Engineering Data ED 15112-12

Group : Controls Part Number: ED 15112 Date : March 2014 Supersedes: ED 15112-11

MicroTech ® III Rooftop and Self Contained Unit Controller Protocol Information

BACnet ® Networks LON WORKS ® Networks

• RoofPak™ Applied Rooftop Models: RPE, RDE, RPS, RDT, RFS, RDS and RAH

• Self-Contained Models: SWT, SWP

• Maverick™ II Commercial Rooftop Model: MPS

• Rebel™ Model: DPS

© 2014 Daikin Applied Table of Contents

Table of Contents ...... 2 Effective Discharge Air Temperature Setpoint ...... 51 Revision History ...... 4 Effective Setpoint Output ...... 52 Software Revision ...... 4 Emergency Off Switch ...... 52 Reference Documents ...... 5 Emergency Override ...... 53 Notice ...... 5 Energy Recovery Leaving Air Temperature ...... 53 Limited Warranty ...... 5 Energy Recovery Exhaust Air Temperature ...... 54 Introduction ...... 6 Energy Recovery Wheel Hours ...... 54 Unit Controller Data Points ...... 6 Energy Recovery Wheel Status ...... 54 Protocol Definitions ...... 6 Energy Recovery Wheel Speed ...... 55 Basic Protocol Information ...... 7 Entering Temperature / Leaving Coil Temp ...... 55 Setting Unit Controller Communications Parameters ...... 7 Entering Water Temperature ...... 55 BACnet Networks ...... 7 Exhaust Fan Capacity ...... 56 MicroTech III Unit Controller Device Object ...... 9 Exhaust Fan Capacity Input...... 56 Network Considerations ...... 10 Exhaust Fan Status ...... 57 LON WORKS Networks ...... 11 Freeze Switch (Fault) ...... 57 Typical Application: Minimum Integration ...... 14 Freeze Switch (Problem) ...... 58 Set up the Unit for Network Control ...... 14 Heat Fail Input ...... 58 Display Important Data Points...... 14 Heating Capacity ...... 58 Network Off ...... 14 Heating Hours ...... 59 Network Occupancy Scheduling ...... 14 Heating Status ...... 59 Alarms and Events...... 15 High Pressure Circuit 1 Switch ...... 60 Unit Controller Sequence of Operation ...... 16 High Pressure Circuit 2 Switch ...... 60 Comprehensive Data Point Tables ...... 17 High Pressure Circuit 3 Switch ...... 61 BACnet Standard Objects ...... 17 High Pressure Circuit 4 Switch ...... 61 LON WORKS Variables ...... 25 High Pressure Circuit 5 Switch ...... 61 Detailed Data Point Information ...... 30 High Pressure Circuit 6 Switch ...... 62 AHU Loc/Net ...... 34 High Pressure Circuit 7 Switch ...... 62 Application Mode ...... 34 High Pressure Circuit 8 Switch ...... 63 Airflow Switch (Fault) ...... 35 HVAC Unit Type Identifier ...... 63 Airflow Switch (Warning) ...... 36 Indoor Temperature ...... 64 Application Version ...... 36 Inverter Hours ...... 64 Building Static Pressure ...... 36 Inverter Compressor Body Temperature ...... 64 Building Static Pressure Setpoint ...... 37 Local OA Temperature ...... 65 Compressor 1 Hours ...... 37 Local Space Temperature ...... 65 Compressor 2 Hours ...... 37 Low Pressure Circuit 1 Switch ...... 65 Compressor 3 Hours ...... 38 Low Pressure Circuit 2 Switch ...... 66 Compressor 4 Hours ...... 38 Low Pressure Circuit 3 Switch ...... 66 Compressor 5 Hours ...... 38 Low Pressure Circuit 4 Switch ...... 66 Compressor 6 Hours ...... 39 Low Pressure Circuit 5 Switch ...... 67 Compressor 7 Hours ...... 39 Low Pressure Circuit 6 Switch ...... 67 Compressor 8 Hours ...... 39 Low Pressure Circuit 7 Switch ...... 68 Compressor Cooling Hours ...... 40 Low Pressure Circuit 8 Switch ...... 68 Compressor Heating Hours ...... 40 Max Purge Time ...... 68 Conductivity ...... 40 Maximum Discharge Air Heating Setpoint ...... 69 Control Temp Source ...... 41 Maximum Leaving Coil Temperature Dehum Setpoint ...... 69 Control Temperature ...... 41 Daikin Applied AHU Unit Status ...... 69 Cooling Capacity ...... 42 Mechanical Cooling Hours ...... 70 Cooling Status ...... 42 Minimum Discharge Air Cooling Setpoint ...... 71 Date ...... 43 Minimum Leaving Coil Temperature Dehum Setpoint ...... 71 Defrost State ...... 43 Minimum Send Time ...... 71 Defrost Temperature ...... 43 Mixed Air Temperature ...... 72 Dehumidification Hours ...... 44 Morning Warm-up Heating Setpoint ...... 72 Dehumidification Status ...... 44 Network Discharge Air Cooling Setpoint ...... 73 Dew Point Setpoint ...... 44 Network Discharge Air Heating Setpoint ...... 73 Dew Point Temperature ...... 45 Object Request ...... 73 Dirty Filter Switch ...... 45 Object Status ...... 74 Discharge Air Temperature ...... 45 Occupancy ...... 75 Discharge Line Temperature 1 ...... 46 Occupancy Mode ...... 76 Discharge Line Temperature 2 ...... 46 Occupancy Scheduler Input ...... 77 Discharge Line Temperature 3 ...... 46 Occupied Cooling Setpoint...... 78 Discharge Refrigerant Pressure ...... 47 Occupied Heating Setpoint ...... 79 Discharge Refrigerant Pressure Circuit 1...... 47 Outdoor Air Minimum Position Input ...... 79 Discharge Refrigerant Pressure Circuit 2...... 47 Outdoor Air Temperature ...... 80 High Limit Switch ...... 48 Outdoor Air Temperature Input ...... 80 Duct Static Pressure...... 48 Outdoor Airflow ...... 81 Duct Static Pressure Setpoint ...... 49 Outdoor Airflow Setpoint ...... 81 Capacity ...... 49 Outdoor Refrigerant Temperature ...... 81 Economizer Enable...... 49 Primary Cool Enable ...... 82 Economizer Hours ...... 50 Primary Heat Enable ...... 82 Economizer Status ...... 50 Receive Heartbeat ...... 83

2 ED15112-12 Reheat Capacity ...... 84 High Discharge Line Temperature Unload Event ...... 123 Relative ...... 84 High Inverter Compressor Body Temp Problem ...... 124 Relative Humidity Input ...... 85 High Discharge Superheat Problem...... 124 Relative Humidity Setpoint ...... 85 High Discharge Superheat Unload Event ...... 124 Remote Return/Exhaust Fan Capacity Control Flag ...... 86 High Pressure Circuit 1 Problem ...... 125 Remote Supply Fan Capacity Control Flag ...... 86 High Pressure Circuit 2 Problem ...... 125 Return Air Temperature ...... 87 High Pressure Circuit 3 Problem ...... 126 Return/Exhaust Fan Capacity ...... 88 High Pressure Circuit 4 Problem ...... 126 Return/Exhaust Fan Hours ...... 88 High Pressure Circuit 5 Problem ...... 126 Return Fan Capacity Input ...... 89 High Pressure Circuit 6 Problem ...... 127 Send Heartbeat ...... 89 High Pressure Circuit 7 Problem ...... 127 Space CO 2 ...... 90 High Pressure Circuit 8 Problem ...... 127 Space IAQ Input ...... 90 High Pressure Problem ...... 128 Space Temperature ...... 90 High Pressure Unload Event ...... 128 Space Temperature Input ...... 91 High Return Temp Fault...... 129 Staged Exhaust 1 Hours ...... 91 Interface Board Communication Problem ...... 129 Staged Exhaust 2 Hours ...... 92 Inverter Compressor Problem ...... 129 Suction Refrigerant Pressure ...... 92 Low Discharge Pressure Problem ...... 130 Suction Line Refrigerant Temperature ...... 92 Low Discharge Pressure Unload Event ...... 130 Sump Pump Water Level Switch ...... 93 Low Discharge Superheat Problem ...... 130 Supplemental Heating Capacity ...... 93 Low Discharge Superheat Unload Event ...... 131 Supplemental Heating Status ...... 93 Low Discharge Temp Fault ...... 131 Supply Fan Capacity ...... 94 Low Pressure Circuit 1 Problem ...... 131 Supply Fan Capacity Input ...... 94 Low Pressure Circuit 2 Problem ...... 132 Supply Fan Hours ...... 95 Low Pressure Circuit 3 Problem ...... 132 Temperature Setpoint Input ...... 95 Low Pressure Circuit 4 Problem ...... 133 Tenant Override Hours ...... 95 Low Pressure Circuit 5 Problem ...... 133 Time ...... 96 Low Pressure Circuit 6 Problem ...... 133 Unit State ...... 96 Low Pressure Circuit 7 Problem ...... 134 Unit Support ...... 97 Low Pressure Circuit 8 Problem ...... 134 Unoccupied Cooling Setpoint ...... 97 Low Pressure Differential Problem ...... 135 Unoccupied Heating Setpoint ...... 98 Low Pressure Problem ...... 135 VAV Box Output ...... 98 Low Refrigerant Charge Problem ...... 135 Variable Compressor Hours ...... 99 Low Superheat Warning ...... 136 Variable Compressor Oil Status ...... 99 Mixed Air Temp Problem ...... 136 Water Flow Switch ...... 100 Oil Boost Event ...... 137 Water Regulating Valve ...... 100 Outdoor Temp Problem ...... 137 Waterflow Switch Input ...... 100 Outdoor Fan Problem ...... 137 Alarms and Events ...... 102 Reheat Stage Limited Event ...... 138 Fault Alarms (Highest Priority) ...... 102 Return Temp Problem ...... 138 Problem Alarms (Medium Priority) ...... 103 Return/Exhaust Fan Warning ...... 138 Warning Alarms (Lowest Priority) ...... 104 Space Temp Problem ...... 139 Events ...... 105 Sump Water Level Problem ...... 139 Alarm Monitoring ...... 105 Variable Compressor Emergency Stop Event ...... 140 Alarm and Event Notification ...... 106 Variable Compressor Problem ...... 140 Alarm Clearing ...... 108 Waterflow Switch Problem ...... 140 Objects ...... 108 Water Regulating Valve Problem ...... 141 Clear Alarms ...... 108 BACnet Device Management ...... 142 Notification Class - Events ...... 109 DeviceCommunicationControl - Disable ...... 142 Notification Class - Faults ...... 110 DeviceCommunicationControl - Enable ...... 142 Notification Class - Problem ...... 110 ReinitializeDevice (Reset) ...... 142 Notification Class - Warnings ...... 111 BACnet File Objects ...... 143 Alarm Value ...... 112 BACnet Client Config File ...... 143 Warning Alarm ...... 115 BACnet COV Config File ...... 143 Problem Alarm ...... 115 Error Log File...... 143 Fault Alarm ...... 117 History Log File ...... 143 Airflow Fault ...... 117 BACnet Event Enrollment Config File ...... 144 Airflow Switch Warning ...... 118 EDE File ...... 144 Charge Loss Problem ...... 118 EDE File – State Text...... 144 Conductivity Warning ...... 118 Appendix A: Protocol Implementation Control Temp Fault ...... 119 Conformance Statement (PICS)...... 145 Dirty Filter Warning ...... 119 BACnet Protocol Implementation Conformance Statement ...... 145 Discharge Sensor Fault ...... 119 Product Description ...... 145 Duct High Limit Fault ...... 120 BACnet Standardized Device Profile ...... 145 Emergency Off Fault ...... 120 Standard Object Types Supported ...... 147 Entering Fan Temp / Leaving Coil Temp Problem ...... 120 Data Link Layer Options ...... 150 Entering Water Temp Problem ...... 121 Segmentation Capability ...... 150 Expansion Valve Problem ...... 121 Device Address Binding ...... 150 Freeze Fault ...... 122 Networking Options ...... 151 Freeze Problem ...... 122 Character Sets Supported ...... 151 Heat Fail Problem...... 123 Index ...... 152 High Discharge Line Temperature Problem ...... 123

ED15112-12 3

Revision History ED15112 September 2008 Preliminary release. ED15112-1 October 29, 2008 Added 2 notification class objects to BACnet. There are now a total of 3 objects (faults, problems & warnings). ED15112-2 January 22, 2009 The only change was to the Networking Options section of the Protocol Information Conformance Statement (PICS). The BBMD does support registration by foreign devices. This was previously marked no. Changed the enumeration for the Water Regulating Valve object from 0=Open and 1=Closed to 0=normal and 1=alarm. ED15112-3 March 11, 2009 The only change was to the Standard Object Types Supported section of the Protocol Information Conformance Statement (PICS). • Present Value, Priority Array were removed from the optional list for Binary Outputs. These properties are required. • Removed Alarm Value from the optional list for Binary Outputs. This is not a propertie of this object. Also removed Priority Array from Binary Inputs. This is not a property of this object. • Modified the optional properties for Multi-state Input. • Modified the optional properties for Multi-state Output ED 15112-4 November, 2009 Added Maverick II (MPS) model. Modified keypad navigation per new global standard. Updated points affected by removal of BACnet heartbeat function (changed points from commandable to writable and removed reference to writing at priority 8). Added the following points: Heat Fail 199, Heat Fail Problem BV, ERDAT (AV), EREhht (AV), ERWhlOnOff (MV), ERWheelSpd (AV), Min OA Flw Spt (AV) ED 15112-5 December, 2009 Changed ER Discharge Air Temp & ER Exhaust Air Temp BACnet object types from AV to AI.Updated firmware version from 2506017300 to 2506017301 in Software Revision and PICs sections. ED 15112-6 February, 2010 Changed ER Wheel Speed BACnet object types from AV15 to AI15. Removed reference to energy recovery from Return Fan Capacity Input & Exhause Fan Capacity Input (Detailed Data Information section). Changed Application Mode enumerations in detailed data section. Updated PICS to include software v2506017302. ED 15112-7 June, 2010 Changed nvoUnitStatus_inAlarm_ to nvo WarnAlarm, nvoProbAlarm, and nvoFaultAlarm in detailed data section. Updated software revision to v2506017304. Removed references to S7 switch on fig. 4. ED 15112-8 February 2011 Added Control Temp Source (MSV 39) to BACnet. This is available in application 2506017306. Added DAC checkbox to Relative Humidity Input on the BACnet Standard Objects Table. Added Low/High Pressure Circuit Switch 7 and 8, added Low/High Pressure Circuit 7 and 8 Problem, changed Sump Pump Switch to Sump Pump Water Level Switch, changed Sump Pump Fail Problem to Sump Water Level Problem. ED 15112-9 April 2012 Specified in the Space Temperature Input section.that the range of the network space temperature is different for BACnet and LonWorks. Specified LonWorks invalid value for Build Static Pressure Setpoint and Duct Static Pressure Setpoint. Updated BACnet and LonWorks Data Point Tables and detailed data sections for the

following: added Morning Warm-up Heating Setpoint, changed Zone Temp to Htg/Clg C for network access, removed MRNG WRMUP from Unit State (LON only), changed Sump Pump Water Level Fail to Problem Alarm, Renamed ER DAT= and ER ExhT= to ER LAT= and ER EAT added Rebel model DPS, changed AV53 in detailed data section from read-only to read-write. Updated Daikin logo and references ED 15112-10 Mayt 2012 Clarified Application Mode description. Spelling corrections. ED 15112-11 July 2012 Correction s to data points by model type – Table 4. Updated PICS for new application/firmware versions. ED 15112-12 March 2014 Added Dehumidification Status and Ret/Exh Fan Warning. Modified Remote Supply Fan Capacity Control Flag to add the following enumerations: BSP, CO2 and CFM. Added: Defrost State, Inverter Compressor Body Temperature, High Inverter Comp Body Temp problem, Inverter Comp Body Temp Sensor Problem, Max Purge Time, Min & Max Leaving Coil Temperature Dehumidification Setpoints. Added datapoints, alarms and events to support variable . Updated Daikin Applied logo and references

Software Revision Keypad Menu Path Version Information\App Version= The software part number is encoded in the controller’s memory and is available for display on the keypad/display. The part number is available via BACnet® system integration tools. The software part number codification is as follows: 250 6017 4 01 Implied digits on all MicroTech III Air Handling software* Base part number (6017 indicates standard software) Version Revision

4 ED15112-12 *This edition documents network protocols for version 2506017401 (and all subsequent versions until otherwise indicated) of the standard MicroTech ® III Unit Controller application for Applied Rooftop models RDE, RPS, RDT, RFS, RDS and RAH, Self-Contained models SWT and SWP, and Maverick II, model MPS. It also documents version 2506018101 (and subsequent versions) for Rebel Packaged Rooftop, model DPS. However, if your software is of a later version, some of the information in this document may not completely describe your application. You can determine the revision of the application software from the keypad/display. The path for this information from the main menu is Version Information\App Version= .

Reference Documents Company Number Title Source Daikin Applied OM 920 MicroTech III Unit Controller for Commercial Rooftop, www.DaikinApplied.com Applied Rooftop and Self-Contained Systems Daikin Applied OM 1141 MicroTech III Unit Controller for Rebel Commercial www.DaikinApplied.com Rooftop Systems American Society of Heating, ANSI/ BACnet® A Data Communication Protocol for Building www..org Refrigerating and Air- ASHRAE 135- Automation and Control Networks Conditioning Engineers 2008 LonMark Interoperability 078-0120-01G LonMark® Layers 1-6 Interoperability Guidelines, www.lonmark.org Association Version 3.4 LonMark Interoperability 078-0120-01G LonMark Application Layer Interoperability Guidelines, www.lonmark.org Association Version 3.4 LonMark Interoperability 8500_10 LonMark Functional Profile: Space Comfort Controller, www.lonmark.org Association Version 1.0 LonMark Interoperability 8600_10 LonMark Functional Profile: Discharge Air Controller, www.lonmark.org Association Version

Daikin Applied ED 15113 MicroTech III Rooftop and Self-Contained Systems www.DaikinApplied.com BACnet Protocol Implementation and Conformance Statement (PICS) Echelon Corporation 078-0156-01G LON WORKS FTT-10A Free Topology Transceiver Users www.echelon.com Guide

Notice © 2014 Daikin Applied, Minneapolis MN. All rights reserved throughout the world. Daikin Applied reserves the right to change any information contained herein without prior notice. The user is responsible for determining whether this product is appropriate for his or her application.   The following are trademarks or registered trademarks of their respective companies: BACnet from American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Echelon, LON WORKS , LON MARK , and LonTalk from Echelon Corporation, Windows from Microsoft Corporation, and Daikin Applied, Maverick II, Rebel, and MicroTech III from Daikin Applied.

Limited Warranty Consult your local Daikin Applied Representative for warranty details. Refer to Form 933-430285Y. To find your local Daikin Applied Representative, go to www.DaikinApplied.com .

ED15112-12 5 Introduction

This document contains the necessary information you need to incorporate a MicroTech III Unit Controller (i.e. Applied Rooftop, Self-Contained, Maverick II™ or Rebel™) from Daikin Applied into a system (BAS). It lists ® all BACnet properties, LON WORKS variables, and corresponding MicroTech III Unit Controller data points. It also contains the BACnet Protocol Implementation Conformance Statement (PICS). BACnet and LON WORKS terms are not defined. Refer to the respective specifications for definitions and details. Unit Controller Data Points The MicroTech III Unit Controller contains data points or unit variables that are accessible from three user interfaces: the unit keypad, a BACnet network (BACnet/IP or MS/TP), or a LON WORKS network. Not all points are accessible from each interface. This manual lists all important data points and the corresponding path for each applicable interface. Refer to OM 920 (available on www.DaikinApplied.com) for keypad details. This document contains the network details necessary to incorporate the MicroTech III Unit Controller into the network. Protocol Definitions The MicroTech III Unit Controller can be configured in either an interoperable BACnet or LON WORKS network. The controller must have the corresponding communication module installed for network integration (see Reference Document section for corresponding part numbers). There are three communication modules: BACnet/IP, BACnet MS/TP (Master/Slave Token Passing), and LON WORKS . There are two LON WORKS modules: one in accordance with the LonMark Space Comfort Controller (General) functional profile and one in accordance with the Discharge Air Controller functional profile. BACnet Protocol BACnet is a standard communication protocol for Building Automation and Control Networks developed by the American National Standards Institute (ANSI) and American Society of Heating, and Air-conditioning Engineers (ASHRAE) specified in ANSI/ASHRAE standard 135-2008. It addresses all aspects of the various systems that are applied to building control systems. BACnet provides the communication infrastructure needed to integrate products manufactured by different vendors and to integrate building services that are now independent. LON WORKS Networks A control network specification for information exchange built upon the use of LonTalk for transmitting data developed by the Echelon Corporation. LonTalk Protocol A protocol developed and owned by the Echelon Corporation. It describes how information should be transmitted between devices on a control network. LonMark Certification LonMark certification is an official acknowledgement by the LonMark Interoperability Association that a product communicates using the LonTalk protocol and transmits and receives data per a standard LonMark functional profile. The LON WORKS communication modules are LonMark 3.4 certified in accordance with the Space Comfort Controller (SCC) and Discharge Air Controller (DAC) functional profiles.

6 ED15112-12 Basic Protocol Information

Setting Unit Controller Communications Parameters There are 12 communication parameters involved in setting up the unit controller for proper communication with the four communication module options (BACnet IP, BACnet MS/TP, LON WORKS SCC or LON WORKS DAC). These parameters are set differently depending on which communication module is ordered and shipped with the unit. The table below lists the three possible sets of default parameter settings. Not all the parameters apply to all the module options. The bold parameters can be changed using the keypad display located on the unit controller.

Communication Setup Parameter Settings Parameter Name BACnet IP BACnet MS/TP LON (DAC or SCC) DHCP On N/A N/A IP Address DHCP Enabled N/A N/A IP Subnet Mask DHCP Enabled N/A N/A Given IP Address 1 127.0.0.1 N/A N/A Given IP Subnet 255.255.255.0 N/A N/A Mask 1 Given Gateway 127.0.0.1 N/A N/A Address 1 UDP Port Number 47808 N/A N/A MSTP MAC N/A 18 N/A Address 2 MSTP Baud Rate N/A 38400 N/A Device Instance variable variable N/A Number Max APDU Length 1476 480 N/A Device Object POL908_FF2BEE 3 POL904_AD45EC28 4 N/A Name Receive Heartbeat 0Sec 0Sec 0Sec Max Master N/A 127 N/A Max Info Frames N/A 1 N/A Term Resistor N/A No 5 N/A Notes: 1. These addresses are used if DHCP is set to Off. For changes to these parameters to take effect, use the keypad display and set Apply IP Chg on the IP Setup menu to Yes and cycle power. 2. The MSTP MAC Address is set via the keypad/display. You must cycle power after changing it for the changes to take effect. 3. The last 6 digits are the last 6 digits of the MAC address. The MAC address is printed a sticker affixed to the BACnet communication module. 4. The last 8 digits are computed from the production number and date code. 5. Term Resistor is only changeable via the keypad/display. This item must be set to Yes for the first and last unit on the MS/TP network. On all other units, this variable should be set to No (default).

BACnet Networks Compatibility The MicroTech III Unit Controller Unit Controller is tested according to the BACnet Testing Laboratory (BTL) Test Plan. It is designed to meet the requirements of the BACnet Standard (ANSI/ASHRAE 135-2008) as stated in the Protocol Implementation and Conformance Statement (PICS). However, it is not BTL listed. The PICS is located at the end of this manual or the separate PICS document, ED 15113 (available on www.DaikinApplied.com .)

BACnet Objects MicroTech III Unit Controllers incorporate standard BACnet object types (i.e., object types defined in the BACnet Standard) that conform to the BACnet Standard. Each object has properties that control unit variables or data points. Some object types occur more than once in the MicroTech III Unit Controller; each occurrence or instance has different properties and controls different unit variables or data points. Each instance is designated with a unique instance index. Some

ED15112-12 7 properties can be adjusted (read/write properties, e.g., setpoints) from the network and others can only be interrogated (read- only properties, e.g., status information). Each data point accessible from a BACnet network is described with a table that gives the Object Identifier, Property Identifier, Full BACnet Reference or path, and the Name enumeration of the property.

Example of BACnet Data Point

Keypad Menu Path Standard Menus\Flow Summary\Ret/Exh Fan= Object Identifier Property Object Type Type ID Instance Name ID Binary Output 4 1 Present_Value 85 Full Reference .ExhFanState.Present_Value Enumeration 0 = Off 1 = On

Object Identifier Object Identifiers are each designated with an Object type as defined in the BACnet specification. The first column of the data point definition gives the object type. This object happens to be Return/Exhaust Fan Status (See page 88.) The object identifier is a property of the object that you can read from the object. The name of the property is “Object_Identifier” and the property identifier is 75. Each object in the unit controller has a unique identifier. BACnet object identifiers are two-part numbers of BACnet Object Identifier data type. The first part identifies the object type (the first 10 bits of the 32-bit BACnet Object Identifier [See ANSI/ASHRAE 135-2008 BACnet A Data Communication Protocol for Building Automation and Control Networks]). The first column of the data point definition gives the object type. The second part identifies the instances of that particular object type (the last 22 bits of the 32-bit BACnet Object Identifier). The object identifier is shown in the data points listing as two numbers. The first number is shown in the Type ID column and designates the Object type enumeration. The second number is shown in the Instance column and designates the instance of that particular object type. The object identifier is a property of the object that you can read from the object code. The name of the property is “Object_Identifier” and the property identifier is 75. The ASHRAE BACnet specification reserves the first 128 numbers for ASHRAE defined objects. Manufacturers may define additional object types and assign a number above 127 as long as they conform to the requirements of the ASHRAE BACnet specification. Each object also has a name. Object names are character strings. The object name is a property of the object that you can read from the object. The name of the property is “Object_Name” and the property identifier is 77. Objects are sometimes referred to as an object type and instance number as they are in the BACnet specification. The example object above would be: Binary Output, Instance 1. Property Identifier Each object has a number of properties or attributes. Each property has a unique identifier of BACnet Property Identifier data type. Property identifiers are an enumerated set; a number identifies each member. The Property Identifier enumeration number is shown in the Property ID column. In the example above the property identifier is 85. Property Name Each property also has a unique name. Property names are character strings and shown in the Property Name column. In the example above the property name is Present Value. Full Reference The full reference is the path of the property within the network where the MicroTech III Unit Controller resides. It is a character string equivalent to the object identifier and the property identifier. In the example above the full reference is .ExhFanState.Present_Value. Enumerated Values Some properties are standard data types and some are enumerated sets. If the property value is an enumerated set, all enumerated values and corresponding meaning are given in the Enumeration column of the data point listing.

8 ED15112-12

MicroTech III Unit Controller Device Object Each BACnet compatible device must have one and only one BACnet Device Object. Device Object Identifier The MicroTech III Unit Controller Device Object Identifier uniquely specifies the unit within the network. The device object type for all devices is fixed by ASHRAE at 8. Therefore the device object instance number must be unique. The initial Device Object identifier is set at manufacturing. The device object identifier can be read from the unit controller. The name of the property is “Object_Identifier” and the property identifier is 75. The initial device object instance number is 1579312. This number must be unique on the entire BACnet network. The object instance number can be changed via the keypad display. You must cycle power for the change to take effect.

! CAUTION

If another device in the network already has this object identifier (instance number), you must change the instance number of one device object, so that all devices in the network have a unique device identifier.

Device Object Name The Device Object Name uniquely specifies a device in the network. It must be unique in the network. The device name for the MicroTech III Unit Controller device is to be determined. The device name is the “prefix” of all object names in the MicroTech III Unit Controller. All objects include the device name and a period “.” preceding the object name. The Device Object name is also available to the network in the device. The property name is “Object_Name” and property identifier is 77. For a BACnet IP card, the default Object Name is POL908_###### where ###### is the last 6 digits of the MAC address. For a BACnet MS/TP card, the default Object Name is POL904_######## where ######## is computed from the production number and date code. Device Object Properties The device object contains many other informative properties as shown in Table 1. Table 1. MicroTech III Air Handling Unit Controller Device Object Properties

Property Identifier Default Value Data Type Object Identifier 75 Device, variable BACnetObjectIdentifier Object Name 77 POL908_FF2BEE 1 Character String

Object Type 79 8 BACnetObjectType System Status 112 BACnetDeviceStatus Vendor Name 121 Daikin Applied Character String Vendor Identifier 120 3 Unsigned 16 Model Name 70 AHU Character String Firmware Version 44 variable Character String Application Software Revision 12 variable Character String Location 58 Character String Description 28 MTech III AHU Character String Protocol Version 98 1 Unsigned Protocol Revision 139 6 Unsigned Protocol Services Supported 97 BACnetServicesSupported Protocol Object Types Supported 2 96 AI, AO, AV, BI, BO, BV, Cal, BACnetObjectTypesSupported Device, MSI, MSO, NC, Sch, MSV Object List 76 Sequence of BACnetObjectIdentifer Max APDU Length Accepted 62 1476 (IP) / 480 (MS/TP) Unsigned 16

ED15112-12 9 Property Identifier Default Value Data Type Segmentation Supported 107 None BACnetSegmentation Max Segments Accepted 167 16 Unsigned Local Time3 57 variable Time Local Date 3 56 variable Date UTC Offset 119 -60 (Range: –780 .. 780) Integer Daylight Savings Status 24 variable Boolean APDU Segment Timeout 10 2000 Unsigned APDU Timeout 11 6000 Unsigned Number of APDU Retries 73 3 Unsigned Device Address Binding 30 Sequence of BACnetAddressBinding Database Revision 115 1 Unsigned Active COV Subscriptions 152 List of BACnetCOVSubsriptions

1. For BACnet IP, the last 6 digits are the last 6 digits of the MAC address. The MAC address is printed a sticker affixed to the BACnet communication module. For BACnet MS/TP, the last 8 digit are computed from the production number printed on the bar code label affixed to the side of the module. 2. While the MicroTech III Unit Controller supports the entire set of object types, not all object types are used. See the Object List for details. 3. The BACnet communication module and the MicroTech III Unit Controller both have their own time clocks. The date and time read via BACnet could differ from the date and time in the unit controller the date or time is changed via the keypad display. The two time clocks resynchronize approximately every 60-68 minutes and after every power cycle of the unit controller or BACnet communication module.

Network Considerations Access to Properties Object properties are accessible from the network by specifying the device object identifier, object identifier, and the property identifier. To access a property, you must specify the object identifier including the device object identifier or the object name including the device object name and the property identifier.

BACnet/IP Addressing The BACnet/Internet Protocol (BACnet/IP) address of the MicroTech III Unit Controller in a BACnet/IP network consists of the four-octet Internet Protocol address followed by the two-octet UDP (User Datagram Protocol) port number. The BACnet/IP address is a six-octet value analogous to a MAC address. The IP address portion of the BACnet/IP address must be unique in the BACnet/IP network segment. The default UDP port number in the MicroTech III Unit Controller is 47808 (BAC0 in hexadecimal). The device object of the MicroTech III Unit Controller contains a Given Internet Protocol Subnet Mask (Default is 255.255.255.0) and a default Given IP address of 127.0.0.1. The controller does support DHCP (Dynamic Host Configuration Protocol) IP addressing which is enabled by default. The keypad/display can be used to configure the BACnet/IP addressing. The keypad will display the current IP address only when the network is connected. The MicroTech III Unit Controller can be incorporated into a BACnet/IP network dedicated to BACnet devices only or an Ethernet network shared with BACnet devices and other devices.

Shared Ethernet Networks Integrating the MicroTech III Unit Controller into a shared Ethernet LAN requires close cooperation with the network administrator of the shared Ethernet network. First, verify whether DHCP should or should not be enabled. If not, obtain the IP Subnet Mask of the shared network from the network administrator. Then, obtain static IP Addresses for all MicroTech III Unit Controllers you are integrating into the shared network. Finally obtain the address of an IP Router to use for sending IP messages to and from the BACnet IP subnets. Once you have these, refer to Setting Unit Controller Communication Parameters in the Basic Protocol Information section found previously in this document.

10 ED15112-12 Configuring the Unit Controller The MicroTech III Unit Controller with attached BACnet communication module is ready to operate with the default values of the various parameters. Default values may be changed with the unit’s keypad or via the network. Refer to the MicroTech III Unit Controller for Commercial Rooftop, Applied Rooftop and Self-Contained Systems (OM 920) or MicroTech III Unit Controller for Rebel Commercial Rooftop Systems (OM 1141). BACnet MS/TP Network Addressing The BACnet MS/TP device address (Media Access Control [MAC] address) of the MicroTech III Air Handling Unit Controller in a BACnet Master Slave/Token Passing (MS/TP) Local Area Network (LAN) is set using the keypad/display. Navigate to the Advanced Menus\MSTP Setup menu to change this value. You must cycle power (turn the unit controller off and then on again) in order for the new address to take effect. LON WORKS Networks LON WORKS technology, developed by Echelon Corporation, is the basis for LonMark interoperable systems. This technology is independent of the communications media. The LonMark Interoperable Association has developed standards for interoperable LON WORKS technology systems. In particular they have published standards for HVAC equipment including the Discharge Air Controller functional profile and the Space Comfort Controller functional profile. These profiles specify a number of mandatory and optional standard network variables and standard configuration parameters. This manual defines these variables and parameters available in the MicroTech III Unit Controller.

Compatibility The MicroTech III Unit Controller with LON WORKS communication module operates in accordance with the Discharge Air Controller (DAC) functional profile or the Space Comfort Controller (SCC) functional profile of the LonMark Interoperability standard.

LON WORKS Variables MicroTech III Unit Controllers incorporate LON WORKS network variables to access unit data points. The unit controller uses LON WORKS Standard Network Variable Types (SNVT) from each profile. Some data points can be adjusted (input network variables, nvi) (read/write attributes, e.g., setpoints) from the network and others can only be interrogated (output network variables, nvo) (read only attributes, e.g., status information). Configuration variables (nci) are included with the read/write attributes. Each data point accessible from a LON WORKS network is described with a table that gives the LON WORKS Name, Profile, SNVT Type, and SNVT Index. If the variable is a configuration variable the table also includes the SCPT Reference and the SCPT Index.

Example of LON WORKS Data Point LonWorks LonWorks Name Profile SNVT Type SNVT Index nvoBldgStatPress DAC, SCC SNVT_press_p 113

LON WORKS Name Each network variable has a name that you use to access the data point. This is the name of the variable from the profile. In the example above the name network variable is nvoBldgStatPress. Profile The profile column designates the MicroTech III LON WORKS Communication Module that incorporates this network variable. The variable itself may not be a standard component of that particular profile, but the communications module does implement and it is available to the network.

SNVT Type This column gives the name of the standard network variable type from the master list.

SNVT Index This column gives the number of the standard network variable type from the master list.

SCPT Reference This column gives the name of the Standard Configuration Parameter Type (SCPT) from the master list.

SCPT Index This column gives the number of the Standard Configuration Parameter Type (SCPT) from the master list.

ED15112-12 11

Network Considerations Network Topology Each LON WORKS Communication Module is equipped with an FTT-10A transceiver for network communications. This transceiver allows for (1) free topology network wiring schemes using twisted pair (unshielded) cable and (2) polarity insensitive connections at each node. These features greatly simplify installation and reduce network commissioning problems. Additional nodes may be added with little regard to existing cable routing. Free Topology Networks A LON WORKS “free topology network“ means that devices (nodes) can be connected to the network in a variety of geometric configurations. For example, devices can be daisy-chained from one device to the next, connected with stub cables branching off from a main cable, and connected using a tree or star topology, or any of these configurations can be mixed on the same network. Free topology segments require termination for proper transmission performance. Only one termination is required. It may be placed anywhere along the segment . Refer to Echelon LON WORKS FTT-10A Transceiver User’s Guide for further details). Free Topology Restrictions Although free topology wiring is very flexible, there are restrictions. See below for a basic summary of limitations. Refer to the Echelon FTT-10A User’s Guide for complete details. 1. The maximum number of nodes per segment is 64. 2. The maximum total bus length depends on the wire size: Wire Size Maximum Node-to-Node Length Maximum Cable Length 24 AWG 820 ft (250 m) 1476 ft (450 m) 22 AWG 1312 ft (400 m) 1640 ft (500 m) 16 AWG 1640 ft (500 m) 1640 ft (500 m)

The longest cable path between any possible pair of nodes on a segment must not exceed the maximum node-to-node distance. If two or more paths exist between a pair of nodes (e.g., a loop topology), the longest path should be considered. Note that in a bus topology, the longest node-to-node distance is equal to the total cable length. 1. The total length of all cable in a segment must not exceed the maximum total cable length. 2. One termination is required in each segment. It may be located anywhere along the segment. Doubly Terminated Networks You can extend the maximum total cable length without using a repeater by using doubly-terminated network topology. The trade-offs are (1) this network topology must be rigorously followed during the installation and subsequent retrofits and (2) two terminations must be installed at the ends of the bus for proper transmission performance. Refer to Echelon LON WORKS FTT-10A Transceiver User’s Guide. Network Cable Termination LON WORKS network segments require termination for proper data transmission performance. The type and number of terminations depend on network topology. Refer to Echelon LON WORKS FTT-10A Transceiver User’s Guide. LonWorks Network Addressing Every Neuron Chip has a unique 48-bit Neuron ID or physical address. This address is generally used only at initial installation or for diagnostic purposes. For normal network operation, a device address is used. Device addresses are defined at the time of network configuration. All device addresses have three parts. The first part is the Domain ID, designating the domain. Devices must be in the same domain in order to communicate with each other. The second part is the Subnet ID that specifies a collection of up to 127 devices that are on a single channel or a set of channels connected by repeaters. There may be up to 255 subnets in a domain. The third part is the Node ID that identifies an individual device within the subnet.

