State Issued Type of Cited Code Violation (Fire Identification Number Building Code used for Short Description of the Nature of the Marshall/Life Safety Code and/or Date of Citation (Violations between July 1st, 2015 Institution Institution Code (SLAB) BoR Facilities Inventory Full Official State Building Name Cited Code Violation Elevator Deficiencies) and June 30, 2016) University of at Lafayette 19 S04853 0025 Judice Hall Fire Alarm Yellow Tagged, OSFM NFPA 72 11/10/16 Fryer, Hood Suppression System University of Louisiana at Lafayette 19 S04943 0048 Conference Center Inoperable NFPA 54.4.1.5 10/20/16 University of Louisiana at Lafayette 19 L21058 OLVT Olivier Tower Door Self-Closure and Latch Hardware NFPA 101.8.4.3.5 9/29/16 Elevator - Exposed travel cable, Adjust car gate switch, phone inoperable, no emergency cab light, no guard on cab University of Louisiana at Lafayette 19 S05037 0097 Football Stadium lights ASME A17.2 6/30/16 Elevators - water in pit, adjust door eccentrics, replace counterweight roller guide, missing toe guard on car top handrail, cross head labeling, install University of Louisiana at Lafayette 19 S04943 0048 Conference Center pit ladder ASME A17.2 6/16/16 Elevator: adjust car door pressure, University of Louisiana at Lafayette 19 S05005 0201 Film Library perform 5 year full load test ASME A17.2 6/15/16 Elevators - adjust car door, phase 1 keyswitch, emergency car lighting, Add one clamp to governor cable, machine University of Louisiana at Lafayette 19 S04880 0046 Griffin Hall and pit lighting ASME A17.2 6/17/16 Elevators - governor failed to engage, adjust door opening, routine safety circuit, emergency alarm bell, clean University of Louisiana at Lafayette 19 S04878 0016 Wharton Hall hoist ropes ASME A17.2 6/21/16 University of Louisiana at Lafayette 19 S04862 0041 Billeaud Hall Elevator: Adjust direct drive ASME A17.2 6/21/16 Elevator: Phase 1 Fire Svc needs repair, shorten hoist ropes, adjust car University of Louisiana at Lafayette 19 L21100 HGR0 Huger Hall to run a design speed ASME A17.2 6/21/16 Elevators: keyswitch labeling, adjust hoistway access, monitor governor rope, adjust car to run at contract University of Louisiana at Lafayette 19 L21048 BKR0 Baker Hall speeds ASME A17.2 6/24/16 Elevators: Unit failed full load test. University of Louisiana at Lafayette 19 L21058 OLVT Olivier Tower Repair governor and re-test ASME A17.2 7/8/16 Elevators: crosshead data plate, proper pit ladder, fire hat device not University of Louisiana at Lafayette 19 S04857 0157 Dupre Library working ASME A17.2 7/8/16 Elevators: door restrictor, code data University of Louisiana at Lafayette 19 S04865 0044 Madison Hall plate ASME A17.2 7.8/16 University of Louisiana at Lafayette 19 S4863 0170 Montgomery Hall Elevator: Code Data Plate ASME A17.2 7/8/16 Elevators: door restrictor, add oil to pump, clean pit and car top, floor University of Louisiana at Lafayette 19 S04942 0031 Student Union numbering labels ASME A17.2 7/12/16 Elevators: emergency lighting, adjust University of Louisiana at Lafayette 19 S15431 TSCG Taft Street Parking Garage door closure ASME A17.2 7/13/16 University of Louisiana at Lafayette 19 S04853 0025 Judice Hall Elevator: Code Data Plate ASME A17.2 7/15/16 University of Louisiana at Lafayette 19 S04851 0019 Burke Hawethorne Elevator: door restrictor ASME A17.2 7/12/16 University of Louisiana at Lafayette 19 s04876 0087 Angelle Hall Elevators: code data plate ASME A17.2 7/13/16 University of Louisiana at Lafayette 19 S04856 0029 Hamilton hall Elevator: machine room ventilation ASME A17.2 7/13/16 University of Louisiana at Lafayette 19 BNA0 Bonin Hall Elevators: code data plate ASME A17.2 7/13/16 University of Louisiana at Lafayette 19 S04933 0024 Randolph Hall Elevator: Code Data Plate ASME A17.2 7/13/16 University of Louisiana at Lafayette 19 S13770 MX00 Moody Hall Elevator: cod data plate ASME A17.2 7/14/16 Elevator: door restrictor, GFCI, fire University of Louisiana at Lafayette 19 S04846 0007 Broussard Hall extinguisher, crosshead data plate ASME A17.2 7/14/16 University of Louisiana at Lafayette 19 S04888 003B FG Mouton Elevator: Crosshead Data Plate ASME A17.2 7/14/16 University of Louisiana at Lafayette 19 S04934 0028 Harris Hall Elevators: Code data plate ASME A17.2 7/14/16 University of Louisiana at Lafayette 19 S04878 0016 Wharton Hall Elevators: adjust car doors, ASME A17.2 7/12/16 University of Louisiana at Lafayette 19 S0487 0008 Lee Hall Elevator: car top stop switch ASME A17.2 7/19/16 University of Louisiana at Lafayette 19 S04842 003A Martin Hall Elevators: crosshead data plate ASME A17.2 7/19/16 Elevator: emergency lighting, alarm University of Louisiana at Lafayette 19 S04882 0037 Fletcher Hall bell, car top railing, pit lighting ASME A17.2 7/20/16 Elevator: Code data plate, emergency University of Louisiana at Lafayette 19 Non-University UAM2 Art Museum lighting ASME A17.2 7/20/16 University of Louisiana at Lafayette 19 S01795 0052 Rougeau hall Elevator: shut off valve ASME A17.2 7/20/16 University of Louisiana at Lafayette 19 S04879 UAM1 A. Hayes town Elevator: clean unit ASME A17.2 7/20/16 Elevator: Door Edge Guards, jack University of Louisiana at Lafayette 19 S13083 0920 Abdalla hall packing, floor ID Numbers ASME A17.2 7/20/16 Elevator: Code Data Plate, access University of Louisiana at Lafayette 19 S04850 BUCH Buchanan Hall switch ASME A17.2 7/20/16 Elevator: door restrictors, access University of Louisiana at Lafayette 19 S14825 OLVR Oliver Hall/Advnd. Comp switch ASME A17.2 7/20/16 University of Louisiana at Lafayette 19 S05006 0200 Intl. Student Center Elevator: fire service key switch ASME A17.2 7/20/16 Elevators: adjust door closing force, door restrictor, code data plate, fire fighter service, floor numbering, pit University of Louisiana at Lafayette 19 S05001 0101 light, emergency lights, etc ASME A17.2 7/21/16 Elevators: Clean equipment, door restrictor, alarm bell, pit light swicth, University of Louisiana at Lafayette 19 S13343 CONV Cajundome Convention Center fire svc, etc ASME A17.2 7/21/16 University of Louisiana at Lafayette 19 APC0 Athletic Performance Center Elevator: door restrictor, clean unit ASME A17.2 7/21/16 University of Louisiana at Lafayette 19 L28230 094B Track/Soccer Stadium Elevator: clean unit ASME A17.2 7/30/16 University of Louisiana at Lafayette 19 S05057 0093 Bourgeois hall Elevator: Code Data Plate, clean unit ASME A17.2 7/28/16 University of Louisiana at Lafayette 19 L21058 OLVT Olivier Tower Parking Garage Elevators: water in pit, ASME A17.2 8/9/16 Service, inspect fire panel (yellow Southeastern Louisiana University 18 S13765 SEA Southeastern Oaks Office tagged) LAC 55:V:3037 9/8/15 Southeastern Louisiana University 18 S28831 Kinsesiology Track Pressbox Install new handrails 7.2.2.4 9/22/15 Replace ceiling tiles, service fire extinguishers, replace light switch Southeastern Louisiana University 18 S03266 CNH0 Cardinal Newman Hall cover, and repair emergency light 4.5.8., RS 40:1575 9/22/15 Service, inspect fire panel (yellow tagged), repair/replace smoke Southeastern Louisiana University 18 L13852 LIVH Livingston Hall detectors LAC 55:V:3037, 4.5.8. 9/22/15 Service, inspect fire panel (yellow Southeastern Louisiana University 18 L13850 PRDH Pride Hall tagged) LAC 55:V:3037 9/22/15 Repair/replace smoke detector, service Southeastern Louisiana University 18 L15439 SHAC Tangiphoa Hall fire extinguisher 4.5.8. 9/22/15 Southeastern Louisiana University 18 S03238 PPMG Physical Plant M6 Obstructed egress door RS 40:1575/1583 11/19/15 Service, inspect fire panel (yellow Southeastern Louisiana University 18 L13852 LIVH Livingston Hall tagged) LAC 55:V:3037 11/19/15 Repair emergency lights, lock electrical panel, replace light switch, service fire Southeastern Louisiana University 18 S13734 VILA Greek Village #1 extinguisher RS 40:1575 12/15/15 Southeastern Louisiana University 18 S13735 VILB Greek Village #2 Repair emergency lights 4.5.8. 12/15/15 Repair emergency light, repair/replace smoke detectors, remove storage Southeastern Louisiana University 18 S13737 VILD Greek Village #4 around electrical panels 4.5.8., RS 40:1575 12/15/15

Repair emergency lights, repair/replace smoke detector, repair sprinkler heads, Southeastern Louisiana University 18 S13757 VILE Greek Village #5 service fire extinguisher 4.5.8., RS 40:1575 12/15/15 Southeastern Louisiana University 18 L13852 LIVH Livingston Hall Deficient elevator: 1.18 A17.1 2/18/16 Southeastern Louisiana University 18 L13853 LAH0 Louisiana Hall Deficient elevator: 1.18, 3.27 A17.1 2/18/16 Southeastern Louisiana University 18 L15442 SHAB St. Tammany Hall Deficient elevator: 3.2, 3.27 A17.1 2/18/16 Southeastern Louisiana University 18 L15441 SHAA Washington Hall Deficient elevator: 1.18, 2.14, 3.27 A17.1 2/18/16 Southeastern Louisiana University 18 S13758 VILE Greek Village #6 Deficient elevator: 1.18 A17.1 2/22/16 Southeastern Louisiana University 18 L15440 SHAD Hammond Hall Deficient elevator: 1.18, 3.2 A17.1 2/22/16 Southeastern Louisiana University 18 L13850 PRDH Pride Hall Deficient elevator: 1.18 A17.1 2/22/16 Southeastern Louisiana University 18 L15439 SHAC Tangiphoa Hall Deficient elevator: 1.18 A17.1 2/22/16 Southeastern Louisiana University 18 L13851 TAYH Taylor Hall Deficient elevator: 1.18 A17.1 2/22/16

Deficient elevator: 1.5, 1.6, 1.18, 2.5, Southeastern Louisiana University 18 S23027 SUN0 War Memorial Student Union North 2.10, 2.14, 2.37, 3.16, 3.27, 4.5, 5.1, 6.4 A17.1 2/23/16 Deficient elevator: 1.5, 1.6, 1.18, 2.12, Southeastern Louisiana University 18 S03245 TECM Charles E. Cate Teacher Ed. Center 2.14, 3.8, 3.9, 3.13, 4.1, 5.1, 6.4 A17.1 2/24/16 Southeastern Louisiana University 18 S03280 MUSR Music Recital Hall Deficient elevator: 2.35, 3.9 A17.1 2/24/16 Deficient elevator: 1.5, 1.6, 2.14, 3.9, Southeastern Louisiana University 18 S11817 NCMB North Campus - Main Building 5.1 A17.1 2/24/16 Southeastern Louisiana University 18 S13616 SLBC Southeast Louisiana Business Center Deficient elevator: 1.6, 2.5, 3.9, 5.1 A17.1 2/24/16 Deficient elevator: 1.6, 1.18, 2.35, 3.9, Southeastern Louisiana University 18 S03276 UC00 University Center 5.1 A17.1 2/24/16 Repair emergency lights, service fire Southeastern Louisiana University 18 L13913 HMB0 Housing Maintenance Building extinguishers 4.5.8. 2/25/16 Deficient elevator: 1.5, 1.6, 1.8, 2.7 , Southeastern Louisiana University 18 S22065 BIOL Biology Building Addition 2.6 A17.1 2/25/16 Southeastern Louisiana University 18 S03200 MEAD Eleanore H. Meade Hall Deficient elevator: 1.5, 1.6, 1.18 A17.1 2/25/16 Southeastern Louisiana University 18 S03198 CH00 J. Leon Clark Hall Deficient elevator: 1.16, 1.18, 2.14 A17.1 2/25/16 Southeastern Louisiana University 18 S13156 SAC0 Pennington Student Activity Center Deficient elevator: 2.5, 3.9 A17.1 2/25/16 Southeastern Louisiana University 18 S15769 INMO Parking Garage Deficient elevator: 1.6, 1.8, 2.7, 5.1 A17.1 2/25/16 Southeastern Louisiana University 18 S13760 SE02 Southeastern Oaks #2 Repair/replace smoke detector RS 40:1575 2/26/16 Repair/replace smoke detector, repair Southeastern Louisiana University 18 S13761 SE03 Southeastern Oaks #3 emergency light RS 40:1575 2/26/16 Southeastern Louisiana University 18 S13762 SE04 Southeastern Oaks #4 Repair emergency and strobe lights RS 40:1575 2/26/16 Southeastern Louisiana University 18 S13763 SE05 Southeastern Oaks #5 Repair emergency lights RS 40:1575 2/26/16 Southeastern Louisiana University 18 S13764 SE06 Southeastern Oaks #6 Repair emergency lights RS 40:1575 2/26/16 Southeastern Louisiana University 18 S03211 AZH0 Charles Analone Hall Deficient elevator: 1.6, 2.14 A17.1 2/26/16 Deficient elevator: 1.5, 1.16, 2.14, 3.8, Southeastern Louisiana University 18 S03242 DVIC D. Vickers Hall 3.9 A17.1 2/26/16 Deficient elevator: 1.5, 1.6, 1.7, 2.4, Southeastern Louisiana University 18 S13256 FAY0 Fayard Hall 2.7,3.9 A17.1 2/26/16 Deficient elevator: 1.1, 1.5, 1.6, 2.3, Southeastern Louisiana University 18 S03201 TH00 G. Jack Tinsley Hall 2.14, 3.9 A17.1 2/26/16 Deficient elevator: 1.5, 1.6, 1.8, 1.18, Southeastern Louisiana University 18 S03228 MIMS Gertie Lee Mims Hall 2.12, 2.14, 3.9, 5.1 A17.1 2/26/16 Kinesiology & Health Studies Building Southeastern Louisiana University 18 S22165 KHSA Annex Deficient elevator: 1.18, 2.7, 3.9 A17.1 2/26/16 Deficient elevator: 1.18, 2.14, 3.2, 3.8, Southeastern Louisiana University 18 S03240 PH00 R.T. Pursley Hall 3.9, 6.4 A17.1 2/26/16 Repair and inspect fire sprinkler system Southeastern Louisiana University 18 S03242 DVIC D. Vickers Hall (yellow tagged) LAC 55:V:3037 3/17/16

Southeastern Louisiana University 18 S03200 MEAD Eleanore H. Meade Hall Repair sprinkler system (yellow tagged) LAC 55:V:3037 3/17/16

Southeastern Louisiana University 18 S03267 MUSA Music Annex Repair sprinkler system (yellow tagged) LAC 55:V:3037 3/17/16

Southeastern Louisiana University 18 S03243 UPD0 Range Hall Repair sprinkler system (yellow tagged) LAC 55:V:3037 3/17/16 Service, inspect fire panel (yellow Southeastern Louisiana University 18 L13853 LAH0 Louisiana Hall tagged) LAC 55:V:3037 3/17/16 Southeastern Louisiana University 18 L13851 TAYH Taylor Hall Mark means of egress 29.2.10 4/8/16 Southeastern Louisiana University 18 L15440 SHAD Hammond Hall Repair sprinkler system LAC 55:V:3037 4/20/16

Southeastern Louisiana University 18 L15442 SHAB St. Tammany Hall Repair sprinkler system (yellow tagged) LAC 55:V:3037 4/20/16

Southeastern Louisiana University 18 L15439 SHAC Tangiphoa Hall Repair sprinkler system (yellow tagged) LAC 55:V:3037 4/20/16

Southeastern Louisiana University 18 L13851 TAYH Taylor Hall Repair sprinkler system (yellow tagged) LAC 55:V:3037 4/20/16

