Section 3 - Drain Details

Revision Date General Notes SD-000 NOV 2019 General Notes SD-001 NOV 2019 Catch Basin Type 1 SD-010 NOV 2019 Catch Basin Type 1L SD-020 NOV 2019 Catch Basin Type 2 SD-040 NOV 2019 Gutter Transition Section SD-050 NOV 2019 Inlet SD-060 NOV 2019 Combination Inlet SD-070 JUN 2021 Catch Basin Single Flow or Single Direction Vaned Grate SD-110 NOV 2019 Catch Basin Vaned Grate Bi- Directional SD-112 NOV 2019 State Grate Base SD-116 NOV 2019 State Grate Frame Unit SD-117 NOV 2019 State Grate SD-118 NOV 2019 Inlet SD-120 NOV 2019 SD-130 NOV 2019 23” x 10” Manhole Frame SD-150 NOV 2019 23” x 6” Manhole Frame SD-160 NOV 2019 24-¾” Diameter Storm SD-170 NOV 2019 Manhole Slope Protector SD-180 NOV 2019 Connection for Dissimilar SD-220 NOV 2019 Storm Water SD-240 NOV 2019

NOV 2019

Storm Drain Notes

1. All public storm systems shall be constructed in accordance with the latest edition of the Washington State Department of Transportation Standard Specifications for , , and Municipal Construction and the of Longview Standard Plans and Specifications. 2. All public storm drainage system construction is subject to inspection and approval by the City Department of Public Works. The Contractor shall notify the City a minimum of two full business days prior to the start of construction. 3. The Contractor shall be responsible for determining the location of all underground utilities prior to the start of construction/excavation and shall notify the engineer of any potential conflicts. The Contractor is required to contact the Northwest Utility Notification Center a minimum of two full business days prior to the start of construction and/or any excavation at 811 or www.callbeforeyoudig.org. 4. Tracer wire shall be installed with all non-conductive pipes in one continuous strand. Tracer wire shall be minimum #12 AWG steel reinforced wire. The insulation color shall be green and its material shall be a minimum 30 mil composed of high density polyethylene (HDPE) or high molecular weight polyethylene (HMWPE). Secure the wire on the pipe with tape every 8-10 feet as needed to keep the wire straight and on top of the pipe. Install a green warning tape 12-18 inches above the pipe in the same orientation to the installed pipe. See SS-260 for locator box detail and requirements. Continuity testing of tracer wire is required. 5. To protect flow control and quality treatment facilities from sedimentation, they shall be connected to the storm conveyance system only after all site work, road construction, utility work and landscaping are in place in all areas above and upstream of the facility. 6. The existing storm sewer system shall stay isolated from the new system via mechanical plug until the new system is cleaned, tested, video inspected and approved for use. 7. Storm drain pipe shall be cleaned by use of high pressure nozzle and prior to video inspection. Video inspection shall be performed in an organized and sequential order as approved by the City Engineer. Video recordings shall be submitted on a CD, DVD, flash drive or similar media approved and accepted by the City. If debris is found to be in the lines, further cleaning will be required prior to acceptance.

STORM DRAIN GENERAL NOTES

SD - 000 K.H. NOV 2019 Storm Drain Construction Notes - Page 2

8. All storm drain pipe shall be tested for deflection. Storm sewer constructed with flexible pipe shall be tested for deflection in accordance with section 7-17.3(2)G of the Standard Specifications. All pipe shall be constructed in accordance with section 7-04. 9. Deflections in flexible pipe shall not exceed 0.03 feet. 10. Pressure testing of all storm main lines is required in accordance with the Standard Specifications Section 7-04. 11. Vacuum testing all new storm is required in accordance with ASTM Designation C 1244-93. 12. As-built drawings shall be submitted and approved prior to project acceptance. 13. Pipe bedding shall be per standard plan SS-240. 14. When the material at the bottom of an excavation is not suitable enough to support the structure, the contractor shall excavate below grade and replace the unsuitable material with gravel backfill. 15. Geosynthetic materials shall meet the requirements of WSDOT Standard Specifications 9-33.Geosynthetic materials shall be installed with all catch basins and manholes and shall be placed on undisturbed subgrade and below fill materials. 16. Unless otherwise approved a minimum cover of 24” is required above the top of the pipe to the top of the finish grade. There shall be a minimum of 12” separation from the top of the pipe to the bottom of the roadway section (e.g. laterals from catch basins). A minimum cover of 12” may be used for HDPE pipe diameters 18” or less in conditions not to exceed incidental H-20 loading, unless otherwise approved by the City Engineer. Minimum cover is measured from the top of the pipe to the bottom of flexible pavement or to top of rigid pavement. This standard assumes the pipe is installed in accordance with manufacture's recommendations and may not address the cover needed to prevent flotation. In every case where at least 12” minimum cover cannot be obtained, ductile iron or box shall be used as approved by the City. 17. All storm sewer pipe which crosses water pipe shall be in accordance with Standard Plans W-290, W-295 or W-300 as applicable to the situation and approved by the Engineer.

STORM DRAIN GENERAL NOTES

SD - 001 K.H. NOV 2019 FLOW NOTES 1. As acceptable alternatives to the shown in the PRECAST BASE SECTION, fibers (placed according to the Standard Specifications), or DI wire mesh having a minimum area of 0.12 square inches per foot shall be used with the minimum required rebar shown in the ALTERNATIVE PRECAST BASE SECTION. Wire mesh shall not be placed in the knockouts.

