Surge Protection (SPD) & Power Conditioning Products 34.0-1 September 2016 Sheet 34001

Contents 22 Surge Protection (SPD) & Power Conditioning Products Surge Protection Products—SPD 23 Facility-Wide Protection ...... 34.1-1 Integrated Surge Protection ...... 34.1-3 24 Integrated Panelboard SPD ...... 34.1-4 SPD Series Sidemount Units...... 34.1-6 25 SPD MAX Series Surge Protection ...... 34.1-16 Sidemount Surge Protective Device for Commercial and Light Industrial Applications ...... 34.1-20 26 CVX050/100...... 34.1-25 Eaton SP1 ...... 34.1-28 27 Eaton SP2 ...... 34.1-30 AEGIS Powerline Filters...... 34.1-32 28 Power Conditioning Products Sag Ride Through (SRT2) ...... 34.1-37 Electronic Voltage Regulator (EVR)...... 34.1-40 29 Specifications See Eaton’s Product Specification Guide, available on CD or on the Web. 30 CSI Format: ...... 1995 2010 SPD Series Integrated ...... Section 16671A Section 26 43 13 31 SPD Series Side Mount ...... Section 16671B Section 26 43 16 32

33

34

35

36

37

38

39

40

Surge Protection (SPD) & Protection Surge 41

42

4 3

Eaton Surge Protection Family Power Conditioning Products Power

CA08104001E For more information, visit: www.eaton.com/consultants Surge Protection (SPD) & Power Conditioning Products 34.0-2 September 2016 Sheet 34002

This page intentionally left blank. 22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

4 3

For more information, visit: www.eaton.com/consultants CA08104001E Surge Protection (SPD) & Power Conditioning Products 34.1-1 September 2016 Surge Protection Products—SPD Sheet 34003 Facility-Wide Protection—SPD Series

Facility-Wide Protection 22 Incoming LV A Facility-Wide Protection Substation LV Busway Strategy Should be Employed to 23

Address Power Quality Issues SPD Bus Plug SPD120 Why Coordinated (Cascaded) 24 Facility-Wide Protection? As recommended in the IEEE® Service Entrance Emerald Book, a cascaded or staged or 25 protection approach should be Switchgear SPD250 developed and executed to reduce external/internal impulse waveforms 26 to harmless levels. Eaton surge protection solutions are available in all common voltages and configurations, 27 in surge current capacity ratings up to 800 kA and with a variety of optional Switchboard 28 features such as EMI/FFI filtering, SPD120 audible alarm, Form C contacts and surge counters. Eaton’s complete 29 offering of surge protective devices ensures there is a solution for any application in a cascaded facility-wide 30 protection strategy. A surge device equipped with filtering should be installed at the main service 31 entrance and key distribution or branch panelboards to eliminate ringing and Motor Control Center SPD120 impulse disturbances, as well as high 32 frequency EMI/RFI noise. Filtering is available on the SPD, SPC and SPM Panelboard SPD100 Series models. 33 Eaton surge devices are coordinated to work on a “system basis”. Surge units SPD Series Unit 34 installed at each level in the system work together to isolate and remove externally/internally generated 35 disturbances, creating superior facility- Figure 34.1-1. Cascaded Performance wide performance and reliability. Integrated SPD Series units maximize 36 flexibility, space and protection and are available in switchboards, switchgear, panelboards, motor control centers and 37 automatic transfer . Integrating the surge device into the electrical assembly maximizes protection by 38 keeping installation leads as short as possible. 39 Benefits of Facility-Wide Surge Protection ■ High amplitude lightning impulses reduced to negligible levels 40 ■ The electrical distribution’s noise attenuation is significantly enhanced 41 The coordinated design ensures effective current sharing between main and branch surge devices. 42 Installing appropriately rated surge protection at locations throughout a facility provides a layered defense 4 3 solution and helps ensure complete protection of critical equipment.

CA08104001E For more information, visit: www.eaton.com/consultants Surge Protection (SPD) & Power Conditioning Products 34.1-2 Surge Protection Products—SPD September 2016 Sheet 34004 Facility-Wide Protection—SPD Series

22 10,000 SPD 23 480V 120/208V SPD High Energy Transient Disturbance Input at Main Panel 24 —IEEE Category C-High Impulse (Combination) Waveform, 10,000V, 10,000A Computer 5000 25 Stage 1 Protection Sensitive Best Achievable Performance (Service Entrance) Loads with Single SPD at 480V SPD250 Recommended 800 Main Panel (Stage 1) Stage 2 Protection

26 (Branch Entrance) (V) Let-Through Voltage SPD200 Recommended Two Stage use of SPDs 400 System Test Parameters: (Cascade Approach) Achieves Best Possible Surge Protection (Stage 2) 27 IEEE C62.41 and C62.45 test procedures using C-High impulse 480V main entrance panels; 100 ft (30m) of three-phase wire; 480/208V 0 distribution ; and 120/208V branch 25μS 50μSS 28 SPD Series Unit Time (Microseconds)

29 Figure 34.1-2. IEEE Emerald Book Recommends a Cascaded (or Two-Stage) Approach System Application Surge Current Capacity 30 The SPD applications covered under The minimum surge current capacity this section include distribution and that the device is capable of withstand- branch panel locations, busway, motor ing shall be as shown in Table 34.1-1. 31 control centers (MCC), switchgear SPD Type and switchboard assemblies. All SPDs shall be tested and demonstrate All SPDs installed on the line side 32 suitability for application within of the service entrance disconnect ANSI/IEEE C62.41 Category C, B shall be Type 1 SPDs. All SPDs and A environments. installed on the load side of the service entrance disconnect shall 33 be Type 1 or Type 2 SPDs.

34 Table 34.1-1. Surge Current Capacity Minimum Surge Current Capacity Based on ANSI/IEEE C62.41 Location Category Category Application Per Phase Per Mode 35 C Service entrance locations (switchboards, 250 kA 125 kA switchgear, MCC, main entrance) B High exposure roof top locations 160 kA 80 kA 36 (distribution panelboards) A Branch locations (panelboards, MCCs, busway) 120 kA 60 kA 37 Features 38 Table 34.1-2. Eaton Surge Protection Model Features Product L to N L to G Per EMI/RFI Nominal Short- Alarm Audible Surge Warranty Enclosure Disconnect Integrated Series Protection and N to G Phase kA Filtering Discharge Circuit Contacts Alarm Counter (Years) Options (Option) Mounting Mode Protection Range Attenuation Current Current (Option) (Option) (Option) (NEMA (Option) 39 Modes (In) Rating Ty p e s ) (SCCR) 4 SPD Yes Yes 50–400 50 dB 20 kA 200 kA Yes Yes Yes 15 1, 4 & 4X Yes Yes 40 4 SPM Yes Yes 100–800 50 dB 20 kA 200 kA Yes Yes Yes 20 4 & 4X Yes No 4 SPC Yes Yes 50–200 40 dB 20 kA 200 kA Yes Yes No 10 4X No No 1 2 41 CVX Yes Yes 50–100 No 20 kA 100 kA No No No 5 4X No No 3 SP1 Yes No 50 only No 20 kA 200 kA No No No 2 4 No No SP2 Yes No 45 only No 10 kA 200 kA No No No 2 4X No No 42 1 100 kA units only. 2 480L, 600D, and 600Y units rated 10 kA I . 3 n 600Y and 600D units rated 10 kA I . 4 n 4 3 With on-line product registration.

For more information, visit: www.eaton.com/consultants CA08104001E Surge Protection (SPD) & Power Conditioning Products 34.1-3 September 2016 Surge Protection Products—SPD Sheet 34005 SPD Series

Integrated Surge Protection 208Y/120V Panelboard 22 Eaton was the first to introduce the 700–800V “Direct-On™ bus bar” connect SPD •Based on IEEE that provides customers with the lowest C62.41 (2002) 23 Cable Connected SPD Combination Wave system let-through voltage at the bus (14-Inch Cable Lead Length to Bus Bar) bar when compared to traditional cable connected surge protectors. 24

By using a direct bus bar connection, 500–600V the SPD Series achieves the industry’s 25 lowest let-through voltage—effectively Integrated SPD System suppressing both high and low energy transient events providing protection 26 for all connected electronic loads. This at Bus Bar Let-Through Voltage design provides superior suppression ratings and eliminates poor performance 05 10 27 that results from cable connections Time (microseconds) and/or long lead lengths. Figure 34.1-3. 120V/208Y Panelboard—Integrated SPD vs. Cable Connected 28 Other Products Other surge suppressor manufacturers’ measurements are made at the SPD 29 module or the suppressor’s terminals, not at the electrical distribution equip- ment’s bus bar. The distance between 30 module or suppressor terminals and the distribution equipment bus bar is often 14.00 inches (355.6 mm) or 31 more. The impedance associated with cabling required to connect the surge suppressor to the electrical 32 distribution equipment (also referred to as lead length) significantly effects the overall performance of the surge 33 suppressor and results in an increase in let-through voltage. 34

35

36 The SPD Series is also available as an integrated unit interfaced via a circuit In this installation, the SPD Series is breaker resident in the electrical assembly. 37 mounted directly to the panelboard’s bus This installation keeps connected lead bars. This type of installation will provide lengths short while providing a means of the best possible surge protection by disconnecting power to the unit quickly minimizing the connected lead length. 38 and easily. 39

40

41

42

4 3 SPD Series Unit Integrated Within an Eaton Pow-R-Line 1a Panelboard

CA08104001E For more information, visit: www.eaton.com/consultants Surge Protection (SPD) & Power Conditioning Products 34.1-4 Surge Protection Products—SPD September 2016 Sheet 34006 Let-Through Voltage Consideration

22 Integrated Panelboard SPD

23

24

25

26

27 SPD 28 Ground Connection 29 SPD 30 Neutral Connection (Connected 31 and Trimmed by Installer) 32

33 Form C Contacts Wiring 34

Integrated SPD Series Unit in PRL1a Panel Direct Bus Mounted SPD Series Unit in a PRL1a Panel 35 (Shown with Option SPD Integral Disconnect) Another distinct advantage that Eaton integrated SPDs offer Integral Disconnect Option—For PRL1a, 2a, 3a, and is the availability of neutral and ground connections on both 36 3E panelboards. sides of the unit. This enables both the neutral and ground wires to be kept as short as possible. Only one neutral and For applications where load interruptions are intolerable, ground connection is required, with the connection point an internal dedicated SPD disconnect option chosen for each being the one that is in closest proximity 37 is available. SPD is cable connected via a three-pole 30 A to the neutral and ground bars. circuit breaker. (Breaker rating and type dependent on panel type.) In a sidemount installation, either the neutral or ground 38 wire connection will be very long, decreasing the installed Note: The addition of the SPD circuit breaker adds 100 V to the published SPD let-through voltage ratings. See Page 34.1-5. performance of the unit. When a sidemount SPD is installed, its wires enter on one side of the panel. If that point of entry 39 is closest to the panel’s ground bar, the ground wire is short and the neutral wire must stretch to the opposite side of the panel where the neutral bar is located. If the SPD’s wires 40 enter on the side of the panel where the neutral bar is located, the neutral wire is kept short but the ground wire 41 will be much longer. The presence of neutral and ground connections on both sides of an integrated unit keeps both leads as short as 42 possible, increasing the installed performance of the unit.

4 3

For more information, visit: www.eaton.com/consultants CA08104001E Surge Protection (SPD) & Power Conditioning Products 34.1-5 September 2016 Surge Protection Products—SPD Sheet 34007 Facility-Wide Protection—SPD Series

Retrofit Installation Recommendations to 22 Reduce Let-Through Voltage When installing a surge suppressor in 23 a retrofit environment, it is important to mount the suppressor as close to the electrical equipment as possible, 24 keep the wiring (lead length) between the electrical equipment and the suppressor as short as possible 25 (less than 14.00 inches (355.6 mm) is recommended), and twist/wire tie the conductors to reduce inductive 26 effects. Eaton SPD, SPC, SPM, CVX, SP1 and SP2 Series offer side-mount surge protection. 27 SPD Series Sidemount Unit As shown in Figure 34.1-4 below, installation lead length reduces the 28 performance of any surge suppressor. For each inch of wiring (installation lead length), add 15 V to 25 V to the surge 29 suppressor’s published let-through value (e.g., suppressor let-through at 400 V and installation of 3 ft (0.9 m) 30 of cable = 1000 V installed rating). Sidemount Installation Recommendations Eaton SPD, SPC, SPM, CVX, SP1 and 31 SP2 Series devices passed UL 1449 4th edition testing without an external 1000 Wire Size overcurrent protection device (OCPD) 900 32 and therefore do not require an OCPD 14 AWG 800 209V (23%) unless otherwise required by NEC, UL 10 AWG and local electrical requirements to 700 4 AWG 33 protect electrical conductors. NEC 600 673V (75%)

Article 310.15 (B) (16) defines the 500 maximum rating of the OCPD required 34 to protect the electrical conductors. 400 NEC shows #10 AWG conductors at 300 60 °C typically requiring a single-pole 200 35

(for single-phase systems), two-pole 100

(for split-phase systems) or three-pole Additional Let-Through Voltage 0 (for three-phase systems) 30 A (Additional to device “Let Through”) 36 branch circuit breaker to protect 3 ft (0.9m) Lead Length 1 ft (0.3m) Lead Length SPD conductors. Loose Wiring Twisted Wires Twisted Wires 37 Installation Criteria Order of Importance: 1) Lead Length—75% reduction 2) Twisting Wires—23% reduction 38 3) Larger Wire—minimal reduction 39

Figure 34.1-4. Let-Through Graph 40

41

42

4 3

CA08104001E For more information, visit: www.eaton.com/consultants Surge Protection (SPD) & Power Conditioning Products 34.1-6 Surge Protection Products—SPD September 2016 Sheet 34008 SPD Series

