PT-Link II BACnet4® Technical Guide

VCB-X Controller Code: SS1051 Version 2.0 VCM-X Controller Code: SS1026 & Y200920 Version 2.0 and up; VCM-X Modular Controller Code: SS1030 & SS1034 VCM-X WSHP Controller Code: SS1032 & SS1033 SA Controller Code: Y200921 VCM Controller Code: SS1016, Y200409, Y200616, Y200822 Zone TABLE OF CONTENTS Zone

1. GENERAL INFORMATION...... 4 1.1 Overview and System Requirements...... 4 1.1.1 Data Sharing...... 4 1.1.2 Scheduling...... 4 1.1.3 Hardware Specifications...... 4 1.1.4 System Requirements...... 4

2. SETTING UP YOUR PT-LINK II...... 5 2.1 Quick Start Guide...... 5 2.2 Connection and Wiring Information...... 6 2.3 Configuring the PT-Link DIP Switches...... 7 2.3.1 Set the BACnet® MS/TP Baud Rate...... 7 2.3.2 Set the BACnet® MS/TP MAC Address...... 7

3. PT-LINK CONFIGURATION...... 8 3.1 Graphical User Interface...... 8 3.2 PT-Link II Ethernet Connection...... 9 3.3 IP Address Configuration...... 10 3.3.1 Computer IP Address Setup for Windows 10®...... 10 3.3.2 BACnet® MS/TP: Setting Node_Offset to Assign Specific Device Instances...... 12 3.4 Verifying Communications...... 13

4. UPDATING THE SOFTWARE...... 14 4.1 Updating the PT-Link II Controller...... 14 4.1.1 Updating the PT-Link II with Prism 2...... 14 4.1.2 Finding What COM Port Number the PT-Link II is Using...... 16 4.1.3 Changing the USB COM Port Number...... 17 4.2 Updating the Field Server Software...... 18

www.aaon.com

This manual is also available for download from www.aaon.com/controlsmanuals, under PT-Link, where you can always find the latest literature updates.

AAON, Inc. AAON P/N: G042790, Rev. 01E 2425 South Yukon Ave. All rights reserved. © April 2020 AAON, Inc. Tulsa, OK 74107-2728 AAON® is a registered trademark of AAON, Inc., Tulsa, OK. www.aaon.com BACnet® is a registered trademark of ASHRAE Inc., Atlanta, GA. Factory Technical Support Phone: 918-382-6450 FieldServer is a Registered Trademark of FieldServer Technologies, Controls Support Phone: 866-918-1100 Milpetas, CA AAON® assumes no responsibility for errors or Windows® 10 is a registered trademark of Microsoft Corporation. omissions in this document. This document is subject to change without notice. Zone TABLE OF CONTENTS Zone

5. TROUBLESHOOTING...... 19 5.1 Troubleshooting Communications...... 19 5.1.1 Check Wiring and Settings...... 19 5.1.2 Verifying Communications...... 19 5.2 Troubleshooting LEDs...... 20 5.2.1 PT-Link Board LEDs...... 20 5.2.2 PT-Link Module LEDs...... 21 5.3 Troubleshooting the PT-Link Controller...... 22 5.3.1 Addressing AAON Devices in a BACnet® Network...... 22 5.3.2 BACnet® Explorer for Validating PT-Link in the Field...... 22 5.3.3 Viewing Diagnostic Information...... 23 5.4 FieldServer Diagnostic Utilities...... 24 5.4.1 Diagnostic Capture Procedures...... 24

6. DATA ARRAYS...... 26 6.1 VCCX2 Data Arrays...... 26 6.2 VCB-X Data Arrays...... 27 6.3 VCM-X Modular & VCM-X WSHP (Tulsa) Data Arrays...... 28 6.4 VCM-X WSHP (Coil) & VCM-X Data Arrays...... 29 6.5 SA & VCM Data Array...... 30

7. PARAMETER TABLES...... 30 7.1 VCCX2 BACnet® Parameters...... 31 7.1.1 VCCX2 PT-Link II BACnet® Property Identifier...... 46 7.2 VCB-X BACnet® Parameters...... 47 7.2.1 VCB-X PT-Link II BACnet® Property Identifier...... 58 7.3 VCM-X Modular BACnet® Parameters...... 59 7.4 VCM-X WSHP (Tulsa) BACnet® Parameters...... 60 7.5 VCM-X WSHP (Coil) BACnet® Parameters...... 62 7.6 VCM-X BACnet® Property Identifier...... 63 7.6.1 VCM-X PT-Link II BACnet® Property Identifier...... 68 7.7 SA Controller BACnet® Parameters...... 69 7.7.1 SA Controller PT-Link II BACnet® Property Identifier...... 72 7.8 VCM BACnet® Parameters...... 73 7.8.1 VCM PT-Link II BACnet® Property Identifier...... 78

8. FIELDSERVER GRAPHICAL USER INTERFACE...... 79 8.1 The FieldServer Graphical User Interface (FS-GUI) with Configuration Parameter Page Navigation Tree..... 79 8.2 Network Settings...... 80 8.3 Setting a Password for the FS-GUI...... 80

9. MAC ADDRESS & DEVICE INSTANCE...... 82

10. BACNET PIC STATEMENT...... 84 10.1 Protocessor Driver - (PICS) BACnet® Protocol Implementation Conformance Statement...... 84

PT-LInk II BACnet4 Technical Guide 3 Zone 1. GENERAL INFORMATION Zone 1.1 Overview and System Requirements

The PT-Link II BACnet4® provides bi-directional communication be- 1.1.2 Scheduling tween your BACnet® MS/TP protocol network and up to four* of any of the following types of Orion controllers—VCCX2, VCB-X, VCM-X, • Allows BACnet® devices to send Schedule events SA, VCM, MUA II, or VAV/CAV: to the Orion controller side of the gateway by using standard BACnet® services. VCCX2 Controller (SS1088) VCB-X Controller (SS1051) 1.1.3 Hardware Specifications VCM-X Controller (SS1026, SS1030, SS1032, SS1033, SS1034, Y200920) SA Controller (Y200921) Technical Data VCM Controller (SS1016, Y200409, Y200616, Y200822) BACnet®-MS/TP Loop 9600, 19200, 38400, 76800 Mbps **VAV/CAV Controller (SS1003, Y200301) and Controller Loop RS-485, 9600 Baud Rate MUA II Controller (SS1004, Y200405) Network Protocol BACnet®

To determine what controller you have, you must look at the software Protocol HSI Open Protocol Token Passing (Watt Comm Loop) label located on the controller. NOTE: The label is located on the EPROM on older devices. If the controller label does not match any of Power Input Voltage 18-30 VAC the SS or Y numbers listed above, your controller will not work with Power Consumption 10 VA Maximum ® the PT-Link II BACnet . Operating Temp -30°F to 150°F Operating 0-95% RH Non-Condensing ® *NOTE: The PT-Link II BACnet device can be used to con- Weight 4.5 oz. nect to four Orion controllers. If more than four Orion controllers are present in a system, you will need ad- Table 1: PT-Link II BACnet® Interface ® ditional PT-Link II BACnet devices. Technical Data

**NOTE: Documentation is available for MUA II/VAV/CAV on our website: www.aaon.com/controlsmanuals under 1.1.4 System Requirements Previous Generation Controls. • The PT-Link II BACnet® interface is packaged and assembled for panel mounting. Panel mounting components 1.1.1 Data Sharing are included for your convenience. • Computer running Microsoft® Windows 10 operating system. • Provides values from points on the Orion side of the gateway to BACnet® devices as if the values were • Ethernet Crossover Cable (supplied). originating from BACnet® objects. • PT-Link II BACnet software—located on included flash • Allows BACnet® devices to modify point values on the drive and downloadable from www.aaon.com/controlstech Orion controller side of the PT-Link II BACnet® by using support. standard BACnet® write services.

4 PT-LInk II BACnet4 Technical Guide Zone Zone 2. QUICK PT-LINK SETUP 2.1 Quick Start Guide

The following steps will get you up and running in no time: 4. Configure your PT Link DIP Switches. See Section 2.3, page 7. • Set the BACnet® MS/TP baud rate via the B Bank set of 1. Familiarize yourself with the PT-Link II components (Figure 1). DIP switches. 2. Connect your PT-Link II to the Controller(s) on your system (up • Set the BACnet® MS/TP MAC Address using the PT-Link A to four) and connect your PT-Link II to the BACnet® Network Bank DIP switches. The BACnet® MS/TP MAC Address (Figure 2). NOTE: Controllers must be addressed as MUST be set between 1 and 127. 1, 2, 3 & 4.

3. Obtain the following from your System Integrator: the BACnet® MAC address (System Node ID) and the MS/TP network baud rate. Also, relay to your System Integrator that the BACnet® Device Instance Number for the PT-Link will be the MAC address + 50,000 (50,000 is the default Device Instance Number). If you want the Device Instance number to be anything other than 50,000, you will need to access the FS-GUI Toolbox. See Section 3.3.2, page 12.

Figure 1: PT-Link II BACnet® Dimensions and Components

PT-LInk II BACnet4 Technical Guide 5 Zone 2. QUICK PT-LINK SETUP Zone 2.2 Connection and Wiring Information

Figure 2: PT-Link II BACnet® Interface Wiring

6 PT-LInk II BACnet4 Technical Guide Zone Zone 2. QUICK PT-LINK SETUP 2.3 Configuring the PT-Link DIP Switches

The DIP Switches allow you to set the protocol between BACnet® MS/ FFP-485 TP and BACnet® IP (AAON only supports BACnet® MS/TP appli- cations), set the BACnet® MS/TP baud rate, set the BACnet® MS/TP MAC address, and set the BACnet® MS/TP device instance. You can obtain the MAC address, Device Instance, and baud rate from your Building Automation System (BAS) Integrator. The DIP Switches are DIP shown in Figure 3. Switch Bank A NOTE: You must cycle power after making changes to the DIP Switch Settings for the settings to take effect.

2.3.1 Set the BACnet® MS/TP Baud Rate

“B” bank DIP switches B1 – B4 is used to set the BACnet® MS/TP baud rate of the PT-Link. This matches the baud rate required by the Building DIP Switch Using B1 – B4 to Set Baud Rate Bank B Baud B1 B2 B3 B4 9600 ON ON ON ON 19200 OFF OFF OFF ON 38400 ON ON OFF ON Figure 3: DIP Switches 57600 OFF OFF ON ON 76800 ON OFF ON ON CAUTION: DIP Switch 8 in Bank A must always remain OFF Table 2: Baud Rate Settings for proper operation.

® 2.3.2 Set the BACnet MS/TP MAC Address

1. Only (1) MAC address is set for the PT-Link regardless of how many devices are connected to it.

2. Set the BACnet® MS/TP MAC addresses of the PT-Link to a value between 1 and 127 (MAC Master Addresses). This is so that the BMS Front End can find the PT-Link via the BACnet® auto discovery func- tion. MAC addresses from 128 to 255 cannot be auto discovered by the BMS Front End.

3. Set “A” bank DIP switches A1 – A7 to assign a MAC Address to the PT-Link for BACnet® MS/TP. Please refer to Section 9, page 82 for the complete range of MAC Addresses and DIP switch settings.

NOTE: The BACnet® Device’s Instance is generated by adding the MAC address to the Node Offset, which defaults to 50,000. If the Device Instance must be set to something other than in the range of 50,001 to 50,127, see Section 3.3.2, page 12 to change the Node Offset value.

PT-LInk II BACnet4 Technical Guide 7 Zone 3. PT-LINK CONFIGURATION Zone 3.1 Graphical User Interface

The PT-Link is configured using a Graphic User Interface (GUI) The following items are needed to be able to run the GUI: which is a password protected web browser-based interface that uses a combination of technologies and devices to provide a platform from • PC Requirements—a computer with a web browser which you can gather and process information. The GUI allows you that connects over the Ethernet on port 80* to do the following: *NOTE: Computer and network firewalls must be opened for Port 80 to allow the GUI to function. • Change the BACnet® Device Instance to something other than 50,001 to 50,127 • Software Requirements—Chrome 19.0 and higher, Firefox 13.0 and higher, Opera 11.0 and higher, • Check the status and diagnostics of the PT-Link, Microsoft Edge, and Safari 4.1 and higher such as network settings, connection information, node information, map descriptors, and error messages NOTE: Internet Explorer is not supported. • Monitor the PT-Link’s internal data and parameters • Change or update the PT-Link’s internal data and parameters • Restart the PT-Link

8 PT-LInk II BACnet4 Technical Guide Zone Zone 3. PT-LINK CONFIGURATION 3.2 PT-Link II Ethernet Connection

PT-Link II Hardware Connection

1.) Connect the PT-Link II directly to your computer by using a standard CAT5 or crossover cable (by others) as shown. See Figure 4 for details. 2.) Locate a CAT5 cable and plug one end into your computer’s Ethernet port. Plug the other end of the Cable into the Ethernet port on the PT-Link II. 3.) Power up the PT-Link II by plugging in the power cable. The PT-Link II may take up to three minutes to power up completely. Once the PT-Link II is powered up, you should notice that the RUN LED is blinking continuously on the ProtoCessor Board. See Figure 18, page 21 for a diagram showing the location of the ProtoCessor RUN LED.

Figure 4: Connecting With Crossover Cable

PT-LInk II BACnet4 Technical Guide 9 Zone 3. PT-LINK CONFIGURATION Zone 3.3 IP Address Configuration

3.3.1 Computer IP Address Setup for 3.) In the Network and Sharing Center Window, select the Windows® 10 Local Area Connection entry. The Local Area Connection Status Window will appear. In order for the PT-Link II to communicate properly, it is imperative to set the IP address of both the PT-Link II as well as the computer to be within the same netmask. You need to change the IP address on your computer. The following instructions will explain how to configure the IP address for Microsoft® Windows 10 operating system.

NOTE: Consult your IT Specialist to ensure that your Firewall and anti-virus software are turned off before proceeding.

The following instructions explain how to change your computer’s IP address.

1.) Right click the Windows icon or ; then click .

2.) Then click . The Network and Sharing Center Window will appear. Figure 6: Local Area Connection Status Window

Figure 5: Network and Sharing Center Window

NOTE: If any wireless connections are listed, disable them by right-clicking the connection and selecting .

10 PT-LInk II BACnet4 Technical Guide Zone Zone 3. PT-LINK CONFIGURATION 3.3 IP Address Configuration

4.) Click the button. The Local Area Connection Properties Window will appear.

Figure 7: Local Area Connection Properties Window Figure 8: Internet Protocol Properties Window

5). In the Connection Items List Box (Figure 7), be sure the 6). Type in the following information: Internet Protocol Version (TCP/IPv4) is checked. Click on a.) Make the IP address 192.168.1.5 Internet Protocol (TCP/IP v4) to highlight it and then click b.) Make the Subnet mask 255.255.255.0 . The Internet Protocol Properties Window will c.) Blank out the Default gateway setting (leave appear. the setting blank as shown in Figure 8). d.) Blank out the Preferred DNS server setting and the Alternate DNS server setting (see Figure 8).

7.) Select until all of the above windows are closed. You may have to reboot the computer before the new val- ues are valid.

PT-LInk II BACnet4 Technical Guide 11 Zone 3. PT-LINK CONFIGURATION Zone 3.3 IP Address Configuration

3.3.2 BACnet MS/TP - Setting Node_ Offset to Assign Specific Device Instances

After setting your PC to be on the same subnet as the PT-Link, open a web browser on your PC and enter the IP address of the PT-Link; the default address is 192.168.1.24.

1. If the IP address of the PT-Link has been changed by previous configuration, you will need to get the assigned IP address from the network administrator or use the FieldServer Toolbox to find the IP Address.

2. The configuration page will be displayed as your landing page. (Figure 9)

3. The node offset can be changed on the configuration page.

4. The Node_Offset field will be presented displaying the current value (default = 50,000).

5. Change the value of Node_Offset to establish the desired Device Instance value, and click .

Device Instance = Node_Offset + A bank DIP switch setting (A1-A7)

Figure 9: BACnet MS/TP Settings for Node_Offset

12 PT-LInk II BACnet4 Technical Guide Zone Zone 3. PT-LINK CONFIGURATION 3.4 Verifying Communications

3.4.1 Verifying Communications

1. ) In the Navigation Window on the left of the FS-GUI Main Screen, click and then click . See Figure 10.

Figure 11: VCM-X Data Array Table

3 ) You can now cross reference the values shown in Figure 11 with the listed parameter names in the appropriate Data Array Table for your controller type. These tables can be found on pages 26-29.

3.4.2 FS-GUI Reference Guide

Figure 10: Navigation Window - View Data Arrays An FS-GUI Reference Guide can be found in Section 8, page 62.

2. ) Click on the Controller name. In this case, it is DA_C160_I0, a VCM-X Controller. The Controller’s Data Array Table will display. See Figure 11.

PT-LInk II BACnet4 Technical Guide 13 Zone 4. UPDATING THE SOFTWARE Zone 4.1 Updating the PT-Link II Controller

4.1.1 Updating the PT-Link II with 8.) Click on the icon. The Job-Sites Window will appear. Prism 2 In the Type of CommLink Dialog Box, select “CommLink 5 or USB Link II.” Under “Network Configurationm,”select “Single Loop/USB Link.” The PT-Link II is equipped with the ability to update its software with the use of a computer. You will need the following before you begin:

• PT-Link II in need of an update (powered up, no other connections necessary) • Computer running Microsoft® Windows ®10 operating system • Prism 2 software from www.aaon.com/prism • Latest version of PT-Link II software and software sheet (e-mailed from AAON Controls Support staff) • USB Driver Setup.exe file from flash drive or downloaded from www.aaon.com /prism 9.) In the Job-Sites Window, from the Serial Port drop down list, select • USB cable the correct COM port. If you don’t know the COM port number or if the number is 10 or higher, follow the directions on pages 16 and 17. Follow these simple steps to update the PT-Link II:

1.) Power up the PT-Link II.

2.) Turn on your computer and download the latest Prism 2 software from www.aaon.com/prism

3.) Either download and unzip the PT-Link II update file from aaon. 10.) From Prism 2’s Communications tab, select “Flash Selected com/controlstechsupport or unzip and save the file to your computer Controller”, and then select “Manual Flashing.” from the e-mail you received from AAON Controls Support. Record the path and name of the file for later use. You will need to know where the file is located for Step 16. Also, print the software sheet provided for future reference. NOTE: You must unzip the file in order for Prism to recognize the hex file.

4.) Run the USB Driver Setup.exe file (found on the PT-Link II flash drive or downloaded from aaon.com/controlstechsupport) so that Prism can communicate to the PT Link II. Unzip the file to the directory where you saved your PT-Link II software.

5.) Plug the USB cable into the computer’s and PT-Link II’s USB ports.

6.) A message will pop-up from the lower menu bar of Windows that reads, “Found New Hardware.” Click on this message and follow the instructions that appear to install the USB drivers.

7.) Open Prism 2 and Login with the User Name, admin and the Pass- word, admin. If successful, “Administrator Access” will appear at the lower right of the Prism program. NOTE: If using a Prism 2 version 11.) The Manual Flash Controller Window will appear. prior to 4.0, the Login is flash. If successful, “Level 4 Access” will ap- pear at the lower right of the Prism program.

14 PT-LInk II BACnet4 Technical Guide Zone 4. UPDATING THE SOFTWARE Zone 4.1 Updating the PT-Link II Controller

12.) From the Manual Flash Controller Window’s Connection tab, select 17.) Now, cycle power to the PT-Link II once again and within 5 “Direct”. Keep the Flash Controller Window open seconds click on the button (shown in Step 16). If successful, you should see the Progress Application HEX bar showing the progress percentage.

13.) In the Manual Flash Controller Window’s Loop and Unit fields, enter 0 for the Loop and 63 for the Unit, and then press . 18.) When the bar shows 100% completed, verify the PT-Link II’s software is running by observing the Timer LED blinking.

19.) Verify the PT-Link II’s Application Version by once again cycling power to the PT-Link II and within 5 seconds clicking the button.

20.) Verify all fields are correct in the information below the button and under “Finalization Data.” The “Int Flash Length” and “Checksum” values should match the values provided with the software sheet. 14.) Cycle power to the PT-Link II and within 5 seconds, click the button in the Flash Controller Window. The PT-Link II in- formation will now appear in the window under the button.

15.) The Application ID should be SS1035 and the Application Version should match the software version you will be updating to.

16.) In the HEX File field, enter the path and name of the HEX file you downloaded and/or copied to your hard drive. Use the Browse button (...) to the right of the field if you need help in locating the file.

PT-LInk II BACnet4 Technical Guide 15 Zone 4. UPDATING THE SOFTWARE Zone 4.1 Updating the PT-Link II Controller

4.1.2 Finding What COM Port Number the PT-Link II is Using (Windows® 10)

1. Right-click on the Windows® icon, located on the bottom left or top left of the Windows® Tool Bar.

2. Click on .

3. Click on to see all of the common ports.

4. Locate the USB Serial Port (COM#). The COM# in parentheses is the port it is located on. Write this COM port number down. You will need to know this when setting up the Prism software.

5. If the COM port number is 10 or greater, go to “Changing the USB COM Port Number” on page 17.

16 PT-LInk II BACnet4 Technical Guide Zone 4. UPDATING THE SOFTWARE Zone 4.1 Updating the PT-Link II Controller

4.1.3 Changing the USB COM Port 6. To assign a port number less than 10, click on Number (Windows® 10) . The Advanced Settings Window will appear.

When the PT-Link II is first plugged in, it will be assigned a COM port number to be used for communicating with the Prism 2 software. If the port number is 10 or greater, it needs to be changed to a value less than 10 to be recognized by Prism.

1. Right-click on the Windows® icon, located on the bottom left or top left of the Windows® Tool Bar.

2. Click on .

3. Click on to see all of the common ports.

7. In the COM Port Number drop box, located at the bottom left, select which COM port you wish to use. Make sure you select a COM port number that is not currently in use (you can see the ports in use in the Device Manager Window). Select a port that is less than 10.

4. Locate the USB Serial Port (COM#). The COM# in NOTE: Windows® will assign a port number to every de- parentheses is the port it is located on. vice that has ever been installed on your computer. So if there are no available ports below 10, choose 5. Right-click on “USB Serial Port (COM#)” and a port number less than 10 for a device listed that select . In the Properties Window, you know you are not currently using. select the tab.

8. Once you select the correct COM port number, click and close any windows opened in the process of changing the port number. Make note of this number because you will need it for your Prism setup.

PT-LInk II BACnet4 Technical Guide 17 ZoneZone 4. UPDATING THE SOFTWARE ZoneZone 4.2 Updating the Field Server Software

1.) Extract and save the update file you receive from Field Server onto 4.) Refer to the File Transfer Window below (Figure 14). In the General your PC. Tab, click and locate the file you saved in Step 1. Then click on . When the download is complete, click on the button. which defaults to <192.168.1.24>, and press . The GUI will launch. Click . The Main Screen will appear. See Figure 12.

Figure 14: File Transfer - General Tab

Figure 12: The FS-GUI Main Screen

3.) In the Navigation Window on the left of the FS-GUI Screen, click and then click . See Figure 13.

Figure 13: Navigation Window - File Transfer

18 PT-LInk II BACnet4 Technical Guide ZoneZone 5. TROUBLESHOOTING ZoneZone 5.1 Troubleshooting Communications

5.1.1 Check Wiring and Settings 5.1.2 Verifying Communications

No COMS on AAON side 1. ) In the Navigation Window on the left of the FS-GUI Main Screen, click and then click . See Figure 15. If TX/RX are not flashing rapidly, then there is a COM issue on the AAON side and you need to check the following things:

• Visual observations of LEDs on ProtoNode. (Figure 18, page 21) • Check baud rate, parity, data bits, stop bits • Check AAON device address • Verify wiring • Verify all the AAON devices that were discovered in FST Web Configurator. page( 12)

NOTE: If the problem still exists, a Diagnostic Capture needs to be taken and sent to AAON Controls Support. See page 24.

Figure 15: Navigation Window - View Data Arrays

Field COM problems 2. ) Click on the Controller name. In this case, it is DA_C160_I0, a • Visual observations of LEDs on PT-Link. (Figure 17, VCM-X Controller. The Controller’s Data Array Table will display. page 20) See Figure 16.

• Visual dipswitch settings (using correct baud rate and device instance)

• Verify IP address setting

• Verify wiring

NOTE: If the problem still exists, a Diagnostic Capture needs to be taken and sent to AAON Controls Support. See page 24.

Figure 16: VCM-X Data Array Table

3 ) You can now cross reference the values shown in Figure 16 with the listed parameter names in the appropriate Data Array Table for your controller type. These tables can be found on pages 26-30.

PT-LInk II BACnet4 Technical Guide 19 Zone 5. TROUBLESHOOTING Zone 5.2 Troubleshooting LEDs

5.2.1 PT-Link II Board LEDs The PT-Link II BACnet® is equipped with LEDs that can be used for troubleshooting. There are eight LEDs on the PT-Link board. See Figure 17 for the locations of the LEDs on the PT-Link board. The LED descrip- tions and functions are listed in the following paragraphs.

POWER LED When the PT-Link II BACnet® is powered up, the “POWER” LED should light up and stay on continuously. If it does not light up, check to be sure that you have 24 VAC connected to the board, that the wir- ing connections are tight, and that they are wired for correct polarity. The 24 VAC power must be connected so that all ground wires remain common. If after making all these checks the “POWER” LED still does not light up, please contact AAON Controls Support at our Toll Free number—866-918-1100—for assistance.

LOOP LED When power is applied to the PT-Link II BACnet®, the “LOOP” LED will also light up. The LED should flicker rapidly, indicating that the PT-Link is trying to communicate with the controllers on the loop. A “flicker” is defined as a brief moment when the LED turns off and back on. If the “LOOP” LED does not operate as indicated above, first power down the unit and then reapply power. If this does not work, please con- tact AAON Controls Support at our Toll Free number—866-918-1100— for assistance.

LED 1 When power is first applied, LED“ 1” will be off temporarily and then will blink one time for each controller it is communicating with. For example, if you have 4 controllers on the loop connected to the PT-Link, “LED 1” will blink 4 times. If the amount of blinks does not match the number of controllers connected to the loop, it indicates there is a com- munications problem. The best way to find out which board is not com- municating is to go to each controller and look at its “COMM” LED. The “COMM” LED should be solid and will flicker occasionally indicating communication with the PT-Link II BACnet®. If the “COMM” LED does not flicker, there is no communication with that controller.

LED 2 Figure 17: PT-Link II BACNET® LED Locations When power is first applied, LED“ 2” will be off temporarily and then will blink slowly indicating that the PT-Link baseboard is communicating with the ProtoCessor Module. If “LED 2” does not blink, check that the ProtoCessor Module is installed correctly on the PT-Link baseboard and WATCH DOG LED that the “PWR” LED is lit up on the ProtoCessor Module. The “W-DOG” LED is used for troubleshooting by AAON Controls Support. The “W-DOG” LED should always be on solid. PROTO LED When the PT-Link II is first powered up, the PROTO“ ” LED should HEARTBEAT LED blink rapidly and may appear to be on solid. This LED verifies com- The “H-BEAT” LED blinks to show the PT-Link II board software is munication with the board and the ProtoCessor. If the LED doesn’t running. If the LED doesn’t light up, and all other checks have been light up, check that the ProtoCessor is installed correctly and firmly made, please contact AAON Controls Support at our Toll Free num- connected to the Base Board. The “PWR” LED should also be lit on ber—866-918-1100—for assistance. the ProtoCessor Module.

TIMER LED The “TIMER” LED is used for troubleshooting by AAON Controls Support. The “TIMER” LED should always be blinking steadily.

