Ventilation for Acceptable Indoor Air Quality

Total Page:16

File Type:pdf, Size:1020Kb

Ventilation for Acceptable Indoor Air Quality ANSI/ASHRAE Addendum n to ANSI/ASHRAE Standard 62-2001 Ventilation for Acceptable Indoor Air Quality Approved by the ASHRAE Standards Committee on June 28, 2003; by the ASHRAE Board of Directors on July 3, 2003; and by the American National Standards Institute on January 8, 2004. This standard is under continuous maintenance by a Standing Standard Project Committee (SSPC) for which the Standards Committee has established a documented program for regular publication of addenda or revisions, including procedures for timely, documented, consensus action on requests for change to any part of the standard. The change submittal form, instruc- tions, and deadlines may be obtained in electronic form from the ASHRAE web site, http://www.ashrae.org, or in paper form from the Manager of Standards. The latest edition of an ASHRAE Stan- dard and printed copies of a public review draft may be pur- chased from ASHRAE Customer Service, 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. E-mail: [email protected]. Fax: 404-321- 5478. Telephone: 404-636-8400 (worldwide), or toll free 1-800-527- 4723 (for orders in U.S. and Canada). ©Copyright 2003 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ISSN 1041-2336 ASHRAE Standard Project Committee 62.1 Cognizant TC: TC 4.3, Ventilation Requirements and Infiltration SPLS Liaison: Fredrick H. Kohloss Andrew K. Persily, Chair* Roger L. Hedrick Walter L. Raynaud* David S. Bulter, Sr., Vice-Chair* Thomas P. Houston* Lisa J. Rogers Leon E. Alevantis* Eli P. Howard, III* Robert S. Rushing* Michael Beaton Ralph T. Joeckel Lawrence J. Schoen Lynn G. Bellenger Donald G. Koch* Dennis A. Stanke Hoy R. Bohanon, Jr. * Carl A. Marbery* Jan Sundell* Dale J. Cagwin Bernice A. Mattsson* Terry Lee Sutherland James L. Coggins* John K. McFarland Wayne Thomann Elissa Feldman* Christopher O. Muller* James A. Tshudy Francis J. Fisher, Jr.* Guillermo A. Navas Dilip Y. Vyavaharkar* Francis Michael Gallo John E. Osborn* David R. Warden Scott Douglas Hanson* R. Dean Rasmussen* Michael W. Woodford* *Denotes members of voting status when the document was approved for publication ASHRAE STANDARDS COMMITTEE 2002-2003 Thomas E. Watson, Chair David E. Knebel Van D. Baxter, Vice-Chair Frederick H. Kohloss Charles G. Arnold William J. Landman Dean S. Borges Merle F. McBride Paul W. Cabot Ross D. Montgomery Charles W. Coward, Jr. Cyrus H. Nasseri Brian P. Dougherty Davor Novosel Hakim Elmahdy Dennis A. Stanke Arthur D. Hallstrom Michael H. Tavares Matt R. Hargan Steven T. Taylor Richard D. Hermans David R. Tree Stephen D. Kennedy Terry E. Townsend, CO Maureen Grasso, ExO Claire B. Ramspeck, Manager of Standards SPECIAL NOTE This American National Standard (ANS) is a national voluntary consensus standard developed under the auspices of the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). Consensus is defined by the American National Standards Institute (ANSI), of which ASHRAE is a member and which has approved this standard as an ANS, as “substantial agreement reached by directly and materially affected interest categories. This signifies the concurrence of more than a simple majority, but not necessarily unanimity. Consensus requires that all views and objections be considered, and that an effort be made toward their resolution.” Compliance with this standard is voluntary until and unless a legal jurisdiction makes compliance mandatory through legislation. ASHRAE obtains consensus through participation of its national and international members, associated societies, and public review. ASHRAE Standards are prepared by a Project Committee appointed specifically for the purpose of writing the Standard. The Project Committee Chair and Vice-Chair must be members of ASHRAE; while other committee members may or may not be ASHRAE members, all must be technically qualified in the subject area of the Standard. Every effort is made to balance the concerned interests on all Project Committees. The Manager of Standards of ASHRAE should be contacted for: a. interpretation of the contents of this Standard, b. participation in the next review of the Standard, c. offering constructive criticism for improving the Standard, d. permission to reprint portions of the Standard. DISCLAIMER ASHRAE uses its best efforts to promulgate Standards and Guidelines for the benefit of the public in light