A group is a logical collection of devices within a domain. Groups are assembled with regard for their physical location in the domain. There may be up to 256 groups in domain. A group address is the address that identifies all devices of the group. There may be any number of devices in a group when unacknowledged messaging is used. Groups are limited to 64 devices if acknowledged messaging is used. A broadcast address identifies all devices within a subnet or domain.

LON WORKS network variables for both the Discharge Air Controller and the Space Comfort Controller are defined below. Variables are used in both the Space Comfort Controller and Discharge Air Controller profiles unless marked otherwise.

12 ED15112-12

Commissioning the Network Pressing the service pin, switch on the LON WORKS Communication Module, generates a service pin message, which contains the Neuron ID and the program code identification of the node. A service pin message is a network message that is generated by a node and broadcast on the network. It can be used to commission the LON WORKS network. A network configuration tool maps device Neuron IDs to the domain/subnet/node logical addressing scheme when it creates the network image, the logical network addresses and connection information for all devices (nodes) on the network. External Interface File (XIF) LonMark guidelines specify exact documentation rules so that proprietary configuration tools are not required to commission and configure LON WORKS devices. The MicroTech III LON WORKS Communication Module is self- documenting so that any network management tool can obtain all the information needed over the network to connect it into the system and to configure and manage it. An External Interface File (a specially formatted PC text file with an extension .XIF) is also available so that any network tool can design and configure it prior to installation. XIF files are available on http://www.DaikinApplied.com/ and www.lonmark.org.

Configuring the Unit Controller 1. The MicroTech III Unit Controller is designed, programmed, and configured to be a rooftop or self-contained unit controller in accordance with either the LON MARK Discharge Air Controller (DAC) or LonMark Space Comfort Controller (SCC) functional profile. The unit is ready to operate with the default values of the various parameters set at the factory. Default values may be changed with the unit’s keypad or via the network. See the MicroTech III Unit Controller Operation Manual (OM 920).

Data Integrity The integrity of some data depends on a valid network connection to maintain current values. The following data points require a valid network connection if bound. If data points listed in Table 2 do not change after a given time, the controller reverts to local control. In the case of the LonWorks module, the variables will revert to their default values.

Table 2. Receive Heartbeat Variables Data Point LonWorks Variable Occupancy Scheduler Input nviOccSchedule Application Mode nviApplicCmd Supply Fan Capacity Input nviSupFanCap Outdoor Air Temperature nviOutdoorTemp Space Temperature nviSpaceTemp Primary Cool Enable nviPriCoolEnable Primary Heat Enable nviPriHeatEnable Economizer Enable nviEconEnable Exhaust Fan Capacity Input nviExhFanCap Return Fan Capacity Input nviRetFanCap Water Flow Switch Input nviCWFlow Space (IAQ) Input nviSpaceIAQ Relative Humidity Input nviSpaceRH

ED15112-12 13 Typical Application: Minimum Integration

When you have integrated the unit into your network, you can monitor and control unit operation from your workstation. At a minimum, you can: • Display and monitor a minimum of important data points on your workstation display • Turn the unit on or off from your workstation • Set the schedule from your workstation and • Operate the unit safely This section gives you the basic information and outlines a procedure to set up the unit for network control.

Set up the Unit for Network Control To control the MicroTech III Unit Controller over the network, set the Control Mode function to AUTO from the unit keypad. The keypad password (2526) is required to edit this function. For a detailed description of how to use the keypad, refer to the MicroTech III Unit Controller for Commercial Rooftop, Applied Rooftop and Self-Contained Systems (OM 920) or MicroTech III Unit Controller for Rebel Commercial Rooftop Systems (OM 1141).

Display Important Data Points Typical workstation displays of MicroTech III Unit Controller attributes include the following significant data points (page number of detailed description in parenthesis). Each data point is identified with a number that also identifies it in the Comprehensive Data Point Tables. These data points are also shaded in the comprehensive tables so that you can distinguish them from the rest of the data points in the table. References in the text of this section also identify these data points with a number and shading. Table 3. Significant Data Points

No Configuration No Temperatures/Pressures No Setpoints No Clear Alarms 1 Unit State (96) 5 Discharge Air Temperature 9 Duct Static Pressure Setpoint 14 Clear Alarms (108) (45) (49) 2 Application Mode 6 Return Air Temperature 10 Unoccupied Cooling Setpoint (34) (87) (97) 3 Occupancy (75) 7 Outdoor Air Temperature 11 Occupied Cooling Setpoint (80) (78) 4 Occupancy Mode 8 Duct Static Pressure (46) 12 Occupied Heating Setpoint (76) (79) 13 Unoccupied Heating Setpoint (98)

You can display any number of additional data points based on job requirements or individual preference. See LON WORKS Variables for lists of all LON WORKS Variables available to a LON WORKS network. See BACnet Standard Objects on page 17 for a list of all Standard BACnet Objects available to a BACnet network. For a more detailed description of all available data points, see the Detailed Data Point Information section. Network Off The unit can be turned off over the network by writing to the Application Mode. Writing AUTO to Application Mode allows the unit controller to determine its mode of operation based on input conditions. Writing OFF to Application Mode shuts down the unit, etc. The Emergency Override Mode Flag can also be used to shut down the unit from the network.

Network Occupancy Scheduling Using the keypad, set the Occupancy Mode to Auto. Schedule unit operation over the network with the Occ Scheduler input. Switching from OCC, UNOCC, BYPASS (TntOvrd), or AUTO commands the unit into the mode you select.

14 ED15112-12 Alarms and Events Alarms in a MicroTech III Unit Controller are divided into three classes: Faults, Problems, and Warnings. • Fault Alarms have the highest priority. • Problem Alarms have medium priority. • Warning Alarms have the lowest priority. Notification BACnet MicroTech III Unit Controllers may have their alarms monitored by one of four methods: 1) individually by BACnet Binary Values, 2) Alarm value using one BACnet Analog Value, 3) Alarm class, or 4) Notification Classes. 1. To monitor alarms individually, read the Present_Value of the desired Binary Value object. Each alarm has its own Binary Value object. If the Present_Value is Inactive (0), the alarm is not active. If the Present_Value is Active (1), the alarm is active. 2. To monitor alarms by alarm value, read the Present_Value property of the Alarm Value Analog Value object. The Present_Value displays a value that corresponds to the highest priority alarm that is active. It is possible to have multiple active alarms, but only the highest priority is displayed. For example, if there is a simultaneous Dirty Filter Warning (value of 24) and a Freeze Fault (value of 252), then the Freeze Fault value of 252 will display in the Present_Value because it is the higher priority alarm of the two. Once the Freeze Fault condition is corrected and the fault is cleared, the next priority active alarm value (in this example, value of 24 for Dirty Filter alarm) is displayed. The values for all alarms are described in the Alarms section tables. If the Present_Value displays a zero, there are no active alarms. 3. To monitor alarms by alarm class, read the Present_Value of the appropriate Analog Value object (Warnings, Problems and Faults). The Present_Value displays a value that corresponds to the highest priority alarm that is active for that particular alarm class. It is possible to have multiple active alarms, but only the highest priority is displayed. 4. To monitor alarms using the Notification Class objects, see the Alarm Notification section.

LON WORKS MicroTech III Unit Controllers may have their alarms monitored by one of two methods: 1) by using the In_alarm attribute of nvoUnitStatus or 2) by alarm class. 1. Alarms within MicroTech III Unit Controllers can be monitored individually by using the In Alarm attribute of the Unit Status Network Variable Output (i.e. nvoUnitStatus_in_alarm). This attribute displays a value that corresponds to the highest priority alarm that is active. It is possible to have multiple active alarms, but only the highest priority is displayed in this attribute. For example, if there is a simultaneous Dirty Filter Warning (value of 24) and a Freeze Fault (value of 252), then the Freeze Fault value of 252 will display in nvoUnitStatus_in_alarm because it is the higher priority alarm of the two. Once the Freeze Fault condition is corrected and the fault is cleared, the next priority active alarm value (in this example, value of 24 for Dirty Filter alarm) is displayed. The values for all alarms are described in the Alarms section tables. If the attribute nvoUnitStatus_in_alarm displays a zero, there are no active alarms. When the nvoUnitStatus_in_alarm attribute reads a value in the range of 1 to 99, a Warning Alarm is active. When the attribute reads a value in the range of 100 to 199, a Problem Alarm is active. When the attribute reads a value in the range of 200 to 255, a Fault Alarm is active. 2. To monitor alarms by alarm class, read nvoWarnAlarm, nvoProbAlarm and nvoFaultAlarm. The value corresponds to the highest priority alarm that is active. It is possible to have multiple active alarms, but only the highest priority is displayed.

Clearing BACnet MicroTech III Unit Controllers have one Multi-State Value objects that can be used to clear alarms. All alarms of a particular class may be cleared by writing the appropriate value to the Present Value property of ClearAlarms (2=ClearAllFaults, 3=ClearAllProblems, 4=ClearAllWarnings). All alarms of all three classes can be cleared by writing a 5 (ClearAllAlarms) to Present_Value. Once the alarms are cleared, the Present_Value of this object goes back to None (1).

LON WORKS MicroTech III Unit Controllers have one variable that can be used to clear alarms; nviClearAlarms. All alarms of a particular class may be cleared by writing the appropriate value to nviClearAlarms (1=ClearAllFaults, 2=ClearAllProblems,

ED15112-12 15 3=ClearAllWarnings). All alarms of all three classes can be cleared by writing a 4 (ClearAllAlarms) to nviClearAlarms. Once the alarms are cleared, this variable goes back to None (0).

Unit Controller Sequence of Operation The sequence of operation for a MicroTech III Unit Controller depends on the control type. Refer to the MicroTech III Unit Controller for Commercial Rootop, Applied Rooftop and Self-Contained Systems (OM 920) or MicroTech III Unit Controller for Rebel Commercial Rooftop Systems (OM 1141) available on http://www.DaikinApplied.com/, for sequence of operation details, including keypad operation.

16 ED15112-12 Comprehensive Data Point Tables

The two data point tables below contain the significant information for each BACnet object or LONWORKS variable available via the network from the MicroTech III unit controller. Additionally, refer to Table 4 for a summary of data points specific to each MicroTech III Unit Controller model. The Detailed Data Point Information section provides a comprehensive description of the properties, or attributes, for each point. BACnet Standard Objects Network Control Property (Keypad attributes available as BACnet Standard Objects for Description SCC SCC DAC DAC Type Type network control of the unit) Page Object Object Instance Instance Read, Write Read, Write

Unit Status/Settings Unit State 96 R MSV 15   1=Off, 2=Start, 3=Recirc, 4=FanOnly, 5=MinDAT, 6=Htg, 7=Econo, 8=Clg Daikin Applied AHU Unit Status 69 R MSV 1   Mode: 1=Enabled, 2=OffMan, 3=OffManCtrl, 4=OffNet, 5=OffAlm, 6=OffFanRetry Dehumidification Status 44 R MSV 46   1=Inactive, 2=Active Cooling Status 42 R MSV 2   1=Enabled, 2=None, 3=OffAmb, 4=OffAlarm, 5=OffNet, 6=OffMan Heating Status 59 R MSV 4   1=Enabled, 2=None, 3=OffAmb, 4=OffAlarm (Not Used), 5=OffNet, 6=OffMan Supplemental Heating Status 93 R MSV 45   1=Enabled, 2=None, 3=OffAmb, 4=OffAlarm (Not Used), 5=OffNet, 6=OffMan Economizer Status 50 R MSV 3   1=Enabled, 2=None, 3=OffAmb, 4=OffAlarm (Not Used), 5=OffNet, 6=OffMan, 7=OffDehum Cooling Capacity 42 R AV 1   cooling capacity (%) Heating Capacity 58 R AV 2   heating capacity (%) Supplemental Heating Capacity 93 R AV 54   Supplemental heating capacity (%) Supply Fan Capacity 91 R AI 8   Current supply fan capacity (%) Return/Exhaust Fan Capacity 88 R AI 10   Current return or exhaust fan capacity (%) Economizer Capacity 49 R AV 15   Feedback value (%) Emergency Override 53 W MSV 10   1=Normal, 2=Off (Shuts unit off via a network signal, puts Unit Status = OffNet) 1 Application Mode 34 W MSV 5   1=Off, 2=HeatOnly, 3=CoolOnly, 4=FanOnly, 5=Auto, 6=NA Applies only when Ctrl Mode=Auto Occupancy Occupancy 75 R MSV 6   1=Occ, 2=Unocc, 3=TntOvrd Occupancy Mode 76 W MSV 7   1=Occ, 2=Unocc, 3=TntOvrd, 4=Standby (not used) 5=Auto. Temperatures Control Temperature 41 R AI 14   Current reading of sensor Discharge Air Temperature 45 R AI 1   Current reading of sensor Return Air Temperature 87 R AI 2   Current reading of sensor C AV 45 Current reading of the Return Air Sensor. The Present Value of this object will be the same as the Present Value for AI2. This object is only present for intrinsic reporting of the High Return Air Temperature alarm. Though this object is commandable, the controller commands this object at priority 1 to avoid the BAS from writing to this and therefore disabling the high limit alarm. Space Temperature 90 R AI 3   Current reading of sensor Outdoor Air Temperature 80 R AI 4   Current reading of sensor Entering Fan / Leaving Coil Temp 55 R AI 7   Current reading of sensor Entering Water Temperature 55 R AI 6   Current reading of sensor Mixed Air Temperature 72 R AI 5   Current reading of sensor Discharge Line Temperature 3 46 R AI 21   Current reading of sensor Discharge Line Temperature 1 46 R AI 22   Current reading of sensor

ED15112-12 17 Network Control Property (Keypad attributes available as BACnet Standard Objects for Description SCC SCC DAC DAC Type Type network control of the unit) Page Object Object Instance Instance Read, Write Read, Write

Defrost Temperature 43 R AI 23   Current reading of sensor Suction Line Refrigerant 92 R AI 24   Current reading of sensor Temperature Indoor Refrigerant Temperature 64 R AI 27   Current reading of sensor Outdoor Refrigerant Temperature 81 R AI 28   Current reading of sensor Inverter Compressor Body 64 R AI 29   Current reading of sensor Temperature Discharge Line Temperature 2 46 R AI 32   Current reading of sensor Flow Status Exhaust Fan Status 57 R BV 1   0=Off, 1=On VAV Box Output 98 R MSV 14 N/A  1=Heat (Off), 2=Cool (On) SAF Spd Control Duct Static Pressure 48 R AV 6 N/A  Current reading of sensor. If unit has two sensors the lower of the two is displayed Duct Static Pressure Setpoint 48 W AV 7 N/A  Default = 1.00” WC Remote Supply Fan Capacity 86 W MSV 11   1=DSP, 2=Speed, 3=1ZnVAV, 4=BSP, 5=CO2, 6=CFM Control Flag 1 Supply Fan Capacity Input 94 W AV 21 N/A  Default = 163.835 (Null) Applies only when MSV11=Speed (2) RF/EF Spd Control Building Static Pressure 36 R AI 9   Current reading of sensor value Building Static Pressure Setpoint 37 W AV 8   Default = 0.050” WC Remote Return/Exhaust Fan 86 W MSV 12   1=None, 2=Tracking, 3=BldgP, 4=Speed, 5=OAD Capacity Control Flag 1 Return Fan Capacity Input 89 W AV 22   Default = 163.835 (Null) Applies only when MSV 12=Speed (4) 1 Exhaust Fan Capacity Input 56 W AV 23   Default = 163.835 (Null) Applies only when MSV 12=Speed (4) Cooling Occupied Cooling Setpoint 78 W AV 9   Default = 72°F / 22.22°C Unoccupied Cooling Setpoint 97 W AV 10   Default = 85°F / 29.44°C Network Discharge Air Cooling 73 W AV 13 N/A  Default = 55°F / 12.75°C Setpoint Applies only when ClgReset=Network Min Discharge Air Cooling Setpoint 71 W AV 14 N/A  Default = 55°F / 12.75°C Htg/Clg Chgovr Set-Up Control Temp Source 41 W MSV 39   1=RAT (NA on 100%OA Unit) 2=Space 3=MAT (Applicable on UnitType=SCU and ControlType=DAT only) 4=OAT (Applicable on ControlType=DAT only) 5=None (Applicable on ControlType=DAT only) Evap Cond Set-Up Conductivity 40 R AI 12   This variable provides the conductivity of the water in the sump of an evaporative cooled condenser. Min OA Set-Up

Space CO 2 90 R AI 13   This variable provides the concentration of CO 2 in the space (PPM). Outdoor Airflow 81 R AV 42   Outdoor Airflow Setpoint 81 W AV 53   Default = 2000 CFM/943.9 1/s Heating Occupied Heating Setpoint 79 W AV 11   Default = 68°F / 20°C Unoccupied Heating Setpoint 98 W AV 12   Default = 55°F / 12.78°C Morning Warm-up Heating Setpoint 72 W AV 55  Default=70°F / 21.11°C

18 ED15112-12 Network Control Property (Keypad attributes available as BACnet Standard Objects for Description SCC SCC DAC DAC Type Type network control of the unit) Page Object Object Instance Instance Read, Write Read, Write

Network Discharge Air Heating 73 W AV 17 N/A  Default = 100°F / 37.78°C Setpoint Applies only when Htg Reset=Network Max Discharge Air Heating Setpoint 69 W AV 18 N/A  Default = 120°F / 48.89°C Dehumidification Relative Humidity 84 R AI 11   Displays value of optional relative humidity sensor Dew Point Temperature 45 R AV 20   Indicates current calculated dew point Relative Humidity Setpoint 85 W AV 40   Dew Point Setpoint 44 W AV 41   Reheat Capacity 84 R AV 44   0-100% Energy Rec Set-Up Energy Recovery Leaving Air 53 R AI 16   Indicates current value of Energy Recovery Wheel leaving air Temperature temperature sensor Energy Recovery Exhaust Air 54 R AI 17   Indicates current value of Energy Recovery Wheel exhaust air Temperature temperature sensor Energy Recovery Wheel Status 54 R MSV 37   Energy Recovery Wheel On/Off Command Status, 0=Off, 1=On Energy Recovery Wheel Speed 55 R AI 15   Current Energy Recovery Wheel Speed (%) Refrigeration Circuit Suction Refrigerant Pressure 92 R AI 25   Current reading from refrigerant circuit suction pressure sensor. Discharge Refrigerant Pressure 46 R AI 26   Current reading from refrigerant circuit discharge pressure sensor. Discharge Refrigerant Pressure 47 R AI 30   Current reading from circuit 1 refrigerant discharge pressure Circuit 1 sensor. Discharge Refrigerant Pressure 47 R AI 31   Current reading from circuit 2 refrigerant discharge pressure Circuit 2 sensor. Operation Hours Supply Fan Hours 46 W AV 100   Indicates the accumulated supply fan hours of operation Return/Exhaust Fan Hours 88 W AV 101   Indicates the accumulated return or exhaust fan hours of operation Staged Exhaust 1 Hours 91 W AV 102   Indicates the accumulated stage 1 exhaust fan hours of operation Staged Exhaust 2 Hours 92 W AV 103   Indicates the accumulated stage 2 exhaust fan hours of operation Mechanical Cooling Hours 70 W AV 104   Indicates the accumulated mechanical cooling hours of operation Compressor 1 Hours 37 W AV 105   Indicates the accumulated compressor 1 hours of operation Compressor 2 Hours 37 W AV 106   Indicates the accumulated compressor 2 hours of operation Compressor 3 Hours 38 W AV 107   Indicates the accumulated compressor 3 hours of operation Compressor 4 Hours 38 W AV 108   Indicates the accumulated compressor 4 hours of operation Compressor 5 Hours 38 W AV 109   Indicates the accumulated compressor 5 hours of operation Compressor 6 Hours 39 W AV 110   Indicates the accumulated compressor 6 hours of operation Compressor 7 Hours 39 W AV 111   Indicates the accumulated compressor 7 hours of operation Compressor 8 Hours 39 W AV 112   Indicates the accumulated compressor 8 hours of operation Compressor Cooling Hours 40 W AV 113   Indicates the accumulated compressor cooling hours of operation Compressor Heating Hours 40 W AV 114   Indicates the accumulated compressor heating hours of operation Inverter Compressor Hours 64 W AV 115   Indicates the accumulated inverter compressor hours of operation Heating Hours 59 W AV 116   Indicates the accumulated heating hours of operation Economizer Hours 50 W AV 117   Indicates the accumulated economizer hours of operation Tenant Override Hours 95 W AV 118   Indicates the accumulated tenant override hours of operation Dehumidification Hours 44 W AV 119   Indicates the accumulated dehumidification hours of operation

ED15112-12 19 Network Control Property (Keypad attributes available as BACnet Standard Objects for Description SCC SCC DAC DAC Type Type network control of the unit) Page Object Object Instance Instance Read, Write Read, Write

Energy Recovery Wheel Hours 54 W AV 120   Indicates the accumulated energy recovery wheel hours of operation Variable Compressor Hours 99 W AV 121   Indicates the accumulated Variable Compressor hours of operation Setup: IP or MS/TP Receive Heartbeat 83 W AV 43   Default is 0 seconds. This disables this feature. As of Application version 2506017300, this point is no longer used. Unit Support 97 W MSV 16   1 = SI, 2 = English Defrost Set-Up Defrost State 43 W MSV 47   1=Off, 2=Init (Defrost Initialization), 3=Exec (Execute Defrost), 4=Term (Terminate Defrost) Dehum Set-Up Minimum Leaving Coil 71 W AV 56   Default= 45°F/7.22°C Temperature Dehumidification Setpoint Maximum Leaving Coil 69 W AV 57   Default= 52°F/11.11°C Temperature Dehumidification Setpoint Network Variables 1 Outdoor Air Temperature Input 80 W AV 29   Network input of Outdoor Air Temp (–50°F to 150°F, - 45.56°C to 65.56°C ) Default = 327.67 (Null). This parameter reverts to the Null value if written out of range. 1 Space Temperature Input 91 W AV 28   Network input of Space Temp (0°F to 150°F, -17.78°C to 65.56°C ) Default = 327.67 (Null). This parameter reverts to the Null value if written out of range. 1 Occupancy Scheduler Input 77 W   Current State MSV 8 1=Occ, 2=Unocc, 3=TntOvrd (not used), 4=Standby (not Next State used), 5=Auto (default). Time To Next State MSV 9 1=Occ, 2=Unocc, 3=TntOvrd (not used), 4=Standby (not used), 5=Auto (default). AV 3 Default = 65535.0 (Null) 1 Primary Cool Enable 82 W AV 34 & 35   Allows the network to partially or completely disable cooling. Applies only when Ctrl Mode=Auto 1 Primary Heat Enable 82 W AV 36 & 37   Allows the network to partially or completely disable heating. Applies only when Ctrl Mode=Auto 1 Economizer Enable 49 W AV 32 & 33   Allows the network to partially or completely disable economizer functions. 1 Waterflow Switch Input 100 W AV 38   Allows the network to set the waterflow status. 0=No Flow, 1=Flow. 1 Space IAQ Input 90 W AV 31   This input may be set by the network and is used for minimum OA damper control (0-5000 PPM). Default=32767 (Null) 1 Relative Humidity Input 85 W AV 19   Network relative humidity value. Default=163.835 (Null) Outdoor Air Damper Minimum 79 W AV 16   Current OA damper min position setpoint (%) Position Input Applies only when OA Reset=Network Eff Discharge Air Temp Setpoint 51 R AV 39 N/A  This parameter will equal the Effective Heating Discharge Temperature Setpoint if the unit is in the heating state. Otherwise, it will equal the Effective Cooling Discharge Temperature Setpoint. AHU Loc/Net 34 R MSV 38   This parameter is writable via the unit keypad display only. It must be set to Network for most of the writable network properties to apply (applicable parameters in this table denoted with a “ 1” ). 1=Network, 2=Local Active Alarms Clear Alarms 108 W MSV 13   1=None, 2=ClrFlts, 3=ClrPrblms, 4=ClrWrngs, 5=ClrAllAlms Date/Time/Schedules Max Purge Time 68 W AV 58   Default=0 Minutes (0-300 Minutes)

20 ED15112-12 Network Control Property (Keypad attributes available as BACnet Standard Objects for Description SCC SCC DAC DAC Type Type network control of the unit) Page Object Object Instance Instance Read, Write Read, Write

Version Information Application Version 36 R Device *   Read the Application_Software_Version property. This is the version of the software loaded in the MTIII unit controller. Non-Keypad Items Local Space Temperature 65 R AV 4   Current reading of the local sensor Local OA Temperature 65 R AV 5   Current reading of the local sensor Notification Class - Faults 110 W NC 1   Generates notifications for fault alarms. Notification Class - Problems 110 W NC 2   Generates notifications for problem alarms. Notification Class - Warnings 111 W NC 3   Generates notifications for warning alarms. Notification Class - Events 109 W NC 4   Generates notifications for warning alarms. Warning Alarm 115 R AV 24   0=No Active Warnings, 24=Dirty Filter, 28=Airflow Sw, 32=Conductivity, 34=Ret/Exh Fan Warn, 40=LowSuperHtWarn, 50=Over Econo Warning, 52=Under Econo Warning, 54=Excess OA Warning, 56=OAD Stuck Warning Problem Alarm 115 R AV 25   0=No Active Problems, 102=IRT Sensor Problem, 104=ORT Sensor Problem, 106=DRT3 Sensor Problem, 108=DRT2 Sensor Problem, 111= DRT1 Sensor Problem, 114=Variable Comp Problem, 115=LoDischP Problem, 116=LoDischSH Problem, 117=HiDischSH Problem, 119=DFT Sensor Problem, 121=SRT Sensor Problem, 124=High Disch Line Temp, 126=Exp Valve Problem, 128=OAFan Problem, 130=Low Refrig Charge, 131=ChargeLossPrb, 132=PTS Sensor Problem, 133=PTD2 Sensor Problem, 134=PTD or PTD1 Sensor Problem, 135=IFB Comm Problem, 136=Lo Pressure Differential, 137=Waterflow Sw, 140=Water Regulating Valve, 145= Variable Comp Low Oil Problem, 148=High INV Comp Body Temp, 149=INV Comp Body Temp Sensor Problem, 152= Low Pressure–Circuit 8, 153= Low Pressure – Circuit 7, 154=Low Pressure–Circuit 6, 155=Low Pressure – Circuit 5, 156=Low Pressure–Circuit 4, 157=Low Pressure – Circuit 3, 158=Low Pressure–Circuit 2, 159=Low Pressure – Circuit 1, 160=High Pressure–Circuit 8, 161=High Pressure – Circuit 7, 162=High Pressure–Circuit 6, 163=High Pressure – Circuit 5, 164=High Pressure–Circuit 4, 165=High Pressure – Circuit 3, 166=High Pressure – Circuit 2, 167=High Pressure – Circuit 1, 169=Sump Water Level Problem, 179=EFT_LCT Problem, 182=Return Air Sensor Problem, 185=Space Sensor Problem, 188=OAT Sensor Problem, 191=EWT Problem, 194=MAT Problem, 197=Freeze Problem, 199=HeatFail Problem Fault Alarm 117 R AV 26   0=No Active Faults, 208=Airflow Fault, 212=Low Discharge Air Temp, 216=High Discharge Air Temp , 220=High Return Air Temp, 224=Duct High Limit, 228=Discharge Sensor Fail, 244=Control Temp Fault, 250=Emergency Stop Fault, 252=Freeze Fault Alarm Value 112 R AV 27   0=No Active Warnings, 24=Dirty Filter, 28=Airflow Sw, 32=Conductivity, 34=Ret/Exh Fan Warn, 40=LowSuperHtWarn, 50=Over Econo Warning, 52=Under Econo Warning, 54=Excess OA Warning, 56=OAD Stuck Warning, 102=IRT Sensor Problem, 104=ORT Sensor Problem, 106=DRT3 Sensor Problem, 108=DRT2 Sensor Problem, 111= DRT1 Sensor Problem, 114=Variable Comp Problem, 115=LoDischP Problem, 116=LoDischSH Problem, 117=HiDischSH Problem, 119=DFT Sensor Problem, 121=SRT Sensor Problem, 124=High Disch Line Temp, 126=Exp Valve Problem, 128=OAFan Problem, 130=Low Refrig Charge, 131=ChargeLossPrb, 132=PTS Sensor Problem, 133=PTD2 Sensor Problem, 134=PTD or PTD1 Sensor Problem, 135=IFB Comm Problem, 136=Lo Pressure Differential, 137=Waterflow Sw, 140=Water Regulating Valve, 145=Var Comp Low Oil Problem, 148=High INV Comp Body Temp, 149=INV Comp Body Temp Sensor Problem, 152= Low Pressure–Circuit 8, 153= Low Pressure – Circuit 7,

ED15112-12 21 Network Control Property (Keypad attributes available as BACnet Standard Objects for Description SCC SCC DAC DAC Type Type network control of the unit) Page Object Object Instance Instance Read, Write Read, Write

154=Low Pressure–Circuit 6, 155=Low Pressure – Circuit 5, 156=Low Pressure–Circuit 4, 157=Low Pressure – Circuit 3, 158=Low Pressure–Circuit 2, 159=Low Pressure – Circuit 1, 160=High Pressure–Circuit 8, 161=High Pressure – Circuit 7, 162=High Pressure–Circuit 6, 163=High Pressure – Circuit 5, 164=High Pressure–Circuit 4, 165=High Pressure – Circuit 3, 166=High Pressure–Circuit 2, 167=High Pressure – Circuit 1, 169=Sump Water Level Problem, 179=EFT_LCT Problem, 182=Return Air Sensor Problem, 185=Space Sensor Problem, 188=OAT Sensor Problem, 191=EWT Problem, 194=MAT Problem, 197=Freeze Problem, 199=HeatFail Problem, 208=Airflow Fault, 212=Low Discharge Air Temp, 216=High Discharge Air Temp , 220=High Return Air Temp, 224=Duct High Limit, 228=Discharge Sensor Fail, 244=Control Temp Fault, 250=Emergency Stop Fault, 252=Freeze Fault Alarm Binary Indications Airflow Fault 117 R BV 27   0=Normal, 1=Alarm Airflow Switch Warning 118 R BV 2   0=Normal, 1=Alarm Conductivity Warning 118 R BV 3   0=Normal, 1=Alarm Control Temp Fault 119 R BV 28   0=Normal, 1=Alarm Dirty Filter Warning 119 R BV 4   0=Normal, 1=Alarm Discharge Sensor Fault 119 R BV 29   0=Normal, 1=Alarm Duct High Limit Fault 120 R BV 30   0=Normal, 1=Alarm Emergency Off Fault 120 R BV 31   0=Normal, 1=Alarm Entering Fan Temp / Leaving Coil 120 R BV 5   0=Normal, 1=Alarm Temp Problem Entering Water Temp Problem 121 R BV 6   0=Normal, 1=Alarm Freeze Fault 122 R BV 32   0=Normal, 1=Alarm Freeze Problem 122 R BV 7   0=Normal, 1=Alarm Heat Fail Problem 123 R BV 38   0=Normal, 1=Alarm High Discharge Temp Fault 124 R BV 33   0=Normal, 1=Alarm High Pressure Circuit 1 Problem 125 R BV 8   0=Normal, 1=Alarm High Pressure Circuit 2 Problem 125 R BV 9   0=Normal, 1=Alarm High Pressure Circuit 3 Problem 126 R BV 10   0=Normal, 1=Alarm High Pressure Circuit 4 Problem 126 R BV 11   0=Normal, 1=Alarm High Pressure Circuit 5 Problem 126 R BV 12   0=Normal, 1=Alarm High Pressure Circuit 6 Problem 127 R BV 13   0=Normal, 1=Alarm High Pressure Circuit 7 Problem 127 R BV 52   0=Normal, 1=Alarm High Pressure Circuit 8 Problem 127 R BV 53   0=Normal, 1=Alarm High Return Temp Fault 129 R BV 34   0=Normal, 1=Alarm Low Discharge Temp Fault 131 R BV 35   0=Normal, 1=Alarm Low Pressure Circuit 1 Problem 131 R BV 14   0=Normal, 1=Alarm Low Pressure Circuit 2 Problem 132 R BV 15   0=Normal, 1=Alarm Low Pressure Circuit 3 Problem 132 R BV 16   0=Normal, 1=Alarm Low Pressure Circuit 4 Problem 133 R BV 17   0=Normal, 1=Alarm Low Pressure Circuit 5 Problem 133 R BV 18   0=Normal, 1=Alarm Low Pressure Circuit 6 Problem 133 R BV 19   0=Normal, 1=Alarm Low Pressure Circuit 7 Problem 134 R BV 50   0=Normal, 1=Alarm Low Pressure Circuit 8 Problem 134 R BV 51   0=Normal, 1=Alarm Mixed Air Temp Problem 136 R BV 20   0=Normal, 1=Alarm Outdoor Temp Problem 137 R BV 21   0=Normal, 1=Alarm Return Temp Problem 138 R BV 22   0=Normal, 1=Alarm

22 ED15112-12 Network Control Property (Keypad attributes available as BACnet Standard Objects for Description SCC SCC DAC DAC Type Type network control of the unit) Page Object Object Instance Instance Read, Write Read, Write

Space Temp Problem 139 R BV 23   0=Normal, 1=Alarm Sump Water Level Problem 139 R BV 24   0=Normal, 1=Alarm Waterflow Switch Problem 140 R BV 25   0=Normal, 1=Alarm Water Regulating Valve Problem 141 R BV 26   0=Normal, 1=Alarm Airflow Switch (Fault) 35 R BI 1   0=Closed, 1=Open High Pressure Problem 128 R BI 32   0=Normal, 1=Alarm Low Pressure Problem 135 R BI 33   0=Normal, 1=Alarm Inverter Compressor Problem 129 R BI 34   0=Normal, 1=Alarm High Discharge Line Temperature 123 R BI 35   0=Normal, 1=Alarm Problem Outdoor Fan Problem 137 R BI 36   0=Normal, 1=Alarm Interface Board Communication 129 R BI 38   0=Normal, 1=Alarm Problem Low Pressure Differential Problem 135 R BI 39   0=Normal, 1=Alarm Expansion Valve Problem 121 R BI 40   0=Normal, 1=Alarm Charge Loss Problem 118 R BI 41   0=Normal, 1=Alarm Return/Exhaust Fan Warning 138 R BI 42   0=Normal, 1=Alarm High Inverter Compressor Body 124 R BI 43   0=Normal, 1=Alarm Temp Problem Low Superheat Warning 136 R BI 46   0=Normal, 1=Alarm Binary Inputs Airflow Swich (Warning) 36 R BI 2   0=Open, 1=Closed Dirty Filter Switch 45 R BI 3   0=Open, 1=Closed High Pressure Circuit 1 Switch 60 R BI 4   0=Open, 1=Closed High Pressure Circuit 2 Switch 60 R BI 5   0=Open, 1=Closed High Pressure Circuit 3 Switch 61 R BI 6   0=Open, 1=Closed High Pressure Circuit 4 Switch 61 R BI 7   0=Open, 1=Closed High Pressure Circuit 5 Switch 61 R BI 8   0=Open, 1=Closed High Pressure Circuit 6 Switch 62 R BI 9   0=Open, 1=Closed High Pressure Circuit 7 Switch 62 R BI 26   0=Open, 1=Closed High Pressure Circuit 8 Switch 63 R BI 27   0=Open, 1=Closed Low Pressure Circuit 1 Switch 65 R BI 10   0=Open, 1=Closed Low Pressure Circuit 2 Switch 66 R BI 11   0=Open, 1=Closed Low Pressure Circuit 3 Switch 66 R BI 12   0=Open, 1=Closed Low Pressure Circuit 4 Switch 66 R BI 13   0=Open, 1=Closed Low Pressure Circuit 5 Switch 67 R BI 14   0=Open, 1=Closed Low Pressure Circuit 6 Switch 67 R BI 15   0=Open, 1=Closed Low Pressure Circuit 7 Switch 68 R BI 24   0=Open, 1=Closed Low Pressure Circuit 8 Switch 68 R BI 25   0=Open, 1=Closed Sump Pump Water Level Switch 93 R BI 16   0=Open, 1=Closed Water Flow Switch 100 R BI 17   0=Open, 1=Closed Water Regulating Valve 100 R BI 18   0=Normal, 1=Alarm Freeze Switch (Fault) 57 R BI 19   0=Open, 1=Closed Freeze Switch (Problem) 58 R BI 20   0=Open, 1=Closed Duct High Limit Switch 48 R BI 21   0=Open, 1=Closed Emergency Off Switch 52 R BI 22   0=Open, 1=Closed Heat Fail Input 58 R BI 23   0=Normal, 1=Alarm Variable Compressor Problem 140 R BI 47   0=Normal, 1=Alarm Low Discharge Pressure Problem 130 R BI 48   0=Normal, 1=Alarm

ED15112-12 23 Network Control Property (Keypad attributes available as BACnet Standard Objects for Description SCC SCC DAC DAC Type Type network control of the unit) Page Object Object Instance Instance Read, Write Read, Write

Low Discharge Superheat Problem 130 R BI 49   0=Normal, 1=Alarm High Discharge Superheat Problem 124 R BI 50   0=Normal, 1=Alarm Variable Compressor Oil Status 99 R BI 51   0=Normal, 1=Alarm Event Binary Indications High Pressure Unload Event 128 R BI 52   0=Inactive, 1=Active Low Discharge Pressure Unload 130 R BI 53   0=Inactive, 1=Active Event Variable Compressor Emergency 140 R BI 54   0=Inactive, 1=Active Stop Event High Discharge Line Temperature 123 R BI 55   0=Inactive, 1=Active Unload Event Low Discharge Superheat Unload 131 R BI 56   0=Inactive, 1=Active Event High Discharge Superheat Unload 124 R BI 57   0=Inactive, 1=Active Event Reheat Stage Limited Event 138 R BI 58   0=Inactive, 1=Active Oil Boost Event 137 R BI 59   0=Inactive, 1=Active File Objects BACnet Client Config File 143 N/A File 1   This file contains the BACnet client configuration. For this application, the controller acts as a server, so this file does not apply. BACnet COV Config File 143 N/A File 2   This file contains the BACnet COV configuration. Error Log File 143 N/A File 3   This is the error log file for the BACnet module. History Log File 143 N/A File 4   This is the history log file for the BACnet module. BACnet Event Enrollment Config 144 N/A File 5   This is the BACnet Event Enrollment Configuration file. File EDE File 144 N/A File 6   This is the engineering data exchange file of this controller. This file details the BACnet interface of the controller. It tells you what points are available and information about each point. EDE File – State Text 144 N/A File 7   This is the engineering data exchange file of this controller with state text. 1 MSV 38 (AHU Loc/Net) must be set to Network (1) for this property to apply. AHU Loc/Net is changeable only via the keypad display.