SPD Series Sidemount Units Three Feature Package 22 Options Available The SPD Series provides users with 23 the option of selecting between three feature packages. These feature packages are the basic, standard 24 and standard with surge counter. The proper feature package can be selected based on the requirements 25 of the application or specification. A side by side comparison of the individual features found in each 26 package is below. SPD Series Sidemount Units Basic Feature Package 27 The basic feature package is perfect General Description Features, Benefits for applications where basic, cost- effective, safe and reliable surge 28 Eaton’s SPD Series surge protective and Functions protection is required, but budgets devices are the latest and most don’t allow for extra, additional features. ■ Uses thermally protected metal advanced UL® 1449 4th Edition oxide varistor (MOV) technology Rather than sacrifice performance or 29 certified surge protectors. Units safety due to cost, SPD Series units are available integrated within Eaton ■ Three feature package options with the basic feature package provide electrical assemblies, including panel- ■ True protection status indicators you with high-performing surge 30 boards, switchboards, motor control report the status of the protection protection without sacrificing safety centers, switchgear, automatic transfer elements, not the status of the or reliability. The basic feature package switches and bus plugs. applied power provides the same level of surge 31 ■ Available integrated within the protection and safety provided by following Eaton electrical assem- the standard and standard with surge blies: panelboards, switchboards, counter feature packages minus some 32 motor control centers, switchgear, of the features found in them. The automatic transfer switches and package contains dual-colored protection bus plugs status LEDs that report the true status 33 ■ 10-year warranty of the protection in each phase/mode. (15-year with registration) All four-wire plus ground units also contain an additional set of dual- 34 Safety Features colored protection status LEDs that SPD Series Integrated Units report the status of the protection in ■ All units use thermally protected the neutral/ground mode. 35 A complete offering of sidemount metal oxide varistor technology units designed for mounting external (MOV) as their core surge suppres- Standard Feature Package to electrical distribution equipment sion component. Usage of this The standard feature package includes 36 is also available. Application of SPD technology ensures safe operation all of the features found in the basic Series units throughout a facility will when the unit is subjected to feature package, plus an audible alarm ensure that equipment is protected abnormal conditions such as with silence button, EMI/RFI filtering, 37 with the safest and most reliable surge temporary overvoltage or high and a Form C relay contact that can protective devices available. SPD fault current conditions. Under such be used for remote annunciation of Series units are available in all conditions, the thermally protected the SPD’s status. The audible alarm 38 common voltages and configurations MOVs are removed from the circuit activates and the Form C relay contact and also in a variety of surge current quickly and safely before a poten- changes state when any loss of protec- capacity ratings from 50 through tially unsafe condition can occur tion is detected or a fault condition 39 400 kA. Three feature package options ■ SPD Series units contain no replace- exists with the unit. Should such a are also available to choose from, able parts such as surge modules, condition occur, the audible alarm ensuring the proper unit is available fuses, or surge counter memory can be silenced by pressing the silence 40 for a variety of applications. backup batteries. This prevents button. The EMI/RFI filter provides up potential arc flash and shock to 50 dB of noise attenuation over the hazards, as the units require no range of 10 kHz through 100 MHz. 41 periodic service or user intervention after installation ■ Integrated versions of the unit 42 are factory installed and sidemount versions are factory sealed. These important safety measures further 4 3 enhance user safety

For more information, visit: www.eaton.com/consultants CA08104001E Surge Protection (SPD) & Power Conditioning Products 34.1-7 September 2016 Surge Protection Products—SPD Sheet 34009 SPD Series

Standard with Surge Counter Table 34.1-3. Side-By-Side Comparison of the SPD Series’ Available Feature Packages Feature Package Feature Package Basic Standard Standard with 22 The standard with surge counter Comparison Surge Counter feature package includes all of the features found in the standard feature UL 1449 4th Edition Type ■■ ■ 23 package plus a six-digit surge counter Surge protection using thermally protected ■■ ■ with a reset button. The surge counter MOV technology indicates the ongoing count of the Dual-colored protection status indicators ■■ ■ 24 number of surges the unit has been for each phase exposed to and stores them in Dual-colored protection status indicators — ■■ nonvolatile memory. Should power for the N–G protection mode 25 to the SPD Series unit be completely Audible alarm with silence button — ■■ interrupted, the surge counter will Form C relay contact — ■■ recall and display the surge count prior EMI/RFI filtering, providing up to 50 dB of noise — ■■26 to the interruption when power attenuation from 10 kHz to 100 MHz is restored. Unlike many surge Surge counter with reset button —— ■ protectors, the SPD Series’ surge 27 counter memory feature does not require a backup battery that would Standards and Certifications Technical Data require periodic replacement in order and Specifications 28 to achieve its memory functionality. ■ Integrated versions of the unit are UL 1449 4th Edition recognized ■ 20 kA nominal discharge current components for the United (I ) rating (maximum rating 29 States and Canada, covered n assigned by UL) by Underwriters Laboratories certification and follow-up service ■ 50 through 400 kA surge current capacity ratings 30 ■ Sidemount versions are UL 1449 4th Edition listed devices and are also ■ 200 kA short-circuit current CSA® approved rating (SCCR) 31

32

33

34

35

36

37

38

39

40

41

42

4 3

CA08104001E For more information, visit: www.eaton.com/consultants Surge Protection (SPD) & Power Conditioning Products 34.1-8 Surge Protection Products—SPD September 2016 Sheet 34010 SPD Series

Table 34.1-4. Integrated Product Applications 22 Switchboard Switchgear Motor Control Centers

23

24

25

26 Features: Features: Features: ■ The SPD can be integrated into any ■ Available on all switchgear designs ■ Ideal protection for PLCs, sensors, drives, switchboard ■ Disconnect is a standard feature electronic starters, or other digital equipment 27 ■ Specifiers have the flexibility to install the ■ Unique design minimizes installation ■ SPD is designed to fit in Freedom 2100 in a SPD in any location within the switchboard impedance standard (3X) size 18-inch (457.2 mm) ■ Disconnect switch is a standard feature ■ SPD250 ideal for critical industrial compartment 28 ■ Unique design minimizes installation switchgear applications ■ May be used in new/aftermarket applications impedance ■ Ideal for water treatment, petrochemical and other industrial applications 29 Safety Standards: Safety Standards: Safety Standards: ■ UL 891 (Switchboard) ■ UL 1558 (Switchgear) ■ UL 845 (MCC) ■ UL 1449 4th Edition (Surge Suppressor) ■ UL 1449 4th Edition (Surge Suppressor) ■ UL 1449 4th Edition (Surge Suppressor) 30 ■ UL 1283 5th Edition (EMI/RFI Filter) ■ UL 1283 5th Edition (EMI/RFI Filter) ■ UL 1283 5th Edition (EMI/RFI Filter) ■ CSA C22.2 Certified (Suppressor) ■ CSA C22.2 Certified (Suppressor) ■ CSA C22.2 Certified (Suppressor) 31 Panelboards Busway Retrofit 32

33

34

35 Features: Features: Features: ■ The SPD is used extensively on branch ■ Ideal for busway fed distribution systems ■ SPD units can be externally mounted to panelboards for computer rooms, laboratories, ■ Easy to install SPD units fit in standard bus existing distribution equipment 36 schools, hospitals and industrial applications plug assembly ■ Standard NEMA 1, 4 or 4X enclosures ■ 200% rated neutral is provided for non-linear ■ Isolates critical busway sections from nearby ■ Requires field installation loads disturbance producing loads ■ SPD Retrofit 50–400 kA/phase units 37 ■ Cost-effective branch protection (assumes ■ Designed for new and existing facilities main panel protection employed) ■ Integral disconnect Safety Standards: Safety Standards: Safety Standards: 38 ■ UL 67 (Panelboards) ■ UL 857 (Busway) ■ UL 1449 4th Edition (Surge Suppressor) ■ UL 1449 4th Edition (Surge Suppressor) ■ UL 1449 4th Edition (Surge Suppressor) ■ UL 1283 5th Edition (EMI/RFI Filter) ■ UL 1283 5th Edition (EMI/RFI Filter) ■ UL 1283 5th Edition (EMI/RFI Filter) ■ CSA C22.2 Certified (Suppressor) 39 ■ CSA C22.2 Certified (Suppressor) ■ CSA C22.2 Certified (Suppressor)

Note: The SPD Surge components can be integrated into safety switches, automatic transfer switches (ATS) and other assemblies. 40 Contact your local Eaton sales office.

41

42

4 3

For more information, visit: www.eaton.com/consultants CA08104001E Surge Protection (SPD) & Power Conditioning Products 34.1-9 September 2016 Surge Protection Products—SPD Sheet 34011 SPD Series

Catalog Numbering System 22 Table 34.1-5. SPD Series Units Mounted Internal to Electrical Distribution Equipment (Integrated Units) 23 SPD 250 480D 2 J

2 24 Series Application—Integrated Units SPD = Surge protective kA Rating A = Panelboards (PRL1a, 2a, 3a, 3E), device 050 = 50 kA per phase Voltage Code direct bus mounted 25 080 = 80 kA per phase 240S = 120/240 single split-phase B = Switchgear (includes remote display) 100 = 100 kA per phase 208Y = 120/208 wye (4W+G) C = Panelboards (PRL1a, 2a, 3a, 3E, 4), 120 = 120 kA per phase 220Y = 127/220 wye (4W+G) switchboards, busway 160 = 160 kA per phase 400Y = 230/400 wye (4W+G) J = Motor control centers 26 200 = 200 kA per phase 480Y = 277/480 wye (4W+G) 250 = 250 kA per phase 600Y = 347/600 wye (4W+G) 300 = 300 kA per phase 240D = 240 delta (3W+G) Feature Package 27 400 = 400 kA per phase 480D = 480 delta (3W+G) 1 = Basic 600D = 600 delta (4W+G) 2 = Standard 240H = 240 high-leg delta (4W+G) 3 = Standard + surge counter 1 on ‘B’ phase 28

1 Please consult the factory for 240 high-leg delta (4W+G) applications with high leg on ‘C’ phase. 2 29 Units used in PRL1a, 2a, 3a and 3E panelboard applications are available in 50–200 kA ratings only. Use the ‘C’ option for PRL1a, 2a, 3a and 3E panelboard applications when unit is connected through a circuit breaker. Example: SPD250480D2J = SPD Series, 250 kA per phase, 480D voltage, standard feature package, motor control center application. 30 Table 34.1-6. SPD Series Units for Mounting External to Electrical Distribution Equipment (Sidemount Units) 31 SPD 250 480D 2 K 32 Series Application—Sidemount Units SPD = Surge protective kA Rating K = NEMA 1 enclosure 4 device 050 = 50 kA per phase Voltage Code L = NEMA 1 flushmount enclosure 33 080 = 80 kA per phase 240S = 120/240 single split-phase M = NEMA 1 enclosure with internal 100 = 100 kA per phase 208Y = 120/208 wye (4W+G) disconnect 120 = 120 kA per phase 220Y = 127/220 wye (4W+G) N = NEMA 4 enclosure 160 = 160 kA per phase 400Y = 230/400 wye (4W+G) O = NEMA 4 enclosure with internal 34 200 = 200 kA per phase 480Y = 277/480 wye (4W+G) disconnect 250 = 250 kA per phase 600Y = 347/600 wye (4W+G) P = NEMA 4X enclosure (stainless steel) 300 = 300 kA per phase 240D = 240 delta (3W+G) Q = NEMA 4X enclosure with internal 35 400 = 400 kA per phase 480D = 480 delta (3W+G) disconnect (stainless steel) 600D = 600 delta (4W+G) 240H = 240 high-leg delta (4W+G) 3 on ‘B’ phase Feature Package 36 1 = Basic 2 = Standard 3 = Standard + surge counter 37

3 Please consult the factory for 240 high-leg delta (4W+G) applications with high leg on ‘C’ phase. 4 NEMA 1 flushmount units are available in 50–200 kA ratings only. 38 Example: SPD250480D2K = SPD Series, 250 kA per phase, 480D voltage, standard feature package, housed in NEMA 1 enclosure. 39

40

41

42

4 3

CA08104001E For more information, visit: www.eaton.com/consultants Surge Protection (SPD) & Power Conditioning Products 34.1-10 Surge Protection Products—SPD September 2016 Sheet 34012 SPD Series

22 Dimensions in Inches (mm) Standard Dimensions —Integrated Units 23

Mounting 0.22 3x Bus Mounting 8.80 (5.6) 24 (223.5) 4.40 0.19 (111.8) 4x Mounting 0.04 2.02 2.02 25 0.34 (4.8) Bus (1.0) (51.2) (51.2) (8.6)

0.95

NEUTRALNEUTRAL NEUTRAL 26 (24.1) NEUTRAL

5.40 27 Mounting Ῡ CAUTION (137.2) 3.42 (86.9) 4.66 3.42 (118.4)

28 (86.9) FORM “C” CONTACTS GROUND

SURGE SURGE GROUND SURGE

SURGE SURGE 29 GROUND GROUND 2.52 3.42 0.22 0.26 4x Mounting (64.0) (86.9) (5.6) (6.6) 30 3.45 Terminals 4x #10–32 x 0.38 DP (87.6) 8.74 Brass Terminals (222.0) 31 9.50 (241.3)

32 Figure 34.1-5. 50–200 kA Integrated Units

33 Mounting 8.80 4x Mounting (223.5) 34 2.52 3.42

(64.0) (86.9)

GROUND GROUND SURGE

35 SURGE SURGE GROUND SURGE

36 IN. LBS. IN. 36 GROUND 3.42 Mounting FORM “C” CONTACTS (86.9) 3.42 CAUTION Ῡ 5.40 36 (86.9) (137.2) 4.66 37 (118.4)

1.71 36 IN. LBS.

NEUTRAL NEUTRAL NEUTRAL

38 (43.4) NEUTRAL Terminals 0.22 4.85 4x Mounting (123.2) 8.74 (5.6) 39 (222.0) 5.78 9.50 4x #10–32 x 0.38 40 (146.8) (241.3) DP Brass Terminals Figure 34.1-6. 250–400 kA Integrated Units 41 Weights ■ 50–200 kA units approximately 3.5 lb (1.6 kg) 42 ■ 250–400 kA units approximately 7.0 lb (3.2 kg)

4 3

For more information, visit: www.eaton.com/consultants CA08104001E Surge Protection (SPD) & Power Conditioning Products 34.1-11 September 2016 Surge Protection Products—SPD Sheet 34013 SPD Series

Standard Dimensions—Sidemount Units 22

7.28 7.28 (184.9) 1.00 Flushmount Panel (184.9) 1.00 23 5.27 (25.4) (4) #8–32 Flat Hd Screws 5.27 (25.4) (133.9) (133.9) 24

10.48 12.05 (306.1) (266.2) 8.00 25 (203.2) 12.05 10.48 11.25 (266.2) (285.8) 11.25 (306.1) 0.68 0.68 (285.8) 26 (17.3) (17.3) 5.24 14.00 5.24 (133.1) (355.6) (133.1) Ø0.20 (Ø5.1) 27 Ø0.20 (Ø5.1) 0.78 (19.8) 5.00 2.00 3.48 0.11 0.40 7.47 (127.0) 28 (50.8) 0.40 2.00 (88.4) (2.8) (10.2) 0.78 (189.7) 7.47 3.48 (10.2) (50.8) 4.41 (19.8) 1.76 (189.7) 0.98 (88.4) (112.0) (44.7) (24.9) 4.41 11.00 29 (112.0) (279.4)

Figure 34.1-7. 50–200 kA Units in a NEMA 1 Rated Enclosure, Figure 34.1-9. 50–200 kA Units in a NEMA 1 Rated Flushmount 30 Weight = 6.8 lb Enclosure, Weight = 6.8 lb

1.00 31 5.47 (25.4) 6.69 9.14 (138.9) (169.9) (232.2) 32

12.30 0.66 12.05 (312.4) (16.8) 33 10.48 11.50 (306.1) 11.25 (266.2) 2.61 10.73 (292.1) (285.8) (66.3) (272.5) 0.67 34 5.24 (17.0) (133.1)

