TM SJE PumpMaster® and SJE PumpMaster® Plus Quick Fit Pump Switches Installation Instructions

SJE-Rhombus® wide angle pump switches are designed to provide automatic control of pumps in water and sewage applications.

SJE PUMPMASTER® QUICK FIT SJE PUMPMASTER® PLUS QUICK FIT

Mechanically activated Mechanically activated pump switch for direct pump switch for direct control of pumps in: control of pumps in: n Sewage n Sewage n Water n Water

U.S. Patent Nos. 5,087,801 & 5,142,108 .S. Patent Nos. 5,087,801 & 5,142,108 tether tether length 3.5 6 10 14 18 22 24 3.5 6 10 14 18 22 24 min. length min. pumping 7 10 16 22 28 33 36 pumping 7 10 16 22 28 33 36 range range

FEATURES

n float and piggyback plug are separate to allow for quick fit installation by routing the float cord through conduit and heat shrink, then attaching the piggyback plug by inserting the quick connect terminals and applying the protective heat shrink.

PREVENTATIVE MAINTENANCE • Periodically inspect the product. Check that the cable has not become worn or that the housing has not been damaged so as to impair the protection of the product. Replace the product immediately if any damage is found or suspected. • Periodically check to see that the float is free to move and operate the switch. • Use only SJE-Rhombus® replacement parts.

SJE-RHOMBUS® FIVE-YEAR LIMITED WARRANTY

SJE-RHOMBUS® warrants to the original consumer that this product shall Some states do not allow limitations on how long an implied warranty free of manufacturing defects for five years after the date of consumer lasts, so the above limitation may not apply to you. Some states do not purchase. During that time period and subject to the conditions set forth allow the exclusion or limitation of incidental or consequential damages, below, SJE-RHOMBUS® will repair or replace, for the original consumer, so the above limitation or exclusion may not apply to you. This warranty any component which proves to be defective due to defective materials gives you specific legal rights, and you may also have other rights which or workmanship of SJE-RHOMBUS®. vary from state to state.

ELECTRICAL WIRING AND SERVICING OF THIS PRODUCT MUST TO OBTAIN WARRANTY SERVICE: The consumer shall assume all BE PERFORMED BY LICENSED ELECTRICIAN. responsibility and expense for removal, reinstallation, and freight. Any item to be repaired or replaced under this warranty must be returned to THIS WARRANTY DOES NOT APPLY: (A) to damage due to lightning SJE-RHOMBUS®, or such place as designated by SJE-RHOMBUS®. or conditions beyond the control of SJE-RHOMBUS®; (B) to defects or malfunctions resulting from failure to properly install, operate or maintain ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS the unit in accordance with printed instructions provided; (C) to failures ARE LIMITED TO THE DURATION OF THIS WRITTEN WARRANTY. resulting from abuse, misuse, accident, or negligence; (D) to units which SJE-RHOMBUS® SHALL NOT, IN ANY MANNER, BE LIABLE FOR are not installed in accordance with applicable local codes, ordinances, ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES AS A RESULT or accepted trade practices, and () to units repaired and/or modified OF A BREACH OF THIS WRITTEN WARRANTY OR ANY IMPLIED without prior authorization from SJE-RHOMBUS®. WARRANTY.

NOTICE! Products returned must be cleaned, sanitized, or decontaminated as necessary prior to shipment to ensure that employees will not be exposed to health hazards in handling said material. All applicable laws and regulations shall apply. ELECTRICAL SHOCK HAZARD EXPLOSION OR FIRE HAZARD Disconnect power before installing or servicing this Do not use with flammable liquids. product. A qualified service person must install and Install in accordance with ANSI/NFPA 70. service this product according to applicable electrical Suitable for usage with intrinsically safe circuit and plumbing codes. extensions as defined by UL 698A. Failure to follow these precautions could result in serious injury or death. Replace product immediately if switch cable becomes damaged or severed. Keep these instructions with warranty after installation. This product must be installed in accordance with National Electric Code, ANSI/NFPA 70 so as to prevent moisture from entering or accumulating within boxes, conduit bodies, fittings, float housing, or cable.

For detailed specifications on this product, or for the complete line of SJE-Rhombus® panel, alarm, and switch products, visit our web-site at www.sjerhombus.com. MOUNTING THE SWITCH PIGGY-BACK PLUG INSTALL 1. Determine the required cord n Electrical outlet must be located in 5. Using a heat gun or torch, gradually tether length according to an enclosure providing strain relief apply heat to the heat shrink until it product specifications on the such as a plugger box. shrinks and fits snugly to the cable front page and as shown in n Electrical outlet voltage, piggy-back outer jacket, and quick connect Figure A. plug voltage, and pump voltage terminals. The heat shrink is lined 2. Place the cord into the clamp as must match. with adhesive. When properly shown in Figure B. installed, there should be a small 3. Locate clamp at desired 1. Follow steps 1 through 4 of amount of adhesive squeezed out activation level and secure the “Mounting The Switch.” at each end. CAUTION - Take care clamp to the discharge pipe as 2. Route the float cable into a plugger not to burn the heat shrink or cable shown in Figure B. Note: Do not box. jacket during this process. install cord under hose clamp. 3. Slide heat shrink onto the float 6. Insert the piggy-back plug into the 4. Tighten the hose clamp using cable and connect piggy-back plug outlet. screwdriver. Over tightening by fully inserting the quick connect 7. Plug the pump into the piggy-back may result in damage to the terminals. plug as shown in figure A. plastic clamp. Make sure the 4. Move the heat shrink so that it is 8. Check the installation. Allow float cable is not allowed to centered over the splice connection system to cycle to insure proper touch the excess hose clamp as shown in Figure C. installation. band during operation. Warning - Not installing heat shrink as defined in steps 4-5 Note: All hose clamp components introduces safety hazards and Figure B are made of 18-8 stainless steel may result in serious injury, material. See your SJE-Rhombus® electric shock, or death. supplier for replacements. Figure A

plugger box

WARNING: Tethering switches below minimum pump plug tether length can effect switch operation and will reduce the fatigue life of the cable. switch piggyback plug heat shrink ! Due to weight of cable, pumping range above horizontal is NOT equal to pumping range below horizontal. Use values published on front page as a guide. Pumping ranges are based on testing in tether length non-turbulent conditions. Range may vary due to water temperature and cord shape. Note: As the Figure C tether length increases, so does the variance of the pumping range.

pumping ↓ range Float Piggyback

Switch Plug ↓

Center Heat Shrink on Terminal Connection

TM

22650 County Highway 6 n P.. Box 1708 n Detroit Lakes, Minnesota 56502 USA 1-888-DIAL-SJE (1-888-342-5753) n Phone: 218-847-1317 n Fax: 218-847-4617 n E-mail: [email protected] Instl. Instr. PN 1036770F ©SJE-Rhombus 02/18