Note: Objects that appear in multiple locations on the keypad are only listed in the location they first appear on the keypad. Not all menus and items shown here will appear on keypad depending upon the specific unit configuration. Those that do not appear are not applicable to the unit.

24 ED15112-12 LON WORKS Variables Network Control Property Keypad attributes available as SNVT/SCPT LON WORKS Variables for network Page Variable Name SCC DAC Description control of the unit Index

System Unit State 96 nvoUnitStatus 112   Mode 0=AUTO, 1=HEAT, , 3=COOL, 6=OFF, 9=FAN_ONLY, 10=FREE_COOL, 0XFF=NUL Daikin Applied AHU Unit Status 69 nvoMcQAHUStatus N/A   Mode: 0=Enabled, 1=OffManCtrl, 2=OffMan, 3=OffNet, 4=OffAlm, 5=OffFanRetry Cooling Status 42 nvoMcQAHUStatus N/A   0=Enabled, 1=None, 2=Off Amb, 3=Off Alarm, 4=Off Net, 5=Off Man Heating Status 59 nvoMcQAHUStatus N/A   0=Enabled, 1=None, 2=Off Amb, 3=Off Alarm (Not Used), 4=Off Net, 5=Off Man Economizer Status 50 nvoMcQAHUStatus N/A   0=Enabled, 1=None, 2=Off Amb, 3=Off Alarm (Not Used), 4=Off Net, 5=Off Man Cooling Capacity 42 nvoUnitStatus 112   nvoUnitStatus.cool_output(%) Heating Capacity 57 nvoUnitStatus 112   nvoUnitStatus.heat_output_primary(%) Supply Fan Capacity 91 nvoUnitStatus 112   Fan_Output Current supply fan capacity (%) Return/Exhaust Fan Capacity 88 nvoExhFanStatus 95   Current return or exhaust fan capacity (%) Economizer Capacity 49 nvoUnitStatus 112   Economizer_Output Feedback value (%) Emergency Override 53 nviEmergOverride 103   0=NORMAL, 4=SHUTDOWN, 0xFF=NUL (other states not used) Application Mode 34 nviApplicMode 108   0=AUTO, 1=HEAT, 3=COOL, 6=OFF, 9=FAN_ONLY (other states not used) Occupancy Occupancy 75 nvoEffectOccup 109   0=OCCUPIED, 1=UNOCCUPIED, 2=BYPASS, 3=STANDBY, 0xFF=NUL Occupancy Mode 76 nviOccManCmd 109   0=OCCUPIED, 1=UNOCCUPIED, 2= BYPASS, 3=STANDBY, 0xFF=NUL Temperature Discharge Air Temperature 45 nvoDischAirTemp 105   Current reading of sensor Return Air Temperature 87 nvoRATemp 105   Current reading of sensor Space Temperature 90 nvoSpaceTemp 105   Current reading of sensor Outdoor Air Temperature 80 nvoOutdoorTemp 105   Current reading of sensor Entering Fan / Leaving Coil Temp 53 nvoEFT_LCT 105   Current value of sensor Entering Water Temperature 55 nvoCWTemp 105   Current value of sensor Mixed Air Temperature 72 nvoMATemp 105 N/A  Current value of sensor Mixed Air Temperature 72 nvoMixedAirTemp 105  N/A Current value of sensor Flow Summary Return/Exhaust Fan Status 88 nvoExhFanStatus 95   State: 0=Off, 1=On , -1(0xFF)=Undefined VAV Box Output 98 nvoVAVBoxOut N/A N/A  0=Heat (Off), 1=Cool (On) SAF Spd Control Duct Static Pressure 46 nvoDuctStatPress 113 N/A  Current reading of sensor. If unit has two sensors the lower of the two is displayed Duct Static Pressure Setpoint 49 nviDuctStaticSP 113 N/A  Default = 1.00” WC Remote Supply Fan Cap Control Flag 86 nviSupFanCtrl N/A  0=Duct Press, 1=Speed, 2=1ZnVAV, 4=BSP, 5=CO2, 6=CFM Supply Fan Capacity Input 94 nviSupFanCap 81 N/A  Default = 25% Sets the discharge air VFD speed when Supply Fan Capacity Control Flag is set to Speed RF/EF Spd Control Building Static Pressure 36 nvoBldgStatPress 113   Current reading of sensor value Building Static Pressure Setpoint 37 nviBldgStaticSP 113   Default = 0.050” WC Remote Return/Exhaust Fan Cap 86 nviExhRetFanCtrl N/A   0=None, 1=Tracking, 2=Bldg Press, 3=Speed, Control Flag 4=OAD Return Fan Capacity Input 89 nviRetFanCap 81  

ED15112-12 25 Network Control Property Keypad attributes available as SNVT/SCPT LON WORKS Variables for network Page Variable Name SCC DAC Description control of the unit Index

Exhaust Fan Capacity Input 56 nviExhFanCap 81   Cooling Occupied Cooling Setpoint 78 nciSetpoints 106/60   Occupied_Cool Default = 72°F / 22.22°C SCPTsetPnts Unoccupied Cooling Setpoint 97 nciSetpoints 106/60   Unnoccupied_Cool Default = 85°F / 29.44°C SCPTsetPnts Discharge Air Cooling Setpoint 73 nviDAClSP 105 N/A  Default = 55°F (32-86°F) / 12.78°C Minimum Discharge Air Cooling 71 nciDAClSP 105 N/A  Used to set the discharge air cooling setpoint via Setpoint the network. Condensing Conductivity 40 nvoConductivity N/A   This variable provides the conductivity of the water in the sump of an evaporative cooled condenser. Min OA Damper

Space CO 2 90 nvoSpaceCO2 29   0-5000ppm Outdoor Airflow 81 nvoOAFlow 15   Heating Occupied Heating Setpoint 79 nciSetpoints 106/60   Occupied_Heat Default = 68°F / 20°C SCPTsetPnts Unoccupied Heating Setpoint 98 nciSetpoints 106/60   Unoccupied_Heat Default = 55°F / 12.78°C SCPTsetPnts Discharge Air Heating Setpoint 73 nviDAHtSP 105 N/A  Default = 100°F (50-158°F) / 37.78°C Maximum Discharge Air Heating 69 nciDAHtSP 184 N/A  Setpoint Dehumidification Relative Humidity 84 nvoSpaceRH 81   Value of optional relative humidity sensor or network input Dew Point Temperature 44 nvoSpaceDewPt 105   Indicates current calculated dew point (calculated from Relative Humidity) Relative Humidity Setpoint 85 nviSpaceDehumSP 81   Dew Point Setpoint 44 nviSpaceDewPtSP 105   Reheat Capacity 84 nvoUnitStatus 112   nvoUnitStatus.heat_output_secondary(%) LON WORKS Setup Receive Heartbeat 83 nciRcvHrtBt 107/48   Default is 0 seconds SCPTmaxRcvTime Send Heartbeat 89 nciSndHrtBt 107/49   Default is 60 seconds SCPTmaxSendTime Network Variables Outdoor Air Temperature Input 80 nviOutdoorTemp 105   Network input of Outdoor Air Temp (–10°C to 50°C) Space Temperature Input 91 nviSpaceTemp 105   Network input of Space Temp (–10°C to 50°C) Occupancy Scheduler Input 77 nviOccSchedule 128   Network schedule Primary Cool Enable 81 nviPriCoolEnable 95   Enables or disables cooling via two properties: State=0, cooling disabled State=1 and Value=0, cooling disabled State=1 and Value>0, cooling enabled State=-1, network is not cooling economizer Primary Heat Enable 82 nviPriHeatEnable 95   Enables or disables heating via two properties: State=0, heating disabled State=1 and Value=0, heating disabled State=1 and Value>0, heating enabled State=-1, network is not effecting heating Economizer Enable 49 nviEconEnable 95   Enables or disables economizer via two properties: State=0, economizer disabled State=1 and Value=0, economizer disabled

26 ED15112-12 Network Control Property Keypad attributes available as SNVT/SCPT LON WORKS Variables for network Page Variable Name SCC DAC Description control of the unit Index

State=1 and Value>0, economizer enabled State=-1, network is not effecting economizer Waterflow Switch Input 100 nviCWFlow 95   Space IAQ Input 90 nviSpaceIAQ 29   This input may be set by the network and is used for minimum OA damper control (0-5000 PPM). Relative Humidity Input 85 nviSpaceRH 81   Network input Temperature Setpoint Input 95 nviSetpoint 105   Adjusts effective heat enable and effective cool enable setpoint via the network. Effective Heat SP = nviSetpoint – 0.5 (Occupied_Cool – Occupied_Heat). Effective Cool SP = nviSetpoint + 0.5 (Occupied_Cool – Occupied_Heat). Outdoor Air Damper Minimum 79 nviOAMinPos 81   Current OA damper min position setpoint (%) Position Input Effective Enable Setpoint 52 nvoEffectSetpt 105   Current enable setpoint which the unit will use. HVAC Unit Type Identifier 60 nciHvacType 145/169  N/A Equipment Type = HVT_GENERIC (Read SCPThvacType Only) Active Alarms Clear Alarms 108 nviClearAlarms N/A   0=None, 1=Clear All Faults, 2=Clear All Problems, 3=Clear All Warnings, 4=Clear All Alarms Non-Keypad Variables Local Space Temperature 65 nvoLocalSpaceTmp 105   Current reading of the local space sensor Local OA Temperature 63 nvoLocalOATemp 105   Current reading of the local outdoor air temperature sensor Effective Discharge Setpoint 51 nvoEffDATempSp 105 N/A  Current discharge air setpoint which the unit will use. Minimum Send Time 71 nciMinOutTm 107/52   Defines min period of time between automatic SCPTminSendTime network variable output time (reducing traffic on network) Warning Alarm 115 nvoWarnAlarm N/A   0=No Active Warnings, 24=Dirty Filter, 28=Airflow Sw, 32=Conductivity, 34=Ret/Exh Fan Warn, 40=LowSuperHtWarn, 50=Over Econo Warning, 52=Under Econo Warning, 54=Excess OA Warning, 56=OAD Stuck Warning Problem Alarm 115 nvoProbAlarm N/A   0=No Active Problems, 102=IRT Sensor Problem, 104=ORT Sensor Problem, 106=DRT3 Sensor Problem, 108=DRT2 Sensor Problem, 111= DRT1 Sensor Problem, 114=Variable Comp Problem, 115=LoDischP Problem, 116=LoDischSH Problem, 117=HiDischSH Problem, 119=DFT Sensor Problem, 121=SRT Sensor Problem, 124=High Disch Line Temp, 126=Exp Valve Problem, 128=OAFan Problem, 130=Low Refrig Charge, 131=ChargeLossPrb, 132=PTS Sensor Problem, 133=PTD2 Sensor Problem, 134=PTD or PTD1 Sensor Problem, 135=IFB Comm Problem, 136=Lo Pressure Differential, 137=Waterflow Sw, 140=Water Regulating Valve, 145= Variable Comp Oil Problem, 148=High INV Comp Body Temp, 149=INV Comp Body Temp Sensor Problem, 152= Low Pressure–Circuit 8, 153= Low Pressure – Circuit 7, 154=Low Pressure–Circuit 6, 155=Low Pressure – Circuit 5, 156=Low Pressure–Circuit 4, 157=Low Pressure – Circuit 3, 158=Low Pressure–Circuit 2, 159=Low Pressure – Circuit 1, 160=High Pressure–Circuit 8, 161=High Pressure – Circuit 7, 162=High Pressure–Circuit 6, 163=High Pressure – Circuit 5, 164=High Pressure–Circuit 4, 165=High Pressure – Circuit 3, 166=High Pressure – ED15112-12 27 Network Control Property Keypad attributes available as SNVT/SCPT LON WORKS Variables for network Page Variable Name SCC DAC Description control of the unit Index

Circuit 2, 167=High Pressure – Circuit 1, 169=Sump Water Level Problem, 179=EFT_LCT Problem, 182=Return Air Sensor Problem, 185=Space Sensor Problem, 188=OAT Sensor Problem, 191=EWT Problem, 194=MAT Problem, 197=Freeze Problem, 199=HeatFail Problem Fault Alarm 117 nvoFaultAlarm N/A   0=No Active Faults, 208=Airflow Fault, 212=Low Discharge Air Temp, 216=High Discharge Air Temp , 220=High Return Air Temp, 224=Duct High Limit, 228=Discharge Sensor Fail, 244=Control Temp Fault, 250=Emergency Stop Fault, 252=Freeze Fault Alarm Value 112 nvoUnitStatus 112   0=No Active Warnings, 24=Dirty Filter, 28=Airflow Sw, 32=Conductivity, 34=Ret/Exh Fan Warn, 40=LowSuperHtWarn, 50=Over Econo Warning, 52=Under Econo Warning, 54=Excess OA Warning, 56=OAD Stuck Warning, 102=IRT Sensor Problem, 104=ORT Sensor Problem, 106=DRT3 Sensor Problem, 108=DRT2 Sensor Problem, 111= DRT1 Sensor Problem, 114=Variable Comp Problem, 114=Variable Comp Problem, 115=LoDischP Problem, 116=LoDischSH Problem, 117=HiDischSH Problem, 119=DFT Sensor Problem, 121=SRT Sensor Problem, 124=High Disch Line Temp, 126=Exp Valve Problem, 128=OAFan Problem, 130=Low Refrig Charge, 131=ChargeLossPrb, 132=PTS Sensor Problem, 133=PTD2 Sensor Problem, 134=PTD or PTD1 Sensor Problem, 135=IFB Comm Problem, 136=Lo Pressure Differential, 137=Waterflow Sw, 140=Water Regulating Valve, 145=Var Comp Low Oil Problem, 148=High INV Comp Body Temp, 149=INV Comp Body Temp Sensor Problem, 152= Low Pressure–Circuit 8, 153= Low Pressure – Circuit 7, 154=Low Pressure–Circuit 6, 155=Low Pressure – Circuit 5, 156=Low Pressure–Circuit 4, 157=Low Pressure – Circuit 3, 158=Low Pressure–Circuit 2, 159=Low Pressure – Circuit 1, 160=High Pressure–Circuit 8, 161=High Pressure – Circuit 7, 162=High Pressure–Circuit 6, 163=High Pressure – Circuit 5, 164=High Pressure–Circuit 4, 165=High Pressure – Circuit 3, 166=High Pressure–Circuit 2, 167=High Pressure – Circuit 1, 169=Sump Water Level Problem, 179=EFT_LCT Problem, 182=Return Air Sensor Problem, 185=Space Sensor Problem, 188=OAT Sensor Problem, 191=EWT Problem, 194=MAT Problem, 197=Freeze Problem, 199=HeatFail Problem, 208=Airflow Fault, 212=Low Discharge Air Temp, 216=High Discharge Air Temp, 220=High Return Air Temp, 224=Duct High Limit, 228=Discharge Sensor Fail, 244=Control Temp Fault, 250=Emergency Stop Fault, 252=Freeze Fault Object Status 74 nvoStatus 92   This variable is part of the Node Object and reports the status of the requested functional block in the device. Object Request 73 nviRequest 93   This variable is part of the Node Object and requests a particular mode for a particular functional block in the device. Only the required RQ_NORMAL, RP_UPDATE_STATUS AND RQ_REPORT_MASK are implemented.

28 ED15112-12 Note: Objects that appear in multiple locations on the keypad are only listed in the location they first appear on the keypad. Not all menus and items shown here will appear on keypad depending upon the specific unit configuration. Those that do not appear are not applicable to the unit.

ED15112-12 29 Detailed Data Point Information

The data points or properties (attributes) defined in this section reference data that is generated in the MicroTech III Unit Controller. Refer to Table 4 below for a summary of data points by rooftop or self-contained model type, followed by a detailed description of each data point.

Note: Data points are referred to as “properties” in the BACnet protocol and “network variables” or “configuration parameters” in the LON WORKS protocol. In this document, the text refers to this information as a “data point.” In general, the data point is applicable to both BACnet and LON WORKS . When a data point is specific to the BACnet protocol, the text refers to a “property.” When a data point is specific to the LON WORKS protocol, the text refers to a “network variable” or “configuration parameter.”

Table 4. Data Points by MicroTech III Rooftop/Self-Contained Model

MicroTech III Rooftop/Self-Contained Unit RPE, RDE, RPS, RDT, RFS, SWT, SWP DPS MPS Controller Data Point RDS and RAH Self-Contained Rebel Maverick II Applied Rooftop Commercial Commercial Rooftop Rooftop Unit State X X X X Daikin Applied AHU Unit Status X X X X Dehumidification Status X X X Cooling Status X X X X Heating Status X X X X Supplemental Heating Status X Economizer Status X X X X Cooling Capacity X X X X Heating Capacity X X X X Supplemental Heating Capacity X Supply Fan Capacity X X X X Return/Exhaust Fan Capacity X X X X Economizer Capacity X X X X Emergency Override X X X X Application Mode 1 X X X X Occupancy X X X X Occupancy Mode X X X X Control Temperature X X X X Discharge Air Temperature X X X X Return Air Temperature X X X X Space Temperature X X X X Outdoor Air Temperature X X X X Entering Fan / Leaving Coil Temp X X X Entering Water Temperature X Mixed Air Temperature X Discharge Line Temperature 1 X X Discharge Line Temperature 2 X Discharge Line Temperature 3 X Defrost Temperature X Suction Line Refrigerant Temperature X Indoor Refrigerant Temperature X Outdoor Refrigerant Temperature X Inverter Compressor Body Temperature X Exhaust Fan Status X X X VAV Box Output X X X X Duct Static Pressure X X X X Duct Static Pressure Setpoint X X X X Remote Supply Fan Capacity Control Flag X X X X Supply Fan Capacity Input 1 X X X X Building Static Pressure X X X Building Static Pressure Setpoint X X X

30 ED15112-12 MicroTech III Rooftop/Self-Contained Unit RPE, RDE, RPS, RDT, RFS, SWT, SWP DPS MPS Controller Data Point RDS and RAH Self-Contained Rebel Maverick II Applied Rooftop Commercial Commercial Rooftop Rooftop Remote Return/Exhaust Fan Capacity Control Flag X X X Return Fan Capacity Input 1 X Exhaust Fan Capacity Input 1 X X X Occupied Cooling Setpoint X X X X Unoccupied Cooling Setpoint X X X X Network Discharge Air Cooling Setpoint X X X X Min Discharge Air Cooling Setpoint X X X X Control Temp Source X X X X Conductivity X

Space CO 2 X X X X Outdoor Airflow X X X X Outdoor Airflow Setpoint X X X X Occupied Heating Setpoint X X X X Unoccupied Heating Setpoint X X X X Morning Warm-up Heating Setpoint X X X X Network Discharge Air Heating Setpoint X X X X Max Discharge Air Heating Setpoint X X X X Relative Humidity X X X X Dew Point Temperature X X X X Relative Humidity Setpoint X X X Dew Point Setpoint X X X Reheat Capacity X X X Energy Recovery Leaving Air Temperature X X X Energy Recovery Exhaust Air Temperature X X X Energy Recovery Wheel Status X X X Energy Recovery Wheel Speed X X Suction Refrigerant Pressure X X Discharge Refrigerant Pressure X Supply Fan Hours X X X X Return/Exhaust Fan Hours X X X X Staged Exhaust 1 Hours X X Staged Exhaust 2 Hours X X Mechanical Cooling Hours X X X X Compressor 1 Hours X X X Compressor 2 Hours X X X Compressor 3 Hours X X X X Compressor 4 Hours X X X Compressor 5 Hours X X X Compressor 6 Hours X X X Compressor 7 Hours X X Compressor 8 Hours X X Compressor Cooling Hours X Compressor Heating Hours X Inverter Compressor Hours X Variable Compressor Hours X Heating Hours X X X X Economizer Hours X X X X Tenant Override Hours X X X X Dehumidification Hours X X X Energy Recovery Wheel Hours X X X Receive Heartbeat X X X X Unit Support X X X X Defrost State X Minimum Leaving Coil Temperature Dehum Setpoint X X X Maximum Leaving Coil Temperature Dehum Setpoint X X Outdoor Air Temperature Input X X X X Space Temperature Input X X X X

ED15112-12 31 MicroTech III Rooftop/Self-Contained Unit RPE, RDE, RPS, RDT, RFS, SWT, SWP DPS MPS Controller Data Point RDS and RAH Self-Contained Rebel Maverick II Applied Rooftop Commercial Commercial Rooftop Rooftop Occupancy Scheduler Input X X X X Current State X X X X Next State X X X X X X Time To Next State X X Primary Cool Enable X X X X Primary Heat Enable X X X X Economizer Enable X X X X Waterflow Switch Input X Space IAQ Input X X X X Relative Humidity Input X X X X Outdoor Air Damper Minimum Position Input X X X X Eff Discharge Air Temp Setpoint X X X X AHU Loc/Net X X X X Clear Alarms X X X X Max Purge Time X X X X Application Version X X X X Local Space Temperature X X X X Local OA Temperature X X X X Notification Class - Faults X X X X Notification Class - Problems X X X X Notification Class - Warnings X X X X Notification Class - Events X X X X Warning Alarm X X X X Problem Alarm X X X X Fault Alarm X X X X Alarm Value X X X X Airflow Fault X X X X Airflow Switch Warning X X X X Conductivity Warning X Control Temp Fault X X X X Dirty Filter Warning X X X X Discharge Sensor Fault X X X X Duct High Limit Fault X X X X Emergency Off Fault X X X X Entering Fan Temp / Leaving Coil Temp Problem X X X Entering Water Temp Problem X Freeze Fault X X X X Freeze Problem X X X X Heat Fail Problem X High Discharge Temp Fault X X X X High Pressure Circuit 1 Problem X X X High Pressure Circuit 2 Problem X X X High Pressure Circuit 3 Problem X High Pressure Circuit 4 Problem X High Pressure Circuit 5 Problem X High Pressure Circuit 6 Problem X High Pressure Circuit 7 Problem X High Pressure Circuit 8 Problem X High Return Temp Fault X X X X Low Discharge Temp Fault X X X X Low Pressure Circuit 1 Problem X X X Low Pressure Circuit 2 Problem X X X Low Pressure Circuit 3 Problem X Low Pressure Circuit 4 Problem X Low Pressure Circuit 5 Problem X Low Pressure Circuit 6 Problem X

32 ED15112-12 MicroTech III Rooftop/Self-Contained Unit RPE, RDE, RPS, RDT, RFS, SWT, SWP DPS MPS Controller Data Point RDS and RAH Self-Contained Rebel Maverick II Applied Rooftop Commercial Commercial Rooftop Rooftop Low Pressure Circuit 7 Problem X Low Pressure Circuit 8 Problem X Mixed Air Temp Problem X Outdoor Temp Problem X X X X Return Temp Problem X X X X Space Temp Problem X X X X Sump Water Level Problem X Waterflow Switch Problem X Water Regulating Valve Problem X Airflow Switch (Fault) X X X X Expansion Valve Problem X High Discharge Line Temperature Problem X High Pressure Problem X Low Pressure Problem X Interface Board Communication Problem X Inverter Compressor Problem X Low Pressure Differential Problem X Low Refrigerant Charge Problem X Outdoor Fan Problem X Charge Loss Problem X Return/Exhaust Fan Warning X X X High Inverter Compressor Body Temp Problem X Low Superheat Warning X Airflow Swich (Warning) X X X X Dirty Filter Switch X X X X High Pressure Circuit 1 Switch X X X High Pressure Circuit 2 Switch X X X High Pressure Circuit 3 Switch X High Pressure Circuit 4 Switch X High Pressure Circuit 5 Switch X High Pressure Circuit 6 Switch X High Pressure Circuit 7 Switch X High Pressure Circuit 8 Switch X Low Pressure Circuit 1 Switch X X X Low Pressure Circuit 2 Switch X X X Low Pressure Circuit 3 Switch X Low Pressure Circuit 4 Switch X Low Pressure Circuit 5 Switch X Low Pressure Circuit 6 Switch X Low Pressure Circuit 7 Switch X Low Pressure Circuit 8 Switch X Sump Pump Water Level Switch X Water Flow Switch X Water Regulating Valve X Freeze Switch (Fault) X X X X Freeze Switch (Problem) X X X X Duct High Limit Switch X X X X Emergency Off Switch X X X X Heat Fail Input X Variable Compressor Oil Status X Low Discharge Pressure Problem X Low Discharge Superheat Problem X High Discharge Superheat Problem X High Pressure Unload Event X Low Discharge Pressure Unload Event X Variable Compressor Emergency Stop Event X High Discharge Line Temperature Unload Event X

ED15112-12 33 MicroTech III Rooftop/Self-Contained Unit RPE, RDE, RPS, RDT, RFS, SWT, SWP DPS MPS Controller Data Point RDS and RAH Self-Contained Rebel Maverick II Applied Rooftop Commercial Commercial Rooftop Rooftop Low Discharge Superheat Unload Event X High Discharge Superheat Unload Event X Reheat Stage Limited Event X Oil Boost Event X BACnet Client Config File X1 X1 X1 X1 BACnet COV Config File X1 X1 X1 X1 Error Log File X1 X1 X1 X1 History Log File X1 X1 X1 X1 BACnet Event Enrollment Config File X1 X1 X1 X1 EDE File X1 X1 X1 X1 EDE File – State Text X1 X1 X1 X1 1 These points only apply for BACnet firmware version 9.26 or higher.

AHU Loc/Net Keypad Menu Path Main Menu\BMS Communications\BACnet MSTP Set-Up\AHU Loc/Net= Main Menu\BMS Communications\BACnet IP Set-Up\AHU Loc/Net= This read only attribute indicates whether the unit controller is set to use local or network inputs. AHU Loc/Net is only changeable at the keypad/display.

Measurement Units Data Type Valid Range Uses Heartbeat Default Value State N/A BACnet: Unsigned Enumerated N/A Network

BACnet Object Identifier Property Object Type Type ID Instance Name ID Multistate Value 19 38 Present_Value 85 Full Reference .AHULoc/Net.Present_Value Enumeration 1 = Network 2 = Local

LonWorks No LONWORKS equivalent.

Application Mode Keypad Menu Path Main Menu\View/Set Unit\Unit Status/Settings\Net App Mode= This read/write attribute sets the unit in an application mode (auto, off, heat only, cool only, fan only, or dehumidification). Application Mode does not "force" the unit into any state. However, it disables certain unit operation. For example, an Application Mode of "Cool Only" disables heating, "Heat Only" disables cooling, and "Fan Only" disables heating and cooling. ). This attribute has no affect unless Control Mode is set to Auto. Control Mode is only set at the keypad/display.

Measurement Units Data Type Valid Range Uses Heartbeat Default Value Mode N/A BACnet: Unsigned Enumerated Yes N/A LonWorks: Real

BACnet Object Identifier Property Object Type Type ID Instance Name ID Multistate Value 19 5 Present_Value 85

34 ED15112-12 Full Reference .ApplicCmd.Present_Value Enumeration 1= Off 2 = Heat 3= Cool 4= Fan Only 5= Auto 6= N/A

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nviApplicMode DAC, SCC Yes SNVT_hvac_mode 108

Enumeration Definitions Value Identifier Notes 0 HVAC_AUTO Controller automatically changes between application modes 1 HVAC_HEAT Heating only 2 HVAC_MRNG_WRMUP Application-specific morning warm-up (Not Used) 1 3 HVAC_COOL Cooling only 4 HVAC_NIGHT_PURGE Application-specific night purge (Not Used) 1 5 HVAC_PRE_COOL Application-specific pre-cool (Not Used) 1 6 HVAC_OFF Controller not controlling outputs 7 HVAC_TEST Equipment being tested (Not Used) 1 8 HVAC_EMERG_HEAT Emergency heat mode () (Not Used) 1 9 HVAC_FAN_ONLY Air not conditioned, fan turned on 10 HVAC_FREE_COOL Cooling with compressor not running (Not Used) 1 11 HVAC_ICE Ice-making mode (Not Used) 1 12 HVAC_MAX_HEAT (Not Used) 1 13 HVAC_ECONOMY Controller automatically changes between application modes (Not Used) 1 14 HVAC_DEHUMID Controller automatically changes between application modes (Not Used) 1 0xFF HVAC_NUL Value not available 1 Writing to a state that is not used by the unit controller causes it to control as if HVAC_AUTO (0) was selected.

Airflow Switch (Fault) Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Airflow Switch (Closed (1) or Open (0)). The Off Normal state of this object indicates an Air Flow fault.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 1 Present_Value 85 Full Reference .AirFlwSw.Present_Value Enumeration 0 – Closed 1 – Open LON WORKS No LON WORKS equivalent.

ED15112-12 35 Airflow Switch (Warning) Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Airflow Switch (Closed (1) or Open (0)). The OffNormal state of this object indicates an Airflow Switch Warning.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 2 Present_Value 85 Full Reference .AirFlwWrSw.Present_Value Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent.

Application Version Keypad Menu Path Main Menu\About This AHU\App Version= This read-only property identifies the version of application software loaded into the unit controller.

Measurement Units Data Type Valid Range Default Value N/A N/A CharacterString N/A N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Device 8 Variable Application_Software_Version 12 Full Reference . Application_Software_Version

Building Static Pressure Keypad Menu Path Main Menu\View/Set Unit\RF/EF Spd Control\Bldg Press= This read-only property displays the unit’s building static pressure. This variable only applies to units that have their return/exhaust fan method set to building pressure.

Measurement Units Data Type Valid Range Default Value Pressure (gauge) IWC or Pa Real -0.2489 – +0.2489 IWC N/A -62.0 .. 62.0 Pa

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 9 Present_Value 85 Full Reference .BldgStatPress.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoBldgStatPress DAC, Yes SNVT_press_p 113 Daikin AppliedRTU-

36 ED15112-12 SCC

Building Static Pressure Setpoint Keypad Menu Path Main Menu\Quick Menu\BldgSP Spt= Main Menu\View/Set Unit\RF/EF Spd Control\Bldg Press= This read/write property sets the building static pressure setpoint used for controlling the return air or exhaust fan inlet VFD. The VFD is modulated to maintain the building static pressure sensor input at this Setpoint. This attribute uses maximum and minimum limits. If the Present Value is set beyond these limits from the network, the value is ignored and the controller continues to control to the last valid value. This variable only applies if the unit is configured for a modulating return/exhaust fan.

Measurement Units Data Type Valid Range Uses Heartbeat Default Value Pressure (gauge) IWC or Pa Real -0.2489 – +0.2489 IWC No 0.050 IWC / -62.0 .. 62.0 Pa 12.5 Pa BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 8 Present_Value 85 Full Reference .BldgStaticSP.Present_Value

LON WORKS Note: invalid LonWorks value is 131.779 IWC / 32767 Pa LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nviBldgStaticSP DAC, No SNVT_press_p 113 Daikin Applied RTU- SCC

Compressor 1 Hours Keypad Menu Path Main Menu\View/Set Unit\Service\Operating Hours\Comp 1= Main Menu\View/Set Unit\Unit Maintenance\Operating Hours\Comp 1= This read/write property indicates the Compressor 1 accumulated run hours. It can be reset via the network. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Time Hrs Real 0–50000 Hrs No N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 105 Present_Value 85 Full Reference .Comp1Hrs.Present_Value LON WORKS No LON WORKS equivalent. Compressor 2 Hours Keypad Menu Path Main Menu\View/Set Unit\Service\Operating Hours\Comp 2= Main Menu\View/Set Unit\Unit Maintenance\Operating Hours\Comp 2= This read/write property indicates the Compressor 2 accumulated run hours. It can be reset via the network. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Time Hrs Real 0–50000 Hrs No N/A

ED15112-12 37 BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 106 Present_Value 85 Full Reference .Comp2Hrs.Present_Value LON WORKS No LON WORKS equivalent. Compressor 3 Hours Keypad Menu Path Main Menu\View/Set Unit\Service\Operating Hours\Comp 3= Main Menu\View/Set Unit\Unit Maintenance\Operating Hours\Comp 3= This read/write property indicates the Compressor 3 accumulated run hours. It can be reset via the network. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Time Hrs Real 0–50000 Hrs No N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 107 Present_Value 85 Full Reference .Comp3Hrs.Present_Value LON WORKS No LON WORKS equivalent.

Compressor 4 Hours Keypad Menu Path Main Menu\View/Set Unit\Service\Operating Hours\Comp 4= Main Menu\View/Set Unit\Unit Maintenance\Operating Hours\Comp 4= This read/write property indicates the Compressor 4 accumulated run hours. It can be reset via the network. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Time Hrs Real 0–50000 Hrs No N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 108 Present_Value 85 Full Reference .Comp4Hrs.Present_Value LON WORKS No LON WORKS equivalent. Compressor 5 Hours Keypad Menu Path Main Menu\View/Set Unit\Service\Operating Hours\Comp 5= Main Menu\View/Set Unit\Unit Maintenance\Operating Hours\Comp 5= This read/write property indicates the Compressor 5 accumulated run hours. It can be reset via the network. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Time Hrs Real 0–50000 Hrs No N/A

38 ED15112-12 BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 109 Present_Value 85 Full Reference .Comp5Hrs.Present_Value LON WORKS No LON WORKS equivalent.

Compressor 6 Hours Keypad Menu Path Main Menu\View/Set Unit\Service\Operating Hours\Comp 6= Main Menu\View/Set Unit\Unit Maintenance\Operating Hours\Comp 6= This read/write property indicates the Compressor 6 accumulated run hours. It can be reset via the network. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Time Hrs Real 0–50000 Hrs No N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 110 Present_Value 85 Full Reference .Comp6Hrs.Present_Value LON WORKS No LON WORKS equivalent.

Compressor 7 Hours Keypad Menu Path Main Menu\View/Set Unit\Service\Operating Hours\Comp 7= Main Menu\View/Set Unit\Unit Maintenance\Operating Hours\Comp 7= This read/write property indicates the Compressor 7 accumulated run hours. It can be reset via the network. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Time Hrs Real 0–50000 Hrs No N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 111 Present_Value 85 Full Reference .Comp7Hrs.Present_Value LON WORKS No LON WORKS equivalent. Compressor 8 Hours Keypad Menu Path Main Menu\View/Set Unit\Service\Operating Hours\Comp 8= Main Menu\View/Set Unit\Unit Maintenance\Operating Hours\Comp 8= This read/write property indicates the Compressor 8 accumulated run hours. It can be reset via the network. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Time Hrs Real 0–50000 Hrs No N/A

ED15112-12 39 BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 112 Present_Value 85 Full Reference .Comp8Hrs.Present_Value LON WORKS No LON WORKS equivalent.