2.75 Ø0.20 35 Ø0.20 2.00 0.78 (69.9) (Ø5.1) 11.14 (Ø5.1) 7.47 (19.8) (283.0) (50.8) 0.40 5.76 0.78 5.76 (189.7) (19.8) (10.2) (146.3) (146.3) 6.55 36 6.69 (166.4) (169.9) 37 Figure 34.1-8. 250–400 kA Units in a NEMA 1 Rated Enclosure, Figure 34.1-10. 50–400 kA Units in a NEMA 1 Rated Enclosure with Weight = 13.5 lb Internal Disconnect, Weight = 14.7 lb 38

39

40

41

42

4 3

CA08104001E For more information, visit: www.eaton.com/consultants Surge Protection (SPD) & Power Conditioning Products 34.1-12 Surge Protection Products—SPD September 2016 Sheet 34014 SPD Series

Standard Dimensions—Sidemount Units 22

23 SPD Series Surge Protective Device 13.50 SPD Series 12.50 (342.9) Surge Protective Device (317.5) 11.75 12.75 24 (298.5) 11.98 (323.9) (304.3) 10.98 12.28 (278.9) 11.28 3.12 (311.9) (286.5) (79.2)

5.49

25 Device Protective Surge

0.65 0.65 Device Protective Surge

SPD Series SPD (139.4) Series SPD (16.5) (16.5) 26 2.60 0.76 3.36 10.18 Ø0.33 0.76 6.00 (66.0) (19.3) (85.3) (258.6) (Ø8.4) (19.3) (152.4) Ø0.33 7.68 12.47 5.39 8.65 (Ø8.4) (195.1) (316.7) 27 (136.9) (219.7)

28 Figure 34.1-11. 50–200 kA Units in a NEMA 4 or 4X Rated Enclosure, Figure 34.1-13. 50–400 kA Units in a NEMA 4 or 4X Rated Enclosure with Weight = 14.6 lb Internal Disconnect, Weight = 27.5 lb 29

SPD Series Surge Protective Device 10.98 11.28 30 (278.9) (286.5) 11.75 12.50 (298.5) 31 (317.5)

5.49 0.65 Device Protective Surge

(139.4) (16.5) Series SPD 32 4.10 6.00 0.76 (104.1) (152.4) Ø0.33 (19.3) 7.68 8.65 (8.4) 33 (195.1) (219.7)

Figure 34.1-12. 250–400 kA Units in a NEMA 4 or 4X Rated Enclosure, 34 Weight = 14.6 lb

35

36

37

38

39

40

41

42

4 3

For more information, visit: www.eaton.com/consultants CA08104001E Surge Protection (SPD) & Power Conditioning Products 34.1-13 September 2016 Surge Protection Products—SPD Sheet 34015 SPD Series

Technical Data 22 Table 34.1-7. SPD Series Specifications Description Specification 23 Surge capacity ratings available 50, 80, 100, 120, 160, 200, 250, 300, 400 kA per phase Nominal discharge current (In) 20 kA (maximum rating assigned by UL) Short-circuit current rating (SCCR) 200 kA 24 SPD type Basic feature package = Type 1 (can also be used in Type 2 applications) Standard and standard with surge counter feature packages = Type 2 25 Single split-phase voltages available 120/240 Three-phase wye system voltages available 120/208, 127/220, 230/400, 277/480, 347/600 Three-phase delta system voltages available 240, 480, 600 26 Input power frequency 50/60 Hz Power consumption (basic units): 208Y, 220Y, 240S, 240D and 240H voltage codes 0.5 W 27 400Y, 480Y and 480D voltage codes 1.1 W 600Y and 600D voltage codes 1.3 W Power consumption (standard and standard with surge counter units): 28 208Y, 220Y, 240S, 240D and 240H voltage codes 0.6 W 400Y, 480Y and 480D basic voltage codes 1.7 W 600Y and 600D voltage codes 2.1 W 29 Protection modes Single split-phase L-N, L-G, N-G, L-L Three-phase wye L-N, L-G, N-G, L-L Three-phase delta L- G , L- L Three-phase high-leg delta L-N, L-G, N-G, L-L 30 Maximum continuous operating voltage (MCOV): 240S, 208Y, 220Y and 240H MCOV 150 L-N, 150 L-G, 150 N-G, 300 L-L 400Y and 480Y MCOV 320 L-N, 320 L-G, 320 N-G, 640 L-L 31 600Y MCOV 420 L-N, 420 L-G, 420 N-G, 840 L-L 240D MCOV 320 L-G, 320 L-L 480D MCOV 640 L-G, 640 L-L 600D MCOV 840 L-G, 840 L-L 32 Ports 1 Operating temperature –40 °F through 122 °F (–40 °C through 50 °C) 33 Operating humidity 5% through 95%, noncondensing Operating altitude Up to 16,000 ft (5000 m) Seismic withstand capability Meets or exceeds the requirements specified in IBC 2006 and CBC 2007 34 Form C relay contact ratings 150 Vdc or 125 Vac, 1A maximum Form C relay contact logic Power ON, normal state—NO contact = open, NC contact = closed Power OFF or fault state—NO contact = closed, NC contact = open 35 EMI/RFI filtering attenuation Up to 50 dB from 10 kHz to 100 MHz 36

37

38

39

40

41

42

4 3

CA08104001E For more information, visit: www.eaton.com/consultants Surge Protection (SPD) & Power Conditioning Products 34.1-14 Surge Protection Products—SPD September 2016 Sheet 34016 SPD Series

Voltage Protection It is important that users are familiar The higher VPR rating of 700 V is likely 22 with the difference in testing methods caused by the higher level of surge Rating (VPR) and the subsequent effect on the value current during the measured limiting of the VPR. Without considering or voltage test. In order to make an 23 The measured limiting voltage test in understanding the differences in the accurate assessment of devices, the UL 1449 4th Edition uses a 6 kV/3 kA level of currents used in the test, one VPR rating of one device must be combination wave surge to determine might assume that a UL 1449 4th Edition compared with the VPR rating of 24 the voltage protection rating (VPR) device with a VPR of 700 V has a higher another device. Comparing a VPR of the SPD. This test is similar to the limiting voltage than a UL 1449 2nd rating to an SVR rating yields no useful suppressed voltage rating (SVR) as Edition device with an SVR of 400 V. or conclusive information. 25 performed in UL 1449 2nd Edition. The Such a conclusion would be inaccurate. key difference between the tests in the 2nd Edition and the 4th Edition is that Table 34.1-9. VPR Ratings for 80–400 kA Units Rated 120/240 V Single Split-Phase 1 26 the magnitude of the current used for the test is six times greater in the 4th Type (All Voltage Code 240S) Protection Mode Edition versus the 2nd Edition. This L-N L-G N-G L-L 2 27 much higher current level will mean Integrated direct bus connected 500 600 500 900 that the measured limiting voltage will Integrated circuit breaker connected 700 700 700 1000 likely be significantly higher for the Sidemount NEMA 1 700 800 700 1200 28 higher current level. For example, the Sidemount NEMA 1 with breaker 800 900 700 1500 VPR for an SPD will likely be much Sidemount NEMA 4/4X 900 900 700 1200 higher than the SVR of an identical Sidemount NEMA 4/4X with breaker 900 900 700 1500 1 29 SPD. With higher current levels come Highest VPR shown for each model and mode. Specific units may have lower VPR ratings based higher limiting voltages. Please note upon options used. Refer to specific VPR ratings shown in TD01005006E for integrated SPDs and TD01005025E for sidemount SPDs. that VPR ratings fall into predefined 2 30 voltage categories as outlined in the Direct bus connected not available above 200 kA. UL 1449 4th Edition. The standard Note: VPR ratings of 50 kA units and ratings of each specific configuration can be found in VPR voltages are shown in the TD01005006E for integrated SPDs and TD01005025E for sidemount SPDs. following table. 31 Table 34.1-10. VPR Ratings for 80–400 kA Units Rated 120/208 V Wye (4W + G) 3 Table 34.1-8. Voltage Protection Ratings and 127/220V Wye (4W +G) 32 Measured Minimum Voltage Type (All Voltage Code 208Y and 220Y) Protection Mode Limiting Voltage Protection Rating L-N L-G N-G L-L (VPR) 4 Integrated direct bus connected 500 600 500 900 33 330 V or Less 330 Integrated circuit breaker connected 700 700 700 1000 331 V to 400 V 400 Sidemount NEMA 1 700 800 700 1200 401 V to 500 V 500 Sidemount NEMA 1 with breaker 800 1200 700 1500 34 501 V to 600 V 600 Sidemount NEMA 4/4X 900 900 700 1500 601 V to 700 V 700 Sidemount NEMA 4/4X with breaker 900 900 700 1500 701 V to 800 V 800 3 Highest VPR shown for each model and mode. Specific units may have lower VPR ratings based 35 801 V to 900 V 900 upon options used. Refer to specific VPR ratings shown in TD01005006E for integrated SPDs and 901 V to 1000 V 1000 TD01005025E for sidemount SPDs. 4 1001 V to 1200 V 1200 Direct bus connected not available above 200 kA. 36 1201 V to 1500 V 1500 Note: VPR ratings of 50 kA units and ratings of each specific configuration can be found in 1501 V to 1800 V 1800 TD01005006E for integrated SPDs and TD01005025E for sidemount SPDs. 1801 V to 2000 V 2000 2001 V to 2500 V 2500 Table 34.1-11. VPR Ratings for 80–400 kA Units Rated 230/400 V Wye (4W + G) 37 5 2501 V to 3000 V 3000 and 277/480 V Wye (4W +G) 3001 V to 4000 V 4000 Type (All Voltage Code 400Y and 480Y) Protection Mode 38 Therefore, if an SPD is tested with a L-N L-G N-G L-L 6 kV/3 kA combination wave surge and 6 Integrated direct bus connected 1000 1200 1000 1800 the let-through voltage is measured Integrated circuit breaker connected 1200 1200 1200 1800 39 to be 610 V, the SPD is given a VPR of Sidemount NEMA 1 1200 1200 1200 2500 700 V. The SPD is given the same Sidemount NEMA 1 with breaker 1500 1500 1200 2500 700 V VPR if the same test results in a Sidemount NEMA 4/4X 1200 1200 1200 2500 40 let-through voltage measurement of Sidemount NEMA 4/4X with breaker 1200 1500 1200 2500 5 698 V. Additionally, if the let-through Highest VPR shown for each model and mode. Specific units may have lower VPR ratings based voltage is measured to be 2005 V, the upon options used. Refer to specific VPR ratings shown in TD01005006E for integrated SPDs and 41 SPD is given a VPR of 2500 V. TD01005025E for sidemount SPDs. 6 Direct bus connected not available above 200 kA. Note: VPR ratings of 50 kA units and ratings of each specific configuration can be found in 42 TD01005006E for integrated SPDs and TD01005025E for sidemount SPDs.

4 3

For more information, visit: www.eaton.com/consultants CA08104001E Surge Protection (SPD) & Power Conditioning Products 34.1-15 September 2016 Surge Protection Products—SPD Sheet 34017 SPD Series

Table 34.1-12. VPR Ratings for 80–400 kA Units Rated 347/600 V Table 34.1-15. VPR Ratings for 80–400 kA Units Rated 600 V Wye (4W + G) 1 Delta (3W +G) 7 22 Type (All Voltage Code 600Y) Protection Mode Type (All Voltage Code 600D) Protection Mode L-N L-G N-G L-L L-N L-G N-G L-L 23 2 8 Integrated direct bus connected 1200 1500 1500 2500 Integrated direct bus connected N/A 2500 N/A 2500 Integrated circuit breaker connected 1500 1500 1500 2500 Integrated circuit breaker connected N/A 2500 N/A 2500 Sidemount NEMA 1 1500 1500 1500 2500 Sidemount NEMA 1 N/A 3000 N/A 2500 24 Sidemount NEMA 1 with breaker 1500 1500 1500 2500 Sidemount NEMA 1 with breaker N/A 3000 N/A 2500 Sidemount NEMA 4/4X 1500 1500 1500 2500 Sidemount NEMA 4/4X N/A 3000 N/A 2500 Sidemount NEMA 4/4X with breaker 1500 1500 1500 2500 Sidemount NEMA 4/4X with breaker N/A 2500 N/A 2500 1 7 25 Highest VPR shown for each model and mode. Specific units may have Highest VPR shown for each model and mode. Specific units may have lower VPR ratings based upon options used. Refer to specific VPR lower VPR ratings based upon options used. Refer to specific VPR ratings shown in TD01005006E for integrated SPDs and TD01005025E ratings shown in TD01005006E for integrated SPDs and TD01005025E for sidemount SPDs. for sidemount SPDs. 26 2 8 Direct bus connected not available above 200 kA. Direct bus connected not available above 200 kA. Note: VPR ratings of 50 kA units and ratings of each specific Note: VPR ratings of 50 kA units and ratings of each specific configuration can be found in TD01005006E for integrated SPDs configuration can be found in TD01005006E for integrated SPDs 27 and TD01005025E for sidemount SPDs. and TD01005025E for sidemount SPDs.

