Black Wire (-) Wire Black (-) Wire Black ON O AUT ON O AUT ON

ON M

I E A E O M E L U P P A O

IN IN LINE LINE LINE M

I

R D D I H2 H2 H4 H4 H3 H3 P L O T E T E N N

D

G E

E A Y DELA Y DELA TIMER TIMER MODE MODE F1 F1 E S O R R

N

U

D 1 2 E Ground Ground H

R

Y D Black Red Red R J3 J3 A

G

A : S

T

: - - - : S EMERGENCY EMERGENCY W Red

Orange T

T E E

L P A F G B Y Black T

Orange I

I

O

N N A O T I U A White White L / 3 R - N L2 2 L1 L1 A N T D U C 0 N X N N F E E 0 A J2 J2 I S

I E Y A I I

C

S

E M S C L

M R

G G E

BK L2 BK WH N WH N N E N I P D L A E N P A O T J9 J9 F TRANSFORMER TRANSFORMER C I E T I Ri Ri R S D R G R T L S D DISCONNECT DISCONNECT L O O E H1 H1 24v / 20va 24v / 20va P G I I E Y O H C Ro Ro E G N W D N R E

S E T W O R G H I E D S / , S N

M N

3

C C

N

E T S 2 L 2 L 2 L 2 L N N 1 L 1 1 L 1 L L D P U C 0 J1 J1 D , P O N L R R C C Y P I O O A S D E C E

E U Y E P S C D U A S N N N

M C E T T I T L T S S

: R O P A I O P U M C R T

A A1 A1 N R 1 1 U T R O E E 10-127 V 10-127 V E T D I R E R M S N E M 200-240/1/50-60 1 G 10-127/1/50-60 F S A A2 A2 N AUXILIAR AUXILIAR S E O D ( A E S E E R V E (HEA (HEA N . E N C T E P AC AC A3 A3 E

S T D TING) TING) E Y RELA Y RELA T P O E N R N I L N R O I D M Y Y A L L T I I Y N F E . G J4 J4 S 318.29 Pcbw-001sep-042 318.29 Pcbw-001sep-042 ) PSB CIRCUIT BOARD PSB CIRCUIT BOARD L P L H 1 5 1 F 1 N 2 6 3 8 7 A 9 4 1 PUMP OFF: ON: (INACTIVE) ON: (ACTIVE) 1 E E ) 2 ) A ) ) U ) ) ) ) ) A 0 O 3 D O

) ) R ) F T D U M ‘ L D U F I E ‘ D S W F F N M A S D M B I R C J N J T M L W A R H A E E O U V E E S S A A U Y E U U O P 1 A ’ ’ A 1 2 S I E A R P W W

I I D N E E O T E E L N T X E E R M Y T T A S T L S

L : T : M T N S D T R O N O A E E R S R I

D E E * * G T U U W R T O I ( ( T P A A I W

1 I L T R S P N U N I : C J TIMER ST G Y N T Z U O O M Y R R N S M E F I R R R I R R 2 SECONDS : . R I L G H S D E W I E E U N D A O A C

M E L S R

N H R W M O M T M L R O I O A E O A E E A E E 2 H E E E R S E N O S G R L R T I A A E O G E R W N N L S 4 N I R S I T S P R . R O N A U S

H T . T D T A L Y N T N T C T E E P M I D H L T H A T G G S T D T E / T M H O I 2 A O D M L W O I L A I I A O A A K T H R N A I G E A H O C R O E Y T U T R H J E E N I L O S O L L E S W D P T O E - T L S R U

: P H E E A I N D A R O T A A L S :

, V I V 1 A M C U N E A ( S ( S E J I D O N E P L E T R S A T I T H T W C I C E T G A E O T O S U T R G C T E T N R I A E T O E T I

N A T E I A C P C : A O L U N C H D O T I A R A E I I O I S N S S O

TUS H A I

D N R L V L D A I D R O S T T O O L G P O N M T H T U F R O T A T ) N T S E N D T A T U L

D M R O E S S

R C O T M G E 2 H N I E M N R M I L O N F I T

) . / I T M T R L F F I D M U T I O B S A O N O K N C E C I S A M T / E S W A

R S E D C M F O L A A G R M L R I : N E A N F W D P R P R E U D N A 2 S S E G O I N I I E P O R E R I H L A O N E L I P C E N T A I T E R L M L L E Z I B T M S C E W W A T T F L S O A P L T N S D T O G N T N E A U L R A Y M L E E S O Y A E I 2 A A O C W O U R B H

E A L I T O

N S U T T A

. F T C L 1 Y S A P T P I R T S B C L O L E I X O O , F A

D T N S G I O U S 1 L H N L

A L E P O T O N T I O L T E I L O E S T I

N A 0 E P R O D I I E

N P T U L R E G F R S A O E O S C S I O U O B W W I C F v R E L 2 SECONDS I P I M D C R O B T E I Q I S C M F H A P C R W A A O E W F

K T N NO LIGHT M O K R F N H E U

U E R R M E T L R E R E U A R A ( A ½ R L O W E R R D T P L R O E C T O N H Y E R A D R P O Y F T

I N B D Y I P M O E . M A O I E M P N I M O M F T L A I E W A C O O

. O S S S

E S C I T T R R T M M O L S F S U C O M S M A D A T O E P R R

T A M T C P O P E A , A C I I E P R A E R E A I D T A

I A S M O N R O N T S N T D ( O N S I L D T ( N L N E L I N ) O N A L E C T R S A E K B H S I W I B A O . A D U S E I A I U E T T N E E N D V S

L T O G O R T I L I E Y D L A

T C J S B N A Y S C A . N D E N T I A G / I . N H U U N T

U O B S R U C E L

T L R N A ) I E I O R ( R ‘ I G S S A F L R N A L T O A N E G O S O E T R E U I P T U D E T B E ’ G S L

J I 3 A R , A T T /

P E S S V O O C T A S A L S R N E E A T I P T U O ) H A D

I E C E N F N E N , A E E P I T S E L P E I A U L N S R C R R O I G P T M L U AN OPERA W R A R K D G O D Y Y 062816 HE-Z/L R E I N O E A A E E O C A N E I O P Y E Y L L N R H R C

E R A E S D M T C R C W ) O B C G D T S A L O P O R 2 N R M T . I H , A T

R C E C H

A I N L I L N L , S H O I W R A W T ) S N N O I N R Q E T U N T O E I A O O R 2 SECONDS G S U ( E A T I E L E M O A I D N O D M I L

I C U O L C R E N F T I E O 4 R L T N C S I E D L F O A C / S L I N A S A E E R 5 O L H T K

I O D 2 E . N N G O A N A F P L O N T / O R N T V

S 4 W M F E N W E R S O

P O E N G N E A I O O H S O V N N . E C O W -Z 1 R N O D O E A O F I S TION MODE T R V D A P E E A S S F D P 3 E W R D R C L T T F F . I I T F C A R Q 0 U E T N N E

5 A

H I ) O T C T O H I O R D A T O R ) L I U R S U T S I U F E M

L N 10V/220V

A E H R P G E E L R . U E P E A O E R X Y A N D I E E U Q T R T E C S N N C F O U I S T

A S R L B N I B U A R Y B T L C S U O N O S H M I I A I E O M L I I L S T E A F Y E T T N G E R O M T F S F Y O E T T W . S E R S . D E I N A E O .

E H N T S R . Y S S N . M R E E G

. M E .