20 PT-LInk II BACnet4 Technical Guide Zone 5. TROUBLESHOOTING Zone 5.2 Troubleshooting LEDS

5.2.2 PT-Link Module LEDs RX & TX LEDs During normal operation, the “RX” LED will flash when a message is received on the field port of the ProtoCessor and the TX“ ” LED will Refer to Figure 18 for LED locations. flash when a message is sent on the field port of the ProtoCessor. The “TX” and “RX” LEDs work together to indicate that communication PWR LED is being established with the desired protocol network. If both LEDs When the PT-Link II is first powered up, the PWR“ ” green LED should are blinking, then communication is working properly. If not, check light up and stay on continuously. If the LED doesn’t light up, check the protocol network wiring and the baud rate in the configuration file. that the ProtoCessor is installed correctly and firmly connected to the Base Board. RUN LED Upon power up, the “RUN” LED should light up and stay solid for 15 seconds. It should then blink steadily, signifying normal operation. The ProtoCessor will be able to access RUINET once this LED starts flashing.

RUN2 LED The “RUN2” LED should blink steadily after power up, signifying normal operation. The Protocessor will be able to access RUINET once this LED starts flashing.

SYS ERR LED The “SYS ERR” LED will go on solid 15 seconds after power up and then shut off. A steady red light will indicate there is a system error on the ProtoCessor. If this occurs, immediately report the related “system error” shown in the error screen of the Remote User Interface to Field- Server Technologies for evaluation.

NODE OFFLINE LED The “NODE OFFLINE” amber LED will go on solid 15 seconds after power up and then shut off. A steady amber light indicates the ProtoCes- sor is not communicating with a device that it is polling.

Figure 18: PT-Link II BACnet4® LED Locations NOTE: If all of these tests are made and the controller still doesn’t operate, please contact AAON Controls Support at our Toll Free number—866-918-1100—for assistance.

Figure 19: PT-Link II BACnet4® Components

PT-LInk II BACnet4 Technical Guide 21 Zone 5. TROUBLESHOOTING Zone 5.3 Troubleshooting the PT-Link Controller

5.3.1 Addressing AAON Devices in a 5.3.2 BACnet® Explorer for Validating BACnet® Network PT-Link in the Field

Each PT-Link II BACnet® generates only one BACnet® device Sierra Monitor Corporation offers a tool, BACnet® Explorer, that regardless of the number of AAON controls connected to it. This can be used to validate BACnet® MS/TP communications of the PT- device will have all the properties of all the AAON controls con- Link in the field without having to have the BMS Integrator on site. nected. The instance of the device is equal to the unit address. The ® properties of each control can be differentiated by an offset of 500. For instructions on downloading BACnet Explorer, perform a search in your internet browser for the latest Sierra Monitor’s BACnet® Examples: Explorer Start-up Guide. For purchasing information, go to the BACnet® Explorer page on 1.) Properties of the controller address as 1 will range the Sierra Monitor website (www.sierramonitor.com/connect/all- from 0 to 499. protocol-gateway-products/bacnet-explorer) and click on the “BUY 2.) Properties of the controller address as 2 will range NOW” tab. from 500 to 999. 3.) Properties of the controller address as 3 will range from 1000 to 1499.

To search for the instance of a specific property, follow the next formula:

Property Instance = ((Controller Address – 1) * 500) + Instance Number from table.

Example: 1.) The PT-Link II BACnet® has a Node ID equal to five. 2.) Two VCM controllers connected and addressed to one and four. 3.) Searching for the Outdoor Temperature of each controller. 4.) Instance of the Outdoor Temperature in the VCM table equal to AI: 54. 5.) Client will only see Device 5. 6.) Under Device 5 it will see AI: 54 for the Outdoor Temperature of the unit addressed as 1 and AI: 1554 for the Outdoor Temperature of the unit addressed as 4.

NOTE: To simplify the calculation, we recommend that the AAON controllers be addressed in sequential order from one to the last controller without any unused address(es) in between.

22 PT-LInk II BACnet4 Technical Guide Zone 5. TROUBLESHOOTING Zone 5.3 Troubleshooting the PT-Link Controller

5.3.3 Viewing Diagnostic Information

1. Type the IP address of the PT-Link into your web browser or use the FieldServer Toolbox to connect to the PT-Link

2. Click on then click on , and then click on . See Figure 20.

3. If there are any errors showing in the Connections Window, please refer to Section 5.1.1, page 19 for the relevant wiring and settings.

Figure 20: Connections Window

PT-LInk II BACnet4 Technical Guide 23 Zone 5. TROUBLESHOOTING Zone 5.4 FieldServer Diagnostic Utilities

5.4.1 Diagnostic Capture Procedures 5. Disable firewall and virus protection software if possible.

1. Once the Diagnostic Capture is complete, email it to 6. Connect a standard Cat 5 Ethernet cable between the PC [email protected]. The Diagnostic Capture will and ProtoNode. allow us to rapidly diagnose the problem. 7. Double-click on the FS Toolbox Utility. Refer to Figure 2. Ensure that FieldServer Toolbox is Loaded on the PC 26, page 25 for Toolbox components. that is currently being used, or download FieldServer- Toolbox.zip at www.sierramonitor.com/content/ 8. Click on the diagnose icon of the desired device. fieldserver-toolbox-0 See Figure 22. 3. Extract the executable file and complete the installation. 9. Select Full Diagnostic. See Figure 23. 4. Disable any wireless Ethernet adapters on the PC/Laptop. See Figure 21.

Figure 21: Ethernet Port Location Figure 23: Full Diagnostic

Figure 22: FieldServer Toolbox - Diagnostic Icon

24 PT-LInk II BACnet4 Technical Guide Zone 5. TROUBLESHOOTING Zone 5.4 FieldServer Diagnostic Utilities

10. If desired, the default capture period can be changed. 12. Wait for the Capture period to finish. The Diagnostic See Figure 24. Test Complete Window will appear. Figure 25.

11. Click on . Figure 24.

Figure 25: Diagnostic Test Complete Window

13. Once the Diagnostic test is complete, a .zip file will be saved on the PC.

14. Click in the Diagnostic Test Complete Window to launch explorer and have it point directly at the correct folder. Figure 24: Set Capture Period and Start Diagnostic 15. Send the Diagnostic zip file to [email protected].

*

* Note: Blue: Limited connectivity. You might have an older software version on the FieldServer ProtoCessor. You would need to run the RUINET setup instead of using the FS-GUI interface. Please contact AAON Controls Support for assistance.

Figure 26: FieldServer Toolbox Components

PT-LInk II BACnet4 Technical Guide 25 Zone 6. DATA ARRAYS Zone 6.1 VCCX2 Data Array

VCCX2 Data Array For Field Server Offset 0 1 2 3 4 5 6 7 0 AppVer CtrlMod CtrlSts HvacMode CtrlTp ClSt HtSt SldAdOfs 8 SaTp SaTpSt CoilTpSt SpcTp InRh RaTp RaRH OaTp 16 OaRh OaWtbl OaDewPt SaStRt DuctPr FanVfdSg BuildPr RlfSgl 24 OaCFM SaCFM RaCFM EtCFM CO2 EcoPos T24EcFb RaDmp 32 RetBydmp MdClSgl MdHtSgl Rt2Pos MdGsVPos A1Cmpr A2Cmpr A1Cndr 40 A2Cndr A1SucPr A2SucPr A1HdPr A2HdPr A1SauTp A2SauTp A1SucTp 48 A2SucTp A1SupHt A2SupHt A1ExpVv A2ExpVv A1DscTp A2DscTp ALevWtr 56 B1Cmpr B2Cmpr B1Cndr B2Cndr B1SucPr B2SucPr B1HdPr B2HdPr 64 B1SauTp B2SauTp B1SucTp B2SucTp B1SupHt B2SupHt B1ExpVv B2ExpVv 72 B1DscTp B2DscTp BLevWtr C1Cmpr C2Cmpr C1Cndr C2Cndr C1SucPr 80 C2SucPr C1HdPr C2HdPr C1SauTp C2SauTp C1SucTp C2SucTp C1SupHt 88 C2SupHt C1ExpVv C2ExpVv C1DscTp C2DscTp CLevWtr D1Cmpr D2Cmpr 96 D1Cndr D2Cndr D1SucPr D2SucPr D1HdPr D2HdPr D1SauTp D2SauTp 104 D1SucTp D2SucTp D1SupHt D2SupHt D1ExpVv D2ExpVv D1DscTp D2DscTp 112 DLevWtr AlmSts PreHtLv1 PreHtLv2 PreHtEnt PreHtRst PreHtScr PreHtPwm 120 ClEnbl HtEnbl EcoEnbl AuxHtEn EmHtEnbl Pof EtHood RmOc 128 RmCl RmHt RmDhum SaTpAlm RaTpAlm OaTpAlm SpcTpAlm CO2Alm 136 RefAlm OaCfmAlm EaCfmAlm SaCfmAlm RaCfmAlm ClAlm HtAlm FanAlm 144 DrtFlAlm EmerAlm RlRnTm EcoMs EcoFlA EcoFlB EcoFlC EcoFlD 152 EcoFlE HiCfAlm LoCfAlm HiMdAlm LoMdAlm PreHtAlm BadMod1 BadMod2 160 BadMod3 BadMod4 BadPreBd BadRhtBd BadMgsBd BadEm1Bd BadExRly OnRly1 168 OnRly2 OnRly3 OnRly4 OnRly5 OnRly6 OnRly7 OnRly8 Em1Rly1 176 Em1Rly2 Em1Rly3 Em1Rly4 Em1Rly5 ExRly1 ExRly2 ExRly3 ExRly4 184 ExRly5 ExRly6 ExRly7 ExRly8 ExRly9 ExRly10 ExRly11 ExRly12 192 PreHtEn PreHtEm PreHtBi3 MdGsEn RehtEnbl A1CmpEn A2CmpEn A1Alm 200 A2Alm ADfrSw AWtrPf M1Rly1 M1Rly2 M1Rly3 M1Rly4 M1Rly5 208 B1CmpEn B2CmpEn B1Alm B2Alm BDfrSw BWtrPf M2Rly1 M2Rly2 216 M2Rly3 M2Rly4 M2Rly5 C1CmpEn C2CmpEn C1Alm C2Alm CDfrSw 224 CWtrPf M3Rly1 M3Rly2 M3Rly3 M3Rly4 M3Rly5 D1CmpEn D2CmpEn 232 D1Alm D2Alm DDfrSw DWtrPf M4Rly1 M4Rly2 M4Rly3 M4Rly4 240 M4Rly5 OcpClSt OcpHtSt OaClSt OaHtSt UnClOst UnHtOst MdSelDb 248 HiClTpSt LoClTpSt SaClSt SaHtSt SaClRt SaHtRt SaClSgWd SaHtSgWd 256 WmupSt WmupSaSt ClDnSaSp ClLkOut HtLkOut LoSaCuOf HiSaCuOf PrHtClSt 264 PrHtVtSt PrHtHtSt DptSt EcoEnbl1 HtWhDefr PreHtSp MaxSldEf SpcTpOst 272 SaTpOst RaTpOst OaTpOst CO2Ost LWAmbnt LoClRsSr HiClRsSr LoHtRsSr 280 HiHtRsSr CTpHiAlO CTpLoAlO HpLkt MaxVfd VFDClMin VFDHtMin VFDVtMin 288 MaxEcoHt MinEco MaxEco CO2MinLv CO2MaxLv InRhLoSt InRhHiSt DuctPrSt

Table 3: VCCX2 Data Array For Field Server

26 PT-LInk II BACnet4 Technical Guide Zone 6. DATA ARRAYS Zone 6.2 VCB-X Data Array

VCCX2 Data Array For Field Server Offset 0 1 2 3 4 5 6 7 296 DuctPrDb RfPrSt RlfPrDb OACfmMin OaCfmDb SZVAVFnI RlRnTmLm HdPrCl 304 HdPrDhum SupHtSp HdPrCndr SchdFrc HvacMdOv FanVfdOv EcoOv A1CondST 312 A2CondST A1CondSH A2CondSH A1CondEV A2CondEV B1CondST B2CondST B1CondSH 320 B2CondSH B2CondSH B2CondEV C1CondST C2CondST C1CondSH C2CondSH C1CondEV 328 C2CondEV D1CondST D2CondST D1CondSH D2CondSH D1CondEV D2CondEV AEmShtDn 336 BEmShtDn CEmShtDn DEmShtDn SaStOv SpcTVal SpcRhVal Reserved RelFanOV 344 RelPrVal CO2Val OaTVal OaRhVal HiLvlEtp LoLvlEtp MxPPrRst MnPPrRst 352 EtpEnSp EtpEnDb MxStaRst MnStaRst StaRstIv ClDnTgTp WmUpOv ClDnOv 360 RAHiLmtP RALoLmtP EFRAFPOF – – – – –

Table 3, cont.: VCCX2 Data Array For Field Server

VCB-X Modular Data Array For Field Server Offset 0 1 2 3 4 5 6 7 8 9 0 AppVer ClSt HtSt SpcTp SaTp OaTp UnitMode CtrlSts ClEnbl HtEnbl 10 EcoEnbl FanDly OnRlys EcoPos VfdBwPos AlmSts AlmGrp1 AlmGrp2 AlmGrp3 SaTpAlm 20 OaTpAlm SpcTpAlm MchClAlm MchHtAlm PofAlm DrtFlAlm SmokeAlm LoSaAlm HiSaAlm CtrlTpCF 30 CtrlTpHF CtrlTp InRh InRhStM MdClPos MdHtPos OcpClSt OcpHtSt UnClOst UnHtOst 40 SaClSt SaHtSt SpcTpOst SaTpOst OaTpOst SchdFrc OnRly1 OnRly2 OnRly3 OnRly4 50 OnRly5 OnRly6 MnExRly1 MnExRly2 MnExRly3 MnExRly4 MnExRly5 RlExRly1 RlExRly2 RlExRly3 60 RlExRly4 RlExRly5 RlExRly6 RlExRly7 RlExRly8 RlExRly9 RlExRly10 RlExRly11 RlExRly12 MinEcoSt 70 OaCFM EtCFM SaCFM FrcHvacM FrcFanSp FrcEcono SaTpStM RaTp OaRh StaticPr 80 CO2 BuildPr EtFnSpd CoilTp RaCFM HeadPr RtVlvPos LvWtrTp MdGsVPos HeadPrSt 90 CdCtrSg1 OaClSt OaHtSt WmupTg RhDewpSt EcoEnbSt RaTpOst ColTpOft LWAmbnt PreHtAmb 100 C02MinLv C02MaxLv InRhSt StatPrSt RfPrSt OACfmMin HiInRh ClHdPrSt HtHdPrSt LoClTpSt 110 HiClTpSt SaClRt SaHtRt ClLoRt ClHiRt HtLoRt HtHiRt CtrlMod DschgTp OaWtbl 120 OaDewPt SucPr CoilTpSt RetBydmp RaDmp RaRH SldAdOfs MdSelDb ClStgWdw HtStgWdw 130 MchClLkt MchHtLkt LoSaCf HiSaCf DfrSt LvH2OOst CO2Ost CTpHiAlm CTpLoAlm HpLkt 140 VFDClMin VFDHtMin VFDVtMin MaxEcoHt MaxEcoCO HpDfrInt AptDfr DuctPfDb RlfPrDb OaCfmDb 150 SZVAVFnI SaWmupSt SaCldnSt RehtEnbl EmHtEnbl RaTpAlm MisEM1 ColPfAlm CO2Alm DschgAlm 160 OaCfmAlm ExtCmSr SaCfmSr RaCfmSr MisMHGRV MisMDGAS Mis12Rly HiCtrlMd LoCtrlMd DigCmpCf 170 DigCmpLk HiHedPr H2OProf LoSucPr HiSucPr – – – – –

Table 4: VCB-X Data Array For Field Server

PT-LInk II BACnet4 Technical Guide 27 Zone 6. DATA ARRAYS Zone 6.3 VCM-X Modular & VCM-X WSHP Tulsa Data Arrays

VCM-X Modular Data Array For Field Server Offset 0 1 2 3 4 5 6 7 8 9 0 AppVer ClSt HtSt OaWtbl TpDmnd SpcTp SaTp RaTp OaTp DuctPr 10 OaRh UnitMode CtrlSts ClEnbl HtEnbl EcoEnbl FanDly PofCfg CO2Cfg MdHt2Ins 20 Rt2Ins OnRlys ExRlys12 ExRlys34 EcoPos VfdBwPos VfdExPos AlmSts AlmGrp1 AlmGrp2 30 AlmGrp3 SaTpAlm OaTpAlm SpcTpAlm MchClAlm MchHtAlm PofAlm DrtFAlm SmokeAlm LoSaAlm 40 HiSaAlm CtrlTpCF CtrlTpHF CtrlTp InRh InRhStM DptStM MdClPos MdHtPos MdHt2Pos 50 Rt2Pos OcpClSt OcpHtSt UnClOst UnHtOst WtblSt SaClSt SaHtSt WmupSt SpcTpOst 60 SaTpOst RaTpOst OaTpOst CoilTpSt DptSt InRhSt DuctPrSt RfPrSt SchdFrc OnRly1 70 OnRly2 OnRly3 OnRly4 OnRly5 ExRly1 ExRly2 ExRly3 ExRly4 ExRly5 ExRly6 80 ExRly7 ExRly8 ExRly9 ExRly10 ExRly11 ExRly12 ExRly13 ExRly14 ExRly15 ExRly16 90 CO2St MinEcoSt CO2Level ByPasDmp RaDmp RfPr OaDwpt CoilTp SaTpStM PreHtSp 100 OaCFM EtCFM SaCFM OACfmSt OACfmRs OACfmStM MdCmp2 HdPr1 HdPr2 CdFan1 110 CdFan2 RmVFDPos SaClRt SaHtRt ClLoRt ClHiRt HtLoRt HtHiRt T24EcFb T24TpAlm 120 T24NEWS T24EWISN T24DpAlm T24ExsOA RaTpAlm AlmGrp5 HdPr22 HdPr22 CdFan21 CdFan22

Table 5: VCM-X Modular Data Array For Field Server

VCM-X WSHP (Tulsa) Data Array For Field Server Offset 0 1 2 3 4 5 6 7 8 9 0 AppVer ClSt HtSt OaWtbl TpDmnd SpcTp SaTp RaTp OaTp DuctPr 10 OaRh UnitMode CtrlSts ClEnbl HtEnbl EcoEnbl FanDly PofCfg CO2Cfg MdHt2Ins 20 Rt2Ins OnRlys ExRlys12 ExRlys34 EcoPos VfdBwPos VfdExPos AlmSts AlmGrp1 AlmGrp2 30 AlmGrp3 SaTpAlm OaTpAlm SpcTpAlm MchClAlm MchHtAlm PofAlm DrtFAlm SmokeAlm LoSaAlm 40 HiSaAlm CtrlTpCF CtrlTpHF CtrlTp InRh InRhStM DptStM MdClPos MdHtPos MdHt2Pos 50 Rt2Pos OcpClSt OcpHtSt UnClOst UnHtOst WtblSt SaClSt SaHtSt WmupSt SpcTpOst 60 SaTpOst RaTpOst OaTpOst CoilTpSt DptSt InRhSt DuctPrSt RfPrSt SchdFrc OnRly1 70 OnRly2 OnRly3 OnRly4 OnRly5 ExRly1 ExRly2 ExRly3 ExRly4 ExRly5 ExRly6 80 ExRly7 ExRly8 ExRly9 ExRly10 ExRly11 ExRly12 ExRly13 ExRly14 ExRly15 ExRly16 90 CO2St MinEcoSt CO2Level ByPasDmp RaDmp RfPr OaDwpt CoilTp SaTpStM PreHtSp 100 OaCFM EtCFM SaCFM OACfmSt OACfmRs OACfmStM MdCmp2 HdPr1 HdPr2 CdFan1 110 CdFan2 WaterTpA WaterTpB A1LSPAlm A1LktAlm A2LSPAlm A2LktAlm B1LSPAlm B1LktAlm B2LSPAlm 120 B2LktAlm LWT1Alm LWT2Alm POWF1Alm POWF2Alm ComMAlm RmVFDPos SaClRt SaHtRt ClLoRt 130 ClHiRt HtLoRt HtHiRt T24EcFb T24TpAlm T24NEWS T24EWISN T24DpAlm T24ExsOA RaTpAlm 140 AlmGrp5 HdPr22 HdPr22 CdFan21 CdFan22 – – – – –

Table 6: VCM-X WSHP (Tulsa) Data Array For Field Server

28 PT-LInk II BACnet4 Technical Guide Zone 6. DATA ARRAYS Zone 6.4 VCM-X WSHP (Coil) & VCM Data Arrays

VCM-X WSHP (Coil) Data Array For Field Server Offset 0 1 2 3 4 5 6 7 8 9 0 AppVer ClSt HtSt OaWtbl TpDmnd SpcTp SaTp RaTp OaTp DuctPr 10 OaRh UnitMode CtrlSts ClEnbl HtEnbl EcoEnbl FanDly PofCfg CO2Cfg MdHt2Ins 20 Rt2Ins OnRlys ExRlys12 ExRlys34 EcoPos VfdBwPos VfdExPos AlmSts AlmGrp1 AlmGrp2 30 AlmGrp3 SaTpAlm OaTpAlm SpcTpAlm MchClAlm MchHtAlm PofAlm DrtFAlm SmokeAlm LoSaAlm 40 HiSaAlm CtrlTpCF CtrlTpHF CtrlTp InRh InRhStM DptStM MdClPos MdHtPos MdHt2Pos 50 Rt2Pos OcpClSt OcpHtSt UnClOst UnHtOst WtblSt SaClSt SaHtSt WmupSt SpcTpOst 60 SaTpOst RaTpOst OaTpOst CoilTpSt DptSt InRhSt DuctPrSt RfPrSt SchdFrc OnRly1 70 OnRly2 OnRly3 OnRly4 OnRly5 ExRly1 ExRly2 ExRly3 ExRly4 ExRly5 ExRly6 80 ExRly7 ExRly8 ExRly9 ExRly10 ExRly11 ExRly12 ExRly13 ExRly14 ExRly15 ExRly16 90 CO2St MinEcoSt CO2Level ByPasDmp RaDmp RfPr OaDwpt CoilTp SaTpStM PreHtSp 100 OaCFM EtCFM SaCFM OACfmSt OACfmRs OACfmStM MdCmp2 HdPr1 HdPr2 CdFan1 110 CdFan2 WaterTpA A1LSPAlm A1LktAlm B1LSPAlm B1LktAlm LWT1Alm POWF1Alm ComMAlm RmVFDPos 120 SaClRt SaHtRt ClLoRt ClHiRt HtLoRt HtHiRt T24EcFb T24TpAlm T24NEWS T24EWISN 130 T24DpAlm T24ExsOA RaTpAlm – – – – – – –

Table 7: VCM-X WSHP (Coil) Data Array For Field Server

VCM-X Data Array For Field Server Offset 0 1 2 3 4 5 6 7 8 9 0 AppVer ClSt HtSt OaWtbl TpDmnd SpcTp SaTp RaTp OaTp DuctPr 10 OaRh UnitMode CtrlSts ClEnbl HtEnbl EcoEnbl FanDly PofCfg CO2Cfg MdHt2Ins 20 Rt2Ins OnRlys ExRlys12 ExRlys34 EcoPos VfdBwPos VfdExPos AlmSts AlmGrp1 AlmGrp2 30 AlmGrp3 SaTpAlm OaTpAlm SpcTpAlm MchClAlm MchHtAlm PofAlm DrtFAlm SmokeAlm LoSaAlm 40 HiSaAlm CtrlTpCF CtrlTpHF CtrlTp InRh InRhStM DptStM MdClPos MdHtPos MdHt2Pos 50 Rt2Pos OcpClSt OcpHtSt UnClOst UnHtOst WtblSt SaClSt SaHtSt WmupSt SpcTpOst 60 SaTpOst RaTpOst OaTpOst CoilTpSt DptSt InRhSt DuctPrSt RfPrSt SchdFrc OnRly1 70 OnRly2 OnRly3 OnRly4 OnRly5 ExRly1 ExRly2 ExRly3 ExRly4 ExRly5 ExRly6 80 ExRly7 ExRly8 ExRly9 ExRly10 ExRly11 ExRly12 ExRly13 ExRly14 ExRly15 ExRly16 90 CO2St MinEcoSt CO2Level ByPasDmp RaDmp RfPr OaDwpt CoilTp SaTpStM PreHtSp 100 OaCFM EtCFM SaCFM OACfmSt OACfmRs OACfmStM SaClRt SaHtRt ClLoRt ClHiRt 110 HtLoRt HtHiRt – – – – – – – –

Table 8: VCM-X Data Array For Field Server

PT-LInk II BACnet4 Technical Guide 29 Zone 6. DATA ARRAYS ZoneZone 6.5 SA & VCM Data Arrays

SA Controller Data Array For Field Server Offset 0 1 2 3 4 5 6 7 8 9 0 AppVer ClSt HtSt TpDmnd SpcTp SaTp DuctPr UnitMode CtrlSts ClEnbl 10 HtEnbl EcoEnbl FanDly MdHt2Ins Rt2Ins EcoPos VfdBwPos SaTpAlm SpcTpAlm MchClAlm 20 MchHtAlm PofAlm DrtFAlm LoSaAlm HiSaAlm CtrlTpCF CtrlTpHF CtrlTp InRh InRhStM 30 DptStM MdClPos MdHtPos MdHt2Pos Rt2Pos OcpClSt OcpHtSt UnClOst UnHtOst SaClSt 40 SaHtSt WmupSt SpcTpOst SaTpOst CoilTpSt DptSt InRhSt DuctPrSt SchdFrc OnRly1 50 OnRly2 OnRly3 OnRly4 OnRly5 ExRly1 ExRly2 ExRly3 ExRly4 ExRly5 ExRly6 60 ExRly7 ExRly8 ExRly9 ExRly10 ExRly11 ExRly12 ExRly13 ExRly14 ExRly15 ExRly16 70 CoilTp SaTpStM PreHtSp EaTp EwTp EaRH HdPr1 HdPr2 CoilTp2 EaDpt 80 WSEByp WSEByp2 MdCmp2 CoilTpSt CdPos1 CdPos2 EaTpAlm EmerAlm PoWFAlm DrnAlm 90 EaTpOst EwTpOst SaClRt SaHtRt ClLoRt ClHiRt HtLoRt HtHiRt – –

Table 9: SA Controller Data Array For Field Server

VCM Data Array For Field Server Offset 0 1 2 3 4 5 6 7 8 9 0 AppVer ClSt HtSt OaWtbl TpDmnd SpcTp SaTp RaTp OaTp DuctPr 10 OaRh UnitMode CtrlSts ClDmnd HtDmnd DehmDmnd ClEnbl HtEnbl EcoEnbl FanDly 20 WmupDmnd PofCfg CO2Cfg MdHt2Ins Rt2Ins OnRlys ExRlys12 ExRlys34 EcoPos VfdBwPos 30 VfdExPos AlmSts AlmGrp1 AlmGrp2 AlmGrp3 SaTpAlm OaTpAlm SpcTpAlm MchClAlm MchHtAlm 40 PofAlm DrtFlAlm SmokeAlm LoSaAlm HiSaAlm CtrlTpCF CtrlTpHF CtrlTp InRh InRhStM 50 DptStM MdClPos MdHtPos MdHt2Pos Rt2Pos OcpClSt OcpHtSt UnClOst UnHtOst WtblSt 60 SaClSt SaHtSt WmupSt SpcTpOst SaTpOst RaTpOst OaTpOst CoilTpSt DptSt InRhSt 70 DuctPrSt RfPrSt SchdFrc OnRly1 OnRly2 OnRly3 OnRly4 OnRly5 ExRly1 ExRly2 80 ExRly3 ExRly4 ExRly5 ExRly6 ExRly7 ExRly8 ExRly9 ExRly10 ExRly11 ExRly12 90 ExRly13 ExRly14 ExRly15 ExRly16 CO2St MinEcoSt CO2Level ByPasDmp RaDmp RfPr 100 OaDwpt CoilTp SaTpStM PreHtSp – – – – – –

Table 10: VCM Data Array For Field Server

30 PT-LInk II BACnet4 Technical Guide Zone 7. PARAMETER TABLES ZoneZone 7.1 VCCX2 BACnet® Parameters

® NOTE: Objects labeled AI and BI are read-only. Objects BACnet Properties for the VCCX2 Controller labeled AV are read/writeable. Objects labeled AV are Parameter Name Object Description Limits read/writeable. You cannot write directly to Sensor Space SpcTp AI: 72 Current value of the Inputs. Temperature Space Temperature Sensor. Space InRh AI: 67 Current value of the Humidity Space Humidity. BACnet® Properties for the VCCX2 Controller Return Air RaTp AI: 64 Current value of the Parameter Name Object Description Limits Temperature Return Temperature Application AppVer AI: 99 Current version of the Sensor. Software software in the unit. Return Air RaRH AI:337 Current value of the Version Humidity Return Air Humidity. Control CtrlMod AI: 97 Configured unit See Outdoor Air OaTp AI: 54 Current value of the Mode application. Control Temperature Outdoor Air Mode Temperature Sensor. Bits on page 46. Outdoor Air OaRh AI: 52 Current value of the Humidity Outdoor Humidity Control CtrlSts AI: 4 Current Occupied/ See Sensor. Status Unoccupied Status. Control Status Outdoor Air OaWtbl AI: 55 Current calculated Bits on Wetbulb Outdoor Wetbulb page 46. Temperature. Hvac Mode HvacMode AI: 175 Current operational See Outdoor Air OaDewPt AI: 332 Current Calculated status. HVAC Dewpoint Outdoor Air Dewpoint Mode Bits Temperature. on page 46. Supply Air SaStRt AI: 290 Supply Air Temp Control CtrlTp AI: 9 Current value of the Setpoint Setpoint Reset Input Temperature Control Temperature Reset Voltage Signal Sensor. Static DuctPr AI: 14 Current Duct Static Mode ClSt AI: 7 Cooling Mode En- Pressure Pressure Cooling able Setpoint Mirror Duct Static FanVfdSg AI: 292 Current Duct Static Setpoint (adjusted by the Space Control Control Signal ( Sensor Slide adjust- Signal VFD) ment and/or Night Setback offsets.) Building BuildPr AI: 272 Current value of the Pressure Building Pressure Mode HtSt AI: 31 Heating Mode En- Sensor. Heating able Setpoint Mirror Setpoint (adjusted by the Space Building RlfSgl AI: 293 Current Building Pres- Sensor Slide adjust- Pressure sure Control Signal ment and/or Night Control Setback offsets.) Signal Sensor Slide SldAdOfs AI: 338 Amount of Current Outdoor OaCFM AI: 193 Current Outdoor Adjust Effect Sensor Slide Offset Airflow Airflow Measurement. Supply Air SaTp AI: 83 Current value of the Supply SaCFM AI: 195 Current Supply Airflow Temperature Supply Air Airflow Measurement. Temperature sensor Return RaCFM AI: 275 Current Return Airflow Supply Air SaTpSt AI: 81 Current SAT Cooling Airflow Measurement. Setpoint or Heating Setpoint if there is no reset source; Exhaust EtCFM AI: 194 Current Exhaust Current Airflow Airflow Measurement calculated SAT setpoint with Reset Source Carbon CO2 AI: 271 Current Indoor Dioxide CO Level. Controlling CoilTpSt AI: 334 This is the current 2 Coil Temp calculated Coil Suction Desired EcoPos AI: 16 Current Modulating Setpoint Temperature target Signal to the Econo- during Position mizer . Dehumidification Mode. Economizer T24EcFb AI: 384 Title 24 current posi- Feedback tion of feedback from Position Economizer actuator.