Table 34.1-13. VPR Ratings for 80–400 kA Units Rated 240 V Table 34.1-16. VPR Ratings for 80–400 kA Units Rated 240 V High-Leg 28 Delta (3W +G) 3 Delta (4W +G) 9 Type (All Voltage Code 240D) Protection Mode Type (All Voltage Code 240H) Protection Mode L-N L-G N-G L-L L-N L-G N-G L-L 29 4 Integrated direct bus connected N/A 1000 N/A 900 Integrated direct bus connected j 500 600 500 900 Integrated circuit breaker connected N/A 1200 N/A 1200 Integrated circuit breaker connected 700 700 700 1000 30 Sidemount NEMA 1 N/A 1000 N/A 1000 Sidemount NEMA 1 700 800 700 1200 Sidemount NEMA 1 with breaker N/A 1000 N/A 1000 Sidemount NEMA 1 with breaker 800 900 700 1500 Sidemount NEMA 4/4X N/A 1000 N/A 1000 Sidemount NEMA 4/4X 900 900 700 1500 31 Sidemount NEMA 4/4X with breaker N/A 1000 N/A 1000 Sidemount NEMA 4/4X with breaker 900 900 700 1500 3 9 Highest VPR shown for each model and mode. Specific units may have Highest VPR shown for each model and mode. Specific units may have lower VPR ratings based upon options used. Refer to specific VPR lower VPR ratings based upon options used. Refer to specific VPR ratings shown in TD01005006E for integrated SPDs and TD01005025E ratings shown in TD01005006E for integrated SPDs and TD01005025E 32 for sidemount SPDs. for sidemount SPDs. 4 Direct bus connected not available above 200 kA. j Direct bus connected not available above 200 kA. Note: VPR ratings of 50 kA units and ratings of each specific Note: VPR ratings of 50 kA units and ratings of each specific 33 configuration can be found in TD01005006E for integrated SPDs configuration can be found in TD01005006E for integrated SPDs and TD01005025E for sidemount SPDs. and TD01005025E for sidemount SPDs. 34 Table 34.1-14. VPR Ratings for 80–400 kA Units Rated 480 V Delta (3W +G) 5 Type (All Voltage Code 480D) Protection Mode 35 L-N L-G N-G L-L 6 Integrated direct bus connected N/A 1800 N/A 1800 36 Integrated circuit breaker connected N/A 2000 N/A 2000 Sidemount NEMA 1 N/A 2500 N/A 2500 Sidemount NEMA 1 with breaker N/A 2500 N/A 2500 37 Sidemount NEMA 4/4X N/A 2500 N/A 2500 Sidemount NEMA 4/4X with breaker N/A 2500 N/A 2500 5 Highest VPR shown for each model and mode. Specific units may have 38 lower VPR ratings based upon options used. Refer to specific VPR ratings shown in TD01005006E for integrated SPDs and TD01005025E for sidemount SPDs. 6 Direct bus connected not available above 200 kA. 39 Note: VPR ratings of 50 kA units and ratings of each specific configuration can be found in TD01005006E for integrated SPDs and TD01005025E for sidemount SPDs. 40

41

42

4 3

CA08104001E For more information, visit: www.eaton.com/consultants Surge Protection (SPD) & Power Conditioning Products 34.1-16 Surge Protection Products—SPD September 2016 Sheet 34018 SPD MAX Series

Feature Package Options 22 SPD MAX Series Features, Benefits Surge Protection and Functions The SPD MAX Series provides users with the option of selecting between 23 ■ Uses thermally protected metal two feature packages: basic and oxide varistor (MOV) technology standard with surge counter. The ■ Lockout and tagout provisions proper feature package can be 24 ■ Safety barriers selected based on the application’s requirements or specifications. ■ 20 kA nominal discharge current (In) See Table 34.1-17. 25 rating (maximum rating assigned by UL) Enclosure Options, ■ 100 kA through 800 kA surge current Dimensions and Weights 26 capacity ratings ■ Installation flexibility, #10 to 1/0 wire There are two enclosure options for may be used the SPD MAX Series, painted steel NEMA 4 or stainless steel NEMA 4X. ■ Two feature package options 27 The maximum weight of the SPD MAX ■ 200 kA short-circuit current rating Series is 52 lb. (SCCR) (maximum rating assigned 28 by UL) Performance Data SPD MAX Series ■ Field serviceable Table 34.1-18 contains representative 29 ■ 15-year warranty standard, voltage protection rating (VPR) data for General Description additional 5 years with product all SPD MAX Series voltage ratings, registration but the VPR varies based on the Eaton’s SPD MAX Series side-mounted feature package, kA rating, number 30 surge protective devices are the latest of modules, and enclosure option. and most advanced UL 1449 4th The UL website contains the actual Edition certified surge protectors. 31 VPR for every possible configuration. Applying SPD MAX Series units at main service entrances and critical loads 32 will ensure that equipment is protected with the safest and most reliable surge Table 34.1-17. Feature Package Comparison protective devices (SPDs) available. Feature Package Comparison Basic Standard with 33 Units are available in all common Surge Counter voltages and configurations, and also Surge protection using thermally protected MOV technology ■ ■ in a variety of surge current capacity ■■ 34 ratings from 100 kA through 800 kA. Dual-colored protection status indicators for each phase Additionally, you may choose from two Dual-colored protection status indicators for the N–G protection mode ■■ feature package options. Audible alarm with silence button — ■ 35 Form C relay contact — ■ Application Description EMI/RFI filtering that provides up to 50 dB of noise attenuation — ■ The breadth of the SPD MAX Series’ from 10 kHz to 100 MHz 36 features, options, and configurations Surge counter with reset button — ■ ensures that the correct unit is available for all electrical applications, including Table 34.1-18. ANSI/UL 1449 4th Edition Voltage Protection Ratings 37 service entrances, main switchgear, Nominal L–G L–L L–N N–G H–G H–L H–N motor control centers, distribution Voltage VPR VPR VPR VPR VPR VPR VPR switchboards, panelboards, and point- 208Y 800 1200 900 900 — — — 38 of-use applications. 220Y 800 1200 900 900 — — — 230L 1500 — 1500 1200 — — — Standards and Certifications 240D 1200 1200 — — — — — 39 240H 800 1200 900 900 1500 2000 1500 ■ UL 1449 4th Edition 240S 800 1200 900 900 — — — ■ UL 1283 5th Edition 400Y 1500 2000 1500 1200 — — — 40 480D 1500 2000 — — — — — ■ Canadian Standards Association (CSA) 480Y 1500 2000 1500 1200 — — — ■ Built in an ISO® 9001 facility 600D 1500 2500 — — — — — 41 ■ Designed and tested in 600Y 1500 2500 1800 1500 — — — accordance with: 42 ❑ IEEE C62.41.1 ❑ IEEE C62.41.2 4 3 ❑ IEEE C62.43-2005 ❑ IEEE C62.45-2002 ❑ IEEE C62.48-2005 ❑ IEEE C62.62-2010

For more information, visit: www.eaton.com/consultants CA08104001E Surge Protection (SPD) & Power Conditioning Products 34.1-17 September 2016 Surge Protection Products—SPD Sheet 34019 SPD MAX Series

Catalog Numbering System 22 Table 34.1-19. SPD MAX Series Catalog Numbering System 23 SPM 250 480D 3 R 24 SPM Application Suffix kA Rating Options R = 1 module, NEMA 4 enclosure with internal 1 100 = 100 kA per phase Feature Package Options circuit breaker 25 120 = 120 kA per phase 1 =Basic S = 2 module, NEMA 4 enclosure with internal 160 = 160 kA per phase Dual-colored LED per phase to circuit breaker 200 = 200 kA per phase indicate protection status. T = 1 module, NEMA 4 enclosure with internal 26 250 = 250 kA per phase Dual-colored LED to indicate terminal block 300 = 300 kA per phase protection status of the U = 2 module, NEMA 4 enclosure with internal 320 = 320 kA per phase N–G mode on units with a terminal block 400 = 400 kA per phase neutral wire. V = 1 module, NEMA 4X enclosure with internal 27 600 = 600 kA per phase 3 = Standard with surge counter. circuit breaker 800 = 800 kA per phase Dual-colored LED per phase to W= 2 module, NEMA 4X enclosure with internal indicate protection status. circuit breaker 28 X = 1 module, NEMA 4X enclosure with internal Voltage Code Options Dual-colored LED to indicate protection status of the terminal block 240S = 120/240 split-phase N–G mode on units with a Y = 2 module, NEMA 4X enclosure with internal 208Y = 120/208 wye (4W + G) neutral wire. terminal block 29 220Y = 127/220 wye (4W + G) Audible alarm with silence button. 400Y = 230/400 wye (4W + G) Form C relay contact. 600Y = 347/600 wye (4W + G) EMI/RFI filtering that provides up 30 240D = 240 delta (3W + G) to 50 dB of noise attenuation from 480D = 480 delta (3W + G) 10 kHz to 100 MHz. 600D = 600 delta (3W + G) Surge counter with alarm silence 240H = 240 delta high leg (reset) button. 31 (4W + G) on B phase 230L = 230 single-phase 32 1 Please consult the factory for 240 delta high leg (4W+G) applications with high leg on C phase. Example: SPD250480D3R = SPD MAX Series, 250 kA per phase, 480 D voltage, standard with counter features package, 33 NEMA 4 enclosure with internal circuit breaker. Table 34.1-20. Valid Module and Enclosure Configurations per kA 34 kA per Phase Number of Surge Modules Available Enclosure Options

100 kA Single module only R, T, V, X enclosures 120 kA Single module only R, T, V, X enclosures 35 160 kA Single module only R, T, V, X enclosures 200 kA Single or dual module All enclosures 250 kA Single module only R, T, V, X enclosures 36 300 kA Single module only R, T, V, X enclosures 320 kA Dual module only S, U, W, Y enclosures 400 kA Single or dual module All enclosures 37 500 kA Dual module only S, U, W, Y enclosures 600 kA Dual module only S, U, W, Y enclosures 800 kA Dual module only S, U, W, Y enclosures 38

39

40

41

42

4 3

CA08104001E For more information, visit: www.eaton.com/consultants Surge Protection (SPD) & Power Conditioning Products 34.1-18 Surge Protection Products—SPD September 2016 Sheet 34020 SPD MAX Series

22 Technical Data and Specifications Table 34.1-21. SPD MAX Series Specifications 23 Description Specification Surge current capacity per phase 100 kA, 120 kA, 160 kA, 200 kA, 250 kA, 300 kA, 320 kA, 400 kA, 600 kA, 800 kA ratings available Nominal discharge current (In) 20 kA 24 Short-circuit current rating (SCCR) 200 kA SPD type Basic feature package = Type 1 (can also be used in Type 2 applications) 25 Standard with surge counter feature package = Type 2 Enclosure types NEMA 4, NEMA 4X enclosure Circuit breaker—30 A Eaton catalog number: FDC3030L 26 Circuit Breaker Load and Line Terminal torque specifications #10 AWG 35 lb-in; #8 AWG 40 lb-in; #6–#4 AWG 45 lb-in; #3–1/0 AWG 50 lb-in (SPD maximum wire range #10–1/0 AWG) 27 Standard split phase voltages available 120/240 Single-phase 230 28 Three-phase wye system voltages available 120/208, 127/220, 230/400, 277/480, 347/600 Three-phase delta system voltages 240, 480, 600 Three-phase high leg delta system voltages 120/240 high leg phase wire will be identified with a tag from the factory 29 Input power frequency 50/60 Hz Power Consumption (Standard with Surge Counter Units) 30 208 Y, 220 Y, 230 L, 240 S, 240 D, and 240 H voltage codes 0.6 W 400 Y, 480 Y, and 480 D basic voltage codes 1.7 W 600 Y and 600 D voltage codes 2.1 W 31 Protection modes Single split phase L–N, L–G, N–G, L–L, single-phase L–N, L–G, N–G, three-phase delta L–G, L–L, three-phase wye L–N, L–G, N–G, L–L, three-phase high leg delta L–N, L–G, N–G, L–L Maximum Continuous Operating Voltage (MCOV) 32 230 V single-phase 320 V L–N, 320 V L–G, 320 V N–G 127 V/220 V wye, 120 V/240 V single split phase 150 V L–N, 150 V L–G, 150 V N–G, 300 V L–L 33 120 V/240 V hi leg 150 V L–N, 150 V L–G, 150 V N–G, 300 V L–L, 320 V H–N, 320 V H–G, 470 V H–L 230 V/400 V wye, 277 V/480 V wye 320 V L–N, 320 V L–G, 320 V N–G, 640 V L–L 347 V/600 V wye 420 V L–N, 420 V L–G, 420 V N–G, 840 V L–L 34 240 V delta 300 V L–G, 300 V L–L 480 V delta 640 V L–G, 640 V L–L 35 600 V delta 840 V L–G, 840 V L–L Ports 1 or 2 Operating temperature and humidity –20 °C through +50 °C (–4 °F through +122 °F), 5% through 95%, noncondensing 36 Storage temperature –20 °C through +50 °C (–4 °F through +122 °F) Operating altitude Up to 16,000 ft (5000 m) 37 Weight Not to exceed 52 lb Form C relay contact ratings Maximum 0.46 A, 150 Vac, 1 A, 30 Vdc Form C terminal block ratings Rated 300 V, 16 A, 30–12 AWG solid or stranded wire. Torque range 5–7 lb-in 38 Form C relay contact logic Power on, normal state—NO contact = OPEN, NC contact = CLOSED Power off, fault state—NO contact = CLOSED, NC contact = OPEN EMI/RFI filtering attenuation (standard with surge counter) Up to 50 dB from 10 kHz to 100 MHz 39 Standards / agency certifications UL 1449 4th Edition—standard for surge protective devices UL 1283 5th Edition—standard for EMI filters (Type 2 SPDs only) CSA Electrical Notice No. 516 Edition 1—surge/transient voltage suppressor 40 (excludes 230 L voltage code) CSA 22.2 NO. 8-M1986 Edition 4—EMI filters Warranty 15 years from the date of delivery to the purchaser, 20 years if the product is properly 41 registered at www.eaton.com RoHS compliant Yes 42

4 3

For more information, visit: www.eaton.com/consultants CA08104001E Surge Protection (SPD) & Power Conditioning Products 34.1-19 September 2016 Surge Protection Products—SPD Sheet 34021 SPD MAX Series

Dimensions 22

Optional Entry 23 2½ NPT Maximum 1Ø AWG Maximum 24 2.33 (59.14) 6.58 25 1.13 (167.09) (28.58) 1.63 (41.28) 26

27 ¾ NPT Maximum Form C Entry

12.00 28 (304.8) Mounting Dimension 29

30 2½ NPT Maximum Optimal Entry 16.00 1Ø Maximum (406.40) 31

16.75 17.50 (425.45) (444.50) Mounting 32 17.50 Dimension (444.50) 33 8.00 (203.20) 34

Scale 1000 35 2.33 14.91 (4X) Ø0.31 (59.14) (378.8) (Ø7.87) 1/4–20 Mounting 36 Hardware

¾ NPT Maximum 37 Form C Entry 38 8.32 1.13 (211.25) (28.58) 9.30 6.58 39 (236.30) (167.09) 2.33 (59.14) 40

2½ NPT Maximum 1.63 Optimal Entry (41.28) 41 0.50 1Ø Maximum (12.70) 13.00 (330.20) 42 14.00 (355.60) 4 3 Figure 34.1-14. SPD MAX Dimension in Inches (mm)

CA08104001E For more information, visit: www.eaton.com/consultants Surge Protection (SPD) & Power Conditioning Products 34.1-20 Surge Protection Products—SPC September 2016 Sheet 34022 SPC Series