Southeastern Louisiana University 18 L15441 SHAA Washington Hall Repair sprinkler system (yellow tagged) LAC 55:V:3037 4/20/16 Southeastern Louisiana University 18 S03245 TECM Charles E. Cate Teacher Ed. Center Blocked exit RS 40 5/10/16 Southeastern Louisiana University 18 S03240 PH00 R.T. Pursley Hall Repair emergency lights RS 40 5/10/16 Southeastern Louisiana University 18 S11989 NORC Concession Building Repair emergency lights RS 40 6/21/16 Univeristy of Louisiana Monroe 16 S0884 837007/29 Band Building problems with weight of doors/door sticking101:7.2.1.4 10/9/15 Univeristy of Louisiana Monroe 16 S08907 837007/45 Golf Facility repair emergency lighting 4.6.13.1 6/23/16 Univeristy of Louisiana Monroe 16 S08907 837007/45 Golf Facility inspect and tag fire extinguisher 55v3035 6/23/16 Univeristy of Louisiana Monroe 16 L14898 837007/4 Bayou Commons #1 Fire & stairwell doors repaired to close and latch101:6-6113 10/21/15 Univeristy of Louisiana Monroe 16 L14898 837007/4 Bayou Commons #1 Repair or replace emergency lights 101:4.6.13.1 10/21/15 Univeristy of Louisiana Monroe 16 L14898 837007/4 Bayou Commons #1 Repair open holes in 3rd floor room for proper operation of sprinkler systemNFPA 13 10/21/15 Univeristy of Louisiana Monroe 16 L14899 837007/5 Bayou Commons #2 maintain smoke detection systems 101:4.6.13.1 2/5/16 Univeristy of Louisiana Monroe 16 L14899 837007/5 Bayou Commons #2 stairwell fire doors should close and latch101:6-6113 2/5/16 Univeristy of Louisiana Monroe 16 L14899 837007/5 Bayou Commons #2 sprinkler riser should have clear path of accessNFPA 25:4.1.2 2/5/16 Univeristy of Louisiana Monroe 16 L14899 837007/5 Bayou Commons #2 maintain sprinkler heads NFPA 13 2/5/16 Univeristy of Louisiana Monroe 16 L14899 837007/5 Bayou Commons #2 painted sprinkler heads from manufacturer onlyNFPA13:6.2.6.2.2 2/5/16 Univeristy of Louisiana Monroe 16 L14899 837007/5 Bayou Commons #2 maintain emergency lights 101:4.6.13.1 2/5/16 Univeristy of Louisiana Monroe 16 L14899 837007/5 Bayou Commons #2 rated walls with a sprinkler system should be maintainedNFPA 13 2/5/16 Univeristy of Louisiana Monroe 16 L14899 837007/5 Bayou Commons #2 repair exit door that does not consistently release the latch101:7.2.1.4 2/5/16 Univeristy of Louisiana Monroe 16 L14899 837007/5 Bayou Commons #2 means of egress shall be maintained free and unobstructed 101:4.5.3.2 2/5/16 Univeristy of Louisiana Monroe 16 L14899 837007/5 Bayou Commons #2 bathroom door handle should be of level styleADAG 2/5/16 Univeristy of Louisiana Monroe 16 L14900 837007/6 Bayou Village Suites maintain smoke detection systems 101:4.6.13.1 2/5/16 Univeristy of Louisiana Monroe 16 L14900 837007/6 Bayou Village Suites stairwell fire doors should close and latch101:6-6113 2/5/16 Univeristy of Louisiana Monroe 16 L14900 837007/6 Bayou Village Suites sprinkler riser should have clear path of accessNFPA 25:4.1.2 2/5/16 Univeristy of Louisiana Monroe 16 L14900 837007/6 Bayou Village Suites painted sprinkler heads from manufacturer onlyNFPA 13:6.2.6.2.2 2/5/16 Univeristy of Louisiana Monroe 16 L14900 837007/6 Bayou Village Suites manitain all emergency lights 101:4.6.13.1 2/5/16 Univeristy of Louisiana Monroe 16 L14900 837007/6 Bayou Village Suites rated walls with a sprinkler system should be maintainedNFPA 13 2/5/16 Univeristy of Louisiana Monroe 16 Bayou Village Bldg. 5,6,7 Maintain smoke detection systems 101:4.6.13.1 10/22/15 Univeristy of Louisiana Monroe 16 Fire & stairwell doors repaired to close and latch101:6-6113 10/22/15 Univeristy of Louisiana Monroe 16 Remove storage in path of spinkler riser bldg. 7NFPA 25:4.1.2 10/22/15 Univeristy of Louisiana Monroe 16 repair fire alarm panel. Yellow tagged. 55v3037 10/22/15 Univeristy of Louisiana Monroe 16 Candles prohibited, Room 5311A 40v1575 10/22/15 Univeristy of Louisiana Monroe 16 maintain emergency lights 101:4.6.13.1 10/22/15 Univeristy of Louisiana Monroe 16 S08862 837007/10 Biedenharn Hall live parts guarded against accidental contactNFPA 70 110-27 (A) 10/5/15 Univeristy of Louisiana Monroe 16 S14212 837049/1 Bienville Building (Pharmacy) correct fire extinguisher in maintenance roomNFPA 10 6/10/16 Univeristy of Louisiana Monroe 16 S14212 837049/1 Bienville Building (Pharmacy) fire alarm system certification out of date55v3037 6/10/16 Univeristy of Louisiana Monroe 16 S08863 837007/11 Brown Hall repair/replace emergency lights 1967 LSC 2-3112 10/5/15 Univeristy of Louisiana Monroe 16 S08863 837007/11 Brown Hall room 119 covers over receptacles & switchesNFPA 1970 110-27(A) 11/5/15 Univeristy of Louisiana Monroe 16 S08863 837007/11 Brown Hall mens locker room receptacles & switch coversNFPA 1970 110-27(A) 11/5/15 Univeristy of Louisiana Monroe 16 S08905 837007/43 Chemistry & Natural Science repair or replace latching hardware on 1st floor8.5.4.3 6/30/16 Univeristy of Louisiana Monroe 16 S08905 837007/43 Chemistry & Natural Science stairwell doors don't fully close 8.5.4.4 6/30/16 Univeristy of Louisiana Monroe 16 S28495 837007/98 Child Development Center remove hasp and lock from laundry room door101:4.5.3.2 10/6/15 Univeristy of Louisiana Monroe 16 S28495 837007/98 Child Development Center fire alarm system should be certified 55v3037 10/6/15 Univeristy of Louisiana Monroe 16 S28495 837007/98 Child Development Center no one shall obstruct any exit passage 40:1583 10/6/15 Univeristy of Louisiana Monroe 16 S09841 837007/64 Clarke Williams Student Success Centerrepair/replace emergency lights 1967 LSC 2-3112 10/6/15 Univeristy of Louisiana Monroe 16 S09841 837007/64 Clarke Williams Student Success Centerservice fire alarm system 55v3037 6/24/16 Univeristy of Louisiana Monroe 16 S09841 837007/64 Clarke Williams Student Success Centerproperly maintain life safety features NFPA 101:4.6.12.2 6/24/16 Univeristy of Louisiana Monroe 16 S09841 837007/64 Clarke Williams Student Success Centerequipment grounding conductors should be permitted to be bare, covered, or insulatedNFPA 70:250.119 6/24/16 Univeristy of Louisiana Monroe 16 S09841 837007/64 Clarke Williams Student Success Centerprovide intersystem bonding terminationNFPA 70:250.94 6/24/16 Univeristy of Louisiana Monroe 16 S09841 837007/64 Clarke Williams Student Success Centerclose unused openings for circuit breakersNFPA 70:408.7 6/24/16 Univeristy of Louisiana Monroe 16 S09841 837007/64 Clarke Williams Student Success Centerboth ends of raceway should be bonded to the contained conductorNFPA 70:830.100A6 6/24/16 Univeristy of Louisiana Monroe 16 S08943 837007/66 Coenen Hall provide emergency lighting 101:32.2.9.1 10/6/15 Univeristy of Louisiana Monroe 16 S08943 837007/66 Coenen Hall issues with door weights/doors sticking 101:7.2.1.4 10/6/15 Univeristy of Louisiana Monroe 16 S08943 837007/66 Coenen Hall repair emergency lighting 101:32.2.9.1 11/6/15 Univeristy of Louisiana Monroe 16 S08943 837007/66 Coenen Hall NE corner exit door sticking; 1 leaf not opening101:7.2.1.4 11/6/15 Univeristy of Louisiana Monroe 16 S08890 837007/34 Construction School Building doors should be provided with panic hardware101:12.2.2.2.3 10/9/15 Univeristy of Louisiana Monroe 16 S08868 837007/15 Garrett Hall emergency lighting should be provided and maintained101:32.2.9.1 10/9/15 Univeristy of Louisiana Monroe 16 S08939 837007/62 Greenhouse (Large) provide portable fire extinguisher LA 55:303D 10/6/15 Univeristy of Louisiana Monroe 16 S08872 837007/18 Hanna Hall signs should be continuously illuminated101:7.10.5.2 10/9/15 Univeristy of Louisiana Monroe 16 S08887 837007/32 Malone Football Stadium have fire extinguishers serviced and taggedLAC 55:V:3059D 10/5/15 Univeristy of Louisiana Monroe 16 S08887 837007/32 Malone Football Stadium repair exit sign in 1st floor locker room 4.6.13.1 6/10/16 Univeristy of Louisiana Monroe 16 S08887 837007/32 Malone Football Stadium repair emergency lights in suite boxes - visitor side4.6.13.1 6/10/16 Univeristy of Louisiana Monroe 16 S08887 837007/32 Malone Football Stadium cover unused openings in 1st floor electrical room70:110-12(a) 6/10/16 Univeristy of Louisiana Monroe 16 S08887 837007/32 Malone Football Stadium install extinguishers correctly in suite boxes - visitor sideNFPA 10 6/10/16 Univeristy of Louisiana Monroe 16 S08887 837007/32 Malone Football Stadium clean dust from sprinkler heard throughout NFPA 13 6/10/16 Univeristy of Louisiana Monroe 16 S08887 837007/32 Malone Football Stadium replace sprinkler head in locker room NFPA13 6/10/16 Univeristy of Louisiana Monroe 16 S08887 837007/32 Malone Football Stadium repair sprinkler assemblies, missing escutcheonsNFPA 13 6/10/16 Univeristy of Louisiana Monroe 16 S13318 837007/75 Hemphill Hall emergency lighting should be provided and maintained101:32.2.9.1 10/9/15 Univeristy of Louisiana Monroe 16 S08953 837007/68 Madison Dorms A & C Repair smoke detectors room 249, 261 101:4.6.13.1 10/22/15 Univeristy of Louisiana Monroe 16 S08953 837007/68 Madison Dorms A & C replace electrical panel covers NFPA 70 10/22/15 Univeristy of Louisiana Monroe 16 S08953 837007/68 Madison Dorms A & C Remove multi plug adapters or use surge protectNFPA 70 10/22/015 Univeristy of Louisiana Monroe 16 S08953 837007/68 Madison Dorms A & C repair or replace exit signs 101:7.10.5 10/22/15 Univeristy of Louisiana Monroe 16 S08953 837007/68 Madison Dorms A & C remove Christmas lights RS 40:1575 10/22/15 Univeristy of Louisiana Monroe 16 S08953 837007/68 Madison Dorms A & C maintain emergency lights 101:4.6.13.1 10/22/15 Univeristy of Louisiana Monroe 16 Madison Dorm B wall plates and receptacles repair/replaceNFPA 70 10/22/15 Univeristy of Louisiana Monroe 16 Madison Dorm B expired tag fire extinguisher 55v3035 10/22/15 Univeristy of Louisiana Monroe 16 Madison Dorm B repair or replace exit signs 101:7.10.5 10/22/15 Univeristy of Louisiana Monroe 16 Madison Dorm B remove Christmas lights from ceiling, room 305RS 40:1575 10/22/15 Univeristy of Louisiana Monroe 16 Madison Dorm B repair outside emergency lights 101:4.6.13.1 10/22/15 Univeristy of Louisiana Monroe 16 S08947 837007/67 Masur Hall exit doors do not open/lock properly 101:5-2131 10/29/15 Univeristy of Louisiana Monroe 16 S08947 837007/67 Masur Hall replace/repair emergency lights 101:2-3.1.1.2 9/18/15 Univeristy of Louisiana Monroe 16 S08947 837007/67 Masur Hall replace missing covers on electrical breaker box70:370-25 9/18/15 Univeristy of Louisiana Monroe 16 S08947 837007/67 Masur Hall fix/replace smoke detector 101:2-3.1.1.2 9/18/15 Univeristy of Louisiana Monroe 16 S13817 836006/77 4709A Athletic Grounds Bldg. have fire extinguishers certified 55v3035 5/24/16 Univeristy of Louisiana Monroe 16 S13817 836006/77 4709A Athletic Grounds Bldg. live parts should be guarded 70:110.27a 5/24/16 Univeristy of Louisiana Monroe 16 S08954 837007/69 Ouachita Hall Fire & stairwell doors repaired to close and latch101:6-6113 10/21/15 Univeristy of Louisiana Monroe 16 S08954 837007/69 Ouachita Hall repair or replace signs in lobby and stairwells101:2-3112 10/21/15 Univeristy of Louisiana Monroe 16 S08954 837007/69 Ouachita Hall replace smoke detectors; wiring 101:2-3112 10/21/15 Univeristy of Louisiana Monroe 16 S08954 837007/69 Ouachita Hall 1st floor handrail repair 101:2-3112 10/21/15 Univeristy of Louisiana Monroe 16 S08942 837007/65 Schulze Dining Hall provide adequate coverage for electrical boxesNFPA 70:314.28 © 6/24/16 Univeristy of Louisiana Monroe 16 S08883 837007/28 Strauss Hall all junctions boxes need proper coverageNFPA70 10/5/15 Univeristy of Louisiana Monroe 16 S08866 837007/13 Stubbs Hall repair/replace emergency lights 1981 LSC 31_1.3.1 10/6/15 Univeristy of Louisiana Monroe 16 S08940 837007/63 Student Union Building service fire alarm system 55:V.3037 10/6/15 Univeristy of Louisiana Monroe 16 S08869 837007/16 University House missing escutcheons on 1st & 2nd floor NFPA 13 11/5/15 Univeristy of Louisiana Monroe 16 S08869 837007/16 University House fire alarm tag expired 55v3037 11/5/15 Univeristy of Louisiana Monroe 16 S08869 837007/16 University House 1st floor rear exit door hadr latching 101:7.2.1.4.5.1 11/5/15 Univeristy of Louisiana Monroe 16 S12809 837007/74 University Library everything with wiring should have a coverNFPA 70 10/5/15 Univeristy of Louisiana Monroe 16 S12809 837007/74 University Library class K extinguisher should be provided for hazardsNFPA 10.6.6.1 10/5/15 Univeristy of Louisiana Monroe 16 S12809 837007/74 University Library sprinkler assembly/piping need to be clearNFPA 13 10/5/15 Univeristy of Louisiana Monroe 16 S12809 837007/74 University Library ceiling tiles should be installed NFPA 13 10/5/15 Univeristy of Louisiana Monroe 16 S28937 837007/102 ULM Water Ski Facility walking surface requires handrails 101:7.2.2.4.1.1 12/10/15 Univeristy of Louisiana Monroe 16 S28937 837007/102 ULM Water Ski Facility install handicap parking signage and striping40:1731 12/10/15 Univeristy of Louisiana Monroe 16 S28940 837007/104 University Park Maintenance Building have all fire extinguishers inspected and tagged55:v.3035 11/28/15 Nicholls State University 15 S15322 0102 Brady Complex Bld. 2 Emergency Lights inoperable NFPA 101 - 7.9.2.1 August 19, 2015 Nicholls State University 15 S15321 0103 Brady Complex Bld. 3 Emergency Lights inoperable NFPA 101 - 7.9.2.1 August 19,2015 Nicholls State University 15 S15319 0104 Brady Complex Bld .4 Emergency Lights inoperable NFPA 101 - 7.9.2.1 August 19,2015 Nicholls State University 15 S15324 0105 Brady Complex Bld. 5 Emergency Lights inoperable NFPA 101 - 7.9.2.1 August 19,2015 Nicholls State University 15 S15320 0106 Brady Complex Bld. 6 Emergency Lights inoperable NFPA 101 - 7.9.2.1 August 19,2015 Nicholls State University 15 S15325 0107 Brady Complex Bld. 7 Emergency Lights inoperable NFPA 101 - 7.9.2.1 August 19,2015 Nicholls State University 15 S15326 0108 Brady Complex Bld. 8 Emergency Lights inoperable NFPA 101 - 7.9.2.1 August 19,2015 Nicholls State University S04305 0017 Ellender Library Portable fire extinguisher needs LAC 55:V November 2, 2015 15 inspection Nicholls State University 15 S04305 0017 Ellender Library Exit signs were not illuminated NFPA 101 - 7.8.1.1 November 2, 2015 owner shall have fire alarm system none (not State inspected and tagged by a licensed LA McNeese State University 14 owned) 5101 CAMPP contractor (Fire Marshal) 40:1646(b) April 28, 2016 EI - Repair inoperative two-way Louisiana Tech University 13 S07879 5 WYLY TOWER #7 communication 1.6 8.6.4.15 March 29, 2016 EI - Phase II operation instructions Louisiana Tech University 13 S07879 5 WYLY TOWER #7 required 1.15 2.27.7 March 29, 2016 EI - Owner to arrange alternate testing Louisiana Tech University 13 S07879 5 WYLY TOWER #7 date 1.17 March 29, 2016 Louisiana Tech University 13 S07879 5 WYLY TOWER #7 EI - Provide door restriction 1.18 2.12.5 March 29, 2016 EI - Provide self closing machine room Louisiana Tech University 13 S07879 5 WYLY TOWER #7 door 2.1 2.7.3.4.1 March 29, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S07879 5 WYLY TOWER #7 ground fault circuit interrupter 2.33 nec 620.85 March 29, 2016 EI - Remove prohibited equipment Louisiana Tech University 13 S07879 5 WYLY TOWER #7 from machine room 2.4 2.7.2.1 March 29, 2016 EI - Remove prohibited equipment Louisiana Tech University 13 S07879 5 WYLY TOWER #7 from machine room 2.4 8.6.4.8 March 29, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S07879 5 WYLY TOWER #7 disconnect switch 2.10 2.29.1 March 29, 2016 EI - Provide a mainlnie disconnect with over current protection and lockable in Louisiana Tech University 13 S07879 5 WYLY TOWER #7 the open position 2.11 2.26.4 March 29, 2016 EI - Provide a mainline disconnect Louisiana Tech University 13 S07879 5 WYLY TOWER #7 within sight of motor controller 2.11 2.26.4 March 29, 2016 EI - Provide a code data plate on the controller or mainline disconnect that indicates the code in effect at the time Louisiana Tech University 13 S07879 5 WYLY TOWER #7 of installation or alteration 2.14 8.6.1.5.1 March 29, 2016 EI - Provide guards on main drive Louisiana Tech University 13 S07879 5 WYLY TOWER #7 sheave 2.18 2.10.1 March 29, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07879 5 WYLY TOWER #7 code section 8.6 2.40 8.6.1.4 March 29, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S07879 5 WYLY TOWER #7 testing is accomplished. 2.40 8.6.11.1 March 29, 2016

EI - A standard railing shall be provided if the distance between the car top and Louisiana Tech University 13 S07879 5 WYLY TOWER #7 any horizontal clearance exceeds 12" 3.4 2.14.1.7.1 March 29, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S07879 5 WYLY TOWER #7 1/2" high 3.9 2.29.1 March 29, 2016 EI - Fire alarm initiating devices shall be installed in hoistway, when sprinklers are located in those hoistways, which will cause elevators to go into Phase I (device should be within 18" of Louisiana Tech University 13 S07879 5 WYLY TOWER #7 sprinkler head) 3.11 2.27.3.2.1 March 29, 2016 EI - Remove prohibited equipment located in the hoistway. (cable in Louisiana Tech University 13 S07879 5 WYLY TOWER #7 hoistway) 3.12 2.8.1 March 29, 2016 EI - Provide guarding of not less than 75 degrees on <>2", <>4" or more projections in hoistway. (uneven pits Louisiana Tech University 13 S07879 5 WYLY TOWER #7 should be protected) (4" 2000 code) 3.13 2.1.6.2 March 29, 2016 EI - Provide a counterweight guard. Louisiana Tech University 13 S07879 5 WYLY TOWER #7 (A17.1-1996) 3.28 2.3.2 March 29, 2016 EI - Owner to arrange alternate testing Louisiana Tech University 13 S07879 5 WYLY TOWER #7 date 4.12 March 29, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07879 5 WYLY TOWER #7 with characters at least 3" high 4.13 2.29.1 March 29, 2016 EI - Phase I operation instructions Louisiana Tech University 13 S07879 5 WYLY TOWER #7 required 4.14 2.27.7 March 29, 2016 EI - Provide a pit stop switch approximately 18" above landing and Louisiana Tech University 13 S07879 5 WYLY TOWER #7 adjacent to pit ladder. 5.1 2.2.6.2 March 29, 2016 EI - Provide a ladder with handholds that extend a minimum of 42" above Louisiana Tech University 13 S07879 5 WYLY TOWER #7 the landing sill. 5.1 2.2.4.2 March 29, 2016 EI - NEC620.85 Provide 125 volt duplex receptical in every pit and it shall be a Louisiana Tech University 13 S07879 5 WYLY TOWER #7 ground fault circuit interrupter. 5.1 nec 620.85 March 29, 2016 Louisiana Tech University 13 S07879 5 WYLY TOWER #1 EI - Provide emergency lighting in car 1.5 2.14.7.1 March 29, 2016 EI - Phase II operation instructions Louisiana Tech University 13 Un3197 5 WYLY TOWER #1 required 1.15 2.27.7 March 29, 2016 EI - Owner to arrange alternate testing Louisiana Tech University 13 Un3197 5 WYLY TOWER #1 date 1.17 March 29, 2016 Louisiana Tech University 13 Un3197 5 WYLY TOWER #1 EI - Provide door restriction 1.18 2.12.5 March 29, 2016 EI - Provide a minimum headroom of 7 Louisiana Tech University 13 Un3197 5 WYLY TOWER #1 feet throughout the machine room 2.2 2.7.4 March 29, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S07879 5 WYLY TOWER #1 ground fault circuit interrupter 2.33 nec 620.85 March 29, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S07879 5 WYLY TOWER #1 disconnect switch 2.10 2.29.1 March 29, 2016 EI - Provide a mainlnie disconnect with over current protection and lockable in Louisiana Tech University 13 Un3197 5 WYLY TOWER #1 the open position 2.11 2.26.4 March 29, 2016 EI - Provide a code data plate on the controller or mainline disconnect that indicates the code in effect at the time Louisiana Tech University 13 S07879 5 WYLY TOWER #1 of installation or alteration 2.14 8.6.1.5.1 March 29, 2016 EI - Provide guards on main drive Louisiana Tech University 13 S07879 5 WYLY TOWER #1 sheave 2.18 2.10.1 March 29, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07879 5 WYLY TOWER #1 code section 8.6 2.40 8.6.1.4 March 29, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S07879 5 WYLY TOWER #1 testing is accomplished. 2.40 8.6.11.1 March 29, 2016