-11- © 1995-2020 Energy Saving Products Ltd. Module LVZ LV-Z Series Fan Coil Installation (12/28)

LV-Z Fan Coil - PSB Circuit Board Wiring 24 VAC Input terminals (tstat connections):

1st stage Heating, Runs at the heating speed when 24v (R) is supplied, set by the heat trim W1: pot. 2nd stage Heating, Runs at the heating speed when 24v (R) is supplied, set by the heat trim pot. The difference between a W1 call and a W2 call is the output terminal that will be W2: energized with 24v. (W1 energized on t-stat terminal strip will provide 24v to W1 on out- put terminal strip, W2 energized on t-stat terminal strip will provide 24v to W2 on output terminal strip,) C: Common Constant Fan, Runs at the Constant Fan speed when 24v (R) is supplied, set by the Fan trim G: pot. 24 volt supply R: (Note: As long as Transformer is connected & the Fire Disconnect/Jumper Pin Header is Present) 2nd stage Cooling, Runs at the Cooling speed when 24v (R) is supplied, set by the Cool trim Y2: pot. 1st stage Cooling, Runs at the Cooling speed when 24v (R) is supplied, set by the Cool trim pot. The difference between a Y1 call and a Y2 call is the output terminal that will be Y1: energized with 24v. (Y1 energized on t-stat terminal strip will provide 24v to Y1 on output terminal strip, Y2 energized on t-stat terminal strip will provide 24v to Y2 on output terminal strip,) D: Runs at 70% Cooling speed when 24v (R) is supplied, set by the Cool trim pot.

O/B: Heat Pump Reversing Fan Speed Priority Sequence (from highest to lowest): D=1st Y=2nd W=3rd G=4th

24 VAC Output terminals (24v output connections):

24 volt Supply R: (Note: As long as Transformer is connected & the Fire Disconnect/Jumper Pin Header is Present) C: Common

Y1: 1st Stage Cooling Equipment Y2: 2nd Stage Cooling Equipment* W2: 24v Output to 2nd Stage Heating Equipment.

W1: 24v Output to 1st Stage Heating Equipment.

FZ: Freeze Stat Connection*

FZ: Freeze Stat Connection*

*Note: FZ to FZ recommended to be wired to Freeze Stat (Anti-Ice Control). For chilled water applications, a jumper between FZ to FZ must be installed to complete the Y2 - 24V Signal to Y on Condenser.

-12- © 1995-2020 Energy Saving Products Ltd. Module LVZ LV-Z Series Fan Coil Installation (13/28)

LV-Z Fan Coil - PSB Circuit Board Wiring Cont’d

Emergency Disconnect:

C: Common

C: Common Provides 24VAC to the entire PSB board. In order for “Ro” to receive power it must be con- nected to terminal “Ri”. This can be done via the three pin jumper header (H1) located above Ro: the terminal strip, a wire jumper or normally closed safety device installed between “Ro” and “Ri”. The jumper pin header (H1) will need to be removed to activate the emergency disconnect option.

Receives 24VAC direct from the transformer. Power must then be sent to the “Ro” terminal Ri: to be distributed throughout the rest of the PSB board.

3 Pin Jumper Terminals:

H1: Emergency Disconnect Pump timer cycles the pump on for 5 minutes every 24 hours to prevent stagnant water. H2 Timer: (on/off) The jumper pin header (H2) will need to be in the ON position for the timer to be active. the control method used by the PSB to control motor speed. “Auto” uses the pressure transducer in order to modulate fan speed to maintain a constant H3 Mode: supply pressure. “Man” allows for direct speed control of the motor by-passing the pressure transducer. The jumper pin header (H3) determines the control method. Cooling/20 second, Heating/30 second fan delay, and 30 second post purge. The jumper H4 Delay: pin header (H4) will need to be in the ON position for the delay to be active.

Auxiliary Heating Relay:

N: Neutral

L: Line Voltage

A1: Auxiliary Relay Normally Open

A2: Auxiliary Relay Normally Closed

A3: Auxiliary Relay Common

Control Signal:

J8: 0-10 Volt DC Output to VFD

-13- © 1995-2020 Energy Saving Products Ltd. Module LVZ LV-Z Series Fan Coil Installation (14/28)

LV-Z Fan Coil - Extended Wiring Diagrams Extended wiring diagrams for the various applications the LV-Z model can be used for. If you do not find the wiring configuration you require, please call the technical department at Energy Saving Products Ltd. for further assistance. Y) AC OR OR T T AC O 15 V WIRING 15 V Y 1 WIRING Y 15v AND 1 CLOSED OPEN 1 CIRCULA 15 V T 1 CIRCULA Y Y L N iring-Pg-1-082615 A1 A2 A3 AGE - W2 ONL RELA RELA ACTS L N A1 A2 A3 Y CONT Y T T A A TING (W1 OR W2) TING (1 ST TING , DR COMMON NORMALL NORMALL AGE AC COIL Y Y Y T 24v OUTPUT EXTERNAL SPDT RELA 24 V TION FZ R FZ C W1 Y1 W2 Y2 -Z-Extended-W T TING (W1) 24V OUTPUT TING (W2) 24V OUTPUT V AC COMMON AC T 24 V CONDENSING UNIT (Y1) 24V OUTPUT CONDENSING UNIT (Y2) 24V OUTPUT AUXILIAR AUXILIAR AUXILIAR AC WIRING T - FREEZE ST - HEA - HEA - AGE HEA - FREEZE ST - LINE VOL Y HE-Z-L L N 24 V A1 A2 A3 Y1 - Y2 A3 - A2 - A1 - ACT FZ FZ W1 W2

N - NEUTRAL L

C - R - 24 V RELA L N A1 A2 A3 O/B T AGE OPERA R C CONT D VE O Y Y2 TERMINALS T WIRING OPTIONS FOR HEA WIRING OPTIONS FOR HEA WIRING OPTIONS FOR HEA DR Y Y Y AL AC Y1 AGE OR 2ND ST AGE HEA 15 V Y2 WIRING

RELA RELA RELA Y T Y Y Y R T T W SPEED) AND 1 Y T T AGE) AGE) A G (W1) 24v OUTPUT (W2) 24v OUTPUT RELA AN SWITCH USE W2 & ACT ACTS ACTS C W1 - FIRST ST AC COIL F W2 - SINGLE ST AUXILIAR AUXILIAR AUXILIAR T EXTERNAL WIRING AGE HEA AGE COOLING REVERSING V O BOILER A CONT FOR SINGLE ST 24 V SPDT RELA CONT Y T W2 Y FZ R FZ C W1 Y1 W2 Y2 CONT Y (RUNS Y L N A1 AGE HEA AGE COOLING A2 A3 DR DR W1 DR RELA (W1 OR W2) SAMPLE SAMPLE SAMPLE ST ST TPUMP AC COMMON AC OUTPUT THERMOST - Y1 - FIRST Y2 - SECOND ST C - 24 V G D - PRIORITY O/B - HEA W2 - SECOND ST (OR SINGLE ST R - 24 V W1 - FIRST (OR SINGLE ST

J4 J4 O/B O/B O/B O/B O/B O/B D L A3 A2 A1 N D L A3 A2 A1 N Y1 Y1 Y1 Y1 T T Y Y Y2 Y2 Y2 Y2 A A R R R R R R Heatpump G G G G G G Heatpump C C C THERMOST C C C THERMOST W2 W2 W2 W2 R C Y1 Y2 W2 W1 FZ FZ W2 W2 R C Y1 Y2 W2 W1 FZ FZ W1 W1 J7 J7 E

