Augusta Utilities Department FOG Section About Traps and Interceptors

Why are Fats, Oil, and Grease a problem?

Fats, oil and grease - - also called FOG in the wastewater business - - can have negative impacts on wastewater collection and treatment systems. Most wastewater collection system blockages can be traced to FOG. Blockages in the wastewater collection system are serious, causing spills, overflows, or sewage backups in homes and businesses.

Large amounts of oil and grease in the wastewater cause trouble in the collection system pipes. It decreases capacity and, therefore, requires that piping systems be cleaned more often and/or some piping to be replaced sooner than otherwise expected. Oil and grease also hamper effective treatment at the wastewater treatment plant.

Grease in a warm liquid may not appear harmful. But, as the liquid cools, the grease or fat congeals and causes nauseous mats on the surface of settling tanks, digesters, and the interior of pipes and other surfaces which may cause a shutdown of wastewater treatment units.

Problems caused by wastes from restaurants and other grease-producing establishments have served as the basis for ordinances and regulations governing the discharge of grease materials to the system. This type of waste has forced the requirement of the installation of preliminary treatment facilities, commonly known as grease traps or interceptors.

What is a grease and how does it work?

A trap is a small reservoir built into the wastewater piping a short distance from the grease producing area. Baffles in the reservoir retain the wastewater long enough for the grease to congeal and rise to the surface. The grease can then be removed and disposed properly.

Grease Trap

A. Flow from four or fewer kitchen fixtures enters the grease trap. B. An approved flow control or restricting device is installed to restrict the flow to the grease trap to the rated capacity of the trap. C. An air intake valve allows air into the open space of the grease trap to prevent siphonage and back-pressure. D. The baffles help to retain grease toward the upstream end of the grease trap since grease floats and will generally not go under the baffle. This helps to prevent grease from leaving the grease trap and moving further downstream where it can cause blockage problems. E. Solids in the wastewater that do not float will be deposited on the bottom of the grease trap and will need to be removed during routine grease trap cleaning. F. Oil and grease floats on the water surface and accumulates behind the baffles. The oil and grease will be removed during routine grease trap cleaning. G. Air relief is provided to maintain proper air circulation within the grease trap. H. Some grease traps have a sample point at the outlet end of the trap to sample the quality of the grease trap . I. A cleanout is provided at the outlet or just downstream of the outlet to provide access into the pipe to remove any blockages. J. The water exits the grease trap through the outlet pipe and continues on to the grease interceptor or to the sanitary sewer system.

What is a grease interceptor and how does it work?

An interceptor is a vault with a minimum capacity of 750 gallons that is located on the exterior of the building. The vault includes a minimum of two compartments, and flow between each compartment is through a 90· fitting designed for grease retention. The capacity of the interceptor provides adequate residence time so that the wastewater has time to cool, allowing any remaining grease not collected by the traps time to congeal and rise to the surface where it accumulates until the interceptor is cleaned. Grease Interceptor

A. Flow from under sink grease traps or directly from fixtures enters the grease interceptor. The State of Georgia Plumbing Code requires that all flow entering the interceptor must enter through the inlet pipe. B. An approved flow control or restricting device is installed to restrict the flow to the grease interceptor to the rated capacity of the interceptor. C. An air intake valve allows air into the open space of the grease interceptor to prevent siphonage and back-pressure. D. Oil and grease floats on the water surface and accumulates behind the grease retaining fittings and the wall separating the compartments. The oil and grease will be removed during routine grease interceptor cleaning. E. Solids in the wastewater that do not float will be deposited on the bottom of the grease interceptor and will need to be removed during routine grease interceptor cleaning. F. Grease retaining fittings extend down into the water to within 12 inches of the bottom of the interceptor. Because grease floats, it generally does not enter the fitting and is not carried into the next compartment. The fittings also extend above the water surface to provide air relief. G. Some interceptors have a sample box so that inspectors or employees of the establishment can periodically take effluent samples. Having a sample box is recommended by the State of Georgia Plumbing Code but not required. H. Flow exits the interceptor through the outlet pipe and continues on to the sanitary sewer system.

Do I need a grease trap or interceptor?

Any establishment that introduces grease or oil into the drainage and sewage system in quantities large enough to cause line blockages or hinder sewage treatment is required to install a grease trap or interceptor. Interceptors are usually required at restaurants and large commercial establishments such as hotels, hospitals, factories, food store, butcher shops or school kitchens. Under the sink grease traps may also be required

. Can you recommend a maintenance schedule?

All grease interceptors should be cleaned at least four times each year. Some establishments will find it necessary to clean their interceptors once a month. Grease traps should be cleaned at least once a week. Some need to be cleaned daily. If the establishment has to clean it too often, the owner should consider installing a larger trap or interceptor.

Is the grease trap I have adequate?

The State of Georgia Plumbing Code requires that no grease trap have a capacity less than 20 gallons per minute (gpm) or more than 55 gpm. The size of the trap depends upon the number of fixtures connected to it. The following table provides criteria for sizing grease traps:

Sizing Requirements

Required Grease retention Total number of fixtures connected rate of flow, capacity, lbs gpm 1 35 70 2 50 100 3 75 150 4 100 200

The size will also depend largely upon the maintenance schedule. If a grease trap or interceptor is not maintained regularly it will not provide the necessary grease removal. The establishment should work out a specific cleaning schedule that is right for the establishment. All grease traps need to have the grease cleaned out periodically. Running extremely hot water down the drain only moves the problem down stream. It does not go away. Catch the grease at the source! This is the most economical means to reduce all costs.