PT-LInk II BACnet4 Technical Guide 31 Zone 7. PARAMETER TABLES Zone 7.1 VCCX2 BACnet® Parameters

BACnet® Properties for the VCCX2 Controller BACnet® Properties for the VCCX2 Controller Parameter Name Object Description Limits Parameter Name Object Description Limits Return RaDmp AI: 154 Current Signal to the A1 Suction A1SucPr AI: 404 Current A1 Damper Return Air Damper if Pressure Suction Pressure Position using Return Air A2 Suction A2SucPr AI: 405 Current Compressor A2 Bypass. Pressure Suction Pressure Return RetBydmp AI: 335 Current Signal to the Bypass Return Air Bypass A1 Head A1HdPr AI: 406 Current Compressor A1 Position Damper if using Return Pressure Head Pressure Air Bypass. A2 Head A2HdPr AI: 407 Current Compressor A2 Modulating MdClSgl AI: 294 Current percentage of Pressure Head Pressure Cooling the Modulating Chilled A1 Saturation A1SauTp AI: 408 Current Compressor A1 Position Water Signal. Temperature Coil Saturation Modulating MdHtSgl AI: 295 Current percentage of Temperature Heat Position the Modulating A2 Saturation A2SauTp AI: 409 Current Compressor A2 Heating signal Temperature Coil Saturation (Hot Water or SCR Temperature heat). A1 Suction A1SucTp AI: 410 Current Compressor A1 Preheater PrHtLv1 AI: 296 Current Preheater Line Suction Line Temperature Leaving Air Leaving Air Temperature Temp #1 Temperature #1 A2 Suction A2SucTp AI: 411 Current Compressor A2 Preheater PrHtLv2 AI: 297 Current Preheater Line Suction Line Leaving Air Leaving Air Temperature Temperature Temp #2 Temperature #2 A1 A1CondST AI: 260 Current Compressor A1 Preheater PrHtEnt AI: 298 Current Entering Condenser Suction Line Entering Air Air Temperature for Suction Temp Temperature Temp Preheater () (Heat Pump) Preheater PrHtRst AI: 299 Current Voltage A2 A2CondST AI: 261 Current Compressor A2 Setpoint Re- Reset Input Value for Condenser Suction Line set Voltage Preheater Suction Temp Temperature Preheater PrHtScr AI: 300 Current Modulat- (Heat Pump) (Heat Pump) SCR Output ing Heat Signal for A1 A1SupHt AI: 412 Current Compressor A1 Signal Preheater Superheat Superheat Temperature Preheater PrHtPwm AI: 301 Current PWM Output Temperature PWM Output Signal for Preheater A2 A2SupHt AI: 413 Current Compressor A2 Signal Superheat Superheat Temperature Mod Hot Gas Rt2Pos AI: 60 Current position of Temperature Reheat Valve MHGRV Modulating Condenser A1CondSH AI: 262 Current Compressor A1 Position Hot Gas Reheat Valve. A1 Superheat Temperature Mod Gas MdGsV- AI: 274 Current position of Superheat (Heat Pump) Heat Valve Pos MODGAS Modulating (Heat Pump) Position Gas Valve Control. Condenser A2CondSH AI: 263 Current Compressor A2 A1 A1Cmpr AI: 400 Current Compressor A2 Superheat Temperature Compressor A1 Modulating Cool- Superheat (Heat Pump) Signal ing Signal (Heat Pump) A1 A1ExpVv AI: 414 Current position of A2 A2Cmpr AI: 401 Current Compressor Expansion Compressor A1 Compressor A2 Modulating Cool- Valve Expansion Valve Signal ing Signal Position A1 A1Cndr AI: 402 Current A1 Condenser A2 A2ExpVv AI: 415 Current position of Condenser Signal Expansion Compressor A2 Signal Valve Posi- Expansion Valve A2 A2Cndr AI: 403 Current A2 Condenser tion Condenser Signal Condenser A1CondEV AI: 264 Current position of Signal A1 Condenser A1 Expansion Expansion Valve Valve Position

32 PT-LInk II BACnet4 Technical Guide Zone 7. PARAMETER TABLES Zone 7.1 VCCX2 BACnet® Parameters

BACnet® Properties for the VCCX2 Controller BACnet® Properties for the VCCX2 Controller Parameter Name Object Description Limits Parameter Name Object Description Limits Condenser A2CondEV AI: 265 Current position of B2 Superheat B2SupHt AI: 443 Current Compressor B2 A2 Expansion Condenser A2 Temperature Superheat Temperature Valve Position Expansion Valve A1 Discharge A1DscTp AI: 416 Current Compressor A1 Condenser B1CondSH AI: 268 Current Compressor B1 Temperature Discharge Temperature B1 Superheat Superheat Temperature (Heat Pump) (Heat Pump) A2 Discharge A2DscTp AI: 417 Current Compressor A2 Condenser B2CondSH AI: 269 Current Compressor B2 Temperature Discharge Temperature B2 Superheat Superheat Temperature A1 Leaving ALevWtr AI: 418 Current A1 Leaving (Heat Pump) (Heat Pump) Water Temp Water Temperature for B1 Expansion B1ExpVv AI: 444 Current position of WSHP Valve Position Compressor B1 B1 B1Cmpr AI: 430 Current Compressor B1 Expansion Valve Compressor Modulating Cooling B2 Expansion B2ExpVv AI: 445 Current position of Signal Signal Valve Position Compressor B2 B2 B2Cmpr AI: 431 Current Compressor B2 Expansion Valve Compressor Modulating Cooling Condenser B1CondEV AI: 380 Current position of Signal Signal B1 Expansion Condenser B1 B1 Condenser B1Cndr AI: 432 Current B1 Condenser Valve Position Expansion Valve Signal Signal Condenser B2CondEV AI: 381 Current position of B2 Condenser B2Cndr AI: 433 Current B2 Condenser B2 Expansion Condenser B2 Signal Signal Valve Position Expansion Valve B1 Discharge B1DscTp AI: 446 Current Compressor B1 B1 Suction B1SucPr AI: 434 Current Compressor B1 Temperature Discharge Temperature Pressure Suction Pressure B2 Discharge B2DscTp AI: 447 Current Compressor B2 B2 Suction B2SucPr AI: 435 Current Compressor B2 Temperature Discharge Temperature Pressure Suction Pressure B1 Leaving BLevWtr AI: 448 Current B1 Leaving B1 Head B1HdPr AI: 436 Current Compressor B1 Water Temp Water Temperature for Pressure Head Pressure WSHP B2 Head B2HdPr AI: 437 Current Compressor B2 C1 C1Cmpr AI: 460 Current Compressor C1 Pressure Head Pressure Compressor Modulating Cooling Signal Signal B1 Saturation B1SauTp AI: 438 Current C2 C2Cmpr AI: 461 Current Compressor C2 Temperature Compressor B1 Coil Compressor Modulating Cooling Saturation Temperature Signal Signal B2 Saturation B2SauTp AI: 439 Current C1 Condenser C1Cndr AI: 462 Current C1 Condenser Temperature Compressor B2 Coil Signal Signal Saturation Temperature B1 Suction B1SucTp AI: 440 Current Compressor B1 C2 Condenser C2Cndr AI: 463 Current C2 Condenser Line Suction Line Signal Signal Temperature Temperature C1 Suction C1SucPr AI: 464 Current Compressor C1 B2 Suction B2SucTp AI: 441 Current Compressor B2 Pressure Suction Pressure Line Suction Line Temperature Temperature C2 Suction C2SucPr AI: 465 Current Compressor C2 Pressure Suction Pressure B1 Condenser B1CondST AI: 266 Current Compressor B1 Suction Temp Suction Line C1 Head C1HdPr AI: 466 Current Compressor C1 (Heat Pump) Temperature Pressure Head Pressure (Heat Pump) B2 Condenser B2CondST AI: 267 Current Compressor B2 C2 Head C2HdPr AI: 467 Current Compressor C2 Suction Temp Suction Line Pressure Head Pressure (Heat Pump) Temperature (Heat Pump) B1 Superheat B1SupHt AI: 442 Current Compressor B1 Temperature Superheat Temperature

PT-LInk II BACnet4 Technical Guide 33 Zone 7. PARAMETER TABLES Zone 7.1 VCCX2 BACnet® Parameters

BACnet® Properties for the VCCX2 Controller BACnet® Properties for the VCCX2 Controller Parameter Name Object Description Limits Parameter Name Object Description Limits C1 Saturation C1SauTp AI: 468 Current Compressor C1 C2 Discharge C2DscTp AI: 477 Current Compressor C2 Temperature Coil Saturation Temperature Discharge Temperature Temperature C1 Leaving CLevWtr AI: 478 Current C1 Leaving C2 Saturation C2SauTp AI: 469 Current Compressor C2 Water Temp Water Temperature for Temperature Coil Saturation WSHP Temperature D1 D1Cmpr AI: 200 Current Compressor D1 C1 Suction C1SucTp AI: 470 Current Compressor C1 Compressor Modulating Cooling Line Suction Line Signal Signal Temperature Temperature D2 D2Cmpr AI: 201 Current Compressor D2 C2 Suction C2SucTp AI: 471 Current Compressor C2 Compressor Modulating Cooling Line Suction Line Signal Signal Temperature Temperature D1 Condens- D1Cndr AI: 202 Current D1 C1 C1CondST AI: 382 Current Compressor C1 er Signal Condenser Signal Condenser Suction Line D2 Condens- D2Cndr AI: 203 Current D2 Condenser Suction Temp Temperature er Signal Signal (Heat Pump) (Heat Pump) C2 C2CondST AI: 383 Current Compressor C2 D1 Suction D1SucPr AI: 204 CurrentCompressor D1 Condenser Suction Line Pressure Suction Pressure Suction Temp Temperature D2 Suction D2SucPr AI: 205 Current Compressor D2 (Heat Pump) (Heat Pump) Pressure Suction Pressure C1 Superheat C1SupHt AI: 472 Current Compressor C1 Temperature Superheat Temperature D1 Head D1HdPr AI: 206 Current Compressor Pressure D1 Head Pressure

C2 Superheat C2SupHt AI: 473 Current Compressor C2 D2 Head D2HdPr AI: 207 Current Compressor Temperature Superheat Temperature Pressure D2 Head Pressure

Condenser C1CondSH AI: 385 Current Compressor C1 D1 Saturation D1SauTp AI: 208 Current Compressor D1 C1 Superheat Superheat Temperature Temperature Coil Saturation (Heat Pump) (Heat Pump) Temperature Condenser C2CondSH AI: 386 Current Compressor C2 D2 Saturation D2SauTp AI: 209 Current Compressor D2 C2 Superheat Superheat Temperature Temperature Coil Saturation (Heat Pump) (Heat Pump) Temperature C1 C1ExpVv AI: 474 Current position of D1 Suction D1SucTp AI: 210 Current Compressor D1 Expansion Compressor C1 Line Suction Line Valve Expansion Valve Temperature Temperature Position D2 Suction D2SucTp AI: 211 Current Compressor D2 C2 C2ExpVv AI: 475 Current position of Line Suction Line Expansion Compressor C2 Temperature Temperature Valve Expansion Valve D1 D1CondST AI: 389 Current Compressor D1 Position Condenser Suction Line Condenser C1CondEV AI: 387 Current position of Suction Temp Temperature C1 Condenser C1 (Heat Pump) (Heat Pump) Expansion Expansion Valve D2 D2CondST AI: 390 Current Compressor D2 Valve Condenser Suction Line Position Suction Temp Temperature Condenser C2CondEV AI: 388 Current position of (Heat Pump) (Heat Pump) C2 Condenser C2 D1 Superheat D1SupHt AI: 212 Current Compressor D1 Expansion Expansion Valve Temperature Superheat Temperature Valve Position C1 Discharge C1DscTp AI: 476 Current Compressor C1 Temperature Discharge Temperature

34 PT-LInk II BACnet4 Technical Guide Zone 7. PARAMETER TABLES Zone 7.1 VCCX2 BACnet® Parameters

BACnet® Properties for the VCCX2 Controller BACnet® Properties for the VCCX2 Controller Parameter Name Object Description Limits Parameter Name Object Description Limits D2 Superheat D2SupHt AI: 213 Current Compressor D2 Occupied OcpClSt AV: 42 If the control tem- 1°F 110°F Temperature Superheat Temperature Cooling perature rises one -17.2°C 43.3°C Setpoint deadband above Condenser D1CondSH AI: 391 Current Compressor D1 this setpoint, the D1 Superheat Superheat Temperature control will acti- (Heat Pump) (Heat Pump) vate the cooling Condenser D2CondSH AI: 392 Current Compressor D2 demand. This D2 Superheat Superheat Temperature setpoint does (Heat Pump) (Heat Pump) not determine the mode in Oc- D1 D1ExpVv AI: 214 Current position of cupied operation Expansion Compressor D1 if the unit is Valve Expansion Valve configured for Position Supply Air Cool- D2 D2ExpVv AI: 215 Current position of ing or Supply Air Expansion Compressor D2 Tempering. Valve Expansion Valve Occupied OcpHtSt AV: 43 If the control 1°F 110°F Position Heating temperature drops -17.2°C 43.3°C Condenser D1CondEV AI: 393 Current position of Setpoint one deadband D1 Condenser D1 below this set- Expansion Expansion Valve point, the control Valve will activate the Position heating demand. This setpoint does Condenser D2CondEV AI: 394 Current position of not determine D2 Condenser D2 the mode in Oc- Expansion Expansion Valve cupied operation Valve if the unit is Position configured for D1 Discharge D1DscTp AI: 216 Current Compressor D1 Supply Air Temperature Discharge Temperature Cooling or Supply Air D2 Discharge D2DscTp AI: 217 Current Compressor D2 Tempering. Temperature Discharge Temperature Hood On OaClSt AV: 45 This is the Cool- 1°F 110°F D1 Leaving DLevWtr AI: 218 Current D1 Leaving Cooling ing Mode Enable -17.2°C 43.3°C Water Temp Water Temperature for Setpoint Setpoint used WSHP only in Hood On Mode or Space Alarm Status AlmSts AI: 1 Indicates an alarm 0 = No Temperature condition. Alarms Control of High 1 = Percentage Alarm(s) Outdoor Air Units Present or VAV Outdoor AI: 145 Current Outdoor Tempering. Enthalpy Hood On OaHtSt AV: 46 This is the Heat- 1°F 110°F Plenum AI: 146 Reserved Heating ing Mode Enable -17.2°C 43.3°C Pressure Setpoint Setpoint used only in Hood On Return Fan AI: 147 Reserved Mode or Space Speed Temperature Control of High Plenum AI: 148 Reserved Percentage Calculated Outdoor Air Units Setpoint or VAV Return Air AI: 149 Current value of Return Tempering. Enthalpy Air Enthalpy. Status

PT-LInk II BACnet4 Technical Guide 35 Zone 7. PARAMETER TABLES Zone 7.1 VCCX2 BACnet® Parameters

BACnet® Properties for the VCCX2 Controller BACnet® Properties for the VCCX2 Controller Parameter Name Object Description Limits Parameter Name Object Description Limits Unoccupied UnClOst AV: 124 During the Unoc- 0°F 30°F Min Coil LoClTpSt AV: 163 This is the lowest 35°F 70°F Cooling cupied Mode of 0°C 16.6°C Setpoint that the Coil Tem- 1.7°C 21.1°C Offset Operation, this Reset Limit perature will be Setpoint offsets reset to during the Occupied Space Humidity Cooling Setpoint Reset of the Coil up by this Suction Tempera- user-adjustable ture Setpoint. If amount. If you do no coil not want Cooling temperature reset to operate during is required, this the Unoccupied value should be Mode, use the set the same as default setting the Max Coil of 30°F for this Reset Limit. setpoint. Supply SaClSt AV: 77 Supply Air Cool- 30°F 80°F Unoccupied UnHtOst AV:125 During the Unoc- 0°F 30°F Air Cooling ing -1.1°C 26.6°C Heating cupied Mode of 0°C 16.6°C Setpoint Setpoint. If Sup- Offset Operation, this ply Air Reset is Setpoint offsets configured this the Occupied is the Low SAT Heating Setpoint Cooling Reset down by this Value. user-adjustable Supply SaHtSt AV: 78 Supply Air Heat- 40°F 240°F amount. If you do Air Heating ing 4.5°C 115.5°C not want Setpoint Setpoint. If Sup- Heating to oper- ply Air Reset is ate during the Un- configured this occupied Mode, is the Low SAT use the default Heating Reset setting of 30°F Value. for this setpoint. Max SAT SaClRt AV: 324 If Supply Air 0°F 100°F Mode MdSelDb AV: 339 This value is 0°F 10°F Cooling Reset is -17.7°C 37.7°C Select added to and 0°C 5.5°C Setpoint configured this Deadband subtracted from Reset Limit is the High SAT the HVAC Mode Cooling Reset Setpoints to Value. create a control deadband range. Max SAT SaHtRt AV: 325 If Supply Air Re- 0°F 250°F Heating set is configured -17.7°C 121.1°C Max Coil HiClTpSt AV: 160 This is the highest 35°F 70°F Setpoint this is the High Setpoint that the Coil Tem- 1.7°C 21.1°C Reset Limit SAT Heating Reset Limit perature will be Reset Value. reset to during Space Humidity Supply Air SaClSgWd AV: 166 In Cooling Mode, 1°F 30°F Reset of the Coil Cooling if the Supply 0.6°C 16.6°C Suction Staging Air Temperature Temperature Window drops below the Setpoint. If no Active Supply Air coil temperature Cooling Setpoint reset is required, minus this Stag- this value should ing Window, a be set the same Cooling Stage as the Min Coil will be deacti- Reset Limit. vated after its Minimum Run Time.

36 PT-LInk II BACnet4 Technical Guide Zone 7. PARAMETER TABLES Zone 7.1 VCCX2 BACnet® Parameters

BACnet® Properties for the VCCX2 Controller BACnet® Properties for the VCCX2 Controller Parameter Name Object Description Limits Parameter Name Object Description Limits Supply Air SaHtSgWd AV: 167 In Heating Mode, 1°F 50°F Mechanical ClLkOut AV: 172 Mechanical Cool- -30°F 100°F Heating if the Supply Air 0.6°C 27.7°C Cooling ing will be locked -34.4°C 37.7°C Staging Temperature rises Outdoor Air out when the Out- Window above the Active Lockout door Air Tempera- Supply Air ture is below this Heating Setpoint Setpoint. plus this Staging Mechanical HtLkOut AV: 173 Mechanical Heat- -30°F 150°F Window, a Heat- Heating ing will be locked -34.4°C 65.5°C ing Stage will be Outdoor Air out when the Out- deactivated after Lockout door Air Tempera- its Minimum Run ture is above this Time. Setpoint. Warm-Up WmupSt AV: 91 If Morning 50°F 90°F Low Supply LoSaC- AV: 344 Cooling will be 0°F 100°F Target Warm-Up is 10°C 32.2°C Temp Cut- uOf disabled if the Sup- -17.7°C 37.7°C Tempera- configured, then off Alarm ply Air ture upon entering oc- Temperature falls (See AV: cupied mode, the below this value. 336 for Warm-Up Mode See sequence for Cool-Down will be activated more details. Target Tem- if the Return perature) Air is below this High Sup- HiSaC- AV: 345 Heating will be 0°F 250°F temperature by ply Temp uOf disabled if the Sup- -17.7°C 121.1°C one degree. Cutoff ply Air Alarm Temperature rises Warm- WmupSaSt AV: 168 During Morning 40°F 240°F above this value. Up Mode Warm-Up, the 4.5°C 115.5°C See sequence for Supply Air Supply Air more details. Setpoint Temperature will be controlled to Preheater PrHtClSt AV: 174 If the Preheater is 35°F 90°F this Setpoint. Cooling enabled, and the -17.7°C 32.2°C Mode unit is in the Cool- Setpoint ing Mode, this setpoint will be Cool-Down ClDnSaSp AV: 171 During Morning 30°F 80°F sent to the Preheat- Mode Cool-Down, the -1.1°C 26.6°C X Controller to Supply Air Supply Air control Leaving Air Setpoint Temperature will Temperature. be controlled to Preheater PrHtVtSt AV: 176 If the Preheater is 35°F 90°F this Setpoint. Venting enabled, and the -17.7°C 32.2°C Mode unit is in the Vent Setpoint Mode, this setpoint will be sent to the Mechanical ClLkOut AV: 172 Mechanical Cool- -30°F 100°F Preheat-X Control- Cooling ing will be locked -34.4°C 37.7°C ler to control Leav- Outdoor Air out when the ing Air Lockout Outdoor Air Tem- Temperature. perature is below this Setpoint. Preheater PrHtHtSt AV: 177 If the Preheater is 35°F 90°F Heating enabled, and the -17.7°C 32.2°C Mode unit is in the Heat- Setpoint ing Mode, this Mechanical HtLkOut AV: 173 Mechanical Heat- -30°F 150°F setpoint will be Heating ing will be locked -34.4°C 65.5°C sent to the Preheat- Outdoor Air out when the X Controller to Lockout Outdoor Air Tem- control Leaving Air perature is above Temperature. this Setpoint.

PT-LInk II BACnet4 Technical Guide 37 Zone 7. PARAMETER TABLES Zone 7.1 VCCX2 BACnet® Parameters

BACnet® Properties for the VCCX2 Controller BACnet® Properties for the VCCX2 Controller Parameter Name Object Description Limits Parameter Name Object Description Limits Outdoor Air DptSt AV: 13 On an MUA unit, 35°F 80°F Return Air RaTpOst AV: 65 If the Return -100°F 100°F Dewpoint if the OA dewpoint 1.7°C 26.6°C Sensor Temperature Sen- -55.5°C 55.5°C Setpoint rises above this Calibration sor is setpoint, Offset reading incorrectly, Dehumidification is you can use this initiated. option to enter an Economizer EcoEnbl AV: 283 The economizer -30°F 80°F offset temperature Enable is enabled if the -34.4°C 26.6°C to adjust the Sen- Setpoint outdoor drybulb, sor’s dewpoint, or wet- Temperature. bulb temperature Outdoor Air OaTpOst AV: 53 If the Outdoor -100°F 100°F falls below this Sensor Temperature -55.5°C 55.5°C setpoint. Calibration Sensor is reading Heat Wheel HtWh- AV: 178 The unit will go 0°F 50°F Offset incorrectly, you can Defrost Defr into Heat Wheel -17.7°C 10°C use this option to Enable Defrost if the Out- enter an offset tem- Setpoint door Air is below perature to adjust this setpoint. the Sensor’s Temperature. PreHeat PreHtSp AV: 196 If the Supply Fan -30°F 70°F Carbon CO2Ost AV: 348 If the CO Sen- -500 500 Enable is energized this is -34.4°C 21.1°C 2 Setpoint the temperature at Dioxide sor is which the Preheat Sensor reading incorrectly, Relay will activate Calibration you can use this or the Preheat-X Offset option to enter Controller will an offset value to activate. Operates adjust the Sensor’s CO reading. only in the 2 Occupied Mode. Low LWAmbnt AV: 285 Temperature at -30°F 70°F Sensor Slide MaxSldEf AV: 179 If your space sen- 0°F 10°F Ambient which the Low -34.4°C 21.1°C Offset Max sor has the optional 0°C 5.5°C Protection Ambient Relay Effect slide Setpoint will activate in the adjustment feature, Occupied or Unoc- this is the maxi- cupied Mode. mum amount the SAT Cool LoClRsSr AV: 164 If doing Supply Air -30°F 150°F slide can adjust the Setpoint Re- Setpoint Reset, this -34.4°C 65.5°C current heating and set Source is the Low Reset cooling setpoints Low Limit Source value in up or down with Cooling that will full deflection of correspond to the slide. the Supply Air Space Sen- SpcTpOst AV: 71 If the Space Tem- -100°F 100°F Cool High Reset sor Calibra- perature -55.5°C 55.5°C Setpoint. tion Offset Sensor is reading SAT Cool HiClRsSr AV: 161 If doing Supply Air 0°F 150°F incorrectly, you Setpoint Re- Setpoint Reset, this -17.7°C 65.5°C can use this option set Source is the High Reset to enter an offset High Limit Source value in temperature to Cooling that will adjust the Sensor’s correspond to the Temperature. Supply Air Cooling Supply Air SaTpOst AV: 80 If the Supply Air -100°F 100°F Setpoint (Low Sensor Temperature Sen- -55.5°C 55.5°C Reset). Calibration sor is Offset reading incorrectly, you can use this option to enter an offset temperature to adjust the Sen- sor’s Temperature.