J5 E E J5 E ANTI-ICE CONTROL W1 R W1 O/B R ANTI-ICE CONTROL Y2 O/B 2 Stage Cooling 3 Heating Y1 Y 1 Stage Cooling 2 Heating C CONDENSER Y CONDENSER C

TION J4 J4 TION O/B O/B D D O L A3 A2 A1 N O L A3 A2 A1 N T T Y1 Y1 Y1 INFORMA INFORMA T Y Y T Y2 Y2 Y2 A A ACT ACT R R R R R G G G G G CONT CONT Y Y AND W2 AND W2 C C C THERMOST C C THERMOST TING MODE: REFER TING MODE: REFER W W W2 W2 R C Y1 Y2 W2 W1 FZ FZ R C Y1 Y2 W2 W1 FZ FZ W2 HEA AUXILIAR FOR W1 W1 W1 AUXILIAR FOR W1 HEA J7 J7

J5 J5 E ANTI-ICE CONTROL W1 R O/B ANTI-ICE CONTROL Y2 2 Stage Cooling 1 Heating Y1 Y 1 Stage Cooling Heating C C CONDENSER CONDENSER

-14- © 1995-2020 Energy Saving Products Ltd. Module LVZ LV-Z Series Fan Coil Installation (15/28)

LV-Z Fan Coil - Extended Wiring Diagrams Extended wiring diagrams for the various applications the LV-Z model can be used for. If you do not find the wiring configuration you require, please call the technical department at Energy Saving Products Ltd. for further assistance. C Y CONT ACTS c/w chilled water circulator 1 Stage Cooling FOR W1 AUXILIAR HEA

TING MODE OPTIONS: REFER

J5 J7 AND W2 W1

Y

CONT Y1 Y2 C R FZ W1 FZ W2 W2 C THERMOST C C ACT Heat pump c/w condenser defrost cycle 1 Stage Cooling 2 Heating G G G INFORMA HEA R R R A Y2 Y Y T

TION Y1

CONDENSER C

A1 A2 N L A3 T D O

O/B

T PUMP J4 Y O/B R CIRCULA W1 COOLING CONTROL ANTI-ICE T OR C/W CONDENSER DEFROST CYCLE - BOILER BACK-UP

FOR W1 AUXILIAR HEA

E J5 E J7 TING MODE: REFER

W1

Y1 Y2 FZ W1 C R FZ W2 AND W2 Y W2 W2 W2 CONT C THERMOST C C ACT G G G INFORMA R R R A T Y2 Y Y T O C Y1

TION

Y A1 A2 N L D A3 O/B O/B

O/B

CONT CHILLER J4 ACTS DR T Y O BOILER CONT T CHILLED W c/w chilled water circulator 2 Stage Cooling T ACT HEA FOR W1 AUXILIAR

TING MODE OPTIONS: REFER

J5 24 V SPDT RELA EXTERNAL J7 AND W2 Y

W1

CONT

AC COIL Y1 Y2 C R FZ W1 FZ W2 W2 ACT C THERMOST C C Y INFORMA G G G R R R A Y2 Y2 Y T TION Y1 Y1

T

A1 A2 N L A3 O CONDENSER D C

A O/B Y1 J4 TER WIRING Y2 CONTROL ANTI-ICE O/B R CIRCULA COOLING W1 T Heat pump c/w condenser defrost cycle 2 Stage Cooling 3 Heating OR

FOR W1 AUXILIAR HEA

E J5 E J7 TING MODE: REFER

W1

Y1 Y2 C R FZ W1 FZ W2 AND W2 Y W2 W2 W2 CONT C THERMOST C C ACT G G G INFORMA R R R A T Y2 Y2 Y2 T O Y1 Y1 Y1

TION

A1 A2 N L D A3

O/B O/B O/B J4 C DR T Y O BOILER CONT T Y T CONT CHILLER ACT c/w chilled water circulator 1 Stage Cooling (Only) ACTS HE-Z-L 24 V SPDT RELA EXTERNAL AC COIL V Y AUXILIAR HEA FOR W1 -Z-Extended-W

TING MODE OPTIONS: REFER

J5 J7

W1 AND W2

Y

Y1 Y2 C R FZ W1 FZ W2 CONT W2 THERMOST C C C ACT G G G INFORMA R R R A Y2 Y T Y iring-Pg-2-082615

Y1 TION

A1 A2 N L A3 T D O

O/B J4 Circulator Chilled water

-15- © 1995-2020 Energy Saving Products Ltd. Module LVZ LV-Z Series Fan Coil Installation (16/28)

LV-Z Fan Coil - Extended Wiring Diagrams Extended wiring diagrams for the various applications the LV-Z model can be used for. If you do not find the wiring configuration you require, please call the technical department at Energy Saving Products Ltd. for further assistance. TIMER Y

J4 O/B O/B O/B AUXILIAR L A3 A2 A1 N D O THE “OFF” POSITION Y1 Y1 Y1 iring-Pg-3-082615 SET T T Y2 Y2 Y2 A R R R G G G C C THERMOST H1 C J9 W2 W2 W2

C C Ro Ri R C Y1 Y2 W2 W1 FZ FZ -Z-Extended-W V W1 J7 E

J5 E HE-Z-L W1 R O/B ANTI-ICE CONTROL ELECTRIC BACK-UP Y2 T A Y1 1 2 C CONDENSER 1 2 C AGING THE ST

15-23 KW UNITS AGE TWO ST 24V TERMINALS THROUGH THERMOST OPTIONAL ELECTRIC STRIP 2 Stage Cooling 3 Heating (Electric) Heat pump c/w condenser defrost cycle TIMER Y

J4 O/B O/B C/W CONDENSER DEFROST CYCLE AUXILIAR L A3 A2 A1 N D O THE “OFF” POSITION Y1 SET T T Y Y2 A R R G G C C H1 THERMOST

T PUMP J9 W2 C C Ro Ri R C Y1 Y2 W2 W1 FZ FZ W2 W1 J7

J5 E HEA ANTI-ICE CONTROL W1 R O/B T A Y 1 2 1 2 C AGING THE ST CONDENSER

C 15-23 KW UNITS AGE 1 Stage Cooling 2 Heating (Electric) Heat pump c/w condenser defrost cycle TWO ST 24V TERMINALS THROUGH THERMOST OPTIONAL ELECTRIC STRIP T A

J4 O/B AGE AGE D L A3 A2 A1 N TWO ST ST 1 1 2 2 SINGLE C C This allows single Y1 . TER (ESH) Y Y T Y2 A R R R 1 2 G C G G 24V HEA AGE C C C THERMOST W W R C Y1 Y2 W2 W1 FZ FZ W2 2 AGING THE 15-23 KW UNITS THROUGH OUT DOOR THERMOST W1 INTERNAL ST ELECTRIC STRIP

1 Stage Heating J7

STRIP J5 SINGLE ST 1 WIRING FOR ELECTRICAL stage of the two banks electric strip to activate, the second stage will be allowed to activate by the outdoor stat. For optional energy savings install a outdoor thermostat to limit the use of second stage of the ESH. For example - 2 staging electric strip interrupt “C” and “1” or “2” with a outdoor stat as shown below OPTIONAL AC 2 1 ACTS 24V ELECTRIC STRIP CONT -16- © 1995-2020 Energy Saving Products Ltd. Module LVZ LV-Z Series Fan Coil Installation (17/28)

Diagnostics and Troubleshooting WEG Faults and Possible Causes This section assists the user to identify and correct possible faults that can occur during the CFW-10 operation. When a fault is detected, the inverter is disabled and the fault code is displayed on the readout in EXX form, where XX is the actual fault code. To restart the inverter after a fault has occurred, the inverter must be reset. The reset can be made as follows: R disconnect and reapply the AC power (power-on reset); R press key (manual reset);

The table below defines each fault code, explains how to reset the fault and shows the possible causes for each fault code.

