FIELDBUS COMPONENTS FOR FOUNDATION™

F1024/02 FIELDBUS COMPONENTS FOR FOUNDATION™ FIELDBUS

Fieldbus systems in process auto- Junction modules in IP67 Junction modules in IP20 mation (1, 4 and 6 ports) (4, 6, 8 and 12 ports) Fieldbus systems have become prevalent • Device versions for use in: • Device versions for use in: in the fi eld of process automation in – zone 1 – zone 1 addition to decentral peripheral systems. – zone 2 – zone 2 FOUNDATION™ fi eldbus and - – Non-Ex area – Non-Ex area PA fi eldbus systems are now the esta- • Adjustable current limitation • Adjustable current limitation blished fi eldbuses in this fi eld (for further • Switch-in terminating resistors • Switch-in terminating resistors information about the TURCK-product • Housing material: powder-coated • Housing material: aluminium portfolio and in particular PROFIBUS-PA aluminium die-cast (4- and 6-port • Connection technology: cage clamp products, please see catalog D301026). types) or encapsulated Polyurethane terminals or removeable connectors The advantages of both of these systems (PUR) for the single channel versions. are the process adapted specifi cation and • Connection technology: cable glands- the real interoperability of fi eld devices or fl ange connections from various manufacturers and their in 7/8“ or M12 × 1, stainless steel compatibility with external host systems.

Both the FOUNDATION™ fi eldbus and PROFIBUS-PA fi eldbus fulfi l the demands of the chemical, pharmaceutical and petrochemical industries. The most important features are : • standardised user profi le • suited for use in explosion hazardous areas • bus supply and fi eldbus Stainless steel housing for IP20 communication via shielded and junction boxes twisted pair cables • Plastic or stainless steel cable glands • online device exchange without • Degree of protection IP67 affecting system processes • Pressure compensation element • diagnostics for Asset Management • Isolated shielding bus Multibarriers in IP66 (4 ports) Comprehensive tests performed by the • Installation in explosion hazardous industry, interest groups and committees areas (zone 1) confi rm the unlimited suitability of both bus • Galvanic isolation between the EEx i systems for use in process engineering. outputs and the EEx e main cable as well as between the individual TURCK fi eldbus components EEx i outputs With TURCK products you are not tied • Fieldbus power supply accord- down to company-specifi c fi eldbus ing to enhanced safety EEx e technologies, but can choose the most • Four intrinsically safe EEx ia suitable bus product for your application outputs, 4 × 40 mA, short-circuit from a comprehensive product spectrum. protected and non-interacting • FISCO and Entity conform outputs TURCK offers the complete range for all (IEC TS 60079-27) conventional industrial fi eldbus systems in • Short-circuit indication via LEDs factory and process automation, no matter (inside housing) whether you require junction modules, • Integrated terminating resistors connection products or even complete (switch-in) systems.

TURCK fi eldbus components are spe- cially designed for the harsh industrial environment. The extensive product line for diverse applications fulfi ls all demands and provides Plug & Play connectivity to ensure fast and easy connection of the fi eld device to the control system.

Fieldbus cables and cordsets in various fi eldbus standards and materials and with different connector types are available for data transfer and voltage supply of the stations.

2 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com Diagnostic Power Conditioner System FISCO and FNICO power supply Terminating resistors • Segment and system diagnostics • Integrated repeater function • Versions for intrinsically-safe and • Commissioning support • Certifi ed to FISCO and FNICO non-intrinsically safe circuits 1 • Longterm diagnostics via FF-HSE • Switch-in terminating resistor • M12 × 1 or 7/8“ • FF functions blocks for diagnostic • Switch-in power supply for the host • Plug-and-Play technology alarms • Output current: • Connector pin assignment conform to • Diagnostics via DTM and/or DD – 120 mA or 265 mA for FISCO CENELEC standard EN 50044 • Redundant power supply – 180 mA or 320 mA for FNICO • High output power for extended fi eldbus segments (800 mA, 30 VDC) • Complete galvanic isolation

Special accessories • Stripping tool, stripping of round (shielded) data conductors from 2.5...8 mm Ø (also for FastConnect®/Fast Assembly™), Connectors • Special tool for cable glands on • Connector size: M12 × 1 or 7/8“, multibarrier and junction modules type: straight or angled • Closure caps and feed-throughs (angled M12 × 1 only) in 7/8“ and M12 × 1 • Plug-and-Play technology • Load capacity: 7/8“ with 9 A, M12 × 1 with 4 A • Connector pin assignment conform to Fieldbus cable available as bulk cable CENELEC standard EN 50044 or premoulded • For indoor and outdoor use • For connection to fi eld-wireable M12 × 1 or 7/8” connectors, PG9 or M16/M20 cable glands • Simple installation via Fast-Assembly™ technology • Just-In-Time delivery by the TURCK- JIT-5D-programme: Delivery of all available premoulded cable lenghts within 5 days.

Flange connections • Field-wireable or prefabricated • Connector size: M12 × 1 or 7/8“ • Solderable and screw-type versions • Standard installation thread • Stainless steel housings

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 3 /0309 Service & Support

A fast delivery service and a comprehen- sive e-support system perfectly comple- ment the extensive TURCK program.

With the product database, available on Around 13000 products, clearly structured www.turck.com, TURCK offers a fast and completely documented, are ready way to problem solving around the clock, for you to download together with all the seven days a week, at any place in this necessary information you need. world and in six different languages. Please have a look on: www.turck.com

4 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FIELDBUS COMPONENTS FOR FOUNDATION™ FIELDBUS

Fieldbus systems – Basics Page FOUNDATION™ fi eldbus – Bus physics 6 FOUNDATION™ fi eldbus – Topology 7 1 Overview – Application areas of TURCK’s fi eldbus components in the explosion hazardous and non-explosion hazardous area 9 Power conditioners/Power supplies Diagnostic power conditioner system DPC-49... 10 Power conditioner RPC-49-205 24 2 Power supply PSU-3214 26 FISCO power supplies RPC-49... 28

Active components Multibarrier MBD49-T415/Ex – Basics and application benefi ts 33 Multibarrier MBD49-T415/Ex 34 3 Fieldbus display FD-49-T317/Ex 36

Junctions Junctions by TURCK 39 T-pieces 40 4 Junction boxes in IP67 with short-circuit protection 42 Junction boxes in IP67 without short-circuit protection 66 Junction boxes in IP20 with short-circuit protection 90 Junction boxes in IP20 without short-circuit protection 106

Fieldbus cables Cable technology– Basics 122 Cable FBY-.../SD... 124 5 Cable FBY-BK/LD... 125 Cable FBH-YE... 126 Cable FBA-YE... 127 Cable 492A.../Cable 492BA... 128 Cable FB4910-BK... 129

Premoulded cables The TURCK JIT-5D-Programme 130 M12 × 1 with cable FBY49... 131 6 7/8“ with cable FBY49... 131 7/8“ with armoured cables 492A... or 492BA... 132

Flange connectors 7/8“ connector 134 M12 × 1 connector 140 7

Field wireable connectors 7/8“ connector 146 M12 × 1 connector 154 8

Bus termination resistors 7/8“ connector 159 M12 × 1 connector 160 9 7/8“ connector for Ex applications 161 Accessories Stainless steel housings 162 Stripping tool, special tool for cable glands, 10 closure caps, feed-through receptacles 166 Type index 172 11

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 5 /0309 FOUNDATION™ fi eldbus Basics

FOUNDATION™ fi eldbus – Bus physics With the publication of the international standard IEC 61158-2 in October 1994, a suitable transmission technology was bus voltage fieldbus data signal determined and internationally specifi ed for the application areas of FOUNDA- 0,75...1,0 VSS TION™ fi eldbus and PROFIBUS-PA. This was later integrated into the European standards as EN 61158-2. 9...32 V

Both systems comply with IEC 61158-2 and operate on the voltage mode with a transmission speed of 31.25 kBit/s. In this t way the data packages are modulated onto the supply voltage for the fi eldbus station and transmitted via a shielded two- Fig. 1 Transmission of data packages to IEC 61158-2 wire cable (see Fig. 1).

These bus physics offer a decisive advantage: fi eldbus communication and power supply of the bus station can be implemented using a single cable. These bus physics lead to enhanced operational safety and lower costs compared with the conventional fi eldbus solution used up to this point with its additional wiring effort.

Characteristic features of the IEC 61158-2 transmission physics

Data transmission digital, bit synchronous, Manchester coding

Transmission speed 31.25 kBit/s, voltage mode

Data security preamble, fault protected start and end delimiter

Cable shielded and twisted 2-wire cable

Remote supply of the stations optionally via signal cables

Protection classes intrinsically safe (Ex ia/ib or Ex nL), increased safe (Ex e or Ex nA) and explosion protected (EEx d/m/p/q)

Topology spur and tree topologies; also in combination

Number of stations up to 32 stations per cable segment

Repeater can be extended with a maximum of 4 repeaters

6 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fi eldbus – Topology The FOUNDATION™ fi eldbus network is 1 either PC Host-System • opened directly via a FOUNDATION™ fi eldbus segment card from the pro-

cess host system and supplied via H1 the TURCK DPC system (diagnostic power conditioner system) Segment in (Fig. 2 and 3) or • enabled via a “linking device” by high DPC speed Ethernet (HSE). PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X

We recommend the use of TURCK multi- Segment out barriers for a FOUNDATION™ fi eldbus Junction box application in the explosion hazardous JBBS-49..-..../-Ex area (Fig. 3) which can supply up to 32 stations (in the explosion hazardous area) when “cascaded”. The benefi ts compared to a simple intrinsically safe power supply device are primarily the enhanced number of stations within a bus segment. Further- more, a higher level of security is given by the enhanced level of availability provided by the galvanic isolation to all sides in the barrier (refer to page 33 for more details).

The number of multibarriers, which can be Fig. 2 Topology – FOUNDATION™ fi eldbus in the non-explosion hazardous area switched in, and the usable cable lengths depend on the output power of the power conditioner and also on the cable type. TURCK recommends the long-distance cable type FBY.../LD (see page 125) for PC Host-System the main cable (trunk line); for the outputs the standard cable type FBY.../SD (see page 124) is recommended. H1 Both system confi gurations in Fig. 2 and 3 are operated with the TURCK DPC sys- Segment in tem (diagnostic power conditioner sys- tem, see from page 10 on). Due to the DPC

high output power of the DPC system, PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X segments can be extended up to 1900 m.

Segment out

Multibarrier MBD49-T415/Ex

ü Trunk in Zone 1 ï EEx e EEx e Trunk out ï ý max. 120 m ï ï þ

Zone 0

Fig. 3 Topology – FOUNDATION™ fi eldbus in the explosion hazardous area

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 7 /0309 FOUNDATION™ fi eldbus Basics

In zone 2 a simple but safe energy limita- tion is necessary. Fig. 4 shows a FOUN- PC Host-System DATION™ fi eldbus network topology for zone 2. The power limitation can of cause be implemented in the power supply, e.g. with the TURCK-FNICO-Power-Supply. The advantage is, that working within zone 2 is possible while the system is under power. The disadvantages are, the Zone 2 low number of fi eld devices per FNICO-Power-Supply and a limited seg- FNICO Power Supplies ment extension of 1000 m maximum.

Due to these disadvantages TURCK rec- ommends the combination of the power Junction box conditioner and the TURCK junction JBBS-49..-..../-Ex boxes with short circuit protection, also applicable in zone 2. The trunk line is fed with explosion protection Ex nA, as the output of the power conditioner is voltage limited. The limitation of power in the junc- tion boxes is implemented such that the circuits of the drop line are limited accord- ing to Ex nL. Therefore working at the fi eld devices during operation is possible and the segment can be extended up to 1900 m max. (Fig. 5). Fig. 4 Topology – FOUNDATION™ fi eldbus with FNICO power supply in zone 2 A FOUNDATION™ fi eldbus network in non-Ex and Ex areas can also be estab- lished via a HSE-H1 link. HSE stands for “High Speed Ethernet” and supports Ethernet fi eldbus solutions. PC Host-System In addition to the Ethernet protocol family, the HSE also supports the FOUNDATION™ fi eldbus H1 protocol. As a result, it is possible to access every Ethernet based H1 network with a transmission speed of 10...1000 MBit/s in H1 fi eldbus segments. Segment in

HSE and H1 have been fundamentally developed as supplementary networks. Power Conditioner Whereas H1 has been optimized for appli- with voltage limitation cations in traditional process automation, HSE is more suited for high performance process control applications. Attractively- Segment out priced, commercial standard Ethernet Junction box devices can be operated in HSE applica- JBBS-49..-..../-Ex Trunk Ex nA tions. Zone 2

The combined H1 and HSE fi eldbus solu- tion enables complete integration of fun- Spurs Ex nL damental and complex industrial process instrumentation and measurement into the higher level control system. This kind of integrated architecture not only helps to reduce system downtimes but also provides improved diagnostic functions and better user information.

Fig. 5 Topology – FOUNDATION™ fi eldbus with power conditioner in zone 2

8 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com Overview – Application areas of TURCK’s fi eldbus components in the explosion hazardous and non-explosion hazardous area 1

Application in Application in Application in Installation Installation EEx i circuits EEx i circuits Ex nL in in the conform to FISCO conform to EN 60079-11 circuits Non-Ex conform to area EEx ia EEx ia EEx ib EEx ib Zone 0 Zone 1 Zone 2 Zone 0 Zone 1 Zone 2 FNICO Entity Zone 0 Zone 1 Zone 2

Junction boxes without short-circuit protection JBBS...M.../3G — — — — — — ✔ ✔ — ✔ ✔ ✔ JBBS...E.../3G — — — — — — ✔ ✔ — ✔ ✔ ✔ JBBS...T.../3G — — — — — — ✔ ✔ — ✔ ✔ ✔ Junction boxes with short-circuit protection JBBS...SC...M.../3G — — — — — — ✔ ✔ — — ✔ ✔ JBBS...SC...E.../3G — — — — — — ✔ ✔ — — ✔ ✔ JBBS...SC...T.../3G — — — — — — ✔ ✔ — — ✔ ✔

Ex junction boxes without short-circuit protection JBBS...M.../Ex ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ — ✔ ✔ ✔ JBBS...E.../Ex ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ — ✔ ✔ ✔ JBBS...T.../Ex ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ — ✔ ✔ ✔ Ex junction boxes with short-circuit protection JBBS...SC...M.../Ex ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ — ✔ ✔ ✔ JBBS...SC...E.../Ex ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ — ✔ ✔ ✔ JBBS...SC...T.../Ex ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ — ✔ ✔ ✔ Ex junction boxes for DIN rail mounting JRBS...1) ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ — ✔ ✔ ✔ Multibarriers MBD...2) ✔ ✔ ✔ ✔ ✔ ✔ — — — ✔ ✔ ✔ Power conditioner system — — — — — — — — — — — ✔ FISCO power supply — ✔ ✔ — — — ✔ ✔ — — ✔ ✔ FNICO power supply — — — — — — ✔ ✔ — — ✔ ✔ Terminating resistors RS...-TR — — — — — — — — — — — ✔ Ex terminating resistors RS...-TR/Ex ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ Passive equipment without electronics (cable, connectors, fl anges ...3) ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔

Application: ✔ = allowed — = not allowed

CAUTION 1) Use only permitted when installed in an additional housing (minimum IP54 degree of protection) If previously operated in non- 2) Equipment with differing protection classes – only the EEx i outputs have intrinsically safe applications, intrinsically safe circuits subsequent installation in 3) Taking consideration of the EN 60079-0, EN 60079-11 and EN 60079-14 standards intrinsically safe applications is not allowed.

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 9 /0309 FOUNDATION™ fieldbus Backplane for the DPC system DPC-49-4RMB

FOUNDATION™ fieldbus Backplane for the DPC system DPC-49-4RMB Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Host 1 2 3 4 + – S + – S + – S + – S

Err Diagnostic Segment 1A Segment 1B Segment 2A Segment 2B Segment 3A Segment 3B Segment 4A Segment 4B

Pwr A –+ + Pwr B –

+ – S + – S + – S + – S 321 4 Case Field Shield ground

The DPC system (Diagnostic Power Condi- The single components of the system are ● Module rack for up to 8 power sup- tioner) is a power supply system for the in- electrically linked via the connection termi- ply modules and 1 diagnostics mo- stallation of FOUNDATION™ fieldbus H1 nals of the backplane. From electrical per- dule for the mounting of up to 4 H1 segments. segments. It provides extensive diagnostic spective, the backplane is to be considered options for monitoring FOUNDATION™ passive. ● Redundant power supply fieldbus segments and thus supports plant- ● Removable terminal blocks with wide asset management. The power can be supplied via two 2-pole screw connections screw connectors. The connection of the ● RJ45 connector for HSE fieldbus A DPC system consists of one or more mo- host system is established per segment via diagnostics dule racks, each with up to eight DPC-49- removable 3-pole screw terminals. IPS1 power supply modules and one DPC- 49-ADU resp. DPC-49-DU diagnostics mo- For the connection of the H1 segments to dule. Up to four H1 segments for each mo- the fieldbus side, each segment is indivi- dule rack can be operated and monitored dually connected with a removable 3-pole redundantly in the FOUNDATION™ fieldbus screw terminal. network. The diagnostic data of the H1 segment can be transmitted via the HSE The shielding is achieved via insulated interface module DPC-49-HSEFD/24VDC shield bus or via the 3-pole screw terminal, to the higher level asset management sys- which is internally connected with the M5 tem (only in conjunction with the diagnos- threaded bolt for equipotential bonding. A tics module DPC-49-ADU). further M5 threaded bolt for equipontential bonding is simply connected to the hou- The module rack consist of a backplane sing. and the actual rack system for the power supply modules and the diagnostics mo- For simple diagnostics processing, a con- dule. nection is provided to the relay alarm con- tact of the diagnostics module.

10 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus Backplane for the DPC system DPC-49-4RMB

Type DPC-49-4RMB Dimensions Ident-No. 6882024

Operational voltage range: 18 … 32 VDC 113 Overvoltage protection > 250 VDC 220 107

Electrical connection removable terminal block, reverse polarity pro- tected, screw connection 2 RJ45 socket 210

Degree of protection IP20 Ambient temperature -20 …+ 60 °C Housing material aluminium Housing color black/yellow Dimensions 220 x 210 x 113 mm Connection mode snap-on DIN rail (EN 60715)

Accessories Type code Ident- Short text Dimension drawing No. BM-DPC 6882015 blind module for unused slots

118

103

18

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 11 /0309 FOUNDATION™ fieldbus Backplane for the DPC system DPC-49-4RMB/SY

FOUNDATION™ fieldbus Backplane for the DPC system DPC-49-4RMB/SY Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Host A Host B 1 2 3 4 1 2 3 4 + – S + – S + – S + – S + – S + – S + – S + – S

Err Diagnostic Segment 1A Segment 1B Segment 2A Segment 2B Segment 3A Segment 3B Segment 4A Segment 4B

Pwr A –+ + Pwr B –

+ – S + – S + – S + – S 321 4 Case Field Shield ground

The DPC system (Diagnostic Power Condi- The single components of the system are ● Module rack for up to 8 power sup- tioner) is a power supply system for the in- electrically linked via the connection termi- ply modules and 1 diagnostics mo- stallation of FOUNDATION™ fieldbus H1 nals of the backplane. From electrical per- dule for the mounting of up to 4 H1 segments. segments. It provides extensive diagnostic spective, the backplane is to be considered options for monitoring FOUNDATION™ passive. ● Redundant power supply fieldbus segments and thus supports plant- ● Redundant HOST connection wide asset management. The power can be supplied via two 2-pole ● Removable terminal blocks with screw connectors. The connection to the screw connections A DPC system consists of one or more mo- host system is provided via two system ca- dule racks, each with up to eight DPC-49- bles. Premoulded system cables are optio- ● RJ45 connector for HSE fieldbus diagnostics IPS1 power supply modules and one DPC- nally available at TURCK. 49-ADU resp. DPC-49-DU diagnostics mo- dule. Up to four H1 segments for each mo- For the connection of the H1 segments to dule rack can be operated and monitored the fieldbus side, each segment is indivi- redundantly in the FOUNDATION™ fieldbus dually connected with a removable 3-pole network. The diagnostic data of the H1 screw terminal. segment can be transmitted via the HSE interface module DPC-49-HSEFD/24VDC The shielding is achieved via insulated to the higher level asset management sy- shield bus or via the 3-pole screw terminal, stem (only in conjunction with the diagno- which is internally connected with the M5 stics module DPC-49-ADU). threaded bolt for equipotential bonding. A further M5 threaded bolt for equipontential The module rack consist of a backplane bonding is simply connected to the hou- and the actual rack system for the power sing. supply modules and the diagnostics mo- dule. For simple diagnostics processing, a con- nection is provided to the relay alarm con- tact of the diagnostics module.

12 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus Backplane for the DPC system DPC-49-4RMB/SY

Type DPC-49-4RMB/SY Dimensions Ident-No. 6882025

Operational voltage range: 18 … 32 VDC 113 Overvoltage protection > 250 VDC 220 107

Electrical connection removable terminal block, reverse polarity pro- tected, screw connection 2 RJ45 socket 210

Degree of protection IP20 Ambient temperature -20 …+ 60 °C Housing material aluminium Housing color black/yellow Dimensions 220 x 210 x 113 mm Connection mode snap-on DIN rail (EN 60715)

Accessories Type code Ident- Short text Dimension drawing No. BM-DPC 6882015 blind module for unused slots

118

103

18

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 13 /0309 FOUNDATION™ fieldbus Backplane for the DPC system DPC-49-1RMB

FOUNDATION™ fieldbus Backplane for the DPC system DPC-49-1RMB Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

+ Host – S + – Field S

Segment 1A Segment 1B

Err

+ Pwr A –

+ Pwr B –

Case Shield ground

The DPC system (Diagnostic Power Condi- The H1 segment is connected separately ● Module rack for two power supply tioner) is a power supply system for the in- on the fieldbus side via a removable 3-pole modules to built a H1 segment stallation of FOUNDATION™ fieldbus H1 screw terminal. ● Redundant power supply segments. ● Removable terminal blocks with The shielding is achieved via insulated screw connections The module rack consist of a backplane shield bus or via the 3-pole screw terminal, and the actual rack system for the power which is internally connected with the M5 supply modules. threaded bolt for equipotential bonding. A further M5 threaded bolt for equipontential The single components of the system are bonding is simply connected to the hou- electrically linked via the connection termi- sing. nals of the backplane. A connection to the relay alarm contact is Redundant power supply via two 2-pole provided for redundancy monitoring of the screw connectors. The connection to the external power supply and the H1 power host system is established via a removable supply modules. 3-pole screw terminal.

14 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus Backplane for the DPC system DPC-49-1RMB

Type DPC-49-1RMB Dimensions Ident-No. 6882026

113 Operational voltage range: 18 … 32 VDC 42 107 Overvoltage protection > 250 VDC

Electrical connection removable terminal block, reverse polarity pro- tected, screw connection 2 Degree of protection IP20 210 Ambient temperature -20 …+ 60 °C Housing material aluminium Housing color black/yellow Dimensions 220 x 210 x 113 mm Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 15 /0309 FOUNDATION™ fieldbus Power supply module DPC-49-IPS1

FOUNDATION™ fieldbus Power supply module DPC-49-IPS1 Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

ON Load Com Fault Segment out Host YE YE YE RD

Diagnostics

Pwr Power GN

The DPC system (Diagnostic Power Condi- performance. ● Supply of one FOUNDATION™ field- tioner) is a power supply system for the in- If two power supply modules are con- bus H1 segment stallation of FOUNDATION™ fieldbus H1 nected, the segment can be operated red- ● Output current: 800 mA segments. It provides extensive diagnostic undantly. Thereby the modules can be ● Output voltage: 28…30 VDC options for monitoring FOUNDATION™ plugged and unplugged during operation fieldbus segments and thus supports plant- (Hot swap-able in run). ● Local diagnostics via LEDs wide asset management. ● Complete galvanic isolation Due to complete galvanic isolation, A DPC system consists of one or more mo- H1 to H1, dule racks, each with up to eight DPC-49- H1 to internal supply, IPS1 power supply modules and one DPC- H1 to the diagnostic module , 49-ADU resp. DPC-49-DU diagnostics mo- H1 to HSE diagnostic bus, dules . Up to four H1 segments for each formation of parasitic voltages is avoided module rack can be operated and moni- and error-free communication is guaran- tored redundantly in the FOUNDATION™ teed. fieldbus network. The diagnostic data of the H1 segment can be transmitted via the Local comissioning and diagnostics are HSE interface module DPC-49-HSEFD/ supported by the following LED indications: 24VDC to the higher level asset manage- ment system (only in conjunction with the Pwr: green: Operational readiness diagnostics module DPC-49-ADU). ON/OFF: yellow: Output ON: Load: yellow: Consumer (field device) detec- The power supply module provides up to ted at segment: 30 VDC and 800 mA for the installation of a Com: yellow: Communication display H1 segment. The network topology can be Fault: red: Short-circuit message extended to 1900 m, due to the high output

16 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus Power supply module DPC-49-IPS1

Type DPC-49-IPS1 Dimensions Ident-No. 6882023

Supply voltage via the backplane Current consumption 0.8 … 1.7 A Test voltage complete galvanic isolation, test voltage 500 VAC

Output circuits Field 2 Output current ð 800 mA 118 Output voltage > 28 VDC Short-circuit protection ð 850 mA Efficiency 80 %

Output circuits HOST 103 Output current < 30 mA Output voltage 27 VDC 18

Indication Operational readiness 1 x green Output active 1 x yellow Output current 1 x yellow Short-circuit message 1 x red Bus communication 1 x yellow

Degree of protection IP20 Ambient temperature -20 …+ 60 °C Relative humidity ð 95% at 55 °C acc. to EN 60069-2 Housing material plastic flammability class V-0 to UL 96 Housing color yellow Dimensions 18 x 118 x 103 mm

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 17 /0309 FOUNDATION™ fieldbus Diagnostic module DPC-49-DU

FOUNDATION™ fieldbus Diagnostic module DPC-49-DU Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

The DPC system (Diagnostic Power Condi- interface module DPC-49-HSEFD/24VDC tioner) is a power supply system for the in- to the higher level Asset Management sys- ● Redundancy monitoring of 4 H1 stallation of FOUNDATION™ fieldbus H1 tem (only in conjunction with the diagnos- segments. segments. It provides extensive diagnostic tics module DPC-49-ADU). ● Local diagnostics via LEDs options for monitoring FOUNDATION™ ● Alarm signal via relay contact fieldbus segments and thus supports plant- The DPC-49-DU monitors the external wide asset management. power supply at the module rack, the ● Complete galvanic isolation FOUNDATION™ fieldbus-H1 power mo- A DPC system consists of one or more mo- dules and their redundant operation mode. dule racks, each with up to eight DPC-49- The diagnostic function can be switched off IPS1 power supply modules and one DPC- separately for each segment. 49-ADU or DPC-49-DU diagnostic modules . Up to four H1 segments per module rack The device features three LEDs indicating can be operated and monitored redun- the operating status. Alarm messages are dantly in the FOUNDATION™ fieldbus net- indicated by a red LED. Alarm signals are work. The diagnostic data of the H1 also output via a relay contact. segment can be transmitted via the HSE

18 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus Diagnostic module DPC-49-DU

Type DPC-49-DU Dimensions Ident-No. 6882021

Supply voltage via the backplane Current consumption < 100 mA Test voltage complete galvanic isolation, test voltage 500 VAC

Diagnostics 1 x relay 2 Switching current ð 1000 mA 118 Switching voltage ð 30 VDC galvanically isolated from other electronic de- vices

103 Operational readiness 2 x green

Alarm 1 x red 18

Degree of protection IP20 Ambient temperature -20 …+ 60 °C Housing material plastic flammability class V-0 to UL 96 Housing color yellow Dimensions 18 x 118 x 103 mm

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 19 /0309 FOUNDATION™ fieldbus Diagnostic module DPC-49-ADU

FOUNDATION™ fieldbus Diagnostic module DPC-49-ADU Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

HSE Host

H1

DPC-49-HSEFD/24VDC

DPC

Segment 1...4

The DPC system (Diagnostic Power Condi- The diagnostics module DPC-49-ADU is ● Long-term diagnostics for 4 H1 seg- tioner) is a power supply system for the in- used as a diagnostic interface between H1 ments stallation of FOUNDATION™ fieldbus H1 segments and the HSE interface module. ● Local diagnostics via LEDs segments. It provides extensive diagnostic The diagnostics module monitors the elec- ● Alarm signal via relay contact options for monitoring FOUNDATION™ trical and the communication parameters of fieldbus segments and thus supports plant- the H1 segments. Operation without dia- ● Complete galvanic isolation wide asset management. gnostics module is possible.

A DPC system consists of one or more mo- The diagnostic information is collected in dule racks, each with up to eight DPC-49- the device and transmitted via the HSE in- IPS1 power supply modules and one DPC- terface module to the higher fieldbus level 49-ADU resp. DPC-49-DU diagnostics mo- (e.g. the host) as diagnostic and alarm data. dules . Up to four H1 segments for each Thereby the modules can be plugged and module rack can be operated and moni- unplugged during operation (Hot swap-able tored redundantly in the FOUNDATION™ in run). fieldbus network. The diagnostic data of the H1 segment can be transmitted via the The device features LEDs indicating the HSE interface module DPC-49-HSEFD/ operating status of the H1 segments. A pre- 24VDC to the higher level asset manage- alarm is indicated by a yellow LED, the main ment system (only in conjunction with the alarm by a red LED. Additionally, alarm si- diagnostics module DPC-49-ADU). gnals can be analysed via a relay contact.

20 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus Diagnostic module DPC-49-ADU

Type DPC-49-ADU Dimensions Ident-No. 6882012

Supply voltage via the backplane Current consumption < 100 mA Test voltage complete galvanic isolation, test voltage 500 VAC

Diagnostics 1 x relay 2 Switching current ð 1000 mA 118 Switching voltage ð 30 VDC galvanically isolated against other electronic parts .

103 Operational readiness 1 x green / red

Alarm 4 x yellow / red 18

Degree of protection IP20 Ambient temperature -20 …+ 60 °C Housing material plastic flammability class V-0 to UL 96 Housing color yellow Dimensions 18 x 118 x 103 mm

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 21 /0309 FOUNDATION™ fieldbus HSE field device DPC-49-HSEFD/24VDC

FOUNDATION™ fieldbus HSE field device DPC-49-HSEFD/24VDC Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

HSE Host

H1

DPC-49-HSEFD/24VDC

DPC

Segment 1...4

The DPC system (Diagnostic Power Condi- nostics data of the DPC-49-ADU are trans- ● HSE interface device for transmissi- tioner) is a power supply system for the in- mitted via the HSE interface module but not on of diagnostics data stallation of FOUNDATION™ fieldbus H1 the process data of the H1 segments. Each ● FOUNDATION™ fieldbus function segments. It provides extensive diagnostic diagnostics module monitors up to four H1 blocks for remote diagnostics options for monitoring FOUNDATION™ segments. ● Local diagnostics via LEDs fieldbus segments and thus supports plant- wide asset management. As a FOUNDATION™ fieldbus device the ● Long-term diagnostics for 16 H1 segments HSE interface module features a resource A DPC system consists of one or more mo- and transducer block as well as several ● Complete galvanic isolation dule racks, each with up to eight DPC-49- standard function blocks. On the basis of IPS1 power supply modules and one DPC- these standard function blocks, suitable ap- 49-ADU resp. DPC-49-DU diagnostics mo- plications can be programmed in the con- dules . Up to four H1 segments for each trol system for the analysis of diagnostic module rack can be operated and moni- data. tored redundantly in the FOUNDATION™ fieldbus network. The diagnostic data of the Features H1 segment can be transmitted via the ● HSE interface device for transmission of HSE interface module DPC-49-HSEFD/ diagnostic data 24VDC to the higher level asset manage- ● FOUNDATION™ fieldbus function blocks ment system (only in conjunction with the for remote diagnostics diagnostics module DPC-49-ADU). ● Local diagnostics via LEDs ● Long-term diagnostics for 4 H1 seg- The diagnostic data of up to 16 H1 seg- ments ments are transmitted by the HSE interface module DPC-49-HSEFD/24VDC via the ● complete galvanic isolation FOUNDATION™ fieldbus-HSE to the higher level asset management system. Only diag-

22 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus HSE field device DPC-49-HSEFD/24VDC

Type DPC-49-HSEFD/24VDC Dimensions Ident-No. 6882014

47 Supply voltage via the backplane 21

Current consumption < 100 mA GW LNK/ACT Pwr 1 Pwr 2 DIAG/ACT +– +– Pwr 1 Pwr 2 Test voltage complete galvanic isolation, test voltage 500 52,5

DPC-49-HSEFD/24VDC VAC FOUNDATION fieldbusTM 105 45466 Mülheim an der Ruhr Germany

Diagnostic Ethernet Indication 2 Operational readiness 2 x green 32 31 State/ Fault 1 x yellow / red 107 176 Bus communication 1 x green / yellow Int. communication (CAN) 1 x yellow / red

Electrical connection removable terminal block, reverse polarity pro- tected, screw connection RJ45 connector

Degree of protection IP20 Ambient temperature -20 …+ 60 °C Housing material aluminium Housing color black/yellow Dimensions 176 x 105 x 31 mm Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 23 /0309 FOUNDATION™ fieldbus Power conditioner, dual channel RPC49-205

FOUNDATION™ fieldbus Power conditioner, dual channel RPC49-205 Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

+ Monitor 1 Power A GN –

+ Monitor 2 Power B GN –

Term. 1 Reset 1 + + GN RD I > 0,5A Segment 1 Out – – Segment 1 In S1 S1

Term. 2 Reset 2 Shield + + GN RD I > 0,5A Segment 2 Out – – Segment 2 In S2 S2 Shield

The RPC49-205 provides two segments for The two green LEDs indicate power ON. ● Supply of 2 H1-segments, connec- the installation of a FOUNDATION™ The green active LEDs also indicate power tion via removable screw terminals fieldbus network. In combination with the ON. The two short-circuit protected outputs ● Aluminium rail housing PSU-3214, each segment provides up to of the power conditioner switch off the ● Degree of protection IP20 500 mA with an output voltage of at least output in case of overload (I > 500 mA). The 27.5 V. The output voltage depends on the switch-off state is indicated by a red LED for ● Connection of the housing potential output current. each segment. The overload protection for via an M5 x 1 bolt the correspondent segment can be reset ● Monitor function The conditioner can be supplied redun- with two reset buttons. ● LEDs for indication of the operating dantly by two supply devices, whereby status "POWER A" is the primary input. As long as Hardware diagnostics is provided via the no redundant voltage supply is available , monitor terminals. The power conditioner is ● 2 x 500 mA output current the voltage supply should be connected to equipped with an optional terminating resi- ● Redundant power supply "POWER B". Should the voltage at stor for the bus. ● Short-circuit protected outputs "POWER A" drop below 20 V, input "POWER B" is energized.

