Advanced Topics in Stray Voltage Investigation
Total Page:16
File Type:pdf, Size:1020Kb
02/20/2015 Advanced Topics in Stray Voltage ‐ Why is that voltage there? Paul Ortmann, P.E. Senior Electrical Engineer Idaho Power Company [email protected] Imagine… You are “the stray voltage person” at work. Your phone rings … 1 02/20/2015 Five phone calls… 1. Blown transformer fuse, voltage normal. 2. Customer shocked from aluminum siding, where is the fault? 3. Worker shocked on grounded pivot sprinkler. 4. Gas company tech finds about 60V AC between gas pipeline and earth. 5. High frequency NEV and contact voltage. Phone call 1: Blown transformer fuse Routine neutral-to-earth voltage check: neutral- to-earth voltage “seems a little high” Three-phase transformer bank has one fuse blown. 120/240V three-phase service has normal voltage; dairy is running. 2 02/20/2015 We find this: Are these really any different? A B C N Open Fuse a b n c Grounded-Wye Delta Open-Wye – Open-Delta (with blown fuse on one power transformer) 3 02/20/2015 Grounded‐Wye – Delta • Contributes to primary system ground fau s – hence blown fuse. • Used temporarily on ungrounded wye-delta banks. • Sometimes installed accidentally. • Contributes primary neutral current. lt Ungrounded‐Wye ‐ Delta • Primary neutral point is deliberately floated. • No primary neutral current due to transformer. 4 02/20/2015 Open‐Wye – Open‐Delta • Three-phase service from two p mary phases • Less prone to ferroresonance than some other connections • Significant primary neutral current contribution ri Primary Neutral Current Comparison Open Wye Open Delta Grounded Wye-Delta Ungrounded Wye-Delta 0 2 4 6 8 10 12 Load: 60kVA 3-phase (balanced) 5 02/20/2015 Primary Neutral Current Comparison Open Wye Open Delta Grounded Wye-Delta Ungrounded Wye-Delta 0 2 4 6 8 10 12 Load: 60kVA 3-phase 25kVA 240V single-phase Ungrounding a grounded‐wye‐delta transformer 72-hour NEV at Transformer Pole 2 1.8 1.6 1.4 1.2 1 0.8 0.6 0.4 0.2 0 Grounded Wye-Delta Ungrounded Wye-Delta 6 02/20/2015 Closing an Open‐Delta transformer Primary Profile NEV 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 Open Delta NEV Closed Delta NEV An NEV model Two important laws: Kirchhoff’s Current Law: Current In = Current Out Ohm’s Law: Voltage = Current x Impedance 7 02/20/2015 Open, Grounded, and Ungrounded‐Wye‐Delta Primary System NEV 9 8 7 6 5 4 3 2 1 0 1 11 21 31 41 51 61 71 81 91 Ungrounded Wye-Delta Open Wye-Delta Grounded Wye-Delta Lessons Learned Check Delta transformer connections carefully. Close open wye-open delta banks if possible. Adding balanced 3-phase load to an ungrounded wye-delta transformer bank should not change NEV. If it does, investigate further. 8 02/20/2015 Intelligent troubleshooting: Compare conditions to expectations: Example expectations: “If this transformer is connected properly and we add load, NEV should…” “If there is a good neutral-to-ground bond, then voltage between these two points should be…” “If the neutral connections between these two panels are in good condition then I should measure…” In short, if you don’t know what “normal” is, you won’t recognize “abnormal”. Phone call 2: Shock from aluminum siding • Customer touched aluminum siding on garage and got shocked • No breakers have tripped • Customer’s equipment appears to operate normally 9 02/20/2015 Ground faults and effective current paths: From the 2014 NEC: (paraphrased) • Ground Fault. An unintentional connection between an ungrounded conductor and the normally non–current-carrying conductors, metallic enclosures, metallic raceways, metallic equipment, or earth. • Effective Ground-Fault Current Path. An intentional, low-impedance path to carry current under ground-fault conditions and facilitates the operation of the overcurrent protective device or ground-fault detectors. Earth faults: The earth shall not be considered an effective ground-fault current path. (2014 NEC-250.4) But what if the earth is the only path for ground‐ fault current? We’ll call this an “Earth fault" 10 02/20/2015 Observations: • Separate garage has a short 3-wire 120/240V overhead service from a breaker in the house panel. • Garage has a subpanel with a main breaker and several branch circuit breakers. • No GFCI circuit breakers or receptacles are installed in garage. Faults – What is supposed to happen? Low-impedance fault current path ensures that plenty of current flows to quickly trip the circuit breaker 11 02/20/2015 A few cycles after the fault starts… Circuit breaker quickly trips. But the breaker did not trip… Earth faults rarely produce enough current to trip a non‐GFCI circuit breaker or blow a fuse. If someone reports being shocked