of available information and accepted industry practices. However, ASHRAE does not guarantee, certify, or assure the safety or performance of any products, components, or systems tested, installed, or operated in accordance with ASHRAE’s Standards or Guidelines or that any tests conducted under its Standards or Guidelines will be nonhazardous or free from risk. ASHRAE INDUSTRIAL ADVERTISING POLICY ON STANDARDS ASHRAE Standards and Guidelines are established to assist industry and the public by offering a uniform method of testing for rating purposes, by suggesting safe practices in designing and installing equipment, by providing proper definitions of this equipment, and by providing other information that may serve to guide the industry. The creation of ASHRAE Standards and Guidelines is determined by the need for them, and conformance to them is completely voluntary. In referring to this Standard or Guideline and in marking of equipment and in advertising, no claim shall be made, either stated or implied, that the product has been approved by ASHRAE. (This foreword is not part of this standard. It is merely needed. Furthermore, since the standard is now focused on informative and does not contain requirements necessary minimum requirements, the ventilation rate requirements are for conformance to the standard. It has not been pro- based on that focus as opposed to the 1989 standard, which cessed according to the ANSI requirements for a stan- was not. Also, in recognition of the fact that indoor air pollut- dard and may contain material that has not been subject ants are generated by both building occupants (and their to public review or a consensus process.) activities) as well as by the contents of a building, the ventila- tion requirements include both a people component (to dilute Foreword to Addendum 62n contaminants from people and their activities) and an area This addendum revises the Ventilation Rate Procedure component (to dilute contaminants from non-occupant-related currently contained in Section 6.1 of ANSI/ASHRAE Standard sources that are more related to floor area than the number of 62-2001. This revision was developed as part of the effort to people). The ventilation requirements for a particular space convert the entire standard to mandatory, enforceable lan- based on people and on floor area are then added together to guage suitable for adoption into building codes and to reflect determine the total ventilation requirement for a space. While new technical information that has become available since the acknowledging that the “additivity” approach does not apply current Ventilation Rate Procedure was prepared in the mid- to all aspects of indoor air quality, the committee believes that 1980s. additivity is the predominant effect when considering multiple contaminant sources that impact occupant perception with The Ventilation Rate Procedure in Standard 62-2001 is respect to odor and irritation. While important questions essentially identical to the version in the 1989 standard and remain regarding additivity, the majority of research data sup- contains a number of requirements that run counter to the cur- port its use in this context. rent objectives of minimum requirements and mandatory, enforceable language. For example, the current standard spec- The first public review of addendum 62n occurred in 1999 ifies outdoor air requirements in the “breathing zone,” which and produced about 70 unique comments. Of these, about half are very difficult to actually measure and therefore to enforce. called for increased ventilation rates, while a smaller number It also requires one to account for air mixing in ventilated suggested further decreases. About 10% of the comments spaces when determining outdoor air rates but provides no addressed the issue of complexity, and these were evenly split specific calculation approach for doing so. Standard 62 also between complaints about too much complexity and requests requires the use of the so-called “multiple spaces” equation to for more detail. About one-third commented on the additive adjust outdoor air rates for recirculating systems that serve methodology for combining the ventilation requirements more than one room. However, this equation is seldom used by based on the number of people with the requirements based on designers (possibly due to its perceived complexity) and, as floor area, but the committee retained this approach based on presented in the