24 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus Power conditioner, dual channel RPC49-205

Type RPC49-205 Dimensions Ident-No. 6603801

er

Operational voltage range: 21 … 32 VDC A tive Pow Ac 05 49-2 RPC uhr er R n d itor A on im a er M lhe B ow ü P Overvoltage protection > 36 VDC M e 5466 -4 Activ er A +– RCK D Pow TU set 1 Re

+– 1 In S1 ent Current consumption 535 mA (1 x 500 mA I ) off egm Term. out S on

1 +–2 In 2 ent S2 et 2 Segm Res 1043 mA (2 x 500 mA I ) ield out 30 Sh Voltage drop ð 4.4 V S1

S1 Shield 2 182 Output circuits 75 Output current ð 500 mA Output voltage Uout = Pwr - [2 V + (Iout x 4.4 Ohm)] Short-circuit protection ð 500 mA

Diagnostics 2 x solid state relay Segment (in/out): Switching current ð 700 mA Switching voltage ð 400 VDC galvanically isolated against other electronic S2 + – S1 + – –+S2 –+S1 parts . Segment 2 In Segment 1 In Segment 2 Out Segment 1 Out

Indication Operational readiness 2 x green power/monitor Output active 2 x green Short-circuit message 2 x red

Electrical connection 8 x 3-pole removable terminal blocks, screw +– –+ connection Power A Monitor A Power B Monitor B Terminal cross-section 2.5 mm2 Earthing bolt M5 x 1

Degree of protection IP20 Voltage dip/ load current Ambient temperature -20 …+ 70 °C UV [V] Relative humidity ð 95 %, non condensing 5 Housing material aluminium 4 Housing color black/yellow Dimensions 182 x 75 x 30 mm 3 Connection mode snap-on DIN rail (EN 60715) 2

1

0 0 0,1 0,2 0,3 0,4 0,5 IL [A]

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 25 /0309 Power supply single-channel PSU-3214

Power supply single-channel PSU-3214 Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

+ 94...265 VAC 32 VDC –

GN

The power supply unit PSU-3214 supplies Depending on the output current, the ● Output voltage 32 VDC a power conditioner. fieldbus segment is supplied with an output ● Output current 1.4 A voltage of approx. 29 V which is provided in The device provides safety extra-low combination with the TURCK power condi- ● Safety extra low voltage SELV ac- cording to IEC/EN 60950 voltage (SELV) according to IEC/EN 60950. tioner RPC49-205. It features protection class II and corre- ● Universal operating voltage sponds to EMC class B. Cable lengths of upto 1900 m in the Ex area (94…264 VAC) can be achieved with the TURCK multibar- The output volgate is 32 VDC with a ma- rier MBD49-T415/Ex in combination with ximum output current of 1.4 A. The over- the power conditioner. load protection is activated if the current exceeds 1.6 A. The green LED indicates operational readi- ness.

26 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com Power supply single-channel PSU-3214

Type PSU-3214 Dimensions Ident-No. 7545024

Operational voltage range: 94 … 265 VAC Frequency 47 … 63 Hz Current consumption 0.6 A at 230 V AC / 1.1 A at 120 V AC Starting current inrush I2t < 2.8 A2s Test voltage Input circuit to output circuit and supply 72 2 voltage for 250 Veff; test voltage 3 kVeff

L1 N NETZ Output circuits LINE

Output current ð 1400 mA PSU-3214

er Output voltage 32 VDC (± 3 %) Pow 32V / 1,4A AUSGANG OUTPUT Residual ripple ð 50 mV + – ss 105 Short-circuit protection ð 1600 mA 45 Efficiency 89 % Derating 2.5 %/K ( starting form +60°C)

Indication Operational readiness 1 x green Output curve Electrical connection flat terminals with self-lifting pressure plates 2 2 Terminal cross-section 1 x 2.5 mm / 2 x 2.5 mm V 35 Degree of protection IP20 Ambient temperature -10 …+ 70 °C 30 Housing material plastic 25 Housing color blue 20 Dimensions 45 x 72 x 105 mm 15 Connection mode snap-on DIN rail (EN 60715) 10 5 0 0 0,4 0,8 1,2 1,6 2,0 A

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 27 /0309 FOUNDATION™ fieldbus FISCO Power Supply RPC49-10120EX

FOUNDATION™ fieldbus FISCO Power Supply RPC49-10120EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

+ 7 4 – S1 IS fieldbus S 8 5 S Host fieldbus

– 9 6 +

S2

1 +

2 – Power

3 +

The intrinsically safe power supply RPC49- designed to exploit the very latest develop- ● FISCO compliant according to IEC 10120EX transmitts the fieldbus signal from ments of the FISCO specification (Fieldbus TS 60079-27 a host to an intrinsically safe fieldbus device Intrinsically Safe Concept) concerning the ● Protection type: [EEx ib] IIC in the Ex area, zone 2. application in explosion hazardous areas. ● Mounting possible in zone 2 To reap the full potential of digital fieldbus The RPC49-10120EX enables integrated communication without system inherent ● FISCO power supply for FOUNDATI- transmission between the host and fieldbus constrains is thus possible. ON™fieldbus connections and thus allows parallel con- ● Output current: 120 mA nection of several devices in the fieldbus The excellent performance and flexibility of ● Fieldbus - Repeater and accordingly a higher number of field the RPC49-10120EX makes it easy to plan, devices in the segment. install and mount fieldbus networks in com- ● Temperature range: -40 …+70°C pliance with the 31.25 kbits/s physical layer Designed to operate in harsh environments specification. Moreover, compatibility with and suitable for installation in zone 2, the the TURCK wiring components and acces- TURCK power supply RPC49-10120EX ex- sories ensures high reliability, low installation pands the boundaries for fieldbus topolo- costs and high operational safety. gies. Power supply to the host is procured via a The RPC49-10120EX provides upto 120 switch making additional power sources mA, powering field devices in Gas Group redundant. IIC. The device is mounted on DIN rail. It is

28 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus FISCO Power Supply RPC49-10120EX

Type RPC49-10120EX Dimensions Ident-No. 6604157

42 137,5 Operational voltage range: 19.2 … 30 VDC Current consumption 235 mA (typ.) 330 mA (max.) at 20 V 190 mA (typ.) 265 mA (max.) at 24 V 155 mA (typ.) 215 mA (max.) at 30 V Test voltage Input circuit to output circuit and supply 166 152,6 117 146 2 voltage for 250 Veff

Output circuits Output current ð 120 mA Output voltage 12.4 VDC Short-circuit protection ð 140 mA

Indication Operational readiness 1 x green Short-circuit message 1 x red Bus communication 2 x yellow

Ex approval acc. to conformity certificate BASEEFA 05 ATEX 0127 FISCO parameter according to IEC TS 60079-27

ð Max.output voltage Uo 14 V ð Max. output current Io 180 mA ð Max. output power Po 2520 mW External inductance/capacitance Lo/Co 300 μH / 0.2 μF Device designation É II (2) GD [EEx ib] IIC É II 3 G EEx nA II T4 X FISCO Power Supply

Electrical connection 3 x 3-pole removable terminal blocks, reverse polarity protected, screw connection or tension spring Terminal cross-section 2.5 mm2

Degree of protection IP20 Ambient temperature -40 …+ 70 °C Housing material plastic Housing color black/yellow Dimensions 42 x 166 x 137.5 mm Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 29 /0309 FOUNDATION™ fieldbus FISCO Power Supply RPC49-10265EX

FOUNDATION™ fieldbus FISCO Power Supply RPC49-10265EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

+ 7 4 – S1 IS fieldbus S 8 5 S Host fieldbus

– 9 6 +

S2

1 +

2 – Power

3 +

The RPC49-10265EX transmitts the latest developments of the FISCO specifica- ● FISCO compliant according to IEC fieldbus signal from a host to an intrinsically tion (Fieldbus Intrinsically Safe Concept) TS 60079-27 safe fieldbus device in the Ex area, zone 2. concerning the application in explosion ha- ● Protection type: [EEx ib] IIB zardous areas. To reap the full potential of ● Mounting possible in zone 2 The RPC49-10265EX enables integrated digital fieldbus communication without sy- transmission between the host and fieldbus stem inherent constrains is thus possible. ● FISCO power supply for FOUNDATI- connections and thus allows parallel con- ON™ fieldbus nection of several devices in the fieldbus The excellent performance and flexibility of ● Output current: 265 mA and accordingly a higher number of field the RPC49-10265EX makes it easy to plan, ● Fieldbus - Repeater devices in the segment. install and mount fieldbus networks in com- pliance with the 31.25 kbits/s physical layer ● Temperature range: -40 …+70°C Designed to operate in harsh environments specification. Moreover, compatibility with and suitable for installation in zone 2, the the TURCK wiring components and acces- TURCK power supply RPC49-10265EX ex- sories ensures high reliability, low installation pands the boundaries for fieldbus topolo- costs and high operational safety. gies. Power supply to the host is procured via a The RPC49-10265EX provides up to 265 switch making additional power sources mA, powering field devices in the Ex area of redundant. the Gas Group IIB. The device is mounted on DIN rail. It is designed to exploit the very

30 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus FISCO Power Supply RPC49-10265EX

Type RPC49-10265EX Dimensions Ident-No. 6604158

42 137,5 Operational voltage range: 19.2 … 30 VDC Current consumption 380 mA (typ.) 495 mA (max.) at 20 V 315 mA (typ.) 410 mA (max.) at 24 V 255 mA (typ.) 330 mA (max.) at 30 V Test voltage Input circuit to output circuit and supply 166 152,6 117 146 2 voltage for 250 Veff

Output circuits Output current ð 265 mA Output voltage 13.1 VDC Short-circuit protection ð 285 mA

Indication Operational readiness 1 x green Short-circuit message 1 x red Bus communication 2 x yellow

Ex approval acc. to conformity certificate BASEEFA 05 ATEX 0127 FISCO parameter according to IEC TS 60079-27

ð Max.output voltage Uo 14.8 V ð Max. output current Io 359 mA ð Max. output power Po 5310 mW External inductance/capacitance Lo/Co 550 μH / 0.5 μF Device designation É II (2) GD [EEx ib] IIB É II 3 G EEx nA II T4 X FISCO Power Supply

Electrical connection 3 x 3-pole removable terminal blocks, reverse polarity protected, screw connection or tension spring Terminal cross-section 2.5 mm2

Degree of protection IP20 Ambient temperature -40 …+ 70 °C Housing material plastic Housing color black/yellow Dimensions 42 x 166 x 137.5 mm Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 31 /0309 FOUNDATION™ fi eldbus

32 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fi eldbus Multibarrier MBD49-T415/Ex – Basics and application benefi ts

The operating principle of the MBD49- Intrinsic safety and galvanic isolation Functions which supplement the T415/Ex multibarrier is physically based between all outputs standard on IEC 61158-2. The use of multibarriers For safety reasons, galvanic isolation of • FISCO conformity increases the number of fi eldbus stations signals plays a decisive role in the Ex area. The FISCO model has been developed in the FOUNDATION™ fi eldbus network to The multibarrier provides four intrinsically for the supply of power to fi eldbus a maximum of 32 fi eld devices. safe and galvanically isolated outputs. The stations in the Ex area by the PTB in complete galvanic isolation exists between cooperation with renowned This high number of stations is achieved the main bus cable (trunk line) and the out- manufacturers. FISCO stands for by enhanced safety of the fi eldbus supply put circuits as well as between all of the Fieldbus Intrinsically Safe Concept. which can be looped through from multi- four individual output circuits. It is intended to simplify the verifi cation barrier to multibarrier. The fi eldbus stations of intrinsic safety of fi eldbus systems. in zone 0 are supplied with power via Galvanic isolation of intrinsically safe cir- Intrinsically safe networks can be the four intrinsically safe outputs of each cuits, as demanded by the industry, confi gured without highly complex multibarrier device. in particular for zone 0, is thus provided. calculations, and also expanded and 3 operated without system certifi cation. User benefi ts Potential transfers and potential equaliza- The outputs of the multibarrier are The user can expect substantial cost ad- tion currents are thus reduced and safe conform to the demands of an Ex vantages due to the possibility of cascad- data transmission is guaranteed. current supply and also conform to ing the multibarriers in a single segment FISCO. in the explosion hazardous area, thus fully Operational safety exploiting the entire function range of the Operational safety of the bus system must • Switch-in terminating resistors bus systems. be guaranteed should a bus station fail Data transmission on bus cables is or malfunction. The four outputs of the frequently infl uenced by signal refl ection, All fi eldbus devices can be operated in multibarrier each supply an output current which can occur when the bus ends are a single fi eldbus segment in the explo- of max. 40 mA. not terminated. The fi eldbus must be sion hazard area. Thus, the costs for an provided with a terminating resistor at additional bus coupler or a segment card If a short-circuit occurs on a fi eldbus sta- both ends in order to avoid signal as well as their integration and parameter tion, the integrated short-circuit protection refl ection. The multibarrier is provided defi nition are eliminated. An additional comes into play. Only the affected output with an integrated terminating resistor, trunk line and the wiring material is also will be shut down, the main line and the which should be activated, when the spared. other outputs of the fi eldbus segment multibarrier is connected as the last remain operational. The short-circuit is device on the main bus line (trunk line). The supply of power to the multibarriers indicated for each channel by a red LED is implemented via the bus which means inside the housing. • Climatic compensation that an additional power cable is not In regions subject to large temperature required. Industrially suitable housing and air-humidity variations, it is possible Industrial environmental conditions are fre- that formation of condensation or a Installation in the explosion hazar- quently harsh and aggressive. Therefore, build-up of water within the housing is dous area a housing suitable for these conditions is possible during operation. In order to The area of application to ATEX is necessary. The enhanced IP66 degree of avoid this, the multibarrier is fi tted on II 2 (1 GD) G EEx m e [ia] IIC T4. protection and the special housing mate- the cable connection end with a rial (die-cast aluminium) – in conjunction pressure equalization element to avoid Due to its EEx e protection rating, the with the encapsulated module electronics the build-up of condensation. MBD49-T415/Ex multibarrier can be – meet these demands and provide a high The pressure equalisation element installed in zone 1 (II 2 G) according to level of operational safety. Direct installa- features IP67 degree of protection and 94/9/EC (ATEX 95a). tion of a multibarrier in the system is thus guarantees continuous and reliable unproblematic. ventilation and venting of the Use in explosion hazardous areas with multibarriers. The ePTFE diaphragm in explosion protection group IIC – in con- The EEx e cable glands guarantee safe the centre of the gland features a very junction with temperature class T4 – is the and quick connection technology in high water ingress pressure and repels standard in the process industry. conjunction with the high-quality cage oil. Even 100 % of salt crystals are kept clamps. out. Within zone 1, the MBD49-T415/Ex is connected via a cable and connections Shield terminals are capacitively connec- with enhanced safety (EEx e) to the main ted to the housing potential in order to line (trunk line) of a fi eldbus conform to divert possible interference voltages on IEC 61158-2. This offers the advantage the cable shield. The riveted ground bolt that the connection to the bus can be connects the housing to the main poten- implemented using a loop isolator without tial equalization. EX approval, but with a suffi ciently high capacity.

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 33 /0309 FOUNDATION™ fieldbus Multibarrier, 4-port MBD49-T415/EX

FOUNDATION™ fieldbus multibarrier, 4-channel MBD49-T415/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

+ 1 – S RD 3,3 nF + + 2 – – Trunk In RD S S 3,3 nF

+ S1 3 – + S RD – Trunk Out 3,3 nF S 1,5 nF + 4 – S RD 3,3 nF

The 4-port multibarrier MBD49-T415/EX The multibarrier is equipped with an selec- ● Entity and FISCO compliant accor- enables the connection of a large number of table bus terminating resistor. This switch is ding to IEC TS 60079-27 field devices to one fieldbus in the Ex-area, integrated in the housing on the board. ● Galvanic isolation between the EEx i according to IEC 61158-2. outputs and the EEx e bus line, as The multibarrier is equipped with four LEDs well as between the EEx i outputs The number of field devices to be con- located on the printed circuit board inside ● Powder-coated die-cast aluminium nected to the multibarrier depends on the the housing to provide short-circuit indica- housing current consumption of the individual de- tions separately for each channel. ● Pressure compensation element for vices. Up to 32 EEx i field devices can be protection against condensation connected to the bus. The number of Because of complete galvanic isolation of water slaves can be extended by the EEx e the ● Connection of the housing potential fieldbus supply which can be looped ● trunk line to EEx i outputs and between via an M5 x 1 bolt through from multibarrier to multibarrier. the ● Temperature range: -20…+70 °C ● EEx i outputs, (-4…+158 °F) Inputs and outputs of the trunk line feature safe operation is guaranteed. increased safety protection (EEx e) and the ● Integrated terminating resistor (switch-in) outputs to the field devices are intrinsically safe (EEx i). ● Cable shielding: capacitive connec- tion to housing potential ● Output data: 10 V/40 mA (short-cir- cuit proof)

34 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus Multibarrier, 4-port MBD49-T415/EX

Type MBD49-T415/EX Dimensions Ident-No. 6611247

260 90 Fieldbus standard IEC 61158-2

Operational voltage range: 16 … 32 VDC Current self-consumption ð 40 mA 160 Test voltage input circuits (EEx e) to output circuits (EEx i) for 253 Veff; output circuits (EEx i) to each other for 60 Veff

Output circuits Output current ð 40 mA ï Output voltage 10 VDC Trunk line Short-circuit protection ð 45 mA 3

Indication Short-circuit message 4 x red S S – – + + EEx e Ex approval acc. to conformity certificate PTB 04 ATEX 2021 ð Max.output voltage Uo 14.3 V ð Max. output current Io 268 mA ð Outputs Max. output power Po 958 mW Internal resistance R 53.3 ò i S1 S2 S3 S4 External inductance/capacitance Li/Ci negligible Characteristic Linear Device designation É II 2(1 G/D)G EEx m e [ia] IIC T4 + – S + – S + – S + – S FISCO / Entity multibarrier EEx i

Electrical connection cable glands Segment IN 1 x M20 x 1.5 (Ø 10…14 mm); plastic; black Current consumption Segment OUT 1 x M20 x 1.5 (Ø 10…14 mm); plastic; black Drop line 4 x M20 x 1.5 (Ø 5…9 mm); plastic; blue mA Terminal cross-section 2.5 mm2 300 Earthing bolt M5 x 1 250 I Degree of protection IP66 200 max Ambient temperature -20 …+ 70 °C 150 Relative humidity ð 95 %, non condensing 100 Housing material powder-coated die-cast aluminium 50 Imin Housing color black/yellow 0 Dimensions 260 x 160 x 90 mm 16 1820 22 24 26 2830 32 V Connection mode Wall mounting

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 35 /0309 FOUNDATION™ fieldbus Fieldbus display, 3-port FD-49-T317/EX

FOUNDATION™ fieldbus Fieldbus display, 3-channel FD-49-T317/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

The 3-port digital indicator FD-49-T317/EX Apart from a measuring value indicator, the displays the process information of the display contains a 41-segment bargraph for ● Entity and FISCO compliant accor- fieldbus nodes of a FOUNDATION™ trend monitoring, which can be scaled ding to IEC TS 60079-27 fieldbus network. separately from the display value. ● Digital fieldbus display for the indi- cation of process values The device (listener) receives and displays The FD-49-T317/EX performs as a "li- ● Powder-coated die-cast aluminium the values of the adjusted fieldbus stener", i.e. initialization by the host is not housing addresses. Parameterization is code word required (integration via software redundant) ● Connection of the housing potential protected and implemented via a keypad and does not appear in the network as a via external earthing on the front side. Adjustements can be node with an own address. done for each port separately. The process value of the actuator/sensor is displayed as The device is supplied with energy by the a 5-digit number and the process value fieldbus (≤ 10 mA) and can be applied in Ex status is displayed via limit value markers. areas up to temperatures of the class T6.

36 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus Fieldbus display, 3-port FD-49-T317/EX

Type FD-49-T317/EX Dimensions Ident-No. 6901312

Fieldbus standard IEC 61158-2

Operational voltage range: 9 … 30 VDC 125 140 Current self-consumption ð 10 mA

Indication

103 71 Display LCD, 5-digit, 7-segment 140

Ex approval acc. to conformity certificate TÜV 07 ATEX 553588 ð Max. input voltage Ui 30 V ð Max. input current Ii 660 mA ð 3 Max. input power Pi 1600 mW External inductance/capacitance Li/Ci negligible Device designation É II 2(1) G EEx ia IIC T6 bzw. T5 É II 2 D IP65 T70°C FISCO / Entity field device

Electrical connection cable glands Terminal cross-section 2.5 mm2

Degree of protection IP66 Ambient temperature -10 …+ 60 °C Housing material powder-coated die-cast aluminium Housing color black Dimensions 140 x 140 x 71 mm Connection mode Wall mounting

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 37 /0309 FOUNDATION™ fi eldbus

38 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fi eldbus Junctions by TURCK

TURCK offers junctions in various designs IP67 T-pieces and junction boxes with IP20 junction boxes with or without for the distribution of energy and data. or without short-circuit protection short-circuit protection (1, 4 and 6 ports) (4 , 6, 8 and 12 ports) The junctions differ in the number of ports, • Explosion-protected junctions (for use • Suitable for the explosion hazardous the housing style and special features in zone 1 or 2, distribution of EEx ia and the safe area such as integrated short-circuit protection, signals in zone 0) • For use in zone 1 or 2, distribution of switch-in terminating resistor and selec- • Standard junctions (non-Ex) EEx ia signals in zone 0 table shielding concept. • IP67 degree of protection • IP20 degree of protection • Switch-in terminating resistor • Switch-in terminating resistor The following junctions are available as • Selectable shielding concept • Selectable shielding concept standard versions. (hard-wired or capacitive grounding) (hard-wired or capacitive grounding) Special solutions are available on request. • Active and passive types • Active and passive types • Pressure compensation element to • Housing material: aluminium prevent water condensation • Connection technology: • Housing material: powder-coated cage-clamp terminals or removable die-cast aluminium screw terminals (4 and 6-port type) • Temperature range: -40°C ...+70°C • Connection technology: stainless steel fl ange connectors 7/8“, M12 or cage- 4 clamp terminals • Cable glands: plastic, stainless steel, nickel-plated brass, EMC • Temperature range: -25°C ... +70°C

CAUTION Explosion Danger! The EC type test examina- tion certifi cate and the manufacturer’s declaration of conformity must be observed. It is essential that the “special conditions” in the EU type test certifi cate are observed.

Junction boxes, which have been used in non intrinsically safe applications, may not be used in intrinsically safe applications subsequently.

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 39 /0309 ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems T-piece RSV-2RKV49

● Version: 7/8’’ connector ● 4-pole, T-piece, stainless steel cou- pling nut ● For use in FOUNDATION Fieldbus™ 73,0 7/8-16UN applications 37,4 28,0

17,5 FOUNDATION™ fieldbus connection 34,8 ø 26,0 7/8-16UN 7/8-16UN 1 = – ø 26,0 1 3 2 = + 2 4 3 = shield 4 = n.c.

Type RSV-2RKV49 Ident-No. 6602319

Junction box T adapter, 7/8'' v Polarity 4-pole 1 = – Grip plastic, PUR, yellow 3 1 2 = + 4 2 3 = shield 4 = n.c. Connector female connector, 2x, 7/8", straight Grip plastic, PUR, yellow Contact carriers plastic, PUR, black Contacts metal, CuZn, gold-plated Coupling nut/screw stainless steel, 1.4404 Wiring diagram Seal plastic Degree of protection IP67, only with screws tightened 1 1 Mechanical lifespan min. 100 Contact durability Pollution degree 3/2 2 2

Connector Connector, 1x, 7/8", straight 3 3 Grip plastic, PUR, yellow Contact carriers plastic, PUR, black 4 4 Contacts metal, CuZn, gold-plated Coupling nut/screw stainless steel, 1.4404 Degree of protection IP67, only when plugged in Mechanical lifespan min. 100 Contact durability 1234 Pollution degree 3/2

Rated voltage max. 250 V Ampacity 4 A Forward resistance ð 5 mò Insulation resistance ï 109 ò Ambient temperature junction -40 … + 80 °C

40 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems T-piece RSCV-2RKCV49

● Version: M12 connector ● 4-pole, T-piece, stainless steel cou- pling nut ● For use in FOUNDATION™ fieldbus 54,9 applications 23,5

FOUNDATION™ fieldbus connection

M12 x 1 M12 x 1

M12 x 1 2 1 = – 2 = + 3 1 3 = shield 4 4 = n.c.

Type RSCV-2RKCV49 Ident-No. 6603431 4 Junction box T adapter, M12 x 1 v Polarity 4-pole 2 1 = – Grip plastic, PUR, yellow 2 = + 1 3 3 = shield 4 4 = n.c. Connector female connector, 2x, M12 x 1, straight Grip plastic, PUR, yellow Contact carriers plastic, PA 6, black Contacts metal, CuZn, gold-plated Coupling nut/screw stainless steel, 1.4404 Wiring diagram Seal plastic Degree of protection IP67, only with screws tightened 1 1 Mechanical lifespan min. 100 Contact durability Pollution degree 3/2 2 2

Connector Connector, 1x, M12 x 1, straight 3 3 Grip plastic, PUR, yellow Contact carriers plastic, PA, black 4 4 Contacts metal, CuZn, gold-plated Coupling nut/screw stainless steel, 1.4404 Degree of protection IP67, only when plugged in Mechanical lifespan min. 100 Contact durability 1234 Pollution degree 3/2

Rated voltage max. 250 V Ampacity 4 A Forward resistance ð 5 mò Insulation resistance ï 109 ò Ambient temperature junction -40 … + 80 °C

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 41 /0309 FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49SC-T415/3G

FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49SC-T415/3G Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Segment IN 1µF Segment OUT n.c. 1 1 n.c. S 2 2 S P1 S0 + 3 3 + – 4 4 –

n.c. 1 1 n.c. S 2 2 S S1 S2 + 3 3 + – 4 4 –

n.c. 1 1 n.c. S 2 2 S S3 S4 + 3 3 + – 4 4 –

Case ground

The 4-port Ex-junction module JBBS- the board. ● Entity and FNICO compliant accor- 49SC-T415/3G is designed for FOUNDA- ding to IEC TS 60079-27 TION™ fieldbus systems. To avoid condensation build-up in the hou- ● Mounting possible in zone 2 sing, the devices are equipped with a con- ● Junction box for wall mounting with The junction box features an adjustable densate drain. PVC cable glands M20 x 1.5 short-circuit limit. The max. current limita- tion is selected for all ports via a rotary The shield is capacitively coupled to the ● Powder-coated die-cast aluminium housing switch. The following values can be sel- housing potential. A switch for direct cou- ected: 30, 35, 45 and 60 mA. pling of the shield and housing is imple- ● Pressure compensation element for mented. protection against condensation water The housing is made of robust die-cast alu- minium and features protection degree Attention: Sufficient equipotential bonding ● Connection of the housing potential IP67. of the installation must be ensured. The de- via an M5 x 1 bolt vice is connected via the bolt of the hou- ● Short-circuit protection per drop The junction box is equipped with a selec- sing to the system’s potentializer. line/spur table bus terminating resistor. The accor- ● For Ex applications: -25…+70 °C ding switch is integrated in the housing on (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) ● Integrated terminating resistor (switch-in) ● Cable shielding: capacitive or direct connection to housing potential sel- ectable via switch ● Isolated support terminal for optio- nal protective conductor incorpora- ted in cable

42 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49SC-T415/3G

Type JBBS-49SC-T415/3G Dimensions Ident-No. 6611440

122 Fieldbus standard IEC 61158-2 64 36 45 Operational voltage range: 12 … 32 VDC Current self-consumption ð 7 mA Voltage drop ð 0.3 V

138 Short-circuit protection ð 30 , 35 , 45 , 60 mA 150 Indication 172 Operational readiness 1 x green Short-circuit message 4 x red

Ex approval acc. to conformity certificate PTB 07 ATEX 2017 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device Terminal Configuration Electrical connection cable glands 4 Segment IN 1 x M20 x 1.5 (Ø 6…12 mm) Segment OUT 1 x M20 x 1.5 (Ø 6…12 mm) 1 = n.c. Drop line 4 x M20 x 1.5 (Ø 6…12 mm) 2 = shield 2 3 = + Terminal cross-section 2.5 mm 1234 4 = – Earthing bolt M5 x 1

Degree of protection IP67 Ambient temperature -25 …+ 70 °C Housing material powder-coated die-cast aluminium Housing color black/yellow Dimensions 64 x 150 x 45 mm Connection mode Wall mounting

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 43 /0309 FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49SC-T615/3G

FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49SC-T615/3G Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Trunk In 1µF Trunk Out n.c. 1 1 n.c. S 2 2 S P1 S0 + 3 3 + – 4 4 –

n.c. 1 1 n.c. S 2 2 S S1 S2 + 3 3 + – 4 4 –

n.c. 1 1 n.c. S 2 2 S S3 S4 + 3 3 + – 4 4 –

n.c. 1 1 n.c. S 2 2 S S5 S6 + 3 3 + – 4 4 –

case ground

The 6-port Ex-junction module JBBS- the board. ● Entity and FNICO compliant accor- 49SC-T615/3G is designed for FOUNDA- ding to IEC TS 60079-27 TION™ fieldbus systems. To avoid condensation build-up in the hou- ● Mounting possible in zone 2 sing, the devices are equipped with a con- ● Junction box for wall mounting with The junction box features an adjustable densate drain. PVC cable glands M20 x 1.5 short-circuit limit. The max. current limita- tion is selected for all ports via a rotary The shield is capacitively coupled to the ● Powder-coated die-cast aluminium housing switch. The following values can be sel- housing potential. A switch for direct cou- ected: 30, 35, 45 and 60 mA. pling of the shield and housing is imple- ● Pressure compensation element for mented. protection against condensation water The housing is made of robust die-cast alu- minium and features protection degree Attention: Sufficient equipotential bonding ● Connection of the housing potential IP67. of the installation must be ensured. The de- via an M5 x 1 bolt vice is connected via the bolt of the hou- ● Short-circuit protection per drop The junction box is equipped with a selec- sing to the system’s potentializer. line/spur table bus terminating resistor. The accor- ● For Ex applications: -25…+70 °C ding switch is integrated in the housing on (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) ● Integrated terminating resistor (switch-in) ● Cable shielding: capacitive or direct connection to housing potential sel- ectable via switch ● Isolated support terminal for optio- nal protective conductor incorpora- ted in cable

44 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49SC-T615/3G

Type JBBS-49SC-T615/3G Dimensions Ident-No. 6611442

122 Fieldbus standard IEC 61158-2 64,0 36,0 45,0 Operational voltage range: 12 … 32 VDC Current self-consumption ð 7 mA Voltage drop ð 0.3 V 173,5 Short-circuit protection ð 30 , 35 , 45 , 60 mA

Indication 185,5 Operational readiness 1 x green 207 Short-circuit message 6 x red

Ex approval acc. to conformity certificate PTB 07 ATEX 2017 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device

Electrical connection cable glands 4 Segment IN 1 x M20 x 1.5 (Ø 6…12 mm) Segment OUT 1 x M20 x 1.5 (Ø 6…12 mm) Terminal Configuration Drop line 6 x M20 x 1.5 (Ø 6…12 mm) Terminal cross-section 2.5 mm2 Earthing bolt M5 x 1 1 = n.c. 2 = shield 3 = + Degree of protection IP67 1234 4 = – Ambient temperature -25 …+ 70 °C Housing material powder-coated die-cast aluminium Housing color black/yellow Dimensions 64 x 185.5 x 45 mm Connection mode Wall mounting

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 45 /0309 FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49SC-E413/3G

FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49SC-E413/3G Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Segment IN 1µF Segment OUT – 1 1 – + 2 2 + P1 S0 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S1 S2 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S3 S4 S 3 3 S n.c. 4 4 n.c.