when they touch something grounded, you may have an earth fault to find. 12 02/20/2015 Measurements: •Voltage measured between a screwdriver in the earth and the garage s aluminum siding is approx’im ately 110-volts, even with meter on “Lo-Z” setting. •Net current on overhead service to garage is about 3-Amps. •Neutral current on overhead service to garage is negligible. Tests: •Open main breaker in garage • Contact voltage disappeared • Fa ult current is going through main breaker •Close main breaker and open individual breakers one at a time • Opening one branch circuit breaker eliminates the contact voltage • Fault is on that circuit 13 02/20/2015 Investigate: • Open electrical boxes on that circuit • Found line-to-ground fault in metal receptacle box • Why didn t the breaker trip?! ’ One missing screw… No bond Earth fault current is too low; breaker won’t trip. Earth is only fault current path 14 02/20/2015 Lessons Learned: If a “ground fault” doesn’t cause a circuit breaker to trip or a fuse to blow, it may actually be an “Earth fault.” Earth faults are a combination of two problems: Problem 1: The ground fault Problem 2: A poor fault current path Both problems must be found! Normal neutral and ground current 15 02/20/2015 Primary NEV with an earth fault at a service Primary System NEV 6 5 4 3 2 1 0 1 11 21 31 41 51 61 71 81 91 Normal Earth Fault Primary and service current with an earth fault 16 02/20/2015 Voltage gradients – where current enters or leaves the earth Altitude gradient Voltage gradient Touch and step voltages during an earth fault • Touch and step voltage downstream of the break in the grounding path can be very high – even lethal. For a single isolated vertical ground rod: ~88% of the voltage drop to remote earth is within one rod-length For a 10’ rod, the voltage from 1’ to 3.5’ away will be about 20% of the faulted line voltage 17 02/20/2015 Finding both parts of the earth fault •The ground fault: 1. Monitor the fault safely while opening circuit breakers, fuses, or disconnects. • M ultimeter or voltage detector can be used. • Can measure contact voltage, gradient, or NEV. 2. Do not assume that first upstream device will interrupt fault current. 3. When opening a disconnect de-energizes the fault, the ground fault is downstream of that disconnect and upstream of other disconnects further downstream. Finding the break in the fault current path 1. M easure voltage across connections; should be nearly zero 2. For underground or overhead, measure NEV; Downstream of break, NEV will be high, and may approach normal line-to- ground voltage 3. Upstream of break, NEV will be elevated but not normally to more than 10-20V. 18 02/20/2015 An Example: NEV at panels 2 and 3 is close to line voltage NEV at panel 1 is 14 Volts Opening disconnect 1 or 2 eliminates high NEV readings Opening disconnect 3 does not eliminate high NEV readings Where is the ground fault? Where is the break in the effective ground fault current path? Phone call 3: The shocking pivot 19 02/20/2015 Report and Observations: • Worker receives painful shocks when working from a ladder on the pivot to replace sprinklers • Pivot is parked parallel and next to a 345kV transmission line for service Measurements: • Voltage from earth to pivot is 2V or less along the pivot’s entire length • Not a pivot grounding problem • Voltage between a person standing on the ground in dry shoes and the wheeled pivot towers is also less than 2V. • Person-to-pivot voltage increases to over 600V across a 10MΩ digital voltmeter as the person climbs an insulated ladder in the middle of a pivot span. • A person-grounding problem! 20 02/20/2015 Electric Field Calculations: • Open-circuit person-to-pivot AC voltage with person on insulated ladder: Over 10kV! • No wonder it hurts… • The pivot is not shocking the worker. The worker is shocking the pivot! The effect is very similar to a fencer pulse. • Steady-state short circuit current for person at working height is less than 0.1mA • Not a steady-state problem if person can be kept grounded. The situation: Person touching pivot is shorting the capacitance between them and the earth/pivot. That capacitance is small, but may be charged to over 10kV at the time of contact. 21 02/20/2015 Typical electric field shape (horizontal conductors) V/m 0 - 100 - 50 0 50 100 You can use a voltage detector to find the peak of the field near a transmission line The issue: Series capacitance •Electric field redistributes charge •Large voltage can appear across capacitances •Shorting the capacitance results in a capacitive discharge – like a fencer pulse 22 02/20/2015 Solution: •Anti-Static wrist strap with large alligator clip.