Compressor Cooling Hours Keypad Menu Path Main Menu\View/Set Unit\Service\Operating Hours\Cmp Cooling= Main Menu\View/Set Unit\Unit Maintenance\Operating Hours\Cmp Cooling= This read/write property indicates the compressor cooling accumulated run hours and applies to Rebel units only. It can be reset via the network. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Time Hrs Real 0–50000 Hrs No N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 113 Present_Value 85 Full Reference .CmpClgHrs.Present_Value LON WORKS No LON WORKS equivalent. Compressor Heating Hours Keypad Menu Path Main Menu\View/Set Unit\Service\Operating Hours\Cmp Heating= Main Menu\View/Set Unit\Unit Maintenance\Operating Hours\Cmp Heating= This read/write property indicates the compressor heating accumulated run hours and applies to Rebel units only. It can be reset via the network. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Time Hrs Real 0–50000 Hrs No N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 114 Present_Value 85 Full Reference .CmpHtgHrs.Present_Value LON WORKS No LON WORKS equivalent.

Conductivity Keypad Menu Path Main Menu\Commission Unit\Evap Cond Set-Up\Conductivity= This read only property provides the conductivity of the water in the sump of an evaporative cooled condenser. This variable only applies to units with evaporative condensing.

Measurement Units Data Type Valid Range Default Value Conductivity N/A Real 0-5000 N/A

40 ED15112-12 BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 12 Present_Value 85 Full Reference .Conductivity.Present_Value

LON WORKS LonWorks Name Profile Uses Heartbeat UNVT Type SNVT Number nvoConductivity Daikin Yes UNVTconductivity N/A AppliedDischargeAir, Daikin AppliedRTU- SCC

Control Temp Source Keypad Menu Path Main Menu\Commission Unit\Htg/Clg Chgovr Set-Up\Ctrl Temp Src= This read/write property selects the temperature sensor input to be used for the unit heating/cooling changeover or zone cooling and heating capacity change decisions. For example, if the CtrlTemp Src parameter is set to “Return,” then the Control Temp parameter reads the same value as the Return Air parameter. When this parameter is set to “None”, the unit uses the discharge air temperature sensor to heat or cool to the cooling discharge air temperature setpoint.

Measurement Units Data Type Valid Range Default Value Method N/A Unsigned Enumerated N/A BACnet Object Identifier Property Object Type Type ID Instance Name ID Multistate Value 19 39 Present_Value 85 Full Reference . CtlrTempSrc.Present_Value Enumeration 1=RAT (NA on 100%OA Unit) 2=Space 3=MAT (Applicable on UnitType=SCU and ControlType=DAT only) 4=OAT (Applicable on ControlType=DAT only) 5=None (Applicable on ControlType=DAT only)

LON WORKS No LON WORKS equivalent

Control Temperature Keypad Menu Path Main Menu\Quick Menu\Control Temp= Main Menu\View/Set Unit\Temperatures\Control Temp= This read-only property indicates the current control temperature.

Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real -50.0–249.998°F N/A -45.56°–121.11°C BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 14 Present_Value 85 Full Reference .ControlTemp.Present_Value LON WORKS No LON WORKS equivalent

ED15112-12 41

Cooling Capacity Keypad Menu Path Main Menu\Quick Menu\Clg Capacity= Main Menu\View/Set Unit\Unit Status\Settings\Clg Capacity= This read-only property indicates the current percentage of unit maximum cooling capacity. The BACnet property reads only the subject attribute; however the LON WORKS variable is only a part of the LON WORKS Unit Status network variable. See Page 96 for details of LON WORKS network variable. The BACnet property only applies to the subject data point. The LON WORKS variable covers six other data points: Unit State, Heating Capacity, Reheat Capacity, Supply Fan Capacity, Economizer Capacity, and In Alarm. This variable only applies if the unit is configured for cooling.

Measurement Units Data Type Valid Range Default Value Percent % BACnet: Real 0-100% N/A LON WORKS : Structure

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 1 Present_Value 85 Full Reference .ClgCapacity.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoUnitStatus.cool_output DAC, SCC Yes SNVT_hvac_status 112

Cooling Status Keypad Menu Path Main Menu\View/Set Unit\Unit Status/Settings\Clg Status= This read-only attribute indicates whether or not cooling is currently enabled. If cooling is disabled, the reason is indicated. Measurement Units Data Type Valid Range Default Value State N/A BACnet: Unsigned Enumerated N/A LonWorks: Real

BACnet Object Identifier Property Object Type Type ID Instance Name ID Multistate Value 19 2 Present_Value 85 Full Reference .ClgStatus.Present_Value Enumeration 1=Enabled 2=None 3=Off Amb 4=Off Alarm 5=Off Net 6=Off Man

LONWORKS LON WORKS Name Profile Uses Heartbeat UNVT Type SNVT Index nvoMcQAHUStatus.ClgStatus Daikin No UNVTmcQAHUStatus N/A AppliedDischargeAir, Daikin AppliedRTU- SCC

42 ED15112-12 Enumeration 0=Enabled 1=None 2=Off Ambient 3=Off Alarm 4=Off Net 5=Off Man

Date Keypad Menu Path Main Menu\View/Set Unit\Date/Time/Schedules\Date= This read/write property sets the current date of the form day, month, year, and day of the week. Dates as BACnet date data types. See ANSI/ASHRAE 135-2008 for a definition of the data type. BACnet Object Identifier Property Object Type Type ID Instance Name ID Device 8 Variable Local_Date 56 Full Reference .Local_Date

Defrost State Keypad Menu Path Main Menu\Commission Unit\Defrost Set-Up\Defrost State= This read-only attribute indicates the current defrost state.

Measurement Units Data Type Valid Range Default Value N/A N/A Unsigned 1 - 4 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Multi-State Value 0 47 Present_Value 85 Full Reference .DefrostState.Present_Value Enumeration 1 = Off 2 = Init (Defrost Initialization) 3 = Exec (Execute Defrost) 4 = Term (Terminate Defrost) LON WORKS No LON WORKS equivalent.

Defrost Temperature Keypad Menu Path Main Menu\View/Set Unit\Temperatures\DFT= This read-only property indicates the current reading of the unit defrost temperature sensor. This property applies only to Rebel units.

Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real -50.0–200.0°F N/A -45.56°–93.33°C BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 23 Present_Value 85 Full Reference .DefrostTemp.Present_Value

ED15112-12 43 LON WORKS No LON WORKS equivalent.

Dehumidification Hours Keypad Menu Path Main Menu\View/Set Unit\Service\Operating Hours\Dehumid= Main Menu\View/Set Unit\Unit Maintenance\Operating Hours\Dehumid= This read/write property indicates the dehumidification accumulated run hours. It can be reset via the network. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Time Hrs Real 0–50000 Hrs No N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 119 Present_Value 85 Full Reference .DehumHrs.Present_Value LON WORKS No LON WORKS equivalent.

Dehumidification Status Keypad Menu Path Main Menu\View/Set Unit\Unit Status/Settings\Dehum Status= This read-only attribute indicates whether or not dehumidification operation is currently active. Measurement Units Data Type Valid Range Default Value State N/A BACnet: Unsigned Enumerated N/A LonWorks: Real

BACnet Object Identifier Property Object Type Type ID Instance Name ID Multistate Value 46 46 Present_Value 85 Full Reference .DehumStatus.Present_Value Enumeration 1=Inactive 2=Active LON WORKS No LON WORKS equivalent.

Dew Point Setpoint Keypad Menu Path Main Menu\View/Set Unit\Dehumidification\Dewpoint Spt= This read/write property sets the Dew Point Setpoint via the network. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Temperature °F / °C Real 0.0–100.0°F No N/A -17.78 - +37.78°C

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 41 Present_Value 85 Full Reference .DewpointSP.Present_Value

44 ED15112-12 LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nviSpaceDewPtSP Daikin No SNVT_temp_p 105 AppliedDischargeAir, Daikin AppliedRTU- SCC

Dew Point Temperature Keypad Menu Path Main Menu\View/Set Unit\Dehumidification\Dewpoint= This read-only attribute indicates the current dew point calculated from the current reading of the optional relative humidity sensor. Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real -50°–150°F N/A -45.56°–65.56°C BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 20 Present_Value 85 Full Reference .SpaceDewPt.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoSpaceDewPt SCC, Yes SNVT_temp_p 105 Daikin AppliedDischargeAir

Dirty Filter Switch Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Dirty Filter Switch (Closed (1) or Open (0)). The OffNormal state of this object indicates a Dirty Filter Warning.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 3 Present_Value 85 Full Reference .DirtyFilterSw.Present_Value Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent.

Discharge Air Temperature Keypad Menu Path Main Menu\Quick Menu\Disch Air= Main Menu\View/Set Unit\Temperatures\Disch Air= This read-only property indicates the current reading of the unit discharge air temperature sensor.

Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real -50.0–249.998°F N/A -45.56°–121.11°C

ED15112-12 45 BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 1 Present_Value 85 Full Reference .DischAirTemp.Present_Value LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoDischAirTemp DAC, SCC Yes SNVT_temp_p 105

Discharge Line Temperature 1 Keypad Menu Path Main Menu\View/Set Unit\Temperatures\DLT1= This read-only property indicates the current reading of the unit inverter compressor (Comp. 1) discharge line refrigerant temperature sensor. This property applies only to Rebel units.

Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real -50.0–392.0°F N/A -45.56°–200.0°C BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 22 Present_Value 85 Full Reference .DischLn1Temp.Present_Value LON WORKS No LON WORKS equivalent.

Discharge Line Temperature 2 Keypad Menu Path Main Menu\View/Set Unit\Temperatures\DLT2= This read-only property indicates the current reading of the unit inverter compressor (Comp. 2) discharge line refrigerant temperature sensor.

Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real -50.0–392.0°F N/A -45.56°–200.0°C BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 32 Present_Value 85 Full Reference .DischLn2Temp.Present_Value LON WORKS No LON WORKS equivalent.

Discharge Line Temperature 3 Keypad Menu Path Main Menu\View/Set Unit\Temperatures\DLT3= This read-only property indicates the current reading of the unit fixed compressor (Comp. 3) discharge line refrigerant temperature sensor. This property applies only to Rebel units.

Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real -50.0–392.0°F N/A -45.56°–200.0°C

46 ED15112-12 BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 21 Present_Value 85 Full Reference .DischLn3Temp.Present_Value LON WORKS No LON WORKS equivalent.

Discharge Refrigerant Pressure Keypad Menu Path Main Menu\Commission Unit\INV Cmp Set-Up\PTD= Main Menu\Commission Unit\OAFan Set-Up\PTD= Main Menu\Commission Unit\Exp Valve Set-Up\PTD=

This read-only property indicates the current reading of the unit discharge line refrigerant pressure sensor. This property applies only to Rebel units.

Measurement Units Data Type Valid Range Default Value Temperature PSI/kPa Real 0.0–725.2PSI N/A 0.0–5000.0kPa BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 26 Present_Value 85 Full Reference .RefDischP.Present_Value LON WORKS No LON WORKS equivalent.

Discharge Refrigerant Pressure Circuit 1 Keypad Menu Path Main Menu\Commission Unit\INV Cmp Set-Up\PTD1= Main Menu\Commission Unit\OAFan Set-Up\PTD1= Main Menu\Commission Unit\Exp Valve Set-Up\PTD1=

This read-only property indicates the current reading of the circuit 1 discharge line refrigerant pressure sensor.

Measurement Units Data Type Valid Range Default Value Temperature PSI/kPa Real 0.0–725.2PSI N/A 0.0–5000.0kPa BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 30 Present_Value 85 Full Reference .C1RefDischP.Present_Value LON WORKS No LON WORKS equivalent.

Discharge Refrigerant Pressure Circuit 2 Keypad Menu Path Main Menu\Commission Unit\INV Cmp Set-Up\PTD2= Main Menu\Commission Unit\OAFan Set-Up\PTD2= Main Menu\Commission Unit\Exp Valve Set-Up\PTD2=

This read-only property indicates the current reading of the circuit 2 discharge line refrigerant pressure sensor.

ED15112-12 47 Measurement Units Data Type Valid Range Default Value Temperature PSI/kPa Real 0.0–725.2PSI N/A 0.0–5000.0kPa BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 31 Present_Value 85 Full Reference .C2RefDischP.Present_Value LON WORKS No LON WORKS equivalent.

Duct High Limit Switch Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Duct High Limit Switch (Closed (1) or Open (0)). The OffNormal state of this object indicates a Duct High Limit Fault.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 21 Present_Value 85 Full Reference .DuctHiLmtSw.Present_Value Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent.

Duct Static Pressure Keypad Menu Path Main Menu\Quick Menu\Duct Press= Main Menu\View/Set Unit\SAF Spd Control\Duct Press= This read-only attribute indicates the current reading of the duct static pressure sensor. When a unit is equipped with two duct static pressure sensors, this attribute displays the lower of the two sensor readings. Static pressure control is then based on the lower of the two readings. This variable only applies to units that are configured for supply fan VFDs.

Measurement Units Data Type Valid Range Default Value Pressure (gauge) IWC / Pa Real 0.00–5.00 IWC N/A 0–1250 Pa

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 6 Present_Value 85 Full Reference .DuctStatPress.Present_Value

LonWorks LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoDuctStatPress DAC Yes SNVT_press_p 113

48 ED15112-12 Duct Static Pressure Setpoint Keypad Menu Path Main Menu\Quick Menu\DuctSP Spt= Main Menu\View/Set Unit\SAF Spd Control\DuctSP Spt= This read/write property sets the Duct Static Pressure Setpoint used to control the discharge air fan VFD. If the Present Value is set beyond the valid limits from the network, the value written from the network is ignored. This variable only applies if the unit’s supply fan type is variable frequency drives (VFD).

Measurement Units Data Type Valid Range Uses Heartbeat Default Value Pressure (gauge) IWC / Pa Real 0.20–4.00 IWC No 1.00 IWC / 49.82–996.36 Pa 249.09 Pa

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 7 Present_Value 85 Full Reference .DuctStaticSP.Present_Value

LON WORKS Note: invalid LonWorks value is 131.779 IWC / 32767 Pa LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nviDuctStaticSP DAC No SNVT_press_p 113

Economizer Capacity Keypad Menu Path Main Menu\Quick Menu\OAD/Econo Cap= Main Menu\View/Set Unit\Economizer\OAD/Econo Cap= This read-only attribute indicates the current economizer capacity or outdoor air damper position. The BACnet property reads only the subject attribute; however the LON WORKS variable is only a part of the LON WORKS Unit Status network variable. See Unit State for details.. The BACnet property only applies to the subject data point. The LON WORKS variable covers six other data points: Unit State, Cooling Capacity, Heating Capacity, Reheat Capacity, Supply Fan Capacity, and In Alarm.

Measurement Units Data Type Valid Range Default Value Percent Percent BACnet: Real 0-100% N/A LON WORKS : Structure

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 15 Present_Value 85 Full Reference .EconCapacity.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoUnitStatus.econ_output DAC, SCC Yes SNVT_hvac_status 112

Economizer Enable Keypad Menu Path Main Menu\Service Menus\Network Input Status\Net Ec Ena Sw= Main Menu\Service Menus\Network Input Status\Net Ec Ena Vl= This read/write configuration property enables or disables the economizer. This variable only applies if the unit is configured for a waterside or airside economizer. In BACnet, if EconEnable is 0, then the economizer is disabled. If it is 1 and EconEnaPercent is 0, the economizer is disabled. If EconEnable is 1 and EconEnaPercent is greater than 0, the economizer is enabled. The LON WORKS point nviEconEnable has two properties; a State and a Value. When the State = 0, economizer control through the network is disabled. When State = 1, the Economizer can be controlled through the network. When the Value = 0 and the State = 1, the economizer is disabled through the LON WORKS network. When the Value is greater than 0 and the State = 1, the economizer is enabled through the LON WORKS network.

ED15112-12 49 Measurement Units Data Type Valid Range Uses Heartbeat Default Value State N/A BACnet: Real Enumerated Yes N/A LON WORKS : Structure

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 32 Present_Value 85 Full Reference .EconEnable.Present_Value

Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 33 Present_Value 85 Full Reference .EconEnablePct.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nviEconEnable DAC, SCC Yes SNVT_switch 95

Valid Range State Value Economizer 0 N/A Disabled 1 0 Disabled 1 1-100% Enabled -1(0xFF) N/A Auto (invalid)

Economizer Hours Keypad Menu Path Main Menu\View/Set Unit\Service\Operating Hours\Economizer= Main Menu\View/Set Unit\Unit Maintenance\Operating Hours\Economizer= This read/write property indicates the economizer accumulated run hours. It can be reset via the network. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Time Hrs Real 0–50000 Hrs No N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 117 Present_Value 85 Full Reference .EconoHrs.Present_Value LON WORKS No LON WORKS equivalent.

Economizer Status Keypad Menu Path Main Menu\View/Set Unit\Unit Status/Settings\EconoStatus= This read-only attribute indicates whether or not the economizer is currently enabled. If the economizer is disabled, the reason is indicated. Measurement Units Data Type Valid Range Default Value State N/A BACnet: Unsigned Enumerated N/A LonWorks: Real

50 ED15112-12

BACnet Object Identifier Property Object Type Type ID Instance Name ID Multistate Value 19 3 Present_Value 85 Full Reference .EconoStatus.Present_Value Enumeration 1=Enabled 2=None 3=Off Amb 4=Off Alarm (Not Used) 5=Off Net 6=Off Man 7=Off Dehum

LON WORKS LON WORKS Name Profile Uses Heartbeat UNVT Type SNVT Number nvoMcQAHUStatus.EconStatus Daikin No UNVTmcQAHUStatus N/A AppliedDischargeAir, Daikin AppliedRTU- SCC Enumeration 0=Enabled 1=None 2=Off Amb 3=Off Alarm (Not Used) 4=Off Net 5=Off Man 6=Off Dehum

Effective Discharge Air Temperature Setpoint Keypad Menu Path No Keypad Equivalent This read-only attribute reveals the effective discharge air temperature setpoint that the unit is using for control. This attribute is set equal to the Discharge Air Heating Temperature Setpoint when the unit is in the heating operating state and equal to the Discharge Air Cooling Setpoint when the unit is in any other operating state.

Measurement Units Data Type Valid Range Default Value Temperature °F / °C Fixed Point Scalar - signed long -83.2 .. +147.2°F N/A -64.0 .. +64.0°C

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 39 Present_Value 85 Full Reference .EffDATempSP.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoEffDATempSp DAC Yes SNVT_temp_p 105

ED15112-12 51 Effective Setpoint Output Keypad Menu Path Main Menu\Service Menus\Network Input Status\nvoEffSpt= This read-only attribute monitors the effective temperature setpoint. It is always set equal to the current controlling setpoint depending on the current unit operating state (i.e. cooling or heating). The Effective Setpoint Output depends on the Occupied Cooling Setpoint, the Occupied Heating Setpoint, and Temperature Setpoint Input. If the Temperature Setpoint Input (nviSetpoint) is set to a valid value: Effective Cooling Enable Setpoint = Temperature Setpoint Input +½(Occupied Cooling Enable Setpoint–Occupied Heating Enable Setpoint)

Effective Heating Enable Setpoint = Temperature Setpoint Input -½(Occupied Cooling Enable Setpoint–Occupied Heating Enable Setpoint) The Effective Setpoint Output (nvoEffectSetpt) equals Effective Heating Enable Setpoint when the control temperature is less than Occupied Heating setpoint + [1/2(Occupied Cooling Enable Setpoint–Occupied Heating Enable Setpoint)]. It is set equal to the Effective Cooing Enable Setpoint when the control temperature is greater than the Occupied Cooling Enable Setpoint – [1/2(Occupied Cooling Enable Setpoint–Occupied Heating Enable Setpoint)]. If the Temperature Setpoint Input (nviSetpoint) is set to an invalid value: Effective Cooling Enable Setpoint = Occupied Cooling Enable Setpoint

Effective Heating Enable Setpoint = Occupied Heating Enable Setpoint

Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real 0.0°-100.0°F N/A -17.78°-37.78°C BACnet No BACnet equivalent.

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type Number nvoEffectSetpt SCC, Yes SNVT_temp_p 105 Daikin AppliedDischargeAir

Emergency Off Switch Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Emergency Off Switch (Closed (1) or Open (0)). The OffNormal state of this object indicates an Emergency Off Fault.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 22 Present_Value 85 Full Reference .EmergencyOffSw.Present_Value Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent.

52 ED15112-12 Emergency Override Keypad Menu Path Main Menu\View/Set Unit\Unit Status/Settings\Emerg Mode= This read/write property shuts off the unit controller. If this property is set to Off, the unit controller cannot start based on a time clock or any other means. The only way to start the unit controller is to change the value to Normal. If a value other than Off or EMERG_SHUTDOWN, is written, this variable reverts back to Normal.

Measurement Units Data Type Valid Range Uses Heartbeat Default Value N/A N/A BACnet: Unsigned Enumerated No Normal LonWorks: Real

BACnet Object Identifier Property Object Type Type ID Instance Name ID Multistate Value 19 10 Present_Value 85 Full Reference .EmergOverride.Present_Value Enumeration 1 = Normal 2 = Off

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nviEmergOverride DAC, SCC No SNVT_hvac_emerg 103

Enumeration Definitions Value Identifier Notes 0 EMERG_NORMAL No emergency mode 1 EMERG_PRESSURIZE Emergency pressurize mode (not used) 2 EMERG_DEPRESSURIZE Emergency depressurize mode (not used) 3 EMERG_PURGE Emergency purge mode (not used) 4 EMERG_SHUTDOWN Emergency shutdown mode 5 EMERG_FIRE (not used) 0xFF EMERG_NUL Value not available

Enumeration Correspondence BACnet Lon 1 Normal 0 EMERG_NORMAL 1 Normal 1 EMERG_PRESSURIZE 1 Normal 2 EMERG_DEPRESSURIZE 1 Normal 3 EMERG_PURGE 2 Off 4 EMERG_SHUTDOWN 1 Normal 5 EMERG_FIRE 1 Normal 0xFF EMERG_NUL

Energy Recovery Leaving Air Temperature Keypad Menu Path Main Menu\Commission Unit\Energy Rec Set-Up\ER LAT= This read-only attribute indicates the current value of the energy recovery discharge air temperature sensor.

Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real -50°–249.998°F N/A -45.56°-121.11°C

ED15112-12 53 BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 16 Present_Value 85 Full Reference .ERLAT.Present_Value LON WORKS No LON WORKS equivalent.

Energy Recovery Exhaust Air Temperature Keypad Menu Path Main Menu\Commission Unit\Energy Rec Set-Up\ER EAT= This read-only attribute indicates the current value of the energy recovery exhaust air temperature sensor.

Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real -20°–199.994°F N/A -28.89°-93.33°C

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 17 Present_Value 85 Full Reference .EREAT.Present_Value LON WORKS No LON WORKS equivalent.

Energy Recovery Wheel Hours Keypad Menu Path Main Menu\View/Set Unit\Service\Operating Hours\ER Wheel= Main Menu\View/Set Unit\Unit Maintenance\Operating Hours\ER Wheel= This read/write property indicates the energy recovery wheel accumulated run hours. It can be reset via the network. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Time Hrs Real 0–50000 Hrs No N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 120 Present_Value 85 Full Reference .ERWhlHrs.Present_Value LON WORKS No LON WORKS equivalent.

Energy Recovery Wheel Status Keypad Menu Path Main Menu\Commission Unit\Energy Rec Set-Up\Wheel= This read-only attribute indicates the command status (On or Off) of the energy recovery wheel.

Measurement Units Data Type Valid Range Default Value N/A N/A Unsigned Enumerated N/A

54 ED15112-12 BACnet Object Identifier Property Object Type Type ID Instance Name ID Multi-State Value 0 37 Present_Value 85 Full Reference .ERWhlOnOff.Present_Value Enumeration 1 = Off 2 = On LON WORKS No LON WORKS equivalent.

Energy Recovery Wheel Speed Keypad Menu Path Main Menu\Commission Unit\Energy Rec Set-Up\Wheel Speed= This read-only attribute indicates the current speed, as a percentage, of the energy recovery wheel.

Measurement Units Data Type Valid Range Default Value Percentage Real 0 –100% N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 15 Present_Value 85 Full Reference .ERWheelSpd.Present_Value LON WORKS No LON WORKS equivalent.

Entering Fan Temperature / Leaving Coil Temp Keypad Menu Path Main Menu\View/Set Unit\Temperatures\EFT/LC Temp= This read-only attribute indicates the current value of the unit entering fan/leaving coil air temperature sensor. This variable only applies to units configured for an entering fan temperature sensor.

Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real -83.2°–249.998°F N/A -64.0°-121.11°C

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 7 Present_Value 85 Full Reference .EFT_LCT.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoEFT_LCT DAC, SCC Yes SNVT_temp_p 105

Entering Water Temperature Keypad Menu Path Main Menu\Quick Menu\EW Temp= Main Menu\View/Set Unit\Temperatures\EW Temp= This read-only attribute indicates the current entering water temperature from the entering water temperature sensor. This variable only applies to Self-Contained units configured with a water condenser.

ED15112-12 55 Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real -50°–150°F N/A -45.56°–65.56°C

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 6 Present_Value 85 Full Reference .CWTemp.Present_Value LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoCWTemp DAC, Yes SNVT_temp_p 105 Daikin AppliedRTU-SCC

Exhaust Fan Capacity Keypad Menu Path Main Menu\Quick Menu\RF/EF Capacity= Main Menu\View/Set Unit\Unit Status/Settings\RF/EF Capacity=

This read-only property indicates the current capacity of the exhaust fans.

Measurement Units Data Type Valid Range Default Value Fan Status N/A BACnet: Real Enumerated N/A LON WORKS : Structure BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 Present_Value 85 Full Reference .ExhFanValue.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoExhFanStatus.value DAC, Yes SNVT_switch 95 Daikin AppliedRTU-SCC Field Definitions Field Units Valid Range Notes value % of Full Scale 0-100% 0-100% state N/A 0, 1 0=Off, 1=On

Exhaust Fan Capacity Input Keypad Menu Path Main Menu\Commission Unit\RF/EF Set-Up\Rem ExhF Cap= This read/write property is used to override the local exhaust fan capacity control. EF Cap Ctrl must be set to Speed for the MicroTech III Unit Controller to use this remote capacity for control. This variable only applies to units that are configured for modulating exhaust fan or that are configured for prop exhaust.

Measurement Units Data Type Valid Range Uses Heartbeat Default Value Capacity Percent Real 0-100% Yes N/A

56 ED15112-12 BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 23 Present_Value 85 Full Reference .ExhFanCapNetIn.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nviExhFanCap DAC, Yes SNVT_lev_percent 81 Daikin AppliedRTU- SCC

Exhaust Fan Status Keypad Menu Path Main Menu\View/Set Unit\Flow Status\Ret/Exh Fan= This read-only property indicates whether the unit controller is commanding the return or exhaust fan on. This variable only applies to units configured for a return/exhaust fan.

Measurement Units Data Type Valid Range Default Value Fan Status N/A BACnet: Enumerated Enumerated N/A LON WORKS : Structure

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 1 Present_Value 85 Full Reference .ExhFanState.Present_Value Enumeration 0 = Off 1 = On

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoExhFanStatus.State DAC, No SNVT_switch N/A Daikin AppliedRTU- SCC Field Definitions Field Units Valid Range Notes value % of Full Scale 0-100% 0-100% state N/A 0, 1 0=Off, 1=On

Freeze Switch (Fault) Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Freeze Switch (Closed (1) or Open (0)). The OffNormal state of this object indicates a Freeze Fault.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 19 Present_Value 85

ED15112-12 57 Full Reference .FreezeFltSw.Present_Value Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent.

Freeze Switch (Problem) Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Freeze Switch (Closed (1) or Open (0)). The OffNormal state of this object indicates a Freeze Problem.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 20 Present_Value 85 Full Reference .FreezeSw.Present_Value Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent.

Heat Fail Input Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Heat Fail input from the Daikin Applied gas heat flame safeguard (FSG) device. (Alarm (1) or Normal (0).

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 23 Present_Value Full Reference .FSGAlarmSw.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Heating Capacity Keypad Menu Path Main Menu\Quick Menu\Htg Capacity= Main Menu\View/Set Unit\Unit Status/Settings\Htg Capacity= This read-only attribute indicates the current percentage of unit maximum heating capacity. The BACnet property reads only the subject attribute and only applies to the subject data point. The LON WORKS variable is only a part of the 58 ED15112-12 LON WORKS Unit Status network variable. See Unit State for details of LON WORKS network variable. The LON WORKS variable covers six other data points: Unit State, Supply Fan Capacity, Secondary Heating (Reheat) Capacity, Economizer Capacity, and In Alarm. This variable only applies to units configured with heating. Measurement Units Data Type Valid Range Default Value Heating Capacity Percent BACnet: Real 0.0–100.0% N/A LonWorks: Structure

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 2 Present_Value 85 Full Reference .HtgCapacity.Present_Value

LON WORKS LonWorks Name Profile Uses Heartbeat SNVT Type SNVT Index nvoUnitStatus.heat_output_primary DAC, SCC Yes SNVT_hvac_status 112

Heating Hours Keypad Menu Path Main Menu\View/Set Unit\Service\Operating Hours\Heating= Main Menu\View/Set Unit\Unit Maintenance\Operating Hours\Heating= This read/write property indicates the heating accumulated run hours. It can be reset via the network. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Time Hrs Real 0–50000 Hrs No N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 116 Present_Value 85 Full Reference .HeatingHrs.Present_Value LON WORKS No LON WORKS equivalent.

Heating Status Keypad Menu Path Main Menu\View/Set Unit\Unit Status/Settings\Htg Status= This read-only attribute indicates whether or not heating is currently enabled. If heating is disabled, the reason is indicated. Measurement Units Data Type Valid Range Default Value State N/A BACnet: Unsigned Enumerated N/A LonWorks: Real

BACnet Object Identifier Property Object Type Type ID Instance Name ID Multistate Value 19 4 Present_Value 85 Full Reference .HtgStatus.Present_Value Enumeration 1=Enabled 2=None 3=Off Amb 4=Off Alarm (Not Used) 5=Off Net 6=Off Man

ED15112-12 59

LON WORKS LON WORKS Name Profile Uses Heartbeat UNVT Type SNVT Number nvoMcQAHUStatus.HtgStatus Daikin No UNVTmcQAHUStatus N/A AppliedDischargeAir, Daikin AppliedRTU- SCC Enumeration 0=Enabled 1=None 2=Off Amb 3=Off Alarm (Not Used) 4=Off Net 5=Off Man

High Pressure Circuit 1 Switch Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the High Pressure Circuit 1 Switch (Closed (1) or Open (0)). The OffNormal state of this object indicates a High Pressure Circuit 1 Problem.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 4 Present_Value 85 Full Reference .HiPress1Sw.Present_Value Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent.

High Pressure Circuit 2 Switch Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the High Pressure Circuit 2 Switch (Closed (1) or Open (0)). The OffNormal state of this object indicates a High Pressure Circuit 2 Problem.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 5 Present_Value 85 Full Reference .HiPress2Sw.Present_Value Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent. 60 ED15112-12

High Pressure Circuit 3 Switch Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the High Pressure Circuit 3 Switch (Closed (1) or Open (0)). The OffNormal state of this object indicates a High Pressure Circuit 3 Problem.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 6 Present_Value 85 Full Reference .HiPress3Sw.Present_Value Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent.

High Pressure Circuit 4 Switch Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the High Pressure Circuit 4 Switch (Closed (1) or Open (0)). The OffNormal state of this object indicates a High Pressure Circuit 4 Problem.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 7 Present_Value 85 Full Reference .HiPress4Sw.Present_Value Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent.

High Pressure Circuit 5 Switch Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the High Pressure Circuit 5 Switch (Closed (1) or Open (0)). The OffNormal state of this object indicates a High Pressure Circuit 5 Problem.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 8 Present_Value 85

ED15112-12 61 Full Reference .HiPress5Sw.Present_Value Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent.

High Pressure Circuit 6 Switch Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the High Pressure Circuit 6 Switch (Closed (1) or Open (0)). The OffNormal state of this object indicates a High Pressure Circuit 6 Problem.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 9 Present_Value 85 Full Reference .HiPress6Sw.Present_Value Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent.

High Pressure Circuit 7 Switch Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the High Pressure Circuit 7 Switch (Closed (1) or Open (0)). The OffNormal state of this object indicates a High Pressure Circuit 7 Problem.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 26 Present_Value 85 Full Reference .HiPress7Sw.Present_Value Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent.

62 ED15112-12 High Pressure Circuit 8 Switch Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the High Pressure Circuit 8 Switch (Closed (1) or Open (0)). The OffNormal state of this object indicates a High Pressure Circuit 8 Problem.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 27 Present_Value 85 Full Reference .HiPress8Sw.Present_Value Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent.

HVAC Unit Type Identifier Keypad Menu Path Main Menu\Service Menus\Network Input Status\nciHVACType= This read-only configuration property indicates the primary application and equipment type for the space comfort controller device. For other SCC object types the application and equipment type can be determined directly from the object type and corresponding device class within the standard program id. The HVAC Unit-Type configuration property can be polled by a tool or an operator interface device, to help the user identify the type of equipment. The HVAC Unit-Type is set at the time of manufacture .

Measurement Units Data Type Valid Range Default Value HVAC Unit Type N/A Real Enumerated 0=HVT_GENERIC

BACnet No BACnet equivalent LON WORKS LonWorks Name Profile SNVT Type SNVT Index SCPT Reference SCPT Index nciHvacType SCC SNVT_hvac_type 145 SCPThvacType 169

Enumeration Definitions (SNVT_HVT.H) Value Identifier Notes 0 HVT_GENERIC Generic 1 HVT_FAN_COIL Fan Coil (Not Used) 2 HVT_VAV Terminal (Not Used) 3 HVT_HEAT_PUMP Heat Pump (Not Used) 4 HVT_ROOFTOP Rooftop Unit (Not Used) 5 HVT_UNIT_VENT Unit Ventilator (Not Used) 6 HVT_CHILL_CEIL Chilled Ceiling (Not Used) 7 HVT_RADIATOR (Not Used) 8 HVT_AHU Air Handling Unit (Not Used) 9 HVT_SELF_CONT Self-Contained Unit (Not Used) 0xFF HVT_NUL Invalid value (Not Used)

ED15112-12 63 Indoor Refrigerant Temperature Keypad Menu Path No Keypad Equivalent This read-only attribute indicates the current indoor refrigerant temperature from the indoor refrigerant temperature sensor. This variable only applies if the unit is configured for heat pump operation. Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real -50°–150°F N/A -45.56°-65.56°C

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 27 Present_Value 85 Full Reference .IndoorRefTemp.Present_Value

LON WORKS No LON WORKS equivalent.

Inverter Compressor Hours Keypad Menu Path Main Menu\View/Set Unit\Service\Operating Hours\INV Comp= Main Menu\View/Set Unit\Unit Maintenance\Operating Hours\INV Comp= This read/write property indicates the inverter compressor accumulated run hours. It can be reset via the network. This property applies only to Rebel units. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Time Hrs Real 0–50000 Hrs No N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 115 Present_Value 85 Full Reference .INVCmpHrs.Present_Value LON WORKS No LON WORKS equivalent.

Inverter Compressor Body Temperature Keypad Menu Path Main Menu\View/Set Unit\Temperatures\INVCompTemp= This read-only attribute indicates the current Inverter Compressor Body Temperature. This variable only applies if the unit is configured with a 12 hp inverter compressor (unit is a DPS015). Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real -83.2°–147.2°F N/A -45.56°-65.56°C

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 29 Present_Value 85 Full Reference .INVCompTemp.Present_Value

LON WORKS No LON WORKS equivalent.

64 ED15112-12 Local OA Temperature Keypad Menu Path No Keypad Equivalent This read-only attribute indicates the current outdoor air temperature from the local outdoor air temperature sensor. This variable only applies if the unit is configured for an outdoor air temperature sensor. Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real -50°–150°F N/A -45.56°-65.56°C

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 5 Present_Value 85 Full Reference .LocalOATemp.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoLocalOATemp DAC, Yes SNVT_temp_p 105 Daikin AppliedRTU-SCC

Local Space Temperature Keypad Menu Path No Keypad Equivalent This read-only attribute indicates the current space air temperature from the local space air temperature sensor. This variable only applies if the unit is configured for a space temperature sensor.

Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real 0°–150°F N/A -17.78°-65.56°C

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 4 Present_Value 85 Full Reference .LocalSpaceTmp.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoLocalSpaceTmp SCC, Daikin Yes SNVT_temp_p 105 AppliedDischargeAir

Low Pressure Circuit 1 Switch Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Low Pressure Circuit 1 Switch (Closed (1) or Open (0)). The OffNormal state of this object indicates a Low Pressure Circuit 1 Problem.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 10 Present_Value 85 Full Reference .LoPress1Sw.Present_Value

ED15112-12 65 Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent.

Low Pressure Circuit 2 Switch Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Low Pressure Circuit 2 Switch (Closed (1) or Open (0)). The OffNormal state of this object indicates a Low Pressure Circuit 2 Problem.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 11 Present_Value 85 Full Reference .LoPress2Sw.Present_Value Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent.

Low Pressure Circuit 3 Switch Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Low Pressure Circuit 3 Switch (Closed (1) or Open (0)). The OffNormal state of this object indicates a Low Pressure Circuit 3 Problem.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 12 Present_Value 85 Full Reference .LoPress3Sw.Present_Value Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent.