Case ground

The 4-port Ex-junction module JBBS- the board. ● Entity and FNICO compliant accor- 49SC-E413/3G is designed for FOUNDA- ding to IEC TS 60079-27 TION™ fieldbus systems. To avoid condensation build-up in the hou- ● Mounting possible in zone 2 sing, the devices are equipped with a con- ● Junction box for wall mounting with The junction box features an adjustable densate drain. stainless steel M12 flange connec- short-circuit limit. The max. current limita- tions tion is selected for all ports via a rotary The shield is capacitively coupled to the ● Powder-coated die-cast aluminium switch. The following values can be sel- housing potential. A switch for direct cou- housing ected: 30, 35, 45 and 60 mA. pling of the shield and housing is imple- mented. ● Pressure compensation element for protection against condensation The housing is made of robust die-cast alu- water minium and features protection degree Attention: Sufficient equipotential bonding IP67. of the installation must be ensured. The de- ● Connection of the housing potential via an M5 x 1 bolt vice is connected via the bolt of the hou- The junction box is equipped with a selec- sing to the system’s potentializer. ● Short-circuit protection per drop table bus terminating resistor. The accor- line/spur ding switch is integrated in the housing on ● For Ex applications: -25…+70 °C (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) ● Integrated terminating resistor (switch-in) ● Cable shielding: capacitive or direct connection to housing potential sel- ectable via switch ● Isolated support terminal for optio- nal protective conductor incorpora- ted in cable

46 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49SC-E413/3G

Type JBBS-49SC-E413/3G Dimensions Ident-No. 6611432

83 Fieldbus standard IEC 61158-2 64 36 45 Operational voltage range: 12 … 32 VDC Current self-consumption ð 7 mA Voltage drop ð 0.3 V

Short-circuit protection ð 30 , 35 , 45 , 60 mA 138

Indication 150 Operational readiness 1 x green 172 Short-circuit message 4 x red

Ex approval acc. to conformity certificate PTB 07 ATEX 2017 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device

Electrical connection M12 flange connection 4 Terminal Configuration Segment IN 1 x M12 - connector Segment OUT 1 x M12 - female connector M12 x 1 M12 x 1 Drop line 4 x M12 - female connector Segment in Segment out, Spur Earthing bolt M5 x 1 2 2 1 = V – Degree of protection IP67 2 = V + 3 1 13 Ambient temperature -25 …+ 70 °C 3 = shield Housing material powder-coated die-cast aluminium 4 4 = n.c. 4 Housing color black/yellow nominal values: 4 A, 300 V Dimensions 64 x 150 x 45 mm Connection mode Wall mounting

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 47 /0309 FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49SC-E613/3G

FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49SC-E613/3G Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Segment IN 1µF Segment OUT – 1 1 – + 2 2 + P1 S0 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S1 S2 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S3 S4 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S5 S6 S 3 3 S n.c. 4 4 n.c.

Case ground

The 6-port Ex-junction module JBBS- the board. ● Entity and FNICO compliant accor- 49SC-E613/3G is designed for FOUNDA- ding to IEC TS 60079-27 TION™ fieldbus systems. To avoid condensation build-up in the hou- ● Mounting possible in zone 2 sing, the devices are equipped with a con- ● Junction box for wall mounting with The junction box features an adjustable densate drain. stainless steel M12 flange connec- short-circuit limit. The max. current limita- tions tion is selected for all ports via a rotary The shield is capacitively coupled to the ● Powder-coated die-cast aluminium switch. The following values can be sel- housing potential. A switch for direct cou- housing ected: 30, 35, 45 and 60 mA. pling of the shield and housing is imple- mented. ● Pressure compensation element for protection against condensation The housing is made of robust die-cast alu- water minium and features protection degree Attention: Sufficient equipotential bonding IP67. of the installation must be ensured. The de- ● Connection of the housing potential via an M5 x 1 bolt vice is connected via the bolt of the hou- The junction box is equipped with a selec- sing to the system’s potentializer. ● Short-circuit protection per drop table bus terminating resistor. The accor- line/spur ding switch is integrated in the housing on ● For Ex applications: -25…+70 °C (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) ● Integrated terminating resistor (switch-in) ● Cable shielding: capacitive or direct connection to housing potential sel- ectable via switch ● Isolated support terminal for optio- nal protective conductor incorpora- ted in cable

48 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49SC-E613/3G

Type JBBS-49SC-E613/3G Dimensions Ident-No. 6611434

83 Fieldbus standard IEC 61158-2 64 36 45 Operational voltage range: 12 … 32 VDC Current self-consumption ð 7 mA Voltage drop ð 0.3 V

173,5 Short-circuit protection ð 30 , 35 , 45 , 60 mA

Indication Operational readiness 1 x green 185,5 207 Short-circuit message 6 x red

Ex approval acc. to conformity certificate PTB 07 ATEX 2017 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device

Electrical connection M12 flange connection 4 Segment IN 1 x M12 - connector Segment OUT 1 x M12 - female connector Drop line 6 x M12 - female connector Terminal Configuration Earthing bolt M5 x 1 M12 x 1 M12 x 1 Degree of protection IP67 Segment in Segment out, Spur Ambient temperature -25 …+ 70 °C 2 2 1 = V – Housing material powder-coated die-cast aluminium 2 = V + Housing color black/yellow 3 1 13 3 = shield Dimensions 64 x 185.5 x 45 mm 4 = n.c. Connection mode Wall mounting 4 4 nominal values: 4 A, 300 V

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 49 /0309 FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49SC-M413/3G

FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49SC-M413/3G Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Segment IN 1µF Segment OUT – 1 1 – + 2 2 + P1 S0 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S1 S2 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S3 S4 S 3 3 S n.c. 4 4 n.c.

Case ground

The 4-port Ex-junction module JBBS- the board. ● Entity and FNICO compliant accor- 49SC-M413/3G is designed for FOUNDA- ding to IEC TS 60079-27 TION™ fieldbus systems. To avoid condensation build-up in the hou- ● Mounting possible in zone 2 sing, the devices are equipped with a con- ● Junction box for wall mounting with The junction box features an adjustable densate drain. stainless steel 7/8" flange connec- short-circuit limit. The max. current limita- tions tion is selected for all ports via a rotary The shield is capacitively coupled to the ● Powder-coated die-cast aluminium switch. The following values can be sel- housing potential. A switch for direct cou- housing ected: 30, 35, 45 and 60 mA. pling of the shield and housing is imple- mented. ● Pressure compensation element for protection against condensation The housing is made of robust die-cast alu- water minium and features protection degree Attention: Sufficient equipotential bonding IP67. of the installation must be ensured. The de- ● Connection of the housing potential via an M5 x 1 bolt vice is connected via the bolt of the hou- The junction box is equipped with a selec- sing to the system’s potentializer. ● Short-circuit protection per drop table bus terminating resistor. The accor- line/spur ding switch is integrated in the housing on ● For Ex applications: -25…+70 °C (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) ● Integrated terminating resistor (switch-in) ● Cable shielding: capacitive or direct connection to housing potential sel- ectable via switch ● Isolated support terminal for optio- nal protective conductor incorpora- ted in cable

50 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49SC-M413/3G

Type JBBS-49SC-M413/3G Dimensions Ident-No. 6611436

96 Fieldbus standard IEC 61158-2 64 36 45 Operational voltage range: 12 … 32 VDC Current self-consumption ð 7 mA Voltage drop ð 0.3 V

Short-circuit protection ð 30 , 35 , 45 , 60 mA 138

150 Indication 172 Operational readiness 1 x green Short-circuit message 4 x red

Ex approval acc. to conformity certificate PTB 07 ATEX 2017 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device

Electrical connection 7/8" flange connection Terminal Configuration 4 Segment IN 1 x 7/8 "- plug Segment OUT 1 x 7/8 "- plug 7/8 7/8" Drop line 4 x 7/8 "- plug Segment in Segment out, Spur Earthing bolt M5 x 1 1 = V – 1 3 3 1 2 = V + Degree of protection IP67 2 4 3 = shield 4 2 Ambient temperature -25 …+ 70 °C 4 = n.c. Housing material powder-coated die-cast aluminium Housing color black/yellow nominal values: 9 A, 300 V Dimensions 64 x 150 x 45 mm Connection mode Wall mounting

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 51 /0309 FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49SC-M613/3G

FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49SC-M613/3G Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Segment IN 1µF Segment OUT – 1 1 – + 2 2 + P1 S0 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S1 S2 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S3 S4 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S5 S6 S 3 3 S n.c. 4 4 n.c.

Case ground

The 6-port Ex-junction module JBBS- the board. ● Entity and FNICO compliant accor- 49SC-M613/3G is designed for FOUNDA- ding to IEC TS 60079-27 TION™ fieldbus systems. To avoid condensation build-up in the hou- ● Mounting possible in zone 2 sing, the devices are equipped with a con- ● Junction box for wall mounting with The junction box features an adjustable densate drain. stainless steel 7/8" flange connec- short-circuit limit. The max. current limita- tions tion is selected for all ports via a rotary The shield is capacitively coupled to the ● Powder-coated die-cast aluminium switch. The following values can be sel- housing potential. A switch for direct cou- housing ected: 30, 35, 45 and 60 mA. pling of the shield and housing is imple- mented. ● Pressure compensation element for protection against condensation The housing is made of robust die-cast alu- water minium and features protection degree Attention: Sufficient equipotential bonding IP67. of the installation must be ensured. The de- ● Connection of the housing potential via an M5 x 1 bolt vice is connected via the bolt of the hou- The junction box is equipped with a selec- sing to the system’s potentializer. ● Short-circuit protection per drop table bus terminating resistor. The accor- line/spur ding switch is integrated in the housing on ● For Ex applications: -25…+70 °C (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) ● Integrated terminating resistor (switch-in) ● Cable shielding: capacitive or direct connection to housing potential sel- ectable via switch ● Isolated support terminal for optio- nal protective conductor incorpora- ted in cable

52 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49SC-M613/3G

Type JBBS-49SC-M613/3G Dimensions Ident-No. 6611438

96 Fieldbus standard IEC 61158-2 64 36 45 Operational voltage range: 12 … 32 VDC Current self-consumption ð 7 mA Voltage drop ð 0.3 V

Short-circuit protection ð 30 , 35 , 45 , 60 mA 173,5

Indication 185,5

Operational readiness 1 x green 207 Short-circuit message 6 x red

Ex approval acc. to conformity certificate PTB 07 ATEX 2017 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device

Electrical connection 7/8" flange connection 4 Segment IN 1 x 7/8 "- plug Segment OUT 1 x 7/8 "- plug Terminal Configuration Drop line 6 x 7/8 "- plug Earthing bolt M5 x 1 7/8 7/8" Segment in Segment out, Spur Degree of protection IP67 Ambient temperature -25 …+ 70 °C 1 = V – 1 3 3 1 Housing material powder-coated die-cast aluminium 2 = V + Housing color black/yellow 2 4 3 = shield 4 2 Dimensions 64 x 185.5 x 45 mm 4 = n.c. Connection mode Wall mounting nominal values: 9 A, 300 V

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 53 /0309 FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49SC-T415B/EX

FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49SC-T415B/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Segment IN 1µF Segment OUT n.c. 1 1 n.c. S 2 2 S P1 S0 + 3 3 + – 4 4 –

n.c. 1 1 n.c. S 2 2 S S1 S2 + 3 3 + – 4 4 –

n.c. 1 1 n.c. S 2 2 S S3 S4 + 3 3 + – 4 4 –

Case ground

The 4-port Ex-junction module JBBS- the board. ● Entity and FISCO compliant accor- 49SC-T415B/EX is designed for FOUNDA- ding to IEC TS 60079-27 TION™ fieldbus systems. To avoid condensation build-up in the hou- ● Junction box for wall mounting with sing, the devices are equipped with a con- PVC cable glands M20 x 1.5 The junction box features an adjustable densate drain. ● Powder-coated die-cast aluminium short-circuit limit. The max. current limita- housing tion is selected for all ports via a rotary The shield is capacitively coupled to the ● Pressure compensation element for switch. The following values can be sel- housing potential. A switch for direct cou- protection against condensation ected: 30, 35, 45 and 60 mA. pling of the shield and housing is imple- water mented. ● Connection of the housing potential The housing is made of robust die-cast alu- via an M5 x 1 bolt minium and features protection degree Attention: Sufficient equipotential bonding IP67. of the installation must be ensured. The de- ● Short-circuit protection per drop line/spur vice is connected via the bolt of the hou- The junction box is equipped with a selec- sing to the system’s potentializer. ● For Ex applications: -25…+70 °C table bus terminating resistor. The accor- (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) ding switch is integrated in the housing on ● Integrated terminating resistor (switch-in) ● Cable shielding: capacitive or direct connection to housing potential sel- ectable via switch ● Isolated support terminal for optio- nal protective conductor incorpora- ted in cable

54 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49SC-T415B/EX

Type JBBS-49SC-T415B/EX Dimensions Ident-No. 6611441

122 Fieldbus standard IEC 61158-2 64 36 45 Operational voltage range: 12 … 32 VDC Current self-consumption ð 7 mA Voltage drop ð 0.3 V

138 Short-circuit protection ð 30 , 35 , 45 , 60 mA 150 Indication 172 Operational readiness 1 x green Short-circuit message 4 x red

Ex approval acc. to conformity certificate PTB 03 ATEX 2236 Entity Parameter ð Max.output voltage Uo 24 V ð Max. output current Io 250 mA ð Max. output power Po 2560 mW Terminal Configuration ð 4 Max. input voltage Ui 24 V ð Max. input current Ii 250 mA ð Max. input power Pi 2560 mW 1 = n.c. FISCO parameter according to IEC TS 60079-27 2 = shield 3 = + 1234 4 = – ð Max.output voltage Uo 17.5 V ð Max. output current Io 380 mA ð Max. output power Po 5320 mW ð Max. input voltage Ui 17.5 V ð Max. input current Ii 380 mA ð Max. input power Pi 5320 mW External inductance/capacitance Li/Ci trunk (in/out): negligible / ð 5.00 nF per field current circuit: negligible / ð 0.47 nF æ field current circuits: negligible / ð 5.00 nF Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) [Ex ibD] EEx ib IIB T4 É II 2 (1) G (1D) [Ex iaD] EEx ia IIB T4 FISCO / Entity field device

Electrical connection cable glands Segment IN 1 x M20 x 1.5 (Ø 6…12 mm) Segment OUT 1 x M20 x 1.5 (Ø 6…12 mm) Drop line 4 x M20 x 1.5 (Ø 6…12 mm) Terminal cross-section 2.5 mm2 Earthing bolt M5 x 1

Degree of protection IP67 Ambient temperature -25 …+ 70 °C Housing material powder-coated die-cast aluminium Housing color black/yellow Dimensions 64 x 150 x 45 mm Connection mode Wall mounting

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 55 /0309 FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49SC-T615B/EX

FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49SC-T615B/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Trunk In 1µF Trunk Out n.c. 1 1 n.c. S 2 2 S P1 S0 + 3 3 + – 4 4 –

n.c. 1 1 n.c. S 2 2 S S1 S2 + 3 3 + – 4 4 –

n.c. 1 1 n.c. S 2 2 S S3 S4 + 3 3 + – 4 4 –

n.c. 1 1 n.c. S 2 2 S S5 S6 + 3 3 + – 4 4 –

case ground

The 6-port Ex-junction module JBBS- the board. ● Entity and FISCO compliant accor- 49SC-T615B/EX is designed for FOUNDA- ding to IEC TS 60079-27 TION™ fieldbus systems. To avoid condensation build-up in the hou- ● Junction box for wall mounting with sing, the devices are equipped with a con- PVC cable glands M20 x 1.5 The junction box features an adjustable densate drain. ● Powder-coated die-cast aluminium short-circuit limit. The max. current limita- housing tion is selected for all ports via a rotary The shield is capacitively coupled to the ● Pressure compensation element for switch. The following values can be sel- housing potential. A switch for direct cou- protection against condensation ected: 30, 35, 45 and 60 mA. pling of the shield and housing is imple- water mented. ● Connection of the housing potential The housing is made of robust die-cast alu- via an M5 x 1 bolt minium and features protection degree Attention: Sufficient equipotential bonding IP67. of the installation must be ensured. The de- ● Short-circuit protection per drop line/spur vice is connected via the bolt of the hou- The junction box is equipped with a selec- sing to the system’s potentializer. ● For Ex applications: -25…+70 °C table bus terminating resistor. The accor- (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) ding switch is integrated in the housing on ● Integrated terminating resistor (switch-in) ● Cable shielding: capacitive or direct connection to housing potential sel- ectable via switch ● Isolated support terminal for optio- nal protective conductor incorpora- ted in cable

56 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49SC-T615B/EX

Type JBBS-49SC-T615B/EX Dimensions Ident-No. 6611443

122 Fieldbus standard IEC 61158-2 64,0 36,0 45,0 Operational voltage range: 12 … 32 VDC Current self-consumption ð 7 mA Voltage drop ð 0.3 V 173,5 Short-circuit protection ð 30 , 35 , 45 , 60 mA

Indication 185,5 Operational readiness 1 x green 207 Short-circuit message 6 x red

Ex approval acc. to conformity certificate PTB 03 ATEX 2236 Entity Parameter ð Max.output voltage Uo 24 V ð Max. output current Io 250 mA ð Max. output power Po 2560 mW ð 4 Max. input voltage Ui 24 V Max. input current I ð 250 mA i Terminal Configuration ð Max. input power Pi 2560 mW FISCO parameter according to IEC TS 60079-27

ð 1 = n.c. Max.output voltage Uo 17.5 V 2 = shield ð 3 = + Max. output current Io 380 mA ð 1234 4 = – Max. output power Po 5320 mW ð Max. input voltage Ui 17.5 V ð Max. input current Ii 380 mA ð Max. input power Pi 5320 mW External inductance/capacitance Li/Ci trunk (in/out): negligible / ð 5.00 nF per field current circuit: negligible / ð 0.47 nF æ field current circuits: negligible / ð 5.00 nF Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) [Ex ibD] EEx ib IIB T4 É II 2 (1) G (1D) [Ex iaD] EEx ia IIB T4 FISCO / Entity field device

Electrical connection cable glands Segment IN 1 x M20 x 1.5 (Ø 6…12 mm) Segment OUT 1 x M20 x 1.5 (Ø 6…12 mm) Drop line 6 x M20 x 1.5 (Ø 6…12 mm) Terminal cross-section 2.5 mm2 Earthing bolt M5 x 1

Degree of protection IP67 Ambient temperature -25 …+ 70 °C Housing material powder-coated die-cast aluminium Housing color black/yellow Dimensions 64 x 185.5 x 45 mm Connection mode Wall mounting

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 57 /0309 FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49SC-E413/EX

FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49SC-E413/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Segment IN 1µF Segment OUT – 1 1 – + 2 2 + P1 S0 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S1 S2 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S3 S4 S 3 3 S n.c. 4 4 n.c.

Case ground

The 4-port Ex-junction module JBBS- the board. ● Entity and FISCO compliant accor- 49SC-E413/EX is designed for FOUNDA- ding to IEC TS 60079-27 TION™ fieldbus systems. To avoid condensation build-up in the hou- ● Junction box for wall mounting with sing, the devices are equipped with a con- stainless steel M12 flange connec- The junction box features an adjustable densate drain. tions short-circuit limit. The max. current limita- ● Powder-coated die-cast aluminium tion is selected for all ports via a rotary The shield is capacitively coupled to the housing switch. The following values can be sel- housing potential. A switch for direct cou- ● Pressure compensation element for ected: 30, 35, 45 and 60 mA. pling of the shield and housing is imple- protection against condensation mented. water The housing is made of robust die-cast alu- ● Connection of the housing potential minium and features protection degree Attention: Sufficient equipotential bonding via an M5 x 1 bolt IP67. of the installation must be ensured. The de- ● Short-circuit protection per drop vice is connected via the bolt of the hou- line/spur The junction box is equipped with a selec- sing to the system’s potentializer. table bus terminating resistor. The accor- ● For Ex applications: -25…+70 °C (-13…+158 °F); for non-Ex applicati- ding switch is integrated in the housing on ons: -40…+70 °C (-40…+158 °F) ● Integrated terminating resistor (switch-in) ● Cable shielding: capacitive or direct connection to housing potential sel- ectable via switch ● Isolated support terminal for optio- nal protective conductor incorpora- ted in cable

58 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49SC-E413/EX

Type JBBS-49SC-E413/EX Dimensions Ident-No. 6611433

83 Fieldbus standard IEC 61158-2 64 36 45 Operational voltage range: 12 … 32 VDC Current self-consumption ð 7 mA Voltage drop ð 0.3 V

Short-circuit protection ð 30 , 35 , 45 , 60 mA 138

Indication 150 Operational readiness 1 x green 172 Short-circuit message 4 x red

Ex approval acc. to conformity certificate PTB 03 ATEX 2236 Entity Parameter ð Max.output voltage Uo 24 V ð Max. output current Io 250 mA ð Max. output power Po 2560 mW ð 4 Max. input voltage Ui 24 V Terminal Configuration ð Max. input current Ii 250 mA ð Max. input power Pi 2560 mW M12 x 1 M12 x 1 FISCO parameter according to IEC TS 60079-27 Segment in Segment out, Spur 2 2 ð 1 = V – Max.output voltage Uo 17.5 V ð 2 = V + Max. output current Io 380 mA 3 1 13 ð 3 = shield Max. output power Po 5320 mW ð 4 = n.c. Max. input voltage Ui 17.5 V 4 4 ð Max. input current Ii 380 mA nominal values: 4 A, 300 V ð Max. input power Pi 5320 mW External inductance/capacitance Li/Ci trunk (in/out): negligible / ð 5.00 nF per field current circuit: negligible / ð 0.47 nF æ field current circuits: negligible / ð 5.00 nF Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) [Ex ibD] EEx ib IIB T4 É II 2 (1) G (1D) [Ex iaD] EEx ia IIB T4 FISCO / Entity field device

Electrical connection M12 flange connection Segment IN 1 x M12 - connector Segment OUT 1 x M12 - female connector Drop line 4 x M12 - female connector Earthing bolt M5 x 1

Degree of protection IP67 Ambient temperature -25 …+ 70 °C Housing material powder-coated die-cast aluminium Housing color black/yellow Dimensions 64 x 150 x 45 mm Connection mode Wall mounting

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 59 /0309 FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49SC-E613/EX

FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49SC-E613/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Segment IN 1µF Segment OUT – 1 1 – + 2 2 + P1 S0 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S1 S2 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S3 S4 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S5 S6 S 3 3 S n.c. 4 4 n.c.

Case ground

The 6-port Ex-junction module JBBS- the board. ● Entity and FISCO compliant accor- 49SC-E613/EX is designed for FOUNDA- ding to IEC TS 60079-27 TION™ fieldbus systems. To avoid condensation build-up in the hou- ● Junction box for wall mounting with sing, the devices are equipped with a con- stainless steel M12 flange connec- The junction box features an adjustable densate drain. tions short-circuit limit. The max. current limita- ● Powder-coated die-cast aluminium tion is selected for all ports via a rotary The shield is capacitively coupled to the housing switch. The following values can be sel- housing potential. A switch for direct cou- ● Pressure compensation element for ected: 30, 35, 45 and 60 mA. pling of the shield and housing is imple- protection against condensation mented. water The housing is made of robust die-cast alu- ● Connection of the housing potential minium and features protection degree Attention: Sufficient equipotential bonding via an M5 x 1 bolt IP67. of the installation must be ensured. The de- ● Short-circuit protection per drop vice is connected via the bolt of the hou- line/spur The junction box is equipped with a selec- sing to the system’s potentializer. table bus terminating resistor. The accor- ● For Ex applications: -25…+70 °C (-13…+158 °F); for non-Ex applicati- ding switch is integrated in the housing on ons: -40…+70 °C (-40…+158 °F) ● Integrated terminating resistor (switch-in) ● Cable shielding: capacitive or direct connection to housing potential sel- ectable via switch ● Isolated support terminal for optio- nal protective conductor incorpora- ted in cable

60 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49SC-E613/EX

Type JBBS-49SC-E613/EX Dimensions Ident-No. 6611435

83 Fieldbus standard IEC 61158-2 64 36 45 Operational voltage range: 12 … 32 VDC Current self-consumption ð 7 mA Voltage drop ð 0.3 V

173,5 Short-circuit protection ð 30 , 35 , 45 , 60 mA

Indication Operational readiness 1 x green 185,5 207 Short-circuit message 6 x red

Ex approval acc. to conformity certificate PTB 03 ATEX 2236 Entity Parameter ð Max.output voltage Uo 24 V ð Max. output current Io 250 mA ð Max. output power Po 2560 mW ð 4 Max. input voltage Ui 24 V ð Max. input current Ii 250 mA ð Max. input power Pi 2560 mW FISCO parameter according to IEC TS 60079-27 Terminal Configuration

ð M12 x 1 M12 x 1 Max.output voltage Uo 17.5 V ð Segment in Segment out, Spur Max. output current Io 380 mA ð 2 Max. output power Po 5320 mW 2 1 = V – ð Max. input voltage Ui 17.5 V 2 = V + ð 3 1 13 Max. input current Ii 380 mA 3 = shield ð Max. input power Pi 5320 mW 4 4 = n.c. 4 External inductance/capacitance Li/Ci trunk (in/out): negligible / ð 5.00 nF nominal values: 4 A, 300 V per field current circuit: negligible / ð 0.47 nF æ field current circuits: negligible / ð 5.00 nF Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) [Ex ibD] EEx ib IIB T4 É II 2 (1) G (1D) [Ex iaD] EEx ia IIB T4 FISCO / Entity field device

Electrical connection M12 flange connection Segment IN 1 x M12 - connector Segment OUT 1 x M12 - female connector Drop line 6 x M12 - female connector Earthing bolt M5 x 1

Degree of protection IP67 Ambient temperature -25 …+ 70 °C Housing material powder-coated die-cast aluminium Housing color black/yellow Dimensions 64 x 185.5 x 45 mm Connection mode Wall mounting

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 61 /0309 FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49SC-M413/EX

FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49SC-M413/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Segment IN 1µF Segment OUT – 1 1 – + 2 2 + P1 S0 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S1 S2 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S3 S4 S 3 3 S n.c. 4 4 n.c.

Case ground

The 4-port Ex-junction module JBBS- the board. ● Entity and FISCO compliant accor- 49SC-M413/EX is designed for FOUNDA- ding to IEC TS 60079-27 TION™ fieldbus systems. To avoid condensation build-up in the hou- ● Junction box for wall mounting with sing, the devices are equipped with a con- stainless steel 7/8" flange connec- The junction box features an adjustable densate drain. tions short-circuit limit. The max. current limita- ● Powder-coated die-cast aluminium tion is selected for all ports via a rotary The shield is capacitively coupled to the housing switch. The following values can be sel- housing potential. A switch for direct cou- ● Pressure compensation element for ected: 30, 35, 45 and 60 mA. pling of the shield and housing is imple- protection against condensation mented. water The housing is made of robust die-cast alu- ● Connection of the housing potential minium and features protection degree Attention: Sufficient equipotential bonding via an M5 x 1 bolt IP67. of the installation must be ensured. The de- ● Short-circuit protection per drop vice is connected via the bolt of the hou- line/spur The junction box is equipped with a selec- sing to the system’s potentializer. table bus terminating resistor. The accor- ● For Ex applications: -25…+70 °C (-13…+158 °F); for non-Ex applicati- ding switch is integrated in the housing on ons: -40…+70 °C (-40…+158 °F) ● Integrated terminating resistor (switch-in) ● Cable shielding: capacitive or direct connection to housing potential sel- ectable via switch ● Isolated support terminal for optio- nal protective conductor incorpora- ted in cable

62 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49SC-M413/EX

Type JBBS-49SC-M413/EX Dimensions Ident-No. 6611437

96 Fieldbus standard IEC 61158-2 64 36 45 Operational voltage range: 12 … 32 VDC Current self-consumption ð 7 mA Voltage drop ð 0.3 V

Short-circuit protection ð 30 , 35 , 45 , 60 mA 138

150 Indication 172 Operational readiness 1 x green Short-circuit message 4 x red

Ex approval acc. to conformity certificate PTB 03 ATEX 2236 Entity Parameter ð Max.output voltage Uo 24 V ð Max. output current Io 250 mA ð Max. output power Po 2560 mW ð Terminal Configuration 4 Max. input voltage Ui 24 V ð Max. input current Ii 250 mA 7/8 7/8" Max. input power P ð 2560 mW i Segment in Segment out, Spur FISCO parameter according to IEC TS 60079-27 1 = V – ð 1 3 3 1 Max.output voltage Uo 17.5 V 2 = V + ð Max. output current Io 380 mA 2 4 3 = shield 4 2 ð Max. output power Po 5320 mW 4 = n.c. Max. input voltage U ð 17.5 V i nominal values: 9 A, 300 V ð Max. input current Ii 380 mA ð Max. input power Pi 5320 mW External inductance/capacitance Li/Ci trunk (in/out): negligible / ð 5.00 nF per field current circuit: negligible / ð 0.47 nF æ field current circuits: negligible / ð 5.00 nF Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) [Ex ibD] EEx ib IIB T4 É II 2 (1) G (1D) [Ex iaD] EEx ia IIB T4 FISCO / Entity field device

Electrical connection 7/8" flange connection Segment IN 1 x 7/8 "- plug Segment OUT 1 x 7/8 "- plug Drop line 4 x 7/8 "- plug Earthing bolt M5 x 1

Degree of protection IP67 Ambient temperature -25 …+ 70 °C Housing material powder-coated die-cast aluminium Housing color black/yellow Dimensions 64 x 150 x 45 mm Connection mode Wall mounting

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 63 /0309 FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49SC-M613/EX

FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49SC-M613/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Segment IN 1µF Segment OUT – 1 1 – + 2 2 + P1 S0 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S1 S2 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S3 S4 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S5 S6 S 3 3 S n.c. 4 4 n.c.

