MODEL SPECIFICATION

Product Kingspan Kooltherm® K8 Cavity Board Application Masonry cavity wall Project Architect Issue Date

1. GENERAL

1.1. Scope of Work – Insulation Masonry cavity walls ______mm thick Kingspan Kooltherm® K8 Cavity Board installed in the masonry cavity wall to achieve a total thermal resistance of RT______heat flow in and RT______heat flow out (TPC Reference No.: ______).

1.2. Company Contacts – Insulation Kingspan Insulation technical contacts Email: [email protected] Telephone: 1300 247 235 Web: www.kingspaninsulation.com.au/Contact-Us/Enquiry

1.3. Manufacturer’s Documents – Insulation Design guide: www.kingspaninsulation.com.au/design-guide/index.html Product datasheet: www.kingspaninsulation.com.au/Literature/Products Safety datasheet: www.kingspaninsulation.com.au/Literature/MSDS

1.4. Interpretation – Insulation Definitions General: For the purposes of this worksection the following definitions apply:  Fire hazard properties: Terminology to NCC A2.4.  Thermal insulation terminology: To AS/NZS 4859.1.  Masonry structures terminology: To AS 3700.

1.5. Inspection – Insulation Notice Inspection: Give notice to Kingspan Insulation so that inspection may be made of the insulation before it is covered up or concealed.

1.6. Submissions – Insulation Certification Certification: CodeMark certificate to be submitted as evidence of compliance with the NCC.

2. MATERIALS

2.1. Product substitution Other insulation: Conform to Submissions – Insulation, Substitutions in the General requirements work section. Use of expanded polystyrene (EPS), extruded polystyrene (XPS), rigid foam polyurethane (PU), glasswool, rockwool and / or polyisocyanurate (PIR) insulation other than those specified are not acceptable unless formally accepted by the relevant fire authorities and the building owners insurance underwriters.

Version: Feb 2015 1 MODEL SPECIFICATION

2.2. Marking – Insulation Identification General: Deliver materials to the site in the Kingspan original sealed packaging, legibly marked to show the following:  Manufacturer’s identification.  Product brand name.  Product type.  Quantity.  Product reference code and batch number.  Date of manufacture.

2.3. Kingspan Insulation Product – Insulation Kingspan Kooltherm® K8 Cavity Board Description: Cavity insulation board comprising a rigid thermoset phenolic insulation core, faced on both sides with reflective composite aluminium foil, autohesively bonded to the insulation core during manufacture.  Thickness: _____ mm  R-value: R______ Foil emittance: E0.06  Board size: 2270 mm x 514 mm / 400 mm / 600 mm  CodeMark certificate: SAIG-CM20043 www.kingspaninsulation.com.au/Literature/Certificates-Warranties#codemark

Fire hazard properties Insulation: When tested to AS 1530.3, Kingspan Kooltherm® K8 Cavity Board achieves the following results:  Ignitability: 9  Flame spread: 0  Heat evolved: 1  Smoke development: 3

The insulation shall have a tested smoke obscuration of not more than 100 m2/kg.

Insulation standard Insulation: Kingspan Kooltherm® K8 Cavity Board complies with AS/NZS 4859.1.

Management standards Insulation: Kingspan Kooltherm® K8 Cavity Board is manufactured under a management system certified to:  BS/IS EN ISO 9001:2008 Quality Management  BS/IS EN ISO 14001:2004 Environmental Management  BS/IS OHSAS ISO 18001:2007 Health and Safety Management

2.4. Fasteners and Supports General: Insulation retaining discs / clips to be approximately 80 mm in diameter.

3. EXECUTION

3.1. Fixing to Masonry Cavity Wall – Insulation Application Location: To the inner leaf

Fixing Construct the inner leaf to at least an appropriate level to allow installation of Kingspan Kooltherm® K8 Cavity Board to proceed. Remove excess mortar and mortar droppings from exposed edges of any installed insulation boards. Offer the Kingspan Kooltherm® K8 Cavity Board to the external face of the internal leaf and secure in place using the wall ties and retaining disc / clip. Ensure wall ties include a retaining disc / clip and be of the double drip type, installed drip downward. The outer leaf is then built up to the level of the top of the boards and the process is repeated.

Version: Feb 2015 2 MODEL SPECIFICATION

Ensure that a residual cavity of at least 40 mm is maintained in accordance with the moisture penetration provisions set out in the masonry structures standard AS 3700 as called up in the NCC B1.4.

Cutting General: Cutting should be carried out either by using a fine toothed saw, or by scoring with a sharp knife, snapping the board over a straight edge and then cutting the facing on the other side. Ensure accurate trimming to achieve close-butting joints and continuity of insulation.

3.2. Completion – Insulation Warranties Warranty: A Project Specific Warranty provided by Kingspan Insulation must be submitted.