Low Pressure Circuit 4 Switch Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Low Pressure Circuit 4 Switch (Closed (1) or Open (0)). The OffNormal state of this object indicates a Low Pressure Circuit 4 Problem.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

66 ED15112-12

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 13 Present_Value 85 Full Reference .LoPress4Sw.Present_Value Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent.

Low Pressure Circuit 5 Switch Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Low Pressure Circuit 5 Switch (Closed (1) or Open (0)). The OffNormal state of this object indicates a Low Pressure Circuit 5 Problem.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 14 Present_Value 85 Full Reference .LoPress5Sw.Present_Value Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent.

Low Pressure Circuit 6 Switch Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Low Pressure Circuit 6 Switch (Closed (1) or Open (0)). The OffNormal state of this object indicates a Low Pressure Circuit 6 Problem.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 15 Present_Value 85 Full Reference .LoPress6Sw.Present_Value Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent.

ED15112-12 67 Low Pressure Circuit 7 Switch Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Low Pressure Circuit 7 Switch (Closed (1) or Open (0)). The OffNormal state of this object indicates a Low Pressure Circuit 7 Problem.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 24 Present_Value 85 Full Reference .LoPress7Sw.Present_Value Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent.

Low Pressure Circuit 8 Switch Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Low Pressure Circuit 8 Switch (Closed (1) or Open (0)). The OffNormal state of this object indicates a Low Pressure Circuit 8 Problem.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 25 Present_Value 85 Full Reference .LoPress8Sw.Present_Value Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent.

Max Purge Time Keypad Menu Path Main Menu\View/Set Unit\Date/Time/Scheudles\Max Purge= This read/write property is used to activate a preoccupancy purge function period that uses unoccupied ecomomizer operation to precool the space. Setting this to 0 minutes deactivates the function.

Measurement Units Data Type Valid Range Uses Heartbeat Default Value Minutes Min Real 0-300 Min No 0 Min

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 58 Present_Value 85

68 ED15112-12 Full Reference .MaxPurgeTime.Present_Value

LON WORKS No LON WORKS equivalent.

Maximum Discharge Air Heating Setpoint Keypad Menu Path Main Menu\Commission Unit\Heating Set-Up\Max Htg Spt= This read/write configuration property defines the maximum discharge air heating setpoint for the controller. It is used to limit the discharge air heating setpoint determined by the discharge air temperature reset function. This point is also changeable via the unit controller keypad/display. The unit controller will use whichever valid value it last received from either the network or the keypad/display. This attribute uses maximum and minimum limits. If the Present Value is set beyond these limits from the network, the value is ignored and the unit controller continues to control to the last valid value.

Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real 40.0°–140.0 °F 120°F / 48.89°C 4.4°–60°C

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 18 Present_Value 85 Full Reference .DefaultDATHtgSetpt.Present_Value

LON WORKS LON WORKS Name Profile SNVT Type SNVT Index SCPT Reference SCPT Index nciDAHtSP DAC SNVT_temp_p 105 SCPTdischargeAirHeatingSetpoint 184

Maximum Leaving Coil Temperature Dehum Setpoint Keypad Menu Path Main Menu\ Commission Unit\Dehum Set-Up\Mx Lvg Coil T= This read/write property is used to set the point where staged cooling is staged down during dehumidification operation.

Measurement Units Data Type Valid Range Uses Heartbeat Default Value Temperature °F / °C Real -39.992°–100.004°F No 51.998°F / 4.44°-37.78°C 11.11°C

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 57 Present_Value 85 Full Reference . MaxDehumLCTSpt.Present_Value

LON WORKS No LON WORKS equivalent.

Daikin Applied AHU Unit Status Keypad Menu Path Main Menu\Unit Status= Main Menu\Quick Menu\Unit Status= Main Menu\View/Set Unit\Unit Status/Settings\Unit Status= This output network variable indicates the operating status of the unit controller. BACnet Object Identifier Property Object Type Type ID Instance Name ID Multistate Value 19 1 Present_Value 85

ED15112-12 69 Full Reference .Daikin AppliedStatus.Present_Value Enumeration 1 = Enabled, 2 = Off Man 3 = Off ManCtrl 4 = Off Net 5 = Off Alarm 6 = Off Fan Retry

LON WORKS LON WORKS Name Profile Uses Heartbeat UNVT Type SNVT Number nvoMcQAHUStatus.Mode Daikin Yes UNVTmcQAHUStatus N/A AppliedDischargeAir, Daikin AppliedRTU- SCC Measurement UNVTmcQAHUStatus Type Category Structure Type Size 2 bytes Valid Range (Resolution) See Below. The value –1 (NUL) represents invalid value. Uses Receive Heartbeat Yes

Field Definitions Field Description Field Description EconStatus 0 = Enabled HtgStatus 0 = Enabled 1 = None 1 = None 2 = Off Ambient 2 = Off Ambient 3 = Off Alarm 3 = Off Alarm 4 = Off Net 4 = Off Net 5= Off Man 5= Off Man 6= Off Dehum ClgStatus 0 = Enabled Mode 0 = Enabled, 1 = None 1 = Off Man 2 = Off Ambient 2 = Off Man Ctrl 3 = Off Alarm 3 = Off Net 4 = Off Net 4 = Off Alarm 5= Off Man 5 = Off Fan Retry

Mechanical Cooling Hours Keypad Menu Path Main Menu\View/Set Unit\Service\Operating Hours\Mech Cool= Main Menu\View/Set Unit\Unit Maintenance\Operating Hours\Mech Cool= This read/write property indicates the mechanical cooling accumulated run hours. It can be reset via the network. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Time Hrs Real 0–50000 Hrs No N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 104 Present_Value 85 Full Reference .MechClgHrs.Present_Value LON WORKS No LON WORKS equivalent.

70 ED15112-12 Minimum Discharge Air Cooling Setpoint Keypad Menu Path Main Menu\Commission Unit\Cooling Set-Up\Min Clg Spt= This read/write configuration property sets the Minimum Discharge Air Cooling Setpoint. This point is also changeable via the unit controller keypad/display. The unit controller will use the last valid value it received from either the network or keypad/display. Measurement Units Data Type Valid Range Default Value Temperature °F / °C BACnet: Real 39.992-100.0°F 55°F / 12.78°C LonWorks: Signed Lon 4.44-37.78°C

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 14 Present_Value 85 Full Reference .DefaultDATClgSetpt.Present_Value

LON WORKS LON WORKS Name Profile SNVT Type SNVT Index SCPT Reference SCPT Index nciDAClSP DAC SNVT_temp_p 105 N/A N/A

Minimum Leaving Coil Temperature Dehum Setpoint Keypad Menu Path Main Menu\ Commission Unit\Dehum Set-Up\Mn Lvg Coil T= This read/write property is used to set the point where staged cooling is staged up during dehumidification operation. If the unit is equipped with modulating cooling (such as or variable speed compressor) this is the point the leaving coil temperature is controlled to during dehumidification operation.

Measurement Units Data Type Valid Range Uses Heartbeat Default Value Temperature °F / °C Real -39.992°–100.004°F No 44.996°F / 4.44°-37.78°C 7.22°C

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 56 Present_Value 85 Full Reference . MinDehumLCTSpt.Present_Value

LON WORKS No LON WORKS equivalent.

Minimum Send Time Keypad Menu Path Main Menu/BMS Communications/LON Set-Up\MinSndTm= This read/write configuration property defines the minimum period of time between automatic network variable output transmissions.

Measurement Units Data Type Valid Range Default Value Time Seconds Fixed Point Scalar - unsigned long 0.0–6553.4 sec 0 Seconds

BACnet No BACnet equivalent. LON WORKS LON WORKS Name Profile SNVT Type SNVT Index SCPT Reference SCPT Index nciMinOutTm DAC, SCC SNVT_time_sec 107 SCPTminSendTime 52

The following network variables are limited by nciMinOutTm if the timer is greater than zero:

ED15112-12 71 Send Heartbeat Table nvoMcQAHUStatus nvoLocalOATemp nvoEffDATempSp nvoUnitStatus nvoEFT_LCT nvoEffectSetpt nvoEffectOccup nvoDuctStatPress nvoExhFanStatus nvoDischAirTemp nvoBldgStatPress nvoConductivity nvoRATemp nvoSpaceRH nvoMATemp nvoSpaceTemp nvoSpaceDewPt nvoCWTemp nvoOutdoorTemp nvoSpaceCO2 nvoOAFlow nvoLocalSpaceTmp

Mixed Air Temperature Keypad Menu Path Main Menu\View/Set Unit\Temperatures\Mixed Air= This read-only attribute indicates the current mixed air temperature from the mixed air temperature sensor. This variable only applies if the unit is configured as a self-contained unit with a mixed air temperature sensor present.

Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real BACnet: -50.0°–249.998°F N/A LON WORKS : -45.56°–121.11°C

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 5 Present_Value 85 Full Reference .MATemp.Present_Value LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoMATemp DAC Yes SNVT_temp_p 105

LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoMixedAirTemp SCC Yes SNVT_temp_p 105

Morning Warm-up Heating Setpoint Keypad Menu Path Main Menu\View/Set Unit\Heating\MWUSpt= This read/write configuration property defines the morning warm-up heating setpoint for the controller when unit is configured for discharge air temperature control. It does not apply to zone temperature control units (the Occupied Heating Setpoint is used for morning warm-up purposes for zone control units). This point is also changeable via the unit controller keypad/display. The unit controller will use whichever valid value it last received from either the network or the keypad/display. This attribute uses maximum and minimum limits. If the Present Value is set beyond these limits from the network, the value is ignored and the unit controller continues to control to the last valid value.

Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real 40.0°–100.0 °F 70°F / 21.11°C 4.4°–37.78°C

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 55 Present_Value 85 Full Reference .DACMWUSpt.Present_Value

LON WORKS No LON WORKS equivalent.

72 ED15112-12 Network Discharge Air Cooling Setpoint Keypad Menu Path Main Menu\Service Menus\Network Input Status\Net Dat Clg Spt This read/write property sets the Network Cooling Discharge Setpoint. This setpoint is set to this value when reset type is set to network. The unit controller internally limits the Present Value that is written between the Min Clg Spt (AV14) and the Max Clg Spt (see the Cooling menu on the unit controller keypad/display). Measurement Units Data Type Valid Range Uses Heartbeat Default Value Temperature °F / °C Real 39.992 – 100.0°F No 55°F / 12.78°C 4.44°–37.78°C

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 13 Present_Value 85 Full Reference .DAClgSetpt.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nviDAClSP DAC No SNVT_temp_p 105

Network Discharge Air Heating Setpoint Keypad Menu Path Main Menu\Service Menus\Network Input Status\Net Dat Htg Spt This read/write property sets the Network Heating Discharge Setpoint. This setpoint is set to this value when reset is network. The unit controller internally limits the Present Value that is written between the Min Htg Spt and the Max Htg Spt (AV18) (see the Heating menu on the unit controller keypad/display).

Measurement Units Data Type Valid Range Uses Heartbeat Default Value Temperature °F / °C Real 39.992–140.0°F No 100°F / 37.78°C 4.44°–60°C

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 17 Present_Value 85 Full Reference .DAHtgSetpt.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nviDAHtSP DAC No SNVT_temp_p 105

Object Request Keypad Menu Path No Keypad Equivalent This input network variable provides the mechanism to request an operation or a mode for a functional block within a device. A request consists of an object ID (the object_id field) and an object request (the object_request field). The object ID is the functional block index for a functional block on the device. The Node Object functional block is index zero. The remaining functional blocks are numbered sequentially, starting with one.

The following functions are supported: • RQ_NORMAL - If the specified functional block was in the disabled or overridden state, this request cancels that state, and returns the functional block to normal operation. If the functional block was already in the normal state, a request to enter the normal state is not an error. After device reset, the state of functional blocks on the device is application-specific. An RQ_NORMAL request that specifies the Node Object functional block index is a request for all functional blocks in the device to leave the disabled and overridden states.

ED15112-12 73 • RQ_UPDATE_STATUS - Requests the status of the specified functional block to be sent to the nvoStatus output network variable. The state of the functional block is unchanged. An RQ_ UPDATE_STATUS request that specifies the Node Object functional block is a request for the status of the device and all functional blocks on the device. The status bits of the Node Object (with the exception of invalid_request and invalid_id ) are defined to be the inclusive- OR of the status bits of all the other functional blocks in the device; with the possible addition of error conditions and other conditions attributed to the device as a whole, rather than to any individual functional block. For example, if comm_failure is supported for the Node Object, then it should be set when reporting the Node Object functional block status whenever any of the functional blocks in the device reports communications failure, as well as when there is a communications failure at the device level. • RQ_REPORT_MASK - Requests a status mask reporting the status bits that are supported by the specified functional block to be sent to the nvoStatus output network variable. A one bit in the status mask means that the device may set the corresponding bit in the object status when the condition defined for that bit occurs. A zero bit in the status mask means that the bit is never set by the device.

Measurement Units Data Type Valid Range Uses Heartbeat Default Value Object Request N/A Structure N/A No N/A

BACnet

No BACnet equivalent

LON WORKS LonWorks Name Profile Uses Heartbeat SNVT Type SNVT Number nviRequest Node Object No SNVT_obj_status 93

Enumeration Definitions (object_request_t) Value Identifier Notes 0 RQ_NORMAL Enable object and remove override 1 RQ_DISABLED Disable object (not supported) 2 RQ_UPDATE_STATUS Report object status 3 RQ_SELF_TEST Perform object self-test (not supported) 4 RQ_UPDATE_ALARM Update alarm status (not supported) 5 RQ_REPORT_MASK Report status bit mask 6 RQ_OVERRIDE Override object (not supported) 7 RQ_ENABLE Enable object (not supported) 8 RQ_RMV_OVERRIDE Remove object override (not supported) 9 RQ_CLEAR_STATUS Clear object status (not supported) 10 RQ_CLEAR_ALARM Clear object alarm (not supported) 11 RQ_ALARM_NOTIFY_ENABLED Enable alarm notification (not supported) 12 RQ_ALARM_NOTIFY_DISABLED Disable alarm notification (not supported) 13 RQ_MANUAL_CTRL Enable object for manual control (not supported) 14 RQ_REMOTE_CTRL Enable object for remote control (not supported) 15 RQ_PROGRAM Enable programming of special configuration properties (not supported) 16 RQ_CLEAR_RESET Clear reset-complete flag (reset_complete) (not supported) 17 RQ_RESET Execute reset-sequence of object (not supported) -1(0xFF) OC_NUL Invalid Value

Object Status Keypad Menu Path No Keypad Equivalent This output network variable reports the status for any functional block on a device. It is also used to report the status of the entire device and all functional blocks on the device. A status update consists of an object ID (the object_id field) and multiple status fields. The object ID is the functional block index as described under nviRequest . If the object ID is zero, the status of the device itself and all functional blocks on the device is reported. The status fields are one-bit bitfields. The only supported status fields are the report_mask , invalid_id , and invalid_request fields; all other status fields are not supported. • invalid_request - Set to one if an unsupported request code is received on the nviRequest input network variable. • invalid_id - Set to one if a request is received for a functional block index that is not defined in the device. No further checking of the request code is required when set to one.

74 ED15112-12 • report_mask Set to one if an RQ_REPORT_MASK request is received by the nviRequest input network variable, and the nvoStatus output network variable is set to contain the status mask. The status mask is an nvoStatus value that describes the status bits that are supported beyond the three mandatory status bits. The status mask consists of all fields in the nvoStatus output network variable, with the exception of the report_mask , invalid_id , and invalid_request fields. A one bit in the mask means that the functional block may set the corresponding bit in the nvoStatus output network variable when the condition defined for that bit occurs. A zero bit means that the functional block may never set the bit.

Measurement Units Data Type Valid Range Default Value Object Status N/A Structure N/A N/A BACnet

No BACnet equivalent

LON WORKS LonWorks Name Profile Uses Heartbeat SNVT Type SNVT Number nvoStatus Node Object No SNVT_obj_request 92

Field Definitions Field Units Valid Range Notes object_id unsigned long 0 to 65,535 2 bytes invalid_id unsigned 0, 1 1 bit (offset 0) invalid_request unsigned 0, 1 1 bit (offset 1) Disabled unsigned 0, 1 1 bit (offset 2) - Not Used out_of_limits unsigned 0, 1 1 bit (offset 3) - Not Used open_circuit unsigned 0, 1 1 bit (offset 4) - Not Used out_of_service unsigned 0, 1 1 bit (offset 5) - Not Used mechanical_fault unsigned 0, 1 1 bit (offset 6) - Not Used feedback_failure unsigned 0, 1 1 bit (offset 7) - Not Used over_range unsigned 0, 1 1 bit (offset 0) - Not Used under_range unsigned 0, 1 1 bit (offset 1) - Not Used electrical_fault unsigned 0, 1 1 bit (offset 2) - Not Used unable_to_measure unsigned 0, 1 1 bit (offset 3) - Not Used comm_failure unsigned 0, 1 1 bit (offset 4) - Not Used fail_self_test unsigned 0, 1 1 bit (offset 5) - Not Used Self_test_in_progress unsigned 0, 1 1 bit (offset 6) - Not Used locked_out unsigned 0, 1 1 bit (offset 7) - Not Used manual_control unsigned 0, 1 1 bit (offset 0) - Not Used in_alarm unsigned 0, 1 1 bit (offset 1) - Not Used in_override unsigned 0, 1 1 bit (offset 2) - Not Used report_mask unsigned 0, 1 1 bit (offset 3) programming_mode unsigned 0, 1 1 bit (offset 4) - Not Used programming_fail unsigned 0, 1 1 bit (offset 5) - Not Used Alarm_notify_disabled unsigned 0, 1 1 bit (offset 6) - Not Used reset_complete unsigned 0, 1 1 bit (offset 7) - Not Used reserved2 unsigned 0 to 0 8 bits (offset 0) - Not Used

Occupancy Keypad Menu Path Main Menu\View/Set Unit\Occupancy\Occupancy= This read-only property indicates if the unit is currently in an occupied, unoccupied, or tenant override mode of operation.

Measurement Units Data Type Valid Range Default Value Occupancy N/A BACnet: Unsigned Enumerated N/A LonWorks: Real

ED15112-12 75 BACnet Object Identifier Property Object Type Type ID Instance Name ID Multistate Value 19 6 Present_Value 85 Full Reference .EffectOccup.Present_Value Enumeration 1 = Occ 2 = Unocc 3 = TntOvrd

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoEffectOccup DAC, SCC Yes SNVT_occupancy 109 Enumeration Definitions Value Identifier Notes 0 OC_OCCUPIED Area is occupied 1 OC_UNOCCUPIED Area is unoccupied 2 OC_BYPASS Area is temporarily occupied for the bypass period 3 OC_STANDBY Area is temporarily unoccupied 0xFF OC_NUL Value not available

Enumeration Correspondence BACnet Occupancy Lon SNVT_occupancy 1 Occ 0 OC_OCCUPIED 2 Unocc 1 OC_UNOCCUPIED 3 TntOvrd 2 OC_BYPASS 1 Occ 3 OC_STANDBY 3 Auto 0xFF OC_NUL

Occupancy Mode Keypad Menu Path Main Menu\Service Menus\Network Input Status\OccManCmd= This read/write property sets the unit into a different occupancy mode. The request is typically sent by a wall-mounted occupant-interface module or a supervisory node, typically used to manually control occupancy modes or to override the scheduled occupancy. This input is used with nviOccSchedule to determine the effective occupancy mode. Refer to Occupancy (nvoEffectOccup) section for more information.

Measurement Units Data Type Valid Range Uses Heartbeat Default Value Mode N/A BACnet: Unsigned Enumerated No Auto or NUL LonWorks: Real

BACnet Object Identifier Property Object Type Type ID Instance Name ID Multistate Value 19 7 Present_Value 85 Full Reference .OccManCmd.Present_Value Enumeration 1 = Occ 2 = Unocc 3 = TntOvrd 4 = Standby (Same as Occ) 5 = Auto

76 ED15112-12 LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nviOccManCmd DAC, SCC No SNVT_occupancy 109 Enumeration Definitions Value Identifier Notes 0 OC_OCCUPIED Area is occupied 1 OC_UNOCCUPIED Area is unoccupied 2 OC_BYPASS Area is temporarily occupied for the bypass period 3 OC_STANDBY Controller reacts as if the area is occupied. 0xFF OC_NUL Value not available

Enumeration Correspondence BACnet nviOccManCmd Lon SNVT_occupancy 1 Occ 0 OC_OCCUPIED 2 Unocc 1 OC_UNOCCUPIED 3 TntOvrd (Bypass) 2 OC_BYPASS 1 Occ 3 OC_STANDBY 4 Auto 0xFF OC_NUL

Occupancy Scheduler Input Keypad Menu Path Main Menu\Service Menus\Network Input Status\NetCurrState= Main Menu\Service Menus\Network Input Status\NetNextState= Main Menu\Service Menus\Network Input Status\NetTmToNxtSt= This read/write property commands the occupancy function of the MicroTech III Unit Controller when Occupancy Mode is set to Auto. A scheduler or a supervisory node typically sends the request. SNVT_tod_event is a structure containing three parts.  Current_state, (required)  Next_state (optional)  Time_to_next_state (optional) This network variable is used in conjunction with Optimal Start. If time_to_next_state is not valid, the unit controller uses an internal calculation to determine when the unit will start. Consequently, if time_to_next_state is valid, the unit controller uses this time to determine when the unit will start. This input is used in conjunction with nviOccManCmd (Occupancy Mode) to determine the effective occupancy mode. Refer to Occupancy Mode for more information.

Measurement Units Data Type Valid Range Uses Heartbeat Default Value State N/A BACnet: Unsigned Enumerated Yes N/A LonWorks: Real BACnet Object Identifier Property Object Type Type ID Instance Name ID Multistate Value 19 8 Present_Value 85 Full Reference .CurrentState.Present_Value Enumeration 1=Occ 2=Unocc 3=TntOvrd (not used) 4=Standby (not used) 5=Auto(NUL) Object Type Type ID Instance Name ID Object Identifier Property Multistate Value 19 9 Present_Value 85 Full Reference .NextState.Present_Value

ED15112-12 77 Enumeration 1=Occ 2=Unocc 3=TntOvrd (not used) 4=Standby (not used) 5=Auto(NUL)

Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 3 Present_Value 85 Full Reference .TimeToNextState.Present_Value LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nviOccSchedule DAC, SCC Yes SNVT_tod_event 128

Field Definitions Field Data Point Reference Units Valid Range Notes current_state Occupancy Scheduler Input occup_t current scheduled occupancy state next_state Occupancy Scheduler Next occup_t next scheduled occupancy state time_to_next_state Occupancy Scheduler Time minutes 0 to 65534 65535=Null

Enumeration Definitions (occup_t) Value Identifier Notes 0 OC_OCCUPIED Area is occupied 1 OC_UNOCCUPIED Area is unoccupied 2 OC_BYPASS Area is temporarily occupied for the bypass period 3 OC_STANDBY Area is temporarily unoccupied 0xFF OC_NUL Value not available

Enumeration Correspondence BACnet LON WORKS 1 Occupied 0 OC_OCCUPIED 0 Unoccupied 1 OC_UNOCCUPIED 3 TntOvrd 2 OC_BYPASS 1 Occupied 3 OC_STANDBY 5 NUL 0xFF OC_NUL

Occupied Cooling Setpoint Keypad Menu Path Main Menu\View/Set Unit\Cooling\Occ Clg Spt= This read/write configuration property sets the Occupied Cooling Setpoint is set to this value when it is not being set by another function. This attribute uses maximum and minimum limits. If the Present Value is set beyond these limits from the network, the value is ignored and the controller continues to control to the last valid value. The BACnet property only applies to the subject data point, but the LON WORKS variable is a structure that covers three other data points: Unoccupied Cooling Setpoint, Occupied Heating Setpoint, and Unoccupied Heating Setpoint. Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real 0.0°–100.0 °F / -17.78°–37.78°C 72°F / 22.22°C BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 9 Present_Value 85 Full Reference .OccCoolSP.Present_Value

78 ED15112-12 LON WORKS LON WORKS Name Profile SCPT Reference SCPT Index SNVT Type SNVT Index nciSetpoints.Occupied_Cool DAC, SCC SCPTsetPnts 60 SNVT_temp_setpt 106

Field Definitions Field Notes Occupied_cool Occupied Cooling Setpoint Standby_cool Standby Cooling Setpoint (Not Used) Unoccupied_cool Unoccupied Cooling Setpoint Occupied_heat Occupied Heating Setpoint Standby_heat Standby Heating Setpoint (Not Used) Unoccupied_heat Unoccupied Heating Setpoint

Occupied Heating Setpoint Keypad Menu Path Main Menu\View/Set Unit\Heating\Occ Htg Spt= This read/write configuration property sets the Occupied Heating Setpoint. The Effective Heating Enable Setpoint is set to this value when it is not being set by any other function. This attribute uses maximum and minimum limits. If the Present Value is set beyond these limits from the network, the value is ignored and the controller continues to control to the last valid value. The BACnet property only applies to the subject data point, but the LON WORKS variable is a structure that covers three other data points: Occupied Cooling Setpoint, Unoccupied Cooling Setpoint, and Unoccupied Heating Setpoint.

Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real 0.0°–100.0 °F 68°F / 20°C -17.78°–37.78°C

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 11 Present_Value 85 Full Reference .OccHeatSP.Present_Value

LON WORKS LON WORKS Name Profile SCPT Reference SCPT Index SNVT Type SNVT Index nciSetpoints.occupied_heat DAC, SCC SCPTsetPnts 60 SNVT_temp_setpt 106

Field Definitions Field Notes Occupied_cool Occupied Cooling Setpoint Standby_cool Standby Cooling Setpoint (Not Used) Unoccupied_cool Unoccupied Cooling Setpoint Occupied_heat Occupied Heating Setpoint Standby_heat Standby Heating Setpoint (Not Used) Unoccupied_heat Unoccupied Heating Setpoint

Outdoor Air Damper Minimum Position Input Keypad Menu Path Main Menu\Service Menus\Network Input Status\Net Min OA= This read/write configuration property sets the Outdoor Air Damper Minimum Position setpoint for MicroTech III Unit Controller. The Minimum Outdoor Air Damper Position Input setpoint uses this value when it is not being set by any other function and when Min OA Type is set to Network. The controller internally limits the Present Value that is written between the DCV Limit and the Vent Limit (see the Min OA Damper menu on the keypad/display). This variable only applies to units configured with an airside economizer.

Measurement Units Data Type Valid Range Uses Heartbeat Default Value Position Percent Real 0–100% No N/A

ED15112-12 79 BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 16 Present_Value 85 Full Reference .MinOAPosNetIn.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nviOAMinPos DAC, SCC No SNVT_lev_percent 81

Outdoor Air Temperature Keypad Menu Path Main Menu\Quick Menu\OA Temp= Main Menu\View/Set Unit\Temperatures\OA Temp= This read-only attribute indicates the current value of a unit-mounted outdoor air temperature sensor. This variable only applies if the unit is configured for an outdoor air temperature sensor.

Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real -50°–150°F N/A -45.56°-65.56°C

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 4 Present_Value 85 Full Reference .OutdoorTemp.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoOutdoorTemp DAC, SCC Yes SNVT_temp_p 105

Outdoor Air Temperature Input Keypad Menu Path Main Menu\Service Menus\Network Input Status\Net OAT In= This read/write property is used to write the outdoor air temperature from the network. If you are using one temperature sensor to determine the outdoor air temperature for the entire network, you can write the temperature to this property. This variable only applies if the unit is configured for an outdoor air temperature sensor, and reverts to the Null value if written out of range.

Measurement Units Data Type Valid Range Uses Heartbeat Default Value Temperature °F / °C Real -50°–150°F Yes 327.67 (Null) -45.56°-65.56°C

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 29 Present_Value 85 Full Reference .OutdoorTempInput.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nviOutdoorTemp DAC, SCC Yes SNVT_temp_p 105

80 ED15112-12 Outdoor Airflow Keypad Menu Path Main Menu\Commission Unit\Min OA Set-Up\OA Flow= This read-only property indicates the Outdoor Airflow. This variable only applies to units configured for design flow.

Measurement Units Data Type Valid Range Default Value Flow Volume ft 3/min (CFM) or l/s BACnet: Real 0-60007.25 CFM N/A LonWorks: Unsigned Long 0-28320 l/s

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 42 Present_Value 85 Full Reference .OAFlow.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoOAFlow DAC, Yes SNVT_flow 15 Daikin AppliedRTU-SCC

Outdoor Airflow Setpoint Keypad Menu Path Main Menu\View/Set Unit\Min OA Set-Up\MinOAFlw Spt= This read/write property indicates the setpoint of Outdoor Airflow. This variable only applies to units configured for design flow.

Measurement Units Data Type Valid Range Default Value Flow Volume ft 3/min (CFM) or l/s BACnet: Real 0-60007.25 2000 CFM/943.9 1/s CFM 0-28320 l/s

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 53 Present_Value 85 Full Reference .MinOAFlowSpt.Present_Value

LON WORKS No LON WORKS equivalent.

Outdoor Refrigerant Temperature Keypad Menu Path No Keypad Equivalent This read-only attribute indicates the current outdoor refrigerant temperature from the outdoor refrigerant temperature sensor. This variable only applies if the unit is configured for heat pump operation. Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real -50°–150°F N/A -45.56°-65.56°C

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 28 Present_Value 85 Full Reference .OutdoorRefTemp.Present_Value

ED15112-12 81 LON WORKS No LON WORKS equivalent.

Primary Cool Enable Keypad Menu Path Main Menu\Service Menus\Network Input Status\Net Cl Ena Sw= Main Menu\Service Menus\Network Input Status\\Net Cl Ena Vl= This read/write configuration property enables or disables the primary cooling. This variable only applies if the unit is configured for mechanical cooling. In BACnet, if CoolEnable is 0, then the primary cooling is disabled. If it is 1 and CoolEnablePct is 0, the primary cooling is disabled. If CoolEnable is 1 and CoolEnablePct is greater than 0, the primary cooling is enabled. When cooling is enabled, CoolEnablePct reflects the percentage of cooling that is enabled. The LON WORKS variable nviPriCoolEnable has two properties; a State and a Value. When the State = 0, primary cooling control is disabled through the network. When State = 1, the primary cooling can be controlled through the network. When the Value = 0 and the State = 1, the primary cooling is disabled through the LON WORKS network. When the Value is greater than 0 and the State = 1, the primary cooling is enabled through the LON WORKS network.

Measurement Units Data Type Valid Range Uses Heartbeat Default Value State N/A BACnet: Real LON WORKS : Enumerated Yes N/A LON WORKS : Structure

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 34 Present_Value 85 Full Reference .CoolEnable.Present_Value Enumeration 0 = Off 1 = Enable

Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 35 Present_Value 85 Full Reference .CoolEnablePct.Present_Value

LON WORKS LonWorks Name Profile Uses Heartbeat SNVT Type SNVT Number nviPriCoolEnable DAC, Yes SNVT_switch 95 Daikin AppliedRTU- SCC Valid Range State Value Cooling 0 N/A Disabled 1 0 Disabled 1 1-100 Enabled. Value equals the percentage of cooling that is enabled when State equals 1. -1(0xFF) N/A Auto (invalid)

Primary Heat Enable Keypad Menu Path Main Menu\Service Menus\Network Input Status\\Net Ht Ena Sw= Main Menu\Service Menus\Network Input Status\\Net Ht Ena Vl= This read/write configuration property enables or disables the primary heating. This variable only applies if the unit is configured for heating. In BACnet, if HeatEnable = 0, then the primary heating is disabled. If it HeatEnable = 1 and HeatEnablePct = 0, the primary heating is disabled. If HeatEnable = 1 and HeatEnablePct is greater than 0, the primary

82 ED15112-12 heating is enabled. When heating is enabled, HeatEnablePct reflects the percentage of heating that is enabled. The LONWORKS variable nviPriHeatEnable has two properties; a State and a Value. When the State = 0, primary heating control is disabled through the network. When State = 1, the primary heating can be controlled through the network. When the Value = 0 and the State = 1, the primary heating is disabled through the LONWORKS network. When the Value is greater than 0 and the State = 1, the primary heating is enabled through the LONWORKS network.

Measurement Units Data Type Valid Range Uses Heartbeat Default Value State N/A BACnet: Real BACnet: 0-1 Yes N/A LON WORKS : Structure LonWorks: Enumerated

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 36 Present_Value 85 Full Reference .HeatEnable.Present_Value Enumeration 0 = Off 1 = Enable

Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 37 Present_Value 85 Full Reference .HeatEnablePct.Present_Value

LON WORKS LonWorks Name Profile Uses Heartbeat SNVT Type SNVT Number nviPriHeatEnable DAC, Yes SNVT_switch 95 Daikin AppliedRTU- SCC Valid Range State Value Heating 0 N/A Disabled 1 0 Disabled 1 1-100 Enabled. Value equals the percentage of cooling that is enabled when State equals 1. -1(0xFF) N/A Auto (invalid)

Receive Heartbeat Keypad Menu Path Main Menu\BMS Communications\LON Set-Up\Rcv Hrt Bt= This read/write configuration property defines the maximum time that elapses after the last update to a specified network variable input before the unit starts to use its default values.

Measurement Units Data Type Valid Range Default Value Time Seconds BACnet: Real 0.0–6553.4 sec 0 seconds LonWorks: Unsigned Long

The only variables that use Receive Heartbeat are: LON WORKS Variable LON WORKS Variable nviOccSchedule nviEconEnable nviApplicCmd nviExhFanCap nviSupFanCap nviRetFanCap nviOutdoorTemp nviCWFlow nviSpaceTemp nviSpaceIAQ nviPriCoolEnable nviSpaceRH

ED15112-12 83 LON WORKS Variable LON WORKS Variable nviPriHeatEnable

BACnet* Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 43 Present_Value 85 Full Reference .ReceiveHeartbeat.Present_Value *Note: This point is not supported for BACnet with MicroTech III unit controller application version 2506017300 or newer.

LON WORKS There are three categories for deciding to use Receive Heartbeat that are based on the network input variable being specified in the Receive Heartbeat table and being bound. The unit controller uses Category 1 and Category 2.

Network Specified for Receive Bound? Result: Use Receive Variable Input Heartbeat in Table? Heartbeat? Category 1 Yes Yes Yes Category 2 Yes No Manufacture Defined Category 3 Yes Don’t Care No

LON WORKS Name Profile SNVT Type SNVT Index SCPT Reference SCPT Index nciRcvHrtBt DAC, SCC SNVT_time_sec 107 SCPTmaxRcvTime 48

Reheat Capacity Keypad Menu Path Main Menu\Quick Menu\Reheat Cap= Main Menu\View/Set Unit\Unit Status/Settings\Reheat Cap= Main Menu\View/Set Unit\Dehumidification\Reheat Cap= This read-only attribute indicates the current percentage of unit reheat capacity. The BACnet property reads only the subject attribute and only applies to the subject data point. The LON WORKS variable is only a part of the LON WORKS Unit Status network variable. See Unit State for details. The LON WORKS variable covers six other data points: Unit State, Supply Fan Capacity, Cooling Capacity, Heating Capacity, Economizer Capacity, and In Alarm. This variable only applies to units configured with cooling.

Measurement Units Data Type Valid Range Default Value Reheat Capacity Percent BACnet: Real 0.0–100.0% N/A LonWorks: Structure

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 44 Present_Value 85 Full Reference .ReheatCapacity.Present_Value

LON WORKS LonWorks Name Profile Uses Heartbeat SNVT Type SNVT Index nvoUnitStatus.heat_output_secondary DAC, SCC Yes SNVT_hvac_status 112

Relative Humidity Keypad Menu Path Main Menu\Quick Menu\Rel Humidity= Main Menu\View/Set Unit\Unit Status/Settings\Rel Humidity= Main Menu\View/Set Unit\Dehumidification\Rel Humidity= Main Menu\Commission Unit\Energy Rec Set-Up\Rel Humidity= This read-only property indicates the current reading of the optional relative humidity sensor.