Case ground

The 6-port Ex-junction module JBBS- the board. ● Entity and FISCO compliant accor- 49SC-M613/EX is designed for FOUNDA- ding to IEC TS 60079-27 TION™ fieldbus systems. To avoid condensation build-up in the hou- ● Junction box for wall mounting with sing, the devices are equipped with a con- stainless steel 7/8" flange connec- The junction box features an adjustable densate drain. tions short-circuit limit. The max. current limita- ● Powder-coated die-cast aluminium tion is selected for all ports via a rotary The shield is capacitively coupled to the housing switch. The following values can be sel- housing potential. A switch for direct cou- ● Pressure compensation element for ected: 30, 35, 45 and 60 mA. pling of the shield and housing is imple- protection against condensation mented. water The housing is made of robust die-cast alu- ● Connection of the housing potential minium and features protection degree Attention: Sufficient equipotential bonding via an M5 x 1 bolt IP67. of the installation must be ensured. The de- ● Short-circuit protection per drop vice is connected via the bolt of the hou- line/spur The junction box is equipped with a selec- sing to the system’s potentializer. table bus terminating resistor. The accor- ● For Ex applications: -25…+70 °C (-13…+158 °F); for non-Ex applicati- ding switch is integrated in the housing on ons: -40…+70 °C (-40…+158 °F) ● Integrated terminating resistor (switch-in) ● Cable shielding: capacitive or direct connection to housing potential sel- ectable via switch ● Isolated support terminal for optio- nal protective conductor incorpora- ted in cable

64 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49SC-M613/EX

Type JBBS-49SC-M613/EX Dimensions Ident-No. 6611439

96 Fieldbus standard IEC 61158-2 64 36 45 Operational voltage range: 12 … 32 VDC Current self-consumption ð 7 mA Voltage drop ð 0.3 V

Short-circuit protection ð 30 , 35 , 45 , 60 mA 173,5

Indication 185,5

Operational readiness 1 x green 207 Short-circuit message 6 x red

Ex approval acc. to conformity certificate PTB 03 ATEX 2236 Entity Parameter ð Max.output voltage Uo 24 V ð Max. output current Io 250 mA ð Max. output power Po 2560 mW ð 4 Max. input voltage Ui 24 V ð Max. input current Ii 250 mA ð Max. input power Pi 2560 mW Terminal Configuration FISCO parameter according to IEC TS 60079-27 7/8 7/8" ð Max.output voltage Uo 17.5 V Segment in Segment out, Spur ð Max. output current Io 380 mA ð 1 = V – Max. output power Po 5320 mW 1 3 3 1 ð 2 = V + Max. input voltage Ui 17.5 V ð 2 4 3 = shield 4 2 Max. input current Ii 380 mA ð 4 = n.c. Max. input power Pi 5320 mW External inductance/capacitance Li/Ci trunk (in/out): nominal values: 9 A, 300 V negligible / ð 5.00 nF per field current circuit: negligible / ð 0.47 nF æ field current circuits: negligible / ð 5.00 nF Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) [Ex ibD] EEx ib IIB T4 É II 2 (1) G (1D) [Ex iaD] EEx ia IIB T4 FISCO / Entity field device

Electrical connection 7/8" flange connection Segment IN 1 x 7/8 "- plug Segment OUT 1 x 7/8 "- plug Drop line 6 x 7/8 "- plug Earthing bolt M5 x 1

Degree of protection IP67 Ambient temperature -25 …+ 70 °C Housing material powder-coated die-cast aluminium Housing color black/yellow Dimensions 64 x 185.5 x 45 mm Connection mode Wall mounting

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 65 /0309 FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49-T415/3G

FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49-T415/3G Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Segment IN 1µF Segment OUT n.c. 1 1 n.c. S 2 2 S P1 S0 + 3 3 + – 4 4 –

n.c. 1 1 n.c. S 2 2 S S1 S2 + 3 3 + – 4 4 –

n.c. 1 1 n.c. S 2 2 S S3 S4 + 3 3 + – 4 4 –

case ground

The 4-port Ex-junction module JBBS-49- To avoid condensation build-up in the hou- ● Entity and FNICO compliant accor- T415/3G is designed for FOUNDATION™ sing, the devices are equipped with a con- ding to IEC TS 60079-27 fieldbus systems. densate drain. ● Mounting possible in zone 2 ● Junction box for wall mounting with The housing is made of robust die-cast alu- The shield is capacitively coupled to the PVC cable glands M20 x 1.5 minium and features protection degree housing potential. A switch for direct cou- IP67. pling of the shield and housing is imple- ● Powder-coated die-cast aluminium housing mented. The junction box is equipped with a selec- ● Pressure compensation element for table bus terminating resistor. The accor- Attention: Sufficient equipotential bonding protection against condensation water ding switch is integrated in the housing on of the installation must be ensured. The de- the board. vice is connected via the bolt of the hou- ● Connection of the housing potential sing to the system’s potentializer. via an M5 x 1 bolt ● For Ex applications: -25…+70 °C (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) ● Integrated terminating resistor (switch-in) ● Cable shielding: capacitive or direct connection to housing potential sel- ectable via switch ● Isolated support terminal for optio- nal protective conductor incorpora- ted in cable

66 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49-T415/3G

Type JBBS-49-T415/3G Dimensions Ident-No. 6611444

122 Fieldbus standard IEC 61158-2 64 36 45 Operational voltage range: 9 … 32 VDC

Ex approval acc. to conformity certificate PTB 07 ATEX 2017 X Device designation É II 3 G Ex nA II T4 138 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device 150

172 Electrical connection cable glands Segment IN 1 x M20 x 1.5 (Ø 6…12 mm) Segment OUT 1 x M20 x 1.5 (Ø 6…12 mm) Drop line 4 x M20 x 1.5 (Ø 6…12 mm) Terminal cross-section 2.5 mm2 Earthing bolt M5 x 1

Degree of protection IP67 Terminal Configuration Ambient temperature -25 …+ 70 °C 4 Housing material powder-coated die-cast aluminium

Housing color black/yellow 1 = n.c. Dimensions 64 x 150 x 45 mm 2 = shield 3 = + Connection mode Wall mounting 1234 4 = –

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 67 /0309 FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49-T615/3G

FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49-T615/3G Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Trunk In 1µF Trunk Out n.c. 1 1 n.c. S 2 2 S P1 S0 + 3 3 + – 4 4 –

n.c. 1 1 n.c. S 2 2 S S1 S2 + 3 3 + – 4 4 –

n.c. 1 1 n.c. S 2 2 S S3 S4 + 3 3 + – 4 4 –

n.c. 1 1 n.c. S 2 2 S S5 S6 + 3 3 + – 4 4 –

case ground

The 6-port Ex-junction module JBBS-49- To avoid condensation build-up in the hou- ● Entity and FNICO compliant accor- T615/3G is designed for FOUNDATION™ sing, the devices are equipped with a con- ding to IEC TS 6007927 fieldbus systems. densate drain. ● Mounting possible in zone 2 ● Junction module for wall mounting The housing is made of robust die-cast alu- The shield is capacitively coupled to the with PVC cable glands M20 x 1.5 minium and features protection degree housing potential. A switch for direct cou- IP67. pling of the shield and housing is imple- ● Powder-coated die-cast aluminium housing mented. The junction box is equipped with a selec- ● Pressure compensation element for table bus terminating resistor. The accor- Attention: Sufficient equipotential bonding protection against condensation water ding switch is integrated in the housing on of the installation must be ensured. The de- the board. vice is connected via the bolt of the hou- ● Connection of the housing potential sing to the system’s potentializer. via an M5 x 1 bolt ● For Ex applications: -25…+70 °C (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) ● Integrated terminating resistor (switch-in) ● Cable shielding: capacitive or direct connection to housing potential sel- ectable via switch ● Isolated support terminal for optio- nal protective conductor incorpora- ted in cable

68 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49-T615/3G

Type JBBS-49-T615/3G Dimensions Ident-No. 6611446

122 Fieldbus standard IEC 61158-2 64,0 36,0 45,0 Operational voltage range: 9 … 32 VDC

Ex approval acc. to conformity certificate PTB 07 ATEX 2017 X Device designation É II 3 G Ex nA II T4 173,5 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device 185,5 Electrical connection cable glands 207 Segment IN 1 x M20 x 1.5 (Ø 6…12 mm) Segment OUT 1 x M20 x 1.5 (Ø 6…12 mm) Drop line 6 x M20 x 1.5 (Ø 6…12 mm) Terminal cross-section 2.5 mm2 Earthing bolt M5 x 1

Degree of protection IP67 Ambient temperature -25 …+ 70 °C 4 Housing material powder-coated die-cast aluminium Terminal Configuration Housing color black/yellow Dimensions 64 x 185.5 x 45 mm Connection mode Wall mounting 1 = n.c. 2 = shield 3 = + 1234 4 = –

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 69 /0309 FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49-E413/3G

FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49-E413/3G Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Segment IN 1µF Segment OUT – 1 1 – + 2 2 + P1 S0 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S1 S2 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S4 S3 S 3 3 S n.c. 4 4 n.c.

Case ground

The 4-port Ex-junction module JBBS-49- To avoid condensation build-up in the hou- ● Entity and FNICO compliant accor- E413/3G is designed for FOUNDATION™ sing, the devices are equipped with a con- ding to IEC TS 60079-27 fieldbus systems. densate drain. ● Mounting possible in zone 2 ● Junction box for wall mounting with The housing is made of robust die-cast alu- The shield is capacitively coupled to the stainless steel M12 flange connec- minium and features protection degree housing potential. A switch for direct cou- tions IP67. pling of the shield and housing is imple- ● Powder-coated die-cast aluminium mented. housing The junction box is equipped with a selec- table bus terminating resistor. The accor- Attention: Sufficient equipotential bonding ● Pressure compensation element for protection against condensation ding switch is integrated in the housing on of the installation must be ensured. The de- water the board. vice is connected via the bolt of the hou- sing to the system’s potentializer. ● Connection of the housing potential via an M5 x 1 bolt ● For Ex applications: -25…+70 °C (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) ● Integrated terminating resistor (switch-in) ● Cable shielding: capacitive or direct connection to housing potential sel- ectable via switch ● Isolated support terminal for optio- nal protective conductor incorpora- ted in cable

70 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49-E413/3G

Type JBBS-49-E413/3G Dimensions Ident-No. 6611424

83 Fieldbus standard IEC 61158-2 64 36 45 Operational voltage range: 9 … 32 VDC

Ex approval acc. to conformity certificate PTB 07 ATEX 2017 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 138 FNICO / Entity field device 150 Electrical connection M12 flange connection 172 Segment IN 1 x M12 - connector Segment OUT 1 x M12 - female connector Drop line 4 x M12 - female connector Earthing bolt M5 x 1

Degree of protection IP67 Ambient temperature -25 …+ 70 °C 4 Housing material powder-coated die-cast aluminium Terminal Configuration Housing color black/yellow Dimensions 64 x 150 x 45 mm M12 x 1 M12 x 1 Connection mode Wall mounting Segment in Segment out, Spur 2 2 1 = V – 2 = V + 3 1 13 3 = shield 4 4 = n.c. 4 nominal values: 4 A, 300 V

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 71 /0309 FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49-E613/3G

FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49-E613/3G Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Segment IN 1µF Segment OUT – 1 1 – + 2 2 + P1 S0 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S1 S2 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S3 S4 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S5 S6 S 3 3 S n.c. 4 4 n.c.

Case ground

The 6-port Ex-junction module JBBS-49- To avoid condensation build-up in the hou- ● Entity and FNICO compliant accor- E613/3G is designed for FOUNDATION™ sing, the devices are equipped with a con- ding to IEC TS 6007927 fieldbus systems. densate drain. ● Mounting possible in zone 2 ● Junction box for wall mounting with The housing is made of robust die-cast alu- The shield is capacitively coupled to the stainless steel M12 flange connec- minium and features protection degree housing potential. A switch for direct cou- tions IP67. pling of the shield and housing is imple- ● Powder-coated die-cast aluminium mented. housing The junction box is equipped with a selec- table bus terminating resistor. The accor- Attention: Sufficient equipotential bonding ● Pressure compensation element for protection against condensation ding switch is integrated in the housing on of the installation must be ensured. The de- water the board. vice is connected via the bolt of the hou- sing to the system’s potentializer. ● Connection of the housing potential via an M5 x 1 bolt ● For Ex applications: -25…+70 °C (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) ● Integrated terminating resistor (switch-in) ● Cable shielding: capacitive or direct connection to housing potential sel- ectable via switch ● Isolated support terminal for optio- nal protective conductor incorpora- ted in cable

72 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49-E613/3G

Type JBBS-49-E613/3G Dimensions Ident-No. 6611426

83 Fieldbus standard IEC 61158-2 64 36 45 Operational voltage range: 9 … 32 VDC

Ex approval acc. to conformity certificate PTB 07 ATEX 2017 X Device designation É II 3 G Ex nA II T4 173,5 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device

Electrical connection M12 flange connection 185,5 207 Segment IN 1 x M12 - connector Segment OUT 1 x M12 - female connector Drop line 6 x M12 - female connector Earthing bolt M5 x 1

Degree of protection IP67 Ambient temperature -25 …+ 70 °C Housing material powder-coated die-cast aluminium 4 Housing color black/yellow Dimensions 64 x 185.5 x 45 mm Connection mode Wall mounting Terminal Configuration

M12 x 1 M12 x 1 Segment in Segment out, Spur 2 2 1 = V – 2 = V + 3 1 13 3 = shield 4 4 = n.c. 4 nominal values: 4 A, 300 V

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 73 /0309 FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49-M413/3G

FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49-M413/3G Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Segment IN 1µF Segment OUT – 1 1 – + 2 2 + P1 S0 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S1 S2 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S4 S3 S 3 3 S n.c. 4 4 n.c.

Case ground

The 4-port Ex-junction module JBBS-49- To avoid condensation build-up in the hou- ● Entity and FNICO compliant accor- M413/3G is designed for FOUNDATION™ sing, the devices are equipped with a con- ding to IEC TS 6007927 fieldbus systems. densate drain. ● Mounting possible in zone 2 ● Junction box for wall mounting with The housing is made of robust die-cast alu- The shield is capacitively coupled to the stainless steel 7/8" flange connec- minium and features protection degree housing potential. A switch for direct cou- tions IP67. pling of the shield and housing is imple- ● Powder-coated die-cast aluminium mented. housing The junction box is equipped with a selec- table bus terminating resistor. The accor- Attention: Sufficient equipotential bonding ● Pressure compensation element for protection against condensation ding switch is integrated in the housing on of the installation must be ensured. The de- water the board. vice is connected via the bolt of the hou- sing to the system’s potentializer. ● Connection of the housing potential via an M5 x 1 bolt ● For Ex applications: -25…+70 °C (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) ● Integrated terminating resistor (switch-in) ● Cable shielding: capacitive or direct connection to housing potential sel- ectable via switch ● Isolated support terminal for optio- nal protective conductor incorpora- ted in cable

74 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49-M413/3G

Type JBBS-49-M413/3G Dimensions Ident-No. 6611428

96 Fieldbus standard IEC 61158-2 64 36 45 Operational voltage range: 9 … 32 VDC

Ex approval acc. to conformity certificate PTB 07 ATEX 2017 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 138

FNICO / Entity field device 150

172 Electrical connection 7/8" flange connection Segment IN 1 x 7/8 "- plug Segment OUT 1 x 7/8 "- plug Drop line 4 x 7/8 "- plug Earthing bolt M5 x 1

Degree of protection IP67 Ambient temperature -25 …+ 70 °C Housing material powder-coated die-cast aluminium Terminal Configuration 4 Housing color black/yellow 7/8 7/8" Dimensions 64 x 150 x 45 mm Segment in Segment out, Spur Connection mode Wall mounting 1 = V – 1 3 3 1 2 = V + 2 4 3 = shield 4 2 4 = n.c. nominal values: 9 A, 300 V

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 75 /0309 FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49-M613/3G

FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49-M613/3G Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Segment IN 1µF Segment OUT – 1 1 – + 2 2 + P1 S0 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S1 S2 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S3 S4 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S5 S6 S 3 3 S n.c. 4 4 n.c.

Case ground

The 6-port Ex-junction module JBBS-49- To avoid condensation build-up in the hou- ● Entity and FNICO compliant accor- M613/3G is designed for FOUNDATION™ sing, the devices are equipped with a con- ding to IEC TS 60079-27 fieldbus systems. densate drain. ● Mounting possible in zone 2 ● Junction box for wall mounting with The housing is made of robust die-cast alu- The shield is capacitively coupled to the stainless steel 7/8" flange connec- minium and features protection degree housing potential. A switch for direct cou- tions IP67. pling of the shield and housing is imple- ● Powder-coated die-cast aluminium mented. housing The junction box is equipped with a selec- table bus terminating resistor. The accor- Attention: Sufficient equipotential bonding ● Pressure compensation element for protection against condensation ding switch is integrated in the housing on of the installation must be ensured. The de- water the board. vice is connected via the bolt of the hou- sing to the system’s potentializer. ● Connection of the housing potential via an M5 x 1 bolt ● For Ex applications: -25…+70 °C (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) ● Integrated terminating resistor (switch-in) ● Cable shielding: capacitive or direct connection to housing potential sel- ectable via switch ● Isolated support terminal for optio- nal protective conductor incorpora- ted in cable

76 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49-M613/3G

Type JBBS-49-M613/3G Dimensions Ident-No. 6611430

96 Fieldbus standard IEC 61158-2 64 36 45 Operational voltage range: 9 … 32 VDC

Ex approval acc. to conformity certificate PTB 07 ATEX 2017 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device 173,5 185,5

Electrical connection 7/8" flange connection 207 Segment IN 1 x 7/8 "- plug Segment OUT 1 x 7/8 "- plug Drop line 6 x 7/8 "- plug Earthing bolt M5 x 1

Degree of protection IP67 Ambient temperature -25 …+ 70 °C Housing material powder-coated die-cast aluminium 4 Housing color black/yellow Dimensions 64 x 185.5 x 45 mm Terminal Configuration Connection mode Wall mounting 7/8 7/8" Segment in Segment out, Spur

1 = V – 1 3 3 1 2 = V + 2 4 3 = shield 4 2 4 = n.c. nominal values: 9 A, 300 V

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 77 /0309 FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49-T415B/EX

FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49-T415B/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Segment IN 1µF Segment OUT n.c. 1 1 n.c. S 2 2 S P1 S0 + 3 3 + – 4 4 –

n.c. 1 1 n.c. S 2 2 S S1 S2 + 3 3 + – 4 4 –

n.c. 1 1 n.c. S 2 2 S S3 S4 + 3 3 + – 4 4 –

case ground

The 4-port Ex-junction module JBBS-49- To avoid condensation build-up in the hou- ● Entity and FISCO compliant accor- E413/EX is designed for FOUNDATION™ sing, the devices are equipped with a con- ding to IEC TS 60079-27 fieldbus systems. densate drain. ● Junction box for wall mounting with PVC cable glands M20 x 1.5 The housing is made of robust die-cast alu- The shield is capacitively coupled to the ● Powder-coated die-cast aluminium minium and features protection degree housing potential. A switch for direct cou- housing IP67. pling of the shield and housing is imple- ● Pressure compensation element for mented. protection against condensation The junction box is equipped with a selec- water table bus terminating resistor. The accor- Attention: Sufficient equipotential bonding ● Connection of the housing potential ding switch is integrated in the housing on of the installation must be ensured. The de- via an M5 x 1 bolt the board. vice is connected via the bolt of the hou- sing to the system’s potentializer. ● For Ex applications: -25…+70 °C (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) ● Integrated terminating resistor (switch-in) ● Cable shielding: capacitive or direct connection to housing potential sel- ectable via switch ● Isolated support terminal for optio- nal protective conductor incorpora- ted in cable

78 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49-T415B/EX

Type JBBS-49-T415B/EX Dimensions Ident-No. 6611445

122 Fieldbus standard IEC 61158-2 64 36 45 Operational voltage range: 9 … 32 VDC

Ex approval acc. to conformity certificate PTB 03 ATEX 2236 Entity Parameter 138 ð Max.output voltage Uo 24 V ð 150 Max. output current Io 250 mA ð Max. output power Po 2560 mW 172 ð Max. input voltage Ui 24 V ð Max. input current Ii 250 mA ð Max. input power Pi 2560 mW FISCO parameter according to IEC TS 60079-27

ð Max.output voltage Uo 17.5 V ð Max. output current Io 380 mA ð Terminal Configuration Max. output power Po 5320 mW 4 ð Max. input voltage Ui 17.5 V ð Max. input current Ii 380 mA ð Max. input power Pi 5320 mW 1 = n.c. 2 = shield External inductance/capacitance Li/Ci trunk (in/out): 3 = + negligible / ð 5.00 nF 1234 4 = – per field current circuit: negligible / ð 0.47 nF æ field current circuits: negligible / ð 5.00 nF Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) [Ex ibD] EEx ib IIB T4 É II 2 (1) G (1D) [Ex iaD] EEx ia IIB T4 FISCO / Entity field device

Electrical connection cable glands Segment IN 1 x M20 x 1.5 (Ø 6…12 mm) Segment OUT 1 x M20 x 1.5 (Ø 6…12 mm) Drop line 4 x M20 x 1.5 (Ø 6…12 mm) Terminal cross-section 2.5 mm2 Earthing bolt M5 x 1

Degree of protection IP67 Ambient temperature -25 …+ 70 °C Housing material powder-coated die-cast aluminium Housing color black/yellow Dimensions 64 x 150 x 45 mm Connection mode Wall mounting

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 79 /0309 FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49-T615B/EX

FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49-T615B/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Trunk In 1µF Trunk Out n.c. 1 1 n.c. S 2 2 S P1 S0 + 3 3 + – 4 4 –

n.c. 1 1 n.c. S 2 2 S S1 S2 + 3 3 + – 4 4 –

n.c. 1 1 n.c. S 2 2 S S3 S4 + 3 3 + – 4 4 –

n.c. 1 1 n.c. S 2 2 S S5 S6 + 3 3 + – 4 4 –

case ground

The 6-port Ex-junction module JBBS-49- To avoid condensation build-up in the hou- ● Entity and FISCO compliant accor- T615B/EX is designed for FOUNDATION™ sing, the devices are equipped with a con- ding to IEC TS 60079-27 fieldbus systems. densate drain. ● Junction box for wall mounting with PVC cable glands M20 x 1.5 The housing is made of robust die-cast alu- The shield is capacitively coupled to the ● Powder-coated die-cast aluminium minium and features protection degree housing potential. A switch for direct cou- housing IP67. pling of the shield and housing is imple- ● Pressure compensation element for mented. protection against condensation The junction box is equipped with a selec- water table bus terminating resistor. The accor- Attention: Sufficient equipotential bonding ● Connection of the housing potential ding switch is integrated in the housing on of the installation must be ensured. The de- via an M5 x 1 bolt the board. vice is connected via the bolt of the hou- sing to the system’s potentializer. ● For Ex applications: -25…+70 °C (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) ● Integrated terminating resistor (switch-in) ● Cable shielding: capacitive or direct connection to housing potential sel- ectable via switch ● Isolated support terminal for optio- nal protective conductor incorpora- ted in cable

80 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49-T615B/EX

Type JBBS-49-T615B/EX Dimensions Ident-No. 6611447

122 Fieldbus standard IEC 61158-2 64,0 36,0 45,0 Operational voltage range: 9 … 32 VDC

Ex approval acc. to conformity certificate PTB 03 ATEX 2236 Entity Parameter 173,5 ð Max.output voltage Uo 24 V ð Max. output current Io 250 mA ð 185,5 Max. output power Po 2560 mW ð 207 Max. input voltage Ui 24 V ð Max. input current Ii 250 mA ð Max. input power Pi 2560 mW FISCO parameter according to IEC TS 60079-27

ð Max.output voltage Uo 17.5 V ð Max. output current Io 380 mA ð Max. output power Po 5320 mW 4 ð Max. input voltage Ui 17.5 V ð Max. input current Ii 380 mA Terminal Configuration ð Max. input power Pi 5320 mW External inductance/capacitance Li/Ci trunk (in/out): negligible / ð 5.00 nF 1 = n.c. per field current circuit: 2 = shield negligible / ð 0.47 nF 3 = + 1234 4 = – æ field current circuits: negligible / ð 5.00 nF Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) [Ex ibD] EEx ib IIB T4 É II 2 (1) G (1D) [Ex iaD] EEx ia IIB T4 FISCO / Entity field device

Electrical connection cable glands Segment IN 1 x M20 x 1.5 (Ø 6…12 mm) Segment OUT 1 x M20 x 1.5 (Ø 6…12 mm) Drop line 6 x M20 x 1.5 (Ø 6…12 mm) Terminal cross-section 2.5 mm2 Earthing bolt M5 x 1

Degree of protection IP67 Ambient temperature -25 …+ 70 °C Housing material powder-coated die-cast aluminium Housing color black/yellow Dimensions 64 x 185.5 x 45 mm Connection mode Wall mounting

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 81 /0309 FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49-E413/EX

FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49-E413/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Segment IN 1µF Segment OUT – 1 1 – + 2 2 + P1 S0 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S1 S2 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S4 S3 S 3 3 S n.c. 4 4 n.c.

Case ground

The 4-port Ex-junction module JBBS-49- To avoid condensation build-up in the hou- ● Entity and FISCO compliant accor- E413/EX is designed for FOUNDATION™ sing, the devices are equipped with a con- ding to IEC TS 60079-27 fieldbus systems. densate drain. ● Junction box for wall mounting with stainless steel M12 flange connec- The housing is made of robust die-cast alu- The shield is capacitively coupled to the tions minium and features protection degree housing potential. A switch for direct cou- ● Powder-coated die-cast aluminium IP67. pling of the shield and housing is imple- housing mented. ● Pressure compensation element for The junction box is equipped with a selec- protection against condensation table bus terminating resistor. The accor- Attention: Sufficient equipotential bonding water ding switch is integrated in the housing on of the installation must be ensured. The de- ● Connection of the housing potential the board. vice is connected via the bolt of the hou- via an M5 x 1 bolt sing to the system’s potentializer. ● For Ex applications: -25…+70 °C (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) ● Integrated terminating resistor (switch-in) ● Cable shielding: capacitive or direct connection to housing potential sel- ectable via switch ● Isolated support terminal for optio- nal protective conductor incorpora- ted in cable

82 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49-E413/EX

Type JBBS-49-E413/EX Dimensions Ident-No. 6611425

83 Fieldbus standard IEC 61158-2 64 36 45 Operational voltage range: 9 … 32 VDC

Ex approval acc. to conformity certificate PTB 03 ATEX 2236 Entity Parameter ð 138 Max.output voltage Uo 24 V Max. output current I ð 250 mA o 150 Max. output power P ð 2560 mW o 172 ð Max. input voltage Ui 24 V ð Max. input current Ii 250 mA ð Max. input power Pi 2560 mW FISCO parameter according to IEC TS 60079-27

ð Max.output voltage Uo 17.5 V ð Max. output current Io 380 mA ð Max. output power Po 5320 mW 4 ð Max. input voltage Ui 17.5 V Terminal Configuration ð Max. input current Ii 380 mA ð M12 x 1 M12 x 1 Max. input power Pi 5320 mW Segment in Segment out, Spur External inductance/capacitance Li/Ci trunk (in/out): negligible / ð 5.00 nF 2 2 1 = V – per field current circuit: 2 = V + negligible / ð 0.47 nF 3 1 13 æ field current circuits: 3 = shield negligible / ð 5.00 nF 4 4 = n.c. 4 Device designation É II 2 G EEx ib IIC/IIB T4 nominal values: 4 A, 300 V É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) [Ex ibD] EEx ib IIB T4 É II 2 (1) G (1D) [Ex iaD] EEx ia IIB T4 FISCO / Entity field device

Electrical connection M12 flange connection Segment IN 1 x M12 - connector Segment OUT 1 x M12 - female connector Drop line 4 x M12 - female connector Earthing bolt M5 x 1

Degree of protection IP67 Ambient temperature -25 …+ 70 °C Housing material powder-coated die-cast aluminium Housing color black/yellow Dimensions 64 x 150 x 45 mm Connection mode Wall mounting

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 83 /0309 FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49-E613/EX

FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49-E613/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Segment IN 1µF Segment OUT – 1 1 – + 2 2 + P1 S0 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S1 S2 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S3 S4 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S5 S6 S 3 3 S n.c. 4 4 n.c.

Case ground

The 6-port Ex-junction module JBBS-49- To avoid condensation build-up in the hou- ● Entity and FISCO compliant accor- E613/EX is designed for FOUNDATION™ sing, the devices are equipped with a con- ding to IEC TS 60079-27 fieldbus systems. densate drain. ● Junction box for wall mounting with stainless steel M12 flange connec- The housing is made of robust die-cast alu- The shield is capacitively coupled to the tions minium and features protection degree housing potential. A switch for direct cou- ● Powder-coated die-cast aluminium IP67. pling of the shield and housing is imple- housing mented. ● Pressure compensation element for The junction box is equipped with a selec- protection against condensation table bus terminating resistor. The accor- Attention: Sufficient equipotential bonding water ding switch is integrated in the housing on of the installation must be ensured. The de- ● Connection of the housing potential the board. vice is connected via the bolt of the hou- via an M5 x 1 bolt sing to the system’s potentializer. ● For Ex applications: -25…+70 °C (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) ● Integrated terminating resistor (switch-in) ● Cable shielding: capacitive or direct connection to housing potential sel- ectable via switch ● Isolated support terminal for optio- nal protective conductor incorpora- ted in cable

84 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49-E613/EX

Type JBBS-49-E613/EX Dimensions Ident-No. 6611427

83 Fieldbus standard IEC 61158-2 64 36 45 Operational voltage range: 9 … 32 VDC

Ex approval acc. to conformity certificate PTB 03 ATEX 2236 Entity Parameter ð 173,5 Max.output voltage Uo 24 V ð Max. output current Io 250 mA Max. output power P ð 2560 mW o 185,5 Max. input voltage U ð 24 V i 207 ð Max. input current Ii 250 mA ð Max. input power Pi 2560 mW FISCO parameter according to IEC TS 60079-27

ð Max.output voltage Uo 17.5 V ð Max. output current Io 380 mA ð Max. output power Po 5320 mW 4 ð Max. input voltage Ui 17.5 V ð Max. input current Ii 380 mA ð Max. input power Pi 5320 mW Terminal Configuration External inductance/capacitance Li/Ci trunk (in/out): negligible / ð 5.00 nF per field current circuit: M12 x 1 M12 x 1 negligible / ð 0.47 nF Segment in Segment out, Spur æ 2 field current circuits: 2 1 = V – negligible / ð 5.00 nF 2 = V + Device designation É II 2 G EEx ib IIC/IIB T4 3 1 13 3 = shield É II 2(1) G EEx ia IIC/IIB T4 4 = n.c. É II 2 G (2D) [Ex ibD] EEx ib IIB T4 4 4 É II 2 (1) G (1D) [Ex iaD] EEx ia IIB T4 nominal values: 4 A, 300 V FISCO / Entity field device

Electrical connection M12 flange connection Segment IN 1 x M12 - connector Segment OUT 1 x M12 - female connector Drop line 6 x M12 - female connector Earthing bolt M5 x 1

Degree of protection IP67 Ambient temperature -25 …+ 70 °C Housing material powder-coated die-cast aluminium Housing color black/yellow Dimensions 64 x 185.5 x 45 mm Connection mode Wall mounting

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 85 /0309 FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49-M413/EX

FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49-M413/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Segment IN 1µF Segment OUT – 1 1 – + 2 2 + P1 S0 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S1 S2 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S4 S3 S 3 3 S n.c. 4 4 n.c.

Case ground

The 4-port Ex-junction module JBBS-49- To avoid condensation build-up in the hou- ● Entity and FISCO compliant accor- M413/EX is designed for FOUNDATION™ sing, the devices are equipped with a con- ding to IEC TS 60079-27 fieldbus systems. densate drain. ● Junction box for wall mounting with stainless steel 7/8" flange connec- The housing is made of robust die-cast alu- The shield is capacitively coupled to the tions minium and features protection degree housing potential. A switch for direct cou- ● Powder-coated die-cast aluminium IP67. pling of the shield and housing is imple- housing mented. ● Pressure compensation element for The junction box is equipped with a selec- protection against condensation table bus terminating resistor. The accor- Attention: Sufficient equipotential bonding water ding switch is integrated in the housing on of the installation must be ensured. The de- ● Connection of the housing potential the board. vice is connected via the bolt of the hou- via an M5 x 1 bolt sing to the system’s potentializer. ● For Ex applications: -25…+70 °C (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) ● Integrated terminating resistor (switch-in) ● Cable shielding: capacitive or direct connection to housing potential sel- ectable via switch ● Isolated support terminal for optio- nal protective conductor incorpora- ted in cable

86 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus IP67 junction box, 4-port JBBS-49-M413/EX

Type JBBS-49-M413/EX Dimensions Ident-No. 6611429

96 Fieldbus standard IEC 61158-2 64 36 45 Operational voltage range: 9 … 32 VDC

Ex approval acc. to conformity certificate PTB 03 ATEX 2236 Entity Parameter ð 138 Max.output voltage Uo 24 V ð Max. output current Io 250 mA 150 Max. output power P ð 2560 mW o 172 ð Max. input voltage Ui 24 V ð Max. input current Ii 250 mA ð Max. input power Pi 2560 mW FISCO parameter according to IEC TS 60079-27

ð Max.output voltage Uo 17.5 V ð Max. output current Io 380 mA ð Max. output power Po 5320 mW 4 ð Terminal Configuration Max. input voltage Ui 17.5 V ð Max. input current Ii 380 mA 7/8 7/8" ð Max. input power Pi 5320 mW Segment in Segment out, Spur External inductance/capacitance Li/Ci trunk (in/out): negligible / ð 5.00 nF 1 = V – 1 3 3 1 per field current circuit: 2 = V + negligible / ð 0.47 nF 2 4 3 = shield 4 2 æ field current circuits: 4 = n.c. negligible / ð 5.00 nF nominal values: 9 A, 300 V Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) [Ex ibD] EEx ib IIB T4 É II 2 (1) G (1D) [Ex iaD] EEx ia IIB T4 FISCO / Entity field device

Electrical connection 7/8" flange connection Segment IN 1 x 7/8 "- plug Segment OUT 1 x 7/8 "- plug Drop line 4 x 7/8 "- plug Earthing bolt M5 x 1

Degree of protection IP67 Ambient temperature -25 …+ 70 °C Housing material powder-coated die-cast aluminium Housing color black/yellow Dimensions 64 x 150 x 45 mm Connection mode Wall mounting

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 87 /0309 FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49-M613/EX

FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49-M613/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Segment IN 1µF Segment OUT – 1 1 – + 2 2 + P1 S0 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S1 S2 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S3 S4 S 3 3 S n.c. 4 4 n.c.