current standard, does not apply to many the principles discussed above and the ability to explicitly common system types. adjust ventilation rates based on occupant density. In response The revision in this addendum addresses these issues to many of the public review comments, a full second public related to the objective of code-intended language in a number draft was developed and issued for comment. In this draft, of ways. It specifies the determination of design ventilation some of the ventilation requirements were increased (most rates that can be easily measured so that compliance can be notably in educational buildings) relative to the first public verified, both by review of the design
Recommended publications
  • Preparing HVAC Systems Before Reoccupying a Building by JOHN MCCARTHY, SC.D., C.I.H., MEMBER ASHRAE; KEVIN COGHLAN, C.I.H
    TECHNICAL FEATURE This article was published in ASHRAE Journal, January 2021. Copyright 2020 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission of ASHRAE. For more information about ASHRAE Journal, visit www.ashrae.org. Preparing HVAC Systems Before Reoccupying A Building BY JOHN MCCARTHY, SC.D., C.I.H., MEMBER ASHRAE; KEVIN COGHLAN, C.I.H. As states across the U.S. roll out new phases of reopening and ease social distanc- ing restrictions instituted to “flatten the curve” of infection from SARS-CoV-2 (the virus that causes COVID-19), commercial building owners and facility manag- ers are seeking direction in preparing their spaces to a return to near-normal levels of occupancy. World Health Organization (WHO) and Centers for Disease Control and Prevention (CDC) recommendations have focused on “de-densifying” spaces and disinfection of surfaces, while the ASHRAE Epidemic Task Force’s comprehen- sive Building Readiness guidance addresses strategies for preparing HVAC systems for buildings reopening after COVID-19 closures.1 Still, facility engineers have been wondering whether disinfecting their facility’s HVAC system is a further protective step to take to prepare for reopening—and about what else they should do. While no blanket answer exists to fit every scenario reduced loads or turned off as an energy-saving and every building type, the current science2 indicates measure. that, in general, disinfection of mechanical systems is not likely to be necessary. However, that doesn’t mean How SARS-CoV-2 Transmission Impacts Disinfection there isn’t work to be done—or risks to address before Recommendations reopening or expanding the number of occupants To understand why HVAC system disinfection may not in the space.
    [Show full text]
  • Simplified Method for Indoor Airflow Simulation
    Proceedings of CLIMA 2000 World Congress, Brussels, Belgium. Simplified Method for Indoor Airflow Simulation Qingyan Chen and Weiran Xu Building Technology Program, Department of Architecture Massachusetts Institute of Technology Room 5-418, 77 Massachusetts Avenue, Cambridge, MA 02139-4307, USA Phone: 617-253-7714, Fax: 617-253-6152 E_mail: [email protected] URL: http://web.mit.edu/qchen/www/ ABSTRACT At present, numerical simulation of room airflows is mainly conducted by either the Computational-Fluid-Dynamics (CFD) method or various zonal/network models. The CFD approach needs a large capacity of computer and a skillful expert. The results obtained with zonal/network models have great uncertainties. This paper proposes a new simplified method to simulate three-dimensional distributions of air velocity, temperature, and contaminant concentrations in rooms. The method assumes turbulent viscosity to be a function of length-scale and local mean velocity. The new model has been used to predict natural convection, forced convection, mixed convection, and displacement ventilation in a room. The results agree reasonably with experimental data and the CFD computations. The simplified method uses much less computer memory and the computing speed is at least 10 times faster, compared with the CFD method. The grid number can often be reduced so that the computing time needed for a three-dimensional case can be a few minutes in a PC. INTRODUCTION Proper design of indoor environment requires detailed information of indoor air distribution, such as airflow pattern, velocity, temperature, and contaminant concentrations. The information can be obtained by experimental measurements and computational simulations. Experimental measurements are reliable but need large labor- effort and time.