38 PT-LInk II BACnet4 Technical Guide Zone 7. PARAMETER TABLES Zone 7.1 VCCX2 BACnet® Parameters

BACnet® Properties for the VCCX2 Controller BACnet® Properties for the VCCX2 Controller Param- Name Object Description Limits Param- Name Object Description Limits eter eter SAT Heat LoHtRsSr AV: 165 If doing Supply -30°F 150°F Minimum VFDClMin AV: 319 In Single Zone 0 100 Setpoint Air Setpoint -34.4°C 65.5°C Main Fan VAV configura- Reset Reset, this is the VFD in tion, this is the Source Low Reset Source Cooling fan speed at Low Limit value in Heating Mode which the VFD that will will start when correspond to the Cooling is initi- Supply Air Heat- ated. In a VAV ing High Reset configuration this Setpoint. is the lowest fan SAT Heat HiHtRsSr AV: 162 If doing Supply 0°F 150°F speed allowed Setpoint Air Setpoint -17.7°C 65.5°C in the Cooling Reset Reset, this is Mode. In CAV Source the High Reset and MUA High Limit Source value in configurations Heating that will this should be set correspond to the to 100%. Supply Air Heat- Minimum VFDHtMin AV: 320 In Single Zone 0 100 ing Setpoint (Low Main Fan VAV configura- Reset). VFD in tion, this is the Control CTpHiAlO AV: 169 If the temperature 0°F 50°F Heating fan speed at Tempera- of the controlling 0°C 27.7°C Mode which the VFD ture High sensor rises above will start when Alarm the Occupied Heating is initi- Offset Cooling Setpoint ated. In a VAV by this value, configuration this a High Control is the lowest fan Temp Alarm will speed allowed occur. Only ap- in the Heating plies if configured Mode. In CAV for Space or and MUA con- Return Air Temp figurations this Control, or as should be set to Single Zone VAV. 100%. Control CTpLoAlO AV: 170 If the temperature 0°F 50°F Minimum VFDVtMin AV: 322 Speed at which 0 100 Tempera- of the controlling 0°C 27.7°C Main Fan the VFD will op- ture Low sensor falls below VFD in erate in the Vent Alarm the Occupied Vent Mode Mode in Single Offset Heating Setpoint Zone VAV. by this value, Maximum MaxEcoHt AV: 353 Max position the 0 100 a Low Control Economizer Economizer Temp Alarm will in Heating Damper can open occur. Only ap- Mode to in Supply Air plies if configured Tempering during for Space or Heating Mode. Return Air Temp Takes priority Control, or as over Max Posi-

Single Zone VAV. tion in High CO2. Heat Pump HpLkt AV: 351 Compressor Heat -30°F 100°F Minimum MinEco AV: 182 The minimum po- 0 100 Compres- will be locked -34.4°C 37.7°C Economizer sition of the Out- sor Heat out below this Position door Air damper Lockout setpoint. in the Occupied Maximum MaxVfd AV: 180 In Single Zone 0 100 Mode. This can Main Fan VAV configura- be reset upwards VFD in tion, this is the based on indoor CO levels. SZ VAV max fan speed 2 Heating the VFD can Mode modulate up to in Heat Mode.

PT-LInk II BACnet4 Technical Guide 39 Zone 7. PARAMETER TABLES Zone 7.1 VCCX2 BACnet® Parameters

BACnet® Properties for the VCCX2 Controller BACnet® Properties for the VCCX2 Controller Param- Name Object Description Limits Parameter Name Object Description Limits eter Indoor InRhHiSt AV: 184 On indoor con- 0 100 Maximum MaxEco AV: 181 The maximum 0 100 Humidity trolled (non MUA) Economizer value the Econo- Setpoint units, this is the

CO2 Reset mizer Minimum High Reset Humidity setpoint Limit Position can be Limit at which the unit reset up to initiates

during CO2 over- Dehumidification. ride. During Coil Temp Minimum CO2MinLv AV: 287 This is the thresh- 0 2000 Reset, this is the highest Space RH Carbon old CO2 level at Dioxide which the value that cor- Setpoint Economizer Min responds to the Low Damper Position Coil Temp Setpoint. Setpoint will Duct Static DuctPrSt AV: 152 Current Static .10 3.0 begin to be reset Pressure Pressure Setpoint. higher. Setpoint

Maximum CO2MaxLv AV: 288 This is the CO2 0 2000 Duct Static DuctPrDb AV: 357 Value above and be- .01 .5 Carbon level at which Pressure low the Duct Static Dioxide the Economizer Control Pressure Setpoint Setpoint Min Damper Deadband where no control Position will change occurs. be reset to the Building RfPrSt AV: 118 Building Pressure -.20 3.0 Economizer Max Pressure Setpoint or Exhaust Position in High Control Duct Static CO . In between 2 Setpoint Pressure Setpoint. the Min and Building RlfPrDb AV: 358 Value above and .01 .5 Max CO2 levels the Economizer Pressure below the Building Min Damper Control Pressure Setpoint Position will be Deadband or the Exhaust Duct proportionally Static Pressure reset between the Setpoint where configured Min no control change Damper Position occurs. and the Max Minimum OACfm- AV: 291 Minimum Outdoor .10K 200K Position in Outdoor Min Airflow CFM High CO2. CFM Re- Setpoint Indoor InRhLoSt AV: 183 On indoor 0 100 quirement Humidity controlled (non Outdoor OaCfmDb AV: 359 Controls rate of 10 1000 Setpoint MUA) units, this CFM change for damper Low Reset is the Humidity Control signal. As OA CFM Limit setpoint at which Deadband moves further from the unit leaves setpoint within this Dehumidification. window, the damper During Coil Temp makes a larger Reset, this is the change. lowest Space RH value that Single SZVAVFnI AV: 360 The Integral 0 10 corresponds to the Zone VAV Constant for Single High Coil Temp Fan Speed Zone VAV Fan Setpoint. Integral Control. Relay RlRnT- AV: 185 If any configured 0 30000 Run-time mLm relay’s run time ex- Hours ceeds this number of Warning hours of operation, Limit a warning alarm is generated so that periodic maintenance can be performed.

40 PT-LInk II BACnet4 Technical Guide Zone 7. PARAMETER TABLES Zone 7.1 VCCX2 BACnet® Parameters

BACnet® Properties for the VCCX2 Controller BACnet® Properties for the VCCX2 Controller Parameter Name Object Description Limits Parameter Name Object Description Limits Cooling HdPrCl AV: 186 Head Pressure Set- 250 450 Space SpcTVal AV: 277 If the controller is 0°F 120°F Mode Head point in the Cooling Tempera- configured for this 48.8°C Pressure Mode. ture operation, the user Setpoint Value can write a Space Dehum Hd- AV: 187 Head Pressure 250 450 Sensor value. Mode Head PrDhum Setpoint in the Space SpcRhVal AV: 278 If the controller is 0 100 Pressure Dehumidification Humidity configured for this Setpoint Mode. Value operation, the user Superheat SupHtSp AV: 188 Superheat Setpoint. 1°F 30°F can write a Space Setpoint 1°C 17°C Humidity Sensor value. Maximum OaCfm- AV: 189 Maximum Outdoor .10K 200K Indoor RH AV: 279 Reserved Outdoor Max Airflow CFM Set- Calibration CFM Re- point in High CO2. Offset quirement (Reserved) Schedule SchdFrc AV: 66 0 = Auto (uses con- 0 2 Force troller’s schedule) Relief Fan RelFanOv AV: 280 Override to force 0% 100% 1 = Forced VFD the VFD to this Occupied percentage speed. 2 = Forced Unoc- Configuring “Auto” Auto=65535 cupied will restore normal Hvac Mode Hvac- AV: 190 Overrides normal 0=Auto unit control of the Override MdOv controller operation 1=Vent VFD speed. in order to force the 2=Cool Relief RelPrVal AV: 281 If the controller is -.5 .5 unit into this desired 3=Heat Pressure configured for this mode. Configur- 4=Vent Value operation, the user ing for “Auto” will Dehum. can write Building restore normal unit 5=Cool Pressure Sensor control of the mode Dehum. value. of operation. 6=Heat Dehum. Carbon CO2Val AV: 282 If the controller is 0 3000 Dioxide configured for this Fan VFD FanVfdOv AV: 191 Override to force 0% 100% Value operation, the user Override the VFD to this Auto=65535 can write a CO percentage speed. 2 Sensor value. Configuring “Auto” will restore normal Outdoor Air OaTVal AV: 283 If the controller is -40°F 150°F unit control of the Tempera- configured for this -40°C 65.5°C VFD speed. ture operation, the user Outdoor Air EcoOv AV: 192 Overrides all other 0% 100% Value can write an Out- Damper Outdoor Sensor value. Override Damper Outdoor Air OaRhVal AV: 284 If the controller is 0 100 position commands Humidity configured for this so as to maintain Auto=65535 Value operation, the this fixed NOTE: If user can write an position. Configur- Economizer Outdoor ing for “Auto” will is enabled and Humidity Sensor restore normal unit a value less value. control of the Out- than 100% is High Level HiLvlEtp AV: 321 Reserved 10 50 door Air Damper/ written, com- Enthalpy Economizer opera- pressors will (Reserved) tion. disable. Supply SaStOv AV: 276 This will override 0°F 200°F Setpoint whatever setpoint 93.3°C Override the Supply Air Tem- Low Level LoLvlEtp AV: 347 Reserved 10 50 perature is currently Enthalpy being controlled to. (Reserved)

PT-LInk II BACnet4 Technical Guide 41 Zone 7. PARAMETER TABLES Zone 7.1 VCCX2 BACnet® Parameters

BACnet® Properties for the VCCX2 Controller BACnet® Properties for the VCCX2 Controller Parameter Name Object Description Limits Parameter Name Object Description Limits Max MxPPrRst AV: 323 Reserved 0.1 0.2 Cool-Down ClDnTgTp AV: 336 If Morning Cool- 50°F 90°F Plenum Target Down is config- 10°C 32.2°C Pressure Tempera- ured then upon Setpoint ture entering occupied Reset Limit (See AV: 91 mode, the Cool- Min Plenum MnPPrRst AV: 326 Reserved 0.1 0.2 for Warm- Down Mode will Pressure Up Target be activated if the Setpoint Tempera- return air is above Reset Limit ture) this temperature by one degree. Enthalpy EtpEnSp AV: 327 If configured 25 35 Enable for Comparative BTU/ BTU/ Warm-Up WmUpOv AV: 340 Commands the 1=Command Setpoint Enthalpy Econo- lb. lb. Override unit into Morning Warm-Up Mode mizer Control, the Warm-Up Mode. OA Enthalpy must Cool Down ClDnOv AV: 341 Commands the 1=Command be below this Override unit into Morning Cool-Down Mode setpoint by the Cool-Down Mode Enthalpy Enable Return Air RAHiLmtP AV: 342 If the Return Air 60 100 Deadband before High Limit Temperature goes the OA/RA En- Protection above this limit, thalpy comparison (for Voting the unit will revert will be utilized to Units or CV to Return Air enable the Econo- Units Only) Control. mizer. Return Air RALoLmtP AV: 343 If the Return Air 45 70 Enthalpy EtpEnDb AV: 329 The OA Enthalpy 0.3 1.5 Low Limit Temperature goes Enable must be below the BTU/ BTU/ Protection below this limit, Deadband Enthalpy Enable lb. lb. (for Voting the unit will revert Setpoint by this Units or CV to Return Air amount, and the Units Only) Control. OA Enthalpy must be below the RA Cooling ClEnbl BI: 6 Status that indi- Enthalpy by this Enabled cates amount to utilize Status Mechanical Cool- the Economizer. ing is enabled based Maximum MxStaRst AV: 330 As the most open 0.01 3.00 on the Static VAV damper rises “WG “WG Cooling Lockout. Setpoint above 80%, the Reset Limit static setpoint will Heating HtEnbl BI: 30 Status that reset up to this Enabled indicates that maximum limit. Status Mechanical Heat- ing is Minimum MnStaRst AV: 331 As the most open 0.01 3.00 enabled based Static VAV damper “WG “WG on the Setpoint drops below 80%, Heating Lockout. Reset Limit the static setpoint will reset down Economizer EcoEnbl BI: 15 Status that indi- to this minimum Enabled cates reset limit. Status the Economizer is enabled based on Static StaRstIv AV: 333 The Reset Interval 10 min 60 min the Economizer Setpoint is how often the Enable Setpoint. Reset setpoint reset Interval calculation occurs. Aux Heat AuxHtEn BI: 305 Heat Pump Auxil- This must be an Enabled iary Heat enabled. infrequent event Status so the default is Emergency EmHtEnbl BI: 364 Shows the Emer- 15 minutes. Heat gency Heat is Enabled enabled based on Status the Compressor Heating Lockout.

42 PT-LInk II BACnet4 Technical Guide Zone 7. PARAMETER TABLES Zone 7.1 VCCX2 BACnet® Parameters

BACnet® Properties for the VCCX2 Controller BACnet® Properties for the VCCX2 Controller Parameter Name Object Description Parameter Name Object Description Fan Proof of Pof BI: 56 Proof of Airflow Binary Input Mechanical HtAlm BI: 315 Heating Mode has been Airflow Status Status Heating Alarm initiated but the Supply Air Exhaust Hood EtHood BI: 306 Exhaust Hood On/Off Binary Temperature has not risen 5°F w/ On/Off Status Input Status in a user-adjustable time period. Alarms on the MODGAS-X & Remote Forced RmOc BI: 307 Remote Forced Occupied Mode Preheat-X Controller will gener- Occupied Binary Input Status ate this alarm. This alarm does Status not apply to Modulating Hot Remote Forced RmCl BI: 308 Remote Forced Cooling Mode Water or Steam Heating. Cooling Status Binary Input Status Fan Proving FanAlm BI: 316 Alarm that indicates an Remote Forced RmHt BI:309 Remote Forced Heating Mode Alarm Airflow failure from the Main Heating Status Binary Input Status Fan. Heating and Cooling will be disabled. Remote Force RmDhum BI: 310 Remote Force Dehum Status Dehumidification Mode Binary Dirty Filter DrtFlAlm BI: 96 Alarm that indicates Input Status Alarm the filters are dirty. Bad Supply Air SaTpAlm BI: 2 Alarm that indicates a failure of Emergency EmerAlm BI: 219 Alarm that indicates Sensor the Supply Air Sensor. Shutdown that Emergency Shutdown has Alarm been activated. Will shut the unit Bad Return Air RaTpAlm BI: 365 Alarm that indicates a failure of down. Sensor the Return Air Sensor. Relay RlRnTm BI: 317 Indicates when any of the con- Bad Outdoor OaTpAlm BI: 311 Failure of the Outdoor Air Tem- Runtime Warn- figured relays exceeds Air Sensor perature Sensor. ing a configured number of hours of runtime. Can be Bad Space SpcT- BI: 101 Failure of the Space used to schedule service, etc. Temp Sensor pAlm Temperature Sensor. If Space is the controlling Economizer EcoMs BI: 318 Title 24 operation sensor, the unit will shut down. Missing Alarm indicates missing economizer feedback.

Bad Carbon CO2Alm BI: 368 Failure of the CO2 Sensor. Economizer EcoFlA BI: 231 Title 24 Air Temperature Sensor Dioxide Title 24 Failure. Sensor Failure A Bad Building RefAlm BI: 312 Alarm indicating missing or Economizer EcoFlB BI: 232 Title 24 Not Economizing when Pressure Sensor failed Building Pressure Sensor. Title 24 it should. Failure B Bad Outdoor OaCf- BI: 370 An Outdoor Airflow Airflow mAlm Sensor is configured, but not Economizer EcoFlC BI: 234 Title 24 Economizing when it Sensor detected. Title 24 should not. Failure C Bad Exhaust EaCf- BI: 313 An Exhaust Airflow Economizer EcoFlD BI: 235 Title 24 Damper Not Airflow mAlm Sensor is configured, but not Title 24 Modulating. Sensor detected. Failure D

Bad Supply SaCf- BI: 372 A Supply Airflow Sensor is Economizer EcoFlE BI: 236 Title 24 Excess Outdoor Air. Airflow mAlm configured, but not detected. Title 24 Sensor Failure E Bad Return RaCf- BI: 373 A Return Airflow High Supply HiCfAlm BI: 237 The Supply Air has risen above Airflow mAlm Sensor is configured, but not Temp Cutoff the Hi SAT Cutoff Setpoint. Heat- Sensor detected. ing stages will deactivate and the fan continues to run. This alarm is Mechanical ClAlm BI: 314 Compressor Relays are enabled generated. Cooling Alarm but the Supply Air Temperature has not fallen 5°F w/in a user- adjustable time period. This does not apply to Modulating Cooling.

PT-LInk II BACnet4 Technical Guide 43 Zone 7. PARAMETER TABLES Zone 7.1 VCCX2 BACnet® Parameters

BACnet® Properties for the VCCX2 Controller BACnet® Properties for the VCCX2 Controller Parameter Name Object Description Parameter Name Object Description Low Supply LoCfAlm BI: 238 The Supply Air has fallen below On Board OnRly4 BI: 130 Current Status of Temp Cutoff the Low SAT Cutoff Setpoint. Relay 4 Configurable Relay #4 on Main Cooling stages will deactivate. Board After 10 minutes, the fan will On Board OnRly5 BI: 131 Current Status of deactivate and this alarm is Relay 5 Configurable Relay #5 on Main generated. Board High Control HiMdAlm BI: 239 Occurs when the On Board OnRly6 BI: 259 Current Status of Mode Alarm Controlling Sensor Relay 6 Configurable Relay #6 on Main Temperature rises above the Board Cooling Mode Enable Setpoint plus the Control Mode High On Board OnRly7 BI: 250 Current Status of Alarm Offset. Applies only to Relay 7 Configurable Relay #7 on Main Space or Return Air Tempera- Board ture controlled units. On Board OnRly8 BI: 251 Current Status of Low Control LoMdAlm BI: 240 Occurs when the Relay 8 Configurable Relay #8 on Main Mode Alarm Controlling Sensor Board Temperature falls below the Expansion Em1Rly1 BI: 252 Current Status of Heating Mode Enable Setpoint Board EM1 Configurable Relay #1 on EM1 minus the Relay 1 Board Control Mode Low Alarm Offset. Applies only to Space Expansion Em1Rly2 BI: 253 Current Status of or Return Air Temperature Board EM1 Configurable Relay #2 on EM1 controlled units. Relay 2 Board Missing BadMod1 BI: 241 Module #1 is bad or Expansion Em1Rly3 BI: 254 Current Status of Refrigerant missing. Board EM1 Configurable Relay #3 on EM1 Module #1 Relay 3 Board Expansion Em1Rly4 BI: 256 Current Status of Missing BadMod2 BI: 242 Refrigerant Module #2 is bad or Board EM1 Configurable Relay #4 on EM1 Refrigerant missing. Relay 4 Board Module #2 Expansion Em1Rly5 BI: 257 Current Status of Missing BadMod3 BI: 243 Refrigerant Module #3 is bad or Board EM1 Configurable Relay #5 on EM1 Refrigerant missing. Relay 5 Board Module #3 12 Relay ExRly1 BI: 133 Current Status of Missing BadMod4 BI: 244 Refrigerant Module #4 is bad or Expansion Configurable Relay #1 on 12 Refrigerant missing. Board Relay 1 Relay Board Module #4 12 Relay ExRly2 BI: 134 Current Status of Missing BadPreBd BI: 245 Preheater Module is bad or Expansion Configurable Relay #2 on 12 Preheater missing. Board Relay 2 Relay Board Board 12 Relay ExRly3 BI: 135 Current Status of Missing BadRhtBd BI: 246 The MHGR board is Expansion Configurable Relay #3 on 12 Reheat Board configured but not Board Relay 3 Relay Board detected. 12 Relay ExRly4 BI: 136 Current Status of Missing Mod BadMgsBd BI: 247 The MODGAS board is config- Expansion Configurable Relay #4 on 12 Gas Board ured but not detected. Board Relay 4 Relay Board Missing EM1 BadEm- BI: 248 EM1 Expansion Board is bad or 12 Relay ExRly5 BI: 137 Current Status of Board 1Bd missing. Expansion Configurable Relay #5 on 12 Board Relay 5 Relay Board Missing 12 BadExRly BI: 249 The 12 Relay Expansion Board Relay is configured but not detected. 12 Relay ExRly6 BI: 138 Current Status of Expansion Expansion Configurable Relay #6 on 12 Board Board Relay 6 Relay Board On Board OnRly1 BI: 127 Current Status of Main Fan 12 Relay ExRly7 BI: 139 Current Status of Relay 1 Main Relay #1 on Main Board Expansion Configurable Relay #7 on 12 Fan Board Relay 7 Relay Board On Board OnRly2 BI: 128 Current Status of 12 Relay ExRly8 BI: 140 Current Status of Relay 2 Configurable Relay #2 on Main Expansion Configurable Relay #8 on 12 Board Board Relay 8 Relay Board On Board OnRly3 BI: 129 Current Status of Relay 3 Configurable Relay #3 on Main Board

44 PT-LInk II BACnet4 Technical Guide Zone 7. PARAMETER TABLES Zone 7.1 VCCX2 BACnet® Parameters

BACnet® Properties for the VCCX2 Controller BACnet® Properties for the VCCX2 Controller Parameter Object Description Parameter Object Description 12 Relay ExRly9 BI: 141 Current Status of Refrigerant M1Rly5 BI: 429 Current Status of Expansion Configurable Relay #9 on 12 Relay Module 1 Relay #5 Board Relay 9 Board Relay 5 12 Relay ExRly10 BI: 142 Current Status of B1 B1CmpEn BI: 449 Current Status of Enable Signal to Expansion Configurable Relay #10 on 12 Compressor Compressor B1 Board Relay 10 Relay Board Enable 12 Relay ExRly11 BI: 143 Current Status of B2 B2CmpEn BI: 450 Current Status of Enable Signal to Expansion Configurable Relay #11 on 12 Compressor Compressor B2 Board Relay 11 Relay Board Enable 12 Relay ExRly12 BI: 144 Current Status of B1 B1Alm BI: 451 Indicates an RSM alarm is present Expansion Configurable Relay #12 on 12 Compressor on the B1 circuit. Board Relay 12 Relay Board Alarms Preheater PreHtEn BI: 302 Status of Preheater B2 B2Alm BI: 452 Indicates an RSM alarm is present Enable Status Enable Input Compressor on the B2 circuit. Preheater PreHtEm BI: 303 Status of Preheater Alarms Emergency Emergency Shutdown Input B1-2 Defrost BDfrSw BI: 453 Outside Coil B1/B2 Temp Switch Shutdown Switch for Defrost Mode Preheater PreHtBi3 BI: 304 Status of Preheater B1-2 Water BWtrPf BI: 454 B1/B2 Switch for Water Proof of Spare Binary Binary Input #3 Proof of Flow Input #3 Flow MODGAS MdGsEn BI: 257 Status of MODGAS B1-4 BEm- BI: 396 Emergency Shutdown Input on Enable Status Controller Emergency ShtDn Module B MHGR RehtEnbl BI: 363 Status of MHGRV Shutdown Enable Status Controller (RSMD) A1 A1C- BI: 419 Current Status of Enable Signal to Refrigerant M2Rly1 BI: 455 Current Status of Compressor mpEn Compressor A1 Module 2 Compressor 1 Enable Relay. Enable Relay 1 A2 A2C- BI: 420 Current Status of Enable Signal to Refrigerant M2Rly2 BI: 456 Current Status of Compressor mpEn Compressor A2 Module 2 Compressor 2 Enable Relay. Enable Relay 2 A1 A1Alm BI: 421 Indicates an RSM alarm is present Refrigerant M2Rly3 BI: 457 Current Status of Compressor on the A1 circuit. Module 2 Condenser 1 Enable Relay. Alarms Relay 3 A2 A2Alm BI: 422 Indicates an RSM alarm is present Refrigerant M2Rly4 BI: 458 Current Status of Compressor on the A2 circuit. Module 2 Relay #4 Alarms Relay 4 A1-2 Defrost ADfrSw BI: 423 Outside Coil A1/A2 Temp Switch Refrigerant M2Rly5 BI: 459 Current Status of Switch for Defrost Mode Module 2 Relay #5 Relay 5 A1-2 Water AWtrPf BI: 424 A1/A2 Water Proof of Flow Switch Proof of C1 C1CmpEn BI: 220 Current Status of Enable Signal to Flow Compressor Compressor C1 Enable A1-4 AEm- BI: 395 Emergency Shutdown Input on Emergency ShtDn Module A C2 C2CmpEn BI: 221 Current Status of Enable Signal to Shutdown Compressor Compressor C2 (RSMD) Enable Refrigerant M1Rly1 BI: 425 Current Status of C1 C1Alm BI: 222 Indicates an RSM alarm is present Module 1 Compressor A1 Enable Compressor on the C1 circuit. Relay 1 Relay. Alarms Refrigerant M1Rly2 BI: 426 Current Status of C2 C2Alm BI: 223 Indicates an RSM alarm is present Module 1 Compressor A2 Enable Relay. Compressor on the C2 circuit. Relay 2 Alarms Refrigerant M1Rly3 BI: 427 Current Status of C1-2 Defrost CDfrSw BI: 224 Outside Coil C1/C2Temp Switch Module 1 Condenser 1 Enable Relay. Switch for Defrost Mode Relay 3 C1-2 Water CWtrPf BI: 225 C1/C2 Switch for Water Proof of Refrigerant M1Rly4 BI: 428 Current Status of Proof of Flow Module 1 Relay #4 Flow Relay 4

PT-LInk II BACnet4 Technical Guide 45 Zone 7. PARAMETER TABLES Zone 7.1 VCCX2 BACnet® Parameters

BACnet® Properties for the VCCX2 Controller BACnet® Properties for the VCCX2 Controller Parameter Object Description Parameter Object Description C1-4 CEmShtDn BI: 397 Emergency Shutdown Input on Preheater PreHtAlm BI: 258 Preheater Alarm Indicator Emergency Module C Alarm Shutdown EF/RA Fan EFRAFPOF BI: 346 Exhaust Fan / Return Fan Proof of (RSMD) POF Flow Alarm Refrigerant M3Rly1 BI: 485 Current Status of Module 3 Compressor 1 Enable Relay. Relay 1 Refrigerant M3Rly2 BI: 486 Current Status of Module 3 Compressor 2 Enable Relay. 7.1.1 VCCX2 BACnet® Property Relay 2 Identifier: Refrigerant M3Rly3 BI: 487 Current Status Module 3 Condenser 1 Enable Relay. Relay 3 BACNETPropertyIdentifier : Refrigerant M3Rly4 BI: 488 Current Status of ::= ENUMERATED { Module 3 Relay #4 VccxControlModeBits Relay 4 Supply Air Cooling Only (0), Refrigerant M3Rly5 BI: 489 Current Status of Supply Air Tempering (1), Module 3 Relay #5 Outdoor Temperature Control (2), Relay 5 Return Air Constant Volume Mode (3), D1 D1CmpEn BI: 220 Current Status of Enable Signal to Space Temp Constant Volume Mode (4), Compressor Compressor D1 Space Temp w/ High OA Content (5), Enable Single Zone VAV (6) D2 D2CmpEn BI: 221 Current Status of Enable Signal to } Compressor Compressor D2 Enable VccxControlStatusBits ::= ENUMERATED { D1 D1Alm BI: 222 Indicates an RSM alarm is present on Unoccupied (0) Compressor the D1 circuit. Alarms Occupied (1), Override Mode (2), D2 D2Alm BI: 223 Indicates an RSM alarm is present on Compressor the D2 circuit. Holiday Unoccupied (3), Alarms Holiday Occupied (4), D1-2 Defrost DDfrSw BI: 224 Outside Coil D1/D2 Temp Switch Forced Occupied (5), Switch for Defrost Mode Forced Unoccupied (6), D1-2 Water DWtrPf BI: 225 D1/D2 Switch for Water Proof of Remote Contact Occupied (7) Proof of Flow Reserved (8) Flow Reserved (9) D1-4 DEmShtDn BI: 398 Emergency Shutdown Input on Reserved (10) Emergency Module D Shutdown OA Damper Calibration (11) (RSMD) } Refrigerant M4Rly1 BI: 226 Current Status of Module 4 Compressor 1 Enable Relay VccxHVACModeStatusBits ::= ENUMERATED { Relay 1 Off (0), Refrigerant M4Rly2 BI: 227 Current Status of Vent Mode (1), Module 4 Compressor 2 Enable Relay Cooling Mode (2), Relay 2 Heating Mode (3), Refrigerant M4Rly3 BI: 228 Current Status of Vent RH Mode (4), Module 4 Condenser 1 Enable Cooling RH Mode (5), Relay 3 Relay Heating RH Mode (6), Refrigerant M4Rly4 BI: 229 Current Status of Module 4 Relay #4 Warm Up Mode (7), Relay 4 Purge Mode (8), Refrigerant M4Rly5 BI: 230 Current Status of Defrost Mode (9), Module 4 Relay #5 Cool Down Mode (10) Relay 5 }

46 PT-LInk II BACnet4 Technical Guide Zone 7. PARAMETER TABLES Zone 7.2 VCB-X BACnet Parameters

BACnet Properties for the VCB-X Controller NOTE: Objects labeled AI and BI are read-only. Objects labeled AV are read/writeable. You cannot write directly Param- Name Object Description Limits to Sensor Inputs. eter

CO2 CO2 AI:271 Current CO2 Level.