EI - A standard railing shall be provided if the distance between the car top and Louisiana Tech University 13 S07879 5 WYLY TOWER #1 any horizontal clearance exceeds 12" 3.4 2.14.1.7.1 March 29, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S07879 5 WYLY TOWER #1 1/2" high 3.9 2.29.1 March 29, 2016 EI - Provide proper 4" high floor numbering on hoistway side of Louisiana Tech University 13 S07879 5 WYLY TOWER #1 hoistway doors. 3.9 2.29.2 March 29, 2016 EI - All live parts of an electrical apparatus in hoistways, at landings, in or on cars, machine spaces shall be Louisiana Tech University 13 S07879 5 WYLY TOWER #1 enclosed to prevent accidental contact 3.16 nec 620.4 March 29, 2016 EI - Provide a counterweight guard. Louisiana Tech University 13 S07879 5 WYLY TOWER #1 (A17.1-1996) 3.28 2.3.2 March 29, 2016 EI - Owner to arrange alternate testing Louisiana Tech University 13 S07879 5 WYLY TOWER #1 date 4.12 March 29, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07879 5 WYLY TOWER #1 with characters at least 3" high 4.13 2.29.1 March 29, 2016 EI - Provide a pit stop switch approximately 18" above landing and Louisiana Tech University 13 S07879 5 WYLY TOWER #1 adjacent to pit ladder. 5.1 2.2.6.2 March 29, 2016 EI - NEC620.85 Provide 125 volt duplex receptical in every pit and it shall be a Louisiana Tech University 13 S07879 5 WYLY TOWER #1 ground fault circuit interrupter. 5.1 nec 620.85 March 29, 2016 EI - Repair <> normal, <> final, <> emergency, <> speed reducing, Terminal stopping device<>s. (bottom Louisiana Tech University 13 S07879 5 WYLY TOWER #1 final limit) 5.3 2.25, 3.25 March 29, 2016 EI - Repair fire Service <> Phase I <> Louisiana Tech University 13 S07879 5 WYLY TOWER #1 Phase II (Phase II inoperable) 6.4 8.6.11.1 March 29, 2016 Louisiana Tech University 13 S07879 5 WYLY TOWER #2 EI - Provide emergency lighting in car 1.5 2.14.7.1 March 28, 2016 EI - Replace with at least equivalent <> material <> strength <> design. Louisiana Tech University 13 S07879 5 WYLY TOWER #2 (missing in car handrail back wall) 1.12 8.6.3.1 March 28, 2016 EI - Owner to arrange alternate testing Louisiana Tech University 13 S07879 5 WYLY TOWER #2 date 1.17 March 28, 2016 Louisiana Tech University 13 S07879 5 WYLY TOWER #2 EI - Provide door restriction 1.18 2.12.5 March 28, 2016 EI - Provide a minimum headroom of 7 Louisiana Tech University 13 Un3197 5 WYLY TOWER #2 feet throughout the machine room 2.2 2.7.4 March 28, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S07879 5 WYLY TOWER #2 ground fault circuit interrupter 2.33 nec 620.85 March 28, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S07879 5 WYLY TOWER #2 disconnect switch 2.10 2.29.1 March 28, 2016 EI - Provide a mainlnie disconnect with over current protection and lockable in Louisiana Tech University 13 Un3197 5 WYLY TOWER #2 the open position 2.11 2.26.4 March 28, 2016 EI - Provide a code data plate on the controller or mainline disconnect that indicates the code in effect at the time Louisiana Tech University 13 S07879 5 WYLY TOWER #2 of installation or alteration 2.14 8.6.1.5.1 March 28, 2016 EI - Provide guards on main drive Louisiana Tech University 13 S07879 5 WYLY TOWER #2 sheave 2.18 2.10.1 March 28, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07879 5 WYLY TOWER #2 code section 8.6 2.40 8.6.1.4 March 28, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S07879 5 WYLY TOWER #2 testing is accomplished. 2.40 8.6.11.1 March 28, 2016

EI - A standard railing shall be provided if the distance between the car top and Louisiana Tech University 13 S07879 5 WYLY TOWER #2 any horizontal clearance exceeds 12" 3.4 2.14.1.7.1 March 28, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S07879 5 WYLY TOWER #2 1/2" high 3.9 2.29.1 March 28, 2016 EI - Provide proper 4" high floor numbering on hoistway side of Louisiana Tech University 13 S07879 5 WYLY TOWER #2 hoistway doors. 3.9 2.29.2 March 28, 2016 EI - Provide hoist rope anti-rotation, Louisiana Tech University 13 S07879 5 WYLY TOWER #2 (hobble). (A17.3 "if replaced") 3.23 8.6.4.1.3 March 28, 2016 EI - Provide a counterweight guard. Louisiana Tech University 13 S07879 5 WYLY TOWER #2 (A17.1-1996) 3.28 2.3.2 March 28, 2016 EI - Owner to arrange alternate testing Louisiana Tech University 13 S07879 5 WYLY TOWER #2 date 4.12 March 28, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07879 5 WYLY TOWER #2 with characters at least 3" high 4.13 2.29.1 March 28, 2016 EI - Provide a pit stop switch approximately 18" above landing and Louisiana Tech University 13 S07879 5 WYLY TOWER #2 adjacent to pit ladder. 5.1 2.2.6.2 March 28, 2016 EI - NEC620.85 Provide 125 volt duplex receptical in every pit and it shall be a Louisiana Tech University 13 S07879 5 WYLY TOWER #2 ground fault circuit interrupter. 5.1 nec 620.85 March 29, 2016 Louisiana Tech University 13 S07879 5 WYLY TOWER #3 EI - Provide emergency lighting in car 1.5 2.14.7.1 March 29, 2016 EI - Phase II operation instructions Louisiana Tech University 13 S07879 5 WYLY TOWER #3 required 1.15 2.27.7 March 29, 2016 EI - Owner to arrange alternate testing Louisiana Tech University 13 S07879 5 WYLY TOWER #3 date 1.17 March 29, 2016 Louisiana Tech University 13 S07879 5 WYLY TOWER #3 EI - Provide door restriction 1.18 2.12.5 March 29, 2016 EI - Provide a minimum headroom of 7 Louisiana Tech University 13 Un3197 5 WYLY TOWER #3 feet throughout the machine room 2.2 2.7.4 March 29, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S07879 5 WYLY TOWER #3 ground fault circuit interrupter 2.33 nec 620.85 March 29, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S07879 5 WYLY TOWER #3 disconnect switch 2.10 2.29.1 March 29, 2016 EI - Provide a mainlnie disconnect with over current protection and lockable in Louisiana Tech University 13 Un3197 5 WYLY TOWER #3 the open position 2.11 2.26.4 March 29, 2016 EI - Provide a code data plate on the controller or mainline disconnect that indicates the code in effect at the time Louisiana Tech University 13 S07879 5 WYLY TOWER #3 of installation or alteration 2.14 8.6.1.5.1 March 29, 2016 EI - Provide guards on main drive Louisiana Tech University 13 S07879 5 WYLY TOWER #3 sheave 2.18 2.10.1 March 29, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07879 5 WYLY TOWER #3 code section 8.6 2.40 8.6.1.4 March 29, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S07879 5 WYLY TOWER #3 testing is accomplished. 2.40 8.6.11.1 March 29, 2016

EI - A standard railing shall be provided if the distance between the car top and Louisiana Tech University 13 S07879 5 WYLY TOWER #3 any horizontal clearance exceeds 12" 3.4 2.14.1.7.1 March 29, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S07879 5 WYLY TOWER #3 1/2" high 3.9 2.29.1 March 29, 2016 EI - Provide proper 4" high floor numbering on hoistway side of Louisiana Tech University 13 S07879 5 WYLY TOWER #3 hoistway doors. 3.9 2.29.2 March 29, 2016 EI - Provide hoist rope anti-rotation, Louisiana Tech University 13 S07879 5 WYLY TOWER #3 (hobble). (A17.3 "if replaced") 3.23 8.6.4.1.3 March 29, 2016 EI - Provide a counterweight guard. Louisiana Tech University 13 S07879 5 WYLY TOWER #3 (A17.1-1996) 3.28 2.3.2 March 29, 2016 EI - Owner to arrange alternate testing Louisiana Tech University 13 S07879 5 WYLY TOWER #3 date 4.12 March 29, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07879 5 WYLY TOWER #3 with characters at least 3" high 4.13 2.29.1 March 29, 2016 EI - Provide a pit stop switch approximately 18" above landing and Louisiana Tech University 13 S07879 5 WYLY TOWER #3 adjacent to pit ladder. 5.1 2.2.6.2 March 29, 2016 EI - NEC620.85 Provide 125 volt duplex receptical in every pit and it shall be a Louisiana Tech University 13 S07879 5 WYLY TOWER #3 ground fault circuit interrupter. 5.1 nec 620.85 March 29, 2016 EI - Repair fire Service <> Phase I <> Louisiana Tech University 13 S07879 5 WYLY TOWER #3 Phase II (Phase II inoperable) 6.4 8.6.11.1 March 29, 2016 Louisiana Tech University 13 S07879 5 WYLY TOWER #4 EI - Provide emergency lighting in car 1.5 2.14.7.1 March 29, 2016 EI - Repair inoperative two-way Louisiana Tech University 13 S07879 5 WYLY TOWER #4 communication 1.6 8.6.4.15 March 29, 2016 EI - Owner to arrange alternate testing Louisiana Tech University 13 S07879 5 WYLY TOWER #4 date 1.17 March 29, 2016 Louisiana Tech University 13 S07879 5 WYLY TOWER #4 EI - Provide door restriction 1.18 2.12.5 March 29, 2016 EI - Provide self closing machine room Louisiana Tech University 13 S07879 5 WYLY TOWER #4 door 2.1 2.7.3.4.1 March 29, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S07879 5 WYLY TOWER #4 ground fault circuit interrupter 2.33 nec 620.85 March 29, 2016 EI - Remove prohibited equipment Louisiana Tech University 13 S07879 5 WYLY TOWER #4 from machine room 2.4 8.6.4.8 March 29, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S07879 5 WYLY TOWER #4 disconnect switch 2.10 2.29.1 March 29, 2016 EI - Provide a mainlnie disconnect with over current protection and lockable in Louisiana Tech University 13 Un3197 5 WYLY TOWER #4 the open position 2.11 2.26.4 March 29, 2016 EI - Provide a mainline disconnect Louisiana Tech University 13 S07879 5 WYLY TOWER #4 within sight of motor controller 2.11 2.26.4 March 29, 2016 EI - Provide a code data plate on the controller or mainline disconnect that indicates the code in effect at the time Louisiana Tech University 13 S07879 5 WYLY TOWER #4 of installation or alteration 2.14 8.6.1.5.1 March 29, 2016 EI - Provide guards on main drive Louisiana Tech University 13 S07879 5 WYLY TOWER #4 sheave 2.18 2.10.1 March 29, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07879 5 WYLY TOWER #4 code section 8.6 2.40 8.6.1.4 March 29, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S07879 5 WYLY TOWER #4 testing is accomplished. 2.40 8.6.11.1 March 29, 2016 EI - Provide maintenance and upkeep Louisiana Tech University 13 S07879 5 WYLY TOWER #4 of car top. 3.4 8.6.4.9 March 29, 2016 EI - Provide maintenance and upkeep Louisiana Tech University 13 S07879 5 WYLY TOWER #4 of car top. 3.6 2.25 3.25 March 29, 2016 EI - Repair <>normal, <>final, <>emergency, <>speed reducing Louisiana Tech University 13 S07879 5 WYLY TOWER #4 terminal stopping device <>s 3.4 2.14.1.7.1 March 29, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S07879 5 WYLY TOWER #4 1/2" high 3.9 2.29.1 March 29, 2016 EI - Provide proper 4" high floor numbering on hoistway side of Louisiana Tech University 13 S07879 5 WYLY TOWER #4 hoistway doors. 3.9 2.29.2 March 29, 2016 EI - Fire alarm initiating devices shall be installed in hoistway, when sprinklers are located in those hoistways, which will cause elevators to go into Phase I (device should be within 18" of Louisiana Tech University 13 S07879 5 WYLY TOWER #4 sprinkler head) 3.11 2.27.3.2.1 March 29, 2016 EI - Provide a counterweight guard. Louisiana Tech University 13 S07879 5 WYLY TOWER #4 (A17.1-1996) 3.28 2.3.2 March 29, 2016 EI - Owner to arrange alternate testing Louisiana Tech University 13 S07879 5 WYLY TOWER #4 date 4.12 March 29, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07879 5 WYLY TOWER #4 with characters at least 3" high 4.13 2.29.1 March 29, 2016 EI - Phase I operation instructions Louisiana Tech University 13 S07879 5 WYLY TOWER #4 required 4.14 2.27.7 March 29, 2016 EI - Provide a pit stop switch approximately 18" above landing and Louisiana Tech University 13 S07879 5 WYLY TOWER #4 adjacent to pit ladder. 5.1 2.2.6.2 March 29, 2016 EI - Provide a ladder with handholds that extend a minimum of 42" above Louisiana Tech University 13 S07879 5 WYLY TOWER #4 the landing sill. 5.1 2.2.4.2 March 29, 2016 EI - NEC620.85 Provide 125 volt duplex receptical in every pit and it shall be a Louisiana Tech University 13 S07879 5 WYLY TOWER #4 ground fault circuit interrupter. 5.1 nec 620.85 March 29, 2016 EI - Provide a disconnect for the car lighting that is fusible and lockable in Louisiana Tech University 13 S07873 68 Stadium #1 the off position. 1.5 2.26.4 March 23, 2016 Louisiana Tech University 13 S07873 68 #1 EI - Provide emergency lighting in car 1.5 2.14.7.1 March 23, 2016 EI - Provide adjustment to excessive Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #1 door closing force 1.8 8.6.4.13.2 March 23, 2016 Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #1 EI - No Phase 2 Installed 1.15 March 23, 2016 Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #1 EI - Provide door restriction 1.18 2.12.5 March 23, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #1 ground fault circuit interrupter 2.3 nec 620.85 March 23, 2016 EI - Provide proper <>natural, <>mechanical ventilation in machine room to avoid overheating of Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #1 equipment 2.7.5.2 March 23, 2016 EI - Provide a guard on machine room Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #1 exposed gears, sprockets, and belts 2.9 2.10.1, 3.10 March 23, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #1 disconnect switch 2.10 2.29.1 March 23, 2016 EI - Provide a code data plate on the controller or mainline disconnect that indicates the code in effect at the time Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #1 of installation or alteration 2.14 8.6.1.5.1 March 23, 2016 EI - Replace gas cock type valve with a valve rated for the designed pressures and designed for hydraulic oil Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #1 application 2.35 3.19.3.1 March 23, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #1 code section 8.6 2.41 8.6.1.4 March 23, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #1 testing is accomplished. 2.41 8.6.11.1 March 23, 2016 EI - Provide car top light with guard and Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #1 electrical outlet 3.2 2.14.7.1.4 March 23, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #1 1/2" high 3.9 2.29.1 March 23, 2016 EI - Provide proper 4" high floor numbering on hoistway side of Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #1 hoistway doors. 3.9 2.29.2 March 23, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #1 with characters at least 3" high 3.9 2.29.1 March 23, 2016 EI - Provide a pit stop switch approximately 18" above landing and Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #1 adjacent to pit ladder. 5.1 2.2.6.2 March 23, 2016 EI - Repair <>upper <>lower Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #1 inoperative pit stop switch 5.1 2.2.4.2 March 23, 2016 Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #1 EI - Provide fire operation to elevator 6.1-6.4 March 23, 2016 Louisiana Tech University 13 S07882 157 EI - Provide emergency lighting in car 1.5 2.14.7.1 March 23, 2016 EI - Repair inoperative two-way Louisiana Tech University 13 S07882 157 Thomas Assembly Center communication 1.6 8.6.4.15 March 23, 2016 Louisiana Tech University 13 S07882 157 Thomas Assembly Center EI - Provide door restriction 1.18 2.12.5 March 23, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S07882 157 Thomas Assembly Center ground fault circuit interrupter 2.3 nec 620.85 March 23, 2016 EI - Provide proper <>natural, <>mechanical ventilation in machine room to avoid overheating of Louisiana Tech University 13 S07882 157 Thomas Assembly Center equipment 2.7.5.2 March 23, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S07882 157 Thomas Assembly Center disconnect switch 2.10 2.29.1 March 23, 2016 EI - Provide car lighting disconnect in machine room, fused & lockable in the Louisiana Tech University 13 S07882 157 Thomas Assembly Center off position and labeled "Car Lighting" 2.11 2.26.4, 3.26 March 23, 2016 EI - Provide current wiring diagrams in Louisiana Tech University 13 S07882 157 Thomas Assembly Center the machine room 2.12 8.6.1.6.3(a) March 23, 2016 EI - Provide a code data plate on the controller or mainline disconnect that indicates the code in effect at the time Louisiana Tech University 13 S07882 157 Thomas Assembly Center of installation or alteration 2.14 8.6.1.5.1 March 23, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07882 157 Thomas Assembly Center code section 8.6 2.41 8.6.1.4 March 23, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S07882 157 Thomas Assembly Center testing is accomplished. 2.41 8.6.11.1 March 23, 2016 EI - Provide car top light with guard and Louisiana Tech University 13 S07882 157 Thomas Assembly Center electrical outlet 3.2 2.14.7.1.4 March 23, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S07882 157 Thomas Assembly Center 1/2" high 3.9 2.29.1 March 23, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07882 157 Thomas Assembly Center with characters at least 3" high 3.9 2.29.1 March 23, 2016 EI - Provide sump cover flush with pit Louisiana Tech University 13 S07882 157 Thomas Assembly Center floor 5.1 2.2.2.6 March 23, 2016 EI - Provide a pit stop switch approximately 18" above landing and Louisiana Tech University 13 S07882 157 Thomas Assembly Center adjacent to pit ladder. 5.1 2.2.6.2 March 23, 2016 Louisiana Tech University 13 S07882 157 Thomas Assembly Center EI - Provide fire operation to elevator 6.1-6.4 March 23, 2016 Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #2 EI - Provide emergency lighting in car 1.5 2.14.7.1 March 23, 2016 EI - Adjust excessive door closing force Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #2 to less than 30 lbs 1.8 2.13.4.2.3 March 23, 2016 Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #2 EI - No Phase 2 Installed 1.15 March 23, 2016 Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #2 EI - Provide door restriction 1.18 2.12.5 March 23, 2016 EI - Provide a safe and convenient means of access to the machine room Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #2 (roof hatch needs maintenance) 2.1 2.7.3.1 March 23, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #2 ground fault circuit interrupter 2.3 nec 620.85 March 23, 2016 EI - Provide proper <>natural, <>mechanical ventilation in machine room to avoid overheating of Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #2 equipment 2.7.5.2 March 23, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #2 disconnect switch 2.10 2.29.1 March 23, 2016 EI - Provide a code data plate on the controller or mainline disconnect that indicates the code in effect at the time Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #2 of installation or alteration 2.14 8.6.1.5.1 March 23, 2016 EI - All live parts of an electrical apparatus in hoistways, at landings, in or on cars, machine spaces shall be enclosed to prevent accidental contact Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #2 (motor leads are not in any enclosure) 2.18 nec620.4 March 23, 2016 EI - Provide guards on main drive Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #2 sheave 2.25 2.10.1 March 23, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #2 code section 8.6 2.40 8.6.1.4 March 23, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #2 testing is accomplished. 2.41 8.6.11.1 March 23, 2016 EI - Provide car top light with guard and Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #2 electrical outlet 3.2 2.14.7.1.4 March 23, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #2 1/2" high 3.9 2.29.1 March 23, 2016 EI - Provide guarding of not less than 75 degrees on <>2", <>4" or more projections in hoistway. (uneven pits Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #2 should be protected) (4" 2000 code) 3.13 2.1.6.2 March 23, 2016 EI - Provide hoist rope anti-rotation, Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #2 (hobble). (A17.3 "if replaced") 3.20 2.20.9.8 March 23, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #2 with characters at least 3" high 4.13 2.29.1 March 23, 2016 EI - Phase I operation instructions Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #2 required 4.14 2.27.7 March 23, 2016 EI - Configuration: "reset-off-on", key removed only in "on" & "off" (replace Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #2 work switch ring) 4.14 2.27.3.1.1(b) March 23, 2016 EI - Provide a pit stop switch approximately 18" above landing and Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #2 adjacent to pit ladder. 5.1 2.2.6.2 March 23, 2016 EI - Phase I and Phase II designations first used in code (provide Phase II Louisiana Tech University 13 S07873 68 Joe Aillet Stadium #2 operation) 6.4 A17.3 3.11.3 March 23, 2016 Louisiana Tech University 13 S07879 5 WYLY TOWER #8 EI - Provide emergency lighting in car 1.5 2.14.7.1 March 28, 2016 EI - Repair inoperative two-way Louisiana Tech University 13 S07879 5 WYLY TOWER #8 communication 1.6 8.6.4.15 March 28, 2016 EI - Adjust excessive door closing force Louisiana Tech University 13 S07879 5 WYLY TOWER #8 to less than 30 lbs 1.8 2.13.4.2.3 March 28, 2016 EI - Phase II operation instructions Louisiana Tech University 13 S07879 5 WYLY TOWER #8 required 1.15 2.27.7 March 28, 2016 EI - Owner to arrange alternate testing Louisiana Tech University 13 S07879 5 WYLY TOWER #8 date 1.17 March 28, 2016 Louisiana Tech University 13 S07879 5 WYLY TOWER #8 EI - Provide door restriction 1.18 2.12.5 March 28, 2016 EI - Provide self closing machine room Louisiana Tech University 13 S07879 5 WYLY TOWER #8 door 2.1 2.7.3.4.1 March 28, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S07879 5 WYLY TOWER #8 ground fault circuit interrupter 2.33 nec 620.85 March 28, 2016 EI - Remove prohibited equipment Louisiana Tech University 13 S07879 5 WYLY TOWER #8 from machine room 2.4 2.7.2.1 March 28, 2016 EI - Remove prohibited equipment Louisiana Tech University 13 S07879 5 WYLY TOWER #8 from machine room 2.4 8.6.4.8 March 28, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S07879 5 WYLY TOWER #8 disconnect switch 2.10 2.29.1 March 28, 2016 EI - Provide a mainlnie disconnect with over current protection and lockable in Louisiana Tech University 13 S07879 5 WYLY TOWER #8 the open position 2.11 2.26.4 March 28, 2016 EI - Provide a mainline disconnect Louisiana Tech University 13 S07879 5 WYLY TOWER #8 within sight of motor controller 2.11 2.26.4 March 28, 2016 EI - Provide a code data plate on the controller or mainline disconnect that indicates the code in effect at the time Louisiana Tech University 13 S07879 5 WYLY TOWER #8 of installation or alteration 2.14 8.6.1.5.1 March 28, 2016 EI - Provide guards on main drive Louisiana Tech University 13 S07879 5 WYLY TOWER #8 sheave 2.18 2.10.1 March 28, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07879 5 WYLY TOWER #8 code section 8.6 2.40 8.6.1.4 March 28, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S07879 5 WYLY TOWER #8 testing is accomplished. 2.40 8.6.11.1 March 28, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S07879 5 WYLY TOWER #8 1/2" high 3.9 2.29.1 March 28, 2016 EI - Fire alarm initiating devices shall be installed in hoistway, when sprinklers are located in those hoistways, which will cause elevators to go into Phase I (device should be within 18" of Louisiana Tech University 13 S07879 5 WYLY TOWER #8 sprinkler head) 3.11 2.27.3.2.1 March 28, 2016 EI - Provide guarding of not less than 75 degrees on <>2", <>4" or more projections in hoistway. (uneven pits Louisiana Tech University 13 S07879 5 WYLY TOWER #8 should be protected) (4" 2000 code) 3.13 2.1.6.2 March 28, 2016 EI - Provide hoist rope anti-rotation, (hobble). (A17.3 "if Louisiana Tech University 13 S07879 5 WYLY TOWER #8 replaced")(counterweight) 3.22 2.20.9.8 March 28, 2016 EI - Provide a counterweight guard. Louisiana Tech University 13 S07879 5 WYLY TOWER #8 (A17.1-1996) 3.28 2.3.2 March 28, 2016 EI - Owner to arrange alternate testing Louisiana Tech University 13 S07879 5 WYLY TOWER #8 date 4.12 March 28, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07879 5 WYLY TOWER #8 with characters at least 3" high 4.13 2.29.1 March 28, 2016 EI - Phase I operation instructions Louisiana Tech University 13 S07879 5 WYLY TOWER #8 required 4.14 2.27.7 March 28, 2016 EI - Provide a pit stop switch approximately 18" above landing and Louisiana Tech University 13 S07879 5 WYLY TOWER #8 adjacent to pit ladder. 5.1 2.2.6.2 March 28, 2016 EI - Provide a ladder with handholds that extend a minimum of 42" above Louisiana Tech University 13 S07879 5 WYLY TOWER #8 the landing sill. 5.1 2.2.4.2 March 28, 2016 EI - NEC620.85 Provide 125 volt duplex receptical in every pit and it shall be a Louisiana Tech University 13 S07879 5 WYLY TOWER #8 ground fault circuit interrupter. 5.1 nec 620.85 March 28, 2016 EI - Visual signal required to be a Fire Louisiana Tech University 13 S07879 5 WYLY TOWER #8 Hat symbol 6.4 2.27.3.1.6(h) March 28, 2016 Louisiana Tech University 13 S07879 5 WYLY TOWER #5 EI - Provide emergency lighting in car 1.5 2.14.7.1 March 28, 2016 EI - Replace <> (ceiling grid missing) with at least equivalent <> material <> Louisiana Tech University 13 S07879 5 WYLY TOWER #5 strength <> design 1.12 8.6.3.1 March 28, 2016 EI - Phase II operation instructions Louisiana Tech University 13 S07879 5 WYLY TOWER #5 required 1.15 2.27.7 March 28, 2016 EI - Owner to arrange alternate testing Louisiana Tech University 13 S07879 5 WYLY TOWER #5 date 1.17 March 28, 2016 Louisiana Tech University 13 S07879 5 WYLY TOWER #5 EI - Provide door restriction 1.18 2.12.5 March 28, 2016 EI - Provide self closing machine room Louisiana Tech University 13 S07879 5 WYLY TOWER #5 door 2.1 2.7.3.4.1 March 28, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S07879 5 WYLY TOWER #5 ground fault circuit interrupter 2.33 nec 620.85 March 28, 2016 EI - Remove prohibited equipment Louisiana Tech University 13 S07879 5 WYLY TOWER #5 from machine room 2.4 2.7.2.1 March 28, 2016 EI - Remove prohibited equipment Louisiana Tech University 13 S07879 5 WYLY TOWER #5 from machine room 2.4 8.6.4.8 March 28, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S07879 5 WYLY TOWER #5 disconnect switch 2.10 2.29.1 March 28, 2016 EI - Provide a mainlnie disconnect with over current protection and lockable in Louisiana Tech University 13 S07879 5 WYLY TOWER #5 the open position 2.11 2.26.4 March 28, 2016 EI - Provide a mainline disconnect Louisiana Tech University 13 S07879 5 WYLY TOWER #5 within sight of motor controller 2.11 2.26.4 March 28, 2016 EI - Provide a code data plate on the controller or mainline disconnect that indicates the code in effect at the time Louisiana Tech University 13 S07879 5 WYLY TOWER #5 of installation or alteration 2.14 8.6.1.5.1 March 28, 2016 EI - Provide guards on main drive Louisiana Tech University 13 S07879 5 WYLY TOWER #5 sheave 2.18 2.10.1 March 28, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07879 5 WYLY TOWER #5 code section 8.6 2.40 8.6.1.4 March 28, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S07879 5 WYLY TOWER #5 testing is accomplished. 2.40 8.6.11.1 March 28, 2016