    [Show full text]
  • Position Document on Resiliency in the Built Environment
    ASHRAE and CIBSE Position Document on Resiliency in the Built Environment Approved by ASHRAE Board of Directors June 26, 2019 Approved by the CIBSE Board July 11, 2019 Expires June 26, 2022 © 2019 ASHRAE and CIBSE ASHRAE • 1791 Tullie Circle, NE • Atlanta, Georgia 30329-2305 • 404-636-8400 • www.ashrae.org CIBSE • 222, Balham High Road • London SW12 9BS • 0208 675 5211 • www.cibse.org © 2019 ASHRAE and CIBSE. For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without copyright holders' prior written permission. COMMITTEE ROSTER The ASHRAE and CIBSE Position Document on Resiliency in the Built Environment was developed by ASHRAE’s Resiliency in the Built Environment Position Document Committee formed on October 10, 2017, with David Under- wood as its chair. David Underwood Andrew Persily Retired NIST Oakville, ON, Canada Gaithersburg, MD, USA Scott Campbell Thomas Phoenix National Ready Mixed Concrete Association Clark Patterson Lee Milwaukee, WI, USA Greensboro, NC, USA Hywel Davies CIBSE Paul Torcellini London, United Kingdom Eastford, CT, USA Bill McQuade Chandra Sekhar AHRI National University of Singapore Arlington, VA, USA Singapore, Singapore The CIBSE Technology Committee was responsible for oversight of the CIBSE contribution to this position docu- ment. Cognizant Committees The chairperson of ASHRAE Technical Committee 2.10, Resilience and Security, also served as an ex-officio member: Jason DeGraw Arvada, CO, USA ASHRAE is a registered trademark in the U.S. Patent and Trademark Office, owned by the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. © 2019 ASHRAE and CIBSE. For personal use only.
    [Show full text]
  • ASHRAE Position Document on Filtration and Air Cleaning
    ASHRAE Position Document on Filtration and Air Cleaning Approved by ASHRAE Board of Directors January 29, 2015 Reaffirmed by Technology Council January 13, 2018 Expires January 23, 2021 ASHRAE 1791 Tullie Circle, NE • Atlanta, Georgia 30329-2305 404-636-8400 • fax: 404-321-5478 • www.ashrae.org © 2015 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission. COMMITTEE ROSTER The ASHRAE Position Document on Filtration and Air Cleaning was developed by the Society's Filtration and Air Cleaning Position Document Committee formed on January 6, 2012, with Pawel Wargocki as its chair. Pawel Wargocki, Chair Dean A. Saputa Technical University of Denmark UV Resources Kongens Lyngby, Denmark Santa Clarita, CA Thomas H. Kuehn William J. Fisk University of Minnesota Lawrence Berkeley National Laboratory Minneapolis, MN Berkeley, CA H.E. Barney Burroughs Jeffrey A. Siegel Building Wellness Consultancy, Inc. The University of Toronto Johns Creek, GA Toronto, ON, Canada Christopher O. Muller Mark C. Jackson Purafil Inc. The University of Texas at Austin Doraville, GA Austin, TX Ernest A. Conrad Alan Veeck BOMA International National Air Filtration Association Washington DC Virginia Beach, VA Other contributors: Dean Tompkins Madison, WI for his contribution on photocatalytic oxidizers Paul Francisco, Ex-Officio Cognizant Committee Chair Environmental Health Committee University of Illinois Champaign, IL ASHRAE is a registered trademark in the U.S. Patent and Trademark Office, owned by the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. © 2015 ASHRAE (www.ashrae.org). For personal use only.