– 1 1 – + 2 2 + S5 S6 S 3 3 S n.c. 4 4 n.c.

Case ground

The 6-port Ex-junction module JBBS-49- To avoid condensation build-up in the hou- ● Entity and FISCO compliant accor- M613/EX is designed for FOUNDATION™ sing, the devices are equipped with a con- ding to IEC TS 60079-27 fieldbus systems. densate drain. ● Junction box for wall mounting with stainless steel 7/8" flange connec- The housing is made of robust die-cast alu- The shield is capacitively coupled to the tions minium and features protection degree housing potential. A switch for direct cou- ● Powder-coated die-cast aluminium IP67. pling of the shield and housing is imple- housing mented. ● Pressure compensation element for The junction box is equipped with a selec- protection against condensation table bus terminating resistor. The accor- Attention: Sufficient equipotential bonding water ding switch is integrated in the housing on of the installation must be ensured. The de- ● Connection of the housing potential the board. vice is connected via the bolt of the hou- via an M5 x 1 bolt sing to the system’s potentializer. ● For Ex applications: -25…+70 °C (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) ● Integrated terminating resistor (switch-in) ● Cable shielding: capacitive or direct connection to housing potential sel- ectable via switch ● Isolated support terminal for optio- nal protective conductor incorpora- ted in cable

88 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus IP67 junction box, 6-port JBBS-49-M613/EX

Type JBBS-49-M613/EX Dimensions Ident-No. 6611431

96 Fieldbus standard IEC 61158-2 64 36 45 Operational voltage range: 9 … 32 VDC

Ex approval acc. to conformity certificate PTB 03 ATEX 2236 Entity Parameter ð Max.output voltage Uo 24 V ð 173,5 Max. output current Io 250 mA ð Max. output power Po 2560 mW 185,5 ð Max. input voltage Ui 24 V 207 ð Max. input current Ii 250 mA ð Max. input power Pi 2560 mW FISCO parameter according to IEC TS 60079-27

ð Max.output voltage Uo 17.5 V ð Max. output current Io 380 mA ð Max. output power Po 5320 mW 4 ð Max. input voltage Ui 17.5 V ð Max. input current Ii 380 mA ð Max. input power Pi 5320 mW Terminal Configuration External inductance/capacitance Li/Ci trunk (in/out): negligible / ð 5.00 nF 7/8 7/8" per field current circuit: Segment in Segment out, Spur negligible / ð 0.47 nF 1 = V – æ field current circuits: 1 3 3 1 negligible / ð 5.00 nF 2 = V + Device designation É II 2 G EEx ib IIC/IIB T4 2 4 3 = shield 4 2 É II 2(1) G EEx ia IIC/IIB T4 4 = n.c. É II 2 G (2D) [Ex ibD] EEx ib IIB T4 nominal values: 9 A, 300 V É II 2 (1) G (1D) [Ex iaD] EEx ia IIB T4 FISCO / Entity field device

Electrical connection 7/8" flange connection Segment IN 1 x 7/8 "- plug Segment OUT 1 x 7/8 "- plug Drop line 6 x 7/8 "- plug Earthing bolt M5 x 1

Degree of protection IP67 Ambient temperature -25 …+ 70 °C Housing material powder-coated die-cast aluminium Housing color black/yellow Dimensions 64 x 185.5 x 45 mm Connection mode Wall mounting

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 89 /0309 FOUNDATION™ fieldbus and PROFIBUS-PA IP20 junction box, 4-port JRBS-40SC-4C/EX

FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 4-port JRBS-40SC-4C/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Trunk In 1µF Trunk Out – – + + P1 S0 S S

– – + + 14 S S

– – + + 23 S S

case ground

The 4-port Ex junction box JRBS-40SC- the board. ● Entity and FISCO compliant accor- 4C/EX is designed for fieldbus systems ac- ding to IEC TS 60079-27 cording to IEC 61158-2, i.e. it is suited for The shield is capacitively coupled to the ● Junction box for DIN rail mounting both PROFIBUS PA and FOUNDATION ™ housing potential. A switch for direct cou- ● Aluminium housing fieldbus. pling of the shield and housing is imple- mented. ● Short-circuit protection per drop The junction box features an adjustable line/spur short-circuit limit. The max. current limita- Attention: Sufficient equipotential bonding ● For Ex applications: -25…+70 °C tion is selected for all ports via a rotary of the installation must be ensured. The de- (-13…+158 °F); for non-Ex applicati- switch. The following values can be sel- vice is connected via the bolt of the hou- ons: -40…+70 °C (-40…+158 °F) ected: 30, 35, 45 and 60 mA. sing to the system’s potentializer. ● Switch-in terminating resistor ● Cable shielding: Capacitive or direct The housing is made of aluminium and fea- Accessories: To increase the degree of connection with housing potential tures protection degree IP20. protection, there are various aluminium and selectable via switch stainless steel housings with IP6x rating and The junction box is equipped with a selec- various cable glands available on request. table bus terminating resistor. The accor- ding switch is integrated in the housing on

90 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus and PROFIBUS-PA IP20 junction box, 4-port JRBS-40SC-4C/EX

Type JRBS-40SC-4C/EX Dimensions Ident-No. 6611451

Fieldbus standard IEC 61158-2

Operational voltage range: 12 … 32 VDC 31 Current self-consumption ð 7 mA

Voltage drop ð 0.3 V 119 75,5 Short-circuit protection ð 30 , 35 , 45 , 60 mA

Indication Operational readiness 1 x green Terminal Configuration Short-circuit message 4 x red

1 = – Ex approval acc. to conformity certificate PTB 05 ATEX 2002 2 = + 3 = S Entity Parameter 123 ð Max.output voltage Uo 24 V ð Max. output current Io 250 mA ð Max. output power Po 2560 mW ð 4 Max. input voltage Ui 24 V ð Max. input current Ii 250 mA ð Max. input power Pi 2560 mW FISCO parameter according to IEC TS 60079-27

ð Max.output voltage Uo 17.5 V ð Max. output current Io 380 mA ð Max. output power Po 5320 mW ð Max. input voltage Ui 17.5 V ð Max. input current Ii 380 mA ð Max. input power Pi 5320 mW External inductance/capacitance Li/Ci Trunk (In/Out): negligible / ð 5.00 nF per field current circuit: negligible / ð 0.82 nF æ field current circuits: negligible / ð 5.00 nF Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) EEx ib [ibD] IIB T4 É II 2 (1) G (1D) EEx ia [iaD] IIB T4 FISCO / Entity field device Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device

Electrical connection cage clamp terminals Terminal cross-section 2.5 mm2 Earthing bolt M5 x 1

Degree of protection IP20 Ambient temperature -25 …+ 70 °C Housing material aluminium Housing color black Dimensions 119 x 31 x 75.5 mm Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 91 /0309 FOUNDATION™ fieldbus and PROFIBUS-PA IP20 junction box, 6-port JRBS-40SC-6C/EX

FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 6-port JRBS-40SC-6C/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Trunk In 1µF Trunk Out – – + + P1 S0 S S

– – + + 1 6 S S

– – + + 2 5 S S

– – + + 3 4 S S

case ground

The 6-port Ex junction box JRBS-40SC- the board. ● Entity and FISCO compliant accor- 6C/EX is designed for fieldbus systems ac- ding to IEC TS 60079-27 cording to IEC 61158-2, i.e. it is suited for The shield is capacitively coupled to the ● Junction box for DIN rail mounting both PROFIBUS PA and FOUNDATION ™ housing potential. A switch for direct cou- ● Aluminium housing fieldbus. pling of the shield and housing is imple- mented. ● Short-circuit protection per drop The junction box features an adjustable line/spur short-circuit limit. The max. current limita- Attention: Sufficient equipotential bonding ● For Ex applications: -25…+70 °C tion is selected for all ports via a rotary of the installation must be ensured. The de- (-13…+158 °F); for non-Ex applicati- switch. The following values can be sel- vice is connected via the bolt of the hou- ons: -40…+70 °C (-40…+158 °F) ected: 30, 35, 45 and 60 mA. sing to the system’s potentializer. ● Switch-in terminating resistor ● Cable shielding: Capacitive or direct The housing is made of aluminium and fea- Accessories: To increase the degree of connection with housing potential tures protection degree IP20. protection, there are various aluminium and selectable via switch stainless steel housings with IP6x rating and The junction box is equipped with a selec- various cable glands available on request. table bus terminating resistor. The accor- ding switch is integrated in the housing on

92 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus and PROFIBUS-PA IP20 junction box, 6-port JRBS-40SC-6C/EX

Type JRBS-40SC-6C/EX Dimensions Ident-No. 6611452

Fieldbus standard IEC 61158-2

31 Operational voltage range: 12 … 32 VDC Current self-consumption ð 7 mA Voltage drop ð 0.3 V 142 Short-circuit protection ð 30 , 35 , 45 , 60 mA 75,5

Indication Operational readiness 1 x green Short-circuit message 6 x red Terminal Configuration

Ex approval acc. to conformity certificate PTB 05 ATEX 2002 1 = – 2 = + Entity Parameter 3 = S ð 123 Max.output voltage Uo 24 V ð Max. output current Io 250 mA ð Max. output power Po 2560 mW ð 4 Max. input voltage Ui 24 V ð Max. input current Ii 250 mA ð Max. input power Pi 2560 mW FISCO parameter according to IEC TS 60079-27

ð Max.output voltage Uo 17.5 V ð Max. output current Io 380 mA ð Max. output power Po 5320 mW ð Max. input voltage Ui 17.5 V ð Max. input current Ii 380 mA ð Max. input power Pi 5320 mW External inductance/capacitance Li/Ci Trunk (In/Out): negligible / ð 5.00 nF per field current circuit: negligible / ð 0.82 nF æ field current circuits: negligible / ð 5.00 nF Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) EEx ib [ibD] IIB T4 É II 2 (1) G (1D) EEx ia [iaD] IIB T4 FISCO / Entity field device Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device

Electrical connection cage clamp terminals Terminal cross-section 2.5 mm2 Earthing bolt M5 x 1

Degree of protection IP20 Ambient temperature -25 …+ 70 °C Housing material aluminium Housing color black Dimensions 142 x 31 x 75.5 mm Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 93 /0309 FOUNDATION™ fieldbus and PROFIBUS-PA IP20 junction box, 8-port JRBS-40SC-8C/EX

FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 8-port JRBS-40SC-8C/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Trunk In 1µF Trunk Out – – + + P1 S0 S S

– – + + 1 8 S S

– – + + 2 7 S S

– – + + 3 6 S S

– – + + 4 5 S S

case ground

The 8-port Ex junction box JRBS-40SC- the board. ● Entity and FISCO compliant accor- 8C/EX is designed for fieldbus systems ac- ding to IEC TS 60079-27 cording to IEC 61158-2, i.e. it is suited for The shield is capacitively coupled to the ● Junction box for DIN rail mounting both PROFIBUS PA and FOUNDATION ™ housing potential. A switch for direct cou- ● Aluminium housing fieldbus. pling of the shield and housing is imple- mented. ● Short-circuit protection per drop The junction box features an adjustable line/spur short-circuit limit. The max. current limita- Attention: Sufficient equipotential bonding ● For Ex applications: -25…+70 °C tion is selected for all ports via a rotary of the installation must be ensured. The de- (-13…+158 °F); for non-Ex applicati- switch. The following values can be sel- vice is connected via the bolt of the hou- ons: -40…+70 °C (-40…+158 °F) ected: 30, 35, 45 and 60 mA. sing to the system’s potentializer. ● Switch-in terminating resistor ● Cable shielding: Capacitive or direct The housing is made of aluminium and fea- Accessories: To increase the degree of connection with housing potential tures protection degree IP20. protection, there are various aluminium and selectable via switch stainless steel housings with IP6x rating and The junction box is equipped with a selec- various cable glands available on request. table bus terminating resistor. The accor- ding switch is integrated in the housing on

94 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus and PROFIBUS-PA IP20 junction box, 8-port JRBS-40SC-8C/EX

Type JRBS-40SC-8C/EX Dimensions Ident-No. 6611453

Fieldbus standard IEC 61158-2

31 Operational voltage range: 12 … 32 VDC Current self-consumption ð 7 mA ð Voltage drop 0.3 V 177

Short-circuit protection ð 30 , 35 , 45 , 60 mA 75,5

Indication Operational readiness 1 x green Short-circuit message 8 x red Terminal Configuration

Ex approval acc. to conformity certificate PTB 05 ATEX 2002 1 = – 2 = + Entity Parameter 3 = S ð 123 Max.output voltage Uo 24 V ð Max. output current Io 250 mA ð Max. output power Po 2560 mW ð 4 Max. input voltage Ui 24 V ð Max. input current Ii 250 mA ð Max. input power Pi 2560 mW FISCO parameter according to IEC TS 60079-27

ð Max.output voltage Uo 17.5 V ð Max. output current Io 380 mA ð Max. output power Po 5320 mW ð Max. input voltage Ui 17.5 V ð Max. input current Ii 380 mA ð Max. input power Pi 5320 mW External inductance/capacitance Li/Ci Trunk (In/Out): negligible / ð 5.00 nF per field current circuit: negligible / ð 0.47 nF æ field current circuits: negligible / ð 5.00 nF Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) EEx ib [ibD] IIB T4 É II 2 (1) G (1D) EEx ia [iaD] IIB T4 FISCO / Entity field device Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device

Electrical connection cage clamp terminals Terminal cross-section 2.5 mm2 Earthing bolt M5 x 1

Degree of protection IP20 Ambient temperature -25 …+ 70 °C Housing material aluminium Housing color black Dimensions 177 x 31 x 75.5 mm Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 95 /0309 FOUNDATION™ fieldbus and PROFIBUS-PA IP20 junction box, 12-port JRBS-40SC-12C/EX

FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 12-port JRBS-40SC-12C/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Trunk In 1µF Trunk Out – – + + P1 S0 S S

– – + + 1 12 S S

......

– – + + 6 7 S S

case ground

The 12-port Ex junction box JRBS-40SC- the board. ● Entity and FISCO compliant accor- 12C/EX is designed for fieldbus systems ding to IEC TS 60079-27 according to IEC 61158-2, i.e. it is suited for The shield is capacitively coupled to the ● Junction box for DIN rail mounting both PROFIBUS PA and FOUNDATION ™ housing potential. A switch for direct cou- ● Aluminium housing fieldbus. pling of the shield and housing is imple- mented. ● Short-circuit protection per drop The junction box features an adjustable line/spur short-circuit limit. The max. current limita- Attention: Sufficient equipotential bonding ● For Ex applications: -25…+70 °C tion is selected for all ports via a rotary of the installation must be ensured. The de- (-13…+158 °F); for non-Ex applicati- switch. The following values can be sel- vice is connected via the bolt of the hou- ons: -40…+70 °C (-40…+158 °F) ected: 30, 35, 45 and 60 mA. sing to the system’s potentializer. ● Switch-in terminating resistor ● Cable shielding: Capacitive or direct The housing is made of aluminium and fea- Accessories: To increase the degree of connection with housing potential tures protection degree IP20. protection, there are various aluminium and selectable via switch stainless steel housings with IP6x rating and The junction box is equipped with a selec- various cable glands available on request. table bus terminating resistor. The accor- ding switch is integrated in the housing on

96 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus and PROFIBUS-PA IP20 junction box, 12-port JRBS-40SC-12C/EX

Type JRBS-40SC-12C/EX Dimensions Ident-No. 6611455

Fieldbus standard IEC 61158-2 31 Operational voltage range: 12 … 32 VDC Current self-consumption ð 7 mA Voltage drop ð 0.3 V

Short-circuit protection ð 30 , 35 , 45 , 60 mA 276

Indication 75,5 Operational readiness 1 x green Short-circuit message 12 x red

Ex approval acc. to conformity certificate PTB 05 ATEX 2002 Terminal Configuration Entity Parameter ð Max.output voltage Uo 24 V ð 1 = – Max. output current Io 250 mA 2 = + ð 3 = S Max. output power Po 2560 mW 123 ð 4 Max. input voltage Ui 24 V ð Max. input current Ii 250 mA ð Max. input power Pi 2560 mW FISCO parameter according to IEC TS 60079-27

ð Max.output voltage Uo 17.5 V ð Max. output current Io 380 mA ð Max. output power Po 5320 mW ð Max. input voltage Ui 17.5 V ð Max. input current Ii 380 mA ð Max. input power Pi 5320 mW External inductance/capacitance Li/Ci Trunk (In/Out): negligible / ð 5.00 nF per field current circuit: negligible / ð 0.33 nF æ field current circuits: negligible / ð 5.00 nF Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) EEx ib [ibD] IIB T4 É II 2 (1) G (1D) EEx ia [iaD] IIB T4 FISCO / Entity field device Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device

Electrical connection cage clamp terminals Terminal cross-section 2.5 mm2 Earthing bolt M5 x 1

Degree of protection IP20 Ambient temperature -25 …+ 70 °C Housing material aluminium Housing color black Dimensions 276 x 31 x 75.5 mm Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 97 /0309 FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 4-port JRBS-40SC-4R/EX

FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 4-port JRBS-40SC-4R/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Trunk In 1µF Trunk Out – – + + P1 S0 S S

– – + + 14 S S

– – + + 23 S S

case ground

The 4-port Ex junction box JRBS-40SC- the board. ● Entity and FISCO compliant accor- 4R/EX is designed for fieldbus systems ac- ding to IEC TS 60079-27 cording to IEC 61158-2, i.e. it is suited for The shield is capacitively coupled to the ● Junction box for DIN rail mounting both PROFIBUS PA and FOUNDATION ™ housing potential. A switch for direct cou- ● Aluminium housing fieldbus. pling of the shield and housing is imple- mented. ● Short-circuit protection per drop The junction box features an adjustable line/spur short-circuit limit. The max. current limita- Attention: Sufficient equipotential bonding ● For Ex applications: -25…+70 °C tion is selected for all ports via a rotary of the installation must be ensured. The de- (-13…+158 °F); for non-Ex applicati- switch. The following values can be sel- vice is connected via the bolt of the hou- ons: -40…+70 °C (-40…+158 °F) ected: 30, 35, 45 and 60 mA. sing to the system’s potentializer. ● Switch-in terminating resistor ● Cable shielding: Capacitive or direct The housing is made of aluminium and fea- Accessories: To increase the degree of connection with housing potential tures protection degree IP20. protection, there are various aluminium and selectable via switch stainless steel housings with IP6x rating and The junction box is equipped with a selec- various cable glands available on request. table bus terminating resistor. The accor- ding switch is integrated in the housing on

98 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 4-port JRBS-40SC-4R/EX

Type JRBS-40SC-4R/EX Dimensions Ident-No. 6611459

Fieldbus standard IEC 61158-2

Operational voltage range: 12 … 32 VDC 60 Current self-consumption ð 7 mA 31 Voltage drop ð 0.3 V

Short-circuit protection ð 30 , 35 , 45 , 60 mA 107 75,5

Indication Operational readiness 1 x green Short-circuit message 4 x red

Ex approval acc. to conformity certificate PTB 05 ATEX 2002 Terminal Configuration Entity Parameter ð Max.output voltage Uo 24 V 1 = – ð 2 = + Max. output current Io 250 mA 3 = S ð 123 Max. output power Po 2560 mW ð 4 Max. input voltage Ui 24 V ð Max. input current Ii 250 mA ð Max. input power Pi 2560 mW FISCO parameter acc. to IEC TS 60079-27 ð Max.output voltage Uo 17.5 V ð Max. output current Io 380 mA ð Max. output power Po 5320 mW ð Max. input voltage Ui 17.5 V ð Max. input current Ii 380 mA ð Max. input power Pi 5320 mW External inductance/capacitance Li/Ci Trunk (In/Out): negligible / ð 5.00 nF per field current circuit: negligible / ð 0.82 nF æ field current circuits: negligible / ð 5.00 nF Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) EEx ib [ibD] IIB T4 É II 2 (1) G (1D) EEx ia [iaD] IIB T4 FISCO / Entity field device Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device

Electrical connection removable terminal block, reverse polarity pro- tected, screw connection Terminal cross-section 2.5 mm2 Earthing bolt M5 x 1

Degree of protection IP20 Ambient temperature -25 …+ 70 °C Housing material aluminium Housing color black Dimensions 119 x 31 x 75.5 mm Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 99 /0309 FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 6-port JRBS-40SC-6R/EX

FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 6-port JRBS-40SC-6R/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Trunk In 1µF Trunk Out – – + + P1 S0 S S

– – + + 1 6 S S

– – + + 2 5 S S

– – + + 3 4 S S

case ground

The 6-port Ex junction box JRBS-40SC- the board. ● Entity and FISCO compliant accor- 6R/EX is designed for fieldbus systems ac- ding to IEC TS 60079-27 cording to IEC 61158-2, i.e. it is suited for The shield is capacitively coupled to the ● Junction box for DIN rail mounting both PROFIBUS PA and FOUNDATION ™ housing potential. A switch for direct cou- ● Aluminium housing fieldbus. pling of the shield and housing is imple- mented. ● Short-circuit protection per drop The junction box features an adjustable line/spur short-circuit limit. The max. current limita- Attention: Sufficient equipotential bonding ● For Ex applications: -25…+70 °C tion is selected for all ports via a rotary of the installation must be ensured. The de- (-13…+158 °F); for non-Ex applicati- switch. The following values can be sel- vice is connected via the bolt of the hou- ons: -40…+70 °C (-40…+158 °F) ected: 30, 35, 45 and 60 mA. sing to the system’s potentializer. ● Switch-in terminating resistor ● Cable shielding: Capacitive or direct The housing is made of aluminium and fea- Accessories: To increase the degree of connection with housing potential tures protection degree IP20. protection, there are various aluminium and selectable via switch stainless steel housings with IP6x rating and The junction box is equipped with a selec- various cable glands available on request. table bus terminating resistor. The accor- ding switch is integrated in the housing on

100 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 6-port JRBS-40SC-6R/EX

Type JRBS-40SC-6R/EX Dimensions Ident-No. 6611460

Fieldbus standard IEC 61158-2 60 Operational voltage range: 12 … 32 VDC 31 Current self-consumption ð 7 mA Voltage drop ð 0.3 V

Short-circuit protection ð 30 , 35 , 45 , 60 mA 142 75,5 Indication Operational readiness 1 x green Short-circuit message 6 x red

Ex approval acc. to conformity certificate PTB 05 ATEX 2002 Terminal Configuration Entity Parameter ð Max.output voltage Uo 24 V 1 = – ð 2 = + Max. output current Io 250 mA 3 = S ð 123 Max. output power Po 2560 mW ð 4 Max. input voltage Ui 24 V ð Max. input current Ii 250 mA ð Max. input power Pi 2560 mW FISCO parameter acc. to IEC TS 60079-27 ð Max.output voltage Uo 17.5 V ð Max. output current Io 380 mA ð Max. output power Po 5320 mW ð Max. input voltage Ui 17.5 V ð Max. input current Ii 380 mA ð Max. input power Pi 5320 mW External inductance/capacitance Li/Ci Trunk (In/Out): negligible / ð 5.00 nF per field current circuit: negligible / ð 0.82 nF æ field current circuits: negligible / ð 5.00 nF Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) EEx ib [ibD] IIB T4 É II 2 (1) G (1D) EEx ia [iaD] IIB T4 FISCO / Entity field device Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device

Electrical connection removable terminal block, reverse polarity pro- tected, screw connection Terminal cross-section 2.5 mm2 Earthing bolt M5 x 1

Degree of protection IP20 Ambient temperature -25 …+ 70 °C Housing material aluminium Housing color black Dimensions 142 x 31 x 75.5 mm Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 101 /0309 FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 8-port JRBS-40SC-8R/EX

FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 8-port JRBS-40SC-8R/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Trunk In 1µF Trunk Out – – + + P1 S0 S S

– – + + 1 8 S S

– – + + 2 7 S S

– – + + 3 6 S S

– – + + 4 5 S S

case ground

The 8-port Ex junction box JRBS-40SC- the board. ● Entity and FISCO compliant accor- 8R/EX is designed for fieldbus systems ac- ding to IEC TS 60079-27 cording to IEC 61158-2, i.e. it is suited for The shield is capacitively coupled to the ● Junction box for DIN rail mounting both PROFIBUS PA and FOUNDATION ™ housing potential. A switch for direct cou- ● Aluminium housing fieldbus. pling of the shield and housing is imple- mented. ● Short-circuit protection per drop The junction box features an adjustable line/spur short-circuit limit. The max. current limita- Attention: Sufficient equipotential bonding ● For Ex applications: -25…+70 °C tion is selected for all ports via a rotary of the installation must be ensured. The de- (-13…+158 °F); for non-Ex applicati- switch. The following values can be sel- vice is connected via the bolt of the hou- ons: -40…+70 °C (-40…+158 °F) ected: 30, 35, 45 and 60 mA. sing to the system’s potentializer. ● Switch-in terminating resistor ● Cable shielding: Capacitive or direct The housing is made of aluminium and fea- Accessories: To increase the degree of connection with housing potential tures protection degree IP20. protection, there are various aluminium and selectable via switch stainless steel housings with IP6x rating and The junction box is equipped with a selec- various cable glands available on request. table bus terminating resistor. The accor- ding switch is integrated in the housing on

102 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 8-port JRBS-40SC-8R/EX

Type JRBS-40SC-8R/EX Dimensions Ident-No. 6611461

Fieldbus standard IEC 61158-2 60

Operational voltage range: 12 … 32 VDC 31 Current self-consumption ð 7 mA Voltage drop ð 0.3 V

Short-circuit protection ð 30 , 35 , 45 , 60 mA 212

Indication 75,5 Operational readiness 1 x green Short-circuit message 8 x red

Ex approval acc. to conformity certificate PTB 05 ATEX 2002 Terminal Configuration Entity Parameter ð Max.output voltage Uo 24 V ð 1 = – Max. output current Io 250 mA 2 = + ð 3 = S Max. output power Po 2560 mW 123 ð 4 Max. input voltage Ui 24 V ð Max. input current Ii 250 mA ð Max. input power Pi 2560 mW FISCO parameter acc. to IEC TS 60079-27 ð Max.output voltage Uo 17.5 V ð Max. output current Io 380 mA ð Max. output power Po 5320 mW ð Max. input voltage Ui 17.5 V ð Max. input current Ii 380 mA ð Max. input power Pi 5320 mW External inductance/capacitance Li/Ci Trunk (In/Out): negligible / ð 5.00 nF per field current circuit: negligible / ð 0.47 nF æ field current circuits: negligible / ð 5.00 nF Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) EEx ib [ibD] IIB T4 É II 2 (1) G (1D) EEx ia [iaD] IIB T4 FISCO / Entity field device Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device

Electrical connection removable terminal block, reverse polarity pro- tected, screw connection Terminal cross-section 2.5 mm2 Earthing bolt M5 x 1

Degree of protection IP20 Ambient temperature -25 …+ 70 °C Housing material aluminium Housing color black Dimensions 177 x 31 x 75.5 mm Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 103 /0309 FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 12-port JRBS-40SC-12R/EX

FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 12-port JRBS-40SC-12R/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Trunk In 1µF Trunk Out – – + + P1 S0 S S

– – + + 1 12 S S

......

– – + + 6 7 S S

case ground

The 12-port Ex junction box JRBS-40SC- the board. ● Entity and FISCO compliant accor- 12R/EX is designed for fieldbus systems ding to IEC TS 60079-27 according to IEC 61158-2, i.e. it is suited for The shield is capacitively coupled to the ● Junction box for DIN rail mounting both PROFIBUS PA and FOUNDATION ™ housing potential. A switch for direct cou- ● Aluminium housing fieldbus. pling of the shield and housing is imple- mented. ● Short-circuit protection per drop The junction box features an adjustable line/spur short-circuit limit. The max. current limita- Attention: Sufficient equipotential bonding ● For Ex applications: -25…+70 °C tion is selected for all ports via a rotary of the installation must be ensured. The de- (-13…+158 °F); for non-Ex applicati- switch. The following values can be sel- vice is connected via the bolt of the hou- ons: -40…+70 °C (-40…+158 °F) ected: 30, 35, 45 and 60 mA. sing to the system’s potentializer. ● Switch-in terminating resistor ● Cable shielding: Capacitive or direct The housing is made of aluminium and fea- Accessories: To increase the degree of connection with housing potential tures protection degree IP20. protection, there are various aluminium and selectable via switch stainless steel housings with IP6x rating and The junction box is equipped with a selec- various cable glands available on request. table bus terminating resistor. The accor- ding switch is integrated in the housing on

104 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 12-port JRBS-40SC-12R/EX

Type JRBS-40SC-12R/EX Dimensions Ident-No. 6611463

Fieldbus standard IEC 61158-2 60

Operational voltage range: 12 … 32 VDC 31 Current self-consumption ð 7 mA Voltage drop ð 0.3 V

Short-circuit protection ð 30 , 35 , 45 , 60 mA 276 Indication Operational readiness 1 x green 75,5 Short-circuit message 12 x red

Ex approval acc. to conformity certificate PTB 05 ATEX 2002 Entity Parameter Terminal Configuration ð Max.output voltage Uo 24 V ð Max. output current Io 250 mA 1 = – ð 2 = + Max. output power Po 2560 mW 3 = S ð 123 4 Max. input voltage Ui 24 V ð Max. input current Ii 250 mA ð Max. input power Pi 2560 mW FISCO parameter acc. to IEC TS 60079-27 ð Max.output voltage Uo 17.5 V ð Max. output current Io 380 mA ð Max. output power Po 5320 mW ð Max. input voltage Ui 17.5 V ð Max. input current Ii 380 mA ð Max. input power Pi 5320 mW External inductance/capacitance Li/Ci Trunk (In/Out): negligible / ð 5.00 nF per field current circuit: negligible / ð 0.33 nF æ field current circuits: negligible / ð 5.00 nF Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) EEx ib [ibD] IIB T4 É II 2 (1) G (1D) EEx ia [iaD] IIB T4 FISCO / Entity field device Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device

Electrical connection removable terminal block, reverse polarity pro- tected, screw connection Terminal cross-section 2.5 mm2 Earthing bolt M5 x 1

Degree of protection IP20 Ambient temperature -25 …+ 70 °C Housing material aluminium Housing color black Dimensions 276 x 31 x 75.5 mm Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 105 /0309 FOUNDATION™ fieldbus and PROFIBUS-PA IP20 junction box, 4-port JRBS-40-4C/EX

FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 4-port JRBS-40-4C/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Trunk In 1µF Trunk Out – – + + P1 S0 S S

– – + + 1 4 S S

– – + + 2 3 S S

case ground

The 4-port Ex junction box JRBS-40-4C/EX The shield is capacitively coupled to the ● Entity and FISCO compliant accor- is designed for fieldbus systems according housing potential. A switch for direct cou- ding to IEC TS 60079-27 to IEC 61158-2, i.e. it is suited for both pling of the shield and housing is imple- ● Junction box for DIN rail mounting PROFIBUS PA and FOUNDATION ™ mented. ● Aluminium housing fieldbus. Attention: Sufficient equipotential bonding ● For Ex applications: -25…+70 °C The housing is made of aluminium and fea- of the installation must be ensured. The de- (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) tures protection degree IP20. vice is connected via the bolt of the hou- sing to the system’s potentializer. ● Switch-in terminating resistor The junction box is equipped with a selec- ● Cable shielding: Capacitive or direct table bus terminating resistor. The accor- Accessories: To increase the degree of connection with housing potential ding switch is integrated in the housing on protection, there are various aluminium and selectable via switch the board. stainless steel housings with IP6x rating and various cable glands available on request.