FAULT RESET(1) POSSIBLE CAUSES

E00 Power-on R Short-circuit between two motor phases. Output Manual (key ) R If this fault occurs during power-up, there may be a short. Overcurrent Auto-Reset R Overcurrent Auto-Reset circuit between ground and one or more output (between phases) DI phases. R Inertia of the load too high, or acceleration ramp too short. R IGBT transistor module is short-circuited. E01 R Power supply voltage too high, generating in the DC link a voltage higher DC Link than the allowed value: Overvoltage R Load inertia too high and acceleration ramp is too short.

E02 R Power supply voltage too low, causing a DC link voltage lower than the al- DC Link lowed value (read the value at Parameter P004). Undervoltage (Ud) E04 R Ambient temperature too high (> 50 ºC) and/or output current too high. Inverter Overtemperature R Blocked or defective fan.

Note: The heat sink overtemperature protection (E04) is activated when the heat sink temperature (P008) reaches 103 ºC or 133 ºC for the 15.2 A model. E05 Overload at output R Motor is under an actual overload condition. I x t Function E06 R Wiring at DI1 to DI4 inputs is open (not connected to GND). External Error (digital input program for ext. fault is open) E08 R Electrical noise. CPU Error E09 Contact WEG Servicing R Memory with corrupted values. Program Memory Error (Checksum) E24 It is automatically reset R Incompatible parameters were programmed. Programming error when the incompatible parameters are changed E31 Contact WEG Servicing R Inverter control circuit is defective. Keypad (HMI) Electrical noise in the installation (electromagnetic interference). Connection Fault

E41 Contact WEG Servicing R Inverter power circuit is defective. Self- Diagnosis Fault

-17- © 1995-2020 Energy Saving Products Ltd. Module LVZ LV-Z Series Fan Coil Installation (18/28)

Troubleshooting - Motor Running Too Fast Start

Jumper desired Tstat settingwith 1 R on the PSB circuit board (Figs. 001-002)

2 Power Fan Coil

Fig. 001 Fig. 002 Fig. 003 Verify that Main Supply Voltage is present on the PSB circuit board 3 between the L and N terminals (Fig. 003) Return to Step 4

N 4 Supply Power present? Inspect Supply Voltage Y Replace Transformer Verify that 24VAC is Y present between R & C on N Ensure Transformer is Fig. 004 5 the PSB circuit board connected properly (Fig. 004) N Turn off Supply Power, connect Y Transformer, turn on Verify that 24VAC is Ensure that Jumper Power - Return to Step 5 N Y 6 present between C & is installed correctly desired T-Stat setting (Fig. 002) Y Call Technical Support N Toll Free 1-888-652-2219 Input Voltage and T’Stat function 7 on PSB is functioning correctly Install Jumper and Fig. 005 return to Step 6 Verify that Pressure Sensing 8 section of PSB is functioning within proper operating range Cooling (Y2 terminal) Turn appropriate Heating PSB trimpot Blue Light present on PSB (W2 terminal) 9 N 1/2 turn Counter-Clockwise, Circuit Board? wait 30-45 seconds for Recirc Fan drive to adjust - (G terminal) Y Fig. 006 Return to Step 9 Verify that Pressure Sensing section of PSB is functioning properly Fig. 007 Call Technical Support 10 by measuring Voltage Output Toll Free 1-888-652-2219 (Volts DC) @ the WEG controller, Ensure that Volt Meter is set to N Terminals 7 & 8 (Fig. 005) read Volts DC. Test Voltage on opposite end of cable Voltage present? (Fig. 006) Y Voltage present? (0-10VDC) N 11 Return to Step 11 Y N 12 VDC < 9VDC Decrease PSB trimpot of Y jumpered tstat setting Continue adjustments 1/2 Return to Step 12 turn Counter-Clockwise - until VDC < 9VDC 13 Read and record Volts DC Value Wait 30 seconds for drive to adjust (Fig. 007) Adjust trimpot 14 1/2 turn Counter-Clockwise

Read and record Volts DC value 15 to confirm adjustment Change PSB Circuit Board Adjust trimpot (Again) Adjust 1/2 turn 1/2 turn N N Counter-Clockwise, N Counter-Clockwise, ? 16 VDC changed wait 30 seconds - wait 30 seconds - Y Y VDC changed? VDC changed? PSB Circuit Board is Y Return to Step 13 17 functioning correctly Return to Step 15 Adjust trimpots on PSB Circuit *To adjust the remaining T-Stat settings: Board until airflow is - Jumper between R & the desired T-Stat setting - Adjust the corresponding trimpot to the desired airflow using the 18 running at desired speed *See System Commissioning method described in the System Commissioning and Set-Up. Report and Set-Up

-18- © 1995-2020 Energy Saving Products Ltd. Module LVZ LV-Z Series Fan Coil Installation (19/28)

Troubleshooting - Motor Running Too Slow Start

Jumper desired Tstat settingwith 1 R on the PSB Circuit Board (Fig. 001)

Unplug Motor Leads and test resistance (ohms) 2 between Windings Fig. 001 Fig. 002 Fig. 003 (Figs. 002 & 003) If Resistance is outside of the X acceptable range Resistance should be equal (6.5 - 10.5 ohms) or uneven across any winding legs, 3 Power Fan Coil between all Windings. Black to Red, Black to White and Red to call Technical Support White. Resistance should be: Toll Free @ 1-888-652-2219 - Verify that Main Supply Voltage is 6.5 - 10.5 ohms If Resistance is acceptable, present on the PSB circuit board re-connect Motor Leads and 4 between the L and N terminals continue to Step 3 Fig. 004 (Fig. 004)

N Inspect Supply Voltage - 5 Supply Power Present? Return to Step 5 Y Replace Transformer Verify that 24VAC is Y present between R & C on N Ensure Transformer is 6 the PSB circuit board connected properly (Fig. 005) N Turn off Supply Power, connect Y transformer, turn on power - Fig. 005 Return to Step 6 Verify that 24VAC is Ensure that Jumper N 7 present between C & is installed correctly desired T-Stat setting (Fig. 001) Y Y Call Technical Support N Toll Free 1-888-652-2219 Input Voltage and T’Stat section 8 on PSB is functioning correctly Install Jumper and return to Step 7

Verify that Pressure Sensing section Fig. 006 of PSB is functioning properly Call Technical Support by measuring Voltage Output 9 Toll Free 1-888-652-2219 (Volts DC) @ the WEG controller, Ensure that Volt Meter is set N terminals 7 & 8 (Fig. 006) to read Volts DC - Test Voltage present? Voltage on opposite end of Cable (Fig. 007) Y N 10 Voltage Present? (0-10VDC) Continue to Step 11 Y N 11 VDC > 9VDC Increase appropriate PSB Continue adjustments Y trimpot - 1/2 turn Clockwise until VDC > 9VDC - PSB Circuit Board is Wait 30 seconds for Return to Step 12. 12 Functioning Correctly motor to adjust

Use Clamp on Amp Meter to 14 test Amperage of input power supply to the fan coil. Call Technical Support @ (Fig. 008) 1-888-652-2219. PSB circuit board is working correctly - Amperage > 2A N Replace WEG controller 15 (1 amp @ 220-240 volt AC) Y Fig. 007 Fig. 008 16 PSB Circuit Board & WEG Call Technical Support Toll Drive functioning correctly Free 1-888-652-2219

N 17 Motor running? Adjust Trimpots on PSB Circuit Board until airflow is Y running at desired speed *See System Commissioning Motor working correctly 18 and Set-Up.