FOUNDRY NAME 2. The knockout diameter shall not be greater than 20". Knockouts shall have a wall thickness of 2" minimum to 2.5" maximum. Provide a 1.5"

FLOW minimum gap between the knockout wall and the outside of the pipe. After the pipe is installed, fill the gap with joint mortar in accordance GRATE with Standard Specification 9-04.3. 3. The maximum depth from the finished grade to the lowest pipe invert shall be 5'. 4. The frame and grate may be installed with the flange down, or integrally cast into the adjustment section with flange up. 30" 5. The Precast Base Section may have a rounded floor, and the walls may 34" 20" be sloped at a rate of 1:24 or steeper. 24" 6. The opening shall be measured at the top of the Precast Base Section. 5" 7. All pickup holes shall be grouted full after the basin has been placed.

NOV 2019 5"

SD -010 8. Standard curb inlet bases shall be precast . Construction of cast-in-place bases, including slip-form method, are not permitted without 2", 4", 6", 12", OR 24" approval from the engineer. 9. Pipe ends shall be flush with the inner wall or 1" maximum intrusion. 10. Masonry, cinder blocks, or similiar materials may be used to adjust the risers to grade prior to grouting. Wood or other non-durable materials CATCH BASIN TYPE1 ONE #3 BAR FOR 6" TALL shall not be used for this purpose. INCREMENT (SPACED EQUALLY) 11. Grouting shall be sufficient to prevent leaks between the precast components RECTANGULAR ADJUSTMENT SECTION of the completed structure & shall be performed inside, between & outside of all risers, joints & pipe penetrations.

(SEE NOTE# 6) 12. Poured in place catch basins may be approved. (submit shop drawing) 22" 26" 13. Use combination inlet where are present unless otherwise approved.

(SEE NOTE 6) 3"

K.H. 4" MIN. (TYP) PIPE ALLOWANCES

#3 BAR 44" MAXIMUM EACH CORNER PIPE MATERIAL INSIDE DIAMETER REINFORCED OR #3 BAR EACH CORNER 12" 18" MIN. PLAIN CONCRETE #3 BAR HOOP 21" MIN. ALL METAL PIPE 15" EACH SIDE CPSSP (STD. SPEC. 9-05.20) 12" #3 BAR HOOP SOLID WALL PVC (STD. SPEC. 9-05.12(1)) 15" #3 BAR EACH WAY PROFILE WALL PVC 15" PRECAST BASE SECTION (STD. SPEC. 9-05.12(2)) (SEE NOTE 1) CORRUGATED POLYETHYLENE STORM SEWER PIPE ALTERNATIVE PRECAST BASE SECTION FLOW

DI NOTES PIPE ALLOWANCES 1. As acceptable alternatives to the rebar shown in the PRECAST BASE SECTION, fibers (placed according to the Standard Specifications), or wire mesh having a minimum area of 0.12 square inches per foot, shall MAXIMUM be used with the minimum required rebar shown in the ALTERNATIVE FOUNDRY NAME PIPE MATERIAL INSIDE PRECAST BASE SECTION. Wire mesh shall not be placed in the DIAMETER knockouts. FLOW REINFORCED OR 18" 2. The knockout shall not be greater than 26", in any direction. Knockouts GRATE PLAIN CONCRETE shall have a wall thickness of 2" minimum to 2.5" maximum. Provide a 1.5" minimum gap between the knockout wall and the outside of the pipe.

FLOW FLOW ALL METAL PIPE 21" After the pipe is installed, fill the gap with joint mortar in accordance with Standard Specification 9-04.3. CPSSP DI (STD. SPEC. 9-05.20) 18" 3. The maximum depth from the finished grade to the lowest pipe invert shall be 5'. SOLID WALL PVC 21" (STD. SPEC. 9-05.12(1)) 4. The frame and grate may be installed with the flange down or integrally cast into the adjustment section with flange up.

FOUNDRY NAME PROFILE WALL PVC 21" (STD. SPEC. 9-05.12(2)) 5. The Precast Base Section may have a rounded floor, and the walls may FLOW FLOW CORRUGATED POLYETHYLENE be sloped at a rate of 1:24 or steeper. STORM SEWER PIPE BI-DIRECTIONAL GRATE 6. The opening shall be measured at the top of the Precast Base Section. NOV 2019 USE BI-DIRECTIONAL GRATE AT LOW POINTS 7. All pickup holes shall be grouted full after the basin has been placed. SD -020 8. Poured in place catch basins may be approved. (submit shop drawing)

30" 9. Use combination inlet where curbs are present unless otherwise approved. 34" 20" 24" CATCH BASIN TYPE1L

5" 5"

2", 4", 6", 12", OR 24"

4" MIN. (TYP) #3 BAR EACH CORNER (SEE NOTE 28" 6) #3 BAR HOOP 18" MIN. ONE #3 BAR FOR EACH 6" HEIGHT 32" INCREMENT, SPACED EQUALLY (SEE NOTE 6) RECTANGULAR ADJUSTMENT SECTION K.H. 2"

36" 40" 20" 24" 8" 8" #3 BAR 44" EACH CORNER #3 BAR 6" EACH SIDE

#3 BAR TWO #3 BAR 4" EACH WAY

HOOPS 16" MIN. (SEE NOTE 1) REDUCING SECTION PRECAST BASE SECTION ALTERNATIVE PRECAST BASE SECTION NOTES 1. No steps are required when height is 4' or less. 2. The bottom of the precast catch basin may be sloped to facilitate cleaning. 3. The rectangular frame and grate may be installed with the flange up or down. The frame may be cast into the adjustment section. 4. Knockouts shall have a wall thickness of 2" minimum to 2.5" maximum. Provide a 1.5" minimum gap between the knockout wall and the outside of the pipe. After the pipe is installed, fill the gap with joint mortar in accordance with Standard Specification 9-04.3.