EI - A standard railing shall be provided if the distance between the car top and Louisiana Tech University 13 S07879 5 WYLY TOWER #5 any horizontal clearance exceeds 12" 3.4 2.14.1.7.1 March 28, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S07879 5 WYLY TOWER #5 1/2" high 3.9 2.29.1 March 28, 2016 EI - Provide proper 4" high floor numbering on hoistway side of Louisiana Tech University 13 S07879 5 WYLY TOWER #5 hoistway doors. 3.9 2.29.2 March 28, 2016 EI - Fire alarm initiating devices shall be installed in hoistway, when sprinklers are located in those hoistways, which will cause elevators to go into Phase I (device should be within 18" of Louisiana Tech University 13 S07879 5 WYLY TOWER #5 sprinkler head) 3.11 2.27.3.2.1 March 28, 2016 EI - Remove prohibited equipment located in the hoistway. (cable in Louisiana Tech University 13 S07879 5 WYLY TOWER #5 hoistway) 3.12 2.8.1 March 28, 2016 EI - Provide guarding of not less than 75 degrees on <>2", <>4" or more projections in hoistway. (uneven pits Louisiana Tech University 13 S07879 5 WYLY TOWER #5 should be protected) (4" 2000 code) 3.13 2.1.6.2 March 28, 2016 EI - Provide a counterweight guard. Louisiana Tech University 13 S07879 5 WYLY TOWER #5 (A17.1-1996) 3.28 2.3.2 March 28, 2016 EI - Owner to arrange alternate testing Louisiana Tech University 13 S07879 5 WYLY TOWER #5 date 4.12 March 28, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07879 5 WYLY TOWER #5 with characters at least 3" high 4.13 2.29.1 March 28, 2016 EI - Phase I operation instructions Louisiana Tech University 13 S07879 5 WYLY TOWER #5 required 4.14 2.27.7 March 28, 2016 EI - Provide a pit stop switch approximately 18" above landing and Louisiana Tech University 13 S07879 5 WYLY TOWER #5 adjacent to pit ladder. 5.1 2.2.6.2 March 28, 2016 EI - Provide a ladder with handholds that extend a minimum of 42" above Louisiana Tech University 13 S07879 5 WYLY TOWER #5 the landing sill. 5.1 2.2.4.2 March 28, 2016 EI - NEC620.85 Provide 125 volt duplex receptical in every pit and it shall be a Louisiana Tech University 13 S07879 5 WYLY TOWER #5 ground fault circuit interrupter. 5.1 nec 620.85 March 28, 2016 Louisiana Tech University 13 S07879 5 WYLY TOWER #6 EI - Provide emergency lighting in car 1.5 2.14.7.1 March 28, 2016 EI - Adjust excessive door closing force Louisiana Tech University 13 S07879 5 WYLY TOWER #6 to less than 30 lbs 1.8 2.13.4.2.3 March 28, 2016 EI - Phase II operation instructions Louisiana Tech University 13 S07879 5 WYLY TOWER #6 required 1.15 2.27.7 March 28, 2016 EI - Owner to arrange alternate testing Louisiana Tech University 13 S07879 5 WYLY TOWER #6 date 1.17 March 28, 2016 Louisiana Tech University 13 S07879 5 WYLY TOWER #6 EI - Provide door restriction 1.18 2.12.5 March 28, 2016 EI - Provide self closing machine room Louisiana Tech University 13 S07879 5 WYLY TOWER #6 door 2.1 2.7.3.4.1 March 28, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S07879 5 WYLY TOWER #6 ground fault circuit interrupter 2.33 nec 620.85 March 28, 2016 EI - Remove prohibited equipment Louisiana Tech University 13 S07879 5 WYLY TOWER #6 from machine room 2.4 2.7.2.1 March 28, 2016 EI - Remove prohibited equipment Louisiana Tech University 13 S07879 5 WYLY TOWER #6 from machine room 2.4 8.6.4.8 March 28, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S07879 5 WYLY TOWER #6 disconnect switch 2.10 2.29.1 March 28, 2016 EI - Provide a mainlnie disconnect with over current protection and lockable in Louisiana Tech University 13 S07879 5 WYLY TOWER #6 the open position 2.11 2.26.4 March 28, 2016 EI - Provide a mainline disconnect Louisiana Tech University 13 S07879 5 WYLY TOWER #6 within sight of motor controller 2.11 2.26.4 March 28, 2016 EI - Provide a code data plate on the controller or mainline disconnect that indicates the code in effect at the time Louisiana Tech University 13 S07879 5 WYLY TOWER #6 of installation or alteration 2.14 8.6.1.5.1 March 28, 2016 EI - Provide guards on main drive Louisiana Tech University 13 S07879 5 WYLY TOWER #6 sheave 2.18 2.10.1 March 28, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07879 5 WYLY TOWER #6 code section 8.6 2.40 8.6.1.4 March 28, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S07879 5 WYLY TOWER #6 testing is accomplished. 2.40 8.6.11.1 March 28, 2016

EI - A standard railing shall be provided if the distance between the car top and Louisiana Tech University 13 S07879 5 WYLY TOWER #6 any horizontal clearance exceeds 12" 3.4 2.14.1.7.1 March 28, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S07879 5 WYLY TOWER #6 1/2" high 3.9 2.29.1 March 28, 2016 EI - Provide proper 4" high floor numbering on hoistway side of Louisiana Tech University 13 S07879 5 WYLY TOWER #6 hoistway doors. 3.9 2.29.2 March 28, 2016 EI - Fire alarm initiating devices shall be installed in hoistway, when sprinklers are located in those hoistways, which will cause elevators to go into Phase I (device should be within 18" of Louisiana Tech University 13 S07879 5 WYLY TOWER #6 sprinkler head) 3.11 2.27.3.2.1 March 28, 2016 EI - Remove prohibited equipment located in the hoistway. (cable in Louisiana Tech University 13 S07879 5 WYLY TOWER #6 hoistway) 3.12 2.8.1 March 28, 2016 EI - Provide guarding of not less than 75 degrees on <>2", <>4" or more projections in hoistway. (uneven pits Louisiana Tech University 13 S07879 5 WYLY TOWER #6 should be protected) (4" 2000 code) 3.13 2.1.6.2 March 28, 2016 EI - Owner to arrange alternate testing Louisiana Tech University 13 S07879 5 WYLY TOWER #6 date 4.12 March 28, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07879 5 WYLY TOWER #6 with characters at least 3" high 4.13 2.29.1 March 28, 2016 EI - Phase I operation instructions Louisiana Tech University 13 S07879 5 WYLY TOWER #6 required 4.14 2.27.7 March 28, 2016 EI - Provide a pit stop switch approximately 18" above landing and Louisiana Tech University 13 S07879 5 WYLY TOWER #6 adjacent to pit ladder. 5.1 2.2.6.2 March 28, 2016 EI - Provide a ladder with handholds that extend a minimum of 42" above Louisiana Tech University 13 S07879 5 WYLY TOWER #6 the landing sill. 5.1 2.2.4.2 March 28, 2016 EI - NEC620.85 Provide 125 volt duplex receptical in every pit and it shall be a Louisiana Tech University 13 S07879 5 WYLY TOWER #6 ground fault circuit interrupter. 5.1 nec 620.85 March 28, 2016 EI - Security systems, floors locked out, switched or otherwise, means which prevent the operation of in car PB's Louisiana Tech University 13 S07879 5 WYLY TOWER #6 shall be rendered inoperative. 6.4 2.27.3.3.1(i) March 28, 2016 EI - Keys required for access, operation, inspection, maintenance, repair and emergency shall be made available to Louisiana Tech University 13 S07859 15 Bogard Hall elevator personnel 1.3 8.6.11.1 March 20, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S07859 15 Bogard Hall disconnect switch 2.10 2.29.1 March 20, 2016 EI - Provide car lighting disconnect in machine room, fused & lockable in the Louisiana Tech University 13 S07859 15 Bogard Hall off position and labeled "Car Lighting" 2.11 2.26.4, 3.26 March 20, 2016 EI - Provide a code data plate on the controller or mainline disconnect that indicates the code in effect at the time Louisiana Tech University 13 S07859 15 Bogard Hall of installation or alteration 2.14 8.6.1.5.1 March 20, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07859 15 Bogard Hall code section 8.6 2.41 8.6.1.4 March 20, 2016 EI - Repair inoperative two-way Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 communication 1.6 8.6.4.15 March 23, 2016 EI - Phase II operation instructions Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 required 1.15 2.27.7 March 23, 2016 Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 EI - Provide door restriction 1.18 2.12.5 March 23, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 ground fault circuit interrupter 2.33 nec 620.85 March 23, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 disconnect switch 2.10 2.29.1 March 23, 2016 EI - Provide a code data plate on the controller or mainline disconnect that indicates the code in effect at the time Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 of installation or alteration 2.14 8.6.1.5.1 March 23, 2016 EI - Set the pressure relief valve to open at a pressure not greater than Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 125% of the working pressure 2.31 3.19.4.2(1)c March 23, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 code section 8.6 2.41 8.6.1.4 March 23, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 testing is accomplished. 2.40 8.6.11.1 March 23, 2016 EI - Provide proper 4" high floor numbering on hoistway side of Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 hoistway doors. 3.9 2.29.2 March 23, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 1/2" high 3.9 2.29.1 March 23, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 with characters at least 3" high 4.13 2.29.1 March 23, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S28906 55 Davison Athletic Center #1 code section 8.6 2.40 8.6.1.4 March 31, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S28906 55 Davison Athletic Center #1 testing is accomplished. 2.40 8.6.11.1 March 31, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S28906 55 Davison Athletic Center #2 code section 8.6 2.40 8.6.1.4 March 31, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S28906 55 Davison Athletic Center #2 testing is accomplished. 2.40 8.6.11.1 March 31, 2016 Louisiana Tech University 13 S07855 36 Carson-Taylor Hall EI - Provide emergency lighting in car 1.5 2.14.7.1 March 24, 2016 EI - Replace the phone box door with at least equivalent <> material <> Louisiana Tech University 13 S07855 36 Carson-Taylor Hall strength <> design. 1.12 8.6.3.1 March 24, 2016 EI - Replace fan or fan switch with at least equivalent <>material <>strength Louisiana Tech University 13 S07855 36 Carson-Taylor Hall <>design 1.14 8.6.3.1 March 24, 2016 Louisiana Tech University 13 S07855 36 Carson-Taylor Hall EI - Provide door restriction 1.18 2.12.5 March 24, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S07855 36 Carson-Taylor Hall ground fault circuit interrupter 2.3 nec 620.85 March 24, 2016 EI - Remove prohibited equipment Louisiana Tech University 13 S07855 36 Carson-Taylor Hall from machine room 2.4 2.7.2.1 March 24, 2016 EI - Provide removal of <>dust, <>trash, <>carbon dust, <>oil, <>grease, <>water from machine room floor Louisiana Tech University 13 S07855 36 Carson-Taylor Hall (water on machine room floor) 2.4 2.7.1.1 March 24, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S07855 36 Carson-Taylor Hall disconnect switch 2.10 2.29.1 March 24, 2016 EI - Provide car lighting disconnect in machine room, fused & lockable in the Louisiana Tech University 13 S07855 36 Carson-Taylor Hall off position and labeled "Car Lighting" 2.11 2.26.4, 3.26 March 24, 2016 EI - Provide a code data plate on the controller or mainline disconnect that indicates the code in effect at the time Louisiana Tech University 13 S07855 36 Carson-Taylor Hall of installation or alteration 2.14 8.6.1.5.1 March 24, 2016 EI - Provide the proper horizontal clearances in the hoistway (the jack can not hit the stop ring without th Louisiana Tech University 13 S07855 36 Carson-Taylor Hall elevator hitting the ceiling) 2.31 2.5.2/3.4 March 24, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07855 36 Carson-Taylor Hall code section 8.6 2.41 8.6.1.4 March 24, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S07855 36 Carson-Taylor Hall testing is accomplished. 2.41 8.6.11.1 March 24, 2016 EI - Provide car top light with guard and Louisiana Tech University 13 S07855 36 Carson-Taylor Hall electrical outlet 3.2 2.14.7.1.4 March 24, 2016