22 Sidemount Surge Protective Features, Benefits Device for Commercial and and Functions 23 Light Industrial Applications ■ Uses thermally protected metal oxide varistor (MOV) technology ■ Proprietary tri-colored LED 24 protection status indicators showing results of continuous self-diagnostic testing, including 25 neutral-ground mode ■ 20 kA nominal discharge current (In) rating (maximum rating in the 26 UL 1449 4th Edition standard) ■ 50 through 200 kA per phase peak 27 surge current capacity ratings ■ Configure to order with eight custom feature combinations 28 ■ Corrosion-resistant NEMA 4X enclosure with mounting feet ■ 200 kA short-circuit current 29 rating (SCCR) SPC Series ■ Factory prewired with 36 inches of 10 AWG wire 30 ■ No user-serviceable parts or items SPC Device Mounted to General Description requiring periodic maintenance an Eaton Panelboard 31 The SPC Series offers robust ■ 5-year warranty can be extended to protection in a compact, flexible 10 years with product registration at design configurable for commercial www.eaton.com/spc 32 and light industrial applications. The SPC Series offers maximum flexibility with configurable features such as: Standards and Certifications 33 EMI/RFI filtering, audible alarm and ■ UL 1449 4th Edition Type 1 Form C contacts. SPC Series units are and Type 2 available in all common voltages and ■ UL 1283 6th Edition 34 configurations, and in a variety of peak surge current capacity ratings from ■ Canadian Standards Association 50 through 200 kA per phase. The (CSA) Type 1 and Type 2 35 compact design and NEMA® 4X ■ CSA C22.2 No. 269.1-14 for Type 1 enclosure of the SPC Series allows SPD, CSA C22.2 No. 269.2-13 for for installation external to an Type 2 SPD, CSA C22.2 no. 8-13 for 36 electrical assembly in a wide variety EMI filter of environments including service entrances, distribution panelboards 37 and point-of-use applications. Table 34.1-22. SPC Configurable Features Feature Standard Available 38 Option Surge protection using thermally protected MOV technology ■ 39 Tri-colored LED protection status indicators for each phase ■ Tri-colored LED protection status indicators for the neutral-ground ■ protection mode 40 Audible alarm ■ Form C relay contact ■ EMI/RFI filtering, providing up to 40 dB of noise attenuation ■ 41 from 10 kHz to 100 MHz

42

4 3

For more information, visit: www.eaton.com/consultants CA08104001E Surge Protection (SPD) & Power Conditioning Products 34.1-21 September 2016 Surge Protection Products—SPC Sheet 34023 SPC Series

Catalog Numbering System 22 Table 34.1-23. SPC Series Catalog Numbering System 23 SPC 200 208Y 8 P 24 SPC Enclosure Suffix P =NEMA 4X Voltage Code 25 kA Rating 120N = 120 V single-phase (2W +G) 050 = 50 kA per phase 240N = 240 V single-phase (2W +G) Features 080 = 80 kA per phase 277N = 277 V single-phase (2W +G) Options SPD 26 100 = 100 kA per phase 480N = 480 V single-phase (2W +G) Application 120 = 120 kA per phase 240S = 120/240 split-phase (3W +G) 150 = 150 kA per phase 240D = 240 delta (3W +G) 1 = No options (standard configuration) Type 1 160 = 160 kA per phase 480D = 480 delta (3W +G) 2 = Filtering, UL 1283 6th Edition Type 2 27 200 = 200 kA per phase 600D = 600 delta (3W +G) 3 = Audible alarm Type 1 240H = 240 V high leg delta (4W +G) 4 =Form C relay Type 1 208Y = 120/208 wye (4W + G) 5 = Audible alarm and Form C relay Type 1 28 415Y = 240/415 wye (4W + G) 6 = Filtering and audible alarm Type 2 480Y = 277/480 wye (4W + G) 7 = Filtering and Form C relay Type 2 600Y = 347/600 wye (4W + G) 8 = Filtering, audible alarm and Form C relay Type 2 29

Example: SPC200208Y8P = SPC Series, 200 kA per phase, 208 wye voltage, features: filtering, audible alarm and Form C relay, NEMA 4X enclosure. 30 The two corrosion-resistant NEMA 4X enclosure sizes are determined by the voltage code and surge rating as shown in Ta b l e 3 4 . 1- 2 4 . 31 Table 34.1-24. SPC Voltage Configurations per Enclosure Size P1 Enclosure P2 Enclosure 32 5.6 x 6 x 3.2 in.; 2.5 lb 7.6 x 8.5 x 3.2 in.; 4 lb

120N/240N/277N/480N 50–200 kA 240S 120–200 kA 240S 50–100 kA 208Y/415Y/480Y/600Y 120–200 kA 33 208Y/415Y/480Y/600Y 50–100 kA 240D/480D 120–200 kA 240D/480D 50–100 kA 600D 50–200 kA 240H 50–100 kA 240H 120–200 kA 34 Table 34.1-25. Available Optional Equipment Available Optional Equipment Catalog Number 35

Flush mount plate for P1 enclosure FLUSHMNTPLATE13 Flush mount plate for P2 enclosure FLUSHMNTPLATE14 36

37

38

39

40

41

42

4 3

CA08104001E For more information, visit: www.eaton.com/consultants Surge Protection (SPD) & Power Conditioning Products 34.1-22 Surge Protection Products—SPC September 2016 Sheet 34024 SPC Series

22 Technical Data and Specifications Table 34.1-26. Specifications 23 Description Specification Peak surge current capacity ratings available 50, 80, 100, 120, 150, 160, 200 kA per phase Nominal discharge current (In) 20 kA 24 Short-circuit current rating (SCCR) 200 kA Single phase voltages available (2W + G) 120, 240, 277, 480 25 Split phase voltages available (3W + G) 120/240 Three-phase wye system voltages available (4W + G) 120/208, 240/415, 277/480, 347/600 Three-phase delta system voltages available (3W + G) 240, 480, 600 26 Three-phase high leg delta system voltage available (4W + G) 240 Input power frequency 50/60 Hz Protection modes Single-phase L-N, N-G, L-G 27 Split-phase L-N, N-G, L-G, L-L Wye L-N, N-G, L-G, L-L D e l t a L- G , L- L 28 Maximum continuous operating voltage (MCOV): 120N 150 L-N, 150 L-G1, 150 N-G 240N, 277N 320 L-N, 320 L-G1, 320 N-G 29 480N 550 L-N, 550 L-G1, 550 N-G 240S, 208Y 150 L-N, 150 L-G, 150 N-G, 300 L-L 240H 150 L-N, 150 L-G, 150 N-G, 300 L-L, 470 H-L, 320 H-N, 320 H-G 415Y and 480Y 320 L-N, 320 L-G, 320 N-G, 640 L-L 30 600Y 420 L-N, 420 L-G, 420 N-G, 840 L-L 240D 320 L-G, 300 L-L 480D 550 L-G, 640 L-L 31 600D 840 L-G, 840 L-L Ports 1 Operating temperature –40 ºF to +140 ºF (–40 ºC to +60 ºC) 32 Storage temperature -–40 ºF to +140 ºF (–40 ºC to +60 ºC) Operating humidity 5% through 95%, noncondensing 33 Operating altitude Up to 2000 m (6561 ft) Agency certification/listing UL 1449 4th Edition, UL 1283 6th Edition, CSA C22.2 No. 269.1-14 for Type 1 SPD, CSA C22.2 No. 269.2-13 for Type 2 SPD, CSA C22.2 no. 8-13 for EMI filter 34 Durability Repetitive Strike Test Passed 12,000 strikes to ANSI/IEEE C62.41 (20 kV, 10 kA) Category C Waveform SPD type UL 1449 4th Edition and CSA Type 1 and Type 2 SPD (dependent on feature options) Enclosure dimensions and weights Refer to Figure 34.1-15 and Figure 34.1-16 for enclosure dimensions and weights 1 35 Enclosure rating NEMA 4X enclosure Form C relay contact ratings 2 A at 30 Vdc or 250 Vac Form C relay contact logic Power ON, normal state—NO contact = open, NC contact = closed 36 Power OFF or fault state—NO contact = closed, NC contact = open EMI/RFI filtering attenuation Up to 40 dB from 10 kHz to 100 MHz 37 RoHS compliant Yes Warranty 5 years standard, 10 years with product registration on www.eaton.com/spc 1 Mounting feet required to achieve NEMA 4X rating. 38

39

40

41

42

4 3

For more information, visit: www.eaton.com/consultants CA08104001E Surge Protection (SPD) & Power Conditioning Products 34.1-23 September 2016 Surge Protection Products—SPC Sheet 34025 SPC Series

Table 34.1-27 contains representative voltage protection rating (VPR) data for all SPC Series voltage ratings. 22 Table 34.1-27. ANSI/UL 1449 4th Edition Voltage Protection Ratings Voltage Code Protection Mode 23 L-N L-G N-G L-L 120–200 kA Unit VPR 24 120N 700 700 700 — 240N 1000 1200 1000 — 277N 1200 1200 1200 — 480N 1800 1800 1800 — 25 240S 700 700 700 1200 208Y 700 700 700 1200 415Y 1200 1200 1200 2000 26 480Y 1200 1200 1200 2000 600Y 1500 1500 1500 2500 240D — 1000 — 1000 27 480D — 1800 — 2000 600D — 2500 — 2500 1 240H 700 700 700 1200 28 80–100 kA Unit VPR 120N 600 600 600 — 240N 1200 1200 1200 — 29 277N 1200 1200 1200 — 480N 1800 1800 1800 — 240S 600 600 600 1000 30 208Y 600 600 600 1000 415Y 1200 1200 1200 2000 480Y 1200 1200 1200 2000 600Y 1500 1500 1500 2500 31 240D — 1000 — 1000 480D — 2000 — 2500 600D — 2500 — 2500 32 1 240H 600 600 600 1000 50 kA Unit VPR 33 120N 700 1200 700 — 240N 1200 2000 1500 — 277N 1200 2000 1500 — 480N 1800 1800 1800 — 34 240S 700 1200 700 1200 208Y 700 1200 700 1200 415Y 1200 2000 1500 2000 35 480Y 1200 2000 1500 2000 600Y 1500 1500 1500 2500 240D — 1000 — 1000 36 480D — 2000 — 2500 600D — 2500 — 2500 2 240H 700 1200 700 1200 37 1 Additional 240H VPRs: 2000 H-L, 1200 H-N, 1200 H-G 2 Additional 240H VPRs: 2000 H-L, 1200 H-N, 2000 H-G 38

39

40

41

42

4 3

CA08104001E For more information, visit: www.eaton.com/consultants Surge Protection (SPD) & Power Conditioning Products 34.1-24 Surge Protection Products—SPC September 2016 Sheet 34026 SPC Series

22 Dimensions in Inches (mm)

23

24 8.50 3.75 (215.9) 8X 0.137 (95.3) Lid 25 36-inch 8X 0.062 7.75 long wires (196.9) 2.38 Mounting feet (60.4) 26 (included) 5.98 (151.9) 7.50 (190.5) 4x #8 (M4) Lid Flathead screw 27 8.62 (219.0) (not included) 9.00 (228.6) 7.56 (192.0) 4X R 0.41 Overall base including 28 0.75 (19.1) stabilization ribs 4X Ø Locknut 0.223 3/4-14 NPS external thread 3.19 29 (81.0) 5.48 (139.2) 4X R 0.25 7.25 (184.2) 9.13 (232.0) 8.50 (215.9) 30 1.00 (25.4) 0.16 (4.1) Mounting feet 31 (included) Figure 34.1-17. Optional Flush Mount Plate for P1 Enclosure (Catalog Number FLUSHMNTPLATE13) Figure 34.1-15. P1 Enclosure, NEMA 4X with Mounting Feet 32 Dimensions, Weight = 2.5 lb

33 8X 0.137 3.75 6.00 34 (95.3) (152.3) Lid 8X 0.062 36-inch 10.25 long wires (260.4) 35 1.12 (28.5) Mounting feet (included) 5.50 (139.6) 8.48 Lid (215.4) 36 6.62 (168.1) 4x #8 (M4) Flathead screw 11.50 (not included) (292.1) 5.56 (141.2) 37 Overall base 4X R 0.41 0.75 (19.1) including stabilization ribs 4X Ø Locknut 0.223 38 3/4-14 NPS external thread 3.19 (81.1) 7.48 (190.0) 4X R 0.25 9.25 (235.0) 39 10.50 (266.7) 7.13 (181.2) 1.00 (25.4) 0.16 (4.1) 40 Mounting feet (included) Figure 34.1-18. Optional Flush Mount Plate for P2 Enclosure (Catalog Number FLUSHMNTPLATE14) 41 Figure 34.1-16. P2 Enclosure, NEMA 4X with Mounting Feet Dimensions, Weight = 4 lb 42

4 3

For more information, visit: www.eaton.com/consultants CA08104001E Surge Protection (SPD) & Power Conditioning Products 34.1-25 September 2016 Surge Protection Products—SPD Sheet 34027 CVX Surge Protective Device

CVX050/100 Features, Benefits Standards and Certifications 22 and Functions ■ UL 1449 4th Edition for surge protective devices ■ Advanced surge path technology 23 for high fault current capacity, low ■ CE marked impedance, high frequency design ■ Vibration tested IEC 60255-21-1 and -2 ■ Rugged NEMA 4X (IP65) enclosure Note: CE, CSA and UL on AC unit only. 24 ■ Large diameter, thermally protected metal oxide varistors provide long life and fail-safe operation 25 ■ LED monitoring of each phase ■ Wide range of voltage applications 26 from 100 to 480 Vac, and 48 and 125 Vdc CVX050/100A ■ 5-year free replacement warranty 27 General Description Optional Features ■ External mounting feet 28 With over two decades of experience (catalog number MNTGFTX) in the surge suppression industry and extensive R&D initiatives, Eaton is ■ Flush mounting plate 29 considered a world leader in surge (catalog number protective device (SPD) manufacturing. FLUSHMNTPLATE12) All of Eaton’s products are manufac- 30 tured in an ISO 9001:2000 and ISO Catalog Number Selection 14001 certified facility. Table 34.1-28. CVX050/100 31 Eaton’s CVX050/100 models are rugged, cost-effective, high-quality SPDs that feature thermally protected CVX 050 - 230L 32 MOVs that eliminate the failure characteristics of standard Metal- Oxide-Varistors. The TPMOV is a Per Phase Peak Configuration and Voltage Ranges (Vac) 33 fail-safe device that monitors the status Surge Current 230L = Single-phase–200, 208, 220, 230, 240, 277 of the metal-oxide disk and connects 050 = 50 kA 480L = Split-phase–380, 400, 440, 460, 480 1 itself from the power system when 100 = 100 kA 240S = Split-phase–100/200, 110/220, 120/240 34 the disk is approaching breakdown. 240H = Three-phase high leg delta–120/240 208Y = Three-phase wye (star)–100/174, 110/190, 120/208, 127/220 The CVX050/100 is easy to install 480Y = Three-phase wye (star)–220/380, 230/400, 240/415, 277/480 35 adjacent or even internal to electrical 600Y = Three-phase wye (star)–305/525, 347/600 equipment. When installing an SPD in 240D = Three-phase delta–200, 208, 220, 230, 240 a retrofit environment, it is important 480D = Three-phase delta–380, 400, 415, 440, 480 600D = Three-phase delta–525, 600 Vac (600D available in 50 kA only) 36 to mount the device as close to the electrical equipment as possible. Keep Configuration and Voltage Ranges (Vdc) 1 the wiring (lead length) between the 048DC = 48 Vdc 1 37 electrical equipment and SPD as short 125DC = Direct Current 125 Vdc as possible, and twist or wire tie the conductors together to reduce the 38 wire’s impedance factor. 1 DC models only available in 50 kA. Application Description 39 Eaton’s CVX050 and CVX100 SPDs protect electronic equipment from 40 damaging transients. These units are suitable for medium and low exposure level applications that 41 require cost-effective, high quality system protection including: 42 ■ Residential/small business ■ Light industrial ■ Light commercial 4 3 ■ Branch panel protection