CATCH BASIN FRAME AND VANED GRATE OR MANHOLE RING AND COVER 5. All risers or adjustment sections shall be the same inside dimension as the base.

CATCH BASIN DIMENSIONS 28" MAX. RECTANGULAR ADJUSTMENT SECTION CATCH MIN. MIN. MAXIMUM MINIMUM OR CIRCULAR ADJUSTMENT SECTION

2" MIN. DISTANCE

16" MAX. BASIN WALL BASE KNOCKOUT

NOV 2019 BETWEEN DIAMETER THICKNESS THICKNESS SIZE KNOCKOUTS SD -040 FLAT SLAB TOP 48" 4" 6" 36" 8" 54" 4.5" 8" 42" 8" 60" 5" 8" 48" 8" SEE TABLE

CATCH BASIN TYPE2 72" 6" 8" 60" 12" MORTAR (TYP.) 84" 8" 12" 72" 12" 96" 8" 12" 84" 12" STEPS OR 120" 10" 12" 96" 12" LADDER 144" 12" 12" 108" 12" 15' - 0" MAX. (FOR MAINTENANCE)

PIPE ALLOWANCES 12" (TYP.) PIPE MATERIAL WITH MAXIMUM INSIDE DIAMETER CATCH SOLID PROFILE K.H. ALL REINFORCING STEEL (TYP.) BASIN CONCRETE CPSSP WALL WALL METAL GRAVEL BACKFILL FOR DIAMETER 1 PVC 2 PVC 3 1" MIN. 2.5" MAX. 24" MIN. "O" RING 12" MAX. 12" PIPE ZONE BEDDING 48" 24" 30" 24" 30" 30" 12" COMPACTED TO 95% 54" 30" 36" 30" 36" 36" 6" 60" 36" 42" 36" 42" 42" SEPARATE BASE INTEGRAL BASE PRECAST PRECAST WITH RISER 72" 42" 54" 42" 48" 48" (48" - 72" ONLY) 84" 54" 60" 54" 48" 48" 96" 60" 72" 60" 48" 48" 120" 66" 84" 60" 48" 48" 144" 78" 96" 60" 48" 48" 1 Corrugated Polyethylene Storm Sewer Pipe (Standard Specification 9-05.20) 2 (Standard Specification 9-05.12(1)) 3 (Standard Specification 9-05.12(2)) PRECAST TOP SLAB SHOWN WITH TOP-FACE OF CURB GUTTER TRANSITION FLARE. NORMAL GUTTER MATCH THE TOP FRONT EDGE OF TOP-FACE OF GUTTER FLOW LINE THE FRAME AND THE TOP FRONT EDGE OF THE TOP SLAB TO THE NORMAL PAVEMENT GRADE.

1 2" DEPRESSED GUTTER NOV 2019 FLOW LINE SD -050 GUTTER TRANSITIONSECTION

TOP-FACE OF CURB MATCH NORMAL PAVEMENT NORMAL GUTTER GRADE AT FRONT EDGE OF FLOW LINE

GUTTER FLARE AND CATCH BASIN TOP SLAB FLOW

3' DI

FLARE GUTTER IN FOUNDRY NAME TRANSITION SECTION FLOW

5" 5"

TOP-FACE OF GUTTER K.H. TOP UNIT 24" X 3 1/2" DUCTILE IRON MANHOLE FRAME AND COVER

SAFETY BAR/DEBRIS GUARD 5/8" MINIMUM DIAMETER STEEL ROD

A TOP OF CURB 32" 36"

6" STORM 9 1/2"

25" x 6" DROP-IN OPENING

1 1 1 3 2" x 2 2" x 4" x 36" GALVANIZED ANGLE A

MATCH NORMAL EDGE OF PAVEMENT

ISOMETRIC VIEW

CATCH BASIN COVER SEE SD-170

HAND FORM DROP-IN OPENING

6" 9.5" 3.5" 8"

32"

CROSS SECTION A-A NOTES: TO BE USED WITH PRECAST INLET BASE CURB INLET

SD - 060 K.H. NOV 2019 NOTES 1. This inlet requires the precast catch basin unit to be rotated 90 degrees so ~ 5 1/2" that the narrow side is parallel to the curb line. When calculating offsets 1" R. LEVEL from curb to CL of the precast catch basin, please note that the CL of the HOOD grate is not the CL of the precast catch basin. See Section A. 1 1" MIN. 6 2. The dimensions of the frame and hood may vary slightly among different 1/2" MIN. OPENING HEIGHT manufacturers. The frame may have cast features intended to support a 0 TO 1" APPROX. 1/2 OF 4" MIN. CLEARANCE OPENING HEIGHT debris guard. Hood units may be mounted inside or outside of the frame. The methods for fastening the safety bar / debris guard rod to the hood TOP OF GRATE may vary. The hood may include casting lugs. The top of the hood may be SEE NOTE 3 cast with a pattern. FRAME 3. Attach the hood to the frame with two 3/4" × 2" hex head bolts, nuts, and oversize washers. The washers shall have diameters adequate to ensure full bearing across the slots. 4. Bolt-down capability is required on all frames, grates and covers. SAFETY BAR / DEBRIS GUARD 5. Only ductile iron vaned Grates shall be used with appropriate flow 5/8" MINIMUM DIAMETER STEEL directions selected (see SD-110 and SD-112). ROD (SEE NOTE 2) JUNE 2021 DETAIL SECTION A 6. This plan is intended to show the installation details of a manufactured