    [Show full text]
  • Dampers and Airflow Control Dampers and Airflow Control Dampers and Airflow Dampers and Airflow Control Is the First Book of Its Kind
    Good airflow control results when solid mechanical design is combined with excellent control strategy. Modern building requirements for the coordination of air ventilation, pres- surization, temperature control, fire and smoke control, and energy reduction require inte- gration at every level of design and operation. Dampers and Airflow Control Dampers and AirflowDampers Control Dampers and Airflow Control is the first book of its kind. It bridges the gap between Laurence G. Felker and Travis L. Felker mechanical design and final damper control. This book covers not only theoretical aspects of application design but also practical aspects of existing applications, and the material applies to both new and retrofit projects. Among the topics discussed are new ASHRAE damper testing data, realistic but simplified pressure drop calculations, damper installations, and methods for economizers and mini- mum outdoor-air control. Tactics to linearize system airflow using damper response curves are also discussed, and new methods—not found in existing literature—are presented to characterize damper response to fit a process. Additional topics include torque, linkages, structural support, actuation, and engineered damper assemblies. Dampers and Airflow Control is written for building systems designers and contractors and provides sound examples and best practices to achieve good airflow control. Felker and Felker Felker American Society of Heating, Refrigerating and ISBN 978-1-933742-53-3 Air-Conditioning Engineers, Inc. 1791 Tullie Circle Atlanta, GA 30329-2305 Telephone: 404-636-8400 (worldwide) 9 781933 742533 www.ashrae.org Product code: 90138 11/09 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Dampers and Airflow Control.indd 1 11/9/2009 4:30:48 PM Dampers and Airflow Control © American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
    [Show full text]
  • Ventilation Heat Recovery Ventilation Glazing; Equipment Insulation
    Town of Warner Building Energy Performance Reports Social Services Government Roads Police Fire Waste Material Waste Water Garage 1 2008 Town Building Energy Use 2 4 5 Oil: 4567 gallons Oil: 4057 gallons LP: 5,122 gallons Elec: 20,160KWH Elec: 19,428KWH Elec: 21,120KWH 72KBtu/ft2 57.4KBtu/ft2 48.4KBtu/ft2 3 8 6* LP: 2,033 gallons Oil: 817 gallons Kerosene: 934 gallons Elec: 19,750KWH Elec: 7,290KWH Elec: 18,731KWH 59.6KBtu/ft2 29.4KBtu ft2 45KBtu/ft2 1 Gallons Btu’s Dollars 7 Oil 10,706 1,483MM $32,118 LP: 2200 gallons LP 9,455 861MM $11,555 Oil: 152 gallons Elec: 130,968KWH Elec 237,906 812MM $37,332 Elec: 459KWH *289KBtu/ft2 TOTALS 2,946MM $81,000 33.8KBtu/ft2 2 Town Building 2008 Utility Costs 3 4 2 $17,615 $15,413 $19,081 5 7 6 $7,005 $9,217 $3,869 8 1 $24,500 $658 3 Town Building 2008 Greenhouse Emissions 2 3 4 120,054lbs 104,184lbs 78,508lbs 5 7 6 34,109lbs 39,232lbs 23,379lbs 8 1 121,507lbs 3,712lbs 4 Town Building Air Leakage Rates 6ACH50 8ACH50 .79cfm/ft2shell 1.21cfm/ft2shell Not tested 2 16ACH50 9ACH50 Not tested 1.3cfm/ft2shell .99cfm/ft2shell ACH50 – Air changes per hour at - 50Pa; relative to building volume 1 6ACH50 33 ACH50 .45cfm/ft2shell Cfm/ft2 shell – cubic feet of air per minute relative to surface area of shell 2.22cfm/ft2shell 5 Summary of Prominent De-ficiencies Insulation Heat Recovery Insulation Ventilation Heat Recovery Ventilation Glazing; Equipment insulation Air Sealing Air Sealing Air Sealing Insulation insulation Equipment Insulation Air Sealing Electric Loads glazing AS / HRV insulation 6 Prioritize by
    [Show full text]
  • ANSI/ASHRAE/ACCA Standard 180-2018