CA08104001E For more information, visit: www.eaton.com/consultants Surge Protection (SPD) & Power Conditioning Products 34.1-26 Surge Protection Products—SPD September 2016 Sheet 34028 CVX Surge Protective Device

22 Technical Data and Specifications Table 34.1-29. CVX050/100 Model Specifications 23 Description Specification Peak kA per phase 50, 100 Peak kA per mode 50 1 24 Nominal discharge current 20 kA Short-circuit current rating 100 kA 25 Single-phase voltages 200, 208, 220, 230, 240, 277, 380, 400, 440, 460, 480 Split-phase voltages 100/200, 110/220/ 120/240 High leg delta voltages 240 26 Wye system voltages 100/175, 110/190, 120/208, 127/220, 220/380, 230/400, 240/415, 277/480, 305/525, 347/600 Delta system voltages 200, 208, 220, 230, 240, 380, 400, 415, 440, 480, 525, 600 2 27 Direct current voltage 48 Vdc, 125 Vdc Input power frequency 47–420 Hz (50/60 Hz typical) Protection modes Single-phase: L-N, N-G, L-G 28 Split-phase: L-N, N-G, L-G, L-L High leg delta: L-N, N-G, L-G, L-L, H-N, H-G, H-L Wye: L-N, N-G, L-G, L-L Delta: L-G, L-L 29 Direct current (DC): L-L, L-G b Number of ports 1 30 Specific energy 100 kJ/Ohm Weight (approximate) 2.0 lb (1.0 kg) Operating temperature –13 °F (–25 °C) to +140 °F (+60 °C) 31 Vibration tested IEC 60255-21-1 and IEC 60255-21-2 1 480L, 600D and 600Y units rated 10 kA I . 2 n DC models only available in 50 kA. 32 Table 34.1-30. CVX050/100 Voltage Ratings 3 Model System Nominal MCOV UL 1449-4 VPR 33 Configuration System Voltage L-L L-N L- G N -G L- L L-N L- G N - G CVX050 34 230L Single-phase two-wire + ground 200, 208, 220, 230, 240, 277 — 320 640 320 — 1200 1200 1200 480L Single-phase two-wire + ground 380, 400, 440, 460, 480 — 550 1100 550 — 1800 4000 1800 240S Split-phase three-wire + ground 100/200, 110/220, 120/240 300 150 300 150 1200 700 1200 800 35 208Y Three-phase wye (star) four-wire + ground 100/175, 110/190, 120/208, 127/220 300 150 300 150 1200 700 1200 800 480Y Three-phase wye (star) four-wire + ground 220/380, 230/400, 240/415, 277/480 640 320 640 320 2500 1200 2000 1200 36 600Y Three-phase wye (star) four-wire + ground 305/525, 347/600 840 420 840 420 2500 1500 2500 1500 240D Three-phase delta three-wire + ground 200, 208, 220, 230, 240 640 — 320 — 2000 — 1200 — 240H Three-phase high leg delta 240 300 150 150 640 1500 700 1200 700 37 480D Three-phase delta three-wire + ground 380, 400, 415, 440, 480 1100 — 550 — 3000 — 1800 — 600D Three-phase delta three-wire + ground 525, 600 1100 — 700 — 3000 — 2500 — 4 048DC Direct current 48 Vdc 130—65— ———— 38 4 125DC Direct current 125 Vdc 288 — 144 — — — — — CVX100 39 230L Single-phase two-wire + ground 200, 208, 220, 230, 240, 277 — 320 320 320 — 1200 1200 1200 480L Single-phase two-wire + ground 380, 400, 440, 460, 480 — 550 550 550 — 1800 1800 1800 240S Split-phase three-wire + ground 100/200, 110/220, 120/240 300 150 150 150 1200 700 800 700 40 208Y Three-phase wye (star) four-wire + ground 100/175, 110/190, 120/208, 127/220 300 150 150 150 1000 600 700 700 480Y Three-phase wye (star) four-wire + ground 220/380, 230/400, 240/415, 277/480 640 320 320 320 1800 1200 1200 1200 41 600Y Three-phase wye (star) four-wire + ground 305/525, 347/600 840 420 420 420 2500 1500 1500 1500 240D Three-phase delta three-wire + ground 200, 208, 220, 230, 240 640 — 320 — 1800 — 1200 — 240H Three-phase high leg delta 240 300 150 150 150 1200 700 700 700 42 480D Three-phase delta three-wire + ground 380, 400, 415, 440, 480 1100 — 550 — 3000 — 1800 — 3 UL 1449 4th Edition VPR (voltage protection rating) test environment: all tests performed with 6-inch lead length, positive polarity. 4 4 3 DC units available in 50 kA only. Voltages shown are the maximum suggested operating voltages and are not UL certified.

For more information, visit: www.eaton.com/consultants CA08104001E Surge Protection (SPD) & Power Conditioning Products 34.1-27 September 2016 Surge Protection Products—SPD Sheet 34029 CVX Surge Protective Device

Dimensions 22

5.67 23 (144.0) 4.75 (120.6) Conduit Fitting 0.75 (19.0) Internal 24 4.17 Taper Pipe Threads (106.0) 25

26 4.75 3.39 (120.6) (86.1) 2.37 27 (60.2) A A 28 Lid Removed 1.0 0 (25.4) 3.55 (90.2) 29 0.17 (4.3) (4) Mounting Holes Under Lid 30

31 Section A-A Mounting Hole Shafts 32 Figure 34.1-19. CVX050/100 Standard Dimensions—Approximate Dimensions in Inches (mm) 33

34

35

36

37

38

39

40

41

42

4 3

CA08104001E For more information, visit: www.eaton.com/consultants Surge Protection (SPD) & Power Conditioning Products 34.1-28 Surge Protection Products—SPD September 2016 Sheet 34030 Eaton SP1

Installation and Operation 22 Eaton SP1 Features Installation and operation of the SP1 is ■ Type 1 SPD capable of installation simple. The unit comes pre-wired with on either the line or load side of 24.00 inches (609.6 mm) of 10-gauge 23 the service entrance disconnect wire and is mounted via the 0.50-inch (12.7 mm) nipple that is molded into its ■ 20 kA nominal discharge current 24 enclosure. Wall or DIN rail mounting rating (In) on most models can also be accomplished with the ■ 50 kA per phase surge addition of an optional kit. When current capacity 25 powered, the unit‘s light-emitting diode ■ Compact footprint— (LED) indicator reports the status of the 4.80 inches (121.9 mm) L x protection elements and is active when 2.90 inches (73.7 mm) W x 26 all of them are intact and providing 2.50 inches (63.5 mm) D protection. Any loss of protection is ■ Pre-wired with 24.00 inches signaled when the LED extinguishes. (609.6 mm) of 10-gauge wire 27 ■ 0.50-inch (12.7 mm) nipple molded into enclosure enables quick and 28 easy mounting ■ Optional kit enables wall or DIN rail mounting 29 ■ Two-year warranty Standards and Certifications 30 Eaton SP1 ■ UL 1449 4th Edition-listed device 31 General Description Eaton‘s SP1 is a UL 1449 4th Edition- Catalog Number Selection listed surge protective device that Table 34.1-31. SP1 Catalog Numbering System 32 provides reliable, cost-effective surge protection. This Type 1 SPD is capable of being installed on either the line SP1 XXXX 33 or load side of the service entrance disconnect and can be used as a replacement for devices formerly Series Voltage Codes 34 known as secondary surge arresters SP1 240S = 120/240 V single split-phase or lightning arresters, which could 208Y = 120/208 wye not be manufactured after UL 1449 480Y = 277/480 wye 35 3rd Edition went into effect on 600Y = 347/600Y wye 240D = 240 delta September 29, 2009. The unit is 480D = 480 delta available in many common voltages 600D = 600 delta 36 and configurations. Multiple mount- ing options coupled with a compact footprint enables installation of the Note: SP1MNTGKIT = optional wall or DIN rail mounting kit (order separately— 37 SP1 in a wide range of applications, not included with SP1 unit). including panelboards, loadcenters, pump panels, control cabinets, 38 and other electrical assemblies and applications. 39

40

41

42

4 3

For more information, visit: www.eaton.com/consultants CA08104001E Surge Protection (SPD) & Power Conditioning Products 34.1-29 September 2016 Surge Protection Products—SPD Sheet 34031 Eaton SP1

Technical Data and Specifications Dimensions in Inches (mm) 22 Table 34.1-32. Specifications Description Rating 1.35 0.50 (12.7) 23 (34.3) Surge current capacity per phase 50 kA Straight Pipe Thread Nominal discharge current (In) 20 kA for SP1-240S, 208Y, 480Y, 240D and 480D 24 10 kA for SP1-600Y and 600D Short-circuit current rating (SCCR) 200 kA 0.79 (20.1) SPD type Type 1 (can also be used in 25 Type 2 applications) System voltages available (Vac) Single split-phase 120/240 26 Three-phase wye 120/208, 277/480, 347/600 Three-phase delta 240, 480, 600 3.95 Protection modes (100.3) 27 Single split-phase and three-phase L- N , L- L wye L- G , L- L Three-phase delta 28 Maximum continuous operating voltage (MCOV) SP1-240S and SP1-208Y 150 L-N, 300 L-L SP1-480Y 320 L-N, 640 L-G 29 SP1-600Y 420 L-N, 840 L-G 2.89 2.46 SP1-240D 300 L-G, 300 L-L (73.4) (62.5) SP1-480D 640 L-G, 640 L-L 30 SP1-600D 840 L-G, 840 L-L Figure 34.1-20. SP1 Dimensions Input power frequency 50/60 Hz Enclosure rating NEMA 4 31 Operating temperature –20 °C to 50 °C (–4 °F to 122 °F) Operating humidity 5–95%, noncondensing Operating altitude Up to 16,000 ft (5000 m) 32 Agency certification and approvals UL 1449 4th Edition listed device Warranty 2 years 33 Table 34.1-33. ANSI/UL 1449 4th Edition Voltage Protection Ratings Protection Mode Catalog 34 L- N L-G L-L Number 600 N/A 1000 SP1-240S 35 600 N/A 1000 SP1-208Y 1200 N/A 2000 SP1-480Y 1500 N/A 2500 SP1-600Y 36 N/A 1000 1000 SP1-240D N/A 2000 2000 SP1-480D N/A 2500 2500 SP1-600D 37 Technical Support Information If you have any questions or need additional information, 38 please contact the Eaton Technical Resource Center at 800-809-2772, option 4, option 2. You may also submit inquiries via e-mail: [email protected]. 39

40

41

42

4 3

CA08104001E For more information, visit: www.eaton.com/consultants Surge Protection (SPD) & Power Conditioning Products 34.1-30 Surge Protection Products—SPD September 2016 Sheet 34032 Eaton SP2

22 SP2 Surge Protective Device Application Description Features, Benefits By providing surge protection, the SP2 and Functions can suppress the transients that are ■ Type 1 UL 1449 4th Edition listed 23 prevalent throughout the power SP2s are easily selected and distribution system to support reliable installed on the loadside or lineside operations in applications including: 24 of the service entrance overcurrent ■ HVAC systems protective device ■ Control panels ■ Thermal disconnect technology 25 ■ Automation cabinets eliminates the need for additional overcurrent protection ■ Pumping systems ■ Compact UV-resistant NEMA 4X ■ 26 Lighting systems enclosure for indoor or outdoor ■ Commercial facilities applications ■ Food processing ■ LED status indicators provide surge 27 ■ Warehouses protection status at a glance—green ■ Retail facilities when good, red to replace 28 ■ Manufacturing operations ■ Voltage-specific models protect electrical systems and equipment, improving performance by more Surge Protection for Light Commercial Standards and Certifications than 110% over “one-size-fits-all” 29 and UL 508A Panel Applications economy surge arresters ■ UL 1449 4th Edition Type 1 SPD ■ File No. E109835, cULus Compact enclosure takes up less General Description space and can be installed in tight 30 ■ Built in an ISO 9001 facility spaces The SP2 provides basic surge ■ Flammability rating UL 94VO protection for light commercial ■ Can be used on single-phase, split- ■ Designed and tested in accordance 31 electrical systems and OEM equipment phase, wye, delta, and high-leg delta with: requirements. The SP2 is available in systems the most popular voltage and system ❑ IEEE C62.41.1 ■ All SP2 devices are individually 32 configurations and delivers superior ❑ IEEE C62.41.2 marked with a serial number for surge protection using MOV thermal ❑ IEEE C62.43-2005 easy tracking and identification disconnect technology that eliminates ■ Two-year warranty 33 ❑ IEEE C62.45-2002 the need for additional overcurrent ■ Compact design allows for easy ❑ protection. IEEE C62.48-2005 installation on an electrical panel ❑ 34 Studies have shown that failure to IEEE C62.62-2010 or meter socket, or integrated into protect sensitive electronic loads control cabinets costs American manufacturing and 35 commercial and service industries more than $39 billion per year in lost time and revenue. Preventing 36 these losses is a major cost-saving opportunity. The SP2 can be used to protect downstream points in the 37 electrical distribution system along with machinery control panels to keep 38 your facility and processes running.