106 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus and PROFIBUS-PA IP20 junction box, 4-port JRBS-40-4C/EX

Type JRBS-40-4C/EX Dimensions Ident-No. 6611448

Fieldbus standard IEC 61158-2

Operational voltage range: 9 … 32 VDC 31

Ex approval acc. to conformity certificate PTB 05 ATEX 2002 119 Entity Parameter 75,5 ð Max.output voltage Uo 24 V ð Max. output current Io 250 mA ð Max. output power Po 2560 mW ð Max. input voltage Ui 24 V Terminal Configuration ð Max. input current Ii 250 mA ð Max. input power Pi 2560 mW 1 = – FISCO parameter according to IEC TS 60079-27 2 = + 3 = S 123 ð Max.output voltage Uo 17.5 V ð Max. output current Io 380 mA ð Max. output power Po 5320 mW 4 ð Max. input voltage Ui 17.5 V ð Max. input current Ii 380 mA ð Max. input power Pi 5320 mW External inductance/capacitance Li/Ci Trunk (In/Out): negligible / ð 5.00 nF per field current circuit: negligible / ð 0.82 nF æ field current circuits: negligible / ð 5.00 nF Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) EEx ib [ibD] IIB T4 É II 2 (1) G (1D) EEx ia [iaD] IIB T4 FISCO / Entity field device Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device

Electrical connection cage clamp terminals Terminal cross-section 2.5 mm2 Earthing bolt M5 x 1

Degree of protection IP20 Ambient temperature -25 …+ 70 °C Housing material aluminium Housing color black Dimensions 119 x 31 x 75.5 mm Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 107 /0309 FOUNDATION™ fieldbus and PROFIBUS-PA IP20 junction box, 6-port JRBS-40-6C/EX

FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 6-port JRBS-40-6C/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Trunk In 1µF Trunk Out – – + + P1 S0 S S

– – + + 1 6 S S

– – + + 2 5 S S

– – + + 3 4 S S

case ground

The 6-port Ex junction box JRBS-40-6C/EX The shield is capacitively coupled to the ● Entity and FISCO compliant accor- is designed for fieldbus systems according housing potential. A switch for direct cou- ding to IEC TS 60079-27 to IEC 61158-2, i.e. it is suited for both pling of the shield and housing is imple- ● Junction box for DIN rail mounting PROFIBUS PA and FOUNDATION ™ mented. ● aluminium housing fieldbus. Attention: Sufficient equipotential bonding ● For Ex applications: -25…+70 °C The housing is made of aluminium and fea- of the installation must be ensured. The de- (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) tures protection degree IP20. vice is connected via the bolt of the hou- sing to the system’s potentializer. ● Switch-in terminating resistor The junction box is equipped with a selec- ● Cable shielding: Capacitive or direct table bus terminating resistor. The accor- Accessories: To increase the degree of connection with housing potential ding switch is integrated in the housing on protection, there are various aluminium and selectable via switch the board. stainless steel housings with IP6x rating and various cable glands available on request.

108 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus and PROFIBUS-PA IP20 junction box, 6-port JRBS-40-6C/EX

Type JRBS-40-6C/EX Dimensions Ident-No. 6611449

Fieldbus standard IEC 61158-2

31 Operational voltage range: 9 … 32 VDC

Ex approval acc. to conformity certificate PTB 05 ATEX 2002 Entity Parameter 142 ð 75,5 Max.output voltage Uo 24 V ð Max. output current Io 250 mA ð Max. output power Po 2560 mW ð Max. input voltage Ui 24 V ð Terminal Configuration Max. input current Ii 250 mA ð Max. input power Pi 2560 mW FISCO parameter according to IEC TS 60079-27 1 = – 2 = + 3 = S ð 123 Max.output voltage Uo 17.5 V ð Max. output current Io 380 mA ð Max. output power Po 5320 mW 4 ð Max. input voltage Ui 17.5 V ð Max. input current Ii 380 mA ð Max. input power Pi 5320 mW External inductance/capacitance Li/Ci Trunk (In/Out): negligible / ð 5.00 nF per field current circuit: negligible / ð 0.82 nF æ field current circuits: negligible / ð 5.00 nF Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) EEx ib [ibD] IIB T4 É II 2 (1) G (1D) EEx ia [iaD] IIB T4 FISCO / Entity field device Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device

Electrical connection cage clamp terminals Terminal cross-section 2.5 mm2 Earthing bolt M5 x 1

Degree of protection IP20 Ambient temperature -25 …+ 70 °C Housing material aluminium Housing color black Dimensions 142 x 31 x 75.5 mm Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 109 /0309 FOUNDATION™ fieldbus and PROFIBUS-PA IP20 junction box, 8-port JRBS-40-8C/EX

FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 8-port JRBS-40-8C/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Trunk In 1µF Trunk Out – – + + P1 S0 S S

– – + + 1 8 S S

– – + + 2 7 S S

– – + + 3 6 S S

– – + + 4 5 S S

case ground

The 8-port Ex junction box JRBS-40-8C/EX The shield is capacitively coupled to the ● Entity and FISCO compliant accor- is designed for fieldbus systems according housing potential. A switch for direct cou- ding to IEC TS 60079-27 to IEC 61158-2, i.e. it is suited for both pling of the shield and housing is imple- ● Junction box for DIN rail mounting PROFIBUS PA and FOUNDATION ™ mented. ● Aluminium housing fieldbus. Attention: Sufficient equipotential bonding ● For Ex applications: -25…+70 °C The housing is made of aluminium and fea- of the installation must be ensured. The de- (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) tures protection degree IP20. vice is connected via the bolt of the hou- sing to the system’s potentializer. ● Switch-in terminating resistor The junction box is equipped with a selec- ● Cable shielding: Capacitive or direct table bus terminating resistor. The accor- Accessories: To increase the degree of connection with housing potential ding switch is integrated in the housing on protection, there are various aluminium and selectable via switch the board. stainless steel housings with IP6x rating and various cable glands available on request.

110 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus and PROFIBUS-PA IP20 junction box, 8-port JRBS-40-8C/EX

Type JRBS-40-8C/EX Dimensions Ident-No. 6611450

Fieldbus standard IEC 61158-2

31 Operational voltage range: 9 … 32 VDC

Ex approval acc. to conformity certificate PTB 05 ATEX 2002 177 Entity Parameter ð 75,5 Max.output voltage Uo 24 V ð Max. output current Io 250 mA ð Max. output power Po 2560 mW ð Max. input voltage Ui 24 V ð Terminal Configuration Max. input current Ii 250 mA ð Max. input power Pi 2560 mW FISCO parameter according to IEC TS 60079-27 1 = – 2 = + 3 = S ð 123 Max.output voltage Uo 17.5 V ð Max. output current Io 380 mA ð Max. output power Po 5320 mW 4 ð Max. input voltage Ui 17.5 V ð Max. input current Ii 380 mA ð Max. input power Pi 5320 mW External inductance/capacitance Li/Ci Trunk (In/Out): negligible / ð 5.00 nF per field current circuit: negligible / ð 0.47 nF æ field current circuits: negligible / ð 5.00 nF Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) EEx ib [ibD] IIB T4 É II 2 (1) G (1D) EEx ia [iaD] IIB T4 FISCO / Entity field device Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device

Electrical connection cage clamp terminals Terminal cross-section 2.5 mm2 Earthing bolt M5 x 1

Degree of protection IP20 Ambient temperature -25 …+ 70 °C Housing material aluminium Housing color black Dimensions 177 x 31 x 75.5 mm Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 111 /0309 FOUNDATION™ fieldbus and PROFIBUS-PA IP20 junction box, 12-port JRBS-40-12C/EX

FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 12-port JRBS-40-12C/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Trunk In 1µF Trunk Out – – + + P1 S0 S S

– – + + 112 S S

......

– – + + 67 S S

case ground

The 12-port Ex junction box JRBS-40-12C/ The shield is capacitively coupled to the ● Entity and FISCO compliant accor- EX is designed for fieldbus systems accor- housing potential. A switch for direct cou- ding to IEC TS 60079-27 ding to IEC 61158-2, i.e. it is suited for both pling of the shield and housing is imple- ● Junction box for DIN rail mounting PROFIBUS PA and FOUNDATION ™ mented. ● Aluminium housing fieldbus. Attention: Sufficient equipotential bonding ● For Ex applications: -25…+70 °C The housing is made of aluminium and fea- of the installation must be ensured. The de- (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) tures protection degree IP20. vice is connected via the bolt of the hou- sing to the system’s potentializer. ● Switch-in terminating resistor The junction box is equipped with a selec- ● Cable shielding: Capacitive or direct table bus terminating resistor. The accor- Accessories: To increase the degree of connection with housing potential ding switch is integrated in the housing on protection, there are various aluminium and selectable via switch the board. stainless steel housings with IP6x rating and various cable glands available on request.

112 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus and PROFIBUS-PA IP20 junction box, 12-port JRBS-40-12C/EX

Type JRBS-40-12C/EX Dimensions Ident-No. 6611454

Fieldbus standard IEC 61158-2 31 Operational voltage range: 9 … 32 VDC

Ex approval acc. to conformity certificate PTB 05 ATEX 2002 Entity Parameter ð 276 Max.output voltage Uo 24 V ð Max. output current Io 250 mA ð Max. output power Po 2560 mW 75,5 ð Max. input voltage Ui 24 V ð Max. input current Ii 250 mA ð Max. input power Pi 2560 mW FISCO parameter according to IEC TS 60079-27 Terminal Configuration

Max.output voltage U ð 17.5 V o 1 = – ð Max. output current Io 380 mA 2 = + ð 3 = S Max. output power Po 5320 mW 123 4 ð Max. input voltage Ui 17.5 V ð Max. input current Ii 380 mA ð Max. input power Pi 5320 mW External inductance/capacitance Li/Ci Trunk (In/Out): negligible / ð 5.00 nF per field current circuit: negligible / ð 0.33 nF æ field current circuits: negligible / ð 5.00 nF Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) EEx ib [ibD] IIB T4 É II 2 (1) G (1D) EEx ia [iaD] IIB T4 FISCO / Entity field device Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device

Electrical connection cage clamp terminals Terminal cross-section 2.5 mm2 Earthing bolt M5 x 1

Degree of protection IP20 Ambient temperature -25 …+ 70 °C Housing material aluminium Housing color black Dimensions 276 x 31 x 75.5 mm Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 113 /0309 FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 4-port JRBS-40-4R/EX

FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 4-port JRBS-40-4R/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Trunk In 1µF Trunk Out – – + + P1 S0 S S

– – + + 1 4 S S

– – + + 2 3 S S

case ground

The 4-port Ex junction box JRBS-40-4R/EX The shield is capacitively coupled to the ● Entity and FISCO compliant accor- is designed for fieldbus systems according housing potential. A switch for direct cou- ding to IEC TS 60079-27 to IEC 61158-2, i.e. it is suited for both pling of the shield and housing is imple- ● Junction box for DIN rail mounting PROFIBUS PA and FOUNDATION ™ mented. ● Aluminium housing fieldbus. Attention: Sufficient equipotential bonding ● For Ex applications: -25…+70 °C The housing is made of aluminium and fea- of the installation must be ensured. The de- (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) tures protection degree IP20. vice is connected via the bolt of the hou- sing to the system’s potentializer. ● Switch-in terminating resistor The junction box is equipped with a selec- ● Cable shielding: Capacitive or direct table bus terminating resistor. The accor- Accessories: To increase the degree of connection with housing potential ding switch is integrated in the housing on protection, there are various aluminium and selectable via switch the board. stainless steel housings with IP6x rating and various cable glands available on request.

114 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 4-port JRBS-40-4R/EX

Type JRBS-40-4R/EX Dimensions Ident-No. 6611456

Fieldbus standard IEC 61158-2

Operational voltage range: 9 … 32 VDC 60 31 Ex approval acc. to conformity certificate PTB 05 ATEX 2002 Entity Parameter Max.output voltage U ð 24 V 107 o 75,5 ð Max. output current Io 250 mA ð Max. output power Po 2560 mW ð Max. input voltage Ui 24 V ð Max. input current Ii 250 mA ð Max. input power Pi 2560 mW Terminal Configuration FISCO parameter acc. to IEC TS 60079-27 ð Max.output voltage Uo 17.5 V ð 1 = – Max. output current Io 380 mA 2 = + ð 3 = S Max. output power Po 5320 mW 123 ð Max. input voltage Ui 17.5 V 4 ð Max. input current Ii 380 mA ð Max. input power Pi 5320 mW External inductance/capacitance Li/Ci Trunk (In/Out): negligible / ð 5.00 nF per field current circuit: negligible / ð 0.82 nF æ field current circuits: negligible / ð 5.00 nF Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) EEx ib [ibD] IIB T4 É II 2 (1) G (1D) EEx ia [iaD] IIB T4 FISCO / Entity field device Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device

Electrical connection removable terminal block, reverse polarity pro- tected, screw connection Terminal cross-section 2.5 mm2 Earthing bolt M5 x 1

Degree of protection IP20 Ambient temperature -25 …+ 70 °C Housing material aluminium Housing color black Dimensions 119 x 31 x 75.5 mm Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 115 /0309 FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 6-port JRBS-40-6R/EX

FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 6-port JRBS-40-6R/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Trunk In 1µF Trunk Out – – + + P1 S0 S S

– – + + 1 6 S S

– – + + 2 5 S S

– – + + 3 4 S S

case ground

The 6-port Ex junction box JRBS-40-6R/EX The shield is capacitively coupled to the ● Entity and FISCO compliant accor- is designed for fieldbus systems according housing potential. A switch for direct cou- ding to IEC TS 60079-27 to IEC 61158-2, i.e. it is suited for both pling of the shield and housing is imple- ● Junction box for DIN rail mounting PROFIBUS PA and FOUNDATION ™ mented. ● Aluminium housing fieldbus. Attention: Sufficient equipotential bonding ● For Ex applications: -25…+70 °C The housing is made of aluminium and fea- of the installation must be ensured. The de- (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) tures protection degree IP20. vice is connected via the bolt of the hou- sing to the system’s potentializer. ● Switch-in terminating resistor The junction box is equipped with a selec- ● Cable shielding: Capacitive or direct table bus terminating resistor. The accor- Accessories: To increase the degree of connection with housing potential ding switch is integrated in the housing on protection, there are various aluminium and selectable via switch the board. stainless steel housings with IP6x rating and various cable glands available on request.

116 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 6-port JRBS-40-6R/EX

Type JRBS-40-6R/EX Dimensions Ident-No. 6611457

Fieldbus standard IEC 61158-2 60 Operational voltage range: 9 … 32 VDC 31 Ex approval acc. to conformity certificate PTB 05 ATEX 2002 Entity Parameter ð Max.output voltage Uo 24 V 142 ð 75,5 Max. output current Io 250 mA ð Max. output power Po 2560 mW ð Max. input voltage Ui 24 V ð Max. input current Ii 250 mA ð Max. input power Pi 2560 mW Terminal Configuration FISCO parameter acc. to IEC TS 60079-27 ð Max.output voltage Uo 17.5 V ð 1 = – Max. output current Io 380 mA 2 = + ð 3 = S Max. output power Po 5320 mW 123 ð Max. input voltage Ui 17.5 V 4 ð Max. input current Ii 380 mA ð Max. input power Pi 5320 mW External inductance/capacitance Li/Ci Trunk (In/Out): negligible / ð 5.00 nF per field current circuit: negligible / ð 0.82 nF æ field current circuits: negligible / ð 5.00 nF Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) EEx ib [ibD] IIB T4 É II 2 (1) G (1D) EEx ia [iaD] IIB T4 FISCO / Entity field device Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device

Electrical connection removable terminal block, reverse polarity pro- tected, screw connection Terminal cross-section 2.5 mm2 Earthing bolt M5 x 1

Degree of protection IP20 Ambient temperature -25 …+ 70 °C Housing material aluminium Housing color black Dimensions 142 x 31 x 75.5 mm Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 117 /0309 FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 8-port JRBS-40-8R/EX

FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 8-port JRBS-40-8R/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Trunk In 1µF Trunk Out – – + + P1 S0 S S

– – + + 1 8 S S

– – + + 2 7 S S

– – + + 3 6 S S

– – + + 4 5 S S

case ground

The 8-port Ex junction box RBS-40-8R/EX The shield is capacitively coupled to the ● Entity and FISCO compliant accor- is designed for fieldbus systems according housing potential. A switch for direct cou- ding to IEC TS 60079-27 to IEC 61158-2, i.e. it is suited for both pling of the shield and housing is imple- ● Junction box for DIN rail mounting PROFIBUS PA and FOUNDATION ™ mented. ● Aluminium housing fieldbus. Attention: Sufficient equipotential bonding ● For Ex applications: -25…+70 °C The housing is made of aluminium and fea- of the installation must be ensured. The de- (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) tures protection degree IP20. vice is connected via the bolt of the hou- sing to the system’s potentializer. ● Switch-in terminating resistor The junction box is equipped with a selec- ● Cable shielding: Capacitive or direct table bus terminating resistor. The accor- Accessories: To increase the degree of connection with housing potential ding switch is integrated in the housing on protection, there are various aluminium and selectable via switch the board. stainless steel housings with IP6x rating and various cable glands available on request.

118 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 8-port JRBS-40-8R/EX

Type JRBS-40-8R/EX Dimensions Ident-No. 6611458

Fieldbus standard IEC 61158-2 60

Operational voltage range: 9 … 32 VDC 31

Ex approval acc. to conformity certificate PTB 05 ATEX 2002 Entity Parameter Max.output voltage U ð 24 V o 212 ð Max. output current Io 250 mA ð 75,5 Max. output power Po 2560 mW ð Max. input voltage Ui 24 V ð Max. input current Ii 250 mA ð Max. input power Pi 2560 mW FISCO parameter acc. to IEC TS 60079-27 Terminal Configuration ð Max.output voltage Uo 17.5 V ð Max. output current Io 380 mA 1 = – ð 2 = + Max. output power Po 5320 mW 3 = S ð 123 Max. input voltage Ui 17.5 V 4 ð Max. input current Ii 380 mA ð Max. input power Pi 5320 mW External inductance/capacitance Li/Ci Trunk (In/Out): negligible / ð 5.00 nF per field current circuit: negligible / ð 0.47 nF æ field current circuits: negligible / ð 5.00 nF Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) EEx ib [ibD] IIB T4 É II 2 (1) G (1D) EEx ia [iaD] IIB T4 FISCO / Entity field device Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device

Electrical connection removable terminal block, reverse polarity pro- tected, screw connection Terminal cross-section 2.5 mm2 Earthing bolt M5 x 1

Degree of protection IP20 Ambient temperature -25 …+ 70 °C Housing material aluminium Housing color black Dimensions 177 x 31 x 75.5 mm Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 119 /0309 FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 12-port JRBS-40-12R/EX

FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 12-port JRBS-40-12R/EX Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

100 W Trunk In 1µF Trunk Out – – + + P1 S0 S S

– – + + 112 S S

......

– – + + 67 S S

case ground

The 12-port Ex junction box JRBS-40-12R/ The shield is capacitively coupled to the ● Entity and FISCO compliant accor- EX is designed for fieldbus systems accor- housing potential. A switch for direct cou- ding to IEC TS 60079-27 ding to IEC 61158-2, i.e. it is suited for both pling of the shield and housing is imple- ● Junction box for DIN rail mounting PROFIBUS PA and FOUNDATION ™ mented. ● Aluminium housing fieldbus. Attention: Sufficient equipotential bonding ● For Ex applications: -25…+70 °C The housing is made of aluminium and fea- of the installation must be ensured. The de- (-13…+158 °F); for non-Ex applicati- ons: -40…+70 °C (-40…+158 °F) tures protection degree IP20. vice is connected via the bolt of the hou- sing to the system’s potentializer. ● Switch-in terminating resistor The junction box is equipped with a selec- ● Cable shielding: Capacitive or direct table bus terminating resistor. The accor- Accessories: To increase the degree of connection with housing potential ding switch is integrated in the housing on protection, there are various aluminium and selectable via switch the board. stainless steel housings with IP6x rating and various cable glands available on request.

120 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com FOUNDATION™ fieldbus und PROFIBUS-PA IP20 junction box, 12-port JRBS-40-12R/EX

Type JRBS-40-12R/EX Dimensions Ident-No. 6611462

Fieldbus standard IEC 61158-2 60

Operational voltage range: 9 … 32 VDC 31

Ex approval acc. to conformity certificate PTB 05 ATEX 2002 Entity Parameter ð Max.output voltage Uo 24 V ð 276 Max. output current Io 250 mA ð Max. output power Po 2560 mW ð 75,5 Max. input voltage Ui 24 V ð Max. input current Ii 250 mA ð Max. input power Pi 2560 mW FISCO parameter acc. to IEC TS 60079-27 Terminal Configuration ð Max.output voltage Uo 17.5 V ð Max. output current Io 380 mA ð 1 = – Max. output power Po 5320 mW 2 = + ð 3 = S Max. input voltage Ui 17.5 V 123 4 ð Max. input current Ii 380 mA ð Max. input power Pi 5320 mW External inductance/capacitance Li/Ci Trunk (In/Out): negligible / ð 5.00 nF per field current circuit: negligible / ð 0.33 nF æ field current circuits: negligible / ð 5.00 nF Device designation É II 2 G EEx ib IIC/IIB T4 É II 2(1) G EEx ia IIC/IIB T4 É II 2 G (2D) EEx ib [ibD] IIB T4 É II 2 (1) G (1D) EEx ia [iaD] IIB T4 FISCO / Entity field device Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X Device designation É II 3 G Ex nA II T4 É II 3 G Ex nA [nL] IIC/IIB T4 FNICO / Entity field device

Electrical connection removable terminal block, reverse polarity pro- tected, screw connection Terminal cross-section 2.5 mm2 Earthing bolt M5 x 1

Degree of protection IP20 Ambient temperature -25 …+ 70 °C Housing material aluminium Housing color black Dimensions 276 x 31 x 75.5 mm Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 121 /0309 FOUNDATION™ fi eldbus Cable technology – Basics

A two or three wire cable is prescribed by Cable parameters In the following table (Tab. 1) we compare IEC 61158-2 as the transmission medium Electrical data and permissible cable types the four standard cable types (at 25 °C): for transmission energy and data. are not prescribed. Cable parameters determine the achievable fi eldbus proper- ties such as the distances to be covered, number of connectable stations and electromagnetic compatibility.

Type A Type B Type C Type D (Reference)

Cable design Twisted One or Multiple twisted Multiple non- conductor pair multiple twisted pairs, not shielded twisted pairs conductor pairs, not shielded overall shield

Conductor cross-section (nominal) 0.8 mm2 0.32 mm2 0.13 mm2 1.25 mm2 (AWG 18) (AWG 22) (AWG 26) (AWG 16)

Loop impedance (DC current) 44 Ω/km 112 Ω/km 264 Ω/km 40 Ω/km

Wave resistance at 31.25 kHz 100 Ω ± 20 % 100 Ω ± 30 % not specifi ed not specifi ed

Wave attenuation at 39 kHz 3 dB/km 5 dB/km 8 dB/km 8 dB/km

Capacitive asymmetry 2 nF/km 2 nF/km not specifi ed not specifi ed

Group delay distortion (7,9...39 kHz) 1.7 µs/km not specifi ed not specifi ed not specifi ed

Degree of shield coverage 90 % not specifi ed not specifi ed not specifi ed

Recommended network expansion 1900 m 1200 m 400 m 200 m (incl. spur lines)

Tab. 1 Cable types to IEC 61158-2

Use of the individual cable types the types and limit values listed in Tab. 1, Maximum cable lengths, spur lines Cables conforming to the minimum but its particularly suitable for FOUN- Each fi eldbus installation must follow a requirements of type A, should be used DATION™ fi eldbus and PROFIBUS-PA defi ned set of rules, the “Network confi - for new installations. Cable types C fi eldbus systems. All of TURCK’s cables guration rules” (see IEC 61158-2, Chap. and D should only be used in so-called for fi eldbuses compliant with IEC 61158-2 11.2.2). The following limit values for “Retrofi t Applications” (usage of cable feature optimum quality even exceeding permissible attenuation, refl ection and already installed) involving only very limited type A requirements. distortion (rule 8), as well as the maximum network extensions. It is necessary to signal delay (rule 4) are listed (see Tab. 2). consider that in these cases the immunity to interference during data transmission may not meet the demands described in the standard.

Installations conform to the FISCO model Attenuation between any two bus interfaces (at 31.25 kHz) 10.5 dB Installations conform to the FISCO model are not subject to any technical safety limi- Attenuation distortion a (f = 39 kHz) – a (f = 7.8 kHz), 6 dB tations, if the limit values defi ned in Tab. 1 monotonic increasing with frequency are observed. Operation outside of these limit values is not generally excluded, but Refl ection factor at any point (7.8...39 kHz) 0.2 requires that each case is considered individually. Signal delay between any two bus interfaces 640 µs For example, the TURCK long distance “Cable FBY../LD” is not comparable with Tab. 2 Limit values for attenuation, distortion, refl ection and propagation delay

122 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com Topology An individual calculation of the four The basis for a network should be a tree If the limit values listed on the previous variables listed in Tab. 2 for all possible or linear topology or a combination of page are taken into consideration, various connections between two bus interfaces both. topologies such as star, tree or linear is associated with a very high effort. It is A network of this type consists of a main structures, as well as every cable is per- advisable to defi ne rules which set down cable (trunk line), a number of spur lines missible. an optimum basic topology. These rules (spur), connection elements (connectors should ensure that the limit values stated or junction boxes) and a terminating resis- cannot be exceeded. tor (see Fig. 1).

process device PC

control room

DPC

PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X

trunk terminating resistor field

spur spur

5

Fig. 1 Network topology

Maximum cable lengths The sum of main cable lengths and all Cable Max. cable lengths (incl. spur lines) spur line lengths results in the overall cable length, as already defi ned in Tab. 1 Type A 1900 m as the network expansion (see Tab. 3). Type B 1200 m

Type C 400 m

Type D 200 m

Tab. 3 Maximum cable lengths (main cable and spur lines)

Maximum spur cable lengths The maximum spur cable length depends Number of 1 device 2 devices 3 devices 4 devices on the number of fi eld devices per spur devices per spur line per spur line per spur line per spur line line and is listed in Tab. 4. 25...32 1 m 1 m 1 m 1 m

19...24 30 m 1 m 1 m 1 m

15...18 60 m 30 m 1 m 1 m Instrumentation to FISCO With FISCO conform EEx i instrumenta- 13...14 90 m 60 m 30 m 1 m tion, the maximum expansion of the trunk line in the explosion hazardous area is 1...12 120 m 90 m 60 m 30 m 1000 m. A maximum spur line length of 60 m may not be exceeded. Tab. 4 Maximum spur line lengths

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 123 /0309 ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Fieldbus cables for fieldbus systems According to IEC61158-2 CABLE FBY-.../SD-...M

G Fieldbus cables, type A, IEC 61158-2 G PVC cable jacket, colour blue, black, yellow or orange Jacket Braid G Oil, gas and sunlight resistant Shield G Temperature range -40... +75 °C G Cable conductor cross section: 18/7 BU 2 Foil Shield Data AWG (0.8 mm ) BN

Conductor cross-section Drain Wire BN

BU

BK Type CABLE FBY-.../SD-...M Ident-No. depending on length and colour, Ident-No. on request

Cable 18/7 AWG (0.8 mm2), stranded plain copper Cable jacket PVC (blue, black, yellow or orange) Shield aluminium foil, tinned copper braid and stran- 8 ded filler litz wire Max. tensile strength ð 90 N Bending radius minimum 5 x cable diameter Core insulation material PE-foam with PE-casing Core insulation colours BN, BU Core cross-section 2 x 0.8 mm2 DC resistance (loop) 43.6 ò/km Shield resistance nom. 9 ò/km Nom. Impedance 100 ± 20 (31.25 kBit/s) ò Working capacitance nom. 60 nF/km Capacitive earthing max. 2 nF/km Dampening max. 3.0 dB/km (with f = 39 kHz] Skew max. 1.7 µs/km (7.9 kHz -39 kHz) Inductivity nom. 0.7 mH/km

Rated voltage max. 300 V Ambient temperature At rest -40... + 75 °C In moving state -5... + 50 °C Approvals UL UV resistance according to UL 1581, section 1200 Resistance to oil according to ICEA S82-552 Flame retardant according to IEC 60332

124 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Fieldbus cables for fieldbus systems According to IEC61158-2 CABLE FBY-BK/LD-...M

G Long-distance fieldbus cables, type A, acc.IEC 61158-2 G PVC cable jacket, colour black Jacket Braid G Oil, gas and sunlight resistant Shield G Temperature range -40... +75 °C G Cable conductor cross section: 14/ BU 2 Foil Shield Data 7AWG (2.1 mm ) BN

Conductor cross-section Drain Wire BN

BU

BK Type CABLE FBY-BK/LD-...M Ident-No. depending on the length, Ident-No. on request

Cable 14/7 AWG (2.1 mm2), stranded plain copper Cable jacket PVC, black Shield aluminium foil, tinned copper braid and stran- ded filler litz wire 11,5 Max. tensile strength ð 90 N Bending radius minimum 5 x cable diameter Core insulation material PE-foam with PE-casing Core insulation colours BN, BU 5 Core cross-section 2 x 2.1 mm2 DC resistance (loop) 17.2 ò/km Shield resistance nom. 6 ò/km Nom. Impedance 100 ± 20 (31.25 kBit/s) ò Working capacitance nom. 60 nF/km Capacitive earthing max. 2 nF/km Dampening max. 3.0 dB/km (with f = 39 kHz] Skew max. 1.7 µs/km (7.9 kHz -39 kHz) Inductivity nom. 0.7 mH/km

Rated voltage max. 300 V Ambient temperature At rest -40... + 75 °C In moving state -5... + 50 °C Approvals UL UV resistance according to UL 1581, section 1200 Resistance to oil according to ICEA S82-552 Flame retardant according to IEC 60332

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 125 /0309 ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Fieldbus cables for fieldbus systems According to IEC61158-2 CABLE FBH-YE/SD-...M

G Fieldbus cables, type A, acc. to IEC 61158-2 G LSZH (low smoke zero halogen) mix Jacket Braid G PVC cable jacket, colour yellow Shield G Oil, gas and sunlight resistant

G BU Temperature range -40 ... +75 °C Foil Shield Data G BN Cable cross section: 18/7 AWG (0.8 mm2)

Drain Wire Conductor cross-section BN

BU

Type CABLE FBH-YE/SD-...M YE Ident-No. depending on the length, Ident-No. on request

Cable 18/7 AWG (0.8 mm2), stranded plain copper Cable jacket LSZH (low smoke zero halogen) mix, yellow Shield aluminium foil, tinned copper braid and stran- ded filler litz wire Max. tensile strength ð 90 N 8 Bending radius minimum 5 x cable diameter Core insulation material PE-foam with PE-casing Core insulation colours BN, BU Core cross-section 2 x 0.8 mm2 DC resistance (loop) 43.6 ò/km Shield resistance nom. 9 ò/km Nom. Impedance 100 ± 20 (31.25 kBit/s) ò Working capacitance nom. 60 nF/km Capacitive earthing max. 2 nF/km Dampening max. 3.0 dB/km (with f = 39 kHz] Skew max. 1.7 µs/km (7.9 kHz - 39 kHz) Inductivity nom. 0.7 mH/km

Rated voltage max. 300 V Ambient temperature At rest -40... + 75 °C In moving state -5... + 50 °C Approvals UL UV resistance according to UL 1581, section 1200 Resistance to oil according to ICEA S82-552 Flame retardant yes Halogen-free yes

126 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Fieldbus cables for fieldbus systems According to IEC61158-2 CABLE FBA-YE/SD...M

G Fieldbus cables, type A, acc. to IEC 61158-2 G PVC cable jacket, colour yellow JacketArmor Braid G Armouring Steel round wire Shield G Oil, gas and sunlight resistant G Temperature range -40 ... +75 °C BU Foil Shield Data G BN Cable conductor cross section: 18/7 AWG (0.8 mm2)

Drain Wire Conductor cross-section BN

BU

Type CABLE FBA-YE/SD...M Ident-No. depending on the length, Ident-No. on request

Cable 18/7 AWG (0.8 mm2), stranded plain copper Cable jacket PVC, yellow Shield aluminium foil, tinned copper braid and stran- ded filler litz wire ð Max. tensile strength 90 N 11,8 Core insulation material PE-foam with PE-casing Core insulation colours BN, BU 5 Core cross-section 2 x 0.8 mm2 DC resistance (loop) 43.6 ò/km Armouring zinc-plated steel round wire Diameter 0.9 mm Shield resistance nom. 9 ò/km Nom. Impedance 100 ± 20 (31.25 kBit/s) ò Working capacitance nom. 60 nF/km Capacitive earthing max. 2 nF/km Dampening max. 3.0 dB/km (with f = 39 kHz] Skew max. 1.7 µs/km (7.9 kHz - 39 kHz) Inductivity nom. 0.7 mH/km

Rated voltage max. 300 V Ambient temperature At rest -40... + 75 °C In moving state -5... + 50 °C Approvals UL UV resistance according to UL 1581, section 1200 Resistance to oil according to ICEA S82-552 Flame retardant according to IEC 60332

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 127 /0309 Fieldbus cables for fi eldbus systems According to IEC 61158-2 Cable 492A-...M, 492BA-...M

• Fieldbus cables, type A, IEC 61158-2 • Suitable for harsh environmental conditions • Aluminium armouring Aluminium Inner • Suitable for 7/8” male connector Jacket Armor Jacket • UV resistant Device GNYE • Temperature range -40...+75 °C Ground • Cable conductor cross section 18/7 BU Foil Shield Data AWG (0.8 mm2) BN • Cable 492A with yellow cable jacket Drain Wire • Cable 492BA with blue cable jacket

Conductor cross-section

GNYE BU Type designation and Ident-No. BN Type Cable 492A-...M depending on the length, Ident-No. on request YE Type Cable 492BA-...M depending on the length, Ident-No. on request

Cable 18/7 AWG (0.8 mm²), stranded bare copper Insulation XLPE foam Color code A-conductor: brown; B-conductor: blue; ground: green/yellow Shield aluminium foil, metallic external surface with contact to the tinned copper braid and 12,7 stranded drain wire Jacket Polyvinyl chloride (PVC) Armoured Aluminium Overall diameter approx. 12.7 mm

Physical properties/ fi re resistance Minimum bending radius once: 40 mm/repeated: 60 mm Ambient temperature At rest -40 ... +75 °C In moving state -5 ... +50 °C UV resistance conform to UL 1581, section 1200 Flame retardant PLTC cable, fl ame resistant conform to CSA- FT4

Electrical properties at 20° C Inductance max. 0.44 mH/km Total capacitance max. 52.43 nF/km Impedance (at 31.25 kBit/s) 100 Ω /± 20 Ω DC resistance 2 x 21.3 Ω/Km High voltage test (conductor/conductor and conductor/shield) 1500 V Operational voltage max. 300 V

128 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com Fieldbus cables for fi eldbus systems According to IEC 61158-2 Cable FB4910-BK...M

• Fieldbus cables, type A, IEC 61158-2 • Special cable for FOUNDATION fi eldbus™ • Area of application: Jacket – offshore – extremely cold regions Device GN Ground – tropical regions BU • Resistant to oil, gases and Foil Shield Data BN sunlight • Excellent tensile strength and Drain Wire abrasion resistance • Highly fl ame resistant conform to IEEE 1202/FT4 and IEC 332-3, category A • Temperature range -50..+90 °C • Cable conductor cross section 18/7 AWG (0.8 mm2) Type Cable FB4910-BK-...M • Approvals Ident-No. depending on the length, Ident-No. on request UL 1309 (Marine Shipboard) and CSA 222 No. 245 Cable 18/7 AWG (0.8 mm²), stranded bare copper Insulation XLPE foam Color code A-conductor: brown; B-conductor: blue; Conductor cross-section ground: green Shield aluminium foil, metallic external surface GN with contact to the tinned copper braid and BU stranded drain wire BN 5 Jacket TPE BK Overall diameter approx. 8.9 mm

Physical properties/fi re resistance Minimum bending radius once: 40 mm/repeated: 60 mm Ambient temperature At rest -40 ... +90 °C In moving state -50 ... +50 °C UV resistance conform to UL 1581, section 1200 8,9 Resistance to oils conform to ICEA S61-402 Flame resistance conform to IEC 60332

Electrical properties at 20° C Inductance max. 0.44 mH/km Total capacitance max. 52.43 nF/km Impedance (at 31.25 kBit/s) 100 Ω /± 20 Ω DC resistance 2 x 21.3 Ω/Km High voltage test (conductor/conductor and conductor/shield) 1500 V Operational voltage max. 300 V

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 129 /0309 JUST IN 1. TIME! Workday

Ideally the length of the cord set is adjusted according to the requirements of the plant. For this reason TURCK now offers a Just-in-Time-delivery service (JIT) for premoulded cables.