BACnet Properties for the VCB-X Controller CO2 CO2Ost AV: 348 If the CO2 -500 500 Sensor Sensor is reading ppm ppm Param- Name Object Description Limits Calibration incorrectly, you eter Deadband can use this Bad or Mis12Rly BI: 376 The 12 Relay Offset option to enter Missing 12 Expansion Board an offset value Relay is configured but to adjust the

Expansion not detected. Sensor’s CO2 Board. reading.

Alarm AlmGrp1 AI: 104 See Alarm CO2 CO2MinLv AV:287 This is the 0 2000

Group 1 Group Bits on Minimum threshold CO2 page 58. Setpoint level at which the Economizer Alarm AlmGrp2 AI: 105 See Alarm Min Damper Group 2 Group Bits on Position page 58. Setpoint will Alarm AlmGrp3 AI: 106 See Alarm begin to be reset Group 3 Group Bits on higher. page 58. CO2 CO2 AV:288 This is the CO2 0 2000 Alarm AlmSts AI: 1 Indicates that 0 = Off Maximum MaxLv level at which Status there is an alarm. 1 = On Setpoint the Economizer See Alarm Min Damper Group Bits on Position will page 58. be reset to the Appli- AppVer AI: 99 Current version Economizer Max cation of the software Position in High CO . In between Software in the unit. 2 Version the Min and Max CO2 levels Unit Mode UnitMode AI:123 See Unit Mode the Economizer Bits on Min Damper page 58. Position will be Building BuildPr AI:272 Current value of proportionally Pressure the Building reset between the Pressure Sensor. configured Min Damper Position Building RfPrSt AV:118 Current Building -.20 .20 and the Max Pressure Pressure Position in High Setpoint Setpoint. CO2 . Building RfPrDb AV:358 Value above .01 0.1 Bad CO2 CO2Alm BI: 368 Failure of the Pressure and below the Sensor CO Sensor. Control Building Pres- 2 Deadband sure Setpoint Coil CoilTp AI: 181 Current coil where no control Tempera- temperature change occurs. ture reading. Coil ColTpOft AV:284 If the Coil -100 100 Tempera- Temperature ture Offset Sensor is reading incorrectly, use this offset to ad- just the Sensor’s Temperature. Bad Coil ColPrAlm BI: 367 Failure of the Pressure Coil Pressure Sensor Sensor. Will shut unit down.

PT-LInk II BACnet4 Technical Guide 47 Zone 7. PARAMETER TABLES Zone 7.2 VCB-X BACnet Parameters

BACnet Properties for the VCB-X Controller BACnet Properties for the VCB-X Controller Param- Name Object Description Limits Param- Name Object Description Limits eter eter Coil Tem- CoilTpSt AI: 334 This is the Control CtrlMod AI: 97 1=Constant perature current Mode Volume Setpoint calculated Coil 2=Supply Air Suction Cooling Only Temperature 3=Outdoor target during Temp Control Dehumidification 4=Single Zone Mode. VAV Low Coil LoClTpSt AV:295 This is the low- 35 70 5=Supply Air Tem- est that the Coil Tempering perature Temperature will 6=Space Temp Setpoint be reset to during Control w/ Limit Space Humid- High OA ity Reset of the Content Coil Suction Unoccupied Temperature Control CtrlTpCF BI: 108 Activated if the Setpoint. If no Tem- control tempera- coil temperature perature ture does not get reset is required, Cooling within 5°F to the this value should Failure occupied cooling be set the same setpoint in an as the High Coil hour in the cool- Temperature ing mode. This Setpoint. alarm is not used High Coil HiClTpSt AV:296 This is the high- 35 70 in 100% outside Tem- est that the Coil air units or sup- perature Temperature will ply air control. Setpoint be reset to during Control CtrlTpHF BI: 109 Activated if the Limit Space Humid- Tem- control tempera- ity Reset of the perature ture does not get Coil Suction Heating within 5°F to the Temperature Failure occupied heating Setpoint. If no setpoint in an coil temperature hour in the heat- reset is required, ing mode. This this value should alarm is not used be set the same in 100% outside as the Low Coil air units or sup- Temperature ply air control. Setpoint. High HiCtrlMd BI: 377 Occurs when the Com- DschgTp AI: 331 Current value of Control Controlling Sen- pressor the Compressor Mode sor Temperature Discharge Discharge Tem- Tempera- rises above the Tempera- perature Sensor. ture Cooling Mode ture Enable Setpoint Bad Com- DschgAlm BI: 369 Failure of the plus the Control pressor Digital Compres- Mode High Discharge sor Discharge Alarm Offset. Sensor Temperature Applies only to Sensor. Space or Return Air Temperature controlled units.

48 PT-LInk II BACnet4 Technical Guide Zone 7. PARAMETER TABLES Zone 7.2 VCB-X BACnet Parameters

BACnet Properties for the VCB-X Controller BACnet Properties for the VCB-X Controller Param- Name Object Description Limits Param- Name Object Description Limits eter eter Low Con- LoCtrlMd BI: 378 Occurs when the Controlling CTpLoAlm AV: 350 If the tempera- 0 50 trol Mode Controlling Sen- Sensor ture of the con- Tempera- sor Temperature Low Alarm trolling sensor ture falls below the Offset falls below the Heating Mode Occupied Heat- Enable Setpoint ing Setpoint by minus the Con- this value, a Low trol Mode Low Control Temp Alarm Offset. Alarm will oc- Applies only to cur. Only applies Space or Return if configured for Air Temperature Space or Return controlled units. Air Temp Con- Cooling ClLoRt AV: 326 If doing Supply 1 150 trol, or as Single Low Reset Air Setpoint Zone VAV. Source Reset, this is Control CtrlSts AI: 4 Current See Control the Low Reset Status operational Status Bits on Source value in status. page 58. Cooling that will Control CtrlTp AI: 9 Current value of correspond to Tempera- the control the Supply Air ture temperature Cool High Reset sensor. Setpoint. Cooling ClEnbl AI: 6 Status that Cooling ClHiRt AV: 327 If doing Supply 1 150 Enabled indicates High Reset Air Setpoint mechanical Source Reset, this is cooling is the High Reset enabled to Source value in operate. Cooling that will correspond to Mechani- MchClLkt AV: 342 The VCB-X -30 100 the Supply Air cal Cooling will Lockout Cooling Setpoint Lockout Mechanical (Low Reset). Cooling when the Outdoor Air Condenser CdCtrSg1 AI:280 Condenser Fan Temperature Control Signal 1 Status. is below this Signal Setpoint. Controlling CTpHiAlm AV: 349 If the tem- 0 50 Mechani- MchClAlm BI: 94 Compressor Re- Sensor perature of the cal Cooling lays are enabled High controlling sen- Alarm but the Supply Alarm sor rises above Air Temperature Offset the Occupied has not fallen Cooling Setpoint 5°F within a by this value, user-adjustable a High Control time period. This Temp Alarm does not apply will occur. Only for Modulating applies if config- Cooling. ured for Space or Return Air Cooling ClSt AI: 7 Occupied Temp Control, or Setpoint Cooling Mode as Single Zone Mirror Enable VAV. Setpoint.

PT-LInk II BACnet4 Technical Guide 49 Zone 7. PARAMETER TABLES Zone 7.2 VCB-X BACnet Parameters

BACnet Properties for the VCB-X Controller BACnet Properties for the VCB-X Controller Param- Name Object Description Limits Param- Name Object Description Limits eter eter Cool ClStgWdw AV: 340 In Cooling 1 30 Economiz- EcoPos AI: 16 Current position Staging Mode, if the er Position of the econo- Window Supply Air mizer damper. Temperature Max MaxEcoHt AV: 353 Max position 0% 60% drops below the Economiz- the Economizer Active Supply er in Heat Damper can Air Cooling Mode open in the Heat- Setpoint minus ing Mode. Takes this Staging Win- priority over dow, a Cooling Max Position in Stage will be High CO . deactivated after 2 its Minimum Max MaxEcoCO AV: 354 The maximum 0% 100% Run Time. Econo- value the mizer in Economizer Adaptive AptDfr AV: 356 Adjustment to 0 Min 30 High CO2 Minimum Posi- Defrost the Heat Pump Min Mode tion can be reset Interval Defrost Interval up to during CO2 Adjust- depending on override. ment whether the Defrost Mode Minimum MinEcoSt AV: 151 Minimum 0 100 lasts 10 minutes Econo- position of the or less than 10 mizer economizer in minutes. Position the occupied mode. Dewpoint RhDewpSt AV:282 On a MUA unit, 35 80 Setpoint if the outdoor Force FrcEcono AV: 267 Overrides all 0% 100% dewpoint rises Econo- other Outdoor Auto=65535 above this mizer Air Damper setpoint, the unit position com- will mands so as to activate Dehu- maintain this midification. fixed position. Configuring Digital DigCmpCf BI: 379 Occurs if the for “Auto” will Compres- digital compres- restore normal sor Cutoff sor discharge unit control of temperature rises the Outdoor Air above 268°F Damper/Econo- or the sensor mizer operation. is shorted. The compressor is Emergency EmHtEnbl BI: 364 Shows the Emer- disabled. Heat gency Heat is Enabled enabled based on Digital DigCmpLk BI: 380 Occurs if five the Compressor Com- Digital Compres- Heating Lockout. pressor sor Cutoffs Lockout occur within Exhaust EtCFM AI:194 Current Exhaust four hours. The Fan CFM Airflow compressor will Measurement be locked out. Missing ExtCfmSr BI: 371 Indicates that the Dirty Filter DrtFlAlm BI: 96 Alarm that Exhaust Exhaust CFM Alarm indicates the CFM Sensor is not filters are dirty. Sensor detected. Economiz- EcoEnbl AI: 15 Status that Exhaust EtFnSpd AI: 273 Current value of er Enabled indicates the Fan Speed the VFD relief economizer is fan signal. enabled. Missing MisEM1 BI: 366 Indicates that the Economiz- EcoEnbSt AV:283 The economizer -30 80 EM1 EM1 Expansion er Enable is enabled if the Expansion Module is not Setpoint outdoor drybulb, Module communicating dewpoint, or with the VCB-X wetbulb temper- Controller. ature falls below this setpoint.

50 PT-LInk II BACnet4 Technical Guide Zone 7. PARAMETER TABLES Zone 7.2 VCB-X BACnet Parameters

BACnet Properties for the VCB-X Controller BACnet Properties for the VCB-X Controller Param- Name Object Description Limits Param- Name Object Description Limits eter eter Fan FanDly AI: 25 Indicates the 0=No Request SAT HtLoRt AV: 328 If doing Supply 1 150 Starting current fan status 1=Fan Heating Air Setpoint Delay related to request Running Low Reset Reset, this is to run, fan 2=Fan Start Source the Low Reset starting delay or Delay Source value in POF failure. 3=POF Failure Heating that will Leaving LvH2OOst AV: 347 If the Leaving -100 100 correspond to the H2O Water Supply Air Offset Temperature Heating High Sensor is reading Reset Setpoint. incorrectly, use SAT HtHiRt AV: 329 If doing Supply 1 150 this to enter an Heating Air Setpoint offset to adjust High Reset Reset, this is the Sensor’s Source the High Reset Temperature. Source value in Water H2OProf BI: 382 Indicates no Cooling that will Proof Proof of Water correspond to of Flow Flow. the Supply Air Failure Cooling Setpoint (Low Reset). Force FrcHvacM AV: 262 Overrides 0=Auto HVAC normal controller 1=Vent Heating HtEnbl AI: 30 Status that Mode operation in 2=Cool Enabled indicates that order to force 3=Heat mechanical heat- the unit into this 4=Vent ing is enabled to desired mode. Dehum. operate. Configuring 5=Cool Heating HtSt AI: 31 Occupied for “Auto” will Dehum. Setpoint Heating Mode restore normal 6=Heat Mirror Enable Setpoint. unit control of Dehum. Heat HtStgWdw AV: 341 In the Heat- 1 50 the mode of Staging ing Mode, if operation. Window the Supply Air Head HeadPr AI:276 Current value of Temperature Pressure the Head rises above the Pressure Active Supply Reading. Air Heating Head HeadPrSt AI:279 Current Head Setpoint plus the Pressure Pressure Heating Stage Setpoint Setpoint. Off Window value, a Heating Head ClHdPrSt AV:293 This is the Head 240 420 stage will be Pressure Pressure Setpoint PSI PSI deactivated after Setpoint the unit will its Minimum in Cooling control to in the Run Time. Mode Cooling Mode. Mechani- MchHtLkt AV: 343 The VCB-X -30 150 Head HtHdPrSt AV:294 This is the Head 240 420 cal Heating will Lockout Pressure Pressure Setpoint PSI PSI Lockout Mechanical Setpoint the unit will Heating when in Reheat control to in the the Outdoor Air Mode Dehumidification Temperature Reheat Mode. is above this High Head HiHedPr BI: 381 Indicates the Setpoint. Pressure Head Pressure is too high.

PT-LInk II BACnet4 Technical Guide 51 Zone 7. PARAMETER TABLES Zone 7.2 VCB-X BACnet Parameters

BACnet Properties for the VCB-X Controller BACnet Properties for the VCB-X Controller Param- Name Object Description Limits Param- Name Object Description Limits eter eter Mechani- MchHtAlm BI: 95 Heating Mode Low LWAmbnt AV:285 Temperature at -30 70 cal Heating has been initiated Ambient which the Low Alarm but the Supply Relay Ambient Relay Air Temperature Setpoint will activate in has not risen the Occupied 5°F within a or Unoccupied user-adjustable Mode. time period. This Mode MdSelDb AV: 339 This Setpoint 1 10 does not apply Select is added to and for Modulating Deadband subtracted from Heating. the HVAC Mode Heat Pump HpLkt AV: 351 Compressor -30 100 Setpoints to de- Compres- Heating will be termine when the sor Heating locked out when unit enters and Outdoor the Outdoor Air leaves a mode of Lockout Temperature operation. is below this Modulat- MdClPos AI: 115 Current position Setpoint. ing of the modulat- Heat Pump HpDfrInt AV: 355 The Heat Pump 10 120 Cooling ing Defrost Defrost Interval Min Min Position cooling signal Interval is the length of ( or time that must digital be met between compressor). Defrost Modes. Modulat- MdGs AI:274 Current Heat Dfrst AV: 346 The unit will go 0 50 ing Gas VPos position of Wheel into Heat Wheel Valve MODGAS Defrost Defrost Mode Position modulating gas Setpoint when the Out- valve control. door Air is below Modulat- MdHtPos AI: 116 Current position this setpoint. ing of the modulat- Indoor InRh AI: 67 Current value Heating ing Humidity of the Indoor Position heating signal Humidity (hot water or Sensor. SCR heat). Indoor InRhSt AV:289 If Coil Temp 0 100 Missing MisMDGAS BI: 375 Alarm that Humidity Reset is being MODGAS indicates that Setpoint used this is also Module the MODGAS the lowest Space module is not RH value that communicating corresponds to with the VCB-X the Hi Coil Temp Controller. Setpoint. Morning WmupTg AV:281 If configured, 50 90 High HiInRh AV:292 During Coil 0 100 Warm-Up upon entering the Indoor Temp Reset, this Return Air occupied mode, Humidity is the highest Target the Warm-up Reset Space RH value Setpoint Demand will be Limit that corresponds activated if the to the Low Coil return air tem- Temp Setpoint. perature is one Indoor InRhStM AI: 114 Mirror of the degree below Humidity InRhSt “read this setpoint. Setpoint only.” Mirror Leaving LvWtrTp AI:278 Leaving Water Water Temperature Tempera- Value ture

52 PT-LInk II BACnet4 Technical Guide Zone 7. PARAMETER TABLES Zone 7.2 VCB-X BACnet Parameters

BACnet Properties for the VCB-X Controller BACnet Properties for the VCB-X Controller Param- Name Object Description Limits Param- Name Object Description Limits eter eter Occupied OcpClSt AV: 42 If the control 1 110 Outdoor OaTp AI: 54 Current value Cooling temperature rises Air Tem- of the Setpoint one degree above perature outdoor this setpoint, temperature the control will sensor. activate the Outdoor OaTpOst AV: 53 If the Outdoor -100 100 cooling demand. Air Temperature If the control Tempera- Sensor is reading temperature is ture Offset incorrectly, use the Supply Air this to enter an Sensor, then the offset to adjust cooling demand the Sensor’s is always active. Temperature. Occupied OcpHtSt AV: 43 If the control 1 110 Minimum OacfmDb AV: 359 The Deadband 10 1000 Heating temperature Outside is used both Setpoint drops one degree Air CFM above and below below Deadband the Outdoor Air this setpoint, CFM setpoint the control will to help prevent activate the hunting. heating demand. If the Outdoor OaTpAlm BI: 117 Indicates a control Air Tem- failure of the temperature perature Outdoor Air is the Supply Sensor Temperature Air Sensor, then Lost Sensor. there is no Outdoor OaWtbl AI: 55 Current calcu- heating Wetbulb lated value of the demand. outdoor wetbulb Hood On OaClSt AV:45 This is the Cool- 1 110 temperature. Outdoor ing Mode Enable Air Setpoint used Preheat PreHtAmb AV:286 If the Supply Fan -30 70 Cooling only in Hood On Relay is energized this Setpoint Mode. Setpoint is the tempera- Hood On OaHtSt AV:46 This is the Heat- 1 110 ture at which the Outdoor ing Mode Enable Preheat Relay Air Setpoint used will activate. Heating only in Hood On Operates only Setpoint Mode. in the Occupied Mode. Outdoor OaCFM AI: 193 Current Outdoor Air CFM Airflow Proof PofAlm BI: 26 Indicates no Measurement of Flow Proof of Water Alarm Flow. Minimum OACfmMin AV:291 Minimum Out- .10K 200K Desired door Airflow Outdoor CFM Setpoint Air CFM Reheat RehtEnbl BI: 363 Modulating Enabled Hotgas Reheat Missing OaCfmAlm BI: 370 Indicates Enabled. Outdoor Outdoor Air Air CFM CFM Sensor is Reheat RtVlvPos AI:277 Current position Sensor not detected. Valve of MHGRV Position modulating hot Outdoor OaRh AI:52 Current value gas reheat valve. Humidity of the Outdoor Humidity Missing MisMH- BI: 374 Indicates that the Sensor. Reheat GRV MHGRV Module Module is not Outdoor OaDewPt AI: 332 Current calcu- communicating Air lated Outdoor with the VCB-X Dewpoint Air Dewpoint. Controller. Return Air RaCFM AI:275 Current Return CFM Airflow Measurement. PT-LInk II BACnet4 Technical Guide 53 Zone 7. PARAMETER TABLES Zone 7.2 VCB-X BACnet Parameters

BACnet Properties for the VCB-X Controller BACnet Properties for the VCB-X Controller Param- Name Object Description Limits Param- Name Object Description Limits eter eter Missing RaCfmSr BI: 373 Indicates Space SpcTpAlm BI: 101 Indicates Return that the Return Tempera- a failure of the Air CFM Air CFM Sensor ture Sensor Space Tempera- Sensor is not detected. Lost ture Sensor. Return Air RaDmp AI: 336 Current Return Static StaticPr AI:270 Current Static Damper Air Damper Pressure Pressure. Position position. Static StatPrSt AV:290 Current Static .10 3.0 Return Air RaRH AI: 337 Current value of Pressure Pressure Humidity the Return Air Setpoint Setpoint. Humidity Sensor. Static DuctPrDb AV:357 Value above and .01 0.5 Return Air RaTp AI: 64 Current value of Pressure below the Duct Tempera- the return tem- Setpoint Static Pressure ture perature sensor. Deadband Setpoint where Return Air RaTpOst AV: 65 If the Return -100 100 no control Tempera- Temperature change occurs. ture Sensor Sensor is reading Suction SucPr AI: 333 Current Suction Offset incorrectly, use Pressure Pressure value. this to enter an High HiSucPr BI: 352 Indicates offset to adjust Suction Suction Pressure the Sensor’s Pressure is above the Temperature. Alarm High Suction Bad Return RaTpAlm BI: 365 Indicates a failure Pressure Cool- Air Sensor of the Return Air ing (Heating) Sensor. Setpoint. Return RetBydmp AI: 335 Current Return Low LoSucPr BI: 383 Indicates Bypass Bypass Damper Suction Suction Pressure Damper position. Pressure is below the Low Position Alarm Suction Pressure Schedule SchdFrc AV: 66 0 = Auto (uses 0 2 Cooling (Heat- Force controller’s ing) Setpoint. schedule) Supply Air SaCFM AI:195 Current Supply 1 = Forced CFM Airflow Occupied Measurement. 2 = Forced High HiSaAlm BI: 33 The Supply Air Unoccupied Supply Air has risen above Current SldAdOfs AI: 338 Current Slide Tempera- the High SAT Slide Adjust Offset ture Alarm Cutoff Setpoint. Adjust value. Heating stages Offset begin to deacti- Smoke SmokeAlm BI: 119 Indicates the vate and the fan Alarm / Smoke sensor continues to run. Emergency has been acti- Low Sup- LoSaAlm BI: 37 The Supply Air Shutdown vated. This will ply Air has fallen below shut down the Tempera- the Low SAT unit. ture Alarm Cutoff Setpoint Space SpcTp AI:72 Current value of and cooling Tempera- the space tem- stages will begin ture perature sensor. to deactivate. If the unit is in Space SpcTpOst AV:71 If the Space -100 100 Economizer, Tempera- Temperature Vent, or Heating ture Offset Sensor is reading Mode the Supply incorrectly, use Fan will shut off. this option to enter an offset Supply Air SaClSt AV:77 Supply Air Cool- 30 80 to adjust the Cooling ing Setpoint. If Sensor’s Setpoint Supply Air Reset Temperature. is configured, this is the Low SAT Cooling Reset Value.

54 PT-LInk II BACnet4 Technical Guide Zone 7. PARAMETER TABLES Zone 7.2 VCB-X BACnet Parameters

BACnet Properties for the VCB-X Controller BACnet Properties for the VCB-X Controller Param- Name Object Description Limits Param- Name Object Description Limits eter eter Supply Air SaClRt AV: 324 If Supply Air Re- 0 100 Cooldown SaCldnSt AV: 362 Cooling will be 30 80 Cool High set is configured, Mode controlled to Reset this is the High Supply Air this Supply Air SAT Cooling Setpoint Setpoint during Reset Value. Cool-Down. Supply Air SaHtRt AV: 325 If Supply Air Re- 0 250 Missing SaCfmSr BI: 372 Indicates the Heat High set is configured, Supply Supply Air CFM Reset this is the High Air CFM Sensor is not SAT Heating Sensor detected. Reset Value. Warmup SaWmupSt AV: 361 Heating will be 40 240 Supply Air SaHtSt AV:78 Supply Air Heat- 40 240 Mode controlled to Heating ing Setpoint. If Supply Air this Supply Air Setpoint Supply Air Reset Setpoint Setpoint during is configured, Morning Warm- this is the Low Up. SAT Heating SZ VAV SZVAVFnl AV: 360 This is the 0 10 Reset Value. Integral Integral Constant Supply Air SaTp AI:83 Current value of Constant for controlling Tempera- the Supply Air the SZ VAV Fan ture Temperature Speed. Sensor. Title 24 T24EcFb AI: 384 Current position Bad SaTpAlm BI: 2 Indicates a fail- Econo- of feedback from Supply Air ure of the Supply mizer Economizer Tempera- Air Temperature Feedback actuator. ture Sensor Sensor. Title 24 T24TpAlm BI: 385 Outside Air Low LoSaCf AV: 344 Cooling will be 0 100 Sensor or Supply Air Supply disabled if the Alarm Temperature Air Temp Supply Air Tem- Sensor is shorted Cutoff perature falls or missing. below this value. Title T24NEWS BI: 386 Economizer is See sequence for 24 Not enabled but not more details. Economiz- following the High HiSaCf AV: 345 Heating will be 0 250 ing When desired Econo- Supply disabled if the It Should mizer position Air Temp Supply Air Tem- commanded. Cutoff perature rises Title 24 T24EWISN BI: 387 Economizer is above this value. Economiz- not enabled but See sequence for ing When the feedback more details. It Should signal indicates Not a position more open than the minimum. Supply Air SaTpOst AV:80 If the Supply Air -100 100 Title 24 T24DpAlm BI: 388 Economizer is Tempera- Temperature Damper enabled but not ture Offset Sensor is reading Failure within 10% of incorrectly, use desired position this offset to ad- within 150 just the Sensor’s seconds. Temperature. Title 24 T24ExsOA BI: 389 Economizer Current SaTpStM AI: 82 Current SAT Excess feedback is lost Supply Air Cooling or Outdoor or Economizer Tem- Heating Air is not follow- perature setpoint if there ing commanded Setpoint is no reset position. source; Current cal- culated SAT setpoint with Reset Source.

