Measuring with a

Gary Nelson The Energy Conservatory Minneapolis, MN www.energyconservatory.com Hidden Construction Details Often the largest and most important air leaks Hidden Construction Details Leakage In some homes, this is the highest priority (particularly in the sun belt) Why Airtightness Matters

• Durability of building components - moisture condensation in components. • Comfort. • Energy use. • . • Reducing callbacks and risk. Purposes of a Blower Door Test

• Document the air tightness of houses (are they leaky - tight - or somewhere in between) and compare to program standards. • Help find air leaks by inducing air to move through all leaks at the same time (chemical smoke, IR camera, feeling with you hand, zonal pressures). • Help determine the need for mechanical ventilation by estimating natural rates. • Investigate duct leakage problems. • Determine the effectiveness of air sealing activities (compare before and after measurements). • Estimate design infiltration loads for heating and cooling. Purposes of a Blower Door Test

• Note: Blower Doors do not directly measure natural infiltration rates. They measure air tightness (e.g. how big is the hole in the ) and infiltration rates are mathematically estimated using infiltration models. Infiltration estimates may be off by 50% or more. Blower Door Equipment

• Adjustable aluminum frame and nylon panel. • Calibrated . • Digital pressure gauge to measure building and airflow through the fan. Preparing the House for a Test

• Close all exterior doors and windows. • Open all interior doors. • Adjust spillage susceptible combustion appliances so they do not turn on during the test. • Turn off all exhaust appliances. • Close and woodstove doors. • Other intentional openings may be sealed depending on program guidelines. Blower Door Test (single point)

• Blower Door fan is used to depressurize (blow air out) or Attic

pressurize (blow air into) the Supply house. -50 • Adjust fan until the house -50 pressure is changed by 50 Pa. (approx. pressure caused by Blower Door 20 mph wind) Fan • Flow through the fan needed Return to create a 50 Pa change is Crawlspace one metric of house air tightness (CFM@50). Blower Door Test

• Blower Door readings can also

be expressed as total equivalent Attic hole size (square inches). Supply • Can also normalize for house

size. One method is to normalize -50 for volume (ACH@50). -50 – <1.5 - very tight

Blower – 1.5 to 3 - tight Door Fan – 3 to 6 - typical pretty good Return new construction or retrofit Crawlspace – 6 to 10 - leaky – 10 to 20 - very leaky Tightness Standards

• Air tightness standards often normalize by building envelope area. • ASHRAE 90.1-2004 Addendum z (proposed) standard is .4CFM@75Pa/ft2 (≈.31CFM@50Pa/ft2) • Building America (DOE) standard is .25CFM@50Pa/ft2 • UK standard is .55CFM@50Pa/ft2. Testing required for commercial buildings >1000m2 since 2002. Houses are type tested. Building must also meet the design air permeability used for calculating compliance with the Target Emission Rate (TER) • Passivhaus standard of .6ACH@50Pa for a 60’X40’X20’ building would be .055CFM@50Pa/ft2. Bemidji Passivhaus is much tighter! • National Association of Architectural Metal Manufacturers specification: .046 CFM@50Pa/ft2 maximum for walls exclusive of operable windows. Measurements of Commercial Buildings

• Persily and Grot, 8 US office buildings: .16 to .79 CFM@50Pa/ft2 • Tamura and Shaw, typical wall leakage in Canada: .08, .231, and .46 CFM@50Pa/ft2 for tight, average, and leaky walls. • Persily and Grot measured natural infiltration in 8 new office buildings: .1 to .6 ACH Blower Door Fan Basics

• Airflow is determined by measuring flow sensor pressure (with reference to upstream of fan). • Airflow can only be measured in one direction (from inlet to exhaust). flow • Motor is reversible for diagnostic sensor purposes only. Blower Door Fan Basics

• Flow Rings are needed when measuring flows below 2,400 cfm (tight houses). • Failure to use Flow Rings can lead to large errors. • Pressure gauge will indicate if a Flow Ring is needed. Fan Configuration Flow Range (cfm) for Model 3 Fan Open (no Flow Ring) 6,300 - 2,400 Ring A 3,000 - 900 Ring B 1,000 - 300 Digital Pressure Gauge

• DG-700 is a 2 channel differential pressure gauge. • Simultaneous display of both house pressure and fan flow readings. • Proper tubing connections and gauge settings are critical. Other Tests Using A Blower Door

• Air Leakage Path investigation – Blower Door with an Infrared Camera. –View wall before Blower Door test – View wall with Blower Door running. – Changes in IR images are caused by air leakage. – Handheld smoke puffer. Other Tests Using A Blower Door

• Duct Leakage Diagnostics – Pressure Pan test to quickly determine if duct work is connected to the outside. With Blower Door maintaining 50 Pa, test registers with Pressure Pan. – Blower Door subtraction measures duct leakage to outside by comparing Blower Door test – one with registers open and one with registers sealed. Other Tests Using A Blower Door

• Zone Pressure Testing – Measure pressure change in attached unconditioned zones (e.g. attic) with Blower Door running. – Helps to quickly identify dominant house leaks. – Can be used to quantify leakage rates, but method is complicated. Blower Door Software

• TECTITE software is used to calculate air tightness results including: – Air tightness metrics (cfm50, ACH50, leakage areas, other normalized leakages and building leakage curve). – Infiltration rates (both design and average annual). – Recommended mechanical ventilation (based on ASHRAE 62.2). – Estimated cost of infiltration. Automated Testing with a DG-700

• Computer required. • TECTITE Software. • Fan control cable. • Serial cable. Advantages of Automated Tests

• Quickly collect thousands of test data points which improves test accuracy in windy weather. • Allows better estimates of leakage areas by measuring at multiple building pressures. • Reduces operator errors and increases consistency between tests by providing operator prompts.

Data Logging with the DG-700

• Connect DG-700 to laptop and simultaneously record fan depressurization and vent performance. • TECLOG software is available at no-charge.

More Useful Information • Visit www.energyconservatory.com • Articles on airsealing and duct leakage diagnostics. • All product manuals and guides are online. • Links to other sites. • Demo versions of TECTITE. • BSRIA website has good best practices recommendations for air tightness of various building types: www..co.uk • Corporation website has a wealth of building science information and recommended details: www.buildingscience.com • Joe Lstiburek and John Straub here Dec 19 & 20 for a building science course focusing on commercial buildings.