EI - A standard railing shall be provided if the distance between the car top and Louisiana Tech University 13 S07855 36 Carson-Taylor Hall any horizontal clearance exceeds 12" 3.4 2.14.1.7.1 March 24, 2016 EI - Provide a minimum headroom of 42" in the overhead space (note code Louisiana Tech University 13 S07855 36 Carson-Taylor Hall relative to 36" minimum…..) 3.4 2.7.4.4 March 24, 2016 EI - Provide car top exit openable only Louisiana Tech University 13 S07855 36 Carson-Taylor Hall from top of car 3.8 2.14.1.5.1 March 24, 2016 EI - Provide proper 4" high floor numbering on hoistway side of Louisiana Tech University 13 S07855 36 Carson-Taylor Hall hoistway doors. 3.9 2.29.2 March 24, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S07855 36 Carson-Taylor Hall 1/2" high 3.9 2.29.1 March 24, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07855 36 Carson-Taylor Hall with characters at least 3" high 3.9 2.29.1 March 24, 2016 EI - Provide a minimum headroom of 42" in the overhead space (note code Louisiana Tech University 13 S07855 36 Carson-Taylor Hall relative to 36" minimum…..) 3.19 2.7.4.4 March 24, 2016 Louisiana Tech University 13 S07855 36 Carson-Taylor Hall EI - Provide fire operation to elevator 6.1-6.4 March 24, 2016 Louisiana Tech University 13 S22068 7789 Tech Pointe EI - Provide door restriction 1.18 2.12.5 March 24, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S22068 7789 Tech Pointe ground fault circuit interrupter 2.3 nec 620.85 March 24, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S22068 7789 Tech Pointe disconnect switch 2.10 2.29.1 March 24, 2016 EI - Set the pressure relief valve to open at a pressure not greater than Louisiana Tech University 13 S22068 7789 Tech Pointe 125% of the working pressure 2.31 3.19.4.2(1)c March 24, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S22068 7789 Tech Pointe code section 8.6 2.41 8.6.1.4 March 24, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S22068 7789 Tech Pointe testing is accomplished. 2.41 8.6.11.1 March 24, 2016 EI - Provide proper 4" high floor numbering on hoistway side of Louisiana Tech University 13 S22068 7789 Tech Pointe hoistway doors. 3.9 2.29.2 March 24, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S22068 7789 Tech Pointe 1/2" high 3.9 2.29.1 March 24, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S22068 7789 Tech Pointe with characters at least 3" high 3.9 2.29.1 March 24, 2016 Louisiana Tech University 13 S28008 9991 College of Business Building EI - Provide door restriction 1.18 2.12.5 March 24, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S28008 9991 College of Business Building ground fault circuit interrupter 2.3 nec 620.85 March 24, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S28008 9991 College of Business Building disconnect switch 2.10 2.29.1 March 24, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S28008 9991 College of Business Building code section 8.6 2.41 8.6.1.4 March 24, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S28008 9991 College of Business Building testing is accomplished. 2.41 8.6.11.1 March 24, 2016 EI - Provide proper 4" high floor numbering on hoistway side of Louisiana Tech University 13 S28008 9991 College of Business Building hoistway doors. 3.9 2.29.2 March 24, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S28008 9991 College of Business Building 1/2" high 3.9 2.29.1 March 24, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S28008 9991 College of Business Building with characters at least 3" high 3.9 2.29.1 March 24, 2016 EI - Phase II operation instructions Louisiana Tech University 13 S07868 58 Nethken required 1.15 2.27.7 March 24, 2016 Louisiana Tech University 13 S07868 58 Nethken EI - Provide door restriction 1.18 2.12.5 March 24, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S07868 58 Nethken ground fault circuit interrupter 2.3 nec 620.85 March 24, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S07868 58 Nethken disconnect switch 2.10 2.29.1 March 24, 2016 EI - Provide a code data plate on the controller or mainline disconnect that indicates the code in effect at the time Louisiana Tech University 13 S07868 58 Nethken of installation or alteration 2.14 8.6.1.5.1 March 24, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07868 58 Nethken code section 8.6 2.41 8.6.1.4 March 24, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S07868 58 Nethken testing is accomplished. 2.41 8.6.11.1 March 24, 2016

EI - A standard railing shall be provided if the distance between the car top and Louisiana Tech University 13 S07868 58 Nethken any horizontal clearance exceeds 12" 3.4 2.14.1.7.1 March 24, 2016 EI - Provide proper 4" high floor numbering on hoistway side of Louisiana Tech University 13 S07868 58 Nethken hoistway doors. 3.9 2.29.2 March 24, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S07868 58 Nethken 1/2" high 3.9 2.29.1 March 24, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07868 58 Nethken with characters at least 3" high 3.9 2.29.1 March 24, 2016 Louisiana Tech University 13 S07833 12 Keeny Hall EI - Provide door restriction 1.18 2.12.5 March 30, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S07833 12 Keeny Hall ground fault circuit interrupter 2.3 nec 620.85 March 30, 2016 EI - Provide self locking (one way Louisiana Tech University 13 S07833 12 Keeny Hall permanent lock) machine room door 2.4 2.7.3.4.1 March 30, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S07833 12 Keeny Hall disconnect switch 2.10 2.29.1 March 30, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07833 12 Keeny Hall code section 8.6 2.41 8.6.1.4 March 30, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S07833 12 Keeny Hall testing is accomplished. 2.41 8.6.11.1 March 30, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S07833 12 Keeny Hall 1/2" high 3.9 2.29.1 March 30, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07833 12 Keeny Hall with characters at least 3" high 3.9 2.29.1 March 30, 2016 Louisiana Tech University 13 S07833 9998 Davison Hall EI - Provide door restriction 1.18 2.12.5 March 30, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S07833 9998 Davison Hall ground fault circuit interrupter 2.3 nec 620.85 March 30, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S07833 9998 Davison Hall disconnect switch 2.10 2.29.1 March 30, 2016 EI - Provide a code data plate on the controller or mainline disconnect that indicates the code in effect at the time Louisiana Tech University 13 S07833 9998 Davison Hall of installation or alteration 2.14 8.6.1.5.1 March 30, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07833 9998 Davison Hall code section 8.6 2.41 8.6.1.4 March 30, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S07833 9998 Davison Hall testing is accomplished. 2.41 8.6.11.1 March 30, 2016 EI - Provide proper 4" high floor numbering on hoistway side of Louisiana Tech University 13 S07833 9998 Davison Hall hoistway doors. 3.9 2.29.2 March 30, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S07833 9998 Davison Hall 1/2" high 3.9 2.29.1 March 30, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07833 9998 Davison Hall with characters at least 3" high 3.9 2.29.1 March 30, 2016 EI - Fire alarm initiating devices shall be installed in hoistway, when sprinklers are located in those hoistways, which will cause elevators to go into Phase I (device should be within 18" of Louisiana Tech University 13 S07833 9998 Davison Hall sprinkler head) 3.11 2.27.3.2.1 March 30, 2016 Louisiana Tech University 13 S07865 56 Visual Arts EI - Provide emergency lighting in car 1.5 2.14.7.1 March 30, 2016 Louisiana Tech University 13 S07865 56 Visual Arts EI - Provide door restriction 1.18 2.12.5 March 30, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S07865 56 Visual Arts ground fault circuit interrupter 2.3 nec 620.85 March 30, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S07865 56 Visual Arts disconnect switch 2.10 2.29.1 March 30, 2016 EI - Set the pressure relief valve to open at a pressure not greater than Louisiana Tech University 13 S07865 56 Visual Arts 125% of the working pressure 2.31 3.19.4.2(1)c March 30, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07865 56 Visual Arts code section 8.6 2.41 8.6.1.4 March 30, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S07865 56 Visual Arts testing is accomplished. 2.41 8.6.11.1 March 30, 2016 EI - Provide proper 4" high floor numbering on hoistway side of Louisiana Tech University 13 S07865 56 Visual Arts hoistway doors. 3.9 2.29.2 March 30, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S07865 56 Visual Arts 1/2" high 3.9 2.29.1 March 30, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07865 56 Visual Arts with characters at least 3" high 3.9 2.29.1 March 30, 2016 EI - Fire alarm initiating devices shall be installed in hoistway, when sprinklers are located in those hoistways, which will cause elevators to go into Phase I (device should be within 18" of Louisiana Tech University 13 S07865 56 Visual Arts sprinkler head) 3.11 2.27.3.2.1 March 30, 2016 EI - Configuration: "pff-hold-on", key removed from any position (present Louisiana Tech University 13 S07865 56 Visual Arts key switch is off-on only) 6.4 2.27.3 March 30, 2016 Louisiana Tech University 13 S13685 1 Hale Hall EI - Provide door restriction 1.18 2.12.5 March 31, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S13685 1 Hale Hall ground fault circuit interrupter 2.3 nec 620.85 March 31, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S13685 1 Hale Hall disconnect switch 2.10 2.29.1 March 31, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S13685 1 Hale Hall code section 8.6 2.41 8.6.1.4 March 31, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S13685 1 Hale Hall testing is accomplished. 2.41 8.6.11.1 March 31, 2016 EI - Provide proper 4" high floor numbering on hoistway side of Louisiana Tech University 13 S13685 1 Hale Hall hoistway doors. 3.9 2.29.2 March 31, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S13685 1 Hale Hall 1/2" high 3.9 2.29.1 March 31, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S13685 1 Hale Hall with characters at least 3" high 3.9 2.29.1 March 31, 2016 EI - provide protection of passengers Louisiana Tech University 13 S07869 57 George G. Madison from potential breakage of car lighting. 1.5 A 17.3 2002 3.4.6 March 31, 2016 EI - Phase II operation instructions Louisiana Tech University 13 S07869 57 George G. Madison required 1.15 2.27.7 March 31, 2016 Louisiana Tech University 13 S07869 57 George G. Madison EI - Provide door restriction 1.18 2.12.5 March 31, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S07869 57 George G. Madison ground fault circuit interrupter 2.3 nec 620.85 March 31, 2016 EI - Spaces containing machines, controllers and other equipment shall be separated from the rest of the Louisiana Tech University 13 S07869 57 George G. Madison building by a fire resistive enclosure 2.4 2.7.1.1.1 March 31, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S07869 57 George G. Madison disconnect switch 2.10 2.29.1 March 31, 2016 EI - Provide car lighting disconnect in machine room, fused & lockable in the Louisiana Tech University 13 S07869 57 George G. Madison off position and labeled "Car Lighting". 2.11 2.26.4, 3.26 March 31, 2016 EI - Provide a code data plate on the controller or mainline disconnect that indicates the code in effect at the time Louisiana Tech University 13 S07869 57 George G. Madison of installation or alteration 2.14 8.6.1.5.1 March 31, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07869 57 George G. Madison code section 8.6 2.41 8.6.1.4 March 31, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S07869 57 George G. Madison testing is accomplished. 2.41 8.6.11.1 March 31, 2016 EI - Provide car top light with guard and Louisiana Tech University 13 S07869 57 George G. Madison electrical outlet 3.2 2.14.7.1.4 March 31, 2016 EI - Provide proper 4" high floor numbering on hoistway side of Louisiana Tech University 13 S07869 57 George G. Madison hoistway doors. 3.9 2.29.2 March 31, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S07869 57 George G. Madison 1/2" high 3.9 2.29.1 March 31, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07869 57 George G. Madison with characters at least 3" high 3.9 2.29.1 March 31, 2016 EI - Audible signal required to be heard from top of car when on inspection Louisiana Tech University 13 S07869 57 George G. Madison operation 6.4 2.27.6 March 31, 2016 EI - Phase I operation instructions Louisiana Tech University 13 S07869 57 George G. Madison required 6.4 2.27.7 March 31, 2016 Louisiana Tech University 13 EI - Louisiana Tech University 13 S07843 17 Tolliver Hall EI - Provide door restriction 1.18 2.12.5 March 31, 2016 EI - Provide a safe and convenient means of access to the machine room Louisiana Tech University 13 S07843 17 Tolliver Hall (roof hatch needs maintenance) 2.1 2.7.3.1 March 31, 2016 EI - Remove or completely separate <> pipes <>and <>ducts not used in conjunction with elevator equipment from the machine room (drain pipe Louisiana Tech University 13 S07843 17 Tolliver Hall leaking water) 2.4 2.8.2 March 31, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S07843 17 Tolliver Hall disconnect switch 2.10 2.29.1 March 31, 2016 EI - Set the pressure relief valve to open at a pressure not greater than Louisiana Tech University 13 S07843 17 Tolliver Hall 125% of the working pressure 2.31 3.19.4.2(1)c March 31, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S07843 17 Tolliver Hall 1/2" high 3.9 2.29.1 March 31, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07843 17 Tolliver Hall with characters at least 3" high 3.9 2.29.1 March 31, 2016 EI - Repair inoperative two-way Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 communication 1.6 8.6.4.15 March 23, 2016 EI - Phase II operation instructions Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 required 1.15 2.27.7 March 23, 2016 Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 EI - Provide door restriction 1.18 2.12.5 March 23, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 ground fault circuit interrupter 2.33 nec 620.85 March 23, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 disconnect switch 2.10 2.29.1 March 23, 2016 EI - Provide current wiring diagrams in Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 the machine room 2.12 8.6.1.6.3(a) March 23, 2016 EI - Provide a code data plate on the controller or mainline disconnect that indicates the code in effect at the time Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 of installation or alteration 2.14 8.6.1.5.1 March 23, 2016 EI - Set the pressure relief valve to open at a pressure not greater than Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 125% of the working pressure 2.31 3.19.4.2(1)c March 23, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 code section 8.6 2.41 8.6.1.4 March 23, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 testing is accomplished. 2.40 8.6.11.1 March 23, 2016 EI - Provide proper 4" high floor numbering on hoistway side of Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 hoistway doors. 3.9 2.29.2 March 23, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 1/2" high 3.9 2.29.1 March 23, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07877 73 Wyly Athletic Center # 1 with characters at least 3" high 4.13 2.29.1 March 23, 2016 Louisiana Tech University 13 S07834 41 Prescott Library EI - Provide door restriction 1.18 2.12.5 March 30, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S07834 41 Prescott Library ground fault circuit interrupter 2.33 nec 620.85 March 30, 2016 EI - Remove prohibited equipment Louisiana Tech University 13 S07834 41 Prescott Library from machine room 2.4 2.7.2.1 March 30, 2016 EI - All live parts of an electrical apparatus in hoistways, at landings, in or on cars, machine spaces shall be Louisiana Tech University 13 S07834 41 Prescott Library enclosed to prevent accidental contact 3.16 nec 620.4 March 30, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S07834 41 Prescott Library disconnect switch 2.10 2.29.1 March 30, 2016 EI - Provide a code data plate on the controller or mainline disconnect that indicates the code in effect at the time Louisiana Tech University 13 S07834 41 Prescott Library of installation or alteration 2.14 8.6.1.5.1 March 30, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07834 41 Prescott Library code section 8.6 2.41 8.6.1.4 March 30, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S07834 41 Prescott Library testing is accomplished. 2.40 8.6.11.1 March 30, 2016 EI - Provide car top light with guard and Louisiana Tech University 13 S07834 41 Prescott Library electrical outlet 3.2 2.14.7.1.4 March 30, 2016

EI - A standard railing shall be provided if the distance between the car top and Louisiana Tech University 13 S07834 41 Prescott Library any horizontal clearance exceeds 12" 3.4 2.14.1.7.1 March 30, 2016 EI - Provide proper 4" high floor numbering on hoistway side of Louisiana Tech University 13 S07834 41 Prescott Library hoistway doors. 3.9 2.29.2 March 30, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S07834 41 Prescott Library 1/2" high 3.9 2.29.1 March 30, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07834 41 Prescott Library with characters at least 3" high 4.13 2.29.1 March 30, 2016 EI - Provide sealing of wall penetrations and holes with fire rating comparable Louisiana Tech University 13 S07834 41 Prescott Library to hoistway walls. 3.10 2.1.1.1 March 30, 2016 EI - Provide 125 volt duplex receptical in every pit and it shall be a ground Louisiana Tech University 13 S07834 41 Prescott Library fault circuit interrupter 5.1 nec 620.85 March 30, 2016 Louisiana Tech University 13 S12296 78 Institute for Micromanfufacturing EI - Provide door restriction 1.18 2.12.5 March 30, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S12296 78 Institute for Micromanfufacturing ground fault circuit interrupter 2.33 nec 620.85 March 30, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S12296 78 Institute for Micromanfufacturing disconnect switch 2.10 2.29.1 March 30, 2016 EI - Provide a disconnect for the car lighting that is fusible and lockable in Louisiana Tech University 13 S12296 78 Institute for Micromanfufacturing the off position. 1.5 2.26.4 March 30, 2016 EI - Provide current wiring diagrams in Louisiana Tech University 13 S12296 78 Institute for Micromanfufacturing the machine room 2.12 8.6.1.6.3(a) March 30, 2016 EI - Provide car top light with guard and Louisiana Tech University 13 S12296 78 Institute for Micromanfufacturing electrical outlet 3.2 2.14.7.1.4 March 30, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S12296 78 Institute for Micromanfufacturing 1/2" high 3.9 2.29.1 March 30, 2016 EI - Provide sealing of wall penetrations and holes with fire rating comparable Louisiana Tech University 13 S12296 78 Institute for Micromanfufacturing to hoistway walls. 3.10 2.1.1.1 March 30, 2016 EI - Fire alarm initiating devices shall be installed in hoistway, when sprinklers are located in those hoistways, which will cause elevators to go into Phase I (device should be within 18" of Louisiana Tech University 13 S12296 78 Institute for Micromanfufacturing sprinkler head) 3.11 2.27.3.2.1 March 30, 2016 EI - Repair Fire Service <>Phase 1 <>Phase II The safety edge can not be Louisiana Tech University 13 S12296 78 Institute for Micromanfufacturing active during recall 6.4 8.6.11.1 March 30, 2016 Louisiana Tech University 13 S28906 55 Davison Athletic Center #3 EI - Provide door restriction 1.18 2.12.5 March 31, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S28906 55 Davison Athletic Center #3 ground fault circuit interrupter 2.33 nec 620.85 March 31, 2016 EI - Provide a mainline disconnect Louisiana Tech University 13 S28906 55 Davison Athletic Center #3 within sight of motor controller 2.11 2.26.4 March 31, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S28906 55 Davison Athletic Center #3 code section 8.6 2.40 8.6.1.4 March 31, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S28906 55 Davison Athletic Center #3 testing is accomplished. 2.40 8.6.11.1 March 31, 2016 Louisiana Tech University 13 S07849 50 Harper Hall #1 EI - Provide emergency lighting in car 1.5 2.14.7.1 April 1, 2016 EI - Repair inoperative two-way Louisiana Tech University 13 S07849 50 Harper Hall #1 communication 1.6 8.6.4.15 April 1, 2016 Louisiana Tech University 13 S07849 50 Harper Hall #1 EI - Provide door restriction 1.18 2.12.5 April 1, 2016 EI - Provide a minimum headroom of 7 Louisiana Tech University 13 S07849 50 Harper Hall #1 feet throughout the machine room 2.2 2.7.4 April 1, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S07849 50 Harper Hall #1 ground fault circuit interrupter 2.33 nec 620.85 April 1, 2016 EI - Provide guards on main drive Louisiana Tech University 13 S07849 50 Harper Hall #1 sheave 2.18 2.10.1 April 1, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07849 50 Harper Hall #1 code section 8.6 2.40 8.6.1.4 April 1, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S07849 50 Harper Hall #1 testing is accomplished. 2.40 8.6.11.1 April 1, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S07849 50 Harper Hall #1 1/2" high 3.9 2.29.1 April 1, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07849 50 Harper Hall #1 with characters at least 3" high 4.13 2.29.1 April 1, 2016 EI - Provide clean down of buffers including plunger. (buffer did not return in optimum time due to Louisiana Tech University 13 S07849 50 Harper Hall #1 collected dirt and debris) 5.9 8.6.4.4.2 April 1, 2016 Louisiana Tech University 13 S07849 50 Harper Hall #2 EI - Provide emergency lighting in car 1.5 2.14.7.1 April 1, 2016 EI - Repair inoperative two-way Louisiana Tech University 13 S07849 50 Harper Hall #2 communication 1.6 8.6.4.15 April 1, 2016 Louisiana Tech University 13 S07849 50 Harper Hall #2 EI - Provide door restriction 1.18 2.12.5 April 1, 2016 EI - Provide a minimum headroom of 7 Louisiana Tech University 13 S07849 50 Harper Hall #2 feet throughout the machine room 2.2 2.7.4 April 1, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S07849 50 Harper Hall #2 ground fault circuit interrupter 2.33 nec 620.85 April 1, 2016 EI - Provide guards on main drive Louisiana Tech University 13 S07849 50 Harper Hall #2 sheave 2.18 2.10.1 April 1, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07849 50 Harper Hall #2 code section 8.6 2.40 8.6.1.4 April 1, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S07849 50 Harper Hall #2 testing is accomplished. 2.40 8.6.11.1 April 1, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S07849 50 Harper Hall #2 1/2" high 3.9 2.29.1 April 1, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07849 50 Harper Hall #2 with characters at least 3" high 4.13 2.29.1 April 1, 2016 Louisiana Tech University 13 S07858 16 Howard Auditorium EI - Provide emergency lighting in car 1.5 2.14.7.1 April 1, 2016 EI - Repair inoperative two-way Louisiana Tech University 13 S07858 16 Howard Auditorium communication 1.6 8.6.4.15 April 1, 2016 EI - Machine rooms shall be constructed of non-combustable Louisiana Tech University 13 S07858 16 Howard Auditorium material (wood box over controller) 2.9 2.7.1.2.1(a) April 1, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S07858 16 Howard Auditorium disconnect switch 2.10 2.29.1 April 1, 2016 EI - Provide a code data plate on the controller or mainline disconnect that indicates the code in effect at the time Louisiana Tech University 13 S07858 16 Howard Auditorium of installation or alteration 2.14 8.6.1.5.1 April 1, 2016 EI - Provide guards on main drive Louisiana Tech University 13 S07858 16 Howard Auditorium sheave 2.18 2.10.1 April 1, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07858 16 Howard Auditorium code section 8.6 2.41 8.6.1.4 April 1, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07858 16 Howard Auditorium with characters at least 3" high 4.13 2.29.1 April 1, 2016 EI - Due to the fact that the govenor is in the hoistway and there is no inspect, Louisiana Tech University 13 S07858 16 Howard Auditorium the safeties were not tested 5.8 April 1, 2016 EI - Provide 125 volt duplex receptical in equipment room and it shall be a Louisiana Tech University 13 S07865 56 Visual Arts Center ground fault circuit interrupter 2.33 nec 620.85 March 31, 2016 EI - Provide numerical identification on elevator controls and main line Louisiana Tech University 13 S07865 56 Visual Arts Center disconnect switch 2.10 2.29.1 March 31, 2016 EI - Provide a code data plate on the controller or mainline disconnect that indicates the code in effect at the time Louisiana Tech University 13 S07865 56 Visual Arts Center of installation or alteration 2.14 8.6.1.5.1 March 31, 2016 EI - Provide maintenance records that properly document compliance with Louisiana Tech University 13 S07865 56 Visual Arts Center code section 8.6 2.41 8.6.1.4 March 31, 2016 EI - Provide a firefighters service monthly test log on the premises that indicates the monthly fire service Louisiana Tech University 13 S07865 56 Visual Arts Center testing is accomplished. 2.40 8.6.11.1 March 31, 2016 EI - Provide proper 4" high floor numbering on hoistway side of Louisiana Tech University 13 S07865 56 Visual Arts Center hoistway doors. 3.9 2.29.2 March 31, 2016 EI - Provide elevator number on crosshead with characters at least 1 Louisiana Tech University 13 S07865 56 Visual Arts Center 1/2" high 3.9 2.29.1 March 31, 2016 EI - Provide elevator number adjacent to or on entrance at designated level Louisiana Tech University 13 S07865 56 Visual Arts Center with characters at least 3" high 3.9 2.29.1 March 31, 2016 EI - Provide sump cover flush with pit Louisiana Tech University 13 S07865 56 Visual Arts Center floor 5.1 2.2.2.6 March 31, 2016 EI - NEC620.85 Provide 125 volt duplex receptical in every pit and it shall be a Louisiana Tech University 13 S07865 56 Visual Arts Center ground fault circuit interrupter. 5.1 nec 620.85 March 31, 2016 EI - Phase I operation instructions Louisiana Tech University 13 S07865 56 Visual Arts Center required 4.14 2.27.7 March 31, 2016 FM - Smoke Alarms -- The smoke alarms in Rooms KA 102 and 203 are hanging from the ceiling. Have repaired/replaced by a Louisiana Louisiana Tech University 13 L03213 97 Kidd A Licensed Company 2000 LSC 29.3.5.1 June 15, 2016 FM - Extinguishing Requirements - The sprinkler heads in both upstairs bedrooms in Room KC 304 are hanging from the ceiling. Have repaired or replaced by a Louisiana Licensed Louisiana Tech University 13 L03194 96 Kidd C Company. 2000 LSC 29.3.5 June 15, 2016 FM - Remove forklift from the south Louisiana Tech University 13 S12296 78 Institute for Micromanfufacturing storage room LRS 40: 1575 September 18, 2015 FM - Marking of means of egress. Louisiana Tech University 13 S07881 158 Lambright Intramural Sports Center Provide exit signs in outside pool area NFPA 101:12.2.10 September 16, 2015 Locking, bolting, or obstructing exit or passages. No person shall bolt, lock, obstruct any exit or any passage, or permit any one else to do so. Exit from pool pump room is obstructed due to door locking behind you at top of stairs and gate being locked at bottom. Remove red barracades from exit doors of outise pool area. Correct by end of day today. Remove storage Louisiana Tech University 13 S07881 158 Lambright Intramural Sports Center from exit corridor by bowling alley RS 40:1575 September 16, 2015