PT-LInk II BACnet4 Technical Guide 55 Zone 7. PARAMETER TABLES Zone 7.2 VCB-X BACnet Parameters

BACnet Properties for the VCB-X Controller BACnet Properties for the VCB-X Controller Param- Name Object Description Limits Param- Name Object Description Limits eter eter Unoc- UnClOst AV: 124 In Unoccupied 0 30 VFD Min VFDHtMin AV: 320 In Single Zone 0% 100% cupied Mode, this Position in VAV configura- Cooling offsets the Heat Mode tion, this is the Offset Occupied Cool- fan speed at ing Setpoint by which the VFD this user adjust- will start when able amount. If Heating is no Unoccupied initiated. In a Cooling is VAV configura- desired, use the tion this is the default setting lowest fan speed of 30°F for this allowed in the setpoint. Heating Mode. Unoc- UnHtOst AV:125 In Unoccupied 0 30 In CAV and cupied Mode, this MUA configura- Heating offsets the tions this should Offset Occupied Heat- be set to 100%. ing Setpoint by VFD Min VFDVtMin AV: 322 Speed at which 0% 100% this user adjust- Position in the VFD will op- able amount. If Vent Mode erate in the Vent no Unoccupied Mode in Single Heating is Zone VAV. desired, use the default setting Remote FrcFanSp AV: 266 Override to 0% 100% of 30°F for this VFD force the VFD to Auto=65535 setpoint. Position this percentage Setpoint speed. Configur- VFD VfdBwPos AI:88 Current ing “Auto” will Position position of the restore normal VFD blower fan unit control of signal. the VFD speed. VFD Min VFDClMin AV: 319 In Single Zone 0% 100% OnBoard OnRlys AI:44 See page 58. Position in VAV configura- Relay Cool Mode tion, this is the Status fan speed at which the VFD On Board OnRly1 BI: 127 Current status will start when Relay 1 of VCB-X Main Cooling is Board relay 1. initiated. In a On Board OnRly2 BI: 128 Current status VAV configura- Relay 2 of VCB-X Main tion this is the Board relay 2. lowest fan speed On Board OnRly3 BI: 129 Current status allowed in the Relay 3 of VCB-X Main Cooling Mode. Board relay 3. In CAV and MUA configura- On Board OnRly4 BI: 130 Current status tions this should Relay 4 of VCB-X Main be set to 100%. Board relay 4. On Board OnRly5 BI: 131 Current status Relay 5 of VCB-X Main Board relay 5. On Board OnRly6 BI: 259 Current status Relay 6 of VCB-X Main Board relay 6. Expansion MnExRly1 BI:311 Current status of Module Relay 1 on the Relay 1 EM1 Expansion Module.

56 PT-LInk II BACnet4 Technical Guide Zone 7. PARAMETER TABLES Zone 7.2 VCB-X BACnet Parameters

BACnet Properties for the VCB-X Controller BACnet Properties for the VCB-X Controller Param- Name Object Description Limits Param- Name Object Description Limits eter eter Expansion MnExRly2 BI:312 Current status of 12 Relay RlExRly8 BI:306 Current status of Module Relay 2 on the Expansion Relay 8 on the Relay 2 EM1 Expansion Module 12 Relay Expan- Module. Relay 8 sion Expansion MnExRly3 BI:313 Current status of Module. Module Relay 3 on the 12 Relay RlExRly9 BI:307 Current status of Relay 3 EM1 Expansion Expansion Relay 9 on the Module. Module 12 Relay Expan- Expansion MnExRly4 BI:314 Current status of Relay 9 sion Module Relay 4 on the Module. Relay 4 EM1 Expansion 12 Relay RlExRly10 BI:308 Current status of Module. Expansion Relay 10 on the Expansion MnExRly5 BI:315 Current status of Module 12 Relay Expan- Module Relay 5 on the Relay 10 sion Relay 5 EM1 Expansion Module. Module. 12 Relay RlExRly11 BI:309 Current status of 12 Relay RlExRly1 BI:299 Current status of Expansion Relay 11 on the Expansion Relay 1 on the Module 12 Relay Expan- Module 12 Relay Expan- Relay 11 sion Relay 1 sion Module. Module. 12 Relay RlExRly12 BI:310 Current status of 12 Relay RlExRly2 BI:300 Current status of Expansion Relay 12 on the Expansion Relay 2 on the Module 12 Relay Module 12 Relay Expan- Relay 12 Expansion Relay 2 sion Module. Module. 12 Relay RlExRly3 BI:301 Current status of Expansion Relay 3 on the Module 12 Relay Expan- Relay 3 sion Module. 12 Relay RlExRly4 BI:302 Current status of Expansion Relay 4 on the Module 12 Relay Expan- Relay 4 sion Module. 12 Relay RlExRly5 BI:303 Current status of Expansion Relay 5 on the Module 12 Relay Expan- Relay 5 sion Module. 12 Relay RlExRly6 BI:304 Current status of Expansion Relay 6 on the Module 12 Relay Expan- Relay 6 sion Module. 12 Relay RlExRly7 BI:305 Current status of Expansion Relay 7 on the Module 12 Relay Expan- Relay 7 sion Module.

PT-LInk II BACnet4 Technical Guide 57 Zone 7. PARAMETER TABLES Zone 7.2 VCB-X BACnet Parameters

7.2.1 VCB-X PT-Link II BACnet® Bad Return CFM Sensor (11), Property Identifier: Bad Reheat Module (12), Bad ModGas Module (13), The PT-Link II BACnet® Link amends the following property identity Bad Relay Expansion Module (14), ® to the BACnet property identifier. Missing EM2 Expansion Board (15) } BACNETPropertyIdentifier : VcbxAlarmGroup2Bits ::= BIT STRING { VcbxUnitMode ::= ENUMERATED { Mechanical Cooling Failure (0), Unoccupied (0) Mechanical Heating Failure (1), Occupied (1), Fan Proving Alarm (2), Override Mode (2), Dirty Filter Alarm (3), Holiday Unoccupied (3), Emergency Shutdown Alarm (4), Holiday Occupied (4), Economizer Air Temperature Failure (5), Forced Occupied (5), Not Economizing When It Should (6), Forced Unoccupied (6), Economizing When It Should Not (7), } Economizer Damper Failure (8), Economizer Excess Outdoor Air (9) VcbxControlStatusBits ::= ENUMERATED { } Off (0), Vent Mode (1), VcbxAlarmGroup3Bits ::= BIT STRING { Cooling Mode (2), High Supply Air Cutoff (0), Heating Mode (3), Low Supply Air Cutoff (1), Vent RH Mode (4), High Control Mode Signal Alarm (2), Cooling RH Mode (5), Low Control Mode Signal Alarm (3), Heating RH Mode (6), Digital Compressor Cutoff Alarm (4), Warm Up Mode (7), Digital Compressor Lockout Alarm (5), Defrost Mode (8), High Head Pressure (6), Purge Mode (9), Loop Water Proof of Flow (7), Cool Down Mode (10), Low Suction Pressure (8), Remote Cooling Mode (11), Unsafe Suction Pressure (9), Remote Heating Mode (12), Low Leaving Water Temp (10) Remote Vent Dehum (13), } Remote Cool Dehum (14), Remote Heat Dehum (15) VcbxOnBoardRelaysBits ::= BIT STRING { } On Board Relay 1 (0), On Board Relay 2 (1), VcbxAlarmGroup1Bits ::= BIT STRING { On Board Relay 3 (2), Bad Supply Air Sensor (0), On Board Relay 4 (3), Bad Return Air Sensor (1), On Board Relay 5 (4) Bad Outside Air Sensor (2), On Board Relay 6 (5) Bad Space Sensor (3), } Bad Main Expansion Board (4), Bad Coil Temp Sensor (5), Bad Co2 Sensor (6), Bad Discharge Sensor (7), Bad OA CFM Sensor (8), Bad Exhaust CFM Sensor (9), Bad Supply CFM Sensor (10),

58 PT-LInk II BACnet4 Technical Guide Zone 7. PARAMETER TABLES Zone 7.3 VCM-X Modular BACnet Parameters

BACnet Properties for VCM-X Modular NOTE: Objects labeled AI and BI are read-only. Objects labeled AV are read/writeable. You cannot write directly Parameter Name Object Description Limits to Sensor Inputs. Condenser CdFan21 AI: 392 Condenser Fan Fan Signal 1 Signal 1 On Head On Head Pres- Pressure Module 2 sure Module 2 NOTE: The following points for the VCM-X Modular, VCM-X Condenser CdFan22 AI: 393 Condenser Fan & WSHP Controllers are additional points. All points Fan Signal 2 Signal 2 On Head and property identifiers in the VCM-X Controller On Head Pres- Pressure Module 2 table (Section 7.6, page 63) also apply to the VCM-X sure Module 2 Modular, & VCM-X WSHP Controllers. Head Pressure HdPr21 AI: 394 Head Pressure Signal 1 on Signal 1 on Head Head Pressure Pressure Module 2 Module 2 NOTE: When a new setpoint is received from BACnet, it is Head Pressure HdPr22 AI: 395 Head Pressure maintained and used in temporary memory until the Signal 2 on Signal 2 on Head unit goes unoccupied. It is then stored in permanent Head Pressure Pressure Module 2 memory and will become the new default setpoint even Module 2 if power is cycled. Therefore, if power is cycled prior Remote VFD RmVFDPos AV: 258 Remote VFD -1 100 to the unit going unoccupied, the setpoint will not have Reset Position Reset been stored in permanent memory. Bad Return RaTpAlm BI: 365 Alarm that indicates Air Sensor a failure in the Re- turn Air Sensor. BACnet Properties for VCM-X Modular Title 24 T24TpAlm BI: 385 Outside Air or Sensor Alarm Supply Air Tem- Parameter Name Object Description Limits perature Sensor is Modulating MdCmp2 AI: 206 Current position shorted or missing. Compressor 2 of the 2nd Stage Title 24 Not T24NEWS BI: 386 Economizer is of Compressor Economiz- enabled but not fol- Modulation. ing When It lowing the desired Head Pressure HdPr1 AI: 207 Head Pressure Should Economizer posi- Signal 1 on Signal 1 on Head tion commanded. Head Pressure Pressure Module 1 Title 24 T24EWISN BI: 387 Economizer is not Module 1 Economiz- enabled but the Head Pressure HdPr2 AI: 208 Head Pressure ing When It feedback signal Signal 2 on Signal 2 on Head Should Not indicates a position Head Pressure Pressure Module 1 more open than the Module 1 minimum. Condenser CdFan1 AI: 209 Condenser Fan Title 24 T24DpAlm BI: 388 Economizer is en- Fan Signal 1 Signal 1 On Head Damper abled but not with- On Head Pres- Pressure Module 1 Failure in 10% of desired sure Module 1 position within 150 seconds. Condenser CdFan2 AI: 210 Condenser Fan Fan Signal 2 Signal 2 On Head Title 24 T24ExsOA BI: 389 Economizer On Head Pres- Pressure Module 1 Excess feedback is lost or sure Module 1 Outdoor Air Economizer is not following com- Title 24 T24EcFb AI: 384 Current posi- manded position. Economizer tion of feedback Feedback from Economizer actuator. Title 24 AlmGrp5 AI: 391 Alarms for the 24 Economizer Title Economizer Alarms

PT-LInk II BACnet4 Technical Guide 59 Zone 7. PARAMETER TABLES Zone 7.4 VCM-X WSHP (Tulsa) BACnet Parameters

BACnet Properties for NOTE: Objects labeled AI and BI are read-only. Objects labeled AV are read/writeable. You cannot write directly VCM-X WSHP (Tulsa) Controller to Sensor Inputs. Parameter Name Object Description Limits Compressor A1 A1LSPAlm BI: 222 Alarm that Low Suction indicates BACnet Properties for Pressure Alarm Suction Pressure VCM-X WSHP (Tulsa) Controller for Compressor A1 is below the Parameter Name Object Description Limits Low Suction Modulating MdCmp2 AI: 206 Current position Pressure Compressor 2 of the Cooling (Heat- 2nd Stage of ing) Setpoint. Compressor Compressor A1 A1LktAlm BI: 223 Alarm that Modulation. Lockout Alarm indicates Head Pressure HdPr1 AI: 207 Head Pressure Compressor A1 Signal 1 on Signal 1 on is locked out. Head Pressure Head Pressure Compressor A2 A2LSPAlm BI: 224 Alarm that Module 1 Module 1 Low Suction indicates Head Pressure HdPr2 AI: 208 Head Pressure Pressure Alarm Suction Pressure Signal 2 on Signal 2 on for Compressor Head Pressure Head Pressure A2 is below the Module 1 Module 1 Low Suction Pressure Cool- Condenser Fan CdFan1 AI: 209 Condenser Fan ing (Heating) Signal 1 On Signal 1 On Setpoint. Head Pressure Head Pressure Module 1 Module 1 Compressor A2 A2LktAlm BI: 225 Alarm that Lockout Alarm indicates Condenser Fan CdFan2 AI: 210 Condenser Fan Compressor A2 Signal 2 On Signal 2 On is locked out. Head Pressure Head Pressure Module 1 Module 1 Compressor B1 B1LSPAlm BI: 226 Alarm that Low Suction indicates Water Temp. A WaterTpA AI: 220 Current water Pressure Alarm Suction Pressure temperature of for Compressor refrigerant for B1 is below the System A. Low Suction Water Temp. B WaterTpB AI: 221 Current water Pressure Cool- temperature of ing (Heating) refrigerant for Setpoint. System B. Compressor B1 B1LktAlm BI: 227 Alarm that Condenser Fan CdFan21 AI: 392 Condenser Fan Lockout Alarm indicates Signal 1 On Signal 1 On Compressor B1 Head Pressure Head Pressure is locked out. Module 2 Module 2 Compressor B2 B2LSPAlm BI: 228 Alarm that Condenser Fan CdFan22 AI: 393 Condenser Fan Low Suction indicates Signal 2 On Signal 2 On Pressure Alarm Suction Pressure Head Pressure Head Pressure for Compressor Module 2 Module 2 B2 is below the Low Suction Head Pressure HdPr21 AI: 394 Head Pressure Pressure Cool- Signal 1 on Signal 1 on ing (Heating) Head Pressure Head Pressure Setpoint. Module 2 Module 2 Compressor 4 B2LktAlm BI: 229 Alarm that Head Pressure HdPr22 AI: 395 Head Pressure Lockout Alarm indicates Signal 2 on Signal 2 on Compressor B2 Head Pressure Head Pressure is locked out. Module 2 Module 2 Remote VFD RmVFDPos AV: Remote VFD -1 100 Reset 258 Position Reset Title 24 Econo- AlmGrp5 AI: 391 Alarms for the 24 mizer Alarms Title Economizer

60 PT-LInk II BACnet4 Technical Guide Zone 7. PARAMETER TABLES Zone 7.4 VCM-X WSHP (Tulsa) BACnet Parameters

BACnet Properties for BACnet Properties for VCM-X WSHP (Tulsa) Controller VCM-X WSHP (Tulsa) Controller Parameter Name Object Description Limits Parameter Name Object Description Limits Low Water LWT1Alm BI: 230 Alarm that Title 24 Not T24NEWS BI: 386 Economizer is Temperature 1 indicates water Economizing enabled but not Alarm temperature is When It Should following the below the desired Econo- Leaving Water mizer position Safety Setpoint commanded. (Heating only) Title 24 Econo- T24EWISN BI: 387 Economizer is for System A. mizing When It not enabled but Low Water LWT2Alm BI: 231 Alarm that Should Not the feedback Temperature 2 indicates water signal indicates Alarm temperature is a position more below the open than the Leaving Water minimum. Safety Setpoint Title 24 Damper T24DpAlm BI: 388 Economizer is (Heating only) Failure enabled but not for System B within 10% of Proof of Water 1 POWF1Alm BI: 232 Alarm that desired position Flow Alarm indicates no within 150 Proof of Water seconds. Flow for System Title 24 Excess T24ExsOA BI: 389 Economizer A (A1/A2) Outdoor Air feedback is lost Proof of Water 2 POWF2Alm BI: 233 Alarm that or Economizer Flow Alarm indicates no is not follow- Proof of Water ing commanded Flow for System position. B (B1/B2) Module ComMAlm BI: 234 Alarm that Communica- indicates that one tions Alarm or more Modules are not communicating with the VCM-X WSHP Control- ler. Bad Return Air RaTpAlm BI: 365 Alarm that Sensor indicates a failure in the Return Air Sen- sor. Title 24 Econo- T24EcFb AI: 384 Current position mizer Feedback of feedback from Economizer actuator. Title 24 T24TpAlm BI: 385 Outside Air Sensor Alarm or Supply Air Temperature Sensor is shorted or missing.

PT-LInk II BACnet4 Technical Guide 61 Zone 7. PARAMETER TABLES Zone 7.5 VCM-X WSHP (Coil) BACnet Parameters

BACnet Properties for VCM-X WSHP (Coil) BACnet Properties for VCM-X WSHP (Coil) Parameter Name Object Description Limits Parameter Name Object Description Limits Modulating MdCmp2 AI: 206 Current Proof of Water POWF1Alm BI: 232 Alarm that Compressor 2 position of the Flow Alarm indicates no 2nd Stage of Proof of Water Compressor Flow. Modulation. Module ComMAlm BI: 234 Alarm that Head Pressure 1 HdPr1 AI: 207 Head Pressure Communica- indicates that for tions one or more 1st Alarm Modules are Compressor not commu- Head Pressure 2 HdPr2 AI: 208 Head Pressure nicating with for the VCM-X 2nd WSHP Compressor Controller. Condenser CdFan1 AI: 209 Condenser Bad Return Air RaTpAlm BI: 365 Alarm that Fan 1 Fan 1 Sensor indicates Signal Status a failure in the Return Air Condenser CdFan2 AI: 210 Condenser Sensor. Fan 2 Fan 2 Signal Status Title 24 Econo- T24EcFb AI: 384 Current mizer Feedback position of Water Temp. A WaterTpA AI: 220 Current water feedback from temperature. Economizer Remote VFD RmVFDPos AV: Remote VFD -1 100 actuator. Reset 258 Position Reset Title 24 T24TpAlm BI: 385 Outside Air Compressor A A1LSPAlm BI: 222 Alarm that Sensor Alarm or Supply Air Low Suction indicates Temperature Pressure Alarm Suction Sensor is Pressure for shorted or Circuit A is missing. below the Title 24 Not T24NEWS BI: 386 Economizer Low Suction Economizing is enabled but Pressure Cool- When It Should not following ing (Heating) the desired Setpoint. Economizer Compressor A A1LktAlm BI: 223 Alarm that in- position com- Lockout Alarm dicates Circuit manded. A Compres- Title 24 Econo- T24EWISN BI: 387 Economizer sors are locked mizing When It is not enabled out. Should Not but the feed- Compressor B B1LSPAlm BI: 226 Alarm that back signal Low Suction indicates indicates a Pressure Alarm Suction position more Pressure for open than the Circuit B is minimum. below the Title 24 Damper T24DpAlm BI: 388 Economizer Low Suction Failure is enabled but Pressure Cool- not within ing (Heating) 10% of de- Setpoint. sired position Compressor B B1LktAlm BI: 227 Alarm that in- within 150 Lockout Alarm dicates Circuit seconds. B Compres- sors are locked Title 24 Excess T24ExsOA BI: 389 Economizer out. Outdoor Air feedback is lost or Low Water LWT1Alm BI: 230 Alarm that Economizer is Temperature indicates water not following Alarm temperature commanded is below the position. Leaving Water Safety Set- point (Heating only).

62 PT-LInk II BACnet4 Technical Guide Zone 7. PARAMETER TABLES Zone 7.6 VCM-X BACnet Parameters

NOTE: Objects labeled AI and BI are read-only. Objects BACnet Properties for the VCM-X Controller labeled AV are read/writeable. You cannot write directly to Sensor Inputs. Parameter Name Object Description Limits Reheat Rt2Pos AI: 60 Current position of Valve MHGRV modulat- NOTE: When a new setpoint is received from BACnet, it is Position ing hot gas reheat maintained and used in temporary memory until the valve control. unit goes unoccupied. It is then stored in permanent Relief RfPr AI: 62 Current value of the memory and will become the new default setpoint even Pressure building pressure if power is cycled. Therefore, if power is cycled prior sensor. to the unit going unoccupied, the setpoint will not have Return Air RaTp AI: 64 Current value of the been stored in permanent memory. Temperature return temperature sensor. BACnet Properties for the VCM-X Controller Indoor InRh AI: 67 Current value of Parameter Name Object Description Limits Humidity the indoor humidity Alarm AlmSts AI: 1 See Alarm sensor. Status Group Bits on Space SpcTp AI: 72 Current value of the page 68. Temperature space temperature Control CtrlSts AI: 4 Current operational sensor. Status status. Current SaTpStM AI: 82 Current SAT Occupied ClSt AI: 7 Occupied Mode Supply Air Cooling or Heating Mode Enable Cooling Setpoint setpoint if there Enable Setpoint Mirror. is no reset source; Cooling Current calculated Setpoint SAT setpoint with Mirror Reset Source. Control CtrlTp AI: 9 Current value of the Supply Air SaTp AI: 83 Current value of the Temperature control temperature Temperature supply air sensor. temperature sensor. Duct Static DuctPr AI: 14 Current value of the Temperature TpDmnd AI: 84 Based on the Pressure duct static pressure Demand comparison sensor. between the current Control Economizer EcoPos AI: 16 Current position Temperature and Position of the economizer the Heating or damper. Cooling Setpoint Occupied HtSt AI: 31 Occupied Mode Temperatures. Does Mode Enable Heating not work for supply Enable Setpoint air control Heating Mirror. VFD VfdBw- AI: 88 Current position of Setpoint Blower Fan Pos the VFD blower fan Mirror signal. Modulating MdHt- AI: 38 Current position VFD VfdExPos AI: 89 Current position of Gas Valve 2Pos of MODGAS II Relief Fan the VFD relief Position modulating gas fan signal. valve control. Application AppVer AI: 99 Current version of On Board OnRlys AI: 44 See page 68. Software the software in the Relays Version unit. Outdoor Air OaDwpt AI: 47 Current calculated Alarm AlrmGrp1 AI: 104 See Alarm Dewpoint outdoor air Group 1 Group Bits on dewpoint added on page 68. version 1.09. Alarm AlrmGrp2 AI: 105 See Alarm Outdoor Air OaRh AI: 52 Current value of the Group 2 Group Bits on Humidity outdoor humidity page 68. sensor. Alarm AlrmGrp3 AI: 106 See Alarm Outdoor Air OaTp AI: 54 Current value of the Group 3 Group Bits on Temperature outdoor tempera- page 68. ture sensor. Dewpoint DptStM AI: 110 Mirror of the DPtSt Outdoor Air OaWtbl AI: 55 Current calculated Setpoint “read only.” Wetbulb value of the outdoor Mirror wetbulb temperature. External ExRlys12 AI: 111 See page 68. Relays 1-2 PT-LInk II BACnet4 Technical Guide 63 Zone 7. PARAMETER TABLES Zone 7.6 VCM-X BACnet Parameters

BACnet Properties for the VCM-X Controller BACnet Properties for the VCM-X Controller Parameter Name Object Description Limits Parameter Name Object Description Limits External ExRlys34 AI: 112 See page 68. Occupied OcpHtSt AV: 43 If the control 0 99 Relays 3-4 Mode temperature drops Enable one degree below Indoor Rh InRhStM AI: 114 Mirror of the Heating this setpoint, Setpoint InRhSt “read only.” Setpoint the control will Mirror activate the heating Modulating MdClPos AI: 115 Current position of demand. If the Cool the modulating control Position cooling signal temperature (Chilled water or is the Supply Air digital compressor). Sensor, then there is Modulating MdHtPos AI: 116 Current position of no heating demand. Heat the modulating Outdoor OaTpOst AV: 53 If the Outdoor -100 100 Position heating signal (hot Air Sensor Temperature Sensor water or SCR heat). Offset is reading Unit Mode UnitMode AI: 123 See page 68. incorrectly, you can use this option to Return Air CO2Level AI: 150 Current value of the enter an offset

CO2 Level CO2 sensor. temperature to adjust the Sensor’s Bypass ByPas- AI: 153 Current position of Temperature. Damper Dmp the bypass damper Position signal. Return RaTpOst AV: 65 If the Return Tem- -100 100 Air Sensor perature Sensor is Return RaDmp AI: 154 Current position of Offset reading incorrectly, Damper the return damper you can use this Position signal. option to enter an Coil CoilTp AI: 181 Current coil offset temperature Temperature temperature reading to adjust the Sen- added on version sor’s Temperature. 1.09. Schedule SchdFrc AV: 66 0 = Auto/ 0 2 Outdoor Air OaCFM AI: 193 Current Outdoor Force Unoccupied Mode CFM Airflow 1 = Forced On Measurement 2 = Forced Off Exhaust EtCFM AI: 194 Current Exhaust Space SpcTpOst AV: 71 If the Space -100 100 CFM Airflow Sensor Temperature Measurement Offset Sensor is reading Supply Air SaCFM AI: 195 Current Supply incorrectly, you can CFM Airflow use this option to Measurement enter an offset temperature to Current OACfm- AI: 205 Current calculated adjust the Sensor’s Calculated StM Outdoor Air CFM Temperature. OA CFM based on CO2 level. setpoint SAT SaClSt AV: 77 Supply Air Setpoint 40 80 Cooling in Cooling Mode. Dewpoint DptSt AV: 13 If the outdoor 35 80 Setpoint Setpoint dewpoint rises above this setpoint, SAT SaHtSt AV: 78 Supply Air Setpoint 40 200 the unit will Heating in Heating Mode. activate the Setpoint Dehumidification Supply SaTpOst AV: 80 If the Supply Air -100 100 Demand. Air Sensor Temperature Sensor Occupied OcpClSt AV: 42 If the control tem- 0 99 Offset is reading incor- Mode perature rises one rectly, you can use Enable degree above this this option to enter Cooling setpoint, the control an offset Setpoint will activate the temperature to cooling demand. If adjust the Sensor’s the control tempera- Temperature. ture is the Supply Air Sensor, then the cooling demand is always active.

64 PT-LInk II BACnet4 Technical Guide Zone 7. PARAMETER TABLES Zone 7.6 VCM-X BACnet Parameters

BACnet Properties for the VCM-X Controller BACnet Properties for the VCM-X Controller Parameter Name Object Description Limits Parameter Name Object Description Limits

Warm Up WmupSt AV: 91 In a VAV 50 90 CO2 CO2St AV: 149 When the CO2 0 3000 Setpoint application, upon Setpoint level rises above

entering the oc- the CO2 Protection cupied mode, the Limit Max Level, Warm-up Demand the Economizer’s will be activated Minimum Position if the return air will begin to reset temperature falls open proportionally

one degree below between the CO2 this setpoint. Protection Limit Max Level Setpoint Wet Bulb WtblSt AV: 92 The economizer is 0 80 and the Reset Setpoint enabled if the Range Setpoint. outdoor tempera- ture or wetbulb falls Minimum MinEcoSt AV: 151 This is the 1 100 below this setpoint. Outside Air minimum position Setpoint of the economizer Coil CoilTpSt AV: 107 This is the coil 35 70 in the occupied Temperature suction temperature modes. Setpoint target during dehumidification Static DuctPrSt AV: 152 This is the target 0.01 3 mode. Produces Pressure duct pressure to be dewpoint in the Setpoint maintained by the supply air VFD blower signal. approximately 10°F Preheater PreHtSp AV: 196 Low Outside Air 0 100 above this setpoint. Setpoint Ambient Relief RfPrSt AV: 118 This is the target -0.2 0.2 Protection Setpoint Pressure building pressure Outdoor OACfmSt AV: 203 Minimum desired 0.10 200 K Setpoint to be maintained Air CFM Outdoor Air CFM. K by the VFD Relief Setpoint signal. Outdoor Air OACfmRs AV: 204 Maximum desired 0.10 200 K Indoor InRhSt AV: 120 If the indoor 0 100 CFM Reset Outdoor Air CFM K Humidity humidity rises Limit when CO2 reaches Setpoint above this setpoint, its reset limit. the unit will acti- vate the Dehumidi- Supply Air SaClRt AV: 324 High Supply Air 40 150 fication Demand. Cool High Cooling Reset Reset Limit Unoccupied UnClOst AV: 124 During the 0 30 Cooling Unoccupied Mode Supply Air SaHtRt AV: 325 High Supply Air 40 150 Offset of Operation, this Heat High Heating Reset Limit Setpoint spreads the Reset Occupied Cooling Cooling ClLoRt AV: 326 Low Cool Reset 1 150 Setpoint out by Low Reset Source Setpoint a user adjustable Source amount. If you do Cooling ClHiRt AV: 327 High Cool Reset 1 150 not want Cooling to High Reset Source Setpoint operate during the Source Unoccupied Mode, use the default Heating HtLoRt AV: 328 Low Heat Reset 1 150 setting of 30°F for Low Reset Source Setpoint these setpoints. Source Unoccupied UnHtOst AV: 125 During the 0 30 Heating HtHiRt AV: 329 High Heat Reset 1 150 Heating Unoccupied Mode High Reset Source Setpoint Offset of Operation, this Source Setpoint spreads the Occupied Heating Setpoint out by a user adjustable amount. If you do not want Heating to operate during the Unoccupied Mode, use the default setting of 30°F for these setpoints.

