Fire Alarm Systems | Detectors

Infrared Flame Detectors

▶ Compact, robust and nearly maintenance-free ▶ Suitable for outdoor use under extreme conditions ▶ Optimal adjustment to the environmental conditions with 10 DIP switches ▶ Two sensitivity levels ▶ Easy-to-see red individual display ▶ For room heights from 1.50 m to 20 m

Infrared Flame Detectors are used to detect open System Overview in rooms or outdoors. They are especially suitable for smokeless liquid and gas 1 2 EOL22(Ex) as well as for fires of materials that contain carbon with strong development.

Typical areas of application are: DFA1101A-Ex large industrial warehouses, airplane hangars, chemical facilities, oil refineries, machine rooms, ferries and freight ships, power plants, printing plants, wood warehouses, FLM-420/4-CON DO1101A-Ex subway tunnels. The DF1101A‑Ex is an inherently safe Infrared Flame DCA1192 SB3 Detector for use in explosive areas of the zones 1 and 2, DO1101A-Ex e. g. in high warehouse halls for flammable liquids, where liquid fires could occur in an explosive atmosphere. DCA1192 SB3 DM 1103 B-Ex DM 1103 B-Ex

Pos. Description 1 Non-Ex area 2 Ex area zone 1 or 2

Functions The detection element of the Infrared Flame Detector consists of two pyroelectric sensors (sensor 1 and 2) and a silicon photo diode (sensor 3).

www.boschsecurity.com 2 | Infrared Flame Detectors

While sensor 1 detects the flame, the other two sensors Parts Included measure the malfunction beam in other wavelength ranges. Detector type Qty. Components DF1192 1 Infrared Flame Detector DF1192 Sensor Spectral range Detection from DF1101A-Ex 1 Infrared Flame Detector DF1101A‑Ex 1 4.0 μm to 4.8 μm CO2 Note With the Infrared Flame Detectors DF1192 2 5.1 μm to 6.0 μm Sources of interference and DF1101A‑Ex, the DFB1190 detector base 3 0.7 μm to 1.1 μm Solar is not included in the scope of delivery and The combination of the three sensors and the intelligent must be ordered separately. signal processing with fuzzy algorithms and wavelet creates outstanding reliability of detection with high protection against false alarms. Technical Specifications

Electrical

Certifications and Approvals Operating voltage 16 V DC . . . 28 V DC The DF1101A‑Ex meets the explosion classification in line Standby current consumption 0.5 mA with IEC 60079 and EN 50020 (Eex ib IIC T4). Mechanics

Individual display LED red Region Certification Connection terminals 2 2 Germany VdS G 299085 DF1101-Ex/DF1192 0.2 mm . . . 2.5 mm Dimensions (W x H x D) Europe CE DF 1192 Detector 135 x 135 x 32 mm DF 1101-Ex • • Detector incl. base 135 x 135 x 77 mm Housing material Installation/Configuration Notes • Detector Cast aluminum • Both Infrared Flame Detectors comply with EN 54‑10. • Base Plastic, PC, fiber-reinforced • The response sensitivity and the resulting monitoring Color (detector and base) White, RAL 9010 area of an Infrared Flame Detector depend on: Weight incl. base - Detection distance - Possible spread of • DF1192 500 g - Fire material • DF1101A-Ex 750 g - Detector sensitivity - Detector arrangement. Environmental conditions Purely for physical reasons, IR flame detectors can • Protection class as per EN 60529 IP 67 detect no fires of inorganic materials (e. g. sulfur, phosphorous, magnesium, natrium, , etc.). Permissible operating tempera- -35 °C . . . +70 °C • The detector must have a direct visual line to all ture possible fire locations of the monitoring area. Permissible storage temperature -40 °C . . . +75 °C Practical area monitoring is achieved with a detector • Relative humidity < 100 %, no heavy condensation of arrangement at a 45° to the corners of the area. the sensor window • If the room height is more than 5 m, the detector axis should be aligned towards the opposite corner of the Planning room. • The space above the detector is outside of the Max. installation height 1.5 . . . 20 m detection area. Max. monitoring area 80 m2 (Heed local guidelines!) • Despite wide-ranging insensitivity, the sensors must be protected against direct or indirect ; it may Special features be necessary to install a covering housing. • The Infrared Flame Detectors can be connected using Detection principle Detection of infrared radiation a FLM‑420/4‑CON Conventional Interface Module to Detection area 90° the Local SecurityNetwork LSN. Infrared Flame Detectors | 3

Ordering Information DF1192 Infrared Flame Detector DF1192 DF1101A‑Ex Infrared Flame Detector for DF1101A-Ex Ex Areas SB3 Safety Barrier incl. DCA1192 Input/ SB3 Output Module limits the electrical energy between non-in- herently safe and inherently safe circuits Accessories DFB1192-BASE Base for Infrared Flame DF1192-BASE Detector Base for Infrared Flame Detectors DF1192 and DF1101A‑Ex, including line termination EOL22(Ex)

www.boschsecurity.com 4 | Infrared Flame Detectors

Americas: Europe, Middle East, Africa: Asia-Pacific: Represented by Bosch Security Systems, Inc. Bosch Security Systems B.V. Robert Bosch (SEA) Pte Ltd, Security Systems 130 Perinton Parkway P.O. Box 80002 11 Bishan Street 21 Fairport, New York, 14450, USA 5600 JB Eindhoven, The Netherlands Singapore 573943 Phone: +1 800 289 0096 Phone: + 31 40 2577 284 Phone: +65 6258 5511 Fax: +1 585 223 9180 Fax: +31 40 2577 330 Fax: +65 6571 2698 [email protected] [email protected] [email protected] www.boschsecurity.us www.boschsecurity.com www.boschsecurity.asia

© Bosch Security Systems Inc. 011 | Data subject to change without notice T284685451 | Cur: en-US, V24, 19 Apr 2011