The new JIT-5D-Programme for perfect connections: Ordering until • Just-in-Time delivery 12 p.m. within 5 days only • Free choice of cable length • Premoulded fi eldbus and power cables • High fl exibility with respect to planning and mounting Production of your application • High cost savings

Delivery 3 workdays after ordering

Arrival at the customer

* valid for deliveries 5. within the European Union (EU) Workday*

130 /0309 Hans Turck GmbH & Co.Co.KGKG • WitzlebenstraßeWitzlebenstraße 7 • 4547245472 MüMülheim/Ruhrlheim/Ruhr • Germany • Tel.Tel. +49 ((0)2080)208 4952-0 • FFaxax +49 ((0)2080)208 4952-264 • [email protected]@turck.com • www.turck.comwww.turck.com M12 x 1 Type designation cable type FBY49x, x = colour (BU, BK, OG, YE), *M = variable length in m m RSCV w WSCV w RKCV v WKCV v

33,5 one-sided » ø 7,6 M12 x 1 » ø 7,6 M12 x 1 33,5 premoulded ø 15 ø 15 38,5 32,0

55,2 48,5 M12 x 1 ø 15 M12 x 1 ø 15 RSCV RSCV-FBY49x- RSCV-RSCV- — RSCV-RKCV- — w *M/5D FBY49x-*M/5D FBY49x-*M/5D WSCV WSCV-FBY49x- — WSCV-WSCV- — WSCV-WKCV- w *M/5D FBY49x-*M/5D FBY49x-*M/5D RKCV RKCV-FBY49x- — — RKCV-RKCV- — v *M/5D FBY49x-*M/5D WKCV WKCV-FBY49x- — — — WKCV-WKCV- v *M/5D FBY49x-*M/5D

w v Pin confi guration: 2 2 Malew 1 = – (BU) 1 = – (BU) 3 1 2 = + (BN) 1 3 2 = + (BN) Female v 3 = S (Shield) 3 = S (Shield) 4 4 = n.c. 4 4 = n.c.

7/8“ Type designation cable type FBY49x, x = colour (BU, BK, OG, YE), *M = variable length in m m RSV w WSV w RKV v WKV v

7/8-16UN 51,25 7/8-16UN 51,25 one-sided ø 15,5 ø 7,3 41,0 ø 15,5 ø 7,3 41,0 ø 8,5 ø 8,5 ø 17,5 ø 17,5 premoulded ø 26,0 ø 26,0 43,5 40,0 34,0 30,55

36,0 18,0 29,0 7/8-16UN 54,0 7/8-16UN 50,5 ø 26,0 ø 26,0

RSV RSV-FBY49x- RSV-RSV-FBY49x- — RSV-RKV-FBY49x- — 6 w *M/5D *M/5D *M/5D WSV WSV-FBY49x- — WSV-WSV-FBY49x- — WSV-WKV-FBY49x- w *M/5D *M/5D *M/5D RKV RKV-FBY49x- — — RKV-RKV-FBY49x- — v *M/5D *M/5D WKV WKV-FBY49x- — — — WKV-WKV-FBY49x- v *M/5D *M/5D

Pin confi guration: w v Malew 1 3 1 = – (BU) 3 1 1 = – (BU) v 2 = + (BN) 2 = + (BN) Female 2 4 3 = S (Shield) 4 2 3 = S (Shield) 4 = n.c. 4 = n.c.

Connectors Cable layout Coupling nut: Stainless steel Outer jacket: Polyvinyl chloride (PVC) Contacts: Gold-plated Core isolation: PE-foam with PR-jacket Grip: PA Colour code: BN, BU Protection degree: IP67 Insolation: Extruded special compound Shield: One side plastic coated with aluminium strip, metal exterior with contact to tin-plated copper braid and stranded drain wire Diameter: ≤ 8 mm Conductor: 18/7 AWG (0.8 mm2), stranded blank copper

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 131 /0309 7/8“ Type designation armoured cable type 492A, 492 BA, *M = variable length in m m RSV w RKV v

one-sided ø 20,5 ø 20,5 7/8-16UN premoulded ø 7,3 7/8-16UN ø 7,3 ø 17,5 ø 27,0 ø 17,5 ø 27,0

36,0 29,0 68,5 65,0

RSV RSV492A-*M — RSV-RKV492A-*M w RSV492BA-*M RSV-RKV492BA-*M RKV RKV492A-*M —— v RKV492BA-*M

Pin confi guration: w v Malew 1 3 1 = – (BU) 3 1 1 = – (BU) v 2 = + (BN) 2 = + (BN) Female 2 4 3 = S (Shield) 4 2 3 = S (Shield) 4 = Ground (GNYE) 4 = Ground (GNYE)

Note: This fi eld-wireable fi eldbus cable is not included in the JIT-5D-Programme.

132 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 6

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 133 /0309 ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Flange connector RSFV49

● Version: male 7/8" connector ● 1/2-14 NPT screw-in thread ● Stainless steel flange housing

26,5 ● 4-pole, solderable 10 7,5 ● For FOUNDATION™ fieldbus appli- cations ø 25,4

FOUNDATION™ fieldbus connection 1/2-14 NPT 26 7/8-16UN

1 = – 1 3 2 = + 2 4 3 = shield 4 = n.c.

Type RSFV49 Ident-No. 6602199

Connector Male flange connector, 7/8'' Polarity 4-pole Contacts metal, CuZn, gold-plated Contact carriers plastic, PUR, black Screw-in thread seal NBR Flange housing stainless steel, 1.4401 (316) Degree of protection IP67, only with screws tightened Screw-in thread 1/2-14 NPT Mechanical lifespan min. 100 Contact durability Pollution degree 3

Rated voltage max. 600 V Insulation resistance ï 109 ò Ampacity 9 A Forward resistance ð 5 mò Ambient temperature Connector -40 … + 105 °C

134 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Flange connector RKFV49

● Version: female 7/8" connector ● 1/2-14 NPT screw-in thread ● Stainless steel flange housing

● 19,5 4-pole, solderable 10 ● For FOUNDATION™ fieldbus appli- cations ø 25,4

FOUNDATION™ fieldbus connection 7/8-16UN 1/2-14 NPT 26 v

1 = – 3 1 2 = + 4 2 3 = shield 4 = n.c.

Type RKFV49 Ident-No. 6602198

Connector female flange connector, 7/8'' Polarity 4-pole Contacts metal, CuZn, gold-plated Contact carriers plastic, PUR, black Screw-in thread seal NBR Flange housing stainless steel, 1.4401 (316) Degree of protection IP67, only with screws tightened Screw-in thread 1/2-14 NPT Mechanical lifespan min. 100 Contact durability Pollution degree 3

Rated voltage max. 600 V Insulation resistance ï 109 ò Ampacity 9 A Forward resistance ð 5 mò Ambient temperature Connector -40 °C

7

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 135 /0309 ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Flange connector RSFV49-0,3M/14,5/C1117

● Version: male 7/8" connector ● 1/2-14 NPT screw-in thread ● Stainless steel flange housing ● 4-pole, litz wire length 0.3 m 33 16 7,5 ● For FOUNDATION™ fieldbus appli- cations 25,4 Pin configuration 26 1/2-14 NPT 7/8" UNC

1 = BU 1 3 2 = BN 2 4 3 = GY 4 = GNYE

Type RSFV49-0,3M/14,5/C1117 Ident-No. 6603396 FOUNDATION™ fieldbus connection Connector Male flange connector, 7/8'', with litz wire Polarity 4-pole Contacts metal, CuZn, gold-plated Contact carriers plastic, PUR, black 1 = – 1 3 Screw-in thread seal NBR 2 = + 2 4 3 = shield Flange housing stainless steel, 1.4401 (316) 4 = n.c. Degree of protection IP67, only with screws tightened Screw-in thread 1/2-14 NPT Mechanical lifespan min. 100 Contact durability Pollution degree 3

Litz wire length 0.3 m Core insulation material PVC Core insulation colours BU, BN, GY, GNYE Core cross-section 4 x 0.8 mm2

Rated voltage max. 600 V Insulation resistance ï 109 ò Ampacity 9 A Forward resistance ð 5 mò Ambient temperature Connector -40 … + 105 °C

136 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Flange connector RKFV49-0,3M/14,5

● Version: female 7/8" connector ● 1/2-14 NPT screw-in thread ● Stainless steel flange housing

25,5 ● 4-pole, litz wire length 0.3 m 16 ● For FOUNDATION™ fieldbus appli- cations ø 25,4

Pin configuration 7/8" UNC 1/2-14 NPT 26 v

1 = BU 3 1 2 = BN 4 2 3 = GY 4 = GNYE

Type RKFV49-0,3M/14,5 Ident-No. 6602475

Connector female flange connector, 7/8'', with litz wire FOUNDATION™ fieldbus connection Polarity 4-pole Contacts metal, CuZn, gold-plated v Contact carriers plastic, PUR, black 1 = – 3 1 Screw-in thread seal NBR 2 = + 4 2 3 = shield Flange housing stainless steel, 1.4401 (316) 4 = n.c. Degree of protection IP67, only with screws tightened Screw-in thread 1/2-14 NPT Mechanical lifespan min. 100 Contact durability Pollution degree 3

Litz wire length 0.3 m Core insulation material PVC Core insulation colours BU, BN, GY, GNYE Core cross-section 4 x 0.8 mm2

Rated voltage max. 600 V Insulation resistance ï 109 ò Ampacity 9 A Forward resistance ð 5 mò Ambient temperature Connector -40 … + 105 °C 7

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 137 /0309 ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Flange connector RSFV49-0,3M/M20/C1117

● Version: male 7/8" connector ● M20 x 1.5 screw-in thread ● Stainless steel flange housing

30 ● 4-pole, litz wire length 0.3 m 10 8 ● For FOUNDATION™ fieldbus appli- cations 25,4

M20 x 1,5 Pin configuration 26 7/8" UNC

1 = BU 1 3 2 = BN 2 4 3 = GY 4 = GNYE

Type RSFV49-0,3M/M20/C1117 Ident-No. 6603583 FOUNDATION™ fieldbus connection Connector Male flange connector, 7/8'', with litz wire Polarity 4-pole Contacts metal, CuZn, gold-plated Contact carriers plastic, PUR, black 1 = – 1 3 Screw-in thread seal NBR 2 = + 2 4 3 = shield Flange housing stainless steel, 1.4401 (316) 4 = n.c. Degree of protection IP67, only with screws tightened Screw-in thread M20 x 1,5 Mechanical lifespan min. 100 Contact durability Pollution degree 3

Litz wire length 0.3 m Core insulation material PVC Core insulation colours BU, BN, GY, GNYE Core cross-section 4 x 0.8 mm2

Rated voltage max. 600 V Insulation resistance ï 109 ò Ampacity 9 A Forward resistance ð 5 mò Ambient temperature Connector -40 … + 105 °C

138 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Flange connector RKFV49-0,3M/M20

● Version: female 7/8" connector ● M20 x 1.5 screw-in thread ● Stainless steel flange housing ● 4-pole, litz wire length 0.3 m 19,5 10 ● For FOUNDATION™ fieldbus appli- cations ø 25,4 Pin configuration M20 x 1,5 7/8" UNC 26 v

1 = BU 3 1 2 = BN 4 2 3 = GY 4 = GNYE

Type RKFV49-0,3M/M20 Ident-No. 6603584

Connector female flange connector, 7/8'', with litz wire FOUNDATION™ fieldbus connection Polarity 4-pole Contacts metal, CuZn, gold-plated v Contact carriers plastic, PUR, black 1 = – 3 1 Screw-in thread seal NBR 2 = + 4 2 3 = shield Flange housing stainless steel, 1.4401 (316) 4 = n.c. Degree of protection IP67, only with screws tightened Screw-in thread M20 x 1,5 Mechanical lifespan min. 100 Contact durability Pollution degree 3

Litz wire length 0.3 m Core insulation material PVC Core insulation colours BU, BN, GY, GNYE Core cross-section 4 x 0.8 mm2

Rated voltage max. 600 V Insulation resistance ï 109 ò Ampacity 9 A Forward resistance ð 5 mò Ambient temperature Connector -40 … + 105 °C 7

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 139 /0309 ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Flange connector FSV49

● Version: M12 connector ● PG 9 screw-in thread ● Stainless steel flange housing ● 4-pole, solderable ● For use in Foundation™ fieldbus PG 9 18 M12 x 1 and PROFIBUS-PA applications

6 FOUNDATION™ fieldbus connection 19

2 1 = – 2 = + 3 1 3 = shield 4 4 = n.c.

Type FSV49 Ident-No. 6604378 PROFIBUS-PA connection Connector Male flange connector, M12 x 1 Polarity 4-pole Contacts metal, CuZn, gold-plated Contact carriers plastic, PA, black 2 1 = + 3 1 2 = ground Screw-in thread seal plastic 3 = – Flange housing stainless steel, 1.4401 (316) 4 4 = shield Degree of protection IP67, only with screws tightened Screw-in thread PG 9 Mechanical lifespan min. 100 Contact durability Pollution degree 3

Rated voltage max. 250 V Insulation resistance ï 109 ò Ampacity 4 A Forward resistance ð 5 mò Ambient temperature Connector -40 … + 90 °C

140 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Flange connector FKV49

● Version: female M12 connector ● PG 9 screw-in thread ● Stainless steel flange housing ● 4-pole, solderable ● For use in Foundation™ fieldbus PG 9 18 M12 x 1 and PROFIBUS-PA applications ø 13,5

7 FOUNDATION™ fieldbus connection 21 v

2 1 = – 2 = + 1 3 3 = shield 4 4 = ground

Type FKV49 Ident-No. 6603426 PROFIBUS-PA connection Connector female flange connector, M12 x 1 Polarity 4-pole v Contacts metal, CuZn, gold-plated Contact carriers plastic, PA, black 2 1 = + 2 = ground Screw-in thread seal plastic 1 3 3 = – Flange housing stainless steel, 1.4401 (316) 4 4 = shield Degree of protection IP67, only with screws tightened Screw-in thread PG 9 Mechanical lifespan min. 100 Contact durability Pollution degree 3

Rated voltage max. 250 V Insulation resistance ï 109 ò Ampacity 4 A Forward resistance ð 5 mò Ambient temperature Connector -40 … + 90 °C

7

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 141 /0309 ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Flange connector FSV49-0,3M/14,5/C1117

● Version: M12 connector ● 1/2-14 NPT screw-in thread ● Stainless steel flange housing

31 ● 4-pole, litz wire length 0.3 m 15 ● For FOUNDATION™ fieldbus appli- cations

Pin configuration 1/2-14 NPT 26 M12 x 1

2 1 = BU 13 2 = BN 3 = GY 4 4 = GNYE

Type FSV49-0,3M/14,5/C1117 Ident-No. 6602107 FOUNDATION™ fieldbus connection Connector Male flange connector, M12 x 1, with litz wire Polarity 4-pole Contacts metal, CuZn, gold-plated 2 1 = – 2 = + Contact carriers plastic, PA, black 3 1 3 = shield Screw-in thread seal plastic 4 4 = n.c. Flange housing stainless steel, 1.4401 (316) Degree of protection IP67, only with screws tightened Screw-in thread 1/2-14 NPT Mechanical lifespan min. 100 Contact durability Pollution degree 3

Litz wire length 0.3 m Core insulation material PVC Core insulation colours BU, BN, GY, GNYE Core cross-section 4 x 0.8 mm2

Rated voltage max. 600 V Insulation resistance ï 109 ò Ampacity 9 A Forward resistance ð 5 mò Ambient temperature Connector -40 … + 105 °C

142 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Flange connector FKV49-0,3M/14,5/C1117

● Version: female M12 connector ● 1/2-14 NPT screw-in thread ● Stainless steel flange housing ● 4-pole, litz wire length 0.3 m 30 14 ● For FOUNDATION™ fieldbus appli- cations

M12 x 1 Pin configuration

1/2-14 NPT 26 v

2 1 = BU 1 3 2 = BN 3 = GY 4 4 = GNYE

Type FKV49-0,3M/14,5/C1117 Ident-No. 6603298 FOUNDATION™ fieldbus connection Connector female flange connector, M12 x 1, with litz wire v Polarity 4-pole Contacts metal, CuZn, gold-plated 2 1 = – 2 = + Contact carriers plastic, PA, black 1 3 3 = shield Screw-in thread seal plastic 4 4 = n.c. Flange housing stainless steel, 1.4401 (316) Degree of protection IP67, only with screws tightened Screw-in thread 1/2-14 NPT Mechanical lifespan min. 100 Contact durability Pollution degree 3

Litz wire length 0.3 m Core insulation material PVC Core insulation colours BU, BN, GY, GNYE Core cross-section 4 x 0.8 mm2

Rated voltage max. 300 V Insulation resistance ï 109 ò Ampacity 4 A Forward resistance ð 5 mò Ambient temperature Connector -40 … + 105 °C 7

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 143 /0309 ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Flange connector FSV49-0,3M/M20/C1117

● Version: M12 connector ● M20 x 1.5 screw-in thread ● Stainless steel flange housing

25 ● 4-pole, litz wire length 0.3 m 15 ● For FOUNDATION™ fieldbus appli- cations

Pin configuration M20 x 1,5 26 M12 x 1

2 1 = BU 13 2 = BN 3 = GY 4 4 = GNYE

Type FSV49-0,3M/M20/C1117 Ident-No. 6603682 FOUNDATION™ fieldbus connection Connector Male flange connector, M12 x 1, with litz wire Polarity 4-pole Contacts metal, CuZn, gold-plated 2 1 = – 2 = + Contact carriers plastic, PA, black 3 1 3 = shield Screw-in thread seal plastic 4 4 = n.c. Flange housing stainless steel, 1.4401 (316) Degree of protection IP67, only with screws tightened Screw-in thread M20 x 1,5 Mechanical lifespan min. 100 Contact durability Pollution degree 3

Litz wire length 0.3 m Core insulation material PVC Core insulation colours BU, BN, GY, GNYE Core cross-section 4 x 0.8 mm2

Rated voltage max. 600 V Insulation resistance ï 109 ò Ampacity 9 A Forward resistance ð 5 mò Ambient temperature Connector -40 … + 105 °C

144 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Flange connector FKV49-0,3M/M20/C1117

● Version: female M12 connector ● M20 x 1.5 screw-in thread ● Stainless steel flange housing

24 ● 4-pole, litz wire length 0.3 m 14 ● For FOUNDATION™ fieldbus appli- cations

M12 x 1 Pin configuration M20 x 1,5 26 v

2 1 = BU 1 3 2 = BN 3 = GY 4 4 = GNYE

Type FKV49-0,3M/M20/C1117 Ident-No. 6603683 FOUNDATION™ fieldbus connection Connector female flange connector, M12 x 1, with litz wire v Polarity 4-pole Contacts metal, CuZn, gold-plated 2 1 = – 2 = + Contact carriers plastic, PA, black 1 3 3 = shield Screw-in thread seal plastic 4 4 = n.c. Flange housing stainless steel, 1.4401 (316) Degree of protection IP67, only with screws tightened Screw-in thread M20 x 1,5 Mechanical lifespan min. 100 Contact durability Pollution degree 3

Litz wire length 0.3 m Core insulation material PVC Core insulation colours BU, BN, GY, GNYE Core cross-section 4 x 0.8 mm2

Rated voltage max. 300 V Insulation resistance ï 109 ò Ampacity 4 A Forward resistance ð 5 mò Ambient temperature Connector -40 … + 105 °C 7

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 145 /0309 ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Field wireable connectors BS4140-0/9

● Version: Connector ● Round connector 7/8" ● Field-wireable ● Screw/terminal connection ø 6...8 84 ● 4-pole, straight anodised aluminium coupling nut ø 28 ● Cable exit 6 … 8 mm ● For use in PROFIBUS-PA and 7/8-16UN FOUNDATION™ fieldbus applicati- ons and and as auxiliary supply for DeviceNet™ slaves

PROFIBUS-PA connection

Type BS4140-0/9 Ident-No. 6914550 1 = + 1 3 2 = n.c. 2 4 3 = – Connector field-wireable male connector, 7/8'', straight 4 = shield Polarity 4-pole Contacts metal, CuZn, gold-plated Contact carriers plastic, TPU, black Grip plastic, PA, black Coupling nut/screw metal, Al, anodized FOUNDATION™ fieldbus connection Seal plastic, NBR Screw-in thread seal plastic, NBR Degree of protection IP67, only with screws tightened 1 = – External diameter of the cable 6 … 8 mm 1 3 2 = + 2 2 4 3 = shield Core cross-section/Clamping ability max. 1 mm 4 = n.c. Screw-in thread PG 9 Connection mode Screw terminals Pollution degree 3

Rated voltage max. 250 V Insulation resistance ï 109 ò Ampacity 9 A Forward resistance ð 5 mò Ambient temperature Connector -40 … + 90 °C

146 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Field wireable connectors BK4140-0/9

● Version: female connector ● Round connector 7/8" ● Field-wireable ● Screw/terminal connection

ø 6...8 ● 4-pole, straight anodised aluminium 85 coupling nut ● Cable exit 6 … 8 mm ø 27 ● For use in PROFIBUS-PA and FOUNDATION™ fieldbus applicati- 7/8-16UN onsand and as auxiliary supply for DeviceNet™ slaves

PROFIBUS-PA connection

v Type BK4140-0/9 Ident-No. 6914551 1 = + 3 1 2 = n.c. 4 2 3 = – Connector field-wireable female connector, 7/8'', 4 = shield straight Polarity 4-pole Contacts metal, CuZn, gold-plated Contact carriers plastic, TPU, black Grip plastic, PA, black FOUNDATION™ fieldbus connection Coupling nut/screw metal, Al, anodized Seal plastic, NBR v Screw-in thread seal plastic, NBR 1 = – Degree of protection IP67, only with screws tightened 3 1 2 = + 4 2 3 = shield External diameter of the cable 6 … 8 mm 4 = n.c. Core cross-section/Clamping ability max. 1 mm2 Screw-in thread PG 9 Connection mode Screw terminals Pollution degree 3 Voltage supply Rated voltage max. 250 V Insulation resistance ï 109 ò v Ampacity 9 A 1 = RD (Aux +) Forward resistance ð 5 mò 3 1 2 = GN (E +) 4 2 3 = WH (E –) Ambient temperature Connector -40 … + 90 °C 4 = BK (Aux –)

8

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 147 /0309 ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Field wireable connectors BSV4140-0/9

● Version: Connector ● Round connector 7/8" ● Field-wireable ● Screw/terminal connection ø 6...8 84 ● 4-pole, straight, stainless steel cou- pling nut ø 28 ● Cable exit 6 … 8 mm ● For use in PROFIBUS-PA and 7/8-16UN FOUNDATION™ fieldbus applicati- ons

PROFIBUS-PA connection

Type BSV4140-0/9 1 = + 1 3 Ident-No. 6914542 2 = n.c. 2 4 3 = – 4 = shield Connector field-wireable male connector, 7/8'', straight Polarity 4-pole Contacts metal, CuZn, gold-plated Contact carriers plastic, TPU, black Grip plastic, PA, black FOUNDATION™ fieldbus connection Coupling nut/screw stainless steel, 1.4404 Seal plastic, NBR Screw-in thread seal plastic, NBR 1 = – Degree of protection IP67, only with screws tightened 1 3 2 = + 2 4 3 = shield External diameter of the cable 6 … 8 mm 4 = n.c. Core cross-section/Clamping ability max. 1 mm2 Screw-in thread PG 9 Connection mode Screw terminals Pollution degree 3

Rated voltage max. 250 V Insulation resistance ï 109 ò Ampacity 9 A Forward resistance ð 5 mò Ambient temperature Connector -40 … + 90 °C

148 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Field wireable connectors BKV4140-0/9

● Version: female connector ● Round connector 7/8" ● Field-wireable ● Screw/terminal connection ø 6...8 ● 4-pole, straight, stainless steel cou- 80 pling nut

ø 28 ● Cable exit 6 … 8 mm ● For use in PROFIBUS-PA and 7/8-16UN FOUNDATION™ fieldbus applicati- ons

PROFIBUS-PA connection

v

Type BKV4140-0/9 1 = + 3 1 Ident-No. 6914543 2 = n.c. 4 2 3 = – 4 = shield Connector field-wireable female connector, 7/8'', straight Polarity 4-pole Contacts metal, CuZn, gold-plated Contact carriers plastic, TPU, black FOUNDATION™ fieldbus connection Grip plastic, PA, black Coupling nut/screw stainless steel, 1.4404 v Seal plastic, NBR 1 = – Screw-in thread seal plastic, NBR 3 1 2 = + 4 2 3 = shield Degree of protection IP67, only with screws tightened 4 = n.c. External diameter of the cable 6 … 8 mm Core cross-section/Clamping ability max. 1 mm2 Screw-in thread PG 9 Connection mode Screw terminals Pollution degree 3

Rated voltage max. 240 V Insulation resistance ï 109 ò Ampacity 9 A Forward resistance ð 5 mò Ambient temperature Connector -40 … + 90 °C

8

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 149 /0309 ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Field wireable connectors BSV4140-0/13.5

● Version: Connector ● Round connector 7/8" ● Field-wireable ● Screw/terminal connection ø 10...12 84 ● 4-pole, straight, stainless steel cou- pling nut ø 28 ● Cable exit 10 … 12 mm

7/8-16UN ● For use in PROFIBUS-PA and FOUNDATION™ fieldbus applicati- ons

PROFIBUS-PA connection

Type BSV4140-0/13.5 1 = + 1 3 Ident-No. 6914562 2 = n.c. 2 4 3 = – 4 = shield Connection mode Screw terminals Junction box field-wireable male connector, 7/8'', straight Polarity 4-pole Grip plastic, PA, black Contact carriers plastic, TPU, black FOUNDATION™ fieldbus connection Contacts metal, CuZn, gold-plated Coupling nut/screw stainless steel, 1.4404 Seal plastic, NBR 1 = – 1 3 2 = + Degree of protection IP67, only with screws tightened 2 4 3 = shield 4 = n.c. Pollution degree 3

External diameter of cable max. 12 mm

Rated voltage max. 250 V Ampacity 9 A Forward resistance ð 5 mò Insulation resistance ï 109 ò Ambient temperature junction -40 … + 90 °C

150 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Field wireable connectors BKV4140-0/13.5

● Version: female connector ● Round connector 7/8" ● Field-wireable

ø 10...12 ● Screw/terminal connection 80 ● 4-pole, straight, stainless steel cou- pling nut ø 28 ● Cable exit 10 … 12 mm 7/8-16UN ● For use in PROFIBUS-PA and FOUNDATION™ fieldbus applicati- ons

PROFIBUS-PA connection

v

Type BKV4140-0/13.5 1 = + 3 1 Ident-No. 6914563 2 = n.c. 4 2 3 = – 4 = shield Connector field-wireable female connector, 7/8'', straight Polarity 4-pole Contacts metal, CuZn, gold-plated Contact carriers plastic, TPU, black FOUNDATION™ fieldbus connection Grip plastic, PA, black Coupling nut/screw stainless steel, 1.4404 v Seal plastic, NBR 1 = – Screw-in thread seal plastic, NBR 3 1 2 = + 4 2 3 = shield Degree of protection IP67, only with screws tightened 4 = n.c. External diameter of the cable 10 … 12 mm Core cross-section/Clamping ability max. 1 mm2 Screw-in thread PG 13,5 Connection mode Screw terminals Pollution degree 3

Rated voltage max. 240 V Insulation resistance ï 109 ò Ampacity 9 A Forward resistance ð 5 mò Ambient temperature Connector -40 … + 90 °C

8

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 151 /0309 ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Field wireable connectors BSV4140-0/16

● Version: Connector ● Round connector 7/8" ● Field-wireable ● Screw/terminal connection ø 12...14 88 ● 4-pole, straight, stainless steel cou- pling nut ø 28 ● Cable exit 12 … 14 mm