Remvoe storage from mechanical/boiler rooms. Room across Louisiana Tech University 13 S07881 158 Lambright Intramural Sports Center from gym and room on track level. RS 40:1575 September 16, 2015 Repair/replace exit signs and Louisiana Tech University 13 S07881 158 Lambright Intramural Sports Center emergency lights throuout building. NFPA 101:4.6.12 September 16, 2015 FM - Have Fire Alarm serviced and Louisiana Tech University 13 S07881 158 Lambright Intramural Sports Center tagged by a licensed company. LAC - 55V1033 September 16, 2015 FM - Remove the gas powered equipment from the storage room, Louisiana Tech University 13 S15194 8890 Biomedical Engineering Building located by the animal research room LRS 40:1575 September 18, 2015 FM - Have the fire alarm serviced and Louisiana Tech University 13 S07868 58 Nethken Hall tgged by a licensed company. LAC - 55V1033 September 18, 2015 Rooms with equipment are unprotected; Headroom clearance at Louisiana State University A&M 22 S11700 SR22 Tiger Stadium Dorm West NFPA101: 1731 & 7.1.5.1 & 8-1711 8/21/15 vomitories; 2-hour separation of exit ramps. 2.1 2.7.3.4.1 – Provide self-closing machine room door; 2.1 2.7.3.4.1 – Provide self-locking (one way permanent lock) machine room Louisiana State University Eunice 23 S10572 0059 Eunice Library door; ASME A17.1 2007 A17.3 2008 1/26/16 2.3 Nec 620.85 Provide 125 volt duplex receptacle in equipment room and it shall be a ground fault circuit interrupter 2.7.3.1 - Provide a safe & convenient means of access to the machine room. Machine access is through the floor in above hallway; 2.7.3.4.1 – Provide self-locking (one way permanent lock) machine room door. Access is not lockable and can be accessed by anyone; 2.3 - Nec 620.85 Provide 125 volt duplex receptacle in equipment room Louisiana State University Eunice 23 S10579 0060 Eunice Science- Classroom ASME A17.1 2007 A17.3 2008 2/1/16 and it shall be a ground fault circuit interrupter; 3.12 2.8.2 (pipes, etc.) Remove prohibited equipment located in the hoist way. (indicate exact location & type or equipment) – ac duct; 3.13 2.1.6.2 Provide guarding of not less than 75 degrees on <>2, <>4 or more projections in hoist way. (4 2000 code) 2.1 2.7.3.4.1 – Provide self-closing machine room door; 2.1 2.7.3.4.1 – Provide self-locking (one- way permanent lock) machine room Louisiana State University Eunice 23 S10574 0063 Eunice Manuel Hall door; ASME A17.1 2007 A17.3 2008 1/26/16 Nec 620.85 – Provide 125 volt duplex receptacle in equipment room and it shall be a ground fault circuit interrupter. 2.11 NEC 110.26 (A)(1) From U-150 Classroom Community Education Louisiana State University Eunice 23 S28106 0111 volts shall maintain 3’ of clearance at ASME A17.1 2007 A17.3 2008 1/26/16 Building disconnect. 2.3 Nec 620.85 Provide 125 volt duplex receptacle in equipment room and it Louisiana State University Eunice 23 S12556 0097 Health Technology Building ASME A17.1 2007 A17.3 2008 2/1/16 shall be a ground fault circuit interrupter. 2.3 Nec 620.85 Provide 125 volt duplex receptacle in equipment room and it shall be a ground fault circuit interrupter; Louisiana State University Eunice 23 S10569 0064 Eunice Health & Physical Ed 2.8 NEC 620.4 All live parts of an ASME A17.1 2007 A17.3 2008 2/12/16 electrical apparatus in hoist ways, at landings, in or on cars, machine spaces shall be enclosed to prevent accidental contact. Shall Provide Service To Fire System Louisiana State University Health Science Center 25 S11010 0004 School of Allied Health Professions NFPA 72 9/4/15 Speaker Circuit On 1st Floor In Trouble Shall Provide Service To Fire Pump: Louisiana State University Health Science Center New Orleans 25 S00522 0173 Stanislaus Hall NFPA 20 9/4/15 Replace Packing Gland And Drain Pipe Shall Replace Missing Ceiling Tiles On Louisiana State University Health Science Center New Orleans 25 S00522 0173 Stanislaus Hall 1st floor Rear Exit For The Proper NFPA 101 9/4/15 Operation Of Sprinkler System Shall Replace 2nd Floor Light Bulbs In Louisiana State University Health Science Center New Orleans 25 S00522 0173 Stanislaus Hall NFPA 101 9/4/15 Stairwell #5 For Proper Lighting Continuing Education building (CEB, Shall Provide Ceiling Tiles To Be Louisiana State University Health Science Center New Orleans 25 S11003 0001 NFPA 101 9/4/15 1542) Installed On 7th Floor Corridor Provide Keys In Fire Command Room Properly Label For Stairwell Entry For Louisiana State University Health Science Center New Orleans 25 S10914 0061 Resource Center Fire Department In Emergency Cases. Note 9/11/15 Please Check All Locks To Doors For Proper Operation. Shall Provide Ceiling To Be Installed In Room 206 Or Relocate Sprinkler And Louisiana State University Health Science Center New Orleans 25 S10914 0061 Resource Center NFPA 101 9/11/15 Smoke Detector To Ceiling For Proper Operational. Shall Provide Service To Kitchen Hood Fire Suppression System, System Yellow Tagged For Improper Nozzles Protection Due To Adding New Grill By Louisiana State University Health Science Center New Orleans Fire Safety And Commodities. No Use Of Grill Til Properly Protected By Nozzle And Properly Shuts Down With Hood 25 S10958 0003 Medical Education Building Suppression System NFPA 17 9/11/15 Shall Provide 16 Inch Clearance From Open Flame And Deep Fryer Or Provide Louisiana State University Health Science Center New Orleans Shield Between Appliances Under 25 S10958 0003 Medical Education Building Kitchen Hood NFPA 17 9/11/15 Shall Provide Exit Lights To Be Louisiana State University Health Science Center New Orleans Operational Stairwell #3 By Room 5D28 25 S10958 0003 Medical Education Building And 3201 NFPA 101 9/11/15 Shall Provide Sprinkler Coverage 3rd Louisiana State University Health Science Center New Orleans Floor Admissions Office, No Sprinkler 25 S10958 0003 Medical Education Building Coverage In Corridors And Office Areas NFPA 13 9/11/15 Shall Remove Extension Cords In Room Louisiana State University Health Science Center New Orleans 25 S10958 0003 Medical Education Building 5219A NFPA 70 9/11/15 Shall Replace Or Repair Lights In 7th Louisiana State University Health Science Center New Orleans 25 S10923 0006 Lions Eye Foundation Floor Stairwell #2 For Proper Egress NFPA 101 9/11/15 8.5.5.3.1 Shall Provide Sprinkler Coverage Under Stairs Where Fixed Louisiana State University Health Science Center New Orleans Objections More than 4 Ft Wide. Provide Sprinkler Coverage Under 6 25 S11010 0004 School of Allied Health Professions Foot Wide Stairs On 1st Floor Entrance NFPA 13 9/14/215 Shall Provide Fire Extinguishers To Be Louisiana State University Health Science Center New Orleans Installed On All Floors Of Parking 25 S13118 0171 Gravier Parking Garage/Enwave Garage NFPA 10 9/25/15 Shall Provide Service To 1st Floor Kitchen Hood Fire Suppression System. At time Of Inspection Day Care Hood Louisiana State University Health Science Center New Orleans System Yellow Tagged By Fire Safety And Commodities For Range Not shutting Down With Fire Suppression 25 S28685 0242 Human Development Center System NFPA 96 9/25/15 Shall Provide Door Closures For Self- Louisiana State University Health Science Center New Orleans Closing To Be Installed Or Repaired On 25 S10551 0015 School of Dentistry Basement Stairwell Doors NFPA 101 10/2/15 Shall Provide Sprinkler To Be Proper Louisiana State University Health Science Center New Orleans Installed In Areas, All Sprinkler To Be 25 S10551 0015 School of Dentistry Lower Or Raised In Ceiling Tiles NFPA 13 10/2/15 Shall Be Installed Escutcheons On All Louisiana State University Health Science Center New Orleans 25 S10551 0015 School of Dentistry Sprinklers NFPA 13 10/2/15 Shall Provide Grease Drips In Kitchen Louisiana State University Health Science Center New Orleans 25 S10550 0016 School of Dentistry Fire Suppression System On 1st Floor NFPA 17 10/2/15 12.2.2.2.3 Shall Provide Fire Rated Panic Hardware To Be Installed On All 4th Floor Stairwell Doors (3) Leading Louisiana State University Health Science Center New Orleans From Assembly Occupancies And 3rd Floor Stairwell Door Leading From 25 S10550 0016 School of Dentistry Outside Library. NFPA 101 10/2/15 Shall Submit Drawings In 10 Working Days To State Fire Marshal Office For Existing Connecting Area Between Building. At Time Of Inspection Table And Chairs In Area And Change Of Occupancy To Area to Assembly. Due Louisiana State University Health Science Center New Orleans to Doors Not Swinging Out, No Panic Hardware And Dead End Corridor State Fire Marshal Office Limited Capacity To 49 On Floors 2nd, 3rd, And 4th Floors. All Table And Chairs To Removed Over 25 S10550 0016 School of Dentistry Capacity. NFPA 101 10/2/15 Shall Provide Door Closures To Be Louisiana State University Health Science Center New Orleans Installed On Stairwell Doors In 25 S10551 0015 School of Dentistry Basement Areas NFPA 101 10/2/15 Central Louisiana Technical Machine room lighting is inoperative - Central Louisiana Technical Community College R4 S06346 A000 Community College - Alexandria 2.3 Elevator Deficiences August 20, 2015 resolved per Safety Manager Louisiana campus Central Louisiana Technical Very loud pump noise in the up Central Louisiana Technical Community College R4 S07126 000A Community College - Leesville 1.19 Elevator Deficiencies September 3, 2015 direction Louisiana campus Central Louisiana Technical Provide ventilation in the machine Central Louisiana Technical Community College R4 S07126 000A Community College - Leesville 2.6 Elevator Deficiencies September 3, 2016 room Louisiana campus Central Louisiana Technical Provide a lockable disconnect for the Central Louisiana Technical Community College R4 S07126 000A Community College - Leesville 2.11 Elevator Deficiencies September 3, 2017 110 VAC Louisiana campus Central Louisiana Technical Provide a building ground to the Central Louisiana Technical Community College R4 S07126 000A Community College - Leesville 2.12 Elevator Deficiencies September 3, 2018 controller Louisiana campus Central Louisiana Technical Provide a code data plate for the Central Louisiana Technical Community College R4 S07126 000A Community College - Leesville 2.14 Elevator Deficiencies September 3, 2019 machine room Louisiana campus Central Louisiana Technical Central Louisiana Technical Community College R4 S07126 000A Community College - Leesville The relief valve is not sealed 2.31 Elevator Deficiencies September 3, 2020 Louisiana campus Central Louisiana Technical Provide a suitable guard for the car top Central Louisiana Technical Community College R4 S07126 000A Community College - Leesville 3.2 Elevator Deficiencies September 3, 2021 light fixture Louisiana campus Central Louisiana Technical Car top inspection/normal switch is Central Louisiana Technical Community College R4 S07126 000A Community College - Leesville 3.3 Elevator Deficiencies September 3, 2022 broken Louisiana campus 1st floor Annex has no audio when Delgado Community College 43 S00311 6705 Issac Delgado Hall Building 1 Life Safety 55:V:3043 May 24, 2016 alarm is active. (wiring) Yellow Tag The panel indicates a negative earth Delgado Community College 43 S00419 6705 Administration Classrooms ground. Ground traced to one branch Life Safety 55:V:3043 May 19, 2016 of Mapnet. Yellow Tag Photo detector M1-27 in corridor by Delgado Community College 43 S00334 6705 Seymour Weis Vocational room 318 has a bad LED and needs Life Safety 55:V:3043 May 25, 2016 replacement. Yellow Tag Phone lines goind to the panel need to be re routed properly or removed in Delgado Community College 43 S23041 6705 Giles Martin Hall order to properly maintain the integrity Life Safety 55:V:3043 May 26, 2016 of the panel. Panel door and face plate is removed..Yellow Tag Control panel is not reporting a battery Delgado Community College 43 S00314 6705 Library disconnect status with batteries Life Safety 55:V:3043 July 6, 2016 disconnected. Yellow Tag Network not connected. Trouble on Delgado Community College 43 S00315 6705 Classrooms Life Safety 55:V:3043 July 5, 2016 panel. Yellow Tag Pull station M2-8 in gym by Delgado Community College 43 S00317 6705 Administration Classrooms concessions needs replacement.Yellow Life Safety 55:V:3043 May 20, 2016 Tag Degraded style 7 on network. Yellow Delgado Community College 43 S00321 6705 Engineering Life Safety 55:V:3043 May 20, 2016 Tag Intermittent positive ground fault. Delgado Community College 43 S16109 6705 Student Life Center Life Safety 55:V:3043 May 20, 2016 Yellow Tag 1. Bad 6.2ah batteries in 2001 panel in room 111-1. (2081-9272) Delgado Community College 43 S00332 6705 Bagert Welding Lab Life Safety 55:V:3043 June 1, 2016 2. Bad 10ah batteries in 4010 panel in room 111-1. (2081-9274).Yellow Tag 2nd floor pull station needs Delgado Community College 43 S00331 6705 Haydel Auto Lab Life Safety 55:V:3043 June 1, 2016 replacement. (4099-9001).Yellow Tag 1. 1st floor main fire panel has bad 50ah batteries.2. 1st floor main fire Delgado Community College 43 N/A 6705 Nursing School Life Safety 55:V:3043 May 27, 2016 panel has an inactive Fire Watch 411 dialer. Yellow Tag 1. Node 1 panel does not report batteries missing. (programming) 2. Node 1 panel does not set the node 2 panel into alarm when in alarm. Delgado Community College 43 S13713 6705 LaRocca Hall Life Safety 55:V:3043 June 3, 2016 (programming) 3. Node 2 photo detector M1-6 needs label changed to "In Mech. Rm. 3-111". (programming) sprinkler system yellow tagged-bell L E Fletcher Technical Community College 77 S14083 355004/4 Allied Health Building NFPA 101 4.6.12 October 7, 2015 not functioning Outlet cover 1st classroom by Northshore Technical Community College R7 S03313 0LCA Hammond Area Campus RS40:1575 November 30, 2015 maintenance Northshore Technical Community College R7 S03313 0LCA Hammond Area Campus Remove hasp on 2nd floor car shop RS40:1583 November 30, 2015 Northshore Technical Community College R7 S03313 0LCA Hammond Area Campus Certifications for hot water heaters RS40:1575 November 30, 2015 Northshore Technical Community College R7 S03313 0LCA Hammond Area Campus Repairs to emergency lighting welding RS40:1575 November 30, 2015 Devalcourt Elevator- No car top South Louisiana Community College 46 428022 0002 South Louisiana Community College handrails, No door restrictors, relocate A17.1 2.10.2,8.6.4.13,2.2.51 July 19, 2016 pit light switches Northwestern State University 17 S08159 0053 St. Denis Hall Exterior stiar - no handrails 13-1221 11/30/15 Northwestern State University 17 S08132 0043 Fournet Hall Exterior stiar - no handrails 13-1221 11/30/15 Northwestern State University 17 S08201 0018 Harry "Rags Turpin Stadium Elevator - Multiple A17.1 - 2.27.1, 2.18, 5.1, 8/27/15 Northwestern State University 17 S08157 0054 Williamson Hall Elevator - Multiple A.17.1 - 2.29.2, 2.20.2, 12.27.3.2 8/28/15 Northwestern State University 17 S08145 0026 Wellness, Recreation, and Activities Center (WRAC)Elevator - Multiple A17.1 - 2.12.5, 2.29.2 8/27/15 University of New Orleans 27 S11547 10 Administration Building Provide 4" numbering on hoisted side of hoist way doors3.9-100.7 4/20/16 Provide platform guard not less than University of New Orleans 27 S11547 10 Administration Building 21" 4.1203.9 (b) 4/25/16 University of New Orleans 27 S11547 10 Administration Building No keys available to test 6.4 4/22/16 University of New Orleans 27 S11560 20 Biology Provide a stop switch inside of car either key operated or behind a locked door1.2-2.6.2.21 4/25/16 University of New Orleans 27 S11560 20 Biology Phase II operation instructions required 1.15-2.27.7 4/22/16 University of New Orleans 27 S11560 20 Biology Provide door restriction 1.18-2.12.5 4/25/16 University of New Orleans 27 S11560 20 Biology NE620.23)c) Provide a duplex, GFICI receptacle in the Machine space 2.3 4/25/16 University of New Orleans 27 S11560 20 Biology Provide an "ABC" type fire extinguisher in the machine room adjacent to the main access door2.7-8.6.1.6.5 4/25/16 University of New Orleans 27 S11560 20 Biology Provide numerical identification on elevator controls and main line disconnect switch2.10-2,29.1 4/25/16 University of New Orleans 27 S11560 20 Biology Provide a code data tag securely attached to the controller or main line disconnect2.14-8.9 4/25/16 University of New Orleans 27 S11560 20 Biology Provide a firefighters' service monthly test log n the premises that indicates the monthly fire service testing is accomplished2.41-8.6.11.1 4/25/16 University of New Orleans 27 S11560 20 Biology Provide care top light with guard and electrical outlet GFCI = 210.43.2-2.14.7.1.4 4/26/16 University of New Orleans 27 S11560 20 Biology Provide care top emergency exit switch 3.8-2.26.2.18 4/21/16 University of New Orleans 27 S11560 20 Biology Provide 4" numbering on hoistway side of hoistway doors, 1 1/2" numbering on crosshead, and 3" numbering adjacent to or on the entrance at designated level3.9-2.29 1&2 4/21/16 University of New Orleans 27 S11560 20 Biology Provide crosshead