SD-070 product. This plan is not intended to show the specific details necessary to fabricate the castings depicted in this drawing. 7. Contractor shall ensure compatibility of catch basin, riser, combination inlet and hood. Riser shall not impede hood adjustment, if such adjustment is required to match top of curb. COMBINATION INLET

CURB OR CURB AND GUTTER

MATCH TOP OF HOOD ` CATCH BASIN ~ TO TOP OF CURB (TYP.) SEE NOTE 1 ` HOOD SAFETY BAR / DEBRIS GUARD 29" MIN. 7" 3" FACE OF GRATE ~ CURB SEE NOTE 1 1" MIN. 20 1/4" 20" × 24" VANED GRATE (TYP.) FRAME

RISER ~ SEE NOTE 7

SEE NOTE 4

K.H. CATCH BASIN TYPE 1

(TYP.) (TYP.) SHOWN 34" (WIDE SIDE)

1 1/2" MIN. SEE NOTE 2 (TYP.) CATCH BASIN TYPE 1 24 1/4" HOLE OR SLOT FOR 29" MIN. 40" (WIDE SIDE) ATTACHING HOOD (TYP.) CATCH BASIN TYPE 1L

34" 30"

FRAME DETAIL SECTION A COMBINATION INLET FRAME, HOOD, AND VANED GRATE NOTES 1. Bolt-down capability is required on all frames, grates, and covers.

2. Grate to be stamped "DUMP NO POLLUTANTS-OUTFALL TO STREAM" 3. Material is Ductile Iron; ASTM A536 Grade 80-55-06

1" FLOW 3" SLOT ~ SEE DETAIL 5" CATCH BASIN SINGLEFLOWOR SINGLEDIRECTIONVANED GRATE AND NOTE 1 DI 5" A 5" NOV 2019 SD -110 20" 5" 1/2" 5" 3/4"

FOUNDRY NAME 1 1/4" 5" 3"

FLOW 5/8"

B SECTION B

24" K.H. 7 OR 8 EQUAL SPACES

DIRECTION OF FLOW 1 5/8" MAX.

SECTION A

NOV 2019 NOV

K.H. SD - 112 - SD CATCH BASIN VANED GRATE BI-DIRECTIONAL GRATE VANED BASIN CATCH

1 5/8" MAX. A

FOUNDRY NAME 4 EQUALSPACES SECTION 3. 2. 1. NOTES Material isDuctileIron:ASTMA536Grade80-55-06. Bolt-down capabilityisrequiredonallframes,grates,andcovers. Grate tobestamped"DUMPNOPOLLUTANTS-OUTFALLTOSTREAM". TOP 24" A 4 EQUALSPACES B SLOT ~SEEDETAIL AND NOTE1

20"

5" 5" 5" 3" SECTION 3" 5" 5" 5" 1" B ISOMETRIC BOLT-DOWN SLOTDETAIL SEE NOTE1 1 1/4"

5/8" 3/4"

1/2" UNIT "H" B UNITS "J" & "K" AS REQUIRED 4" MIN. 5 4" MIN. 4" MIN. 4" MIN. 5 6 1/2" 1/2" 2" A 2" 2" 26" 26" 2 10' - 6" MAX. 10' - 6" MAX. 2 3 (TYP.) 2 54" 1/2" 1/2" PICKUP HOLE

1 TOP VIEW 2 6 9" 6 5 1/2" MIN. 5 1/2" MIN. 9" 2 1/2"

NOV 2019 2 4 5 1/2" MIN. 5 1/2" MIN.

SD -116 5 1/2" MIN. 5 1/2" MIN. 2 1/2" 4 SPACES @ 3 SPACES @ 37" 54" APPROX. 12 1/2" APPROX. 11"

37" UNIT "H" 54" STATE GRATE BASE SECTION A ONE PIECE BASE SECTION B ONE PIECE BASE UNITS "J" & "K" 4" MIN. 4" MIN. 4" MIN. 4" MIN. 13 AS REQUIRED 13 1/2" 1/2" 2" 2" 2" 2" 5 PIPE ALLOWANCES 10 26" 10 26"

36" 36" 10 10 MAXIMUM PIPE MATERIAL INSIDE

1/2" DIAMETER 1/2" 2" 2" REINFORCED OR 18" K.H. PLAIN CONCRETE 13 5" 5 5" 5" 13 5" 10' - 6" MAX. 10' - 6" MAX. MIN. MIN. MIN. MIN. ALL METAL PIPE 21"

4" 4" 4" 4" CPSSP * 18" MIN. 12 MIN. MIN. 13 MIN. (STD. SPEC. 9-05.20) SOLID WALL PVC 21"