● 7/8-16UN For use in PROFIBUS-PA and FOUNDATION™ fieldbus applicati- ons

PROFIBUS-PA connection

Type BSV4140-0/16 1 = + 1 3 Ident-No. 6914541 2 = n.c. 2 4 3 = – 4 = shield Connector field-wireable male connector, 7/8'', straight Polarity 4-pole Contacts metal, CuZn, gold-plated Contact carriers plastic, TPU, black Grip plastic, PA, black FOUNDATION™ fieldbus connection Coupling nut/screw stainless steel, 1.4404 Seal plastic, NBR Screw-in thread seal plastic, NBR 1 = – Degree of protection IP67, only with screws tightened 1 3 2 = + 2 4 3 = shield External diameter of the cable 12 … 14 mm 4 = n.c. Core cross-section/Clamping ability max. 1 mm2 Screw-in thread PG 16 Connection mode Screw terminals Pollution degree 3

Rated voltage max. 250 V Insulation resistance ï 109 ò Ampacity 9 A Forward resistance ð 5 mò Ambient temperature Connector -40 … + 90 °C

152 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Field wireable connectors BKV4140-0/16

● Version: female connector ● Round connector 7/8" ● Field-wireable ● Screw/terminal connection ø 12...14 85 ● 4-pole, straight, stainless steel cou- pling nut ø 28 ● Cable exit 12 … 14 mm

● 7/8-16UN For use in PROFIBUS-PA and FOUNDATION™ fieldbus applicati- ons

PROFIBUS-PA connection

v

Type BKV4140-0/16 1 = + 3 1 Ident-No. 6914544 2 = n.c. 4 2 3 = – 4 = shield Connector field-wireable female connector, 7/8'', straight Polarity 4-pole Contacts metal, CuZn, gold-plated Contact carriers plastic, TPU, black FOUNDATION™ fieldbus connection Grip plastic, PA, black Coupling nut/screw stainless steel, 1.4404 v Seal plastic, NBR 1 = – Screw-in thread seal plastic, NBR 3 1 2 = + 4 2 3 = shield Degree of protection IP67, only with screws tightened 4 = n.c. External diameter of the cable 12 … 14 mm Core cross-section/Clamping ability max. 1 mm2 Screw-in thread PG 16 Connection mode Screw terminals Pollution degree 3

Rated voltage max. 240 V Insulation resistance ï 109 ò Ampacity 9 A Forward resistance ð 5 mò Ambient temperature Connector -40 … + 90 °C

8

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 153 /0309 ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Field wireable connectors BSV8140-0/9

● Version: M12 connector ● Field-wireable ● 4-pole, straight, stainless steel cou- pling nut ø 4...8 ● Cable exit 4.0 … 8.0 mm 60 ● For use in PROFIBUS-PA and ø 21 FOUNDATION™ fieldbus applicati- ons

M12 x 1 19 PROFIBUS-PA connection

2 1 = + 3 1 2 = n.c. 3 = – 4 4 = shield Type BSV8140-0/9 Ident-No. 6914537

Connector field-wireable male connector, M12 x 1, straight FOUNDATION™ fieldbus connection Polarity 4-pole Contacts metal, CuZn,CuSnZn, Optalloy coated Contact carriers plastic, PA, black 2 1 = – Grip plastic, PA, black 2 = + 3 1 Coupling nut/screw stainless steel, 1.4404 3 = shield 4 = n.c. Seal plastic, FKM/FPM 4 Screw-in thread seal plastic, NBR Degree of protection IP67, only with screws tightened External diameter of the cable 4 … 8 mm Core cross-section/Clamping ability 0.14… 0.75 mm2 Screw-in thread PG 9 Connection mode Screw terminals Pollution degree 3

Rated voltage max. 250 V Insulation resistance ï 109 ò Ampacity 4 A Forward resistance ð 5 mò Ambient temperature Connector -25 … + 90 °C

154 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Field wireable connectors BKV8140-0/9

● Version: female M12 connector ● Field-wireable ● 4-pole, straight, stainless steel cou- pling nut

ø 4...8 ● Cable exit 4.0 … 8.0 mm 55 ● For use in PROFIBUS-PA and FOUNDATION™ fieldbus applicati- ø 21 ons

M12 x 1 19 PROFIBUS-PA connection

v

2 1 = + 2 = n.c. 1 3 3 = – 4 4 = shield Type BKV8140-0/9 Ident-No. 6914538

Connector field-wireable female connector, M12 x 1, straight FOUNDATION™ fieldbus connection Polarity 4-pole Contacts metal, CuZn,CuSnZn, Optalloy coated v Contact carriers plastic, PA, black 2 1 = – Grip plastic, PA, black 2 = + Coupling nut/screw stainless steel, 1.4404 1 3 3 = shield 4 = n.c. Seal plastic, FKM/FPM 4 Screw-in thread seal plastic, NBR Degree of protection IP67, only with screws tightened External diameter of the cable 4 … 8 mm Core cross-section/Clamping ability 0.14… 0.75 mm2 Screw-in thread PG 9 Connection mode Screw terminals Pollution degree 3

Rated voltage max. 250 V Insulation resistance ï 109 ò Ampacity 4 A Forward resistance ð 5 mò Ambient temperature Connector -25 … + 90 °C

8

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 155 /0309 ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Field wireable connectors BSV8240-0/9

● Version: M12 connector ● Field-wireable ● 4-pole, angled, stainless steel cou- pling nut 40 ● Cable exit 4…8 mm 19 ● For use in PROFIBUS-PA and ø 21 FOUNDATION™ fieldbus applicati- 40 ons M12 x 1 PROFIBUS-PA connection ø 4...8

2 1 = + 3 1 2 = n.c. 3 = – 4 4 = shield Type BSV8240-0/9 Ident-No. 6914539

Connector field-wireable male connector, M12 x 1, angled FOUNDATION™ fieldbus connection Polarity 4-pole Contacts metal, CuZn,CuSnZn, Optalloy coated Contact carriers plastic, PA, black 2 1 = – Grip plastic, PA, black 2 = + 3 1 Coupling nut/screw stainless steel, 1.4404 3 = shield 4 = n.c. Seal plastic, FKM/FPM 4 Screw-in thread seal plastic, NBR Degree of protection IP67, only with screws tightened External diameter of the cable 4 … 8 mm Core cross-section/Clamping ability 0.14… 0.75 mm2 Screw-in thread PG 9 Connection mode Screw terminals Pollution degree 3

Rated voltage max. 250 V Insulation resistance ï 109 ò Ampacity 4 A Forward resistance ð 5 mò Ambient temperature Connector -25 … + 90 °C

156 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Field wireable connectors BKV8240-0/9

● Version: female M12 connector ● Field-wireable ● 4-pole, angled, stainless steel cou- pling nut 35 ● 19 Cable exit 4.0 … 8.0 mm ● For use in PROFIBUS-PA and ø 21 FOUNDATION™ fieldbus applicati- 40 ons M12 x 1 PROFIBUS-PA connection ø 4...8

v

2 1 = + 2 = n.c. 1 3 3 = – 4 4 = shield Type BKV8240-0/9 Ident-No. 6914540

Connector field-wireable female connector, M12 x 1, angled FOUNDATION™ fieldbus connection Polarity 4-pole Contacts metal, CuZn,CuSnZn, Optalloy coated v Contact carriers plastic, PA, black 2 1 = – Grip plastic, PA, black 2 = + Coupling nut/screw stainless steel, 1.4404 1 3 3 = shield 4 = n.c. Seal plastic, FKM/FPM 4 Screw-in thread seal plastic, NBR Degree of protection IP67, only with screws tightened External diameter of the cable 4 … 8 mm Core cross-section/Clamping ability 0.14… 0.75 mm2 Screw-in thread PG 9 Connection mode Screw terminals Pollution degree 3

Rated voltage max. 250 V Insulation resistance ï 109 ò Ampacity 4 A Forward resistance ð 5 mò Ambient temperature Connector -25 … + 90 °C

8

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 157 /0309 FOUNDATION™ fi eldbus Bus termination resistors

Data transmission on bus cables is TURCK offers plug-in termination frequently infl uenced by signal refl ection, resistors, type M12 × 1 and 7/8“, for which can occur when the bus ends are intrinsically safe and non-intrinsically safe not terminated. circuits. The fi eldbus must be provided with a termination resistor at both ends in order to avoid signal refl ection.

Specifi cation

Connector PUR housing material and contact carriers, oil resistant, 300 V rating Coupling nut stainless steel Protection degree (IEC 60529/EN 60529) IP67 and NEMA 1, 3, 4, 6P Max. ratings

– RSV49-TR, RSEV49-TR Umax = 50 VDC

Ta = -40...+80 °C

– RSV-49-TR-Ex Ui = 25 VDC, Ii = 250 mA, Pi =1.2 W

Ta = -40...70 °C (EEx ia IIC T4) -40...40 °C (EEx ia IIC T6)

Use of the intrinsically-safe version In zone 0 the power supply circuit must The intrinsically-safe fi eldbus termination conform to protection class “ia”. resistors feature protection class “intrinsic safety” and may be used in the explosion The RS-49-TR-Ex termination resistor can hazardous area category 1 G (zone 0), be used in networks, which are designed 2 G (zone 1) or 3 G (zone 2). conform to the FISCO model.

CAUTION NOTE The EC type test The TURCK JBBS... examination junctions to IP67 certifi cate and the (4 and 6 ports) and manufacturer’s declaration JRBS... to IP20 are already of conformity must be provided with integrated observed. switch-in bus termination It is essential that the resistors. “special conditions” in the Special versions excepted. EU type test examination certifi cate are observed.

158 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Bus termination resistor RSV49-TR

● Version: male 7/8" connector ● 4-pole, straight, stainless steel cou- pling nut ● For use in FOUNDATION ™ fieldbus applications 48,5 7/8-16UN

ø 26,0 Wiring diagram 1 3 1 µF 36,0 2 4 100 W

Type RSV49-TR Ident-No. 6602094

Connector Connector, 7/8'' Polarity 4-pole Contacts metal, CuZn, gold-plated Contact carriers plastic, PUR, black Grip plastic, PUR, yellow Coupling nut/screw stainless steel, 1.4404 Degree of protection IP67, only with screws tightened Ambient temperature -40…+ 70 °C

9

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 159 /0309 ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Bus termination resistor RSEV49-TR

● Version: M12 connector ● 4-pole, straight, stainless steel cou- pling nut ● For use in FOUNDATION ™ fieldbus applications 12,5 M12 x 1

ø 14,2 Wiring diagram 4 4,0 18,0 48,5 1 3 1 µF 100 W 2

Type RSEV49-TR Ident-No. 6602096

Connector Connector, M12 x 1 Polarity 4-pole Contacts metal, CuZn, gold-plated Contact carriers plastic, PUR, black Grip plastic, PUR, black Coupling nut/screw stainless steel, 1.4404 Degree of protection IP67, only with screws tightened Ambient temperature -40…+ 70 °C

160 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com ñ Edition: Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

Accessories for fieldbus systems Bus termination resistor RSV-49TR-EX

● FISCO compliant according to IEC TS 60079-27 ● Version: male 7/8" connector ● 4-pole, straight, stainless steel cou- pling nut 48,5 7/8-16UN ● For use in FOUNDATION ™ fieldbus applications ø 26,0

Wiring diagram 36,0 1 3 1 µF 2 4 100 W

Type RSV-49TR-EX Ident-No. 6602709

Connector Connector, M12 x 1 Polarity 4-pole Contacts metal, CuZn, gold-plated Contact carriers plastic, PUR, black Grip plastic, PUR, blue Coupling nut/screw stainless steel, 1.4404 Degree of protection IP67, only with screws tightened Ambient temperature -40…+ 70 °C

Ex approval acc. to conformity certificate TÜV 03 ATEX 2379 X ð Max. input voltage Ui 25 V ð Max. input current Ii 250 mA ð Max. input power Pi 1200 mW External inductance/capacitance Li/Ci negligible

Device designation É II 1 G EEx ia IIC T6 FISCO / Entity field device

9

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 161 /0309 Accessories for fieldbus systems IP67 stainless steel housing EG-VA2020/BV67-T105

accessories for fieldbus systems IP67 stainless steel housing EG-VA2020/BV67-T105 Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

The stainless steel housing EG-VA2020/ with ten M20 × 1.5-cable glands. BV67-T105 is suited for the integration of ● Stainless steel housing to accom- TURCK junction boxes JRBS-… With a pressure compensation element modate the TURCK IP20 junction (Protection degree IP67) a continuous and modules The robust model is especially suited for reliable ventilation is ensured. This way con- ● Protection degree IP67 rough and aggressive environmental condi- densation and accumulation of water is (IEC/EN 60529) tions. avoided. ● 10 plastic cable glands M20 x 1.5 for cable guides Inside the housing a hat rail is located used Note: Ensure sufficient equipotential bon- ● Insulated shield terminals for retaining a 4, 6 or 8 port JRBS junction ding of the installation. The housing is con- box with a maximum width of 180 mm. nected to the equipotential bond via an M5 ● Wall mounting x 1 connector. ● Pressure compensation element ● Connection of the housing potential The connection of the cables is attained via an M5 x 1 bolt

162 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com Accessories for fieldbus systems IP67 stainless steel housing EG-VA2020/BV67-T105

Type EG-VA2020/BV67-T105 Dimensions Ident-No. 6884135

Electrical connection cable glands 10 x M20 x 1.5 (Ø 6…13mm); plastic, black Earthing bolt M5 x 1 M5 x 12 Degree of protection IP67 Ambient temperature -30 …+ 80 °C Relative humidity ð 95 %, non condensing 80,5 Housing material Stainless steel 1.430/AISI304 90 Wall thickness 1.5 mm 200 Housing surface grinded and polished (240 grain size distribu- 220,1 160 tion) Housing color silver Sealing material PUR Dimensions 200 x 200 x 80.5 mm Connection mode Wall mounting

10

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 163 /0309 Accessories for fieldbus systems IP67 stainless steel housing EG-VA2020/BV67-T103

accessories for fieldbus systems IP67 stainless steel housing EG-VA2020/BV67-T103 Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com

The stainless steel housing EG-VA2020/ with ten M20 × 1.5-cable glands. BV67-T103 is suited for the integration of ● Stainless steel housing to accom- TURCK junction boxes JRBS-… With a pressure compensation element modate the TURCK IP20 junction (Protection degree IP67) a continuous and modules The robust model is especially suited for reliable ventilation is ensured. This way con- ● Protection degree IP67 rough and aggressive environmental condi- densation and accumulation of water is (IEC/EN 60529) tions. avoided. ● 10 stainless steel cable glands M20 x 1.5 for cable guides Inside the housing a hat rail is located used Note: Ensure sufficient equipotential bon- ● Insulated shield terminals for retaining a 4, 6 or 8 port JRBS junction ding of the installation. The housing is con- box with a maximum width of 180 mm. nected to the equipotential bond via an M5 ● Wall mounting x 1 connector. ● Pressure compensation element ● Connection of the housing potential The connection of the cables is attained via an M5 x 1 bolt

164 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com Accessories for fieldbus systems IP67 stainless steel housing EG-VA2020/BV67-T103

Type EG-VA2020/BV67-T103 Dimensions Ident-No. 6884136

Electrical connection cable glands 10 x M20 x 1.5 (Ø 6…13mm); stainless steel Earthing bolt M5 x 1 M5 x 12 Degree of protection IP67 Ambient temperature -30 …+ 80 °C Relative humidity ð 95 %, non condensing 80,5 Housing material Stainless steel 1.430/AISI304 90 Wall thickness 1.5 mm 200 Housing surface grinded and polished (240 grain size distribu- 220,1 160 tion) Housing color silver Sealing material PUR Dimensions 200 x 200 x 80.5 mm Connection mode Wall mounting

10

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 165 /0309 FOUNDATION™ fi eldbus Accessories for fi eldbus systems

Dimensions Application Type designation Ident-No.

Stripping the insulation from round (shielded) data cables TCS wire stripping tool 6900454 from Ø 2.5...8 mm (also for FastConnect®/ Fast Assembly™), 1, 2 and 3-stage cable stripping in a single operation; Adjustment block provided for fast preadjustment of the depth, cutting edges can be used on both sides

Special tool for cable glands on multibarriers, excom®- VSTS22 (AF 22) 6884043 housings1) and junctions. VSTS24 (AF 24) 6900462 Open and close cable glands from various positions. Also VSTS27 (AF 27) 6884073 work in diffi cult positions using the swivelling handle. Use is sim- plifi ed by the slot provided in the tube (the cables fed through the cable gland are pushed through the slot on the tube). Tool sizes 22, 24 and 27, special sizes are 22, 24, 27 available on request

1) excom® is the TURCK Ex remote I/O system for use in zones 1 and 2. More detailed information can be found in the product catalog.

166 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com Dimensions Application Material and Type designation Ident-No. colour

7/8-16UN 7/8“ end cap, male, stainless steel RSMV-BC 6603783 ø 25 oil resistant, IP67 to IEC 60529/ EN 60529 and NEMA 1, 3, 4, 6P

7 19,5

ø 25 7/8“ end cap, female, stainless steel RKMV-BC 6603784 7/8-16UN oil resistant, IP67 to IEC 60529/ EN 60529 and NEMA 1, 3, 4, 6P

16,5

7/8-16UN 7/8“ end cap, male, stainless steel RSMV-CC 6604030 ø 25 oil resistant, IP67 to IEC 60529/ EN 60529 and NEMA 1, 3, 4, 6P, 7 24 with wire rope

ø 25 7/8-16UN 7/8“ end cap, female, stainless steel RKMV-CC 6604038 oil resistant, IP67 to IEC 60529/ EN 60529 and NEMA 1, 3, 4, 6P,

21,3 with wire rope

7/8-16UN 7/8“ end cap, male, stainless steel RSMV-CCC 6604490 ø 25 oil resistant, IP67 to IEC 60529/ EN 60529 and NEMA 1, 3, 4, 6P, 7 with chain, approx. 210 mm, 24 closure closed

7/8“ end cap, male, stainless steel RKMV-CCC 6604488 ø 25 7/8-16UN oil resistant, IP67 to IEC 60529/ EN 60529 and NEMA 1, 3, 4, 6P, with chain, approx. 210 mm, 10 21,3 closure closed

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 167 /0309 FOUNDATION™ fi eldbus Accessories for fi eldbus systems

Dimensions Application Material and Type designation Ident-No. colour

7/8-16UN 7/8“ end cap, male, stainless steel RSMV-CCO 6604489 ø 25 oil resistant, IP67 to IEC 60529/ EN 60529 and NEMA 1, 3, 4, 6P, 7 24 with chain, approx. 210 mm, closure open

ø 25 7/8-16UN 7/8“ end cap, female, stainless steel RKMV-CCO 6604485 oil resistant, IP67 to IEC 60529/ EN 60529 and NEMA 1, 3, 4, 6P,

21,3 with chain, approx. 210 mm, closure open

M12 × 1 end cap, male, stainless steel RSEV-BC 6902305 M12 x 1 oil resistant, IP67 to IEC 60529/ ø 16,3 EN 60529 and NEMA 1, 3, 4, 6P

9,5 16

M12 × 1 end cap, female, stainless steel RKEV-BC 6902304 ø 15 M12 x 1 oil resistant, IP67 to IEC 60529/ ø 16,3 EN 60529 and NEMA 1, 3, 4, 6P

16

M12 x 1 M12 × 1 end cap, male, stainless steel RSEV-CC 6604174 ø 16,3 oil resistant, IP67 to IEC 60529/

9,5 EN 60529 and NEMA 1, 3, 4, 6P, 20,2 with chain

ø 15 M12 x 1 M12 × 1 end cap, female, stainless steel RKEV-CC 6604176 ø 16,3 oil resistant, IP67 to IEC 60529/ EN 60529 and NEMA 1, 3, 4, 6P, 20 with chain

168 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com Dimensions Application Material and Type designation Ident-No. colour

7/8-16UN ø 28 Screw-on cap for 7/8“ female connectors, polyamide VZ8 8018816 no internal wiring black 24

12 18

ø 24 7/8-16UN ø 28 Screw-on cap for 7/8“ male connectors, polyamide VK-7/8 6999027 no internal wiring black

24

12 18

Dust cap for 7/8“ fl ange fi tting, polyamide RSM-DUST-CAP 6914862 for male fl anges, no internal wiring black 21,8

1,5

12,7

Dust cap for 7/8“ fl ange fi tting, polyamide RKM-DUST-CAP 6914863 for female fl anges, no internal wiring black 24,8

1,5

12,7

ø 16 M12 x 1 M12 × 1 end cap, male, PUR VS-M12 6999003 oil resistant, IP54 to IEC 60529/ yellow EN 60529 and NEMA 1, 3, 4, 6P

9 14

ø 16 M12 × 1 end cap, female, PUR VK-M12 6999025 oil resistant, IP54 to IEC 60529/ yellow EN 60529 and NEMA 1, 3, 4, 6P 10 M12 x 1

14

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 169 /0309 FOUNDATION™ fi eldbus Accessories for fi eldbus systems

Dimensions Application Material and Type designation Ident-No. colour/ Connection technology

Fig. ( Fxxx )

12,5 M12 x 1 M12 × 1 end cap, male stainless steel/PUR RSEV49-CC 6603489 oil resistant, IP67 to IEC 60529/ grey ø 14,2 EN 60529 and NEMA 1, 3, 4, 6P 4,0 18,0 48,5

7/8“ feed-through receptacles, male/fe- 1 × 7/8“ ( F015 ) RSFV-RKFV49/22 6602357 49.2 32.7 male, IP67 to IEC 60529/EN 60529 and 1 × 7/8“ ( F016 ) NEMA 1, 3, 4, 6, stainless steel 7/8-16UN

7/8-16UN locknut sealing gasket lockwasher thrust washer

47.4 M12 × 1 feed-through receptacles, male/ 1 × M12 ( F040 ) FKV-FSV49/M12 6603678 29.4 O-ring female, IP67 to IEC 60529/EN 60529 and 1 × M12 ( F041 ) NEMA 1, 3, 4, 6, stainless steel M12 x 1

M12 x 1 locknut lockwasher LN-M12 LW-M12

Pin assignment ( F015 ) ( F016 ) ( F040 ) ( F041 ) w v w v 2 2 1 3 3 1 3 1 1 3 2 4 4 2 4 4 1 = – 1 = – 1 = – 1 = – 2 = + 2 = + 2 = + 2 = + 3 = shield 3 = shield 3 = shield 3 = shield 4 = earth 4 = earth 4 = earth 4 = earth

170 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 10

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 171 /0309 Type index

Type designation Page Type designation Page Type designation Page

BK4140-0/9 147 JBBS-49-T615/3G 68 RSV49-TR 159 BKV4140-0/13.5 151 JBBS-49-T615B/Ex 80 RSV-49TR-Ex 161 BKV4140-0/16 153 JRBS-40-12C/Ex 112 RSV-FBY49x-*M/5D 131 BKV4140-0/9 149 JRBS-40-4C/Ex 106 RSV-RKV492A-*M 132 BKV8140-0/9 155 JRBS-40-6C/Ex 108 RSV-RKV492BA-*M 132 BKV8240-0/9 157 JRBS-40-8C/Ex 110 RSV-RKV-FBY49x-*M/5D 131 BS4140-0/9 146 JRBS-40-12R/Ex 120 RSV-RSV-FBY49x-*M/5D 131 BS8149-0/9 144 JRBS-40-4R/Ex 114 TCS wire stripping tool 166 BSV4140-0/13.5 150 JRBS-40-6R/Ex 116 VK-7/8 169 BSV4140-0/16 152 JRBS-40-8R/Ex 118 VK-M12 169 BSV4140-0/9 148 JRBS-40SC-12C/Ex 96 VS-M12 169 BSV8140-0/9 154 JRBS-40SC-4C/Ex 90 VSTS22 166 BSV8240-0/9 156 JRBS-40SC-6C/Ex 92 VSTS24 166 Cable 492A…M 128 JRBS-40SC-8C/Ex 94 VSTS27 166 Cable 492BA…M 128 JRBS-40SC-12R/Ex 104 VZ8 169 Cable FB4910-BK...M 129 JRBS-40SC-4R/Ex 98 WKCV-FBY49x-*M/5D 131 Cable FBA-YE/SD…M 127 JRBS-40SC-6R/Ex 100 WKCV-WKCV-FBY49x-*M/5D 131 Cable FBH-YE/SD…M 126 JRBS-40SC-8R/Ex 102 WKV-FBY49x-*M/5D 131 Cable FBY-.../SD…M 124 MBD49-T415/Ex 34 WKV-WKV-FBY49x-*M/5D 131 Cable FBY-BK/LD…M 125 PSU-3214 26 WSCV-FBY49x-*M/5D 131 DPC-49-1-RMB 14 RKCV-FBY49x-*M/5D 131 WSCV-WKCV-FBY49x-*M/5D 131 DPC-49-4-RMB 10 RKCV-RKCV-FBY49x-*M/5D 131 WSCV-WSCV-FBY49x-*M/5D 131 DPC-49-4-RMB/SY 12 RKEV-BC 168 WSV-FBY49x-*M/5D 131 DPC-49-ADU 20 RKEV-CC 168 WSV-WKV-FBY49x-*M/5D 131 DPC-49-DU 18 RKFV49 135 WSV-WSV-FBY49x-*M/5D 131 DPC-49-HSEFD/24VDC 22 RKFV49-0,3M/14,5 137 DPC49-IPS1 16 RKFV49-0,3M/M20 139 EG-VA2020/BV67-T103 164 RKM-DUST-CAP 169 EG-VA2020/BV67-T105 162 RKMV-BC 167 FD-49-T317/Ex 36 RKMV-CC 167 FKV49 141 RKMV-CCC 167 FKV49-0,3M/14,5/C1117 143 RKMV-CCO 168 FKV49-0,3M/M20/C1117 145 RKV492A-*M 132 FKV-FSV49/M12 170 RKV492BA-*M 132 FSV49 140 RKV-FBY49x-*M/5D 131 FSV49-0,3M/14,5/C1117 142 RKV-RKV-FBY49x-*M/5D 131 FSV49-0,3M/M20/C1117 144 RPC49-10120Ex 28 JBBS-49-E413/3G 70 RPC49-10265Ex 30 JBBS-49-E413/Ex 82 RPC49-205 24 JBBS-49-E613/3G 72 RSCV-2RKCV49 41 JBBS-49-E613/Ex 84 RSCV-FBY49x-*M/5D 131 JBBS-49-M413/3G 74 RSCV-RKCV-FBY49x-*M/5D 131 JBBS-49-M413/Ex 86 RSCV-RSCV-FBY49x-*M/5D 131 JBBS-49-M613/3G 76 RSEV49-CC 170 JBBS-49-M613/Ex 88 RSEV49-TR 160 JBBS-49SC-E413/3G 46 RSEV-BC 168 JBBS-49SC-E413/Ex 58 RSEV-CC 168 JBBS-49SC-E613/3G 48 RSFV49 134 JBBS-49SC-E613/Ex 60 RSFV49-0,3M/14,5/C1117 136 JBBS-49SC-M413/3G 50 RSFV49-0,3M/M20/C1117 138 JBBS-49SC-M413/Ex 62 RSFV-RKFV49/22 170 JBBS-49SC-M613/3G 52 RSM-DUST-CAP 169 JBBS-49SC-M613/Ex 64 RSMV-BC 167 JBBS-49SC-T415/3G 42 RSMV-CC 167 JBBS-49SC-T415B/Ex 54 RSMV-CCC 167 JBBS-49SC-T615/3G 44 RSMV-CCO 168 JBBS-49SC-T615B/Ex 56 RSV-2RKV49 40 JBBS-49-T415/3G 66 RSV492A-*M 132 JBBS-49-T415B/Ex 78 RSV492BA-*M 132

172 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 10

11

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 173 /0309 174 /0309 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 10

11

Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • 45472 Mülheim/Ruhr • Germany • Tel. +49 (0)208 4952-0 • Fax +49 (0)208 4952-264 • [email protected] • www.turck.com 175 /0309 TURCK WORLD-WIDE HEADQUARTERS

GERMANY Hans Turck GmbH & Co. KG Witzlebenstraße 7 45472 Mülheim an der Ruhr P. O. Box 45466 Mülheim an der Ruhr Tel. +49 208 4952-0 Fax +49 208 4952-264 E-Mail [email protected]

AUSTRALIA HUNGARY THE NETHERLANDS TURCK Australia Pty. Ltd. TURCK Hungary kft. TURCK B. V. unit 5, 6-7 Gilda Court Mulgrave Könyves Kalman Krt.76 Postbus 297 Victoria 3170 1087 Budapest 8000 AG Zwolle Tel. +61 (0) 3 95609066 Tel. +36 1 4770-740 Tel. +31 38 4227-750 Fax +61 (0) 3 95601620 Fax +36 1 4770-741 Fax +31 38 4227-451 E-Mail E-Mail [email protected] E-Mail [email protected] [email protected]

BAHRAIN INDIA POLAND TURCK Middle East S.P. TURCK India Automation Pvt Ltd. TURCK sp.z o.o P.O. Box 18370 603/604, 6th Floor, A-wing Ul. Zeromskiego 1 Manama - Kingdom of Bahrain ICC Trade Towers, 45-053 Opole Tel. +973 17 814920 Senapati Bapat Road, Tel. +48 77 443 48 00 Fax +973 17 814925 Pune - 411016, Fax +48 77 443 48 01 E-Mail Maharashtra - India E-Mail [email protected] [email protected] Tel. + 91 20 25630039 25630040 Fax + 91 20 25630040 E-Mail [email protected]

BELGIUM ITALY ROMANIA Multiprox N. V. TURCK Process Automation TURCK Automation Romania SRL P. B. 71 Via ATorta 30/A Str. luliu Tetrat nr. 18 Sector 1 Lion d’Orweg 12 24047 Treviglio (BG) 011914 Bukarest 9300 Aalst Tel. +39 03 6346128 Tel. +40 21 2300279 Tel. +32 53 766566 Fax +39 03 63598268 2300594 Fax +32 53 783977 E-Mail [email protected] Fax +40 21 2314087 E-Mail [email protected] E-Mail: [email protected]

CZECH REPUBLIC JAPAN RUSSIA TURCK s.r.o. TURCK Japan Corporation TURCK Rus O.O.O. Hradecká 1151 #202 MBD Bldg. 2F, 3-3-23, Altufyevskoe shosse, 1/7 500 03 Hradec Králové 3 Minami-Aoyama, 127106 Moskau Tel. +420 495 518 766 Minato-ku, 107-0062, Tokyo, Tel. +7 495 2342661 Fax +420 495 518 767 Japan Fax +7 495 2342665 E-Mail [email protected] Tel. + 81 3 57722820 E-Mail [email protected] Fax + 81 3 34082571 E-Mail [email protected]

PR OF CHINA KOREA SINGAPORE TURCK (Tianjin) Sensor Co. Ltd. TURCK Korea Co. Ltd. TURCK Singapore Pte. Ltd. 18,4th Xinghuazhi Road, RIT center Room No 412, 25 International Business Park Xiqing Economic Gyeonggi Technopark #03-22/23 German Centre Development Area, Phone +82 (31) 5004555 609916 Singapore 300381 Tianjin Fax +82 (31) 5004558 Tel. +65 65628716 Tel. +86 22 83988-188 E-Mail [email protected] Fax +65 65628719 83988-199 E-Mail [email protected] Fax +86 22 83988-111 E-Mail [email protected]

FRANCE MEXICO USA www.turck.com TURCK BANNER S.A.S TURCK Mexico S. DE R.L. DE C.V. TURCK Inc. 3, Rue de Courtalin Carr. Saltillo-Zacatecas km 4.5 s/n 3000 Campus Drive Magny-Le-Hongre Parque Industrial “La Angostura“ Minneapolis, MN 55441-2656 77703 Marne-La-Vallee Cedex 4 Saltillo, COAH. 25070 Tel. +1 763 553-9224 Tel. +33 1 6043-6070 Tel. +52 844 4826-924 553-7300 Fax +33 1 6043-1018 Fax +52 844 4826-926 Fax +1 763 553-0708 E-Mail [email protected] E-Mail [email protected] E-Mail [email protected]

GREAT BRITAIN TURCK BANNER LIMITED Blenheim House Hurricane Way Wickford, Essex SS11 8YT Tel. +44 1268 578888 Fax +44 1268 763648 D301024 0309 E-Mail [email protected] *D301024ßß0309*

... and more than 60 representatives and agencies world-wide. Subject to change without notice