PT-LInk II BACnet4 Technical Guide 65 Zone 7. PARAMETER TABLES Zone 7.6 VCM-X BACnet Parameters

BACnet Properties for the VCM-X Controller BACnet Properties for the VCM-X Controller Parameter Name Object Description Limits Parameter Name Object Description Limits Bad Supply SaTpAlm BI: 2 Alarm that Mechanical MchClAlm BI: 94 Compressor Relays Air Sensor indicates a failure Cooling are enabled but in the Alarm the Supply Air supply air sensor. Temperature has CO Sensor CO2Cfg BI: 3 Status that not fallen 5°F w/in 2 a user-adjustable Installed indicates the CO2 function has been time period. This configured. does not indicate are Cooling ClEnbl BI: 6 Status that indicates active and will not Enabled mechanical cooling shut the unit down. is enabled. Mechanical MchHtAlm BI: 95 Heating Mode has Economizer EcoEnbl BI: 15 Status that indicates Heating been initiated but Enabled the economizer is Alarm the Supply Air enabled. Temperature has Fan Start Up FanDly BI: 25 Status that indicates not risen 5°F w/in Delay the fan is a user-adjustable commanded to run, time period. This but it is in the start does not indicate up delay mode. heat stages are active and will not Fan PofAlm BI: 26 Alarm that shut the unit down. Proving indicates a failure Alarm in the flow of the Dirty Filter DrtFlAlm BI: 96 Alarm that indicates VFD blower. Detected the filters are dirty. Heating HtEnbl BI: 30 Status that Control CtrlTpCF BI: 108 This alarm is Enabled indicates that Temperature activated if the mechanical heating Cool Failure control temperature is enabled. does not get within 5°F to the occupied High HiSaAlm BI: 33 The Supply Air cooling setpoint Supply Air has risen above in an hour in the Temperature the Hi SAT Cutoff cooling mode. This Alarm Setpoint. Heating alarm is not used stages begin to deac- in 100% outside air tivate and the fan units or supply air continues to run. control. Low Supply LoSaAlm BI: 37 The Supply Air has Control CtrlTpHF BI: 109 This alarm is Air fallen below the Hi Temperature activated if the Temperature SAT Cutoff Setpoint Heat Failure control temperature Alarm and cooling stages does not get within will begin to deacti- 5°F to the occupied vate. If the unit is in heating setpoint Economizer, Vent, in an hour in the or Heating Mode heating mode. This the Supply Fan will alarm is not used shut off. in 100% outside air MODGAS MdHt2Ins BI: 39 Status that indicates units or supply air II the MODGAS II control. Connected controller is Outdoor Air OaTpAlm BI: 117 Alarm that connected. Temperature indicates a failure Proof of PofCfg BI: 57 Status that indicates Lost in the outdoor air Flow the proof of flow temperature. Configured function has been Smoke SmokeAlm BI: 119 Alarm that indicates configured. Detector the Smoke sensor REHEAT II Rt2Ins BI: 58 Status that indicates Alarm has been activated. Connected the MHGRV Space SpcTpAlm BI: 101 Alarm that indicates controllers is Temperature a failure in the connected to the Sensor Lost space temperature system. sensor.

66 PT-LInk II BACnet4 Technical Guide Zone 7. PARAMETER TABLES Zone 7.6 VCM-X BACnet Parameters

BACnet Properties for the VCM-X Controller Parameter Name Object Description Limits On Board OnRly1 BI: 127 Current status of Relay 1 relay 1. On Board OnRly2 BI: 128 Current status of Relay 2 relay 2. On Board OnRly3 BI: 129 Current status of Relay 3 relay 3. On Board OnRly4 BI: 130 Current status of Relay 4 relay 4. On Board OnRly5 BI: 131 Current status of Relay 5 relay 5. Expansion ExRly1 BI: 133 Current status of Relay 1 relay 6. Expansion ExRly2 BI: 134 Current status of Relay 2 relay 7. Expansion ExRly3 BI: 135 Current status of Relay 3 relay 8. Expansion ExRly4 BI: 136 Current status of Relay 4 relay 9. Expansion ExRly5 BI: 137 Current status of Relay 5 relay 10. Expansion ExRly6 BI: 138 Current status of Relay 6 relay 11. Expansion ExRly7 BI: 139 Current status of Relay 7 relay 12. Expansion ExRly8 BI: 140 Current status of Relay 8 relay 13. Expansion ExRly9 BI: 141 Current status of Relay 9 relay 14. Expansion ExRly10 BI: 142 Current status of Relay 10 relay 15. Expansion ExRly11 BI: 143 Current status of Relay 11 relay 16. Expansion ExRly12 BI: 144 Current status of Relay 12 relay 17. Expansion ExRly13 BI: 145 Current status of Relay 13 relay 18. Expansion ExRly14 BI: 146 Current status of Relay 14 relay 19. Expansion ExRly15 BI: 147 Current status of Relay 15 relay 20. Expansion ExRly16 BI: 148 Current status of Relay 16 relay 21.

PT-LInk II BACnet4 Technical Guide 67 Zone 7. PARAMETER TABLES Zone 7.6 VCM-X BACnet Parameters

7.6.1 VCM-X PT-Link II BACnet® VcmxExternal Relays2-4Bits::= BIT STRING { Property Identifier: ExpansionBoard3Relay1 (0), ExpansionBoard3Relay2 (1), The PT-Link II BACnet® Link amends the following property identity ExpansionBoard3Relay3 (2), ® to the BACnet property identifier. ExpansionBoard3Relay4 (3), ExpansionBoard4Relay1 (4), BACNETPropertyIdentifier : ExpansionBoard4Relay2 (5), WattBACNETScheduleForce ::= ENUMERATED { ExpansionBoard4Relay3 (6), NormalOperation (0), ExpansionBoard4Relay4 (7) ForceOccupied (1), } ForceUnoccupied (2) } VcmxAlarmStatusBits ::= BIT STRING { Alarm Group1 (0), VcmxUnitMode ::= ENUMERATED { Alarm Group2 (1), Unoccupied (0), Alarm Group3 (2), RemoteContactOccupied (1), Alarm Group4 (3), NormalScheduleOccupied (2), Alarm Group5 (4) PushButtonOrZoneOverride (3), } HolidayModeActive (4), VcmxAlarmGroup1Bits ::= BIT STRING { UnoccupiedZoneDemand (5), SupplyTempSensorFailure (0), RemoteScheduleOverride (6), LostOutdoorTempSensorSignal (1), CurrentOutputForceMode (7), LostSpaceTempSensorSignal (2), SATHighOrLowCutOff (8), ModuleAlarm (3), CO2OverrideInProgress (9), DemandVentilationAlarm (4), PurgeModeActive (10) OutdoorCFMSensorFailure (5), } ReturnTempSensorFailure (6) VcmxControlStatusBits ::= ENUMERATED { } Off (0), Vent (1), VcmxAlarmGroup2Bits ::= BIT STRING { Cool (2), MechanicalCoolingAlarm (0), Heat (3), MechanicalHeatingAlarm (1), Dehum (4), FanProvingAlarm (2), Dehum Cool (5), DirtyFilterDetected (3), Dehum Heat (6), SmokeDetected (4) Warm Up Mode (7), } Defrost (8) VcmxAlarmGroup3Bits ::= BIT STRING { } LowSupplyAirTempAlarm (0), VcmxOnBoardRelaysBits ::= BIT STRING { HighSupplyAirTempAlarm (1), OnBoardRelay1 (0), LowControlTempAlarm (2), OnBoardRelay2 (1), HighControlTempAlarm (3) OnBoardRelay3 (2), } OnBoardRelay4 (3), VcmxAlarmGroup5Bits ::= BIT STRING { OnBoardRelay5 (4) } AirTempSensorFailure (0), NoEconWhenItShould (1), VcmxExternal Relays1-2Bits::= BIT STRING { EconWhenItShouldNot (2), ExpansionBoard1Relay1 (0), DamperFailure (3), ExpansionBoard1Relay2 (1), ExcessOutdoorAir (4) ExpansionBoard1Relay3 (2), } ExpansionBoard1Relay4 (3), ExpansionBoard2Relay1 (4), ExpansionBoard2Relay2 (5), ExpansionBoard2Relay3 (6), ExpansionBoard2Relay4 (7) 68 PT-LInk II BACnet4 Technical Guide Zone 7. PARAMETER TABLES Zone 7.7 SA Controller BACnet Parameters

NOTE: Objects labeled AI and BI are read-only. Objects BACnet Properties for SA Controller labeled AV are read/writeable. You cannot write directly to Sensor Inputs. Parameter Name Object Description Limits Temperature TpDmnd AI: 84 Based on the NOTE: When a new setpoint is received from BACnet, it is Demand comparison between maintained and used in temporary memory until the the current Control unit goes unoccupied. It is then stored in permanent Temperature and the Heating or Cooling memory and will become the new default setpoint even Setpoint Tempera- if power is cycled. Therefore, if power is cycled prior tures. Does not work to the unit going unoccupied, the setpoint will not have for supply air control been stored in permanent memory. VFD Blower VfdBw- AI: 88 Current position of Fan Pos the VFD blower fan BACnet Properties for SA Controller signal. Parameter Name Object Description Limits Application AppVer AI: 99 Current version of the Software software in the unit. Control Status CtrlSts AI: 4 Current operational See Control Version status. Status Bits on page 72. Coil CoilTpSt AI: 107 Current Coil Temperature Temperature Occupied ClSt AI: 7 Occupied Mode Setpoint Setpoint. Mode Enable Cooling Enable Setpoint Mirror. Dewpoint DptStM AI: 110 Mirror of the DPtSt Cooling Setpoint “read only.” Setpoint Mirror Mirror Indoor RH InRhStM AI: 114 Mirror of the InRhSt Control CtrlTp AI: 9 Current value of the Setpoint “read only.” Temperature control temperature Mirror sensor. Modulating MdClPos AI: 115 Current position of Duct Static DuctPr AI: 14 Current value of the Cool the modulating Pressure duct static pressure Position cooling signal sensor. (Chilled water or digital compressor). Economizer EcoPos AI: 16 Current position of Position the waterside Modulating MdHtPos AI: 116 Current position of economizer valve. Heat the modulating Position heating signal (hot Occupied HtSt AI: 31 Occupied Mode water or SCR heat). Mode Enable Heating Enable Heat- Setpoint Unit Mode UnitMode AI: 123 See Unit ing Setpoint Mirror. Mode Bits Mirror on page 72. Modulating MdHt- AI: 38 Current position Coil CoilTp AI: 181 Current coil Gas Valve 2Pos of MODGAS II Temperature temperature reading Position modulating gas valve added on version control. 1.09. Reheat Value Rt2Pos AI: 60 Current position of Modulating MdCmp2 AI: 206 Current position Position MHGRV modulating Compressor 2 of the 2nd Stage of hot gas reheat valve Position Compressor control. Modulation. Indoor InRh AI: 67 Current value of Head HdPr1 AI: 207 Head Pressure for Humidity the indoor humidity Pressure 1 1st unit. sensor. Head HdPr2 AI: 208 Head Pressure for Space SpcTp AI: 72 Current value of the Pressure 2 2nd unit. Temperature space temperature Entering Air EaTp AI: 235 Temperature of the sensor. Temperature air that is Current SaTpStM AI: 82 Current SAT entering the unit. Supply Air Cooling or Heating Entering EwTp AI: 236 Temperature of the Setpoint setpoint if there is no Water water that is reset source; Temperature entering the unit. Current calculated Entering Air EaRh AI: 237 Relative Humidity of SAT setpoint with Humidity the Entering Air. Reset Source. Coil CoilTp2 AI: 240 Current Coil Supply Air SaTp AI: 83 Current value of the Temperature 2 Temperature for 2nd Temperature supply air unit. temperature sensor.

PT-LInk II BACnet4 Technical Guide 69 Zone 7. PARAMETER TABLES Zone 7.7 SA Controller BACnet Parameters

BACnet Properties for SA Controller BACnet Properties for SA Controller Parameter Name Object Description Limits Parameter Name Object Description Limits Entering Air EaDpt AI: 241 Current Entering Air Supply Air SaTpOst AV: 80 If the Supply Air -100 100 Dewpoint Dewpoint Sensor Offset Temperature Sensor Water Side WSEByp AI: 242 Current Water Side is reading Economizer Economizer Bypass incorrectly, you can Bypass Position for 1st unit. use this option to enter an offset Water Side WSEByp2 AI: 243 Current Water Side temperature to Economizer Economizer Bypass adjust the Sensor’s Bypass 2 Position for 2nd unit. Temperature. Condenser CdPos1 AI: 246 Current Condenser Warm Up WmupSt AV: 91 In a VAV 50 90 Position 1 Position for 1st unit. Setpoint application, upon Condenser CdPos2 AI: 247 Current Condenser entering the Position 2 Position for 2nd unit. occupied mode, the Warm-up Demand Dewpoint DptSt AV: 13 If the outdoor 35 80 will be activated Setpoint dewpoint rises above if the return air this setpoint, the temperature falls unit will activate the one degree below Dehumidification this setpoint. Demand. Coil CoilTpSt AV: 107 This is the coil 35 70 Occupied OcpClSt AV: 42 If the control 0 99 Temperature suction temperature Mode temperature rises one Setpoint target during Enable Cool- degree above this dehumidification ing Setpoint setpoint, the control mode. Produces will activate the cool- dewpoint in the ing demand. If the supply air control temperature approximately 10°F is the Supply Air Sen- above this setpoint. sor, then the cooling demand is always Indoor InRhSt AV: 120 If the indoor 0 100 active. Humidity humidity rises Setpoint above this setpoint, Occupied OcpHtSt AV: 43 If the control 99 the unit will Mode temperature drops activate the Enable Heat- one degree below Dehumidification ing this setpoint, Demand. Setpoint the control will activate the heating Unoccupied UnClOst AV: 124 During the 0 30 demand. If the Cooling Unoccupied Mode control temperature Offset of Operation, this is the Supply Air Setpoint spreads Sensor, then there is the Occupied Cool- no heating demand. ing Setpoint out by a user adjustable Schedule SchdFrc AV: 66 0 = Auto/ 0 2 amount. If you do Force Unoccupied Mode not want Cooling to 1 = Forced On operate during the 2 = Forced Off Unoccupied Mode, Space SpcTpOst AV: 71 If the Space -100 100 use the default Sensor Offset Temperature setting of 30°F for Sensor is reading these setpoints. incorrectly, you can use this option to enter an offset temperature to adjust the Sensor’s Temperature. SAT SaClSt AV: 77 Supply Air Setpoint 40 80 Cooling in Cooling Mode. Setpoint SAT SaHtSt AV: 78 Supply Air Setpoint 40 200 Heating in Heating Mode. Setpoint

70 PT-LInk II BACnet4 Technical Guide Zone 7. PARAMETER TABLES Zone 7.7 SA Controller BACnet Parameters

BACnet Properties for SA Controller BACnet Properties for SA Controller Parameter Name Object Description Limits Parameter Name Object Description Unoccupied UnHtOst AV: 125 During the 0 30 Bad Supply SaTpAlm BI: 2 Alarm that indicates a failure in Heating Unoccupied Mode Air Sensor the supply air sensor. Offset of Operation, this Cooling ClEnbl BI: 6 Status that indicates Setpoint spreads mechanical cooling is enabled. the Occupied Enabled Heating Setpoint Economizer EcoEnbl BI: 15 Status that indicates out by a user Enabled the economizer is enabled. adjustable amount. Fan PofAlm BI: 26 Alarm that indicates a failure in If you do not want Proving the flow of the VFD blower. Heating to operate Alarm during the Unoc- cupied Mode, use Heating HtEnbl BI: 30 Status that indicates that me- the default setting Enabled chanical heating is enabled. of 30°F for these High HiSaAlm BI: 33 The Supply Air has risen above setpoints. Supply Air the Hi SAT Cutoff Setpoint. Static DuctPrSt AV: 152 This is the target 0.01 3 Temperature Heating stages begin to Pressure duct pressure to be Alarm deactivate and the fan continues Setpoint maintained by the to run. VFD blower signal. Low Supply LoSaAlm BI: 37 The Supply Air has fallen below Preheater PreHtSp AV: 196 Low Outside Air 0 100 Air the Hi SAT Cutoff Setpoint and Setpoint Ambient Temperature cooling stages will begin to Protection Setpoint Alarm deactivate. If the unit is in Economizer, Vent, or Heating Entering EaTpOst AV: 238 If the Entering Mode the Supply Fan Air Offset Air Temperature will shut off. Setpoint Sensor is reading incorrectly, you MODGAS II MdHt2Ins BI: 39 Status that indicates can use this option Connected the MODGAS II controller is to enter an offset connected. temperature to REHEAT II Rt2Ins BI: 58 Status that indicates adjust the Sensor’s Connected the MHGRV Temperature. controllers is connected to the Entering EwTpOst AV: 239 If the Entering system. Water Water Temperature Mechanical MchClAlm BI: 94 Compressor Relays are enabled Offset Sensor is reading Cooling but the Supply Air Temperature Setpoint incorrectly, you Alarm has not fallen 5°F w/in a user- can use this option adjustable time period. This does to enter an offset not indicate compressors are temperature to active and will not adjust the shut the unit down. Sensor’s Temperature. Mechanical MchHtAlm BI: 95 Heating Mode has been initiated Heating but the Supply Air Temperature Supply Air SaClRt AV: 324 High Supply Air 40 150 Alarm has not risen 5°F w/in a Cool High Cooling Reset user-adjustable time period. Reset Limit This does not indicate heat Supply Air SaHtRt AV: 325 High Supply Air 40 150 stages are active and will not Heat High Heating Reset shut the unit down. Reset Limit Dirty Filter DrtFlAlm BI: 96 Alarm that indicates the filters Cooling Low ClLoRt AV: 326 Low Cool Reset 1 150 Detected are dirty. Reset Source Source Setpoint Control CtrlTpCF BI: 108 This alarm is activated if the Cooling High ClHiRt AV: 327 High Cool Reset 1 150 Temperature control temperature does not Reset Source Source Setpoint Cool Failure get within 5°F to the occupied cooling setpoint in an hour in the Heating Low HtLoRt AV: 328 Low Heat Reset 1 150 cooling mode. This alarm is not Reset Source Source Setpoint used in 100% outside air units or Heating High HtHiRt AV: 329 High Heat Reset 1 150 supply air control. Reset Source Source Setpoint Fan Start Up FanDly BI: 25 Status that indicates Delay the fan is com- manded to run, but it is in the start up delay mode.

PT-LInk II BACnet4 Technical Guide 71 Zone 7. PARAMETER TABLES Zone 7.7 SA Controller BACnet Parameters

BACnet Properties for SA Controller BACnet Properties for SA Controller Parameter Name Object Description Parameter Name Object Description Control CtrlTpHF BI: 109 This alarm is activated if the Drain Pan DrnAlm BI: 244 Alarm that indicates overflow of Temperature control temperature does not Overflow the drain pan. Heat Failure get within 5°F to the occupied Proof of PoWFAlm BI: 245 Alarm that indicates no heating setpoint in an hour in the Water Flow Proof of Water Flow. heating mode. This alarm is not Alarm used in 100% outside air units or supply air control. Entering Air EaTpAlm BI: 248 Alarm that indicates Temperature failure in the Entering Air Space SpcTpAlm BI: 101 Alarm that indicates a failure in Alarm Temperature Sensor. Temperature the space temperature sensor. Sensor Lost On Board OnRly1 BI: 127 Current status of relay 1. Relay 1 On Board OnRly2 BI: 128 Current status of relay 2. Relay 2 7.7.1 SA Controller PT-Link-BACnet® On Board OnRly3 BI: 129 Current status of relay 3. Relay 3 Property Identifier: On Board OnRly4 BI: 130 Current status of relay 4. The PT-Link-BACnet® Link amends the following property identity to Relay 4 the BACnet® property identifier. On Board OnRly5 BI: 131 Current status of relay 5. Relay 5 BACNETPropertyIdentifier : Expansion ExRly1 BI: 133 Current status of relay 6. Relay 1 SAUnitMode ::= ENUMERATED { Expansion ExRly2 BI: 134 Current status of relay 7. Unoccupied (0), Relay 2 RemoteContactOccupied (1), Expansion ExRly3 BI: 135 Current status of relay 8. NormalScheduleOccupied (2), Relay 3 PushButtonOrZoneOverride (3), Expansion ExRly4 BI: 136 Current status of relay 9. HolidayModeActive (4), Relay 4 UnoccupiedZoneDemand (5), Expansion ExRly5 BI: 137 Current status of relay 10. RemoteScheduleOverride (6), Relay 5 CurrentOutputForceMode (7), Expansion ExRly6 BI: 138 Current status of relay 11. SATHighOrLowCutOff (8), Relay 6 CO2OverrideInProgress (9), Expansion ExRly7 BI: 139 Current status of relay 12. PurgeModeActive (10) Relay 7 } Expansion ExRly8 BI: 140 Current status of relay 13. Relay 8 SAControlStatusBits ::= ENUMERATED { Expansion ExRly9 BI: 141 Current status of relay 14. Off (0), Relay 9 Vent (1), Expansion ExRly10 BI: 142 Current status of relay 15. Cool (2), Relay 10 Heat (3), Expansion ExRly11 BI: 143 Current status of relay 16. Dehum (4), Relay 11 Dehum Cool (5), Expansion ExRly12 BI: 144 Current status of relay 17. Dehum Heat (6), Relay 12 Warm Up Mode (7) Expansion ExRly13 BI: 145 Current status of relay 18. Relay 13 } Expansion ExRly14 BI: 146 Current status of relay 19. Relay 14 Expansion ExRly15 BI: 147 Current status of relay 20. Relay 15 Expansion ExRly16 BI: 148 Current status of relay 21. Relay 16 Emergency EmerAlm BI: 219 Alarm that indicates Shutdown Emergency Shutdown. Alarm

72 PT-LInk II BACnet4 Technical Guide Zone 7. PARAMETER TABLES Zone 7.8 VCM BACnet Parameters

NOTE: Objects labeled AI and BI are read-only. Objects labeled AV are read/writeable. You cannot write directly BACnet Properties for the VCM Controller to Sensor Inputs. Parameter Name Object Description Limits Relief RfPr AI: 62 Current value of NOTE: When a new setpoint is received from BACnet, it is Pressure the building pres- maintained and used in temporary memory until the sure sensor. unit goes unoccupied. It is then stored in permanent Return Air CO2Level AI: 150 Current value of memory and will become the new default setpoint even CO2 Level the CO2 sensor. if power is cycled. Therefore, if power is cycled prior Return Air RaTp AI: 64 Current value of to the unit going unoccupied, the setpoint will not have Temperature the return tem- been stored in permanent memory. perature sensor. Space SpcTp AI: 72 Current value of BACnet Properties for the VCM Controller Temperature the space tem- perature sensor. Parameter Name Object Description Limits Supply Air SaTp AI: 83 Current value of Application AppVer AI: 99 Current version of the Temperature the supply air Software software in the unit. temperature Version sensor. Alarm AlmSts AI: 1 See page Temperature TpDmnd AI: 84 Based on the Status 71. Demand comparison Unit Mode UnitMode AI: 123 See page between the 71. current Control Control CtrlSts AI: 4 Current operational Temperature and Status status. the Heating or Cooling Setpoint Control CtrlTp AI: 9 Current value of the Temperatures. Temperature control temperature Does not work sensor. for supply air Occupied ClSt AI: 7 Occupied Mode control. Mode Enable Cooling VFD Blower VfdBwPos AI: 88 Current position Enable Setpoint Fan of the VFD blow- Cooling Mirror. er fan signal. Setpoint Mirror VFD Relief VfdExPos AI: 89 Current position Fan of the VFD relief Duct Static DuctPr AI: 14 Current value of the fan signal. Pressure duct static pressure sensor. Modulating MdHt2Pos AI: 38 Current position Gas Valve of MODGAS II Economizer EcoPos AI: 16 Current position of the Position modulating gas Position economizer damper. valve control. External ExRlys12 AI: 111 See page Reheat Value Rt2Pos AI: 60 Current position Relays 1-2 71. Position of MHGRV External ExRlys34 AI: 112 See page modulating hot Relays 3-4 71. gas reheat valve control. Indoor InRh AI: 67 Current value of the Humidity indoor humidity sensor. Alarm AlrmGrp1 AI: 104 See page 71. Group 1 Occupied HtSt AI: 31 Occupied Mode Mode Enable Heating Setpoint Alarm AlrmGrp2 AI: 105 See page 71. Enable Mirror. Group 2 Heating Alarm AlrmGrp3 AI: 106 See page 71. Setpoint Group 3 Mirror Dewpoint DptStM AI: 110 Mirror of the On Board OnRlys AI: 44 See page Setpoint DPtSt Relays 71. Mirror “read only.” Outdoor Air OaRh AI: 52 Current value of the Indoor RH InRhStM AI: 114 Mirror of the Humidity outdoor humidity Setpoint InRhSt “read sensor. Mirror only.” Outdoor Air OaTp AI: 54 Current value of the Modulating MdClPos AI: 115 Current position Temperature outdoor temperature Cool of the modulating sensor. Position cooling signal Outdoor Air OaWtbl AI: 55 Current calculated value (Chilled water or Wetbulb of the outdoor wetbulb digital compres- temperature. sor). PT-LInk II BACnet4 Technical Guide 73 Zone 7. PARAMETER TABLES Zone 7.8 VCM BACnet Parameters

BACnet Properties for the VCM Controller BACnet Properties for the VCM Controller Parameter Name Object Description Limits Parameter Name Object Description Limits Modulating MdHtPos AI: 116 Current position Minimum MinEcoSt AV: 151 This is the 1 100 Heat of the modulating Outside Air minimum Position heating signal Setpoint position of the (hot water or economizer in SCR heat). the occupied Bypass ByPasDmp AI: 153 Current position modes. Damper of the bypass Occupied OcpClSt AV: 42 If the control 0 99 Position damper signal. Mode temperature rises Enable one degree above Return RaDmp AI: 154 Current position Cooling this setpoint, Damper of the return Setpoint the control will Position damper signal. activate the cooling demand. Outdoor Air OaDwpt AI: 47 Current calcu- If the control Dewpoint lated outdoor air temperature is dewpoint added the Supply Air on version 1.09. Sensor, then the Current SaTpStM AI: 82 Current SAT cooling demand Supply Air Cooling or Heat- is always active. Setpoint ing setpoint if Occupied OcpHtSt AV: 43 If the control 0 99 there is no reset Mode temperature source; Current Enable drops one degree calculated SAT Heating below setpoint with Setpoint this setpoint, Reset Source. the control will Coil CoilTp AI: 181 Current coil activate the Temperature temperature heating demand. reading added on If the version 1.09. control temperature Preheater PreHtSp AV: 196 Low Outside Air 0 100 is the Supply Setpoint Ambient Air Sensor, then Protection there is no heat- Setpoint ing demand. Outdoor Air OaTpOst AV: 53 If the Outdoor -100 100 Sensor Offset Temperature Sensor is reading CO2 CO2St AV: 149 When the CO2 0 3000 Setpoint level rises incorrectly, you can use this op- above the CO2 Protection Limit tion to Max Level, the enter an offset Economizer’s temperature to Minimum Posi- adjust the Sen- tion will begin sor’s Tempera- to reset open ture. proportion- Relief RfPrSt AV: 118 This is the target -0.2 0.2 ally between the Pressure building pressure CO2 Protection Setpoint to be maintained Limit Max Level by the VFD Setpoint and Relief signal. the Reset Range Setpoint. Return Air RaTpOst AV: 65 If the Return -100 100 Sensor Offset Temperature Static DuctPrSt AV: 152 This is the target 0.01 3 Sensor is read- Pressure duct pressure to ing incorrectly, Setpoint be maintained by you can use this the VFD blower option to enter signal. an offset tem- perature to adjust the Sensor’s Temperature.