39

40

41

42

4 3

For more information, visit: www.eaton.com/consultants CA08104001E Surge Protection (SPD) & Power Conditioning Products 34.1-31 September 2016 Surge Protection Products—SPD Sheet 34033 Eaton SP2

Product Selection Dimensions in Inches (mm) 22 Table 34.1-34. SP2 Product Selection

Nominal Maximum System Voltage Connection Catalog 1.06 (26.9) System Continuous Ty p e Protection Points Number Diameter 23 Voltage Operating AC Ratings Voltage (MCOV) (VPR) 1.69 24 120 150 Single-phase, two-wire 700 L–N 2 SP2-120 (42.9) 3.38 240 320 Single-phase, two-wire 1200 L–N 2 SP2-240 (85.9) 1.69 120/240 150 Split-phase, three-wire 700 L–N, 3 SP2-240S (42.9) 25 1200 L–L 240 320 Three-phase delta, 1200 L–G, 4 SP2-240D 2.06 2.06 three-wire + ground 2500 L–L (52.3) (52.3) 26 480 550 Three-phase delta, 1800 L–G, 4 SP2-480D 4.13 three-wire + ground 3000 L–L (104.9) 120/208 150 Three-phase wye, 700 L–G, 4 SP2-208Y 27 three-wire + ground 1200 L–L 3.19 (81.0) 277/480 320 Three-phase wye, 1200 L–G, 4 SP2-480Y three-wire + ground 2500 L–L 4.06 (103.1) 28 34/600 420 Three-phase wye, 1500 L–G, 4 SP2-600Y three-wire + ground 2500 L–L ¾" NPS 29 Technical Data and Specifications 0.87 (22.1) Table 34.1-35. SP2 Specifications 30 Description Specification Figure 34.1-21. SP2 Enclosure

Markets Light commercial and UL 508A panels 31 Product warranty 2 years System types Single, split, delta, and wye 32 Nominal system voltage 120, 208, 240, 480, 600 Vac Installation Two-, three-, four-wire Maximum continuous operating AC voltage Matched to nominal voltage 33 MCOV 150–550 Vac (see table above) L–N protection Yes (single-phase units) L–L protection Yes 34 L–G protection Yes (three-phase units) Protection Surges and transients 35 SCCR 200 kA Nominal discharge current (8 x 20 µs) In 10 kA Maximum discharge current (8 x 20 µs) Imax 45 kA per phase 36 Response time tA <25 ns Voltage protection ratings (VPRs) See table above 37 Overcurrent device (if required by local code) Circuit breaker or fuse sized to protect wires per local codes Frequency 50/60 Hz 38 Operating status / fault indication One bi-color LED—green (good) / red (replace) Conductor gauge/length 10 AWG stranded copper / 18 inches Mounting Chase nipple (¾” NPS) 39 Enclosure rating NEMA 4X—UL 94-5VA Degree of protection (installed state) IP20 (finger-safe) 40 Install location Indoor/outdoor Circuit location Lineside/loadside Standards / agency information UL 1449 4th Edition Type 1 Listed SPD—cULus, 41 RoHS compliant Operating temperature –40 °C to +65 °C Maximum operating altitude 12,000 ft 42 Weight 17 oz (476 g) 4 3

CA08104001E For more information, visit: www.eaton.com/consultants Surge Protection (SPD) & Power Conditioning Products 34.1-32 Surge Protection Products—SPD September 2016 Sheet 34034 AEGIS—Series Protective Device

AEGIS Powerline Filters AEGIS Series devices are available 22 in a variety of common voltages and configurations. 23 Why Should Sensitive Electronic Loads be Protected? PLC manufacturers and service 24 technicians recommend the use of surge suppressors and filters to prevent downtime and equipment The AEGIS PH Series Protects Critical 25 damage due to surges and electrical Loads up to 20 A line noise. One study shows failure to AEGIS Solutions protect sensitive electronic loads costs 26 American manufacturing, commercial General Description and service industries over $39 billion per year in lost time and revenue. 27 Eaton AEGIS™ Series line filters Preventing these losses is a major and surge protectors are specifically cost-saving opportunity. designed to protect sensitive electronics 28 from hazards that exist within a facility. The AEGIS Series hybrid filter reacts Features, Benefits instantly to changes in voltage regard- and Functions 29 less of phase angle or polarity. In comparison to other line filters, this AEGIS powerline filters protect technology provides a higher level against the full spectrum of transient 30 of suppression, reliability and disturbances. The AEGIS PV Series Protects Critical life expectancy. Loads up to 5 A AEGIS filters the entire sine wave and 31 is effective against both frequently Application Description occurring low-energy and occasional high-energy transients. High-energy 32 By providing surge protection and line transients can create immediate filtering, AEGIS devices can suppress damage, while low-energy transients the noise and transients prevalent cause microprocessor failure 33 throughout the power distribution over time. system to support reliable operations in applications including: Catalog Numbering System 34 ■ Instrumentation ■ Water treatment facilities Table 34.1-36. AEGIS Series Catalog Numbering System 35 ■ Pulp and paper operations ■ Refrigeration and heating plants AG ■ Petrochemical and refinery 36 ■ Food processing Product ■ Textiles Family/OEM ■ Automotive assembly AG Protection/ Voltage Amperage Options 37 Filtering ■ Manufacturing operations PH = Premium 120 = 120 Vac 03 = 3 A 38 No matter where transients originate, protection 240 = 240 Vac 05 = 5 A the application of AEGIS Series with hybrid 10 = 10 A devices will help protect sensitive filtering 15 = 15 A 20 = 20 A electronic equipment including: 39 PV = Premium 120 = 120 Vac 01 = 1 A ■ Programmable logic controllers protection 240 = 240 Vac 03 = 3 A (PLCs) with filtering 05 = 5 A 40 1 ■ Scanning devices CF = Critical 120 = 120 Vac 10 = 10 A DIN = DIN mount 2 protection 230 = 230 Vac 15 = 15 A DIN2= DIN2 mount ■ Automatic teller machines (ATMs) 3 with filtering 240 = 240 Vac 30 = 30 A CP = Compact 41 ■ Cash registers 024 = 24 Vdc 60 = 60 A RJ = Telcom protection ■ 048 = 48 Vdc and Form C Alarm systems 4 status contacts 42 ■ Microprocessor-controlled ■ CN = Critical 120 = 120 Vac 30 = 30 A OEM products protection 230 = 230 Vac ■ Robotics without 024 = 24 Vdc 4 3 ■ CAD/CAM systems filtering 048 = 48 Vdc ■ 1 3 Control equipment Not available for 10 A, 230 V or 240 V versions. Only available for 10 A, 120 V CF version. 2 4 ■ Medical electronics and devices Only available for 10 A, 120 V or 240 V CF Only available for 30 A and 60 A CF version. version.

For more information, visit: www.eaton.com/consultants CA08104001E Surge Protection (SPD) & Power Conditioning Products 34.1-33 September 2016 Surge Protection Products—SPD Sheet 34035 AEGIS—Series Protective Device

Product Selection 22 Table 34.1-37. Let-Through Voltages Based on IEEE Std. C62.62-2010 Testing Waveforms 1 Test AEGIS Series 23 Impulse AGPH120xx AGPV120xx AGCF12010 AGCF12010-DIN AGCF12010-CP AGCF12030xxx AGCF12060xxx AGCn12030

IEEE Category A 25 V 30 V 150 V 300 V 300 V 150 V 90 V 400 V 100 kHz ring wave 6000 V, 200 A 24 IEEE Category B 35 V 40 V 330 V 400 V 400 V 330 V 230 V 500 V 100 kHz ring wave 6000 V, 500 A IEEE Category B 360 V 370 V 470 V 480 V 460 V 460 V 450 V 460 V 25 combination wave 6000 V, 3000 A (UL 1449-4 VPR) 1 All tests conducted on 120 Vac units. 26

Technical Data and Specifications 27 Table 34.1-38. AEGIS Specifications 234 AEGIS Series 28 Rating PH PV CF CN

Application Single-phase, two- Single-phase, two- Single-phase, two- Single-phase, two- or three-wire or three-wire or three-wire or three-wire 29 grounded systems grounded systems grounded systems grounded systems Input voltage—AC 100–127 Vac, 200–240 Vac 100–127 Vac, 200–240 Vac 100–127 Vac, 200–240 Vac 100–127 Vac, 200–240 Vac Input voltage—DC N/A N/A 5–38 Vdc, 24–65 Vdc, 5–38 Vdc, 24–65 Vdc, 30 48–149 Vdc, 150–300 Vdc 48–149 Vdc, 150–300 Vdc Amperage 3, 5, 10, 15, and 20 A 1, 3, and 5 A 10, 30, and 60 A 30 A 5 31 DIN mounting Yes Yes Yes No Frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz Protection modes L–N, L–G and N–G L–N, L–G and N–G L–N, L–G and N–G L–N, L–G and N–G 32 MCOV 150 V and 275 V 150 V and 275 V 150 V and 275 V 150 V and 275 V Noise attenuation (normal mode) 74 dB at 100 kHz 56 dB at 100 kHz 48 dB at 100 kHz N/A 33 Filter bandwidth 10 kHz to 100 MHz 10 kHz to 100 MHz 10 kHz to 100 MHz N/A Peak surge current per phase / per mode 60 kA / 30 kA 40 kA / 20 kA Up to 80 kA / 40 kA Up to 80 kA / 40 kA UL nominal discharge current (In) 5 kA 5 kA 5 kA 5 kA 34 4 UL voltage protection rating (VPR) L–G / L–N 330/400 330/400 500/500 500/500 Short-circuit current rating (SCCR) 5 kA 5 kA 10 kA 10 kA Operating temperature –40 °F to +122 °F –40° F to +122 °F –40 °F to +140 °F –40 °F to +140 °F 35 (–40 °C to +50 °C) (–40 °C to +50 °C) (–40 °C to +60 °C) (–40 °C to +60 °C) Response time <1 nanosecond <1 nanosecond <1 nanosecond <1 nanosecond 36 Agency approvals UL 1449 4th Edition, UL 1449 4th Edition, AGCFxxxxx UL 1449 AGCNxxx30 UL 1449, UL 1283 5th Edition UL 1283 5th Edition 4th Edition, UL 1283 UL 1283 5th Edition, and CSA and CSA 5th Edition EMI filter AGCFxxx10-DIN2 37 UL 1449 4th Edition, IEC 61000-4.5 UL 1449 Type Type 2 Type 2 Type 2 Type 2 38 6 Warranty 15 years 15 years 10 years 10 years Status indicator LED LED LED LED 5 39 Form C contacts Yes No Yes No Communication line protection (UL 497A) No No Optional No 7 External circuit breaker Eaton P/N: WMZT1C25 Eaton P/N: WMZT1C07 10 A—Eaton P/N: Eaton P/N: WMZT1C40 40 or equiv. 25 A circuit or equiv. 7 A circuit WMXT1C15 or equiv. or equiv. 40 A circuit breaker breaker 15 A circuit breaker breaker 30 A—Eaton P/N: 41 WMZT1C40 or equiv. 40 A circuit breaker 60 A—Eaton P/N: 42 EGC3100FFG or equiv. 100 A circuit breaker 2 5 Optional on 10 A and 30 A models only. Optional on 30 A and 60 A models only. 3 6 4 3 120 Vac models only. With product registration. 4 7 Ratings shown for 120 Vac models, other External circuit breaker sold separately. voltages listed in Technical Data.

CA08104001E For more information, visit: www.eaton.com/consultants Surge Protection (SPD) & Power Conditioning Products 34.1-34 Surge Protection Products—SPD September 2016 Sheet 34036 AEGIS—Series Protective Device

22 Dimensions in Inches (mm)

23

2.87 2.87 24 (72.9) (72.9) 25

4.44 2.51 26 (112.8) (63.8)

27

4.83 4.83 28 (122.8) (122.8)

4.98 4.98 29 (126.5) (126.5) 30

31 DIN Rail to be Mounted DIN Rail to be Mounted with Screws Provided with Screws Provided 32 Using Slots as Template Using Slots as Template

33

34

35 Figure 34.1-22. AGPHxxxxx Dimensions Figure 34.1-23. AGPVxxxxx Dimensions 36

37

38

39

40

41

42

4 3

For more information, visit: www.eaton.com/consultants CA08104001E Surge Protection (SPD) & Power Conditioning Products 34.1-35 September 2016 Surge Protection Products—SPD Sheet 34037 AEGIS—Series Protective Device

22

2.47 2.25 3.20 23 (52.7) (57.2) (81.2) 24

4.69 3.34 (119.2) 25 (85.0) (4X) Ø 0.19 5.25 (Ø 4.8) 4.77 (133.4) (121.1) 26 5.78 (146.7) 0.35 (8.9) 27

1.25 (31.8) 1.88 28 (47.8) 29 Figure 34.1-24. AGCF12010-CP Dimensions 3.23 Optional DIN Rail (82.0) Mounting Kit (#420-9100) 30

1.36 Figure 34.1-27. AGCFxxx30xxx Dimensions (34.5) 31 4.78 (121.4) 32

3.75 4.72 3.36 (95.3) 2.59 (119.9) 33 (85.2) (65.7) 3.50 5.21 4.41 4.25 (88.9) (132.3) (112.0) (108.0) 34

35 Optional DIN Rail 1.68 Mounting Kit 6.75 (#420-9000) (42.6) Ø 0.19 DIN Mounting 3.36 (171.5) 1.25 (Ø 4.8) 7.29 Each Side (4X) (85.2) (31.8) (185.0) 36 (4X) Ø 0.19 (Ø 4.8) Figure 34.1-25. AGCFxxx10 Dimensions Clear Protective Cover Non DIN Mtg. 37

38 0.98 (24.8) 3.79 (96.1) 4.50 39 (114.3)

0.10 (2.5) 40 Optional DIN Rail Mounting Kit (#420-9000) 3.30 2.92 (83.8) (74.2) Figure 34.1-28. AGCFxxx60xxx Dimensions 41 42

3.12 4 3 (79.4)

Figure 34.1-26. AGCFxxx10-DIN Dimensions

CA08104001E For more information, visit: www.eaton.com/consultants Surge Protection (SPD) & Power Conditioning Products 34.1-36 Surge Protection Products—SPD September 2016 Sheet 34038 AEGIS—Series Protective Device

22

23 2.25 3.20 (57.2) (81.2) 24

25 4.69 (119.2) (4X) Ø 0.1 5.25 (Ø 4.8) 26 (133.4) 5.78 (146.7) 27

28

1.88 29 (47.8) 3.23 (82.0) Optional DIN Rail 30 Mounting Kit (#420-9100) 31 Figure 34.1-29. AGCNxxx30 Dimensions 32

33

34

35

36

37

38

39

40

41

42

4 3

For more information, visit: www.eaton.com/consultants CA08104001E Surge Protection (SPD) & Power Conditioning Products 34.1-37 September 2016 Power Conditioning Products Sheet 34039 SRT2

Application Description Features and Benefits Sag Ride Through (SRT2) 22 Industries and Applications Continuous Sag Regulation Affected by Sags The SRT2 is an active voltage Key industries: conditioner. This means it will 23 constantly respond to voltage sags ■ Semiconductor manufacturers and swells in the ±10% range with a ■ Communications regulated output in the ±1% range. 24 ■ Steel mills The SRT2 can be applied to the main ■ and chemical processing service entrance, at branch locations or in front of critical loads. Eaton’s 25 ■ Healthcare SRT2 provides an outstanding return ■ Paper mills on investment. It delivers operational ■ Automotives productivity that is just not possible 26 ■ Textile with traditional tap switching or ■ Printing ferroresonant technologies. 27 ■ Plastics The SRT2 consists of a voltage source inverter, a bypass circuit and an injec- Equipment or processes: tion transformer connected in series 28 ■ Manufacturing process controllers between the incoming utility supply Sag Ride Through (SRT2) and the load (Figure 34.1-30). ■ Variable speed drives 29 General Description ■ Robotics Sag Correction Using the Sag Ride-Through ■ Motor conductor The SRT2 power conditioner prevents The SRT2 is the latest revision of ■ Telephone systems expensive electrical downtime. It is a 30 Eaton’s sag ride-through products. The ■ HID lighting state-of-the-art solution to today’s power conditioning challenges. operation of the system is designed ■ HVAC controls specifically to meet the demanding 31 ■ requirements of industrial load Medical equipment Standards and Certifications ■ protection where the following Computers The SRT2 meets the stringent require- eatures are particularly important: ments of the SEMI-F47 standard, a key 32 ■ Extremely high electrical efficiency, requirement for sag correction in the meaning much lower ongoing cost semiconductor industry. 33 of ownership than traditional UPS solutions and much less needed heat dissipation from the room in 34 which the SRT2 is located ■ High reliability due to the three levels of redundancy offered in the 35 SRT2 design Three-Phase Compensating ■ High levels of fault clearing capacity Voltage (typically 20 times current short Three-Phase Utility Three-Phase Load 36 Supply Secondary Injection Voltage Transformer term) to allow for the discrimination Distribution Primary of protection systems Transformer 37 ■ Ability to cope with industrial loads, such as motor drives, which are high in harmonic draw and also loads 38 that may regenerate power SRT2 Input SRT2 Output Bypass Circuit 39 Voltage Source Inverter 40 Figure 34.1-30. Block Diagram of the SRT2 Active Voltage Conditioner 41