data tag with required information3.27-2.16.3.1 4/21/16 University of New Orleans 27 S11560 20 Biology Provide a toe guard with a minimum length of 21"4.1-2.15.9.2(b) 4/21/16 University of New Orleans 27 S11560 20 Biology Repair, replace or adjust the hoistway door closures where applicable to ensure proper and self closing operation4.2-8.6.4.13.1(k) 4/21/16 University of New Orleans 27 S11560 20 Biology Provide fireman service 6.4-2.27.3 4/21/16 University of New Orleans 27 S12533 49 Chemical Science #1 Provide alarm bell that will work with power outage1.6-211 4/22/16 University of New Orleans 27 S12533 49 Chemical Science #1 Phase II instructions required (worn and not ledgeable)6.4-211.7 4/22/16 University of New Orleans 27 S12533 49 Chemical Science #2 Provide alarm bell that operates during power outage1.6-211 6/23/16 University of New Orleans 27 S12533 49 Chemical Science #2 Provide maintenance to currently impaired fire alarm systemNFPA101-4.6.12.1 6/23/16 University of New Orleans 27 S12533 49 Chemical Science #2 Provide maintenance to currently impaired fire alarm system. System is yellow-tagged due to smoke detectorNFPA101-4.6.12.1 6/23/16 University of New Orleans 27 S12533 49 Chemical Science #2 Provide phase II operating instructions 6.4-211.7 6/23/16 University of New Orleans 27 S11565 22 Computer Center Provide fireman's service PHI and PHII 6.1-211.3 4/25/16 University of New Orleans 27 S11572 26 Education Provide numerical identification on elevator controls and main line disconnect switch2.10-2.29.1 2/1/16 University of New Orleans 27 S11572 26 Education Provide a firefighters' service monthly test log n the premises that indicates the monthly fire service testing is accomplished2.41-8.6.10.1 2/1/16 University of New Orleans 27 S11572 26 Education Provide elevator number on crosshead with characters at least 1 1/2" high3.9-2.29.1 2/1/16 University of New Orleans 27 S11572 26 Education Fire alarm was found to be yellow tagged for the elevator system not being tied in to recallnfpa 72 2/1/16 University of New Orleans 27 S11572 26 Education Door by third stairwell did not open and it was missing a door ___ shall have door repairednfpa101:7.2.1.15 2/1/16 University of New Orleans 27 S11572 26 Education Provide elevator number adjacent to or on entrance at designated level with characters t least 3" high6.4-2.27.3.1.6(h) 2/1/16 University of New Orleans 27 S11575 29 Engineering #1 Repair inoperative two-way communication1.6-211.1 4/25/16 University of New Orleans 27 S11575 29 Engineering #1 Phase II operation instructions required 1.15-211.7 4/25/16 University of New Orleans 27 S11575 29 Engineering #1 Provide capacity plate in car 1.16-207.3a 4/25/16 University of New Orleans 27 S11575 29 Engineering #1 Provide door restriction 1.18-111.5 4/25/16 University of New Orleans 27 S11575 29 Engineering #1 Provide an "ABC" type fire extinguisher in the machine room adjacent to the main access door2.7-1205.1h 4/25/16 University of New Orleans 27 S11575 29 Engineering #1 Provide car lighting disconnect in machine room, fused & lockable in the off position and labeled "Car Lighting"2.11-201.4/NEC 620.53 4/25/16 University of New Orleans 27 S11575 29 Engineering#2 Repair inoperative in car stop switch 1.2-210.2v 4/25/16 University of New Orleans 27 S11575 29 Engineering#2 Repair inoperative alarm 1.6-211.1 4/25/16 University of New Orleans 27 S11575 29 Engineering#2 Phase II operation instructions required 1.15-211.7 4/25/16 University of New Orleans 27 S11575 29 Engineering#2 Provide door restriction 1.18-111.5 4/25/16 University of New Orleans 27 S11575 29 Engineering#2 Provide an "ABC" type fire extinguisher in the machine room adjacent to the main access door2.7-1205.1h 4/25/16 University of New Orleans 27 S11575 29 Engineering#2 Provide car lighting disconnect in machine room, fused & lockable in the off position and labeled "Car Lighting"4/25/16 University of New Orleans 27 S11575 29 Engineering#5 Repair inoperative two-way communication1.6-211.1 4/25/16 University of New Orleans 27 S11575 29 Engineering#5 Phase II operation instructions required 1.15-211.7 4/25/16 University of New Orleans 27 S11575 29 Engineering#5 Provide door restriction 1.18-111.5 4/25/16 University of New Orleans 27 S11575 29 Engineering#5 Provide an "ABC" type fire extinguisher in the machine room adjacent to the main access door2.7-1205.1h 4/25/16 University of New Orleans 27 S11575 29 Engineering#5 Provide car lighting disconnect in machine room, fused & lockable in the off position and labeled "Car Lighting"2.11-201.4/NEC 620.53 4/25/16 University of New Orleans 27 S11575 29 Engineering#5 Provide guards on main drive sheave 2.18-104.1 4/25/16 University of New Orleans 27 S11575 29 Engineering#5 Provide a firefighters' service monthly test log n the premises that indicates the monthly fire service testing is accomplished2.40-1206.7 4/25/16 University of New Orleans 27 S11575 29 Engineering#5 Provide maintenance & upkeep of car top3.4-1206.2 4/25/16 University of New Orleans 27 S11575 29 Engineering#5 Provide elevator number on crosshead with characters at least 1 1/2" high3.9-211.9 4/25/16 University of New Orleans 27 S11575 29 Engineering#5 Provide crosshead data tag with required information (be specific3.27-207.3 4/25/16 University of New Orleans 27 S11575 29 Engineering#5 Provide maintenance & upkeep of pit by removing rust on pit equipment5.1-1206.2a 4/25/16 University of New Orleans 27 S11582 31 Geology & Psychology Repair alarm bell that is inoperative during power failure1.6-211.1c 4/25/16 University of New Orleans 27 S11582 31 Homer Hitt Visitors Center Set the pressure relief valve to open at a pressure not greater than 125% of the working pressure2.31-3.19.4.2(1)c 4/25/16 University of New Orleans 27 S11582 31 Homer Hitt Visitors Center Provide a firefighters' service monthly test log n the premises that indicates the monthly fire service testing is accomplished2.41-8.6.10.1 4/25/16 University of New Orleans 27 S11582 31 Homer Hitt Visitors Center Provide elevator number on crosshead with characters at least 1 1/2" high3.9-2.29.1 4/25/16 University of New Orleans 27 S11582 31 Homer Hitt Visitors Center Provide elevator number adjacent to or on entrance at designated level with characters t least 3" high3.9-2.29.1 4/25/16 University of New Orleans 27 S11584 33 Repair inoperative 2-way communication1.6-211.1a(2) 4/20/16 University of New Orleans 27 S11584 33 Human Performance Center Provide maintenance and annual inspection for facp. System is impaired due to a faulty elevator recallLARS 40:1646 12/10/15 University of New Orleans 27 S11584 33 Human Performance Center Provide 4" numbers on hoistway side of doors3.9-100.7 4/20/16 University of New Orleans 27 S11584 33 Human Performance Center Connect fire alarm to elevator controller6.4-211.3b 4/20/16 University of New Orleans 27 S13814 55 Kirschman Hall #1 Provide an "ABC type fire extinguisher in the machine room adjacent to the main access door2.7-8.6.1.6..5 4/21/16 University of New Orleans 27 S13814 55 Kirschman Hall #1 Provide a firefighters' service monthly test log on the premises that indicates the monthly fire service testing is accomplished2.4-8.6.10.1 4/21/16 University of New Orleans 27 S13814 55 Kirschman Hall #1 Provide elevator number on crosshead with characters at least 1 1/2" high3.9-2.29.1 4/21/16 University of New Orleans 27 S13814 55 Kirschman Hall #1 Repair inoperative pit lighting 5.1-2.2.5 4/21/16 University of New Orleans 27 S13814 55 Kirschman Hall #1 Fire alarm initiating devices in lobbies, machine rooms & Phase I switch6.4-2.27.3.2 4/21/16 University of New Orleans 27 S13814 55 Kirschman Hall #1 There were no keys available to test 6.4 4/21/16 University of New Orleans 27 S13814 55 Kirschman Hall #2 Provide an "ABC type fire extinguisher in the machine room adjacent to the main access door2.7-8.6.1.6..5 4/21/16 University of New Orleans 27 S13814 55 Kirschman Hall #2 Provide a firefighters' service monthly test log on the premises that indicates the monthly fire service testing is accomplished2.4-8.6.10.1 4/21/16 University of New Orleans 27 S13814 55 Kirschman Hall #2 Provide elevator number on crosshead with characters at least 1 1/2" high3.9-2.29.1 4/21/16 University of New Orleans 27 S13814 55 Kirschman Hall #2 Repair inoperative pit lighting 5.1-2.2.5 4/21/16 University of New Orleans 27 S13814 55 Kirschman Hall #2 Fire alarm initiating devices in lobbies, machine rooms & Phase I switch6.4-2.27.3.2 4/21/16 University of New Orleans 27 S13814 55 Kirschman Hall #2 There were no keys available to test 6.4 4/21/16 University of New Orleans 27 S11557 4 #1 Provide door restriction 1.18-2.12.5 4/26/16 University of New Orleans 27 S11557 4 Lakefront Arena #1 Provide numerical identification on elevator controls and main line disconnect switch2.10-2.29.1 4/26/16 University of New Orleans 27 S11557 4 Lakefront Arena #1 Provide a code data tag securely attached to the controller or main line disconnect2.14-8.9 4/26/16 University of New Orleans 27 S11557 4 Lakefront Arena #1 Provide 4" numbering on hoistway side of hoistway doors, 1 1/2" numbering on crosshead, and 3" numbering adjacent to or on the entrance at designated level3.9-2.29.1&2 4/26/16 University of New Orleans 27 S11557 4 Lakefront Arena #1 Provide proper platform guard a minimum of 21"4.1-2.15.9.2(b) 4/26/16 University of New Orleans 27 S11557 4 Lakefront Arena Lobby Provide capacity plate in car 1.16-207.3 4/26/16 University of New Orleans 27 S11557 4 Lakefront Arena Lobby Mechanic did not have proper equipment to properly test relief pressure2.31 4/26/16 University of New Orleans 27 S11586 34 Liberal Arts Provide a disconnect for the car lighting that is fusible and lockable in the off position1.5-2.26.4 4/21/16 University of New Orleans 27 S11586 34 Liberal Arts Provide door restriction 1.18-2.12.5 4/21/16 University of New Orleans 27 S11586 34 Liberal Arts Provide self locking (one way permanent lock) machine room door2.4-2.7.3.4.1 4/21/16 University of New Orleans 27 S11586 34 Liberal Arts Remove prohibited equipment form machine room. 2.4-2.7.2.1.8.6.4.8 4/21/16 University of New Orleans 27 S11586 34 Liberal Arts Provide numerical identification on elevator controls and main line disconnect switch2.10-2.29.1 4/21/16 University of New Orleans 27 S11586 34 Liberal Arts Provide a disconnect for the car lighting that is fusible and lockable in the off position2.11-2.26.4 4/21/16 University of New Orleans 27 S11586 34 Liberal Arts Provide a fire fighters' service monthly test log on the premises that indicated the monthly fire services testing is accomplished2.41-8.6.10.1 4/21/16 University of New Orleans 27 S11586 34 Liberal Arts Provide elevator number on crosshead with characters at least 1 1/2" high3.9-2.29.1 4/21/16 University of New Orleans 27 S11586 34 Liberal Arts Provide elevator number adjacent to or on entrance at designated level with characters t least 3" high3.9-2.29.1 4/21/16 University of New Orleans 27 S11586 34 Liberal Arts Provide crosshead date plate with required information3.27-2.16.3.1 4/21/16 University of New Orleans 27 S11586 34 Liberal Arts Platform guard shall not be less that 21"3.27-2.15.9.2(b) 4/21/16 University of New Orleans 27 S11586 34 Liberal Arts There were no keys available to test 6.4 4/21/16 University of New Orleans 27 S11587 35 Library #2 Provide hoist rope date tag 3.27-212.2b 4/22/16 University of New Orleans 27 S11587 35 Library #2 Provide maintenance and annual inspection of fire alarm system by a licensed La. Fire alarm contractor. System is impaired due to a faulty horn/strobe on 4th floor, smoke detector on 2nd floor and 4th floor duct detectorLARS 40:1646 12/10/15 University of New Orleans 27 S11587 35 Library #2 System is impaired due to a faulty horn/strobe on 4th floor, smoke detector on 2nd floor and 4th floor duct detectorLARS 40:1646 1/28/16 University of New Orleans 27 S11587 35 Library #2 System is impaired due to a faulty horn/strobe on 4th floor, smoke detector on 2nd floor and 4th floor duct detectorLARS 40:1646 1/28/16 University of New Orleans 27 S11587 35 Library #2 Provide maintenance and annual inspection for fire alarm systemLARS 40:1646 4/13/16 University of New Orleans 27 S11587 35 Library #3 Provide hoist rope date tag 3.27-212.2b 4/22/16 University of New Orleans 27 S11591 38 Math No keys available to test 6.1-2113a6 4/21/16 University of New Orleans 27 S11563 21 Milneburg Hall Provide door restriction 1.18-2.12.5 4/20/16 University of New Orleans 27 S11563 21 Milneburg Hall Provide 125 volt duplex receptacle in equipment room and it shall be a GFCI2.3-NEC 620.85 4/20/16 University of New Orleans 27 S11563 21 Milneburg Hall Provide elevator on each mainline disconnect2.10-2.26.4-N115 4/20/16 University of New Orleans 27 S11563 21 Milneburg Hall Provide a firefighters' service monthly test log on the premises that indicates the monthly fire service testing is accomplished2.42-8.6.10.1 4/20/16 University of New Orleans 27 S11563 21 Milneburg Hall Provide proper 4" high floor numbering on hoistway side of hoistway doors3.9-2.29.2 4/20/16 University of New Orleans 27 S11563 21 Milneburg Hall Provide elevator number on crosshead with characters at least 1 1/2" high3.9-2.29.1 4/20/16 University of New Orleans 27 S11563 21 Milneburg Hall Provide elevator number adjacent to or on entrance at designated level with characters t least 3" high.9-2.29.1 4/20/16 University of New Orleans 27 S11563 21 Milneburg Hall Repair or adjust hoistway access provisions to prevent unlocking with a common tool4.4-2.12.6.2.2 4/20/16 University of New Orleans 27 S11563 21 Milneburg Hall Provide pit light switch accessible from access door5.1-2.2.5.3 4/20/16 University of New Orleans 27 S11563 21 Milneburg Hall Configuration: "off-hold-on, key removed from any position (switch worked intermittently)6.4-2.27.3.3 4/20/16 University of New Orleans 27 S11563 21 Milneburg Hall Provide a disconnect for the car lighting that is fusible and lockable in the off position2.11-2.26.4 4/20/16 University of New Orleans 27 S11596 39 Performing Arts Provide in car emergency lighting 1.5-204.7a3 4/26/16 University of New Orleans 27 S11596 39 Performing Arts Provide self closing equipment space door2.1-1013d2 4/26/16 University of New Orleans 27 S13338 51 Recreation & Fitness Center Provide door restriction 1.18-2.12.5 4/21/16 University of New Orleans 27 S13338 51 Recreation & Fitness Center Provide numerical identification on elevator controls and main line disconnect switch2.10-2.29.1 4/21/16 University of New Orleans 27 S13338 51 Recreation & Fitness Center Provide a firefighters' service monthly test log on the premises that indicates the monthly fire service testing is accomplished2.41-8.6.10.1 4/21/16 University of New Orleans 27 S13338 51 Recreation & Fitness Center Provide elevator number on crosshead with characters at least 1 1/2" high3.9-2.29.1 4/21/16 University of New Orleans 27 S13338 51 Recreation & Fitness Center Provide elevator number adjacent to or on entrance at designated level with characters t least 3" high3.9-2.29.1 4/21/16 University of New Orleans 27 S13338 51 Recreation & Fitness Center There were no keys available to test 6.4 4/21/16 University of New Orleans 27 S12332 48 TRAC #1 Provide contacts in main line disconnect for proper operation of auxiliary lowering2.11-306.6 4/26/16 University of New Orleans 27 S12332 48 TRAC #1 System is impaired due to sound bases failing inspection in 3rd floor dorm rooms, faulty duct detector on 1st floor and needing to replace facp batteriesLARS 40:1646 1/28/16 University of New Orleans 27 S12332 48 TRAC #1 Provide current wiring diagrams 2.12-8.6.1.6.3 4/26/16 University of New Orleans 27 S12332 48 TRAC #1 Provide code data on controller or main line disconnect2.14-8.9.1 4/26/16 University of New Orleans 27 S12332 48 TRAC #1 Security systems, floors locked out, switched or otherwise, means which prevent the operation of in car PB's shall be rendered inoperative (A17.1 2007)6.4-8.27.3.3.1(i) 4/26/16 University of New Orleans 27 S12332 48 TRAC #2 Provide contacts in main line disconnect for proper operation of auxiliary lowering2.11-306.6 4/26/16 University of New Orleans 27 S12332 48 TRAC #2 Provide current wiring diagrams 2.12-8.6.1.6.3 University of New Orleans 27 S12332 48 TRAC #2 System is impaired due to sound bases failing inspection, faulty duck detector on 1st floor and needing to replace facp batteriesLARS 40:1646 1/13/16 University of New Orleans 27 S12332 48 TRAC #2 Provide code data on controller or main line disconnect2.14-8.9.1 University of New Orleans 27 S12332 48 TRAC #2 Security systems, floors locked out, switched or otherwise, means which prevent the operation of in car PB's shall be rendered inoperative (A17.1 2007)6.4-8.27.3.3.1(i) University of New Orleans 27 S11603 43 Science Annex Provide maintenance to currently impaired fire alarm systemNFPA101-4.6.12.1 6/23/16 University of New Orleans 27 S11603 43 Science Annex Provide maintenance to currently imparted fire alarm systemNFPA101-4.6.12.1 6/23/16 University of New Orleans 27 S11584 33 Human Performance Center University of New Orleans 27 S11584 33 Human Performance Center System is impaired due to not having a elevator recallLARS 40:1646 6/23/16 University of New Orleans 27 S11584 33 Human Performance Center Provide maintenance and annual inspection for fire alarm systemLARS 40:1646 4/13/16 University of New Orleans 27 S11605 73 Privateer Park Provide maintenance and exit emergency lighting in tennis building, umpire's dressing room and in men's restroom at baseball stadiumNFPA101-4.6.12.1 3/17/16 University of New Orleans 27 S11575 29 Engineering Building 13 Provide plan of action to this office to repair impaired fire alarm systemNFPA101-4.6.12.1 4/16/16 University of New Orleans 27 S11733 47 International Student Center Over due yellow tag NFPA101-4.6.12.1 4/13/16 Each automatic sprinkler system required by another section of this 7-7.1.1 code shall be installled in accordance Southern University Baton Rouge 31 S12846 TBD SU A O Williams Hall with NFPA 13. (5yr. Test required.) March 16, 2016 Southern University Baton Rouge 31 S12846 TBD SU A O Williams Hall Deficient Elevator 1.5 Car lighting insufficient (E) July 14, 2015 1.18 No door restriction on car Southern University Baton Rouge 31 S12846 TBD SU A O Williams Hall Deficient Elevator doors (E) July 14, 2015 5.1 Excessive accumalation of all water in pit. Almost to top of jack head (E) (bad building design, elevator hoistway has vents exposed to outside Southern University Baton Rouge 31 S12846 TBD SU A O Williams Hall Deficient Elevator nature/weather/rain) July 14, 2015 5.11 Plunger leaking oil out of packing and trailing down cylinder Southern University Baton Rouge 31 S12846 TBD SU A O Williams Hall Deficient Elevator (E) July 14, 2015 Southern University Baton Rouge 31 S02150 TBD SU Arch. East Elect. outlet plate missing in room 131 NFPA 70 April 17, 2016 4.5 Access to hoistway switch inop. Southern University Baton Rouge 31 S02150 TBD SU Arch. East Deficient Elevator (E) July 14, 2015 Southern University Baton Rouge 31 S02150 TBD SU Arch. East Deficient Elevator 5.1 No cover over sump hole (O) July 14, 2015 Bad fire alarm wire from the boiler rm. LAC 55:V 3037 Southern University Baton Rouge 31 S02143 TBD SU Debose Hall to music building. 