84 ED15112-12 Measurement Units Data Type Valid Range Default Value Relative Humidity Percent Real 0%–100% N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 11 Present_Value 85 Full Reference .SpaceRH.Present_Value

Enumeration 1=DSP 2=Speed 3=Space LON WORKS LonWorks Name Profile Uses Heartbeat SNVT Type SNVT Index nvoSpaceRH DAC, SCC Yes SNVT_lev_percent 81 Enumeration 0=DSP 1=Speed 2=Space

Relative Humidity Input Keypad Menu Path Main Menu\Service Menus\Network Input Status\Net Rel Humid= This is a read/write property that the network can use to set the relative humidity from the network. If the network value becomes unreliable, the humidity reverts to the value provided by the attached relative humidity sensor

Measurement Units Data Type Valid Range Uses Heartbeat Default Value Relative Humidity Percent Real 0%–100% Yes 163.835 (Null)

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 19 Present_Value 85 Full Reference .SpaceRHNetIn.Present_Value

LON WORKS LonWorks Name Profile Uses Heartbeat SNVT Type SNVT Index nviSpaceRH DAC, SCC Yes SNVT_lev_percent 81

Relative Humidity Setpoint Keypad Menu Path Main Menu\View/Set Unit\Dehumidification\RH Setpoint= This is a read/write property that the network can use to set the relative humidity setpoint from the network. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Relative Humidity Percent Real 0%–100% No N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 40 Present_Value 85 Full Reference .HumiditySP.Present_Value

ED15112-12 85 LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nviSpaceDehumSP DAC, No SNVT_lev_percent 81 Daikin AppliedRTU- SCC

Remote Return/Exhaust Fan Capacity Control Flag Keypad Menu Path Main Menu\Commission Unit\RF/EF Set-Up\RF/EF Ctrl= This read/write property selects the return or exhaust fan airflow control. If the unit is equipped with return fan VFD and this property is set to Tracking, the return fan airflow is controlled based on an adjustable tracking relationship between the supply fan and return fan airflow. If this parameter is set to Building, the return or exhaust fan airflow is controlled independently of the supply fan airflow to maintain the building static pressure at a building static pressure set point. If this parameter is set to Speed, the return or exhaust fan airflow is controlled to a VFD speed set point set via the Return Fan Capacity Input. If this parameter is set to OAD, the exhaust fan airflow is controlled independently of the supply fan airflow based on the outdoor air damper position. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Mode N/A BACnet: Unsigned Enumerated No N/A LonWorks: Real

BACnet Object Identifier Property Object Type Type ID Instance Name ID Multistate Value 19 12 Present_Value 85 Full Reference .ExhRetFanCtrl.Present_Value Enumeration 1 = None 2 = Tracking 3 = BldgP 4 = Speed 5 = OAD

LON WORKS LON WORKS Name Profile Uses Heartbeat UNVT Type SNVT Index nviExhRetFanCtrl Daikin No UNVTexhRetFanCtrl N/A AppliedDischargeAir, Daikin AppliedRTU- SCC Enumeration 0 = None 1 = Tracking 2 = Bldg Pres 3 = Speed 4 = OAD

Remote Supply Fan Capacity Control Flag Keypad Menu Path Main Menu\SAF Set-Up\SAF Ctrl= This read/write property selects the supply fan airflow control used on a unit equipped with a variable volume supply air fan. If this parameter is set to Duct Static Pressure (DSP), the supply fan airflow maintains the duct static pressure at the duct static pressure set point. If this parameter is set to Speed, the supply fan airflow is controlled to a VFD speed set via the Supply Fan Capacity Input. If this is set to 1ZnVAV the supply fan airflow is controlled to maintain the Control Temperature at the Occupied Cooling Setpoint or the Occupied Heating Setpoint depending on the Unit State. If this is set to Building Static Pressure (BSP), the supply fan airflow maintains the building static pressure at the building static pressure set point. If this is set to Carbon Dioxide (CO2), the supply fan airflow maintains the CO2 level between adjustable limits. If this is set to Airlow (CFM), the supply fan airflow maintains the CFM level at the Outdoor Air Damper Minimum Position setpoint.

86 ED15112-12 Note: BSP, CO2 and CFM can only be selected if the unit is configured for 100% OA operation or if the unit is an SCU unit not configured for airside economizer operation.

Measurement Units Data Type Valid Range Uses Heartbeat Default Value Method N/A BACnet: Unsigned Enumerated No N/A LonWorks: Real BACnet Object Identifier Property Object Type Type ID Instance Name ID Multistate Value 19 11 Present_Value 85 Full Reference .SupFanCtrl.Present_Value Enumeration 1 = DSP (Only applies when unit is not configured for 1ZnVAV operation) 2 = Speed 3 = 1ZnVAV (Only applies if unit is configured for single zone VAV operation) 4 = BSP (Only applies when unit is not configured for 1ZnVAV operation and unit is configured for 100% OA operation or SCU unit without airside economizer.) 5 = CO2 (Only applies when unit is not configured for 1ZnVAV operation and unit is configured for 100% OA operation or SCU unit without airside economizer.) 6 = CFM (Only applies when unit is not configured for 1ZnVAV operation and unit is configured for 100% OA operation or SCU unit without airside economizer.)

LON WORKS LON WORKS Name Profile Uses Heartbeat UNVT Type SNVT Index nviSupFanCtrl Daikin No UNVTsupFanCtrl N/A AppliedDischargeAir Enumeration 0 = DSP (Only applies when unit is not configured for 1ZnVAV operation) 1 = Speed 2 = 1ZnVAV (Only applies if unit is configured for single zone VAV operation) 3 = BSP (Only applies when unit is not configured for 1ZnVAV operation and unit is configured for 100% OA operation or SCU unit without airside economizer.) 4 = CO2 (Only applies when unit is not configured for 1ZnVAV operation and unit is configured for 100% OA operation or SCU unit without airside economizer.) 5 = CFM (Only applies when unit is not configured for 1ZnVAV operation and unit is configured for 100% OA operation or SCU unit without airside economizer.)

Return Air Temperature Keypad Menu Path Main Menu\View/Set Unit\Temperatures\Return Air= This read-only attribute that indicates the current reading from the unit return air temperature sensor. This variable only applies if the unit is configured for a return air sensor. Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real -20°–199.994°F N/A -28.89°–93.33°C

ED15112-12 87 BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 2 Present_Value 85 Full Reference .RATemp.Present_Value

The Present Value of the object below will be the same as the Present Value for AI2 above. This object is only present for intrinsic reporting of the High Return Air Temperature alarm. Though this object is commandable, the controller commands this object at priority 1 to avoid the BAS from writing to this and therefore disabling the high limit alarm. Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 45 Present_Value 85 Full Reference .HiRAT.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoRATemp DAC, Yes SNVT_temp_p 105 Daikin AppliedRTU- SCC Return/Exhaust Fan Capacity Keypad Menu Path Main Menu\Quick Menu\RF/EF Speed= Main Menu\View/Set Unit\Unit Status/Settings\RF/EF Speed= Main Menu\View/Set Unit\RF\EF Spd Control\RF/EF Speed= This read-only attribute indicates the current return fan or exhaust fan capacity. This variable only applies to units configured with a return/exhaust fan.

Measurement Units Data Type Valid Range Default Value Fan Capacity Percent BACnet: Real 0-100% N/A LON WORKS : Structure

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 10 Present_Value 85 Full Reference .ExhFanValue.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoExhFanStatus.value DAC, No SNVT_switch N/A Daikin AppliedRTU- SCC Field Definitions Field Units Valid Range Notes value % of Full Scale 0-100% 0-100% state N/A 0, 1 0=Off, 1=On

Return/Exhaust Fan Hours Keypad Menu Path Main Menu\View/Set Unit\Service\Operating Hours\Ret/Exh Fan= Main Menu\View/Set Unit\Unit Maintenance\Operating Hours\Ret/Exh Fan= This read/write property indicates the return or exhaust fan accumulated run hours. It can be reset via the network. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Time Hrs Real 0–50000 Hrs No N/A

88 ED15112-12

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 101 Present_Value 85 Full Reference .RF_EFHrs.Present_Value LON WORKS No LON WORKS equivalent.

Return Fan Capacity Input Keypad Menu Path Main Menu\Commission Unit\RF/EF Set-Up\Rem RAF Cap= This read/write property sets the return/exhaust air VFD speed when Remote Return/Exhaust Fan Capacity Control Flag property is set to Speed. This variable only applies to units that are configured for a modulating return fan. This attribute uses maximum and minimum limits. If the Present Value is set beyond these limits from the network, the value is ignored and the unit controller continues to control to the last valid value.

Measurement Units Data Type Valid Range Uses Heartbeat Default Value Fan Capacity Percent Real 0–100% Yes N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 22 Present_Value 85 Full Reference .RetFanCapNetIn.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nviRetFanCap DAC, Daikin AppliedRTU- Yes SNVT_lev_percent 81 SCC

Send Heartbeat Keypad Menu Path Main Menu\BMS Communications\LON Set-Up\SndHrtBt= This read/write configuration property defines maximum period of time that expires before the specified network variable output is automatically updated.

Measurement Units Data Type Valid Range Default Value Time Seconds Fixed Point Scalar - unsigned long 0.0–6553.4 sec 60 seconds BACnet No BACnet equivalent. LON WORKS The ability to send a heartbeat is a requirement for LON WORKS devices. Network variable outputs for Send Heartbeat are defined in one of two categories based on whether or not they are specified in the Send Heartbeat table.

Network Variable Output Specified for Send Heartbeat in Table? Result: Use Send Heartbeat? Category 1 Yes Yes Category 2 No Manufacture Defined

The network input variables that use Send Heartbeat are: Send Heartbeat Table nvoMcQAHUStatus nvoLocalOATemp nvoEffDATempSp nvoUnitStatus nvoEFT_LCT nvoEffectSetpt nvoEffectOccup nvoDuctStatPress nvoExhFanStatus nvoDischAirTemp nvoBldgStatPress nvoConductivity nvoRATemp nvoSpaceRH nvoMATemp nvoSpaceTemp nvoSpaceDewPt nvoCWTemp

ED15112-12 89 nvoOutdoorTemp nvoSpaceCO2 nvoOAFlow nvoLocalSpaceTmp

A value of 0 disables the auto update. LON WORKS Name Profile SNVT Type SNVT Index SCPT Reference SCPT Index nciSndHrtBt DAC, SCC SNVT_time_sec 107 SCPTmaxSendTime 49

Space CO 2 Keypad Menu Path Main Menu\Commission Unit\Min OA Set-Up\IAQ PPM= This read-only attribute indicates the current space CO 2 level from the optional space CO 2 sensor. This value reflects the network input nviSpaceIAQ (if valid) or the value from a locally wired sensor if Min OA Type is set to IAQ VDC or IAQ mA. This variable only applies if the unit is configured for an airside economizer and Min OA Type is set to IAQ VDC or IAQ mA.

Measurement Units Data Type Valid Range Default Value Concentration ppm Real 0-5000 ppm N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 13 Present_Value 85 Full Reference .SpaceCO2.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoSpaceCO2 SCC, Daikin Yes SNVT_ppm 29 AppliedDischargeAir

Space IAQ Input Keypad Menu Path Main Menu\Service Menus\Network Input Status\Net Space IAQ=

This read/write attribute indicates the current space CO 2 level from the network. This value takes priority over a locally wired sensor. This variable only applies if Min OA Type is set to IAQ VDC or IAQ mA. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Concentration ppm Real 0-5000 ppm Yes 32767 (Null)

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 31 Present_Value 85 Full Reference .SpaceIAQNetIn.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nviSpaceIAQ SCC, Daikin Yes SNVT_ppm 29 AppliedDischargeAir

Space Temperature Keypad Menu Path Main Menu\View/Set Unit\Temperatures\Space Temp= This read-only attribute indicates the current space or zone temperature from the optional space air temperature sensor. This variable only applies if the unit is configured for a space temperature sensor.

90 ED15112-12 Note: If the optional space temperature sensor is not installed and a BACnet or LONWORKS network is not writing to the space temperature, the Space Sensor attribute in the Unit Configuration menu of the keypad/display should be set to No to disable the alarm function associated with an open circuit at the space temperature sensor input.

Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real 0°–150°F N/A -17.78°-65.56°C

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 3 Present_Value 85 Full Reference .SpaceTemp.Present_Value LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoSpaceTemp DAC, SCC Yes SNVT_temp_p 105

Space Temperature Input Keypad Menu Path Main Menu\Service Menus\Network Input Status Net SpaceT In= This read/write attribute indicates the current space or zone temperature that is written from the network. If this network value becomes unreliable, the temperature reverts to the value provided by the attached Space Temperature sensor. This variable only applies if the unit is configured for a space temperature sensor.

Measurement Units Data Type Valid Range Uses Heartbeat Default Value Temperature °F / °C Real 0°–150°F (BACnet) Yes 327.67 (Null) -17.78°–65.56°C (BACnet) 14°–122°F (LonWorks) -10°–50°C (LonWorks)

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 28 Present_Value 85 Full Reference .SpaceTempInput.Present_Value LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nviSpaceTemp DAC, SCC Yes SNVT_temp_p 105 Staged Exhaust 1 Hours Keypad Menu Path Main Menu\View/Set Unit\Service\Operating Hours\Exh Out 1= Main Menu\View/Set Unit\Unit Maintenance\Operating Hours\Exh Out 1= This read/write property indicates the first stage exhaust fan accumulated run hours. It can be reset via the network. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Time Hrs Real 0–50000 Hrs No N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 102 Present_Value 85 Full Reference .StgExh1Hrs.Present_Value

ED15112-12 91 LON WORKS No LON WORKS equivalent.

Staged Exhaust 2 Hours Keypad Menu Path Main Menu\View/Set Unit\Service\Operating Hours\Exh Out 2= Main Menu\View/Set Unit\Unit Maintenance\Operating Hours\Exh Out 2= This read/write property indicates the second stage exhaust fan accumulated run hours. It can be reset via the network. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Time Hrs Real 0–50000 Hrs No N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 103 Present_Value 85 Full Reference .StgExh2Hrs.Present_Value LON WORKS No LON WORKS equivalent.

Suction Refrigerant Pressure Keypad Menu Path Main Menu\Commission Unit\INV Cmp Set-Up\PTS= Main Menu\Commission Unit\OAFan Set-Up\PTS= Main Menu\Commission Unit\Exp Valve Set-Up\PTS=

This read-only property indicates the current reading of the unit suction refrigerant pressure sensor.

Measurement Units Data Type Valid Range Default Value Temperature PSI/kPa Real 0.0–725.2PSI N/A 0.0–5000.0kPa BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 25 Present_Value 85 Full Reference .RefSuctionP.Present_Value LON WORKS No LON WORKS equivalent.

Suction Line Refrigerant Temperature Keypad Menu Path Main Menu\View/Set Unit\Temperatures\DFT= This read-only property indicates the current reading of the unit suction line refrigerant temperature sensor. This property applies only to Rebel units.

Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real -50.0–200.0°F N/A -45.56°–93.33°C BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 24 Present_Value 85 Full Reference .SucnRefTemp.Present_Value LON WORKS No LON WORKS equivalent.

92 ED15112-12

Sump Pump Water Level Switch Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Sump Pump Water Level Switch (Closed (1) or Open (0)). The OffNormal state of this object indicates a Sump Water Level Problem.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 16 Present_Value 85 Full Reference .SmpWtrLvlSw.Present_Value Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent.

Supplemental Heating Capacity Keypad Menu Path Main Menu\Quick Menu\Supl Htg Cap= Main Menu\View/Set Unit\Unit Status/Settings\Supl Htg Cap= This read-only attribute indicates the current percentage of supplemental heating capacity. This point only applies if the unit is configured as a Rebel unit with heat pump and the unit is configured with heat. In this case, the heating capacity will be the compressor heat from the heat pump and the supplemental heating capacity is the additional heating from the unit. The BACnet property reads only the subject attribute and only applies to the subject data point. The LON WORKS variable is only a part of the LON WORKS Unit Status network variable. See Unit State for details of LON WORKS network variable. The LON WORKS variable covers six other data points: Unit State, Supply Fan Capacity, Secondary Heating (Reheat or Supplemental heat) Capacity, Economizer Capacity, and In Alarm. This variable only applies to units configured with heating. Measurement Units Data Type Valid Range Default Value Heating Capacity Percent BACnet: Real 0.0–100.0% N/A LonWorks: Structure

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 54 Present_Value 85 Full Reference .SuplHtgCap.Present_Value

LON WORKS LonWorks Name Profile Uses Heartbeat SNVT Type SNVT Index nvoUnitStatus.heat_output_ secondary DAC, SCC Yes SNVT_hvac_status 112

Supplemental Heating Status Keypad Menu Path Main Menu\View/Set Unit\Unit Status/Settings\SuplHtgStatus= This read-only attribute indicates the current status of supplemental heating. This point only applies if the unit is configured as a Rebel unit with heat pump and the unit is configured with heat. In this case, the heating status will be the compressor heat from the heat pump and the supplemental heating status is the additional heating from the unit. Measurement Units Data Type Valid Range Default Value State N/A BACnet: Unsigned Enumerated N/A LonWorks: Real

ED15112-12 93 BACnet Object Identifier Property Object Type Type ID Instance Name ID Multistate Value 19 45 Present_Value 85 Full Reference .SuplHtgStatus.Present_Value Enumeration 1=Enabled 2=None 3=Off Amb 4=Off Alarm (Not Used) 5=Off Net 6=Off Man

LON WORKS No Equivalent LonWorks point.

Supply Fan Capacity Keypad Menu Path Main Menu\SAF Speed= Main Menu\View/Set Unit\Unit Status/Settings\SAF Speed= Main Menu\View/Set Unit\SAF Spd Control\SAF Speed= This read-only attribute indicates the current supply fan capacity. The BACnet property reads only the subject attribute; however the LON WORKS variable is only a part of the LON WORKS Unit Status network variable. See Unit State for details. This variable will read 0% whenever the fan is off. If the unit is configured as constant volume, this variable reads 100% when the fan is on. Otherwise it will read the feedback from the VFD. The BACnet property only applies to the subject data point. The LON WORKS variable covers six other data points: Unit State, Cooling Capacity, Heating Capacity, Reheat Capacity, Economizer Capacity, and In Alarm. Measurement Units Data Type Valid Range Default Value Supply Fan Capacity Percent BACnet: Real 0-110% N/A LON WORKS : Structure

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Input 0 8 Present_Value 85 Full Reference .FanSpd.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoUnitStatus.fan_output DAC, SCC Yes SNVT_hvac_status 112

Supply Fan Capacity Input Keypad Menu Path Main Menu\Service Menus\Network Input Status\Rem SAF Cap= This read/write property sets the discharge air VFD speed when the Supply Fan Capacity Control Flag is set to Speed. This attribute uses maximum and minimum limits. If the Present Value is set beyond these limits from the network, the value is ignored and the unit controller continues to control to the last valid value.

Measurement Units Data Type Valid Range Uses Heartbeat Default Value Fan Capacity Percent Real 0–100 % Yes N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 21 Present_Value 85

94 ED15112-12 Full Reference .SupFanCapNetIn.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nviSupFanCap DAC Yes SNVT_lev_percent 81 Supply Fan Hours Keypad Menu Path Main Menu\View/Set Unit\Service\Operating Hours\Supply Fan= Main Menu\View/Set Unit\Unit Maintenance\Operating Hours\Supply Fan= This read/write property indicates the supply fan accumulated run hours. It can be reset via the network. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Time Hrs Real 0–50000 Hrs No N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 100 Present_Value 85 Full Reference .SupplyFanHrs.Present_Value LON WORKS No LON WORKS equivalent. Temperature Setpoint Input Keypad Menu Path Main Menu\Service Menus\Network Input Status\nviSetpoint= This read/write property is only used in LON WORKS networks. It determines the Effective Setpoint Output. If the value is valid, the Effective Setpoint Output is determined by this value. If the value is not valid, the Effective Setpoint Output does not depend on this value (If a value greater than 37.7°C (100.0°F) is written, this value will be considered invalid and the value from the network is ignored. The unoccupied setpoints are not changed.

Note: On space comfort control units the Space Setpoint Type must not be set to Tstat, otherwise the space setpoint adjustment on the optional space sensor overrides the Temperature Setpoint Input (nviSetpoint).

Measurement Units Data Type Valid Range Uses Heartbeat Default Value Temperature °F / °C Fixed Point Scalar - signed long -17.78°–37.7°C No N/A

BACnet No BACnet equivalent. LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nviSetpoint SCC, Daikin No SNVT_temp_p 105 AppliedDischargeAir Tenant Override Hours Keypad Menu Path Main Menu\View/Set Unit\Service\Operating Hours\Tnt Override= Main Menu\View/Set Unit\Unit Maintenance\Operating Hours\Tnt Override= This read/write property indicates the tenant override operation accumulated run hours. It can be reset via the network. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Time Hrs Real 0–50000 Hrs No N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 118 Present_Value 85 Full Reference .TenantORHrs.Present_Value

ED15112-12 95 LON WORKS No LON WORKS equivalent.

Time Keypad Menu Path Main Menu\View/Set Unit\Date/Time/Schedules\Time= This read/write property sets the current time of the form hours, minutes, seconds, and hundredths of a second. See ANSI/ASHRAE 135-2008 for a definition of the data type. Measurement Units Data Type Valid Range Default Value Time hours, minutes, seconds, BACnet time data types N/A N/A and hundredths of a second

BACnet Object Identifier Property Object Type Type ID Instance Name ID Device 8 Variable Local Time 57 Full Reference .Local Time

Unit State Keypad Menu Path Main Menu\Unit State= Main Menu\Quick Menu\Unit State= Main Menu\View/Set Unit\Unit Status/Settings\Unit State= This read-only property indicates the current unit operating state. This is a LON WORKS only variable that covers six other data points: Supply Fan Capacity, Cooling Capacity, Heating Capacity, Reheat Capacity, Economizer, and In Alarm.

Measurement Units Data Type Valid Range Default Value Unit State N/A BACnet: Unsigned Enumerated N/A LON WORKS : Structure

BACnet Object Identifier Property Object Type Type ID Instance Name ID Multistate Value 19 15 Present_Value 85 Full Reference .UnitState.Present_Value Enumeration 1 = Off 2 = Start 3 = Recirc 4 = FanOnly 5 = MinDAT 6 = Htg 7 = Econo 8 = Clg

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Number nvoUnitStatus.Mode DAC, SCC Yes SNVT_hvac_status 112

Enumeration Definitions (hvac_t) Value Identifier Notes 0 HVAC_AUTO Not Used 1 HVAC_HEAT 2 HVAC_MRNG_WRMUP Not Used 3 HVAC_COOL 4 HVAC_NIGHT_PURGE Not Used 5 HVAC_PRE_COOL Not Used

96 ED15112-12 6 HVAC_OFF Unit State is either Off or Startup. 7 HVAC_TEST Not Used 8 HVAC_EMERG_HEAT Not Used 9 HVAC_FAN_ONLY Unit State is Recirc, FanOnly or MinDAT 10 HVAC_FREE_COOL Unit State is Econo 11 HVAC_ICE Not Used 12 HVAC_MAX_HEAT Not Used 13 HVAC_ECONOMY Not Used 14 HVAC_DEHUMID Not Used 15 HVAC_CALIBRATE Not Used 16 HVAC_EMERG_COOL Not Used 17 HVAC_EMERG_STEAM Not Used 0xFF OC_NUL Value not available Unit Support Keypad Menu Path Main Menu\BMS Communications\BACnet IP Set-Up\Unit Support= Main Menu\BMS Communications\BACnet MSTP Set-Up\Unit Support= This is a BACnet-only variable that sets the units that are sent from the main controller to the BACnet network. If the value is Off, the units is always Metric. If the value is On, the units depend on how the keypad/display is setup. If the keypad is displaying Metric, BACnet will display Metric. If the keypad is setup to display English Units, BACnet will display English units. The power must be cycled on the unit controller for this change to take effect. Measurement Units Data Type Valid Range Default Value Unit Support N/A BACnet: Unsigned Off (Always Metric) On (2) LON WORKS : Structure On

BACnet Object Identifier Property Object Type Type ID Instance Name ID Multistate Value 19 16 Present_Value 85 Full Reference .UnitSupport.Present_Value Enumeration 1 = Off 2 = On

Unoccupied Cooling Setpoint Keypad Menu Path Main Menu\View/Set Unit\Cooling\Unocc Clg Spt= This read/write configuration property sets the temperature above which the unit starts and provides cooling (night setup) during unoccupied periods. An optional space temperature sensor is required for unoccupied cooling operation. This attribute uses maximum and minimum limits. If the Present Value is set beyond these limits from the network, the value is ignored and the controller continues to control to the last valid value. The BACnet property only applies to the subject data point, but the LON WORKS variable is a structure that covers three other data points: Occupied Cooling Setpoint, Occupied Heating Setpoint, and Unoccupied Heating Setpoint. Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real 39.992°–99.986 °F 85°F / 29.44°C -4.44°–37.77°C

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 10 Present_Value 85 Full Reference .UnoccCoolSetpt.Present_Value

LON WORKS LON WORKS Name Profile SCPT Reference SCPT Index SNVT Type SNVT Index nciSetpoints.unoccupied_cool DAC, SCC SCPTsetPnts 60 SNVT_temp_setpt 106

ED15112-12 97 Field Definitions Field Notes Occupied_cool Occupied Cooling Setpoint Standby_cool Standby Cooling Setpoint (Not Used) Unoccupied_cool Unoccupied Cooling Setpoint Occupied_heat Occupied Heating Setpoint Standby_heat Standby Heating Setpoint (Not Used) Unoccupied_heat Unoccupied Heating Setpoint

Unoccupied Heating Setpoint Keypad Menu Path Main Menu\View/Set Unit\Heating\Unocc Htg Spt= This read/write configuration property sets the temperature above which the unit starts up and provides unoccupied heating (night setback). An optional space temperature sensor is required for unoccupied heating. This attribute uses maximum and minimum limits. If the Present Value is set beyond these limits from the network, the value is ignored and the controller continues to control to the last valid value. The BACnet property only applies to the subject data point, but the LON WORKS variable is a structure that covers three other data points: Occupied Cooling Setpoint, Unoccupied Cooling Setpoint, and Occupied Heating Setpoint.

Measurement Units Data Type Valid Range Default Value Temperature °F / °C Real 39.992°–99.986 °F 55°F / 12.78°C -4.44°–37.77°C

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 12 Present_Value 85 Full Reference .UnoccHeatSetpt.Present_Value

LON WORKS LON WORKS Name Profile SCPT Reference SCPT Index SNVT Type SNVT Index nciSetpoints.unoccupied_heat DAC, SCC SCPTsetPnts 60 SNVT_ temp_setpt 106

Field Definitions Field Notes Occupied_cool Occupied Cooling Setpoint Standby_cool Standby Cooling Setpoint (Not Used) Unoccupied_cool Unoccupied Cooling Setpoint Occupied_heat Occupied Heating Setpoint Standby_heat Standby Heating Setpoint (Not Used) Unoccupied_heat Unoccupied Heating Setpoint

VAV Box Output Keypad Menu Path No Keypad Equivalent This read-only property indicates the state of the VAV Box Output. This output is provided for interlocking field VAV box operation with the unit heating or cooling. The value is 0 when the unit is in any heating state, Start, or Recirc. The value is 1 when the unit is in any other state. This variable applies only to units configured with supply fan VFDs.

Measurement Units Data Type Valid Range Default Value N/A N/A BACnet: Unsigned BACnet: 1-2 N/A LON WORKS : Enumerated LON WORKS : 0-1

98 ED15112-12 BACnet Object Identifier Property Object Type Type ID Instance Name ID Multistate Value 19 14 Present_Value 85 Full Reference .VAVBoxOutput.Present_Value Enumeration 1 = Heat (Off) 2 = Cool (On)

LON WORKS LonWorks Name Profile Uses Heartbeat UNVT Type SNVT Number nvoVAVBoxOut Daikin No UNVTvavBoxOutput N/A AppliedDischargeAir Enumeration 0 = Heat (Off) 1 = Cool (On)

Variable Compressor Hours Keypad Menu Path Main Menu\View/Set Unit\Service\Operating Hours\Var Comp= OR Main Menu\View/Set Unit\Service\Operating Hours\Var Comp 1= OR Main Menu\View/Set Unit\Service\Operating Hours\Var Comp 2= OR Main Menu\View/Set Unit\Unit Maintenance\Operating Hours\ Var Comp= OR Main Menu\View/Set Unit\Unit Maintenance\Operating Hours\ Var Comp 1= OR Main Menu\View/Set Unit\Unit Maintenance\Operating Hours\ Var Comp 2= OR

This read/write property indicates the Variable Compressors accumulated run hours. It can be reset via the network. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Time Hrs Real 0–50000 Hrs No N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 121 Present_Value 85 Full Reference .VarCmpHrs.Present_Value LON WORKS No LON WORKS equivalent.

Variable Compressor Oil Status Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Oil Status Switch. It is also used for Intrisic Reporting of the Variable Compressor Low Oil Problem.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 51 Present_Value 85 Full Reference .VarCmpOilStatus.Present_Value

ED15112-12 99 Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent.

Water Flow Switch Keypad Menu Path Main Menu\View/Set Unit\Flow Status\Waterflow= This read-only BACnet object indicates the condition of the Water Flow Switch (Closed (1) or Open (0)). The OffNormal state of this object indicates a Water Flow Switch Problem.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 17 Present_Value 85 Full Reference .WtrFlwSw.Present_Value Enumeration 0 – Open 1 – Closed LON WORKS No LON WORKS equivalent.

Water Regulating Valve Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Water Regulating Valve (alarm (1) or normal (0)). The OffNormal state of this object indicates a Water Regulating Valve Problem.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 18 Present_Value 85 Full Reference .WtrRegVlv.Present_Value Enumeration 0 – normal 1 – alarm LON WORKS No LON WORKS equivalent.

Waterflow Switch Input Keypad Menu Path Main Menu\Service Menus\Network Input Status\Net CFlw Val= This read/write property sets the waterflow status via the network. BACnet uses a single variable while LON WORKS uses a SNVT_switch variable containing two properties that are used to determine the status. This variable applies only to units that are configured for mechanical cooling, the cooling configuration is either individual circuits or dual circuit water condenser, and no head pressure control.

100 ED15112-12 Measurement Units Data Type Valid Range Uses Heartbeat Default Value Flow Status N/A BACnet: Real Enumerated Yes N/A LON WORKS : Structure

BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 38 Present_Value 85 Full Reference .WaterflowSwitch.Present_Value

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nviCWFlow DAC, Yes SNVT_switch 95 Daikin AppliedRTU- SCC Valid Range State Value Waterflow Switch 0 N/A Disabled 1 0 Disabled 1 1-100% Enabled -1 (0xFF) N/A Auto (invalid)

ED15112-12 101 Alarms and Events

Two methods of obtaining alarm information are available in the MicroTech III Unit Controller: 1) by monitoring individual alarms and 2) by monitoring alarms according to alarm class. Alarms are divided into three classes: Faults, Problems, and Warnings. Fault alarms have the highest priority. Problem alarms have the next priority. Warning alarms have the lowest priority. The alarms within each class are also prioritized. Refer to the MicroTech III Unit Controller Operation Manual (OM 920) for a description of each alarm. The MicroTech III Unit Controller has various ways of managing alarms, depending on the protocol. Using one of these mechanisms, alarms can be recognized and acknowledged by alarm class or individually, and cleared from the network by alarm class. Refer to Tables 5, 6, and 7 for details.

The following tables describe the alarm messages, indication, and method of clearing Fault, Problem, and Warning alarms. Alarms are listed in order of priority.

Fault Alarms (Highest Priority) Table 5. Fault Alarms in Order of Priority

Alarm Message Indication Clear Heat Fail RPS with gas heating on FSG off on safety lockout Automatic Freeze Supply Fan has been On for at least 30 seconds AND Manual A Waterside Economizer, Chilled Water Coil, Hot Water Coil, or steam coil is installed in the unit. AND Freezestat is in the Open position. Emergency Stop Emergency Stop Input in the Alarm (Open) condition OR Manual A network variable, nviEmergMode in LonMark applications, is set to shutdown via a Lon or BACnet network Control Temp All of the following are true for at longer than the Temperature Alarm Delay (Default = 30 seconds): Manual • Either Space or Return Temperature is selected as the Control Temperature AND • The Return Air Sensor is not Reliable (Either In alarm or Not Present) AND • The Space Sensor is not Reliable (A valid Space Temperature value is not provided via the network and the Space Temperature sensor is either In alarm OR Not Present) OR • Both of the following are true for at longer than the Temperature Alarm Delay (Default = 30 seconds): • The Outdoor Air Temperature Sensor is not Reliable (A valid Outside Air Temperature value is not provided via the network and the Outside Air Temperature sensor is either In alarm OR Not Present) AND • OAT is selected as the Control Temperature OR • All of the following are true for at longer than the Temperature Alarm Delay (Default = 30 seconds): • The MAT Sensor is not Reliable (Either In alarm or Not Present) AND • MAT is selected as the Control Temperature Disch Sensor The Discharge Air Temperature Sensor is not Reliable (Either In alarm or Not Present) for longer than the Manual Temperature Alarm Delay (Default = 30 seconds) Duct Hi Limit Duct High Limit input is Open and the unit is Variable Air Volume Manual High Return Temp RAT exceeded the Hi Return Tmp setting Manual High Disch Temp DAT exceeded the Hi Disch Tmp setting Manual Low Disch Temp DAT fell below the Lo Disch Tmp setting Manual Airflow All of the following are true: Manual • The Supply Fan is Constant Volume AND • Airflow Switch is Open. AND • The Supply Fan has been on for longer than the Airflow Timer (Default =120 seconds) AND • Another Shutdown Fault that could have turned off the fan is not active OR Both of the following are true: • The Supply Fan is Variable Air Volume AND • The unit has been disabled due to Fan Retry conditions three times between 2:00 AM of one day and 2:00 AM of the next day.