    ANSI/ASHRAE/ACCA Standard 180-2018 (Supersedes ANSI/ASHRAE/ACCA Standard 180-2012) Standard Practice for Inspection and Maintenance of Commercial Building HVAC Systems Approved by ASHRAE on June 11, 2018; by the Air Conditioning Contractors of America on May 13, 2018; and by the American National Standards Institute on June 11, 2018. ASHRAE® Standards are scheduled to be updated on a five-year cycle; the date following the Standard number is the year of ASHRAE approval. The latest edition of an ASHRAE Standard may be purchased on the ASHRAE website (www.ashrae.org) or from ASHRAE Customer Service, 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. E-mail: [email protected]. Fax: 678-539-2129. Telephone: 404-636-8400 (worldwide) or toll free 1-800-527-4723 (for orders in US and Canada). For reprint permission, go to www.ashrae.org/permissions. © 2018 ASHRAE and ACCA® ISSN 1041-2336 ASHRAE Standard Project Committee 180 Lead Cognizant TC: 7.3, Operation and Maintenance Management Co-Cognizant TCs: 2.4, Particulate Air Contaminants and Particulate Contaminant Removal Equipment; and TC 9.8, Large Building Air-Conditioning Applications SPLS Liaison: R. Lee Millies, Jr. Thomas L. Paxson*, Chair Kristin H. Heinemeier* Heather L. Platt* Donald R. Langston*, Vice-Chair Donald C. Herrmann Donald Prather* Richard A. Danks*, Secretary Peter C. Jacobs* Gregg A. Ray* Hywel Davies Michael J. Lawing* George Rodriguez* Bill R. Benito* Benjamin E. Lipscomb Dale T. Rossi* Michael Blazey Phil London* Robert J. Roth Glenn Friedman* Phil Maybee* Jeff O. Sturgeon* Michael W. Gallagher Marc Newman* John Warfield * Denotes members of voting status when the document was approved for publication ACCA–EI Standards Task Team 2018–2019 Phil Forner, Chair Warren Lupson Matt Todd Dave Galbreath, Vice-Chair Raymond Granderson Brent Ursenbach Danny Halel, Secretary Timothy Offord Tom Jackson Joe Pacella ASHRAE STANDARDS COMMITTEE 2017–2018 Steven J.
    [Show full text]
  • Assessment of Design Procedures for Vertical Borehole Heat Exchangers
    PROCEEDINGS, Fortieth Workshop on Geothermal Reservoir Engineering Stanford University, Stanford, California, January 26-28, 2015 SGP-TR-204 Assessment of Design Procedures for Vertical Borehole Heat Exchangers Eleonora Sailer1, David M.G. Taborda2 and James Keirstead2 1AECOM, Chelmsford, CM1 1HT, UK, formerly Imperial College London, UK 2Imperial College London, Dept. Civil & Environmental Engineering, London SW7 2AZ UK [email protected] Keywords: Borehole heat exchanger, low enthalpy systems, ground source heat, design guidelines ABSTRACT The use of ground source energy systems is a well-established method to provide low cost heating to buildings, diversify the energy mix and help meeting increasingly stricter sustainability targets. However, considerable uncertainties remain over their efficient design, with several standards, guidelines and manuals being proposed over the last few years. This paper aims at providing insight into the implications to the design of a vertical borehole heat exchanger of the adoption of different design procedures. The hypothetical case of a typical dwelling located in London, UK, is analysed in order to highlight the impact on the final design of the chosen methodology. Moreover, a parametric study using an analytical design procedure was performed to point out the influence of various factors, such as borehole characteristics and thermal properties of the ground. It is shown that there are considerable discrepancies between design methods and that uncertainties in some input parameters, such as the thermal properties of the ground, which for relatively small systems are often selected from tables rather than measured in situ, may have a substantial influence on the length of borehole required. 1. INTRODUCTION Borehole Heat Exchangers (BHE) are one type of Ground Source Heat Pump (GSHP) systems and are classified as low enthalpy geothermal systems since they make use of low temperature differences.