2" (STD. SPEC. 9-05.12(1)) 13 11 11 PROFILE WALL PVC 21"

24" (STD. SPEC. 9-05.12(2))

4 5 1/2" MIN. 5 1/2" MIN. 10"

2 1/2" CORRUGATED POLYETHYLENE * STORM SEWER PIPE

4 SPACES @ 26" 5 1/2" MIN. 5 1/2" MIN.5 1/2" MIN. 5 1/2" MIN. APPROX. 12 1/2" 2" 2" 2" 3 SPACES @ 2" FOR FRAME SEE SD-117 FOR GRATE SEE SD-118 54" APPROX. 11" xx - SEE CHART ON SD-117 SECTION A TWO PIECE BASE 37" SECTION B TWO PIECE BASE NOTES 1. The Steel Angles shall be set so that each bearing bar of prefabricated grate shall have full 8 bearing on both ends. The finished top of concrete shall be even with the grate surface. 54" 2" 2. Top of inlet grate shall be placed at ground level to present an unobstructed ditch or median 6" section. 2" 5" SECTION C UNIT "J" 3. All exposed concrete edges shall be finished with a 1/2" radius. 4. Pipes may enter through the knockouts on any side at any reasonable angle, provided the C outside of the pipe can be contained between two opposite walls. 37" 5. The flow line of the outlet pipe shall be 18" minimum above the inside bottom of the inlet structure.

9 2 1/2" (TYP.) 8 9 6. The grade line of the top inside of any inlet pipe shall enter no lower than the grade line of the 1 1/2" 5" top inside of the outlet pipe.

5" 5" 12" 7. Unit "H" and optional extension units "J" and "K" shall be grouted in place to the satisfaction of UNITS "J" & "K" the Engineer. 8. SECTION UNIT "K" All pickup holes shall be grouted full after the basin has been placed.

1 1/2" C 9. See contract for type of grate specified. See WSDOT Standard Plan for grate details.

NOV 2019 54"

SD -117 2" 42" 2" 6 1/4" GRATE 6 1/4" STATE GRATE FRAME UNIT GRATE ~ SEE NOTE 9

D 2 1/2" 8" 37" 12" E 12" 8" 1/4" x 5 1/2" x 1 1/2" 24 1/2"

STEEL ANGLES 2" 7" (TYP.) 7 (3 BOTH ENDS) F 2" SECTION D UNIT "H" 7" 3 3/8" 47 1/4" 3 3/8" 7 6 1/4"

SECTION E UNIT "H" UNIT "H"

6" K.H.

BENDING DIAGRAM 3" BAR LIST (ALL DIMENSIONS ARE OUT TO OUT) 1/4 MARK LOCATION QTY. SIZE LENGTH DESCRIPTION 1

1 BOTTOM SLAB AND SIDE WALL 3 5' - 9" 2 GRATE 1 1/2" 2 BOTTOM SLAB AND SIDE WALL 2 12' - 5" 3 4' - 1 1/2" 11 1'- 6" 1' - 6" 1' - 7 1/2" 1' - 7 1/2" 10" 3 3 BOTTOM SLAB AND SIDE WALL 7' - 2" 2 2 1 12 12 11 4" × 3" × 3/8"

4 BOTTOM SLAB AND SIDE WALL 2 2' - 9" STRAIGHT STEEL ANGLE 4" 2' - 7 1/2" 5 WALL 4 9' - 1" HOOP 1 2' - 9" 6 4' - 2" 6 14' - 6" HOOP 2 4' - 2" SIDE WALL 3 5 2" 7 4' - 2" 3 3 4' - 2" 7 UNIT H 2 14' - 2" HOOP 4' - 1" 11 4' - 2" 8 5 1/2" × 1 1/2" × 1/4" 4' - 2" 2" 8 UNIT J 2 14' - 2" HOOP 12 2' - 9" 13 STEEL ANGLES 8 UNIT K 3 14' - 2" HOOP 4" (3 BOTH ENDS) 9 UNIT K 4 0' - 9" STRAIGHT 7 1" 10 SIDE WALL 8 2' - 8" STRAIGHT 6

11 BOTTOM SLAB AND SIDE WALL 4 7' - 5" 7 4" 2' - 9" 2' - 7" 2' - 8" 2' - 9" F BOTTOM SLAB AND SIDE WALL 8 DETAIL 12 3 6' - 0" 6 7 8 13 13 FOR BASE SEE SD-116 13 SIDE WALL 4 14' - 6" HOOP FOR GRATE SEE SD-118 46 3/4" 46 3/4"

1 3/8" ELEVEN EQUAL SPACES 1 3/8" 3 1/2" × 3/8" STEEL 1 3/8" ELEVEN EQUAL SPACES 1 3/8" 3 1/2" × 3/8" STEEL PLATE (TYP.) PLATE (BOTH SIDES) 3/16" 3/16"

3 1/2" × 3/4" STEEL PLATES 24 1/8" 24 1/8" NOV 2019 TEN EQUAL SPACES FIVE EQUAL SPACES SD -118

TOP CROSS BARS ~ 3/8" ROUND, OR END TOP CROSS BARS ~ 3/8" ROUND, OR END 3/16" RECTANGULAR OR HEXAGONAL 3/16" RECTANGULAR OR HEXAGONAL BAR OF EQUIVALENT AREA. BAR OF EQUIVALENT AREA.