-19- © 1995-2020 Energy Saving Products Ltd. Module LVZ LV-Z Series Fan Coil Installation (20/28)

Troubleshooting - Motor Not Running Start

Jumper desired Tstat setting with 1 R on the PSB Circuit Board (Fig. 001)

Unplug Motor Leads and test resistance (ohms) 2 between windings Fig. 001 Fig. 002 Fig. 003 (Figs. 002 & 003) If Resistance is outside of the X acceptable range Resistance should be equal (6.5 - 10.5 ohms) or uneven across any winding legs, 3 Power fan coil between all Windings. Black to Red, Black to White and Red to call Technical Support White. Resistance should be: Toll Free @ 1-888-652-2219 - Verify that Main Supply Voltage is 6.5 - 10.5 ohms If Resistance is acceptable, present on the PSB Circuit Board re-connect Motor Leads and 4 between the L and N Terminals continue to Step 3 Fig. 004 (Fig. 004)

N Inspect Supply Voltage - 5 Supply Power Present? Return to Step 5 Y Replace Transformer Verify that 24VAC is Y present between R & C on N Ensure Transformer is 6 the PSB Circuit Board properly connected (Fig. 005) N Turn off Supply Power, connect Y Transformer, turn on Power. Fig. 005 Return to Step 6 Verify that 24VAC is Ensure that Jumper N 7 present between C & is installed correctly desired T-Stat setting (Fig. 001) Y Y Call Technical Support N Toll Free 1-888-652-2219 Input Voltage and T’Stat section 8 on PSB is functioning correctly Install Jumper and return to Step 7

Verify that Pressure Sensing Section Fig. 006 of PSB is functioning properly Call Technical Support 9 by measuring voltage output Toll Free 1-888-652-2219 (Volts DC) @ the WEG controller, Ensure that Volt Meter is set N terminals 7 & 8 (Fig. 006) to read Volts DC - Test Voltage on opposite end of Voltage Present? Cable (Fig. 007) Y N 10 Voltage Present? (0-10VDC) Continue to Step 11 Y N 11 VDC > 9VDC Increase appropriate PSB Continue adjustments Y trimpot - 1/2 turn Clockwise until VDC > 9VDC - PSB Circuit Board is Wait 30 seconds for Return to Step 12. 12 Functioning Correctly motor to adjust

Ensure on N Red Plug PSB Circuit 13 Fan running? Board is properly connected (Fig. 008) Y

Adjust Trimpots on PSB circuit board until airflow is Y Fan Running? 14 running at desired speed *See System Commissioning Fig. 007 Fig. 008 and Set-Up. N

Call Technical Support Toll Free 1-888-652-2219

-20- © 1995-2020 Energy Saving Products Ltd. Module LVZ LV-Z Series Fan Coil Installation (21/28)

Troubleshooting - 24Volt Thermostat to PSB Circuit Board

Start

Verify Line Voltage power Connect Line N Line Voltage plug N between Voltage plug and connected? L and N return to start

Y Y

Check that Line Voltage wiring Return to from breaker is proper Start

N Check N Connect Verify 24v power Transformer Plugs Transformer Plugs and between R & C Connected? return to start

Y Y

Disconnect 24v Transformer plug with two N Red Wires from middle of Circuit Board and check for Replace 24v Transformer 24v from Transformer

Set Thermostat Signal from N N Temperature and Switch Is T’Stat set for Constant for Constant Fan, Thermostat? (Check across Fan, Cooling or Heating? Y1/Y2 & C or W1/W2 & C) Heating or Cooling

Y Y N Refer to Trouble

Fan running? Shooting - Motor N Check for broken or N Not Running incorrect wiring between Fan running? Thermostat and Board Y

Y Y Finished

Check Resettable Finished Fuse (F1) for heat - Caution: Extremely Check for Continuity through N Replace hot if tripped Thermostat Thermostat

Check 24v Wiring for a dead short and Y for possible second 24v source being Refer to Trouble Fix or replace Wiring Shooting - Motor input into the Circuit Board i.e. Y1 or Not Running Y2 & C on 24v Output Terminals.

-21- © 1995-2020 Energy Saving Products Ltd. Module LVZ LV-Z Series Fan Coil Installation (22/28)

Troubleshooting - Cooling 24 Volt Circuit Board

N Start Thermostat Verify 24v Power between Check Thermostat Cooling Call G & C

Y

N Verify 24v Power between Check Thermostat time Y1/Y2 & C delay for Y1/Y2

Y

N Refer to Fan Running? Troubleshooting - Motor Not Running Y

Y1 & C Y2 & C

Verify 24v Power between N Call Technical Support Y1 for Multi Staging X1 & C Toll Free 1-888-652-2219 units only, Y1 controls Blower Only, Y if Single Stage Cooling, use Y2 Verify 24v Power between Y2 N Freeze Stat tripped & C on 24v Output Terminals or not connected N

Trouble Shooting: Heating 24 Volt Circuit Board

Start Thermostat Verify 24v Power between N Check Thermostat Heating Call W1/W2 & C

Y

N Refer to Fan Running? Troubleshooting - Motor Not Running Y

W1 & C W2 & C

Verify 24v Power between W2 N Call Technical Support & C on 24v OutputTerminals Toll Free 1-888-652-2219 W1 for Multi Staging units only, W1 controls Y blower and Auxiliary relay - If Single Stage Heating use W2 N Call Technical Support Auxiliary Relay Activated Toll Free 1-888-652-2219

-22- © 1995-2020 Energy Saving Products Ltd. Module LVZ LV-Z Series Fan Coil Installation (23/28)

Troubleshooting - Outdoor Unit - Electrical

Start Supply 230v Power to Condensor

N

Y Is Contactor 230v into pulled in? Contactor?

N Y

N Y 230v out of Check for 24v across Replace Contactor Contactor Coil Contactor?

N Y

Check for open Y Y Safety Controls Ensure System is properly Check on Outdoor Unit Charged and Airflow is correct

N

24v across X1 & C N at the Refer to Troubleshooting - 24v Fan Coil?