74 PT-LInk II BACnet4 Technical Guide Zone 7. PARAMETER TABLES Zone 7.8 VCM BACnet Parameters

BACnet Properties for the VCM Controller BACnet Properties for the VCM Controller Parameter Name Object Description Limits Parameter Name Object Description Limits Schedule SchdFrc AV: 66 0 = Auto/ 0 2 Dewpoint DptSt AV: 13 If the outdoor 35 80 Force Unoccupied Mode Setpoint dewpoint rises 1 = Forced On above this setpoint, 2 = Forced Off the unit will Space SpcTpOst AV: 71 If the Space -100 100 activate the Sensor Temperature Dehumidification Offset Sensor is reading Demand. incorrectly, you can Coil CoilTpSt AV: 107 This is the coil 35 70 use this option to Temperature suction temperature enter an offset Setpoint target during temperature to dehumidification adjust the Sensor’s mode. Produces Temperature. dewpoint in the SAT/Reset SaClSt AV: 77 Supply Air setpoint 40 80 supply air Source or Reset Source tar- approximately Cooling get temperature in 10°F above this Setpoint Cooling Mode. setpoint. SAT/Reset SaHtSt AV: 78 Supply Air setpoint 40 200 Indoor InRhSt AV: 120 If the indoor 0 100 Source or Reset Source tar- Humidity humidity rises Heating get temperature in Setpoint above this setpoint, Setpoint Heating Mode. the unit will activate the Supply SaTpOst AV: 80 If the Supply Air -100 100 Dehumidification Air Sensor Temperature Demand. Offset Sensor is reading incorrectly, you can Warm Up WmupSt AV: 91 In a VAV 50 90 use this option to Setpoint application, upon enter an offset entering the temperature to occupied mode, the adjust the Sensor’s Warm-up Demand Temperature. will be activated if the return air Unoccupied UnClOst AV: 124 During the 0 30 temperature falls Cooling Unoccupied Mode one degree below Offset of Operation, this this setpoint. Setpoint spreads the Occupied Wet Bulb WtblSt AV: 92 The economizer is 0 80 Cooling Setpoint Setpoint enabled if the out- out by a user door temperature or adjustable amount. wetbulb falls below If you do not want this setpoint. Cooling to operate Bad Supply SaTpAlm BI: 2 Alarm that during the Air Sensor indicates a failure Unoccupied Mode, in the use the default supply air sensor. setting of 30°F for CO Sensor CO2Cfg BI: 3 Status that these setpoints. 2 Installed indicates the CO2 Unoccupied UnHtOst AV: 125 During the 0 30 function has been Heating Unoccupied Mode configured. Offset of Operation, this Cooling ClDmnd BI: 5 Status that Setpoint spreads Demand indicates a demand the Occupied for cooling. Heating Setpoint out by a user Cooling ClEnbl BI: 6 Status that indicates adjustable amount. Enabled mechanical cooling If you do not want is enabled. Heating to operate Economizer EcoEnbl BI: 15 Status that indicates during the Enabled the economizer is Unoccupied Mode, enabled. use the default setting of 30°F for these setpoints.

PT-LInk II BACnet4 Technical Guide 75 Zone 7. PARAMETER TABLES Zone 7.8 VCM BACnet Parameters

BACnet Properties for the VCM Controller BACnet Properties for the VCM Controller Parameter Name Object Description Limits Parameter Name Object Description Limits Fan Start Up FanDly BI: 25 Status that indicates Mechanical MchHtAlm BI: 95 Heating Mode has Delay the fan is Heating been initiated but commanded to run, Alarm the Supply Air but it is in the start Temperature has up delay mode. not risen 5°F w/in Fan PofAlm BI: 26 Alarm that a user-adjustable Proving indicates a failure time period. This Alarm in the flow of the does not indicate VFD blower. heat stages are active and will not Heating HtDmnd BI: 29 Status that indicates shut the unit down. Demand a demand for heating. Dirty Filter DrtFlAlm BI: 96 Alarm that indicates Detected the filters are dirty. Heating HtEnbl BI: 30 Status that Enabled indicates that Control CtrlTpCF BI: 108 This alarm is mechanical heating Temperature activated if the is enabled. Cool Failure control temperature does not get within High HiSaAlm BI: 33 The Supply Air 5°F to the occupied Supply Air has risen above cooling setpoint Temperature the Hi SAT Cutoff in an hour in the Alarm Setpoint. Heating cooling mode. This stages begin to deac- alarm is not used tivate and the fan in 100% outside air continues to run. units or supply air Low Supply LoSaAlm BI: 37 The Supply Air has control. Air fallen below the Hi Control CtrlTpHF BI: 109 This alarm is Temperature SAT Cutoff Setpoint Temperature activated if the Alarm and cooling stages Heat Failure control temperature will begin to deacti- does not get within vate. If the unit is in 5°F to the occupied Economizer, Vent, heating setpoint or Heating Mode in an hour in the the Supply Fan will heating mode. This shut off. alarm is not used MODGAS MdHt2Ins BI: 39 Status that indicates in 100% outside air II the MODGAS II units or supply air Connected controller is control. connected. Dehu- DehmDmnd BI: 113 Status that indicates Proof of PofCfg BI: 57 Status that indicates midification a demand for Flow the proof of flow Demand dehumidification. Configured function has been Outdoor Air OaTpAlm BI: 117 Alarm that configured. Temperature indicates a failure REHEAT II Rt2Ins BI: 58 Status that indicates Lost in the outdoor air Connected the MHGRV con- temperature. trollers is connected Smoke SmokeAlm BI: 119 Alarm that indicates to the system. Detector the Smoke sensor Warm Up WmupD- BI: 90 Status that indicates Alarm has been activated. Mode mnd the control is in the Space SpcTpAlm BI: 101 Alarm that indicates Active Warm-up mode. Temperature a failure in the Mechanical MchClAlm BI: 94 Compressor Relays Sensor Lost space temperature Cooling are enabled but sensor. Alarm the Supply Air On Board OnRly1 BI: 127 Current status of Temperature has Relay 1 relay 1. not fallen 5°F w/in a user-adjustable On Board OnRly2 BI: 128 Current status of time period. This Relay 2 relay 2. does not indicate On Board OnRly3 BI: 129 Current status of compressors are Relay 3 relay 3. active and will not On Board OnRly4 BI: 130 Current status of shut the unit down. Relay 4 relay 4.

76 PT-LInk II BACnet4 Technical Guide Zone 7. PARAMETER TABLES Zone 7.8 VCM BACnet Parameters

BACnet Properties for the VCM Controller Parameter Name Object Description Limits On Board OnRly5 BI: 131 Current status of Relay 5 relay 5. Expansion ExRly1 BI: 133 Current status of Relay 1 relay 6. Expansion ExRly2 BI: 134 Current status of Relay 2 relay 7. Expansion ExRly3 BI: 135 Current status of Relay 3 relay 8. Expansion ExRly4 BI: 136 Current status of Relay 4 relay 9. Expansion ExRly5 BI: 137 Current status of Relay 5 relay 10. Expansion ExRly6 BI: 138 Current status of Relay 6 relay 11. Expansion ExRly7 BI: 139 Current status of Relay 7 relay 12. Expansion ExRly8 BI: 140 Current status of Relay 8 relay 13. Expansion ExRly9 BI: 141 Current status of Relay 9 relay 14. Expansion ExRly10 BI: 142 Current status of Relay 10 relay 15. Expansion ExRly11 BI: 143 Current status of Relay 11 relay 16. Expansion ExRly12 BI: 144 Current status of Relay 12 relay 17. Expansion ExRly13 BI: 145 Current status of Relay 13 relay 18. Expansion ExRly14 BI: 146 Current status of Relay 14 relay 19. Expansion ExRly15 BI: 147 Current status of Relay 15 relay 20. Expansion ExRly16 BI: 148 Current status of Relay 16 relay 21.

PT-LInk II BACnet4 Technical Guide 77 ZoneZone 7. PARAMETER TABLES ZoneZone 7.8 VCM BACnet Parameters

7.8.1 VCM PT-Link II BACnet® VcmExternal Relays1-2Bits::= BIT STRING { Property Identifier: ExpansionBoard1Relay1 (0), ExpansionBoard1Relay2 (1), The PT-Link II BACnet® Link amends the following property identity ExpansionBoard1Relay3 (2), ® to the BACnet property identifier. ExpansionBoard1Relay4 (3), ExpansionBoard2Relay1 (4), BACNETPropertyIdentifier : ExpansionBoard2Relay2 (5), WattBACNETScheduleForce ::= ENUMERATED { ExpansionBoard2Relay3 (6), NormalOperation (0), ExpansionBoard2Relay4 (7) ForceOccupied (1), } ForceUnoccupied (2) } VcmExternal Relays2-4Bits::= BIT STRING { ExpansionBoard3Relay1 (0), VcmUnitMode ::= ENUMERATED { ExpansionBoard3Relay2 (1), Unoccupied (0), ExpansionBoard3Relay3 (2), RemoteContactOccupied (1), ExpansionBoard3Relay4 (3), NormalScheduleOccupied (2), ExpansionBoard4Relay1 (4), PushButtonOrZoneOverride (3), ExpansionBoard4Relay2 (5), HolidayModeActive (4), ExpansionBoard4Relay3 (6), UnoccupiedZoneDemand (5), ExpansionBoard4Relay4 (7) RemoteScheduleOverride (6), } CurrentOutputForceMode (7), SATHighOrLowCutOff (8), VcmAlarmStatusBits ::= BIT STRING { CO2OverrideInProgress (9), Alarm Group1 (0), PurgeModeActive (10) Alarm Group2 (1), } Alarm Group3 (2) } VcmControlStatusBits ::= BIT STRING { Cool Demand (0), Heat Demand (1), DehumidificationMode (2), Cooling Enabled (3), Heating Enabled (4), Economizer Enabled (5), Fan Start-up Delay (6), Warm-up Mode Active (7), Fan Proving (8), RH Priority (9), CarbonDioxideSensorPresent (10), ModGasIIConnected (11), ReheatIIConnected (12) }

VcmOnBoardRelaysBits ::= BIT STRING { OnBoardRelay1 (0), OnBoardRelay2 (1), OnBoardRelay3 (2), OnBoardRelay4 (3), OnBoardRelay5 (4) }

78 PT-LInk II BACnet4 Technical Guide ZoneZone 8. FS-GUI REFERENCE GUIDE ZoneZone 8.1 FieldServer Graphical User Interface

8.1 The FieldServer Graphical User About Interface (FS-GUI) with Configuration About allows you to check the current firmware of the Field Server Parameter Page Navigation Tree gateway plus version identification of the interface and skin, plus contact information. Skin is either the default FieldServer template or a specific Open your web browser, and type the IP Address of the PT-Link, which template specified by the user. is <192.168.1.24>, and press . The FS-GUI Configuration Parameter Page will launch. See Figure 27. Setup

Setup includes File Transfer, Network Settings, and Passwords. File Transfer—Select “File Transfer” to upload files to the FS gateway, including configuration files, firmware, upgrades, and more. Information regarding File Transfers can be found on page 18. Network Settings—Select “Network Settings” to access and modify network connection. See page 80 for further information. Passwords—There are 2 levels of passwords that can be set, Admin and User. See pages 80-81 for further information.

View

View includes Connections, Data Arrays, Nodes, and Map Descriptors. Connections—This screen supplies information on communica- Figure 27: The FS-GUI Main Screen tion between the FS and remote devices. A number of aspect screens are available including settings, info stats, and error stats. The infor- mation on these screens cannot be changed and is for viewing only. Data Arrays—The Data Array Screens can be used to view the Refer to Figure 28 to navigate the FS-GUI. values in data arrays. The values can be changed by clicking the button. You can then edit setpoints by typing the new value and pressing . Note that if values are being written into the array by a driver, then any modifications made by grid editing will be overridden. Nodes—On the Nodes Screens, information about the remote device on each connection can be viewed. A number of aspect screens are available, including settings, status, info stats, and error stats. The in- formation on these screens cannot be changed and is for viewing only. Map Descriptors—On the Map Descriptors Screens, informa- tion on each individual Map Descriptor can be viewed. A number of aspect screens are available, including settings, status, info stats, and error stats. The information on these screens cannot be changed and is for viewing only.

User Messages Figure 28: The Navigation Tree The user message screens display FS messages generated by drivers and the operating system. Home or Root Error Screen—User messages on this screen usually indicate some problem with the configuration or communication and should The root of the navigation tree includes Status, Settings, and Info Stats. be attended to. Status allows you to check the status of the PT-Link gateway, including Info Screen—User messages of an informational type will be the configuration code, version, memory, gateway type, and more. Under displayed on this screen and no user action is usually required. Settings, you can access important network information. The name of Driver Screen—Messages generated by protocol drivers will be the root—Wattmaster MSTP v1.04i—is completely user definable. The displayed on this screen. These messages convey protocol specific button is found at the left bottom of the FS-GUI Main Screen. information that can be useful for field integration purposes. Press this button to return to FS-GUI Main Screen. Combined Screen—This screen contains all messages chronologi- cally from all the above message screens.

PT-LInk II BACnet4 Technical Guide 79 Zone 8. FS-GUI REFERENCE GUIDE Zone 8.1 FieldServer Graphical User Interface

HELP or F1 NOTE: The FieldServer has to be restarted for any changed The button is located at the bottom left of the FS-GUI Main settings to take effect. Also note that enabling the Screen. Or, simply press for Help. DHCP client on an adapter will cause the static IP address settings to be overruled by a DHCP server System Restart on the network.

The button is located at the bottom of the FS-GUI Main Screen. System Restart will restart the FS Gateway. The FieldServer’s built in DHCP server can be enabled to establish easy connection for Support purposes. Set the laptop or computer to automatically obtain an IP address to use this feature. Note that the Field Server DHCP server periodically checks for other DHCP servers on the network and will disable itself should any other DHCP servers 8.2 Network Settings exist on the network. This mode of operation is because the FieldServer DHCP server is strictly for support purposes and does not have all of the 1.) In the Navigation Window on the left of the FS-GUI Screen, click features of a commercial DHCP server. Setting the default gateway IP and then click . See Figure 29. The address to your network gateway will ensure the FieldServer is reach- Networks Settings Window will appear. able on the internet.

8.3 Setting a Password for the FS-GUI

Access to the FS-GUI can be restricted by enabling a password. By default, there are no passwords required to access the FS-GUI. There are 2 access levels defined by 2 account names: Admin or User. The Admin account has unrestricted access to the FS-GUI. The User ac- count can view any FS-GUI information, but cannot make any changes or restart the FS-GUI.

Figure 29: Setup - Network Settings NOTE: The current Admin password (if set) is required to change all passwords. In other words, you must log in with the Admin password to change a password 2.) In the Network Settings Window (Figure 30), the Ethernet adapter unless the password function is disabled. settings of the FieldServer can be changed. The N1 and N2 (if supported) adapter IP address, Netmask, and default Gateway can be changed by 1.) In the Navigation Window on the left of the FS-GUI Screen, click entering values in the applicable fields and clicking on and then click . See Figure 31. The Passwords Settings>. Window will appear.

NOTE: The only time you should change the IP address is during the initial configuration and/or during trouble- shooting.

Figure 31: Setup - Passwords

Figure 30: Network Settings Window

80 PT-LInk II BACnet4 Technical Guide Zone 8. FS-GUI REFERENCE GUIDE Zone 8.1 FieldServer Graphical User Interface

2.) In the Passwords Window, select as the Account Name. Then type a password in the New Password field, retype the password in the Confirm Password field and then click . See Figure 32. If you are changing the Admin password, you must type the current password in the Current Admin Password field.

NOTE: The password must be less than 20 characters in length. We recommend that the password be at least 3 8 characters in length and that /4 of the characters should consist of the following: uppercase letters, Figure 34: Clear Passwords lower case letters, numbers, and symbols. 5.) In order to return to the Passwords Window, in the Navigation Win- dow on the left of the FS-GUI Screen, click and then click . See Figure 35. The Passwords Window will appear.

Figure 32: Changing the Admin Password

3.) If the passwords match, the Authentication Window will pop up. You must type the User Name “Admin” and the password you just created in the window to proceed. See Figure 33. Figure 35: Setup - Passwords

6.) To create or update the User password, in the Passwords Window, select as the Account Name. You must type the Admin password in the Current Admin Password field. Thentype a password in the New Password field,retype the password in the Confirm Password field and then click . See Figure 36.

NOTE: The password must be less than 20 characters in length. We recommend that the password be at least 8 characters in length and that 6 of the characters should consist of the following: uppercase letters, lower case letters, numbers, and symbols. Figure 33: Authentication Log In

4.) After authentication takes place, the FS-GUI will return to the main screen.

NOTE: To disable password protection, clear the Admin password by simply selecting as the Account Name, typing in the Admin password in the Current Admin Password field and leaving the last Figure 36: Changing the User Password two fields blank. Then click . See Figure 34. 7.) If the user password update is successful, a message will pop up confirming the password update.

PT-LInk II BACnet4 Technical Guide 81 Zone 9. MAC ADDRESS & DEVICE INSTANCE Zone 9.1 MAC Address & Device Instance

® Set the BACnet MS/TP MAC Address Bank A DIP Switch Settings 1. Only (1) MAC address is set for the PT-Link regardless of how Address A1 A2 A3 A4 A5 A6 A7 A8 many devices are connected to it. 21 On Off On Off On Off Off Off 22 Off On On Off On Off Off Off 2. Set the BACnet® MS/TP MAC addresses of the PT-Link to a value between 1 and 127 (MAC Master Addresses). This is so that the 23 On On On Off On Off Off Off BMS Front End can find the PT-Link via the BACnet® auto 24 Off Off Off On On Off Off Off discovery function. MAC addresses from 128 to 255 cannot 25 On Off Off On On Off Off Off be auto discovered by the BMS Front End. 26 Off On Off On On Off Off Off 3. Set Bank A DIP switches A1 – A7 to assign a MAC Address to 27 On On Off On On Off Off Off ® the PT-Link for BACnet MS/TP. 28 Off Off On On On Off Off Off 29 On Off On On On Off Off Off NOTE: The BACnet® Device’s Instance is generated by adding 30 Off On On On On Off Off Off the MAC Address to the Node Offset, which defaults to 31 On On On On On Off Off Off 50,000. If the Device Instance must be set to something other than in the range of 50,001 to 50,127, see Section 32 Off Off Off Off Off On Off Off 3.3.2, page 12 to change the Node Offset value. 33 On Off Off Off Off On Off Off 34 Off On Off Off Off On Off Off 35 On On Off Off Off On Off Off CAUTION: DIP Switch 8 in Bank A must always remain OFF 36 Off Off On Off Off On Off Off for proper operation. 37 On Off On Off Off On Off Off 38 Off On On Off Off On Off Off 39 On On On Off Off On Off Off Bank A DIP Switch Settings 40 Off Off Off On Off On Off Off Address A1 A2 A3 A4 A5 A6 A7 A8 41 On Off Off On Off On Off Off 0 Off Off Off Off Off Off Off Off 42 Off On Off On Off On Off Off 1 On Off Off Off Off Off Off Off 43 On On Off On Off On Off Off 2 Off On Off Off Off Off Off Off 44 Off Off On On Off On Off Off 3 On On Off Off Off Off Off Off 45 On Off On On Off On Off Off 4 Off Off On Off Off Off Off Off 46 Off On On On Off On Off Off 5 On Off On Off Off Off Off Off 47 On On On On Off On Off Off 6 Off On On Off Off Off Off Off 48 Off Off Off Off On On Off Off 7 On On On Off Off Off Off Off 49 On Off Off Off On On Off Off 8 Off Off Off On Off Off Off Off 50 Off On Off Off On On Off Off 9 On Off Off On Off Off Off Off 51 On On Off Off On On Off Off 10 Off On Off On Off Off Off Off 52 Off Off On Off On On Off Off 11 On On Off On Off Off Off Off 53 On Off On Off On On Off Off 12 Off Off On On Off Off Off Off 54 Off On On Off On On Off Off 13 On Off On On Off Off Off Off 55 On On On Off On On Off Off 14 Off On On On Off Off Off Off 56 Off Off Off On On On Off Off 15 On On On On Off Off Off Off 57 On Off Off On On On Off Off 16 Off Off Off Off On Off Off Off 58 Off On Off On On On Off Off 17 On Off Off Off On Off Off Off 59 On On Off On On On Off Off 18 Off On Off Off On Off Off Off 60 Off Off On On On On Off Off 19 On On Off Off On Off Off Off 61 On Off On On On On Off Off 20 Off Off On Off On Off Off Off 62 Off On On On On On Off Off

82 PT-LInk II BACnet4 Technical Guide Zone 9. MAC ADDRESS & DEVICE INSTANCE Zone 9.1 Node ID (Device Instance) & MAC Address

Bank A DIP Switch Settings Bank A DIP Switch Settings Address A1 A2 A3 A4 A5 A6 A7 A8 Address A1 A2 A3 A4 A5 A6 A7 A8 63 On On On On On On Off Off 104 Off Off Off On Off On On Off 64 Off Off Off Off Off Off On Off 105 On Off Off On Off On On Off 65 On Off Off Off Off Off On Off 106 Off On Off On Off On On Off 66 Off On Off Off Off Off On Off 107 On On Off On Off On On Off 67 On On Off Off Off Off On Off 108 Off Off On On Off On On Off 68 Off Off On Off Off Off On Off 109 On Off On On Off On On Off 69 On Off On Off Off Off On Off 110 Off On On On Off On On Off 111 On On On On Off On On Off 70 Off On On Off Off Off On Off 112 Off Off Off Off On On On Off 71 On On On Off Off Off On Off 113 On Off Off Off On On On Off 72 Off Off Off On Off Off On Off 114 Off On Off Off On On On Off 73 On Off Off On Off Off On Off 115 On On Off Off On On On Off 74 Off On Off On Off Off On Off 116 Off Off On Off On On On Off 75 On On Off On Off Off On Off 117 On Off On Off On On On Off 76 Off Off On On Off Off On Off 118 Off On On Off On On On Off 77 On Off On On Off Off On Off 119 On On On Off On On On Off 78 Off On On On Off Off On Off 120 Off Off Off On On On On Off 79 On On On On Off Off On Off 121 On Off Off On On On On Off 80 Off Off Off Off On Off On Off 122 Off On Off On On On On Off 81 On Off Off Off On Off On Off 123 On On Off On On On On Off 82 Off On Off Off On Off On Off 124 Off Off On On On On On Off 83 On On Off Off On Off On Off 125 On Off On On On On On Off 84 Off Off On Off On Off On Off 126 Off On On On On On On Off 85 On Off On Off On Off On Off 127 On On On On On On On Off 86 Off On On Off On Off On Off 87 On On On Off On Off On Off 88 Off Off Off On On Off On Off 89 On Off Off On On Off On Off 90 Off On Off On On Off On Off 91 On On Off On On Off On Off 92 Off Off On On On Off On Off 93 On Off On On On Off On Off 94 Off On On On On Off On Off 95 On On On On On Off On Off 96 Off Off Off Off Off On On Off 97 On Off Off Off Off On On Off 98 Off On Off Off Off On On Off 99 On On Off Off Off On On Off 100 Off Off On Off Off On On Off 101 On Off On Off Off On On Off 102 Off On On Off Off On On Off 103 On On On Off Off On On Off

PT-LInk II BACnet4 Technical Guide 83 Zone 10. BACNET PICS STATEMENT Zone 10.1 BACnet® PICS Statement

10.1 ProtoCessor Driver - (PICS) BACnet® Interoperability Building Blocks BACnet® Protocol Implementation Supported (Annex K):

Conformance Statement 7 K.1.2 BIBB - Data Sharing - ReadProperty-B (DS-RP-B) 7 K.1.4 BIBB - Data Sharing - ReadPropertyMultiple-B BACnet® Protocol (DS-RPM-B) Date: January 2012 7 K.1.8 BIBB - Data Sharing - WriteProperty-B (DS-WP-B)

Vendor Name: Sierra Monitor Corporation 7 K.1.10 BIBB - Data Sharing - WritePropertyMultiple-B FieldServer Technologies (DS-WPM-B) 7 K.1.12 BIBB - Data Sharing - COV-B (DS-COV-B) Product Name: FieldServer QuickServer, ProtoNode, ProtoCarrier, ProtoCessor 7 K.2.2 BIBB - Alarm and Event-Notification Internal-B (AE-N-I-B) Product Model Number: ProtoCessor FFP-485 (FPC-FD2) 7 K.2.5 BIBB - Alarm and Event-ACK-B (AE-ACK-B) 7 K.2.11 BIBB - Alarm and Event-Information-B Product Description: ProtoCarrier and ProtoCessor are products (AE-INFO-B) supplied to OEMs to rapidly implement BACnet® in their products. 7 K.5.1 BIBB - Device Management - Dynamic Device Binding-A (DM-DDB-A) BACnet Protocol Version: Version 1 Revision 4 7 K.5.2 BIBB - Device Management - Dynamic Device Binding-B (DM-DDB-B) 7 K.5.4 BIBB - Device Management - Dynamic Object BACnet® Standarized Device Profile (Annex L) Binding-B (DM-DOB-B) - [Note: FieldServer is a gateway device] 7 K.5.6 BIBB - Device Management - Device Communication Control-B (DM-DCC-B) 7 BACnet Application Specific Controller (B-ASC) 7 K.5.12 BIBB - Device Management - Time Synchronization-B (DM-TS-B) 7 K.5.22 BIBB - Device Management – List Manipulation-B (DM-LM-B)

84 PT-LInk II BACnet4 Technical Guide Zone 10. BACNET PICS STATEMENT Zone 10.1 BACnet PICS Statement

Segmentation Capability: None For all of these properties, the following applies:

1.) Does not support BACnet CreateObject Object Types and Optional Properties Supported 2.) Does not support BACnet DeleteObject

3.) No proprietary properties exist Object Type Optional Properties Supported 7 Device Object Location Description Data Link Layer Options: UTC Offset 7 MS/TP master (Clause 9), baud rate up to 76.8 Kbps Active COV Subscriptions 7 Analog Input Reliability 7 MS/TP slave (Clause 9), baud rate up to 76.8 Kbps Description 7 Analog Output Reliability Description Device Address Binding: Not supported Max_Pres_Value Min_Press_Value 7 Analog Output Character Sets Supported: 7 Binary Input Reliability Description Where support for multiple character sets is indicated, this does not Active_Test imply that they can all be supported simultaneously. Inactive_Test 7 ISO 10646 (UTF-8) / ANSI X3.4 7 Binary Output Reliability Description Active_Test Inactive_Test 7 Binary Value Reliability Description Active_Test Inactive_Test 7 Multi State Input Reliability Description State_Test 7 Multi State Output Reliability Description State_Test 7 Multi State Value Reliability Description State_Test 7 Notification Class Object

PT-LInk II BACnet4 Technical Guide 85 PT-Link II BACnet4® Controller Technical Guide G042790 · Rev. 01E · 200414

AAON Factory Technical Support: 918-382-6450 [email protected]

AAON Controls Support: 866-918-1100 Monday through Friday, 7:00 AM to 5:00 PM central standard time

NOTE: Before calling Technical Support, please have the model and serial number of the unit available.

PARTS: For replacement parts please contact your local AAON Representative.

2425 So. Yukon Ave • Tulsa, OK • 74107-2728 Ph: (918) 583-2266 • Fax: (918) 583-6094 AAON® P/N: G042790, Rev. 01E Printed in the USA • © April 2020 AAON • All Rights Reserved