SIDE SIDE STATE GRATE

GRATE "A" GRATE "B" (APPROXIMATE WEIGHT 215 LBS) (APPROXIMATE WEIGHT 215 LBS)

FOR BASE SEE SD-116 FOR FRAME SEE SD-117 K.H.

ISOMETRIC ISOMETRIC 2' 4-3/4" 1'-4 1/2"

30°

3/4" 1/2"X2-1/2" SQ. EDGE FLAT BAR 2' 8-1/2" VARIES 3"X2-1/2"X3/8" ANGLE 6" 2' 3" NOV 2019 6" 2' 3-3/8" SD -120 6" 24" FRAME PLAN 3' 3-3/8" 36" 6" MIN. 6" 6"

SECTION A-A SECTION B-B 2-3/8" 3"

B 5/8"X3" BOLT DITCH INLET 5/8" X 2 2-1/2" SQ. 2-1/2" 2 EACH END 2' 3" EDGE FLAT BAR 4-ANCHORS 5/8" X 2-1/2" X 30" A A 1/4" SQ. EDGE FLAT BAR FRAME SECTION 2' 8" K.H.

PLAN PLAN B NOTE: SPACING * 1. MATERIALS SHALL MEET STANDARD SPECIFICATION 7-05.2. 3" O.C. 2-1/2" 5/8" 5/8" 2. CATCH BASIN, FRAME & GRATES SHALL MEET H20 LOADING. 3. INSIDE FRAME DIMENSIONS: 2' 3-3/8" X 2' 8-1/2". 3/16" 3/16" 4. GROUTING SHALL BE SUFFICIENT TO PREVENT LEAKS BETWEEN THE PRECAST COMPONENTS OF THE COMPLETED STRUCTURE & SHALL BE PERFORMED INSIDE, BETWEEN & OUTSIDE OF ALL RISERS, JOINTS & PIPE PENETRATIONS. 5. ALL RISERS OR ADJUSTMENT SECTIONS SHALL BE THE SAME INSIDE DIMENSIONS AS BASE SECTIONS. 3 GRATE SECTION 6. 8" CROSS BARS SHALL BE FLUSH WITH THE GRATE SURFACE AND MAY BE FILLET WELDED, TYPE 1 RESISTANCE WELDED OR ELECTROFORGED TO BEARING BARS.

* SPACING OF BARS MAY BE INCREASED WITH APPROVAL OF THE CITY ENGINEER IN HIGH FLOW, HIGH DEBRIS AREAS. #5 BARS AT 6" SPACING

FOR FRAME AND COVER USE FLAT TOP FOR RIM TO INVERT SEE SD-150, 160 & 170 DEPTHS OF 5 FEET OR LESS 7" ONLY

RING AND COVER 8" ADJUSTMENT SECTION 25" 19" MAX. 20"X24" OR 24" DIA. HOLE 24" 2" (TYP.) 2", 4", & 6" PRECAST CONE 18" MIN.

36" MAX. (ECCENTRIC UNLESS OTHERWISE SPECIFIED)

8" 48", 54", OR 60" FLAT 1" MIN. 1 SLAB TOP 2-2" MAX. 48", 54", OR 60" ALL JOINTS SHALL BE NEOPRENE GASKETED NOTES: 1. MANHOLES TO BE CONSTRUCTED IN ACCORDANCE WITH STANDARD SPECIFICATION 7-05 UNLESS OTHERWISE SHOWN ON PLANS OR NOTED IN THE STANDARD NOV 2019 SPECIFICATIONS.

SD -130 2. HANDHOLDS IN ADJUSTMENT SECTION SHALL HAVE 3" MINIMUM CLEARANCE. STEPS IN MANHOLE SHALL HAVE 6" MINIMUM CLEARANCE. SEE STANDARD PLAN SS-140 "MISCELLANEOUS MANHOLE DETAILS." 3. ALL REINFORCED CAST IN PLACE CONCRETE SHALL BE CLASS 4000. ALL PRECAST

STORM DRAINMANHOLE CONCRETE SHALL BE CLASS 4000. STORM DRAIN MANHOLE PRECAST RISER SECTIONS 4. PRECAST BASES SHALL BE FURNISHED WITH CUTOUTS OR KNOCKOUTS. KNOCKOUTS