Y

Check for or 24v across N improper Wiring Y Damage between Indoor and Replace X1 & X2 at the Wiring Fan Coil? Outdoor Units

Y

Allow Y System Ensure System is Properly to settle and Freeze Stat opened? Charged and Airflow is correct Freeze Stat to open

N

Replace Freeze Stat

-23- © 1995-2020 Energy Saving Products Ltd. Module LVZ LV-Z Series Fan Coil Installation (24/28)

Troubleshooting - Short Cycling

Start

Y N Fan Verify that 24v power is present Refer to running? between C and Y2 terminals Troubleshooting - 24v

N Y

Refer to Troubleshooting - Motor Check that TX Valve settingand Not Running to ensure fan is Charge is proper working properly

N TX and Refer to Charge good? Charging on page 33

Y

Confirm the Line Confirm that the Unit Sizes are correct is Properly Sized

Check that the Confirm that all TX Valve Bulb Piping is done is installed correctly properly

Is Confirm that Y Freeze Stat N other Safety working Replace Freeze Stat are Controls properly? working properly

Refer to Troubleshooting - 24v

-24- © 1995-2020 Energy Saving Products Ltd. Matching Coils Module LVZ Refrigerant Coils LV-Z Series Fan Coil Installation (25/28) RBM/RPM-E/RCM-70 Chilled Water Coils WBM/WCM-70/1050, 100/1050 WM-1750 Hot Water Coils LV-Z Series Specifications HWC-70/1050, 1750 Low Velocity Fan Coil w/ VFD Electrical Coils ESH-750 (5-18 kW) LV-Z-1050 LV-Z-1750 (1) 1.5 Ton Airflow 2 Ton Airflow 2.5 Ton Airflow 3 Ton Airflow 3.5 Ton Airflow 4 Ton Airflow 5 Ton Airflow Hot Water Heating (5.3 kW) (7.0 kW) (8.8 kW) (10.6 kW) (12.30 kW) (14.1 kW) (17.6 kW) Coil HWC-70/1050 HWC-70/1050 HWC-70/1050(2) HWC-70/1050(2) HWC-1750 HWC-1750 HWC-1750 Coil Type 6 Row/10 FPI 6 Row/10 FPI 6 Row/10 FPI 6 Row/10 FPI 6 Row/10 FPI 6 Row/10 FPI 6 Row/10 FPI Max. BTUH @ 190°F E.W.T. (kW @ 88°C) 50,100 (14.67 kW) 63,200 (18.51 kW) 75,200 (22.02 kW) 86,000 (25.18 kW) 112,800 (33.03 kW) 125,500 (36.75 kW) 149,200 (43.69 kW) Max. BTUH @ 180°F E.W.T. (kW @ 82°C) 45,900 (13.44 kW) 58,000 (16.98 kW) 69,000 (20.20 kW) 78,900 (23.10 kW) 103,400 (30.28 kW) 115,100 (33.70 kW) 136,800 (40.06 kW) Max. BTUH @ 170°F E.W.T. (kW @ 77°C) 41,800 (12.24 kW) 52,800 (15.46 kW) 62,700 (18.36 kW) 71,700 (20.99 kW) 94,200 (27.58 kW) 104,700 (30.66 kW) 124,400 (36.43 kW) Max. BTUH @ 160°F E.W.T. (kW @ 71°C) 37,700 (11.04 kW) 47,500 (13.91 kW) 56,500 (16.54 kW) 64,600 (18.92 kW) 84,800 (24.83 kW) 94,300 (27.61 kW) 112,100 (32.82 kW) Max. BTUH @ 150°F E.W.T. (kW @ 66°C) 33,600 (9.84 kW) 42,300 (12.39 kW) 50,300 (14.73 kW) 57,400 (16.81 kW) 75,500 (22.11 kW) 83,900 (24.57 kW) 99,700 (29.19 kW) Max. BTUH @ 140°F E.W.T. (kW @ 60°C) 29,400 (8.61 kW) 37,000 (10.83 kW) 43,900 (12.85 kW) 50,100 (14.67 kW) 66,100 (19.35 kW) 73,400 (21.49 kW) 87,000 (25.47 kW) Max. BTUH @ 130°F E.W.T. (kW @ 54°C) 25,200 (7.38 kW) 31,700 (9.28 kW) 37,500 (10.98 kW) 42,700 (12.50 kW) 56,600 (16.57 kW) 62,800 (18.39 kW) 74,400 (21.79 kW) Max. BTUH @ 120°F E.W.T. (kW @ 49°C) 21,100 (6.18 kW) 26,500 (7.76 kW) 31,500 (9.22 kW) 35,900 (10.51 kW) 47,400 (13.88 kW) 52,600 (15.40 kW) 62,300 (18.24 kW) Max. BTUH @ 110°F E.W.T. (kW @ 43°C) 17,100 (5.01 kW) 21,400 (6.27 kW) 25,500 (7.47 kW) 29,100 (8.52 kW) 38,300 (11.21 kW) 42,600 (12.47 kW) 50,500 (14.79 kW) GPM Flow ratings (L/s Flow Ratings) 5 (0.32 L/s) 5 (0.32 L/s) 5 (0.32 L/s) 5 (0.32 L/s) 10 (0.63 L/s) 10 (0.63 L/s) 10 (0.63 L/s)

Pressure Drop in FT. H2O (Drop in KPa) 3.9 (11.66 KPa) 3.9 (11.66 KPa) 3.9 (11.66 KPa) 3.9 (11.66 KPa) 3.1 (9.27 KPa) 3.1 (9.27 KPa) 3.1 (9.27 KPa) Chilled Water Cooling(1) WBM/WCM-70/1050 WBM/WCM-100/1050 WM-1750 Coil Type 70/1050 70/1050 100/1050(3) 100/1050(3) 1750 1750 1750 E.W.T. Max. BTUH @ 48°F E.W.T. (kW @ 8.9°C) 20,200 (5.91 kW) 23,800 (6.97 kW) 31,500 (9.22 kW) 34,900 (10.22 kW) 46,700 (13.67 kW) 50,400 (14.76 kW) 56,200 (16.46 kW) Max. BTUH @ 46°F E.W.T. (kW @ 7.8°C) 22,000 (6.44 kW) 25,800 (7.55 kW) 34,200 (10.01 kW) 37,900 (11.10 kW) 50,700 (14.85 kW) 54,600 (15.99 kW) 60,900 (17.83 kW) Max. BTUH @ 44°F E.W.T. (kW @ 6.7°C) 23,700 (6.94 kW) 27,800 (8.14 kW) 37,000 (10.83 kW) 40,800 (11.95 kW) 55,000 (16.10 kW) 58,800 (17.22 kW) 65,500 (19.18 kW) Max. BTUH @ 42°F E.W.T. (kW @ 5.6°C) 25,400 (7.44 kW) 29,900 (8.76 kW) 39,600 (11.60 kW) 43,800 (12.83 kW) 58,300 (17.07 kW) 62,900 (18.42 kW) 70,000 (20.50 kW) Max. BTUH @ 40°F E.W.T. (kW @ 4.4°C) 27,000 (7.91 kW) 31,800 (9.31 kW) 42,200 (12.36 kW) 46,600 (13.64 kW) 62,100 (18.18 kW) 66,900 (19.59 kW) 74,500 (21.81 kW) S.H.R. Max. BTUH @ 48°F E.W.T. (kW @ 8.9°C) 69% 72% 71% 73% 69% 71% 74% Max. BTUH @ 46°F E.W.T. (kW @ 7.8°C) 67% 70% 68% 70% 67% 68% 71% Max. BTUH @ 44°F E.W.T. (kW @ 6.7°C) 65% 67% 66% 68% 65% 66% 69% Max. BTUH @ 42°F E.W.T. (kW @ 5.6°C) 63% 66% 65% 66% 64% 65% 67% Max. BTUH @ 40°F E.W.T. (kW @ 4.4°C) 62% 64% 63% 65% 62% 63% 65% GPM Flow ratings (L/s Flow Ratings) 5 (0.32 L/s) 5 (0.32 L/s) 7 (0.44 L/s) 7 (0.44 L/s) 10 (0.63 L/s) 10 (0.63 L/s) 10 (0.63 L/s)

Pressure Drop in FT. H2O (Drop in KPa) 4.5 (13.45 KPa) 4.5 (13.45 KPa) 4.5 (13.45 KPa) 4.5 (13.45 KPa) 3.6 (10.76 KPa) 3.6 (10.76 KPa) 3.6 (10.76 KPa)