3/16/16 Shall provide service to fire alarm LAC 55:V 3037 Southern University Baton Rouge 31 S02255 TBD SU Dunn Hall system. 3/16/16 Southern University Baton Rouge 31 S02255 TBD SU Dunn Hall Deficient Elevator Elev. OUT OF ORDER 7/14/15 Shall provide maint. to standpipe LAC Southern University Baton Rouge 31 S02178 TBD SU F G Clark Act. Ctr system. 2/19/16 1.18 No door restriction between Southern University Baton Rouge 31 S02178 TBD SU F G Clark Act. Ctr Deficient Elevator longer floors (E) 7/14/15 3.17 Car run with doors opened Southern University Baton Rouge 31 S02178 TBD SU F G Clark Act. Ctr Deficient Elevator more than 2 inches (E) 7/14/15 Fixed systems incldg. Pre-engineered shall be installed, serviced and LAC 55:V 3037 Southern University Baton Rouge 31 S02142 TBD SU J W Fisher Hall maintained. 5/10/16 Southern University Baton Rouge 31 S02142 TBD SU J W Fisher Hall Deficient Elevator 1.5 Emerg. Lighting in car inop. (E) 7/14/15 2.5 Debris in machine space needs Southern University Baton Rouge 31 S02142 TBD SU J W Fisher Hall Deficient Elevator to cleaned (E) 7/14/15 2.14 No code data plate controller Southern University Baton Rouge 31 S02142 TBD SU J W Fisher Hall Deficient Elevator or mainline disconnected (E) 7/14/15 Fixed systems incldg. Pre-engineered shall be installed, serviced and LAC 55:V 3037 Southern University Baton Rouge 31 S02165 TBD SU Frank Hayden maintained. 5/10/16 Fire alarm system red tagged for wiring LAC Southern University Baton Rouge 31 S02151 TBD SU Lab High School problems and ground faults. 2/25/16 Shall provide service to fire alarm LAC 55:V 3037 Southern University Baton Rouge 31 S02132 TBD SU A W Mumford Stadium system. 3/16/16 (Sprnk.) Fixed systems incldg. Pre- engineered shall be installed, serviced LAC 55:V 3037 Southern University Baton Rouge 31 S02132 TBD SU A W Mumford Stadium FH and maintained. 5/10/16 Sprinkler system red tagged due to no LAC 55:V 3037 Southern University Baton Rouge 31 S02151 TBD SU Lab School water to valves. 5/17/16 Sprinkler sys. Currently has multiple LAC 55:V 3037 Southern University Baton Rouge 31 S02163 TBD SU T H Harris Hall issues. 5/23/16 Southern University Baton Rouge 31 S02163 TBD SU T H Harris Hall Deficient Elevator 1.6 Emerg. Phone is inop. (E) 7/14/15 Southern University Baton Rouge 31 S02163 TBD SU T H Harris Hall Deficient Elevator 1.18 No restriction on car doors (E_ 7/14/15 2.14 No code data on plate controller or mainline disconnect Southern University Baton Rouge 31 S02163 TBD SU T H Harris Hall Deficient Elevator (E) 7/14/15 6.4 Unable to do Fire Service test Southern University Baton Rouge 31 S02163 TBD SU T H Harris Hall Deficient Elevator no keys on-site (E) 7/14/15 Southern University Baton Rouge 31 S12942 TBD SU P B S Pinchback Hall Shall prov. Service to sprinkler system LAC 55:V 3037 5/23/16 Southern University Baton Rouge 31 S12942 TBD SU P B S Pinchback Hall Deficient Elevator 1.5 Emerg. Lighting in car inop. (E) 7/14/15 Southern University Baton Rouge 31 S12942 TBD SU P B S Pinchback Hall Deficient Elevator 1.6 Alarm bell inop. (E) 7/14/15 Southern University Baton Rouge 31 S12942 TBD SU P B S Pinchback Hall Deficient Elevator 3.2 No switch for top of car light (E) 7/14/15 3.13 Air cond. Ducts dripping Southern University Baton Rouge 31 S12942 TBD SU P B S Pinchback Hall Deficient Elevator condensation water on car top (O) 7/14/15 Southern University Baton Rouge 31 S12824 TBD SU Camille Shade Dorm Shall prov. Service to sprinkler system LAC 55:V 3037 5/23/16 Southern University Baton Rouge 31 S12824 TBD SU Camille Shade Dorm Deficient Elevator 1.16 No rated load plate in car (E) 7/14/15 2.14 No code data plate on controller or mainline disconnect Southern University Baton Rouge 31 S12824 TBD SU Camille Shade Dorm Deficient Elevator (E) 7/14/15 Southern University Baton Rouge 31 S12704 TBD SU Totty Hall Shall prov. Service to sprinkler system LAC 55:V 3037 5/23/16 Southern University Baton Rouge 31 S12704 TBD SU Totty Hall Deficient Elevator 1.5 Emerg. Lights inop. (E) 7/14/15 Southern University Baton Rouge 31 S12704 TBD SU Totty Hall Deficient Elevator 1.6 Alarm bell inop. (E) 7/14/15 2.4 Machine room being used as a Southern University Baton Rouge 31 S12704 TBD SU Totty Hall Deficient Elevator storage area (O) 7/14/15 Southern University Baton Rouge 31 S02237 TBD SU Bethune Hall Monitoring to FACP inoperative. NFPA 101 28.3.4.3.6 8/21/15 (7) Hearing imparied rooms, stobes not NFPA 101 28.3.4.3.3 Southern University Baton Rouge 31 S02237 TBD SU Bethune Hall provided. 8/21/15 Inoperable exit signs & hazardous LRS 40:1575 Southern University Baton Rouge 31 S02237 TBD SU Bethune Hall elect. throughout. 8/21/15 Southern University Baton Rouge 31 S02237 TBD SU Bethune Hall No emergency lights. LRS 40:1575 8/14/15 Southern University Baton Rouge 31 S13084 TBD SU MA Edmond Show Arena Shall prov. Service to sprinkler system NFPA 101 2/25/16 Southern University Baton Rouge 31 S02203 TBD SU J B Cade Library FACP Inoperative. LAC 55:V 3037 3/16/16 Southern University Baton Rouge 31 S02203 TBD SU J B Cade Library Shall prov. Service to sprinkler system LAC 55:V 3037 3/16/16 (Sprnk.) Fixed systems incldg. Pre- engineered shall be installed, serviced LAC 55:V 3037 Southern University Baton Rouge 31 S02178 TBD SU F G Clark Act. Ctr and maintained. 5/10/16 Shall provide service to fire alarm LAC 55:V 3037 Southern University Baton Rouge 31 S02240 TBD SU Smith Brown Union system. 3/16/16 Southern University Baton Rouge 31 S02240 TBD SU Smith Brown Union Deficient Elevator 1.1 Door reopening device inop. (E) 7/14/15 1.18 Door restriction on car inop. Southern University Baton Rouge 31 S02240 TBD SU Smith Brown Union Deficient Elevator (E) 7/14/15 Southern University Baton Rouge 31 S02240 TBD SU Smith Brown Union Deficient Elevator 2.8 Telephone wire run in duct (E) 7/14/15 2.14 No code data plate on controller or mainline disconnect Southern University Baton Rouge 31 S02240 TBD SU Smith Brown Union Deficient Elevator (E) 7/14/15 Southern University Baton Rouge 31 S02240 TBD SU Smith Brown Union Deficient Elevator 3.9 No floor and emerg. i.d. no. (E) 7/14/15 5.1 Excessive accumalation of all Southern University Baton Rouge 31 S02240 TBD SU Smith Brown Union Deficient Elevator water in pit (E) 7/14/15 Southern University Baton Rouge 31 S11785 TBD SU A C Blanks Hall Deficient Elevator 1.5 Emerg. Lighting inoperable (E) 7/14/15 1.18 No door restriction on longer Southern University Baton Rouge 31 S11785 TBD SU A C Blanks Hall Deficient Elevator floors (E) 7/14/15 2.14 No code data on plate controller or mainline disconnect Southern University Baton Rouge 31 S11785 TBD SU A C Blanks Hall Deficient Elevator (E) 7/14/15 2.5 Accumalation of dirt in machine Southern University Baton Rouge 31 S11785 TBD SU A C Blanks Hall Deficient Elevator room (E) 7/14/15 Southern University Baton Rouge 31 S16011 TBD A W M Stadium Fieldhouse Deficient Elevator 1.18 No door restriction (E) 7/14/15 2.5 Oil on the machine rm. Floor Southern University Baton Rouge 31 S16011 TBD A W M Stadium Fieldhouse Deficient Elevator around tank (E) 7/14/15 5.11 Excessive hydro oil in catch Southern University Baton Rouge 31 S16011 TBD A W M Stadium Fieldhouse Deficient Elevator basins in pit (E) 7/14/15 1.4 Missing tile on floor by door opening and a partial opening in Southern University Baton Rouge 31 S16011 TBD A W M Stadium Fieldhouse Deficient Elevator cab floor (trip hazard) (O) 7/14/15 Southern University Baton Rouge 31 S02132 TBD A W M Stadium Pressbox Deficient Elevator 1.6 Emerg. Phone is inop. (E) 7/14/15 2.14 No code data plate on controller or mainline disconnect Southern University Baton Rouge 31 S02132 TBD A W M Stadium Pressbox Deficient Elevator (E) 7/14/15 Southern University Baton Rouge 31 S02132 TBD A W M Stadium Pressbox Deficient Elevator 3.2 Top of car light inoperable (E) 7/14/15 3.22 Missing cotter key in hoist Southern University Baton Rouge 31 S02132 TBD A W M Stadium Pressbox Deficient Elevator rope shackle (E) 7/14/15 Southern University Baton Rouge 31 S02256 TBD SU Boley Hall Deficient Elevator 1.18 No door restriction (E) 7/14/15 2.14 No code data plate on controller or mainline disconnect Southern University Baton Rouge 31 S02256 TBD SU Boley Hall Deficient Elevator (E) 7/14/15 Southern University Baton Rouge 31 S02256 TBD SU Boley Hall Deficient Elevator 3.2 Car top light switch is inop. (E) 7/14/15 Southern University Baton Rouge 31 S02256 TBD SU Boley Hall Deficient Elevator 3.9 No floor and emerg. i.d. no. (E) 7/14/15 3.22 No anti-rotation device on Southern University Baton Rouge 31 S02256 TBD SU Boley Hall Deficient Elevator counterweight shackles (E) 7/14/15 Southern University Baton Rouge 31 S02256 TBD SU Boley Hall Deficient Elevator 4.13 No Emerg. I.d. No. (O) 7/14/15 Southern University Baton Rouge 31 S02224 TBD SU J K Haynes Hall Deficient Elevator 1.5 Insuff. Emerg. Lighting in car (E) 7/14/15 1.18 No door restriction on car Southern University Baton Rouge 31 S02224 TBD SU J K Haynes Hall Deficient Elevator doors (E) 7/14/15 2.14 No code data plate on controller or mainline disconnect Southern University Baton Rouge 31 S02224 TBD SU J K Haynes Hall Deficient Elevator (E) 7/14/15 Southern University Baton Rouge 31 S02224 TBD SU J K Haynes Hall Deficient Elevator 3.9 No floor and emerg. i.d. no. (E) 7/14/15 5.1 Pit has debris from jack Southern University Baton Rouge 31 S02224 TBD SU J K Haynes Hall Deficient Elevator replacement from car 1 pit (E) 7/14/15 Southern University Baton Rouge 31 S02248 TBD SU J S Jones Hall Deficient Elevator 1.5 Insuff. Emerg. Lighting in car (E) 7/14/15 2.14 No code data plate on controller or mainline disconnect Southern University Baton Rouge 31 S02248 TBD SU J S Jones Hall Deficient Elevator (E) 7/14/15 Southern University Baton Rouge 31 S02248 TBD SU J S Jones Hall Deficient Elevator 3.2 Top of car light inoperable (E) 7/14/15 5.1 Excssv. accumalation of all water in pit. Almost to top of jack Southern University Baton Rouge 31 S02248 TBD SU J S Jones Hall Deficient Elevator head (E) 7/14/15 5.11 Oil coming from packing Southern University Baton Rouge 31 S02248 TBD SU J S Jones Hall Deficient Elevator around piston (E) 7/14/15 6.4 No audible signal on fire service Southern University Baton Rouge 31 S02248 TBD SU J S Jones Hall Deficient Elevator (E) 7/14/15 2.3 Insufficient lighting in machine Southern University Baton Rouge 31 S02171 TBD SU J B Moore Hall Deficient Elevator rm (O) 7/14/15 2.7 No fire extinguisher in machine Southern University Baton Rouge 31 S02171 TBD SU J B Moore Hall Deficient Elevator rm (O) 7/14/15 2.14 No code data on plate controller or mainline disconnect Southern University Baton Rouge 31 S02171 TBD SU J B Moore Hall Deficient Elevator (E) 7/14/15 2.15 Acculation of oil and debris Southern University Baton Rouge 31 S02171 TBD SU J B Moore Hall Deficient Elevator under hydraulic pump unit (E) 7/14/15 2.34 Flexible hydraulic hose out of Southern University Baton Rouge 31 S02171 TBD SU J B Moore Hall Deficient Elevator date (E) 7/14/15 5.1 Excssv. accumalation of all Southern University Baton Rouge 31 S02171 TBD SU J B Moore Hall Deficient Elevator water in pit (E) 7/14/15 Southern University Baton Rouge 31 S02171 TBD SU J B Moore Hall Deficient Elevator 1.6 Emerg. Phone is inop. (E) 7/14/15 2.14 No code data on plate controller or mainline disconnect Southern University Baton Rouge 34 S02135 TBD SU Lenoir Law Center Deficient Elevator (E) 7/14/15 Southern University Baton Rouge 34 S02135 TBD SU Lenoir Law Center Deficient Elevator 3.9 No floor and emerg. i.d. no. (E) 7/14/15 Southern University Baton Rouge 34 S02135 TBD SU Lenoir Law Center Deficient Elevator 4.13 No Emerg. I.d. No. (O) 7/14/15 Southern University Baton Rouge 34 S02135 TBD SU Lenoir Law Center Deficient Elevator 5.1 No cover over sump hole (O) 7/14/15 Southern University Baton Rouge 31 S02213 TBD SU Health and Research Deficient Elevator 1.5 No guard on lights in car (O) 7/14/15 Southern University Baton Rouge 31 S02213 TBD SU Health and Research Deficient Elevator 1.18 No door restriction (E) 7/14/15 2.14 No code data plate on controller or mainline disconnect Southern University Baton Rouge 31 S02213 TBD SU Health and Research Deficient Elevator (E) 7/14/15 Southern University Baton Rouge 31 S02213 TBD SU Health and Research Deficient Elevator 2.32 Oil leak from control valve (E) 7/14/15 3.17 Car run with doors opened Southern University Baton Rouge 31 S02213 TBD SU Health and Research Deficient Elevator more than 2 inches (E) 7/14/15 2.14 No code data plate on controller or mainline disconnect Southern University Baton Rouge 31 S02147 TBD SU Pinkie Thrift Hall Deficient Elevator (E) 7/14/15 5.1 Excessive accumalation of all Southern University Baton Rouge 31 S02147 TBD SU Pinkie Thrift Hall Deficient Elevator water in pit (E) 7/14/15 Southern University Baton Rouge 31 S02141 TBD SU Seymour Gym Deficient Elevator Elev. OUT OF ORDER 7/14/15 Southern University Baton Rouge 31 S12078 TBD SU Higgins Hall Deficient Elevator 1.18 No door restriction (E) 7/14/15 Southern University Baton Rouge 31 S12078 TBD SU Higgins Hall Deficient Elevator 2.3 Lights in machine rm inop. (O) 7/14/15 Southern University Baton Rouge 31 S12078 TBD SU Higgins Hall Deficient Elevator 3.2 Car top light switch is inop. (E) 7/14/15 Southern University Baton Rouge 31 S12078 TBD SU Higgins Hall Deficient Elevator 3.9 No floor and emerg. i.d. no. (E) 7/14/15 6.4 FIRE RECALL key switch in lobby Southern University Baton Rouge 31 S12078 TBD SU Higgins Hall Deficient Elevator inop. (E) 7/14/15 2.14 No code data plate on controller or mainline disconnect Southern University Baton Rouge 31 S12078 TBD SU Higgins Hall Deficient Elevator (E) 7/14/15 1.18 No door restriction on car Southern University Baton Rouge 31 S02167 TBD SU T T Allain Hall Deficient Elevator doors (E) 7/14/15 2.4 Ladders are being stored in Southern University Baton Rouge 31 S02167 TBD SU T T Allain Hall Deficient Elevator machine rm. (O) 7/14/15 2.5 Oil on the machine rm. Floor Southern University Baton Rouge 31 S02167 TBD SU T T Allain Hall Deficient Elevator around tank (E) 7/14/15 Southern University Baton Rouge 31 S02167 TBD SU T T Allain Hall Deficient Elevator 3.9 No floor and emerg. i.d. no. (E) 7/14/15 5.1 Excessive oil accumalation on Southern University Baton Rouge 31 S02167 TBD SU T T Allain Hall Deficient Elevator pit floor (E) 7/14/15 Southern University Baton Rouge 31 S02167 TBD SU T T Allain Hall Deficient Elevator 5.1 No cover over sump hole (O) 7/14/15 5.11 Oil coming from packing 31 Southern University Baton Rouge S02167 TBD SU T T Allain Hall Deficient Elevator around piston (E) 7/14/15