MAX. HEIGHT = 25' SHALL HAVE A WALL THICKNESS OF 2" MINIMUM. 5. MATING SURFACES OF MANHOLE RINGS AND COVERS SHALL BE FINISHED TO ASSURE NON-ROCKING FIT WITH ANY COVER POSITIONS. 6. ALL BASE REINFORCING STEEL SHALL HAVE A MINIMUM YIELD STRENGTH OF 60,000 PSI & BE PLACED IN THE UPPER HALF OF THE BASE WITH 1" MINIMUM CLEARANCE. 7. FOR DETAILS SHOWING GRADE RING, LADDER, STEPS, HANDHOLDS & TOP SLABS, SEE STANDARD PLAN SS-140 "MISCELLANEOUS DETAILS". 8. GEOTEXTILE SHALL MEET THE REQUIREMENTS OF WSDOT STANDARD SPECIFICATIONS 9-33 FOR UNDERGROUND DRAINAGE, MODERATE SURVIVABILITY. GROUTING SHALL BE SUFFICIENT TO PREVENT LEAKS BETWEEN THE PRECAST COMPONENTS OF THE STEPS TO BE HDPE COMPLETED STRUCTURE & SHALL BE PERFORMED INSIDE, BETWEEN & OUTSIDE OF ALL RISERS, JOINTS & PIPE PENETRATIONS. REINFORCED STEEL (FOR PRECASE BASE AND 9. ALL RISERS OR ADJUSTMENT SECTIONS SHALL BE THE SAME INSIDE DIMENSIONS AS INTERGRAL RISER ONLY) BASE SECTIONS. MORTAR FILL 10. CHANNELED MANHOLES MAY BE REQUIRED FOR HIGH AREAS WHERE NEEDED K.H. 0.15 SQ IN/FT IN EACH DIRECTION FOR 48" DIA. HYDRAULICALLY. 24" FROM FLAT 0.19 SQ IN/FT IN EACH DIRECTION FOR 54" DIA. BTTM TO OUTLET 0.25 SQ IN/FT IN EACH DIRECTION FOR 60" DIA. 12" MAX INVERT PRECAST BASE AND INTERGRAL RISER 12" CRUSHED SURFACE TOP COURSE 6" MIN. COMPACTED DEPTH FOR PRECAST BASES ONLY 95% COMPACTION FOUNDATION AS DIRECTED BY THE ENGINEER MANHOLE DIMENSION TABLE

GEOTEXTILE MINIMUM BASE REINFORCING STEEL 2 48" DIA. - 6" WALL BASE MAXIMUM DISTANCE in /ft. IN EACH DIRECTION 54" DIA. - 8" DIA. THICKNESS THICKNESS KNOCKOUT BETWEEN REINFORCED STEEL (FOR SEPARATE BASE ONLY) SIZE KNOCKOUTS SEPARATE BASE INTEGRAL BASE 60" DIA. - 8" 0.23 SQ IN/FT IN EACH DIRECTION FOR 48" DIA. (NO. 3 BARS 6" C/C) 48" 4" 6" 36" 8" 0.23 0.15 0.19 SQ IN/FT IN EACH DIRECTION FOR 54" DIA. (NO. 4 BARS 12" C/C) 0.25 SQ IN/FT IN EACH DIRECTION FOR 60" DIA. (NO. 4 BARS 12" C/C) 54" 4.5" 8" 42" 8" 0.19 .019

FOR FOUNDATION REQUIREMENTS SEE 60" 5" 8" 48" 8" 0.25 .025 STANDARD DETAIL SD-001 72" 6" 8" 60 12" 0.35 0.24 SECTION 84" 8" 12" 72" 12" 0.39 .029 96" 8" 12" 84" 12" 0.39 0.29 7" ADJUSTABLE RING

A A

DETAIL A

5 (4) 8" BY 4" JACK SCREW 5 WITH 8" HEX HEAD

TOP VIEW

31" 25" 7" 23 3/4"

8 1/2" 23"

2 7/8" MAX LIFT (4" SCREW) (SHORTER SCREWS AVAILABLE)

5 (4) 8" SLOT NUT INSERT SECTION A-A

NOTES: 1. CASTING ASSEMBLY TO BE H20 LOAD RATING OR AS APPROVED BY CITY ENGINEER. 2. SCREWS SHALL BE -PLATED, MILD STEEL CONFORMING TO ASTM A 1018. 3. NUTS SHALL BE ZINC ALLOY CONFORMING TO ASTM C41A. 4. GAPS SHALL BE FILLED WITH NON-SHRINK GROUT PER THE MOST CURRENT WSDOT STD. SPECIFICATION 9-20.3(2). 5. MANHOLE RING SHALL BE SHIMLESS ADJUST-TO-GRADE FOLLOWING MANUFACTURER'S REQUIREMENTS. ADJUST SCREWS TO MEET FINISHED GRADE. 6. SEE LONGVIEW STD. PLAN SD-170 FOR MANHOLE COVERS.

23" x 8 1/2" MANHOLE FRAME

SD - 150 K.H. FEB 2021 3" ADJUSTABLE RING

5 (4) 8" BY 4" JACK SCREW 5 WITH 8" HEX HEAD TOP VIEW

31" 25" 7/8" 24 47/64"

3" 6"

23 1/4" 2 1/8"

2"

5 (4) 8" SLOT NUT INSERT SECTION A-A

NOTES: 1. CASTING ASSEMBLY TO BE H20 LOAD RATING OR AS APPROVED BY CITY ENGINEER. 2. SCREWS SHALL BE ZINC-PLATED, MILD STEEL CONFORMING TO ASTM A 1018. 3. NUTS SHALL BE ZINC ALLOY CONFORMING TO ASTM C41A. 4. GAPS SHALL BE FILLED WITH NON-SHRINK GROUT PER THE MOST CURRENT WSDOT STD. SPECIFICATION 9-20.3(2). 5. MANHOLE RING SHALL BE SHIMLESS ADJUST-TO-GRADE FOLLOWING MANUFACTURER'S REQUIREMENTS. ADJUST SCREWS TO MEET FINISHED GRADE. 6. SEE LONGVIEW STD. PLAN SD-170 FOR MANHOLE COVERS. 7. USE OF THIS SIZE FRAME ONLY PERMISSIBLE WITH CITY ENGINEERS APPROVAL. SD-150 TO BE USED FOR NORMAL CIRCUMSTANCES.