    [Show full text]
  • Humidity and Occupants Presentation
    Humidity and Occupants What the Latest in Humidity Research Means for You Presenters Matt Nowak North American Sales Manager Armstrong International Eric Brodsky, PE Director of Technology Research Products Inc. / Aprilaire / DriSteem Duncan Curd General Manager Nortec Humidity Ltd. Jeremy Wolfe National Sales & Marketing Manager CAREL USA Agenda 1. Fundamentals of Humidity • Key Terms and Definitions • How indoor humidity changes throughout the year • Where humidification matter most 2. Humidity and People • Historical Research • Impacts of moisture to the human body • Recent advances in humidity research 3. Recent Research • Microbiome Study Details • Example of Hospital Savings • Results and Recommendations 4. Humidity in Your Building • Technologies for Humidification • Cooling and Humidifying with Adiabatic Systems • Humidification with Steam • Case Studies / Installation Examples What is Humidity and How Do We Measure It? Humidity • The amount of water vapor in the air • Measured in “Absolute” or “Relative” terms Absolute Humidity • Mass of water in particular volume of air • Expressed as mass (grains/lbda or gw/kgda) Relative Humidity • Amount of water vapor in the air relative to how much it can hold at a given temperature (%) 25 20 15 Maximum Moisture Content Of Air Depends 10 5 0 On Air Temperature Grains Grains of/ Water Cubic Foot of Air 0 5 -5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 -10 100 Air Temperature (F) How Much Water Can the Air Hold? Air Heated From 10°F @ 100% RH to 70 °F 1 lb (kg) of Air Would Only Be Less Than 10% RH 35°F (2°C) 30 gr (2g/kg) The Psychrometric Chart Typical RH in Las Vegas, NV Typical Temps in Las Vegas, NV Need for Humidification Summer (July 19th) – 104F @ 10% RH = 72F @ 27.5% RH Winter (Dec.
    [Show full text]
  • Colorcoat Renew SC Design Guide
    Uniclass L5141:P41 CI/SfB (41) Nh2 January 2016 Colorcoat Renew SC® Design guide 2 +44 (0) 1244 892199 | www.tatasteelconstruction.com Contents 1. Colorcoat Renew SC® system overview 4 3.4 Other physical solar collector design considerations 15 1.1 Introduction 4 3.4.1 Perforation diameter and pitch 15 1.2 Working principles of Colorcoat Renew SC® 4 3.4.2 Profile options 16 1.3 Benefits of a Colorcoat Renew SC® system 5 3.4.3 Cavity (plenum) 16 1.4 Colorcoat Renew SC® integration 6 3.4.4 Solar collector integration 17 1.4.1 Suitable building types 6 4. Construction 17 2. System performance factors 7 4.1 Requirements and regulations 17 2.1 General design factors 7 4.2 Collector components 17 2.1.1 Solar collector orientation 7 4.3 Typical construction details 18 2.1.2 Collector angle (Tilt) 8 4.4 Fasteners 21 2.1.3 Shading 8 4.5 Maintenance recommendations 21 2.2 Colour selection and influence on performance 9 5. Mechanical and electrical design considerations 22 2.2.1 Guarantee Colorcoat Renew SC® 10 5.1 Building heating and ventilation 3. Collector design and sizing 11 requirements 22 3.1 Building geometry, occupancy and function 11 5.1.1 Intake air quality 22 3.2 Solar collector sizing - description 12 5.2 Relationship between airflow, temperature increase and efficiency 23 3.2.1 Choosing the wall 5.2.1 Temperature rise 23 3.2.2 Determining the volume of the building space to be heated 5.2.2 Wind considerations 24 3.2.3 Determining the volume of air 5.2.3 Transition duct sizing 24 required by the building ventilation system 5.2.4 Pressure drop 24 3.2.4 Determining the optimum balance 5.3 Operating modes 25 of heating and ventilation requirement 5.4 System control and metering 25 3.2.5 Collector sizing guidelines 6.