(1) Refrigerant Cooling RBM/RPM-E/RCM-70/3rd Party N/A (3rd Party Only) RBM/RPM-E/RCM Modules 1.5 - 3.0 Tons (5.3-10.6 kW) 36,000-60,000 BTUH (10.5-17.59 kW) BTUH Refrigerant TX Cooling Electrical Heating ESH/VESH-750 N/A Kilowatt Range 10 - 18 kW / 5 - 18 kW N/A Fan Coil Specifications LV-Z-1050 LV-Z-1750 Max Rated CFM @ 1" E.S.P. (L/s @ 249 Pa) 1200 (566 L/s) 1750 (826 L/s) Voltage 115/230/1/50/60 F.L.A. 8 amp 115/230/1/50/60 F.L.A. 8 amp Nominal Operating Amperage 6 Amps 8 Amps Integral Surge and Fuse System Yes Yes Horse Power/Watts 1/3hp - 515W 3/4hp - 695W Motor RPM Variable Variable Supply Air Size 18” X 171⁄4” (457mm X 438mm) 22 1⁄2” X 22 1⁄2” (572mm X 572mm) Return Size Needed 182 in2 (0.12m2) 240 in2 (0.12m2) Shipping Weight (no coil) 95 lbs (43 kg) 125 lbs (43 kg) 3 Length 32 5⁄16” (821mm) 38 ⁄4” (984mm) 1 Fan Coil Size Width 19 ⁄2” (495mm) 26 3⁄4” (679mm) 1 Height 18 ⁄4” (464mm) 24 1⁄4” (616mm)

(1) Heating specs are rated at 68°F E.A.T., Cooling specs are rated at 80/67°F dB/wB. BTUH - British Thermal Units per Hour F.L.A. - Full-Load Amperage (2) WCM-100 will provide approximately the same heating capacities. E.W.T. - Entering Water Temperature RPM - Revolutions per Minute SHR - Ratio E.S.P. - External Static Pressure (3) Use a full transition when using the WCM-100 to ensure even airflow across the coil. GPM - US Gallons per Minute E.A.T. - Entering Air Temperature The WCM-70 is not to be used at these airflow rates. L/s - Litres per Second dB/wB - Dry Bulb/Wet Bulb CFM - Cubic Feet per Minute -25- © 1995-2020 Energy Saving Products Ltd. Module LVZ Quick Sizing Guide LV-Z Series Fan Coil Installation (26/28) ALL UNITS Item Length Width Height Hi-Velocity Fan Coils A B C 5 1 1 HE-Z/HE-B/HE/HV-50/51 32 ⁄16” (821mm) 14 ⁄2” (368mm) 18 ⁄4” (464mm) 5 1 1 HE-Z/HE-B/HE/HV-70/71 32 ⁄16” (821mm) 19 ⁄2” (495mm) 18 ⁄4” (464mm) 5 1 1 HE-Z/HE-B/HE/HV-100/101 32 ⁄16” (821mm) 25 ⁄2” (648mm) 18 ⁄4” (464mm)

Lo-Velocity Fan Coils A B C JH-15/30 22” (559mm) 14” (356mm) 12” (304mm) 5 1 1 LV-50 32 ⁄16” (821mm) 14 ⁄2” (368mm) 18 ⁄4” (464mm) 5 1 1 LV-Z-1050, LV-70 32 ⁄16” (821mm) 19 ⁄2” (495mm) 18 ⁄4” (464mm) 5 1 1 LV-120/140 32 ⁄16” (821mm) 25 ⁄2” (648mm) 18 ⁄4” (464mm) 3 3 1 LV-Z-1750 38 ⁄4” (984mm) 26 ⁄4” (679mm) 24 ⁄4” (616mm) Length Width Height Line Size Line Size RPM-E Refrigerant Modules - Pre-Piped E F G J K 1 5 1 RPM-E-50 Fits HE-Z/HE-B/HE/HV-50/51/52, LV-50 (1.5 - 2 Ton) 19 ⁄4” (489mm) 14 ⁄8” (371mm) 18 ⁄2” (470mm) 3⁄8” (9.5mm) 7⁄8” (22mm) 1 5 1 RPM-E-70 Fits HE-Z/HE-B/HE/HV-70/71, LV-70 (2.5 - 3 Ton) 24 ⁄4” (616mm) 14 ⁄8” (371mm) 18 ⁄2” (470mm) 3⁄8” (9.5mm) 7⁄8” (22mm) 5 1 RPM-E-100 Fits HE-Z/HE-B/HE/HV-100/101 (3.5 - 5 Ton) 32” (813mm) 14 ⁄8” (371mm) 18 ⁄2” (470mm) 3⁄8” (9.5mm) 7⁄8” (22mm)

RCM Refrigerant Modules E F G J K 3 1 1 RCM-50 Fits HE-Z/HE-B/HE/HV-50/51/52, LV-50 (1.5 - 2 Ton) 14 ⁄8” (365mm) 10 ⁄8” (257mm) 18 ⁄2” (470mm)) 1/2” (13mm) 7⁄8” (22mm) 3 1 1 RCM-70 Fits HE-Z/HE-B/HE/HV-70/71, LV-70 (2.5 - 3 Ton) 19 ⁄8” (492mm) 10 ⁄8” (257mm) 18 ⁄2” (470mm) 1/2” (13mm) 7⁄8” (22mm) 3 1 1 RCM-100 Fits HE-Z/HE-B/HE/HV-100/101 (3.5 - 5 Ton) 25 ⁄8” (645mm) 10 ⁄8” (257mm) 18 ⁄2” (470mm) 1/2” (13mm) 7⁄8” (22mm)

Water Cooling Modules E F G H I 3 1 1 WCM-50 Fits HE-Z/HE-B/HE/HV-50/51/52, LV-50 14 ⁄8” (365mm) 10 ⁄8” (257mm) 18 ⁄2” (470mm) 3⁄4” (19mm) 3⁄4” (19mm) 3 1 1 WCM-70 Fits HE-Z/HE-B/HE/HV-70/71, LV-70, LV-Z/LV-E-1050 19 ⁄8” (492mm) 10 ⁄8” (257mm) 18 ⁄2” (470mm) 3⁄4” (19mm) 3⁄4” (19mm) 3 1 1 WCM-100 Fits HE-Z/HE-B/HE/HV-100/101, LV-120/140, LV-Z/LV-E-1050 25 ⁄8” (645mm) 10 ⁄8” (257mm) 18 ⁄2” (470mm) 3⁄4” (19mm) 3⁄4” (19mm) 1 1 5 WM-1750 Fits LV-Z/LV-E-1750 26 ⁄4”(667mm) 8 ⁄4” (209mm) 22 ⁄8”(575mm) 1” (25mm) 1” (25mm)