42

4 3

CA08104001E For more information, visit: www.eaton.com/consultants Surge Protection (SPD) & Power Conditioning Products 34.1-38 Power Conditioning Products September 2016 Sheet 34040 SRT2

22 Technical Data and Specifications Table 34.1-39. SRT2 Specifications 23 Description Specifications Load Capacity Capacity (kVA) 150–1800 kVA (consult factory for custom design; up to 36 kVA available) 24 Displacement of connected load 0 lagging to 0.9 leading Crest factor for rated kVA 3 at 100% of rated load 25 Overload capacity (>90% supply voltage) 150%, 30 seconds, once per 500 s Input Supply Nominal supply voltage (according to model) 480 V 1 26 Voltages up to 36 kV available as custom applications Power system type Three-phase, center ground referenced Supply voltage category Level III transient voltage capability 27 Fault capacity Refer to model tables Operating Voltage Range for Regulation 28 Supply voltage for regulation 90–110% of nominal input voltage unit rating Output Supply Nominal voltage (V) Set to match nominal supply voltage 29 Three-phase V regulation range ±10% continuous Three-phase V regulation accuracy ±1% Three-phase balanced sag/swell correction ability: 30 40% model +40% / –10% at least 30 s at full load Sag correction accuracy (within specified range) ±2.5% Sag correction response: 31 Initial <250 µs Complete <0.25 cycle Single-phase sag correction ability: 32 40% model (15% retained voltage / 85% sag) 90% nominal Equivalent series impedance (operating) <4% typical 33 Efficiency of system 0.98 to 0.99 (refer to model tables) Bypass Capacity 100% model rating (kVA) 34 Maximum overload capacity (in bypass): For 10 minutes 125% For 1 minute 150% 35 For 1 second 500% For 200 milliseconds 2000% Transfer time: Inverter to bypass <0.5 ms 36 Equivalent series impedance (in bypass) Equivalent series impedance (in bypass) Interface 37 Access protocol Access protocol Environmental Enclosure rating NEMA® 1, IP20 38 Pollution degree rating 2 Minimum operating temperature 0 ºC 39 Maximum operating temperature 40 ºC Temperature derating Above 40 ºC derate at 2% per ºC to a maximum of 50 ºC Capacity elevation derating –2% every 100 m above 1000 m 40 Cooling: Inverter Forced ventilation Transformer Fan assisted ventilation 41 Humidity <95%, noncondensing EMC emissions CISPR 22 level G 42 Noise 65 dBA Warranty 1 year 1 480 V is standard. If additional voltage is needed, consult factory. 4 3

For more information, visit: www.eaton.com/consultants CA08104001E Surge Protection (SPD) & Power Conditioning Products 34.1-39 September 2016 Power Conditioning Products Sheet 34041 SRT2

Table 34.1-40. System capacities Catalog Load Te rm i n a l Fault System System Airflow Cabinet Dimensions 22 123 Number Capacity Cabinet Capacity Efficiency Dissipation (m3/min) H x W x D in Inches (mm) at Nominal (kVA) (%) (Worst Case) Voltage (kW) 4 23 480 V (kVA)

SRT20150480AA 150 No 40 97.5 3.8 18 85.00 x 32.00 x 32.00 (2159.0 x 812.8 x 812.8) SRT20150480AA-TC 150 Yes 40 97.5 3.8 18 85.00 x 32.00 x 32.00 (2159.0 x 812.8 x 812.8) 24 SRT20225480AA 225 No 40 97.7 5.2 18 85.00 x 32.00 x 32.00 (2159.0 x 812.8 x 812.8) SRT20225480AA-TC 225 Yes 40 97.7 5.2 18 85.00 x 32.00 x 32.00 (2159.0 x 812.8 x 812.8) SRT20300480AA 300 No 40 98.0 6.1 18 85.00 x 40.00 x 32.00 (2159.0 x 1016 x 812.8) 25 SRT20300480AA-TC 300 Yes 40 98.0 6.1 18 85.00 x 40.00 x 32.00 (2159.0 x 1016 x 812.8) SRT20450480AA 450 No 40 98.2 8.0 36 85.00 x 40.00 x 32.00 (2159.0 x 1016 x 812.8) SRT20450480AA-TC 450 Yes 40 98.2 8.0 36 85.00 x 40.00 x 32.00 (2159.0 x 1016 x 812.8) 26 SRT20600480AA 600 No 40 98.4 9.8 36 85.00 x 40.00 x 32.00 (2159.0 x 1016 x 812.8) SRT20600480AA-TC 600 Yes 40 98.4 9.8 36 85.00 x 40.00 x 32.00 (2159.0 x 1016 x 812.8) SRT20750480AA 750 No 40 98.4 12.2 54 85.00 x 96.00 x 48.00 (2159.0 x 2438.4 x 1219.2) SRT20750480AA-TC 750 Yes 40 98.4 12.2 54 85.00 x 96.00 x 48.00 (2159.0 x 2438.4 x 1219.2) 27 SRT20900480AA 900 No 40 98.5 13.2 54 85.00 x 96.00 x 48.00 (2159.0 x 2438.4 x 1219.2) SRT21200480AA 1200 No 40 98.5 18.1 72 85.00 x 126.00 x 96.00 (2159.0 x 3200.4 x 2438.4) SRT21500480AA 1500 No 50 98.7 20.2 90 85.00 x 126.00 x 96.00 (2159.0 x 3200.4 x 2438.4) 28 SRT21800480AA 1800 No 50 98.8 22.1 108 85.00 x 126.00 x 96.00 (2159.0 x 3200.4 x 2438.4) 1 For 50 Hz international applications, consult factory. 2 Eaton external three-breaker maintenance bypass is recommended. If a bypass is not used, a terminal cabinet may be required. Contact factory. 29 3 TC in the model number denotes terminal cabinet, which is not required for units of 900 kVA and larger. 4 480 V is standard. If additional voltage is needed, consult factory. 30 Wiring Diagram 31

S3 32

AC Load Supply 33 S1 S2

SPD SRT2 34

Figure 34.1-31. SRT2 With External Maintenance Bypass Block Diagram 35 Note: A terminal cabinet may be needed if a bypass cabinet is not used. SRT2 units 900 kVA and larger do not require a terminal cabinet; however, an external three-breaker mechanical bypass with integrated surge protection is recommended. 36

37

38

39

40

41

42

4 3

CA08104001E For more information, visit: www.eaton.com/consultants Surge Protection (SPD) & Power Conditioning Products 34.1-40 Power Conditioning Products September 2016 Sheet 34042 Electronic Voltage Regulator

Brownouts 22 Electronic Voltage Features and Benefits In the United States, most facilities Regulator (EVR) ■ Coordinated with standard have sufficient voltage regulation. thermal-magnetic breakers to However, in some U.S. locations and 23 allow motor starts many developing countries, regulation problems occur because of overstressed ■ Optional 50 kA and 100 kA per phase 24 utility distribution systems. surge protection ■ Input frequency range operation In some cases, due to the excessive from 57–63 Hz demand on the utility system, voltage ■ Not affected by load power factor. 25 may be below 10% of nominal (–10%) Can operate effectively in low-load during the day. This condition is called applications due to “unique leakage a voltage regulation or brownout. reactance” technology 26 Customers may notice dim lights and reduced power. During the evening, ■ Fail-safe bypass circuit, isolation voltage may rise above 10% of nominal transformer and overtemperature 27 (+10%) because large facilities and protection loads are shut down. This shutdown ■ Less than 1% THD 28 reduces the power demand on the grid ■ Optional Standard and Premium and results in a voltage increase. metering to monitor voltage, current, frequency, power, energy, PF with Electronic Voltage Regulator (EVR) The IEEE defines voltage regulation as minimum and maximum, and 29 Tap Changer overvoltage or undervoltage. Voltage communication capabilities regulation events last from a few General Description minutes to many hours with voltage ■ Integral manual rotary maintenance 30 varying by ±20%. Long-term regulation bypass switch standard on 50 to Eaton’s Electronic Voltage Regulator problems differ from short duration 500 kVA units and optional on (EVR) is the ideal solution for keeping sags and dips, which are much deeper smaller units 31 your facility and equipment up and voltage drops. running during brownouts, under- voltage conditions and other power The Solution 32 problems. The EVR can significantly Prior to installing an expensive solution, reduce the costs of equipment damage Eaton encourages customers to monitor 33 and downtime when these situations incoming voltage to determine if voltage occur. The state-of-the-art design regulation is a problem. The local provides rapid response time, utility may also be able to provide 34 high efficiency, high inrush current information on voltage expected at capability, and operating advantages the facility. exclusive to Eaton. Using a meter, it can quickly be 35 The EVR maintains a tightly regulated determined if a voltage regulation output voltage by automatically problem or brownout condition exists. activating the appropriate transformer The appropriate solution would be 36 tap through a silicone controlled an EVR. EVRs can be installed at the rectifier (SCR). Tap changer response service entrance, branch panel or at time is initiated at one cycle, ensuring critical loads. 37 rapid and precise regulation. Switching at zero current enables noise reduction Eaton’s EVR is a solid-state tap changing during tap transitions. power conditioner designed to protect 38 against brownouts and long duration voltage regulation problems. 39

40

41

42

4 3

For more information, visit: www.eaton.com/consultants CA08104001E Surge Protection (SPD) & Power Conditioning Products 34.1-41 September 2016 Power Conditioning Products Sheet 34043 Electronic Voltage Regulator

Catalog Number Selection 22 Table 34.1-41. EVR Catalog Numbering System EVR 025 208D 400Y B S M1 23 24 Options B = Bypass 1 switch 25 M1 = Standard kVA Ratings and Dimensions Nominal metering Input Voltage (IQ 130) kVA Weight BTUs/ Bypass Metering Cabinet Size M2 = Premium 26 Lbs (kg) hr Dimensions H x W x D in Inches (mm) (Delta Input: L, L, L, G) metering 010 440 (200) 1,025 Optional No 30.20 x 22.20 x 29.00 (767.1 x 563.9 x 736.6) (IQ 150) 010 520 (236) 1,205 Optional Yes 44.20 x 22.20 x 29.00 (1122.7 x 563.9 x 736.6) 208D = 208 015 465 (211) 1,540 Optional No 30.20 x 22.20 x 29.00 (767.1 x 563.9 x 736.6) 240D = 240 27 400D = 400 Surge Protection 015 700 (318) 1,540 Optional Yes 44.20 x 22.20 x 29.00 (1122.7 x 563.9 x 736.6) 480D = 480 X = No 025 700 (318) 2,560 Optional Yes 44.20 x 22.20 x 29.00 (1122.7 x 563.9 x 736.6) 600D = 600 S = Yes 030 720 (327) 3,090 Optional Yes 44.20 x 22.20 x 29.00 (1122.7 x 563.9 x 736.6) 28 045 950 (431) 4,600 Optional Yes 44.30 x 45.90 x 29.00 (1125.2 x 1165.9 x 736.6) 050 1,176 (534) 7,332 Yes Yes 66.00 x 29.00 x 35.50 (1676.4 x 736.6 x 901.7) Nominal Frequency 075 1,575 (715) 9,514 Yes Yes 76.00 x 34.40 x 35.50 (1930.4 x 873.8 x 901.7) Output Voltage A = 60 Hz 29 (Wye Output: B = 50 Hz 100 2,014 (914) 11,833 Yes Yes 76.00 x 34.40 x 35.50 (1930.4 x 873.8 x 901.7) L, L, L, N, G) 125 2,137 (970) 14,748 Yes Yes 76.00 x 34.40 x 35.50 (1930.4 x 873.8 x 901.7) 150 2,240 (1017) 17,698 Yes Yes 76.00 x 34.40 x 35.50 (1930.4 x 873.8 x 901.7) 208Y = 120/208 30 400Y = 230/400 225 3,300 (1498) 23,000 Yes Yes 77.40 x 56.00 x 41.50 (1966.0 x 1422.4 x 1054.1) 480Y = 277/480 300 4,000 (1816) 30,750 Yes Yes 77.40 x 56.00 x 41.50 (1966.0 x 1422.4 x 1054.1) 600Y = 347/600 500 5,500 (2497) 51,250 Yes Yes 77.00 x 72.40 x 48.40 (1955.8 x 1839.0 x 1229.4) 31

1 Bypass is standard on 50 kVA and larger units and an option on 45 kVA and smaller units. The “B” is not included in the part number for units 50 kVA and larger. 32

Technical Data and Specifications 33 Table 34.1-42. EVR Specification (10 to 500 kVA) Feature Description 34 Technology Electronic tap changer Input voltages 208–600 V, three-phase (three-wire) 35 Input voltage range +10% to –23% of nominal rated input Output voltage ±3% of nominal Response time 1/2 cycle 36 Frequency 60 Hz, ±3% Efficiency 97% typical 37 Line regulation Output is ±3% of nominal for input variations of +10% to –23% of nominal Load regulation Output is maintained within 3% of nominal from no load to full load Correction time Output will be corrected to within ±3% of nominal in 1.5 cycles or less 38 Harmonic distortion Less than 1.0% added to the output waveform under any dynamic linear loading conditions presented to the line regulator Noise attenuation Common-mode—146 dB 39 Normal-mode—3 dB down at 1000 Hz, 40 dB/decade to below 50 dB with resistive load Turn-on characteristics When energized, voltage overshoot will be less than 5% of nominal for 1 cycle or less 40 Overload rating 1000% for 1 cycle and 200% for 10 seconds Ambient rating 14 °F to +104 °F (–10 °C to +40 °C) Monitoring Three green LEDs (phase power on indication), one red LED (alert indication) 41 Surge protection (optional) CVX 50 kA SPD device 50 kVA and below, CVX 100 kA SPD device 75 kVA and above Input breaker MCCB rated 125% of full rated current Bypass switch Normal and bypass selector 42 Metering (optional) Standard metering (IQ 130)—voltage and current with minimum and maximum Premium metering (IQ 150)—voltage, current, frequency, power, energy, PF, with minimum and maximum, 4 3 communications capabilities Warranty 1-year parts

CA08104001E For more information, visit: www.eaton.com/consultants Surge Protection (SPD) & Power Conditioning Products 34.1-42 September 2016 Sheet 34044

This page intentionally left blank. 22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

4 3

For more information, visit: www.eaton.com/consultants CA08104001E