102 ED15112-12 Problem Alarms (Medium Priority) Table 6. Problem Alarms in Order of Priority Alarm Message Indication Clear IRT Sensor Problem The Indoor Refrigerant Temperature (IRT) Sensor has failed. Manual ORT Sensor Problem The Outdoor Refrigerant Temperature (ORT) Sensor has failed. Manual Low Refrigerant The difference between the refrigerant circuit high side (PTD) and low side (PTS) remains below 85.3 psi Manual Differential Pressure when the inverter compressor and fixed speed compressor (if applicable) are at full capacity. This indicates a problem with the sealing of the four way valve in heat pump applications. IFB Comm Problem A communication interruption has occurred between the MicroTech III controller and the inverter Manual compressor IFB board. PTD Sensor Problem The discharge refrigerant pressure sensor has failed. Manual PTD1 Sensor Problem The discharge refrigerant pressure sensor has failed. Manual PTD2 Sensor Problem The discharge refrigerant pressure sensor has failed. Manual PTS Sensor Problem The suction refrigerant pressure sensor has failed. Manual Low Refrigerant Charge The refrigerant system is low on charge Manual Charge Loss Problem Refrigerant system charge has been completely lost. Manual Outdoor Fan Problem There is a problem with the outdoor air fan control. Manual Exp Valve Problem There is a problem with either the indoor or outdoor expansion valve control. Manual High Discharge Line The inverter compressor discharge line temperature has either exceeded 275°F or exceeded 248°F for 10 Manual Temperature minutes. OR The Unit Type is RTU AND Cooling Type is Var Circ 1 or Var Cir 2 AND the discharge line temperature is greater than 250°F (121.11°C) continuously for 3 minutes. SRT Sensor Problem The suction line refrigerant temperature sensor has failed Manual DFT Sensor Problem The defrost temperature sensor has failed Manual INV Comp Problem The inverter compressor control board has indicated a problem with the inverter compressor operation. Manual DRT1 Sensor Problem The inverter compressor discharge refrigerant temperature sensor has failed. Manual DRT2 Sensor Problem The variable compressor discharge refrigerant temperature sensor has failed. Manual DRT3 Sensor Problem The fixed compressor discharge refrigerant line temperature sensor has failed. Manual Heat Fail Problem Daikin Applied gas heat flame safeguard (FSG) device is off on safety lockout. Automatic Freeze Freezestat tripped while SAF was off and a waterside economizer, chilled water coil, hot water coil, or Automatic steam coil is installed on the unit. MAT Sensor The Mixed Air Temperature sensor is not Reliable (Either In alarm or Not Present) for longer than the Automatic Temperature Alarm Delay (Default = 30 seconds) EWT Sensor The Entering Water Temperature Sensor is not Reliable (Either In alarm or Not Present) for longer than the Automatic Temperature Alarm Delay (Default = 30 seconds) OAT Sensor The Outdoor Air Temperature Sensor is not Reliable (A valid Outside Air Temperature value is not Automatic provided via the network and the Outside Air Temperature sensor is either In alarm OR Not Present) for longer than the Temperature Alarm Delay (Default = 30 seconds) Space Sensor The Space Sensor is not Reliable (A valid Space Temperature value is not provided via the network and Automatic the Space Temperature sensor is either In alarm OR Not Present) for longer than the Temperature Alarm Delay (Default = 30 seconds) Return Sensor The Return Air Sensor is not Reliable (Either In alarm or Not Present) for longer than the Temperature Automatic Alarm Delay (Default = 30 seconds) Ent_LCT Sensor The Entering Fan Temperature/Leaving Coil Temperature is not reliable (either in alarm or not present) for Automatic longer than the temperature alarm delay (default=30seconds) Sump Water Level Unit state has been Clg for the SmpWtrLvlDly time and the SmpWtrLvl input remains in the open Manual Problem position. Hi Pres-Ckt1 High Pressure switch SW1 input is in the alarm (Open) position. Manual Hi Pres-Ckt2 High Pressure switch SW2 input is in the alarm (Open) position. Manual Hi Pres-Ckt3 High Pressure switch SW3 input is in the alarm (Open) position. Manual Hi Pres-Ckt4 High Pressure switch SW4 input is in the alarm (Open) position. Manual Hi Pres-Ckt5 High Pressure switch SW5 input is in the alarm (Open) position. Manual Hi Pres-Ckt6 High Pressure switch SW6 input is in the alarm (Open) position. Manual Hi Pres-Ckt7 High Pressure switch SW7 input is in the alarm (Open) position. Manual Hi Pres-Ckt8 High Pressure switch SW8 input is in the alarm (Open) position. Manual Hi Pressure Problem Inverter compressor refrigerant circuit high pressure limits have been exceeded. Manual High INV Comp Body Inverter compressor body temperature limit has been exceeded. Manual Temp High INV Comp Body The inverter compressor body temperature sensor is not Reliable Manual Temp Sensor Problem Lo Pres-Ckt1 The Low Press SW1 input has been in the alarm (Open) position for longer than the Pressure Alarm Delay Automatic (Default = 10 seconds) AND A compressor on Circuit #1 has been on for longer than the Low Pressure Alarm Delay (Default = 65

ED15112-12 103 Alarm Message Indication Clear seconds) Lo Pres-Ckt2 The Low Press SW2 input has been in the alarm (Open) position for longer than the Pressure Alarm Delay Automatic (Default = 10 seconds) AND A compressor on Circuit #2 has been on for longer than the Low Pressure Alarm Delay (Default = 65 seconds) Lo Pres-Ckt3 The Low Press SW3 input has been in the alarm (Open) position for longer than the Pressure Alarm Delay Automatic (Default = 10 seconds) AND A compressor on Circuit #3 has been on for longer than the Low Pressure Alarm Delay (Default = 65 seconds) Lo Pres-Ckt4 The Low Press SW4 input has been in the alarm (Open) position for longer than the Pressure Alarm Delay Automatic (Default = 10 seconds) AND A compressor on Circuit #4 has been on for longer than the Low Pressure Alarm Delay (Default = 65 seconds) Lo Pres-Ckt5 The Low Press SW5 input has been in the alarm (Open) position for longer than the Pressure Alarm Delay Automatic (Default = 10 seconds) AND A compressor on Circuit #5 has been on for longer than the Low Pressure Alarm Delay (Default = 65 seconds) Lo Pres-Ckt6 The Low Press SW6 input has been in the alarm (Open) position for longer than the Pressure Alarm Delay Automatic (Default = 10 seconds) AND A compressor on Circuit #6 has been on for longer than the Low Pressure Alarm Delay (Default = 65 seconds) Lo Pres-Ckt7 The Low Press SW7 input has been in the alarm (Open) position for longer than the Pressure Alarm Delay Automatic (Default = 10 seconds) AND A compressor on Circuit #6 has been on for longer than the Low Pressure Alarm Delay (Default = 65 seconds) Lo Pres-Ckt8 The Low Press SW8 input has been in the alarm (Open) position for longer than the Pressure Alarm Delay Automatic (Default = 10 seconds) AND A compressor on Circuit #6 has been on for longer than the Low Pressure Alarm Delay (Default = 65 seconds) Low Pressure Problem Inverter compressor refrigerant circuit low pressure limits have been exceeded. Manual Water RegValve Water Regulating Valve is installed AND Manual A compressor on either circuit # 1 or circuit # 2 is turned on. AND EWT is less than 58 °F AND The greater of the two refrigerant condensing pressure readings is below the Head Pressure Setpoint by more than the deadband Waterflow Switch Lack of water flow is indicated by an open water flow switch or a Network signal AND Either of the Automatic following is true: • The Bypass Valve has been open for more than the Bypass Valve Timer. • A water side economizer is installed and its position is greater than 50% Variable Compressor The Unit Type is RTU AND Cooling Type is Var Circ 1 or Var Cir 2 AND either the variable compressor Manual Problem enable output has been on for 20 seconds and the variable compressor status input is off (not present) OR the emergency stop event has become active 3 times in a 30 minute period. Low Discharge Pressure The Unit Type is RTU AND Cooling Type is Var Circ 1 or Var Cir 2 AND the variable compressor circuit Manual Problem splitter coil output is ON and the discharge pressure remains lower than 250psi (1723.7kPa) continuously for 15 minutes. Low Discharge The Unit Type is RTU AND Cooling Type is Var Circ 1 or Var Cir 2 AND the discharge superheat is less Manual Superheat Problem than 25°F (13.89°C) AND the minimum variable compressor capacity is equal to the lesser of the effective max variable compressore capacity or 80% (60Hz). High Discharge The Unit Type is RTU AND Cooling Type is Var Circ 1 or Var Cir 2 AND the discharge superheat is Manual Superheat Problem greater than 100°F (55.56°C) and the max VFD capacity has been reset to 53.3% (40Hz). Var Comp Lo Oil The Unit Type is RTU AND Cooling Type is Var Circ 1 or Var Cir 2 AND if VFD oil boost operation Manual Problem becomes active 5 times in a 24 hour period OR the variable compressor has been operating at the EffMaxVFDcap value for the OilBstTm perior and the low oil flag is still active.

Warning Alarms (Lowest Priority) Table 7. Warning Alarms in Order of Priority

Alarm Message Indication Clear Conductivity Conductivity valve is above alarm setpoint value. Manual Airflow Switch Airflow switch is in the Flow (Closed) position AND the supply fan is Off for more than 30 minutes. Manual Dirty Filter The filter switch input is in the alarm (Open) position Manual Return/Exhaust Fan Indicates a problem with the return or exhaust fan operation Automatic Warning Low Superheat The suction and discharge superheat values have been unusually low for 30 minutes during normal Automatic

104 ED15112-12 compressor operation. Over Econo Warning This warning indicates the unit is economizing when it shouldn’t be. Automatic Under Econo Warning This warning indicates the unit is not economizing when it should be. Automatic Excess Outdoor Air This warning indicates that the unit is delivering excess outdoor air. Automatic Warning Outdoor Air Damper Stuck This warning indicates the dampers are stuck and not modulating. Automatic

Events Table 8: List of Possible Events

Event Message Indication Clear High Pressure Unload Event This event is initiated when high discharge pressure occurs on the variable compressor circuit. Automatic Low Discharge Pressure Unload This event is initiated when the variable circuit Splitter Coil output is On and the Variable Automatic Event compressor is On. Variable Compressor Emergency This event is initiated when the Variable Compressor Enable Output has been On for 30 Automatic Stop Event seconds and the Variable Compressor Status Inut is Off (not present). High Discharge Line Temperature This event is initiated when high discharge line temperature conditions occur continuously for Automatic Unload Event 15 seconds and the Variable compressor is on. Low Discharge Superheat Unload This event is initiated when the discharge superheat is low continueously for 15 minutes, the Automatic Event Variable compressor is On and the Effective Min Variable Compressor Capacity is less than 80%. High Discharge Superheat Unload This event is initiated when the discharge superheat is high continueously for 15 minutes, the Automatic Event Variable compressor is On and the Effective Max Variable Compressor Capacity is greater than 53.3%. Reheat Stage Limited Event This event is initiated when the unit is configured for refrigerant circuit based reheat and the Automatic reheat valve is wide open and the unit is still not meeting the reheat setpoint. When this happens a compressor, on the opposite circuit as the reheat, is staged down. Oil Boost Event This event is initiated when the low oil flag is active (digital input is open) for 10 consecutive Automatic minutes or when oil boost is manually initiated. Alarm Monitoring The MicroTech III Unit Controller provides individual alarm identification through a unique value for each alarm. The value assigned to each alarm is the same for both BACnet and LONWORKS applications.

BACnet MicroTech III Unit Controllers may have alarms monitored by one of four methods: 1) individually by BACnet Binary Value Objects, 2) alarm value using one BACnet Analog Values, 3) alarm class or 4) Notification Classes. 1. To monitor alarms individually, read the Present_Value of the desired Binary Value. Each alarm has its own Binary Value object. If the Present_Value is Inactive (0), the alarm is not active. If the Present_Value is Active (1), the alarm is active. 2. To monitor alarms by alarm value, read the Present_Value property of the Alarm Value Analog Value object. The Present_Value displays a value that corresponds to the highest priority alarm that is active. It is possible to have multiple active alarms, but only the highest priority is displayed. For example, if there is a simultaneous Dirty Filter Warning (value of 24) and a Freeze Fault (value of 252), then the Freeze Fault value of 252 will display in the Present_Value because it is the higher priority alarm of the two. Once the Freeze Fault condition is corrected and the fault is cleared, the next priority active alarm value (in this example, value of 24 for Dirty Filter alarm) is displayed. The values for all alarms are described in the Alarms section tables. If the Present_Value displays a zero, there are no active alarms. 3. To monitor alarms by alarm class, read the Present_Value of the appropriate Analog Value object (Warnings, Problems and faults). The Present_Value displays a value that corresponds to the highest priority alarm that is active. It is possible to have multiple active alarms, but only the highest priority is displayed. 4. To monitor alarms using the Notification Class objects, see the Alarm Notification section. LONWORKS MicroTech III Unit Controllers may have their alarms monitored by one of two methods: 1) using the In_alarm attribute of nvoUnitStatus, or 2) alarm class. 1. Alarms can be monitored individually by using the In Alarm attribute of the Unit Status Network Variable Output (i.e. nvoUnitStatus_in_alarm). This attribute displays a value that corresponds to the highest priority alarm that is active. It is possible to have multiple active alarms, but only the highest priority is displayed in this attribute. For example, if there is a simultaneous Dirty Filter Warning (value of 24) and a Freeze Fault (value of 252), then the Freeze Fault value

ED15112-12 105 of 252 will display in nvoUnitStatus_in_alarm because it is the higher priority alarm of the two. Once the Freeze Fault condition is corrected and the fault is cleared, the next priority active alarm value (in this example, value of 24 for Dirty Filter alarm) is displayed. The values for all alarms are described in the Alarms section tables. If the attribute nvoUnitStatus_in_alarm displays a zero, there are no active alarms. Alarms may also be monitored by alarm class if desired. When the nvoUnitStatus_in_alarm attribute reads a value in the range of 1 to 99, a Warning Alarm is active. When the attribute reads a value in the range of 100 to 199, a Problem Alarm is active. When the attribute reads a value in the range of 200 to 255, a Fault Alarm is active. 2. To monitor alarms by alarm class, read nvoWarnAlarm, nvoProbAlarm and nvoFaultAlarm. The value corresponds to the highest priority alarm that is active. It is possible to have multiple active alarms, but only the highest priority is displayed. Alarm and Event Notification The MicroTech III Unit Controller has three Notification Class objects for alarms and uses intrinsic reporting which allows the controller to generate event notifications directed to one or more recipients (maximum 20 recipients). There is one notification class object for each class of alarms (faults, problems and warnings). You must subscribe to the notification class objects in order to use them. The Recipient List property must indicate when and to which device notification should be made. This is a standard BACnet data type as defined in ANSI/ASHRAE 135-2008, BACnet A Data Communication Protocol for Building Automation and Control Networks. The Event_Enable property of each object can be used to separately enable and disable reporting of To-OffNormal, To- Fault, and To-Normal events. For example, if you do not want an event to be generated when the object returns to a normal state after being in alarm, set the To-Normal bit of the objects Event_Enable property to 0. The tables below show the objects that support intrinsic reporting grouped with the notification classes they report to:

Notification Class 1 (Faults) Event_Enable (Default) Alarm Object Type Object Instance To-OffNormal To-Fault To-Normal Airflow Fault BI 1 X X Control Temp Fault AI 14 X X Discharge Sensor Fault AI 1 X X X High Discharge Temp Fault Low Discharge Temp Fault Duct High Limit Fault BI 21 X X Emergency Off Fault BI 22 X X Freeze Fault BI 19 X X High Return Temp Fault AV 45 X X

Notification Class 2 (Problems) Event_Enable (Default) Alarm Object Type Object Instance To-OffNormal To-Fault To-Normal IRT Sensor Problem AI 27 X X ORT Sensor Problem AI 28 X X Compressor 3 Discharge Line AI 21 X X Temperature Sensor Problem Defrost Sensor Problem AI 23 X X Discharge Refrigerant Pressure AI 26 X X (PTD) Sensor Problem Entering Fan Temp / Leaving Coil AI 7 X X Temp Problem Entering Water Temp Problem AI 6 X X Expansion Valve Problem BI 40 X X Freeze Problem BI 20 X X Heat Fail Problem BI 23 X X High Discharge Line Temperature BI 35 X X Problem High Pressure Circuit 1 Problem BI 4 X X High Pressure Circuit 2 Problem BI 5 X X High Pressure Circuit 3 Problem BI 6 X X High Pressure Circuit 4 Problem BI 7 X X High Pressure Circuit 5 Problem BI 8 X X High Pressure Circuit 6 Problem BI 9 X X

106 ED15112-12 High Pressure Circuit 7 Problem BI 26 X X High Pressure Circuit 8 Problem BI 27 X X High Pressure Problem BI 32 X X Interface Board Communication BI 38 X X Problem Inverter Compressor Discharge Line AI 22 X X Temperature Sensor Problem Inverter Compressor Problem BI 34 X X Return Temp Problem AI 2 X X Low Pressure Circuit 1 Problem BI 10 X X Low Pressure Circuit 2 Problem BI 11 X X Low Pressure Circuit 3 Problem BI 12 X X Low Pressure Circuit 4 Problem BI 13 X X Low Pressure Circuit 5 Problem BI 14 X X Low Pressure Circuit 6 Problem BI 15 X X Low Pressure Circuit 7 Problem BI 24 X X Low Pressure Circuit 8 Problem BI 25 X X Low Pressure Problem BI 33 X X Low Refrigerant Charge Problem BI 37 X X Charge Loss Problem BI 41 X X Low Refrigerant Differential BI 39 X X Problem Mixed Air Temp Problem AI 5 X X Outdoor Fan Problem BI 36 X X Outdoor Temp Problem AI 4 X X Space Temp Problem AI 3 X X Suction Refrigerant Pressure (PTS) AI 25 X X Sensor Problem Suction Line Refrigerant AI 24 X X Temperature Sensor Problem Sump Water Level Problem BI 16 X X Waterflow Switch Problem BI 17 X X Water Regulating Valve Problem BI 18 X X High Inverter Compressor Body BI 43 X X Temp Problem INV Comp Body Temp Sensor AI 29 X Problem Variable Compressor Problem BI 47 X X Low Discharge Pressure Problem BI 48 X X Low Discharge Superheat Problem BI 49 X X High Discharge Superheat Problem BI 50 X X Variable Compressor Oil Status BI 51 X X

Notification Class 3 (Warnings) Event_Enable (Default) Alarm Object Type Object Instance To-OffNormal To-Fault To-Normal Airflow Switch Warning BI 2 X X Conductivity Warning AI 12 X X Dirty Filter Warning BI 3 X X Return/Exhaust Fan Warning BI 42 X X Low Superheat Warning BI 46 X X

Notification Class 4 (Events) Event_Enable (Default) Event Object Type Object Instance To-OffNormal To-Fault To-Normal High Pressure Unload Event BI 52 X X Low Discharge Pressure Unload BI 53 X X Event Variable Compressor Emergency BI 54 X X Stop Event High Discharge Line Temperature BI 55 X X Unload Event

ED15112-12 107 Low Discharge Superheat Unload BI 56 X X Event High Discharge Superheat Unload BI 57 X X Event Reheat Stage Limited Event BI 58 X X Oil Boost Event BI 59 X X

Recipient List Property The recipient list property (Recipient_List), of the Notification Class object, is a list of standard BACnet data type BACnetDestination elements. This data type consists of the following elements: Element Standard BACnet Data Description Type Valid Days BACnetDaysOfWeek The set of days of the week that the destination may be used between the From Time and the To Time From Time, To Time Time The window of time (inclusive) when the destination is visible on the days of the week in Valid Days Recipient BACnet Recipient The destination devices to receive the notification. A maximum of 20 destination devices is supported. Process Identifier Unsigned The handle of a process within the recipient device that is to receive the event notification Issue Confirmed Boolean (TRUE) if confirmed notifications are to be sent and (FALSE) if Notification unconfirmed notifications are to be sent Transitions BACnetEventTransitionBits A set of three flags that indicate the transition (TO-OFFNORMAL, TO-FAULT, and TO-NORMAL) that the recipient is suitable.

If the BACnet workstation or BACnet device supports intrinsic alarming, but is unable to subscribe to the recipient list property of the notification class object, the workstation or device can still receive alarm notification by adding its Device Instance to the “NC Dev 1=” or “NC Dev 2=” items on the keypad/display. These items are located on the IP Setup or MSTP Setup menus. Power must by cycled for changes to these items to take effect. Once power is cycled, the unit controller sends out a “Who-Is” command directed at the device. If the device responds, the unit controller sends out Unconfirmed Notifications for all alarms that are generated in the application. If the device does not respond to the Who-Is, the unit controller will periodically send out the Who-Is until the device responds.

Alarm Clearing BACnet Alarms can be cleared via BACnet by setting the ClearAlms variable to value greater than 1. To clear alarms by alarm class, change the Present_Value property to a 2 to clear all faults, a 3 to clear all problems or a 4 to clear all warnings. Setting this variable to a 5 will clear all alarms in all three alarm classes. After the alarms are cleared, this variable will return to None (1). LONWORKS Alarms can be cleared by alarm class using nviClearAlarms. To clear alarms in a particular class, set the value of nviClearAlarms to the appropriate value (1=Clear Faults, 2=Clear Problems, 3=Clear Warnings & 4=Clear All). If the unit is still in the alarm condition, the In Alarm attribute of the Unit Status Network Variable Output (nvoUnitStatus.in_alarm) again reads the number corresponding to the highest priority active alarm that still exists.

Objects Clear Alarms Keypad Menu Path Main Menu\Alarm Lists\Active Alarms\ClrAlms= This read/write property clears all active alarms or all active alarms in a particular alarm class.

Measurement Units Data Type Valid Range Uses Heartbeat Default Value Alarms N/A BACnet: Unsigned Enumerated No N/A LON WORKS : Structure

108 ED15112-12 BACnet Object Identifier Property Object Type Type ID Instance Name ID Multistate Value 19 13 Present_Value 85 Full Reference .ClearAlarms.Present_Value Enumeration 1 = None 2 = ClrFlts 3 = ClrPrblms 4 = ClrWrngs 5 = ClrAllAlms

LON WORKS LonWorks Name Profile Uses Heartbeat UNVT Type SNVT Number nviClearAlarms Daikin No UNVTclearAlarm N/A AppliedDischargeAir, Daikin AppliedRTU- SCC Enumeration 0 = None 1 = Clear All Faults 2 = Clear All Problems 3 = Clear All Warnings 4 = Clear All Alarms

Notification Class - Events Keypad Menu Path No Keypad Equivalent These read/write properties allow subscription to event notifications. The Recipient_List conveys a list of one or more recipients to which notifications will be sent. The Ack_Required property tells whether acknowledgment is required in notifications generated for To-OffNormal, To-Fault, and To-Normal event transitions. The Priority conveys the priority to be used for event notifications to To-OffNormal, To-Fault and To-Normal events. See the Alarm and Event Notification section for more information including a list of objects that report events to this notification class.

Measurement Units Data Type Valid Range Default Value Notification N/A List of BACnetDestination N/A N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Notification Class 15 4 recipient_list 102 Full Reference .NC1-Warnings.recipient_list 1, 2 1 If the BACnet Workstation is unable to subscribe to the recipient_list, you can still subscribe to alarms on the unit controller keypad/display. Navigate to the IP Setup or MSTP Setup menu and enter the Device Instance of the device to receive the alarms in the “NC Dev 1=” or “NC Dev 2=” entries. You must cycle power after changing these properties from the keypad display. 2 Maximum of 20 recipients at one time.

Object Identifier Property Object Type Type ID Instance Name ID Notification Class 15 4 Ack_Required 1 Full Reference .NC4-Events.Ack_Required

Object Identifier Property Object Type Type ID Instance Name ID Notification Class 15 4 Priority 86

ED15112-12 109 Full Reference . NC4-Events.Priority 1 1 A lower number indicates a higher priority.

LON WORKS No LonWorks equivalent.

Notification Class - Faults Keypad Menu Path No Keypad Equivalent These read/write properties allows subscription to alarm notifications. The Recipient_List conveys a list of one or more recipients to which notifications will be sent. The Ack_Required property tells whether acknowledgment is required in notifications generated for To-OffNormal, To-Fault, and To-Normal event transitions. The Priority conveys the priority to be used for event notifications to To-OffNormal, To-Fault and To-Normal events. See the Alarm and Event Notification section for more information including a list of objects that report events to this notification class. Measurement Units Data Type Valid Range Default Value Notification N/A List of BACnetDestination N/A N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Notification Class 15 1 recipient_list 102 Full Reference .NC1-Faults.recipient_list 1, 2 1 If the BACnet Workstation is unable to subscribe to the recipient_list, you can still subscribe to alarms on the unit controller keypad/display. Navigate to the IP Setup or MSTP Setup menu and enter the Device Instance of the device to receive the alarms in the “NC Dev 1=” or “NC Dev 2=” entries. You must cycle power after changing these properties from the keypad/display. 2 Maximum of 20 recipients at one time.

Object Identifier Property Object Type Type ID Instance Name ID Notification Class 15 1 Ack_Required 1 Full Reference .NC1-Faults.Ack_Required

Object Identifier Property Object Type Type ID Instance Name ID Notification Class 15 1 Priority 86 Full Reference .NC1-Faults.Priority 1 1 A lower number indicates a higher priority.

LON WORKS No LonWorks equivalent.

Notification Class - Problem Keypad Menu Path No Keypad Equivalent These read/write properties allow subscription to alarm notifications. The Recipient_List conveys a list of one or more recipients to which notifications will be sent. The Ack_Required property tells whether acknowledgment is required in notifications generated for To-OffNormal, To-Fault, and To-Normal event transitions. The Priority conveys the priority to be used for event notifications to To-OffNormal, To-Fault and To-Normal events. See the Alarm and Event Notification section for more information including a list of objects that report events to this notification class. Measurement Units Data Type Valid Range Default Value Notification N/A List of BACnetDestination N/A N/A

110 ED15112-12 BACnet Object Identifier Property Object Type Type ID Instance Name ID Notification Class 15 2 recipient_list 102 Full Reference .NC1-Problems.recipient_list 1, 2 1 If the BACnet Workstation is unable to subscribe to the recipient_list, you can still subscribe to alarms on the unit controller keypad/display. Navigate to the IP Setup or MSTP Setup menu and enter the Device Instance of the device to receive the alarms in the “NC Dev 1=” or “NC Dev 2=” entries. You must cycle power after changing these properties from the keypad/display. 2 Maximum of 20 recipients at one time.

Object Identifier Property Object Type Type ID Instance Name ID Notification Class 15 2 Ack_Required 1 Full Reference .NC1-Problems.Ack_Required

Object Identifier Property Object Type Type ID Instance Name ID Notification Class 15 2 Priority 86 Full Reference .NC1-Problems.Priority 1 1 A lower number indicates a higher priority.

LON WORKS No LonWorks equivalent.

Notification Class - Warnings Keypad Menu Path No Keypad Equivalent These read/write properties allow subscription to alarm notifications. The Recipient_List conveys a list of one or more recipients to which notifications will be sent. The Ack_Required property tells whether acknowledgment is required in notifications generated for To-OffNormal, To-Fault, and To-Normal event transitions. The Priority conveys the priority to be used for event notifications to To-OffNormal, To-Fault and To-Normal events. See the Alarm and Event Notification section for more information including a list of objects that report events to this notification class.

Measurement Units Data Type Valid Range Default Value Notification N/A List of BACnetDestination N/A N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Notification Class 15 3 recipient_list 102 Full Reference .NC1-Warnings.recipient_list 1, 2 1 If the BACnet Workstation is unable to subscribe to the recipient_list, you can still subscribe to alarms on the unit controller keypad/display. Navigate to the IP Setup or MSTP Setup menu and enter the Device Instance of the device to receive the alarms in the “NC Dev 1=” or “NC Dev 2=” entries. You must cycle power after changing these properties from the keypad display. 2 Maximum of 20 recipients at one time.

Object Identifier Property Object Type Type ID Instance Name ID Notification Class 15 3 Ack_Required 1 Full Reference .NC1-Warnings.Ack_Required

ED15112-12 111 Object Identifier Property Object Type Type ID Instance Name ID Notification Class 15 3 Priority 86 Full Reference .NC1-Warnings.Priority 1 1 A lower number indicates a higher priority.

LON WORKS No LonWorks equivalent.

Alarm Value Keypad Menu Path No Keypad Equivalent This object allows individual notification of the highest priority active alarm. The value in the table below is the largest number in its enumeration that corresponds to an active alarm. This object is set to zero if no alarms are active.

Measurement Units Data Type Valid Range Default Value Alarms N/A BACnet: Real Enumerated N/A LON WORKS : Structure BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 27 Present_Value 85 Full Reference .AlarmValue.Present_Value

112 ED15112-12 Property Value

ED15112-12 113 0 – No Active Alarms 24 - Dirty Filter 28 – Airflow Sw 32 – Conductivity 34 – Ret/Exh Fan Warning 40 – Low Superheat Warning 50 - Over Econo Warning 52 - Under Econo Warning 54 - Excess OA Warning 56 - OAD Stuck Warning 102 - IRT Sensor Problem 104 - ORT Sensor Problem 106 – DRT3 Sensor Problem 108 – DRT2 Sensor Problem 111 – DRT1 Sensor Problem 114 – Variable Comp Problem 115 - LoDischP Problem 116 - LoDischSH Problem 117 -HiDischSH Problem 119 – DFT Sensor Problem 121 – SRT Sensor Problem 124 – High Disch Line Temp 126 – Exp Valve Problem 128 – OAFan Problem 130 – Low Refrig Charge 131 - ChargeLossPrb 132 – PTS Sensor Problem 133 – PTD2 Sensor Problem 134 – PTD or PTD1 Sensor Problem 135 – IFB Comm Problem 136 – Lo Pressure Differential 137 – Waterflow Sw 140 – Water Regulating Valve 145 – Variable Comp Low Oil Problem 148 - High INV Comp Body Temp 149 - INV Comp Body Temp Sensor Problem 152 – Low Pressure – Circuit 8 153 – Low Pressure – Circuit 7 154 – Low Pressure – Circuit 6 155 – Low Pressure – Circuit 5 156 – Low Pressure – Circuit 4 157 – Low Pressure – Circuit 3 158 – Low Pressure – Circuit 2 159 – Low Pressure – Circuit 1 160 – High Pressure – Circuit 8 161 – High Pressure – Circuit 7 162 – High Pressure – Circuit 6 163 – High Pressure – Circuit 5 164 – High Pressure – Circuit 4 165 – High Pressure – Circuit 3 166 – High Pressure – Circuit 2 167 – High Pressure – Circuit 1 169 – Sump Water Level Problem 179 – EFT_LCT Problem 182– Return Air Sensor Problem 185 – Space Sensor Problem 188 – OAT Sensor Problem 191 – EWT Problem 194 – MAT Problem 197 – Freeze Problem 199 – Heat Fail Problem 208 – Airflow Fault 212 – Low Discharge Air Temp 114216 – High Discharge Air Temp ED15112-12 220 – High Return Air Temp 224 – Duct High Limit 228 – Discharge Sensor Fail

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoUnitStatus.in_alarm DAC, SCC Yes SNVT_hvac_status 112 Property Value Same as BACnet.

Warning Alarm Keypad Menu Path No Keypad Equivalent This object allows individual notification of the highest priority active warning alarm. The value in the table below is the largest number in its enumeration that corresponds to an active alarm. This object is set to zero if no warning alarms are active. Measurement Units Data Type Valid Range Default Value Alarms N/A BACnet: Real Enumerated N/A LON WORKS : Structure BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 24 Present_Value 85 Full Reference .ActiveWarning.Present_Value Enumeration 0 – No Active Alarms 24 - Dirty Filter 28 – Airflow Sw 32 – Conductivity 34 – Ret/Exh Fan Warning 40 – LowSuperHtWarn 50=Over Econo Warning 52=Under Econo Warning 54=Excess OA Warning 56=OAD Stuck Warning LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoWarnAlarm DAC, SCC Yes SNVT_hvac_status 112 Property Value Same as BACnet

Problem Alarm Keypad Menu Path No Keypad Equivalent This object allows individual notification of the highest priority active problem alarm. The value in the table below is the largest number in its enumeration that corresponds to an active alarm. This object is set to zero if no problem alarms are active. Measurement Units Data Type Valid Range Default Value Alarms N/A BACnet: Real Enumerated N/A LON WORKS : Structure BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 25 Present_Value 85 Full Reference .ActiveProblem.Present_Value

ED15112-12 115 Enumeration 0 – No Active Alarms 102 - IRT Sensor Problem 104 - ORT Sensor Problem 106 – DRT3 Sensor Problem 111 – DRT1 Sensor Problem 114 – Variable Comp Problem 115 - LoDischP Problem 116 - LoDischSH Problem 117 - HiDischSH Problem 119 – DFT Sensor Problem 121 – SRT Sensor Problem 124 – High Disch Line Temp 126 – Exp Valve Problem 128 – OAFan Problem 130 – Low Refrig Charge 131 - ChargeLossPrb 132 – PTS Sensor Problem 133 – PTD2 Sensor Problem 134 – PTD or PTD1 Sensor Problem 135 – IFB Comm Problem 136 – Lo Pressure Differential 137 – Waterflow Sw 140 – Water Regulating Valve 145 – Variable Comp Low Oil Problem 148 – High INV Comp Body Temp 149 – INV Comp Body Temp Sensor Problem 152 – Low Pressure – Circuit 8 153 – Low Pressure – Circuit 7 154 – Low Pressure – Circuit 6 155 – Low Pressure – Circuit 5 156 – Low Pressure – Circuit 4 157 – Low Pressure – Circuit 3 158 – Low Pressure – Circuit 2 159 – Low Pressure – Circuit 1 160 – High Pressure – Circuit 8 161 – High Pressure – Circuit 7 162 – High Pressure – Circuit 6 163 – High Pressure – Circuit 5 164 – High Pressure – Circuit 4 165 – High Pressure – Circuit 3 166 – High Pressure – Circuit 2 167 – High Pressure – Circuit 1 169 – Sump Water Level Problem 179 – EFT_LCT Problem 182– Return Air Sensor Problem 185 – Space Sensor Problem 188 – OAT Sensor Problem 191 – EWT Problem 194 – MAT Problem 197 – Freeze Problem 199 – Heat Fail Problem

LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoProbAlarm DAC, SCC Yes SNVT_hvac_status 112 Property Value Same as BACnet

116 ED15112-12 Fault Alarm Keypad Menu Path No Keypad Equivalent This object allows individual notification of the highest priority active fault alarm. The value in the table below is the largest number in its enumeration that corresponds to an active alarm. This object is set to zero if no fault alarms are active.

Measurement Units Data Type Valid Range Default Value Alarms N/A BACnet: Real Enumerated N/A LON WORKS : Structure BACnet Object Identifier Property Object Type Type ID Instance Name ID Analog Value 2 26 Present_Value 85 Full Reference .ActiveFault.Present_Value Enumeration 0 – No Active Alarms 208 – Airflow Fault 212 – Low Discharge Air Temp 216 – High Discharge Air Temp 220 – High Return Air Temp 224 – Duct High Limit 228 – Discharge Sensor Fail 244 – Control Temp Fault 250 – Emergency Stop Fault 252 – Freeze Fault LON WORKS LON WORKS Name Profile Uses Heartbeat SNVT Type SNVT Index nvoFaultAlarm DAC, SCC Yes SNVT_hvac_status 112 Property Value Same as BACnet

Airflow Fault Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Airflow Fault alarm is active (1) or not (0).

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 27 Present_Value 85 Full Reference .AirflowFlt.Present_Value Enumeration 0 – Normal 1 – Alarm

LON WORKS No LON WORKS equivalent.

ED15112-12 117

Airflow Switch Warning Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Airflow Switch Warning is active (1) or not (0).

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 2 Present_Value 85 Full Reference .AFSwWrn.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Charge Loss Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the refrigerant system charge has been completely lost (1) or not (0).

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 41 Present_Value 85 Full Reference .ChargeLossPrb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Conductivity Warning Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Conductivity Warning alarm is active (1) or not active (0). This variable applies only to unit configured for evaporative condensing.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 3 Present_Value 85 Full Reference .ConductivityWrn.Present_Value

118 ED15112-12 Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent. Control Temp Fault Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Control Temperature Fault alarm is active (1) or not active (0).

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 28 Present_Value 85 Full Reference .ControlTempFlt.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Dirty Filter Warning Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Dirty Filter Warning alarm is active (1) or not active (0).

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 4 Present_Value 85 Full Reference .DrtyFltrWrn.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Discharge Sensor Fault Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Discharge Sensor Fault alarm is active (1) or not active (0).

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 29 Present_Value 85

ED15112-12 119 Full Reference .DischSensorFlt.Present_Value Enumeration 0 – normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Duct High Limit Fault Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Duct High Limit Fault alarm is active (1) or not active (0). This variable only applies to units configured for supply fan VFDs.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 30 Present_Value 85 Full Reference .DuctHiLmtFlt.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Emergency Off Fault Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Emergency Off Fault alarm is active (1) or not active (0).

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 31 Present_Value 85 Full Reference .EmergencyOffFlt.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Entering Fan Temp / Leaving Coil Temp Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Entering Fan Temp/Leaving Coil Temp Problem alarm is active (1) or not active (0).

120 ED15112-12 Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 5 Present_Value 85 Full Reference .EFT_LCTPrb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Entering Water Temp Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Entering Water Temperature Problem alarm is active (1) or not active (0). This variable only applies to units configured for a waterside condenser.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 6 Present_Value 85 Full Reference .EntWtrTmpPrb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Expansion Valve Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Expansion Valve Problem alarm is active (1) or not active (0). This property applies only to Rebel units.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 40 Present_Value 85 Full Reference .ExpValvePrb.Present_Value Enumeration 0 – Normal 1 – Alarm

ED15112-12 121 LON WORKS No LON WORKS equivalent.

Freeze Fault Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Freeze Fault alarm is active (1) or not active (0).

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 32 Present_Value 85 Full Reference .FreezeFault.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Freeze Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Freeze Problem alarm is active (1) or not active (0). This variable applies only to units configured for at least one of the following: waterside economizer, face and bypass heating, steam/hot water heating, chilled water cooling or face and bypass cooling.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 7 Present_Value 85 Full Reference .FreezePrb.Present_Value Enumeration 0 – normal 1 – Alarm LON WORKS No LON WORKS equivalent.

122 ED15112-12

Heat Fail Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether or not the Heat Fail Switch is in alarm (Alarm (1) or Normal (0)).

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumeration 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 5 38 Present_Value 85 Full Reference .HeatFailProb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

High Discharge Line Temperature Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the High Discharge Temperature Problem alarm is active (1) or not active (0). This property applies only to Rebel units.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 35 Present_Value 85 Full Reference .HiDLTempPrb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

High Discharge Line Temperature Unload Event Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the High Discharge Line Temperature Unload Event. The OffNormal state of this object indicates the High Discharge Line Temperature Unload Event is active.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 55 Present_Value 85 Full Reference . HiDLTmpUnldEvnt.Present_Value

ED15112-12 123 Enumeration 0 – Inactive 1 – Active LON WORKS No LON WORKS equivalent.

High Inverter Compressor Body Temp Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the High Inverter Compressor Body Temp Problem alarm is active (1) or not active (0).

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 5 43 Present_Value 85 Full Reference .HiINVTmpPrb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

High Discharge Superheat Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the High Discharge Superheat Problem. The OffNormal state of this object indicates the High Discharge Superheat Problem is active.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 50 Present_Value 85 Full Reference .HiDischSHPrb.Present_Value Enumeration 0 – Normal 1 – Alarm

High Discharge Superheat Unload Event Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the High High Discharge Superheat Unload Event. The OffNormal state of this object indicates the High Discharge Superheat Unload Event is active.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

124 ED15112-12 BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 57 Present_Value 85 Full Reference . HiDschSHUnldEvnt.Present_Value Enumeration 0 – Inactive 1 – Active LON WORKS No LON WORKS equivalent.

High Pressure Circuit 1 Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the High Pressure Circuit 1 Problem alarm is active (1) or not active (0). This variable applies only to units configured for two or more mechanical cooling circuits.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 8 Present_Value 85 Full Reference .HiPressCkt1Prb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

High Pressure Circuit 2 Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the High Pressure Circuit 2 Problem alarm is active (1) or not active (0). This variable applies only to units configured for two or more mechanical cooling circuits.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 9 Present_Value 85 Full Reference .HiPressCkt2Prb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

ED15112-12 125 High Pressure Circuit 3 Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the High Pressure Circuit 3 Problem alarm is active (1) or not active (0). This variable applies only to units configured for three or more mechanical cooling circuits.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 10 Present_Value 85 Full Reference .HiPressCkt3Prb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

High Pressure Circuit 4 Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the High Pressure Circuit 4 Problem alarm is active (1) or not active (0). This variable applies only to units configured for four or more mechanical cooling circuits.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 11 Present_Value 85 Full Reference .HiPressCkt4Prb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent. High Pressure Circuit 5 Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the High Pressure Circuit 5 Problem alarm is active (1) or not active (0). This variable applies only to units configured for five mechanical cooling circuits.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 12 Present_Value 85 Full Reference .HiPressCkt5Prb.Present_Value

126 ED15112-12 Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

High Pressure Circuit 6 Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the High Pressure Circuit 6 Problem alarm is active (1) or not active (0). This variable applies only to units configured for six or more mechanical cooling circuits.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 13 Present_Value 85 Full Reference .HiPressCkt6Prb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent. High Pressure Circuit 7 Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the High Pressure Circuit 7 Problem alarm is active (1) or not active (0). This variable applies only to units configured for seven or more mechanical cooling circuits.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 52 Present_Value 85 Full Reference .HiPressCkt7Prb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

High Pressure Circuit 8 Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the High Pressure Circuit 8 Problem alarm is active (1) or not active (0). This variable applies only to units configured for eight or more mechanical cooling circuits.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

ED15112-12 127 BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 53 Present_Value 85 Full Reference .HiPressCkt8Prb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

High Pressure Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the High Pressure Problem alarm is active (1) or not active (0). This property applies only to Rebel units.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 32 Present_Value 85 Full Reference .HiPress1Prb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

High Pressure Unload Event Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the High Pressure Unload Event. The OffNormal state of this object indicates the High Pressure Unload Event is active.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 52 Present_Value 85 Full Reference .HiPressUnldEvnt.Present_Value Enumeration 0 – Inactive 1 – Active LON WORKS No LON WORKS equivalent.