What if I don’t have a grease trap?

If the establishment uses grease and oil in food preparation, it must have a grease trap or grease interceptor. An approved grease trap or interceptor shall be installed according to the State of Georgia Plumbing Code. All administrative authorities prohibit the discharge of materials that can solidify and create blockages in the wastewater treatment collection system or treatment plants. The Health Department and Utilities Department makes periodic inspections to see that no health problems exist due to improperly maintained grease interceptors. These rules will be enforced if a problem exists.

How can I get in compliance?

The establishment should contact The City of Augusta’s Utilities Department FOG Section. The establishment will be asked to purchase a permit for the grease trap from the Licensing and Inspections Department. This will enable the proper jurisdiction to assist the establishment in cleaning schedules and advise them of a problem showing up in the wastewater collection system. A grease interceptor permit is required regardless of whether the establishment has an existing trap or is installing a new one.

What are the criteria for inspecting grease traps?

All food service establishments suspected of causing problems to the collection system or treatment facilities will be inspected. Augusta uses the following criteria to inspect grease traps:

Percent of Trap Filled Trap Condition 25 Good 25 – 50 Fair >50 Poor

If the trap is in FAIR condition, the establishment should be advised to keep an eye on the maintenance schedule. The cleaning frequency may need to be increased. If the trap is in POOR condition, the establishment should be issued a compliance order to have it cleaned immediately. The establishment should then be required to contact the issuing authority within 30 days to verify that the grease interceptor has been properly cleaned.

The Bottom Line

Many businesses find that taking steps to prevent FOG materials from entering the sewer system saves money.

• Keeping FOG out of your drains will reduce the likelihood of grease- related plumbing problems. • Fats, oil, and grease can often be recycled, reducing garbage costs. • Establishments that cause excess sewer line maintenance due to FOG will be billed if Augusta Utilities Department’ FOG Section can trace the problem source to the establishment.

How to keep FOG out of the Sewer System

1. Post “No Grease” signs above sinks and in front of dishwashers. Frequent reminders can help educate employees about the importance of keeping FOG out of sinks and drains. 2. Dry wipe pots, pans, and dishes. Get as much oil and grease as possible off the cookware before it hits the water. Send it to the trash for disposal in the solid waste system. 3. Recycle waste cooking oil and other food wastes. Use a waste hauler that will collect and recycle used cooking oil and grease. 4. Use lower water temperatures. Water over 140 degrees will dissolve grease, sending it down the drain in wastewater. Inevitably, this grease will congeal- either in your pipes or in the public sewer system. 5. Use a three-sink dishwashing system. Design a series of sinks for washing, rinsing, and sanitizing with a 5-10 ppm bleach solution. This system allows you to use water temperatures below 140 degrees, lowering you water heating cost, and better controlling the amount of FOG and food wastes that are washed down the drain. 6. Install and properly maintain grease traps and interceptors. Some rules for maintenance are: o Clean under sink grease traps weekly. If grease traps are more than 50 percent full after one week, increase how frequently you clean the trap. You also may want to consider ways to reduce the amount of FOG reaching the sink drain. o Have interceptors cleaned at least 4 times per year. It may be necessary to have interceptors cleaned more often. If more frequent cleanings are needed, consider installing a better trap or an interceptor with larger capacity or using other techniques to keep FOG out of the drain. o Make sure maintenance is done correctly. At least one employee in each facility should be knowledgeable about cleaning procedures for traps and interceptors. That employee should observe maintenance contractors, haulers, and recyclers to make sure all procedures are carried out fully and effectively. 7. Cover any grease and oil storage containers kept outdoors. Open containers can collect rainwater and overflow, sending grease and oil into the storm water system and ultimately polluting local waterways. 8. Keep grease dumpsters and storage containers an adequate distance from storm drains. The farther away you keep these units from a catch basin, the more time there will be for someone to clean up a spill or leak before it reaches the sewer system.

9. Use absorbent pads inside storm drains to catch FOG that may leak into the catch basins. If grease dumpsters or containers are within 20 feet of the catch basin, or you detect signs of FOG near the basin, line the basin with an absorbent cloth or pad. Do not use kitty liter to absorb grease or oil. This can be washed into the sewer system. Use absorbent cloths to clean up any spills or leaks. 10. Keep kitchen exhaust filters clean. Grease and oil escaping through the exhaust system can accumulate on the roof, ultimately getting washed into the storm sewers. Establish a routine schedule and record- keeping system for cleaning the exhaust filters. Make sure wastewater from washing is routed into the interceptor, where oil and grease can be collected before it reaches the sewer. 11. Be cautious about cleaning. Do not conduct outside cleaning activities where wastes can flow into storm drains. 12. Don’t throw wastewater down storm drains. Train employees and contractors to dispose of wastewater appropriately. Water used for mopping, for carpet cleaning, and for washing hood filters should be disposed of through the sanitary sewer system-never into storm drains. To protect the municipal treatment system, limit cleaning chemicals and use the least hazardous products available.