Hot Water Coils (6 Row) B D C H I 1 3 1 JH 15/30 Fits JH-15, JH-30 13 ⁄2” (343mm) 3 ⁄8” (85mm) 12 ⁄2” (317mm) 3⁄8” (9.5mm) 3⁄8” (9.5mm) 1 1 HWC-50 Fits HE-Z/HE-B/HE/HV-50/51, LV-50 13 ⁄2” (343mm) 5 ⁄2” (140mm) 16” (406mm) 3⁄4” (19mm) 3⁄4” (19mm) 1 HWC-70 Fits HE-Z/HE-B/HE/HV-70/71, LV-70, LV-Z/LV-E-1050 19” (483mm) 5 ⁄2” (140mm) 16” (406mm) 3⁄4” (19mm) 3⁄4” (19mm) 1 HWC-100 Fits HE-Z/HE-B/HE/HV-100/101, LV-120/140 25” (635mm) 5 ⁄2” (140mm) 16” (406mm) 3⁄4” (19mm) 3⁄4” (19mm) HWC-1750 Fits LV-Z/LV-E-1750 26” (660mm) 6” (152mm) 22” (559mm) 1” (25mm) 1” (25mm) Heating Coil Add-on does not come as a module, it slides into the Hi-Velocity fan coil Electrical Strip Heater B D C 3 5 1 HV-650 (5-15 kW) Fits HE-Z/HE-B/HE/HV-50/51 BU, LV-50 BU 13 ⁄4” (349mm) 5 ⁄8” (143mm) 15 ⁄2” (394mm) 3 5 1 HV-750 (5-18 kW) Fits HE-Z/HE-B/HE/HV-70/71, LV-70, LV-Z/LV-E-1050 18 ⁄4” (476mm) 5 ⁄8” (143mm) 15 ⁄2” (394mm) 3 5 1 HV-1100 (10-23 kW) Fits HE-Z/HE-B/HE/HV-100/101 BU, LV-120/140 BU 24 ⁄4” (629mm) 5 ⁄8” (143mm) 15 ⁄2” (394mm) Dimensions for the ESH do not include the electrical access panel, add 4” to ESH for Total Length

Hi-Velocity Air Purification System E F G HE PS w/ Merv 13 Filt. Fits All 50/51/70//71/100/101/120/140/1050 Units 25” (635mm) 10” (254mm) 17” (457mm) HE PS-1750 w/ Merv 13 Fits LV-Z/LV-E-1750 25” (635mm) 10” (254mm) 21” (533mm)

Standard Filter Rack E F G 1 1 FR-50 Filter Rack Fits HE-Z/HE-B/HE/HV-50/51, LV-50 14 ⁄2” (368mm) 3” (75mm) 18 ⁄2” (470mm) 1 1 FR-70 Filter Rack Fits HE-Z/HE-B/HE/HV-70/71, LV-70, LV-Z/LV-E-1050 19 ⁄2” (495mm) 3” (75mm) 18 ⁄2” (470mm) 1 FR-100 Filter Rack Fits HE-Z/HE-B/HE/HV-100/101, LV-120/140 26” (660mm) 3” (75mm) 18 ⁄2” (470mm) 1 1 FR-1750 Filter Rack Fits LV-Z/LV-E-1750, HV-140 26 ⁄2” (673mm) 3” (75mm) 24 ⁄2” (622mm)

Standard 1” Filter Replacements E F G FR/RA-50 Filter Fits FR-50 Filter Rack 14” (356mm) 1” (25mm) 18” (457mm) FR/RA-70 Filter Fits FR-70 Filter Rack 18” (457mm) 1” (25mm) 18” (457mm) FR/R-100 Filter Fits FR-100 Filter Rack 24” (610mm) 1” (25mm) 18” (457mm) FR/RA-140 Filter Fits FR-1750 Filter Rack 26” (660mm) 1” (25mm) 24” (610mm) 1 JH-15/30 Filter Fits JH-15/30 Fan Coil 10 ⁄2” (267mm) 1” (25mm) 11” (280mm)

Return Air Base B A C 1 1 1 RA-50 Fits HE-Z/HE-B/HE/HV-50/51, LV-50 14 ⁄2” (368mm) 22 ⁄2” (572mm) 18 ⁄2” (470mm) 1 1 1 RA-70 Fits HE-Z/HE-B/HE/HV-70/71, LV-70, LV-Z/LV-E-1050 19 ⁄2” (495mm) 22 ⁄2” (572mm) 18 ⁄2” (470mm) 1 1 1 RA-100 Fits HE-Z/HE-B/HE/HV-100/101, LV-120/140 25 ⁄2” (648mm) 22 ⁄2” (572mm) 18 ⁄2” (470mm) 1 1 RA-1750 Fits LV-Z/LV-E-1750 26 ⁄2” (673mm) 24” (610mm) 24 ⁄2” (622mm) -26- © 1995-2020 Energy Saving Products Ltd. Module LVZ LV-Z Series Fan Coil Installation (27/28)

WARRANTY

Energy Saving Products Ltd. is proud to offer a limited warranty. This warranty applies strictly to the first purchaser at wholesale level and only to the fan coil unit and module. It does not include connections, attachments and other products or materials furnished by the installer. This warranty excludes any damages caused by changes, relocation to, or installation in a new site. This warranty does not cover any defects caused by failure to follow the installation and operating instructions furnished with the fan coil. This warranty does not cover defects caused by failing to adhere to local building codes and following good industry standards. Failure to correctly install the fan coil, or material related to the unit, may result in improper system performance and/or damages and will void this warranty. This warranty does not cover material installed in or exposed to a corrosive environment. This warranty does not cover products subjected to abnormal use, misuse, improper maintenance, or alteration of the product. Using the fan coil and/or module as a source of temporary heating/cooling during construction will void this warranty.

A Five (5) Year Limited Warranty is extended on all components in products manufactured exclusively by Energy Saving Products. These components include Motors, WEG Controller, Circuit Boards, Dampers, Zoning Controls, Blowers, Motor & Blower Assemblies, Heating Coils, Chilled Water Coils, and Air Conditioning Coils. Note: If any product is installed in or exposed to a corrosive environment, warranty will be void.

A Three (3) Year Limited Warranty is extended on Electric Strip Heaters.

Products sold by Energy Saving Products but manufactured by others, will carry the original manufacturer’s warranty.

TERMS & CONDITIONS • Any repair performed under warranty must be approved by Energy Saving Products Ltd. for this warranty to be valid.

• The liability of Energy Saving Products Ltd. is limited to and shall not exceed the cost of pre-approved replacement parts.

• This warranty does not cover shipping costs to and from the factory, labor costs or any other cost associated with the installation of the replacement part.

• Inoperative parts must be returned to Energy Saving Products Ltd. with an ESP RMA Form that includes model, serial number, and a detailed description of the entire problem. Inoperative parts must be returned in testable condition.

• Should there be multiple consecutive failures of a single part, warranty will not be considered unless a contractor has contacted Energy Saving Products Ltd. Technical Department for assistance, and received a tech code.

• Energy Saving Products Ltd. is not liable for any other damages, personal injury, or any other losses of any nature.

Follow these steps for Service or Repair:

1. Contact the installer of the product or a licensed service company 2. Contact the distributor 3. Contact Energy Saving Products Ltd. Mon-Fri 8 am – 4:30 pm MT 1-888-652-2219

This warranty replaces all other warranties expressed or implied. www.hi-velocity.com

-27- © 1995-2020 Energy Saving Products Ltd. Energy Saving Products Ltd, established in 1983, manufactures the Hi-Velocity SystemsTM product line for residential, commercial and multi-family markets. Our facilities house Administration, Sales, Design, Manufacturing, as well as Research & Development complete with an in-house test lab. Energy Saving Products prides itself on Customer Service and provides design services and contractor support. For all of your Heating, Cooling and Indoor Air Quality needs, the Hi-Velocity System is the right choice for you!

TM

Small Duct Heating, Cooling and IAQ Systems

Build Smart, Breathe Easy Hi-Velocity HE-Z Fan Coils, Green Technology

Phone: 780-453-2093 Fax: 780-453-1932 Toll Free: 1-888-652-2219

www.hi–velocity.com