    [Show full text]
  • Program and Abstracts CONFERENCE COMMITTEE
    ICC 19 San Diego, CA · June 20-23, 2016 P Program and Abstracts CONFERENCE COMMITTEE Conference Chairman Program Committee Dean Johnson Carl Kirkconnell, West Coast Solutions, Jet Propulsion Laboratory, USA USA - Chair Email: [email protected] Mark Zagarola, Creare, USA, - Deputy Chair Conference Co-Chairmen Tonny Benchop, Thales Cryogenics BV, Netherlands Jose Rodriguez Peter Bradley, NIST, USA Jet Propulsion Laboratory, USA Ted Conrad, Raytheon, USA Email: [email protected] Gershon Grossman, Technion, Israel Elaine Lim, Aerospace Corporation, USA Sidney Yuan Jennifer Marquardt, Ball Aerospace, Aerospace Corporation, USA USA Jeff Olson, Lockheed Martin, USA Email : [email protected] John Pfotenhauer, University of Wisconsin – Madison, USA Treasurer Alex Veprik, SCD, Israel Ray Radebaugh Sonny Yi, Aerospace Corporation, USA National Institute of Standards and Technology (NIST), USA ICC Board Email: [email protected] Dean Johnson, JPL, USA-Chairman Ray Radebaugh, NIST, USA – Treasurer Proceedings Co-editors Ron Ross, JPL, USA – Co-Editor Saul Miller Jeff Raab, Retired, USA – Past Chairman Retired Rich Dausman, Cryomech, Inc., USA - Email: icc [email protected] Past Chairman Paul Bailey, University of Oxford, UK Peter Bradley, NIST, USA Ron Ross Martin Crook, RAL, UK Jet Propulsion Laboratory, USA Lionel Duband, CEA, France Email: [email protected] Zhihua Gan, Zhejiang University, China Ali Kashani, Atlas Scientific, USA Takenori Numezawa, National Institute for Program Chair Material Science, Japan Carl Kirkconnell Jeff Olson, Lockheed Martin Space System West Coast Solutions, USA Co., USA Email: [email protected] Limin Qiu, Zhejiang University, China Thierry Trollier, Absolut System SAS, Deputy Program Chair France Mark Zagarola, Creare, USA Mark V.
    [Show full text]
  • Covid-19 Ventilation Faqs
    COVID-19 VENTILATION FAQS Updated July 9, 2021 Limiting COVID-19 transmission in the workplace involves critical elements outlined in the University’s COVID-19 Prevention Plan for the Workplace. Maintaining building systems, including central heating, ventilation, and air conditioning (HVAC) systems, to support safe occupancy is a supplemental effort to the University’s COVID-19 prevention measures. This document contains responses to frequently asked questions from occupants in University facilities. Building coordinators and facility managers may share the responses with occupants as appropriate. Which standards and guidelines does the University follow for maintaining HVAC systems? • American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) o Coronavirus (COVID-19) Response Resources from ASHRAE and Others • Centers for Disease Control and Prevention (CDC) – Ventilation in Buildings • Seattle Mechanical Code / International Mechanical Code • Washington State Department of Labor & Industries o General Coronavirus Prevention Under Stay Home-Stay Healthy Order o COVID-19 Guidance on Ventilation in the Workplace What do I need to know about ventilation in University buildings? UW buildings are typically supplied with a percentage of outside air either via mechanical fans (a mechanical HVAC system), or natural ventilation (e.g., operable windows), dependent on each building and system. Those systems are maintained to provide ventilation and thermal comfort as designed through the following activities: • In most cases, air filters in buildings equipped with central heating, ventilation, and air conditioning (HVAC) systems are rated at MERV-13 or higher as recommended by the CDC and have been inspected and changed per maintenance procedures and schedules. • Building HVAC systems have continued to operate normally during all phases of the pandemic, even while buildings were unoccupied or at reduced occupancy.
    [Show full text]