23" x 6" MANHOLE FRAME

SD - 160 K.H. FEB 2021 STORM DRAIN MANHOLES

FOR FRAMES SEE SD-150 & 160

BOTTOM VIEW

24-3/4" 1"

1-1/2" 1" 7/8" SECTION A-A

MACHINE TO A TRUE BEARING ALL AROUND

A STORM

A

NOTES: 1. STORM MANHOLE COVERS SHALL BE STAMPED TOP VIEW "STORM".

2. CAST IRON OR DUCTILE W/ H20 LOAD RATING APPROVED BY CITY ENGINEER.

24 3/4" DIAMETER STORM MANHOLE COVER

SD - 170 K.H. NOV 2019 CL

6" SLOPE VARIES

3' MIN #4 BARS @ 12" EACH WAY A A (WALLS AND SLAB)

2" SLOPE VARIES (MATCH GROUND SLOPE) MANHOLE SLOPEPROTECTOR NOV 2019 8'-0" SD -180 1" MANHOLE SLOPEPROTECTOR H1 - SEE TABLE 6" 1' - 6"

6" #4 BAR HOOP

6" 6' MIN 6"

PLAN SECTION A - A K.H.

NOTE: CONC. STEEL SLOPE H1 (IN.) (CU. YD.) (LB.) ALL REINFORCING STEEL SHALL BE PLACED 2" CLEAR OF NEAREST FACE OF CONCRETE UNLESS SHOWN OR 1 : 1.5 3' - 0" 1.00 88 1 NOTED OTHERWISE. 1 : 2 2' - 4 2" 0.89 75 1 : 3 1' - 9" 0.78 70 1 1 : 4 1' - 5 4" 0.72 63 1 1 : 6 1' - 1 2" 0.66 60

NOV 2019 NOV

K.H. SD - 220 - SD CONNECTION FOR DISSIMILAR CULVERT PIPE CULVERT DISSIMILAR FOR CONNECTION

6" MIN. NOTES: Increase theoutsidediameterofmetalpipetomatch outside Use aflatTypeKCouplingBand.Bandswith dimplesare not allowedfortheinstallationdetailshown.TheCouplingBand optionshall connection isinstalled. concrete pipe,thebellendofpipeshallberemovedbefore the 9-07.7. Installtwowrapsforsize6×W1.4(10Gage) Steel Steel WeldedWireFabricshallbeinaccordancewithStandard Specification Collar optionshallonlybeusedtoextendexistingpipes. Collars maybeusedwithallpipematerialsanddiameters.The Concrete or less. only beusedforextendingexistingpipesthathaveaninside diameter of36" accordance withWSDOTStandardSpecification9-04.4(3). diameter oftheconcretepipebyinstalling12"widerubbergaskets, When aCouplingBandconnectionrequiresattachmenttothe bellendofa Welded WireFabricoronewrapforanyofthefollowingsizes: the largestpipe.TheminimumConcreteCollarwidthshallbe 12".Concrete The ConcreteCollarwidthshallbeonehalfoftheoutsidepipe diameterof Transition Ferncoorapprovedequalmaybeusedincludingconcrete collars thickness asrequired(CouplingBandonly).Therubbergaskets shallbein when connectingtoCMP 6 ×W2.9(6Gage) 6 ×W2.1(8Gage) 4 ×W4.0(4Gage) 4 ×W2.9(6Gage) . COVER QUARRY SPALLS INSTALL WHITE WITH 4 INCHES TOP REFLECTIVE SOIL (TAMP IN PLACE) FLEXIBLE GUARD POST. SEE NOTE 2. AND SEED. TOP OF TOP OF BANK BANK

ARMOR OUTFALL WITH QUARRY SPALLS, MIN. 1.0' THICK. SEE NOTE 1. STORMWATER OUTFALL PIPE

NOV 2019 NORMAL

SD -240 WATER SURFACE

INSTALLATION NOTES: STORMWATER OUTFALL 1.) QUARRY SPALLS PER WSDOT SPEC 9-13.1(5), PLACED A MINIMUM OF ONE FOOT THICK. QUARRY SPALLS SHALL EXTEND TO A MIN. ONE FOOT ABOVE PIPE AND MIN. TWO FEET ON EACH SIDE OF PIPE. QUARRY SPALLS SHALL EXTEND MIN. THREE FEET BELOW EXTEND QUARRY NORMAL WATER SURFACE AS MEASURED SPALLS 3.0' MIN. BELOW PARALLEL TO BANK. COVER QUARRY SPALLS WATER SURFACE AS WITH FOUR INCHES OF SOIL AFTER MEASURED PARALLEL PLACEMENT AND SEED WITH EROSION TO BANK. CONTROL SEED MIXTURE. K.H. 2.) WHITE REFLECTIVE FLEXIBLE FIBERGLASS LOCATOR POST PER LONGVIEW STANDARD PLAN SS-270 OR APPROVED EQUAL SHALL BE INSTALLED IMMEDIATELY ADJACENT TO PIPE AND SHALL EXTEND A MIN. OF FOUR FEET ABOVE PIPE WITH A MIN. EMBEDMENT DEPTH OF TWO FEET. SET POST IN CONCRETE.

3.) ALL DISTURBED AREAS SHALL BE SEEDED WITH SEED MIXTURE UPON PROJECT COMPLETION.

4.) THIS STANDARD PLAN NOT INTENDED TO PROVIDE FOR FISH PASSAGE REQUIREMENTS.