128 ED15112-12 High Return Temp Fault Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the High Return Temperature Fault alarm is active (1) or not active (0). This variable applies only to units configured for a return air temperature sensor.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 34 Present_Value 85 Full Reference .HiReturnTmpFlt.Present_Value Enumeration 0 – normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Interface Board Communication Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Interface Board Communication Problem alarm is active (1) or not active (0). This property applies only to Rebel units.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 38 Present_Value 85 Full Reference .IFBCommPrb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Inverter Compressor Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Inverter Compressor Problem alarm is active (1) or not active (0). This property applies only to Rebel units.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 34 Present_Value 85 Full Reference .INVCompPrb.Present_Value

ED15112-12 129 Enumeration 0 – normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Low Discharge Pressure Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Low Discharge Pressure Problem. The OffNormal state of this object indicates the Low Discharge Pressure Problem is active.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 48 Present_Value 85 Full Reference .LoDischPPrb.Present_Value Enumeration 0 – Normal 1 – Alarm

Low Discharge Pressure Unload Event Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Low Discharge Pressure Unload Event. The OffNormal state of this object indicates the Low Discharge Pressure Unload Event is active.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 53 Present_Value 85 Full Reference .LoDschPUnldEvnt.Present_Value Enumeration 0 – Inactive 1 – Active LON WORKS No LON WORKS equivalent.

Low Discharge Superheat Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Low Discharge Superheat Problem. The OffNormal state of this object indicates the Low Discharge Superheat Problem is active.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

130 ED15112-12 BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 49 Present_Value 85 Full Reference .LoDischSHPrb.Present_Value Enumeration 0 – Normal 1 – Alarm

Low Discharge Superheat Unload Event Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Low Low Discharge Superheat Unload Event. The OffNormal state of this object indicates the Low Discharge Superheat Unload Event is active.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 56 Present_Value 85 Full Reference .LoDschSHUnldEvnt.Present_Value Enumeration 0 – Inactive 1 – Active LON WORKS No LON WORKS equivalent.

Low Discharge Temp Fault Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Low Discharge Temperature Fault alarm is active (1) or not active (0).

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 35 Present_Value 85 Full Reference .LoDischTmpFlt.Present_Value Enumeration 0 – normal 1 – Alarm LON WORKS No LON WORKS equivalent. Low Pressure Circuit 1 Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Low Pressure Circuit 1 Problem alarm is active (1) or not active (0). This variable applies only to units configured for two or more mechanical cooling circuits.

ED15112-12 131 Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 14 Present_Value 85 Full Reference .LoPressCkt1Prb.Present_Value Enumeration 0 – normal 1 – Alarm LON WORKS No LON WORKS equivalent. Low Pressure Circuit 2 Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Low Pressure Circuit 2 Problem alarm is active (1) or not active (0). This variable applies only to units configured for two or more mechanical cooling circuits.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 15 Present_Value 85 Full Reference .LoPressCkt2Prb.Present_Value Enumeration 0 – normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Low Pressure Circuit 3 Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Low Pressure Circuit 3 Problem alarm is active (1) or not active (0). This variable applies only to units configured for three or more mechanical cooling circuits.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 16 Present_Value 85 Full Reference .LoPressCkt3Prb.Present_Value Enumeration 0 – normal 1 – Alarm

132 ED15112-12 LON WORKS No LON WORKS equivalent.

Low Pressure Circuit 4 Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Low Pressure Circuit 4 Problem alarm is active (1) or not active (0). This variable applies only to units configured for four or more mechanical cooling circuits.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 17 Present_Value 85 Full Reference .LoPressCkt4Prb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Low Pressure Circuit 5 Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Low Pressure Circuit 5 Problem alarm is active (1) or not active (0). This variable applies only to units configured for five or more mechanical cooling circuits.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 18 Present_Value 85 Full Reference .LoPressCkt5Prb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Low Pressure Circuit 6 Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Low Pressure Circuit 6 Problem alarm is active (1) or not active (0). This variable applies only to units configured for six or more mechanical cooling circuits.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

ED15112-12 133 BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 19 Present_Value 85 Full Reference .LoPressCkt6Prb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Low Pressure Circuit 7 Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Low Pressure Circuit 7 Problem alarm is active (1) or not active (0). This variable applies only to units configured for seven or more mechanical cooling circuits.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 50 Present_Value 85 Full Reference .LoPressCkt7Prb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Low Pressure Circuit 8 Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Low Pressure Circuit 8 Problem alarm is active (1) or not active (0). This variable applies only to units configured for eight or more mechanical cooling circuits.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 51 Present_Value 85 Full Reference .LoPressCkt8Prb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

134 ED15112-12 Low Pressure Differential Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Low Pressure Differential Problem alarm is active (1) or not active (0).

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 39 Present_Value 85 Full Reference .LoPressDiffPrb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent. Low Pressure Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Low Pressure Problem alarm is active (1) or not active (0). This property applies only to Rebel units.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 33 Present_Value 85 Full Reference .LoPress1Prb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Low Refrigerant Charge Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Low Refrigerant Charge Problem alarm is active (1) or not active (0). This property applies only to Rebel units.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 37 Present_Value 85 Full Reference .LoChargePrb.Present_Value

ED15112-12 135 Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Low Superheat Warning Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Low Superheat Warning alarm is active (1) or not active (0).

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 5 46 Present_Value 85 Full Reference .LowSuperHtWrn.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Mixed Air Temp Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Mixed Air Temperature Problem alarm is active (1) or not active (0). This variable applies only to units configured for a mixed air temperature sensor.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 20 Present_Value 85 Full Reference .MixAirTmpPrb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

136 ED15112-12

Oil Boost Event Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Oil Boost Event. The OffNormal state of this object indicates the Oil Boost Event is active.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 59 Present_Value 85 Full Reference .OilBoostEvnt.Present_Value Enumeration 0 – Inactive 1 – Active LON WORKS No LON WORKS equivalent.

Outdoor Temp Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Outdoor Temperature Problem alarm is active (1) or not active (0). This variable applies only to units configured for an outdoor temperature sensor.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 21 Present_Value 85 Full Reference .OutdoorTmpPrb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent. Outdoor Fan Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Outdoor Fan Problem alarm is active (1) or not active (0). This property applies only to Rebel units.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 36 Present_Value 85 Full Reference .OAFanPrb.Present_Value

ED15112-12 137 Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Reheat Stage Limited Event Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Reheat Stage Limited Event. The OffNormal state of this object indicates the Reheat Stage Limited Event is active.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 58 Present_Value 85 Full Reference .RhtStgLmtEvnt.Present_Value Enumeration 0 – Inactive 1 – Active LON WORKS No LON WORKS equivalent.

Return Temp Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Return Temperature Problem alarm is active (1) or not active (0). This variable applies only to units configured for a return air temperature sensor.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 22 Present_Value 85 Full Reference .ReturnTmpPrb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Return/Exhaust Fan Warning Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the return/exhaust fan farning is active.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

138 ED15112-12 BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 42 Present_Value 85 Full Reference .Ret/ExhFanWrn.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Space Temp Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Space Temperature Problem alarm is active (1) or not active (0). This variable applies only to units configure for a space temperature sensor.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 23 Present_Value 85 Full Reference .SpaceTmpPrb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Sump Water Level Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Sump Water Level Problem alarm is active (1) or not active (0). This variable applies only to units configured for an evaporative condenser.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 24 Present_Value 85 Full Reference .SmpWtrLvlPrb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

ED15112-12 139

Variable Compressor Emergency Stop Event Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the High Variable Compressor Emergency Stop Event. The OffNormal state of this object indicates the Variable Compressor Emergency Stop Event is active.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 54 Present_Value 85 Full Reference .VarCmpEmrgStopEvnt.Present_Value Enumeration 0 – Inactive 1 – Active LON WORKS No LON WORKS equivalent.

Variable Compressor Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates the condition of the Variable Compressor Problem. The OffNormal state of this object indicates the Variable Compressor Problem alarm is active.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Input 3 47 Present_Value 85 Full Reference .VarCompPrb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

Waterflow Switch Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Waterflow Switch Problem alarm is active (1) or not active (0). This variable applies only to units configured for a waterside condenser.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 25 Present_Value 85

140 ED15112-12 Full Reference .WtrFlowSwPrb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent. Water Regulating Valve Problem Keypad Menu Path No Keypad Equivalent This read-only BACnet object indicates whether the Water Regulating Valve Problem alarm is active (1) or not active (0). This variable applies only to units configured for head pressure control.

Measurement Units Data Type Valid Range Default Value Alarm N/A Enumerated 0-1 N/A

BACnet Object Identifier Property Object Type Type ID Instance Name ID Binary Value 5 26 Present_Value 85 Full Reference .WtrRegVlvPrb.Present_Value Enumeration 0 – Normal 1 – Alarm LON WORKS No LON WORKS equivalent.

ED15112-12 141 BACnet Device Management

The following functions are specific to the BACnet device. These functions are used for maintenance and testing. A network management tool such as VTS is typically used to issue the network commands.

DeviceCommunicationControl - Disable The purpose of this command is to reduce network traffic for diagnostic testing of the BACnet network. When the BACnet Communication module receives a network command to Disable communications it stops communicating information to the network. An optional time may be specified for how long to suspend communications. The unit continues to operate during the Disabled state.

DeviceCommunicationControl - Enable When the BACnet Communication module receives a network command to Enable communications, MicroTech III AHU communications to BACnet is restored.

ReinitializeDevice (Reset) When the BACnet Communication module is capable of receiving a network ReinitializeDevice command to reboot itself (cold start or warm start). The functionality of a cold and warm start are the same and simple reboot the BACnet Communication module. No password is required.

142 ED15112-12 BACnet File Objects

The MicroTech III unit controller contains several file objects that may be available via BACnet. Whether or not the objects are available depends on the firmware version of the BACnet communication module attached to the unit controller.

Note: The file objects described below are only available with BACnet firmware (BSP) version 9.26 and later. Earlier versions of the BACnet firmware do not support these objects. BACnet Client Config File Keypad Menu Path No Keypad Equivalent This file contains the BACnet client configuration. However, the MicroTech III unit controller acts as a server (versus a client), so the BACnet Client Config File does not apply to this application. Object Identifier Property Object Type Type ID Instance File Access Method ID File 10 1 Stream-access (1) 41 Full Reference .BACnetClientConfig

BACnet COV Config File Keypad Menu Path No Keypad Equivalent This file contains the BACnet Change of Value (COV) configuration. Object Identifier Property Object Type Type ID Instance File Access Method ID File 10 2 Stream-access (1) 41 Full Reference .BACnetCOVConfig

Error Log File Keypad Menu Path No Keypad Equivalent This is the error log file for the BACnet communication module. The information displayed in the error log may vary depending on the BAS. Object Identifier Property Object Type Type ID Instance File Access Method ID File 10 3 Stream-access (1) 41 Full Reference .ErrorLog

History Log File Keypad Menu Path No Keypad Equivalent This is the history log file for the BACnet communication module. Object Identifier Property Object Type Type ID Instance File Access Method ID File 10 4 Stream-access (1) 41 Full Reference .HistoryLog

ED15112-12 143 BACnet Event Enrollment Config File Keypad Menu Path No Keypad Equivalent This is the BACnet Event Enrollment Configuration file. Object Identifier Property Object Type Type ID Instance File Access Method ID File 10 5 Stream-access (1) 41 Full Reference .BACnetEventEnrollmentConfig

EDE File Keypad Menu Path No Keypad Equivalent This is the engineering data exchange file of this controller. This file details the BACnet interface of the unit controller. It describes what points are available and information about each point. Object Identifier Property Object Type Type ID Instance File Access Method ID File 10 6 Stream-access (1) 41 Full Reference .EDE-File

EDE File – State Text Keypad Menu Path No Keypad Equivalent This is the engineering data exchange file of this controller with state text. This file details the BACnet interface of the unit controller. It describes what points are available and information about each point. Object Identifier Property Object Type Type ID Instance File Access Method ID File 10 7 Stream-access (1) 41 Full Reference .EDE-File_StateText

144 ED15112-12 Appendix A: Protocol Implementation Conformance Statement (PICS)

This section contains the Protocol Implementation Conformance Statement (PICS) for the MicroTech III Unit Controller as required by ANSI/ASHRAE (American National Standards Institute/American Society of Heating, Refrigeration, and Engineers) Standard 135-2008, BACnet; A Data Communication Protocol for Building Automation and Control Networks.

BACnet Protocol Implementation Conformance Statement Date December 2011 Vendor Name Daikin Applied Product Name Unit Controller Product Model Number AHU Application Software Version - Rooftop and Self-Contained Models RDE, RPS, 2506017500 RDT, RFS, RDS, RAH, SWT, SWP and Maverick II, Model MPS Application Software Version - Rebel Packaged Rooftop, Model DPS 2506018200 Firmware Revision 10.26 BACnet Protocol Revision Version 1 Revision 10

Product Description The MicroTech III Unit Controller with optional BACnet Communication Module is a microprocessor-based controller designed to operate Air Handling Units (Applied Rooftop, Self-Contained, Maverick II Commercial Rooftop, and Rebel Packaged Rooftop) and integrate them into BACnet building automation systems. The unit controller provides normal temperature, static pressure and ventilation control and alarm monitoring with alarm- specific component shutdown in critical system conditions. Access to temperatures, pressures, operating states, alarm messages, control parameters and schedules is available through an equipment-mounted keypad/display and the BACnet control network. BACnet Standardized Device Profile Based on BIBBs supported, the MicroTech III Unit Controller with optional BACnet Communications Module is a BACnet Building Controller (B-BC). Refer to the section below entitled BACnet Interoperability Building Blocks (BIBBs) Supported for a complete listing of BIBBS. BACnet Operator Workstation (B-OWS) BACnet Building Controller (B-BC) BACnet Advanced Application Specific Controller (B-AAC) BACnet Application Specific Controller (B-ASC) BACnet Smart Sensor (B-SS) BACnet Smart Actuator (B-SA)

ED15112-12 145 BACnet Interoperability Building Blocks (BIBBs) Supported BIBB Name Designation Data Sharing – ReadProperty – B DS-RP-B Data Sharing – ReadPropertyMultiple – B DS-RPM-B Data Sharing – WriteProperty – B DS-WP-B Data Sharing – WritePropertyMultiple – B DS-WPM-B Data Sharing – COV – B DS-COV-B Data Sharing – ReadProperty – A DS-RP-A Data Sharing – ReadPropertyMultiple – A DS-RPM-A Data Sharing – WriteProperty – A DS-WP-A Data Sharing – COV – A DS-COV-A Alarm & Event – Notification Internal - B AE-N-I-B Alarm & Event – AcknowledgeAlarm - B AE-ACK-B Alarm & Event – ACK –B AE-ACK-B Alarm & Event – Information - B AE-INFO-B Alarm & Event – Alarm Summary - B AE-ASUM-B Alarm & Event – Event-Enrollment Summary - B AE-ESUM-B Scheduling – Internal - B SCHED-I-B Scheduling – External - B SCHED-E-B Trending – Viewing and Modifying Trends Internal – B T-VMT-I-B Trending – Automated Trend Retrieval – B T-ATR-B Device Management – Dynamic Device Binding – A DM-DDB-A Device Management – Dynamic Device Binding – B DM-DDB-B Device Management – Dynamic Object Binding – B DM-DOB-B Device Management – Device Communication Control – B DM-DCC-B Device Management – TimeSynchronization – B DM-TS-B Device Management – UTCTimeSynchronization – B DM-UTS-B Device Management – Reinitialize Device – B DM-RD-B Device Management – List Manipulation – B DM-LM-B Device Management – Object Creation and Deletion – B DM-OCD-B Device Management – Backup and Restore – B DM-BR-B Network Management – Connection Establishment – A NM-CE-A

146 ED15112-12 Standard Object Types Supported

Object-Type Optional Properties Supported Writeable Properties Not Required To Be Writeable

Creatable Deleteable 1 Analog Input Description Present_Value High_Limit COV_Increment 2 Low_Limit Event_Enable COV_Increment Limit_Enable 3 Notification_Class Reliability Max_Pres_Value Min_Pres_Value Deadband Acked_Transitions Event_Enable Notify_Type Limit_Enable Time_Delay Event_Time_Stamps Analog Output Description Out_Of_Service Reliability Relinquish_Default Min_Pres_Value High_Limit Max_Pres_Value Low_Limit COV_Increment Deadband Time_Delay Limit_Enable Notification_Class COV_Increment 2 High_Limit Event_Enable Low_Limit Deadband Limit_Enable Event_Enable Acked_Transistions Notify_Type Event_Time_Stamps Analog Value Description Present_Value 1,6 High_Limit COV_Increment 2 Low_Limit Event_Enable COV_Increment Priority_Array Relinquish_Default Notification_Class Reliability Deadband Acked_Transistions Event_Enable Notify_Type Limit_Enable Time_Delay Event_Time_Stamps

ED15112-12 147

Object-Type Optional Properties Supported Writeable Properties Not Required To Be Writeable Creatable Deleteable Binary Input Description Present_Value Inactive_Text Event_Enable Active_Text Elapsed_Active_Time (only 0) Notification_Class Reliability Acked_Transitions Event_Enable Alarm_Value Notify_Type Time_Delay Event_Time_Stamps Elapsed_Active_Time Time_Of_Active_Time_Reset Binary Output Description Event_Enable Reliability Polarity Inactive_Text Feedback_Value Active_Text Relinquish_Default Notification_Class Elapsed_Active_Time (only 0) Feedback_Value Acked_Transitions Event_Enable Notify_Type Time_Delay Event_Time_Stamps Elapsed_Active_Time Time_Of_Active_Time_Reset Binary Value Description Acked_Transitions Inactive_Text Event_Enable Active_Text Present_Value 1,5 Priority_Array Elapsed_Active_Time (only 0) Relinquish_Default Notification_Class Reliability Acked_Transitions Event_Enable Alarm_Value Notify_Type Time_Delay Event_Time_Stamps Elapsed_Active_Time Time_Of_Active_Time_Reset Calendar Description Date_List (Max 10)

148 ED15112-12

Object-Type Optional Properties Supported Writeable Properties Not Required To Be Writeable Creatable Deleteable Device Location Description Description Location Active_Cov_Subsription (<=50) Max_ADPU_Length_Accepted(1476>= x >=50) ADPU_Segment_Timeout UTC_Offset Local_Time Max_Segments_Accepted Local_Date ADPU_Segment_Timeout (>100) UTC_Offset APDU_Timeout (>100) Daylight_Savings_Status Number_Of_APDU_Retries Max_Master (MS/TP only) Segmentation_Supported Max_Info_Frames (MS/TP only) Max_Master (MS/TP only) Max_Segments_Accepted Max_Info_Frames (MS/TP only) Configuration_Files Last_Restore_Time Backup_Failure_Timeout Event_Enrollment Object_Name Event_Type Notify_Type Event_Parameters Object_Property_Reference Event_Enable Notification_Class File Description Multi-State Input Description Present_Value(if Out Of Service=True) State_Text Out_Of_Service Notification_Class Event_Enable Acked_Transitions Alarm_Values (max 16) Event_Enable Fault_Values (max 16) Notify_Type Time_Delay Alarm_Values Fault_Values Reliability Event_Time_Stamps Multi-State Description Event_Enable Output Reliability Relinquish_Default (1…Number_Of_States) State_Text Notification_Class Acked_Transitions Event_Enable Notify_Type Time_Delay Event_Time_Stamps Feedback_Value Notification Class Description Recipient_List (Max 20) Priority Ack_Required Schedule Description Present_Value4 Weekly_Schedule Schedule_Default Exception_Schedule Effective_Period Weekly_Schedule (Max 6 per day) Priority_For_Writing (1..16) Exception_Schedule List_Of_Object_Property_Refs

ED15112-12 149

Object-Type Optional Properties Supported Writeable Properties Not Required To Be Writeable

Creatable Deleteable 1 Multi-State Value Description Present_Value Priority_Array Event_Enable Relinquish_Default Notification_Class Reliability Acked_Transitions Event_Enable Alarm_Values Fault_Values Notify_Type Time_Delay Event_Time_Stamps State_Text Trend_Log Description Start_Time Start_Time Stop_Time Stop_Time Log_Device_Object_Property Log_Device_Object_Property Log_Interval Log_Interval Client_COV_Increment Client_COV_Increment Stop_When_Full Notification_Threshold Notification_Threshold Records_Since_Notification Event_Enable Last_Notify_record Notification_Class Event_Enable Acked_Transistions Notify_Type Event_Time_Stamps 1 Some objects of this type are read only. For those objects, the Present_Value is not commandable or writable. 2 Changes to this property do not take effect until the power is cycled on the unit controller. After changing COV_Increment, you must wait at least one minute before cycling power. Otherwise, this change will not be saved. 3 Thought this property is writable via BACnet, if the object is setup for Intrinsic Reporting, this value will revert to the controller value. This is a safety feature so the network cannot disable alarms from occurring. 4 Writeable only if Out of Service is true. Also limited to multistate or analog. 5 Priority 5 is reserved for the application for commandable objects. BACnet writes at priority 5 will fail. 6 Priority 1 is reserved for the application for commandable objects. BACnet writes at priority 1 will fail.

Data Link Layer Options BACnet IP, (Annex J) BACnet IP, (Annex J), Foreign Device MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 76800 MS/TP slave (Clause 9), baud rate(s): 9600, 19200, 38400, 76800

Segmentation Capability Segmented requests supported Window Size: 4 for IP and 1 for MS/TP Segmented responses supported Window Size: 4 for IP and 1 for MS/TP

Device Address Binding Static Device Binding Yes No

150 ED15112-12 Networking Options Router, Clause 6 – List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc. Annex H, BACnet Tunneling Router over IP BACnet/IP Broadcast Management Device (BBMD) Number of BDT entries: Does the BBMD Support registration by Foreign Devices? Yes No

Character Sets Supported ANSI X3.4 IBM /Microsoft  DBCS ISO 8859-1 ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS C 6226 Note: Support for multiple character sets does not imply they can be supported simultaneously.

ED15112-12 151 Index

AHU Loc/Net, 20, 32, 34 Economizer Enable, 13, 20, 26, 32, 49 Airflow Fault, 22, 32, 106, 117 Economizer Hours, 19, 31, 50 Airflow Switch, 23, 33 Economizer Status, 17, 25, 30, 50 Airflow Switch (Fault), 35 EDE File, 24, 34, 144 Airflow Switch (Warning), 23, 33, 36 EDE File – State Text, 24, 34, 144 Airflow Switch Warning, 22, 32, 107, 118 Eff Discharge Air Temp Setpoint, 20, 32 Alarm and Event Notification, 106, 109, 110, 111 Effective Cooling Discharge Setpoint, 78 Alarm Value, 21, 32, 112 Effective Cooling Enable Setpoint, 52 Alarms and Events, 15 Effective Discharge Air Temperature Setpoint, 51 Application Mode, 13, 14, 17, 25, 30, 34 Effective Discharge Setpoint, 27 Application Version, 21, 32, 36 Effective Enable Setpoint, 27 ASHRAE, 6, 8, 43, 96, 145 Effective Heating Discharge Setpoint, 79 BACnet Client Config File, 24, 34, 143 Effective Heating Enable Setpoint, 52 BACnet COV Config File, 24, 34, 143 Effective Minimum Outdoor Damper Position Setpoint, 79, 86 BACnet Event Enrollment Config File, 24, 34, 144 Effective Setpoint Output, 52, 95 BACnet Standard Objects, 14, 17 Emergency Off Fault, 22, 32, 106, 120 BACnet/IP, 6, 10 Emergency Off Switch, 23, 33, 52 BIBBs, 145, 146 Emergency Override, 14, 17, 25, 30, 53 Building Static Pressure, 18, 25, 30, 36 Energy Recovery Exhaust Air Temperature, 19, 31, 54 Building Static Pressure Setpoint, 18, 25, 30, 37 Energy Recovery Leaving Air Temperature, 19, 31, 53 Charge Loss Problem, 23, 33, 107, 118 Energy Recovery Wheel Hours, 20, 31, 54 Clear Alarms, 20, 27, 32, 108 Energy Recovery Wheel Speed, 19, 31, 55 Clearing, 108 Energy Recovery Wheel Status, 19, 31, 54 Compressor 1 Hours, 19, 31, 37 Entering Fan / Leaving Coil Temp, 17, 25, 30, 55 Compressor 2 Hours, 19, 31, 37 Entering Fan Temp / Leaving Coil Temp Problem, 22, 32, 106, 120 Compressor 3 Discharge Line Temperature Sensor Problem, 106 Entering Water Temp Problem, 22, 32, 106, 121 Compressor 3 Hours, 19, 31, 38 Entering Water Temperature, 17, 25, 30, 55 Compressor 4 Hours, 19, 31, 38 Error Log File, 24, 34, 143 Compressor 5 Hours, 19, 31, 38 Ethernet, 10 Compressor 6 Hours, 19, 31, 39 Example of BACnet Data Point, 8 Compressor 7 Hours, 19, 31, 39 Excess Outdoor Air Warning, 105 Compressor 8 Hours, 19, 31, 39 Exhaust Fan Capacity, 56 Compressor Cooling Hours, 19, 31, 40 Exhaust Fan Capacity Input, 13, 18, 26, 31, 56 Compressor Heating Hours, 19, 31, 40 Exhaust Fan Status, 8, 18, 30, 57 Conductivity, 18, 26, 31, 40 Expansion Valve Problem, 23, 33, 106, 121 Conductivity Warning, 22, 32, 107, 118 Fault Alarm, 21, 28, 32, 117 Control Temp Fault, 22, 32, 106, 119 Fault Alarms, 102 Control Temp Source, 18, 31, 41 free topology, 12 Control Temperature, 17, 30, 41 Freeze Fault, 22, 32, 106, 122 Cooling Capacity, 17, 25, 30, 42 Freeze Problem, 22, 32, 106, 122 Cooling Status, 17, 25, 30, 42 Freeze Switch (Fault), 23, 33, 57 Date, 10, 43, 149 Freeze Switch (Problem), 23, 33, 58 Defrost Sensor Problem, 106 Full Reference, 8 Defrost State, 20, 31, 43 Heat Fail Input, 23, 33, 58 Defrost Temperature, 18, 30, 43 Heat Fail Problem, 22, 32, 106, 123 Dehumidification Hours, 19, 31, 44 Heating Capacity, 17, 25, 30, 58 Dehumidification Status, 17, 30, 44 Heating Hours, 19, 31, 59 Device Object, 9 Heating Status, 17, 25, 30, 59 Dew Point Setpoint, 19, 26, 31, 44 High Discharge Line Temperature Problem, 23, 33, 106, 123 Dew Point Temperature, 19, 26, 31, 45 High Discharge Line Temperature Unload Event, 24, 33, 105, 107, 123 Dirty Filter Switch, 23, 33, 45 High Discharge Superheat Problem, 24, 33, 107, 124 Dirty Filter Warning, 22, 32, 107, 119 High Discharge Superheat Unload Event, 24, 34, 105, 108, 124 Discharge Air Controller profile, 6, 12 High Discharge Temp Fault, 22, 32, 106 Discharge Air Cooling Setpoint, 26 High Inverter Compressor Body Temp Problem, 23, 33, 107, 124 Discharge Air Heating Setpoint, 26 High Pressure Circuit 1 Problem, 22, 32, 106, 125 Discharge Air Temperature, 17, 25, 30, 45 High Pressure Circuit 1 Switch, 23, 33, 60 Discharge Line Temperature 1, 17, 30, 46 High Pressure Circuit 2 Problem, 22, 32, 106, 125 Discharge Line Temperature 2, 18, 30, 46 High Pressure Circuit 2 Switch, 23, 33, 60 Discharge Line Temperature 3, 17, 30, 46 High Pressure Circuit 3 Problem, 22, 32, 106, 126 Discharge Refrigerant Pressure, 19, 31, 47 High Pressure Circuit 3 Switch, 23, 33, 61 Discharge Refrigerant Pressure (PTD) Sensor Problem, 106 High Pressure Circuit 4 Problem, 22, 32, 106, 126 Discharge Refrigerant Pressure Circuit 1, 19, 47 High Pressure Circuit 4 Switch, 23, 33, 61 Discharge Refrigerant Pressure Circuit 2, 19, 47 High Pressure Circuit 5 Problem, 22, 32, 106, 126 Discharge Sensor Fault, 22, 32, 106, 119 High Pressure Circuit 5 Switch, 23, 33, 61 doubly-terminated network, 12 High Pressure Circuit 6 Problem, 22, 32, 106, 127 Duct High Limit Fault, 22, 32, 106, 120 High Pressure Circuit 6 Switch, 23, 33, 62 Duct High Limit Switch, 23, 33, 48 High Pressure Circuit 7 Problem, 22, 32, 107, 127 Duct Static Pressure, 14, 18, 25, 30, 48, 86 High Pressure Circuit 7 Switch, 23, 33, 62 Duct Static Pressure Setpoint, 14, 18, 25, 30, 49 High Pressure Circuit 8 Problem, 22, 32, 107, 127 Economizer Capacity, 17, 25, 30, 49 High Pressure Circuit 8 Switch, 23, 33, 63

152 ED15112-12 High Pressure Problem, 23, 33, 107, 128 Object Identifier, 8 High Pressure Unload Event, 24, 33, 105, 107, 128 Object Request, 28, 73 High Return Temp Fault, 22, 32, 106, 129 Object Status, 28, 74 History Log File, 24, 34, 143 Object Type, 8 HVAC Unit Type Identifier, 27, 63 Occupancy, 13, 17, 25, 30, 75, 76 In Alarm, 28, 108 Occupancy Mode, 14, 17, 25, 30, 76, 77 Indoor Refrigerant Temperature, 18, 30, 64 Occupancy Scheduler Input , 20, 26, 32, 77 Instance, 8 Occupied Cooling Setpoint, 14, 18, 26, 31, 78 Interface Board Communication Problem, 23, 33, 107, 129 Occupied Heating Setpoint, 14, 18, 26, 31, 79 interoperable, 6, 11 Oil Boost Event, 24, 34, 105, 108, 137 INV Comp Body Temp Sensor Problem, 107 ORT Sensor Problem, 106 Inverter Compressor Body Temperature, 18, 30, 64 Outdoor Air Damper Minimum Position Input, 20, 27, 32, 79 Inverter Compressor Discharge Line Temperature Sensor Problem, 107 Outdoor Air Damper Position, 79 Inverter Compressor Hours, 19, 31, 64 Outdoor Air Damper Stuck Warning, 105 Inverter Compressor Problem, 23, 33, 107, 129 Outdoor Air Temperature, 13, 14, 17, 25, 30, 80 IP address, 10 Outdoor Air Temperature Input, 20, 26, 31, 80 IP Subnet Mask, 10 Outdoor Airflow, 18, 26, 31, 81 IRT Sensor Problem, 106 Outdoor Airflow Setpoint, 18, 31, 81 Local OA Temperature, 21, 27, 32, 65 Outdoor Fan Problem, 23, 33, 107, 137 Local Space Temperature, 21, 27, 32, 65 Outdoor Refrigerant Temperature, 18, 30, 81 LonTalk, 30 Outdoor Temp Problem, 22, 33, 107, 137 LonWorks Variables, 11, 14, 25 Over Econo Warning, 105 Low Discharge Pressure Problem, 23, 33, 107, 130 Primary Cool Enable, 13, 20, 26, 32, 82 Low Discharge Pressure Unload Event, 24, 33, 105, 107, 130 Primary Heat Enable, 13, 20, 26, 32, 82 Low Discharge Superheat Problem, 24, 33, 107, 130 Problem Alarm, 21, 27, 32, 115 Low Discharge Superheat Unload Event, 24, 34, 105, 108, 131 Problem Alarms, 103 Low Discharge Temp Fault, 22, 32, 106, 131 properties, 30 Low Pressure Circuit 1 Problem, 22, 32, 107, 131 Protocol Implementation Conformance Statement, 6, 145 Low Pressure Circuit 1 Switch, 23, 33, 65 Receive Heartbeat, 20, 26, 31, 83 Low Pressure Circuit 2 Problem, 22, 32, 107, 132 Reheat Capacity, 19, 26, 31, 84 Low Pressure Circuit 2 Switch, 23, 33, 66 Reheat Stage Limited Event, 24, 34, 105, 108, 138 Low Pressure Circuit 3 Problem, 22, 32, 107, 132 Relative Humidity, 19, 26, 31, 84 Low Pressure Circuit 3 Switch, 23, 33, 66 Relative Humidity Input, 13, 20, 27, 32, 85 Low Pressure Circuit 4 Problem, 22, 32, 107, 133 Relative Humidity Setpoint, 19, 26, 31, 85 Low Pressure Circuit 4 Switch, 23, 33, 66 Remote Return/Exhaust Fan Capacity Control Flag, 18, 25, 31, 86, 89 Low Pressure Circuit 5 Problem, 22, 32, 107, 133 Remote Supply Fan Capacity Control Flag, 18, 25, 30, 86 Low Pressure Circuit 5 Switch, 23, 33, 67 Return Air Temperature, 14, 17, 25, 30, 87 Low Pressure Circuit 6 Problem, 22, 32, 107, 133 Return Fan Capacity Input, 13, 18, 25, 31, 89 Low Pressure Circuit 6 Switch, 23, 33, 67 Return Temp Problem, 22, 33, 107, 138 Low Pressure Circuit 7 Problem, 22, 33, 107 Return/Exhaust Fan Capacity, 17, 25, 30, 88 Low Pressure Circuit 7 Problem, 134 Return/Exhaust Fan Hours, 19, 31, 88 Low Pressure Circuit 7 Switch, 23, 33, 68 Return/Exhaust Fan Status, 25 Low Pressure Circuit 8 Problem, 22, 33, 107 Return/Exhaust Fan Warning, 23, 33, 104, 107, 138 Low Pressure Circuit 8 Problem, 134 Send Heartbeat, 26, 89 Low Pressure Circuit 8 Switch, 23, 33, 68 service pin, 13 Low Pressure Differential Problem, 23, 33, 135 Space CO 2, 18, 26, 31, 90 Low Pressure Problem, 23, 33, 107, 135 Space Comfort Controller, 6, 11, 12, 13 Low Refrigerant Charge Problem, 33, 107, 135 Space IAQ Input, 13, 20, 27, 32, 90 Low Refrigerant Differential Problem, 107 Space Setpoint Type, 95 Low Superheat Warning, 104 Space Temp Problem, 23, 33, 107, 139 Low Superheat Warning, 23, 33 Space Temperature, 13, 17, 25, 30, 90 Low Superheat Warning, 107 Space Temperature Input, 20, 26, 31, 91 Low Superheat Warning, 136 Staged Exhaust 1 Hours, 19, 31, 91 MAC address, 10 Staged Exhaust 2 Hours, 19, 31, 92 Max Purge Time, 20, 32, 68 Standard Configuration Parameter Type, 11 Maximum Discharge Air Heating Setpoint, 19, 26, 31, 69 Standard Network Variable Types, 11 Maximum Leaving Coil Temperature Dehum Setpoint, 20, 31, 69 Suction Line Refrigerant Temperature, 18, 30, 92 McQuay AHU Unit Status, 17, 25, 30, 69 Suction Line Refrigerant Temperature Sensor Problem, 107 Mechanical Cooling Hours, 19, 31, 70 Suction Refrigerant Pressure, 19, 31, 92 Minimum Discharge Air Cooling Setpoint, 18, 26, 31, 71 Suction Refrigerant Pressure (PTS) Sensor Problem, 107 Minimum Leaving Coil Temperature Dehum Setpoint, 20, 31, 71 Sump Pump Water Level Switch, 23, 33, 93 Minimum Send Time, 27, 71 Sump Water Level Problem, 23, 33, 107, 139 Mixed Air Temp Problem, 22, 33, 107, 136 Suplimental Heating Capacity, 17, 30, 93 Mixed Air Temperature, 17, 25, 30, 72 Suplimental Heating Status, 17, 93 Morning Warmup Heating Setpoint, 18, 31, 72 Supply Fan Capacity, 17, 25, 30, 94 MSTP, 6, 11 Supply Fan Capacity Input, 13, 18, 25, 30, 86, 94 Network Discharge Air Cooling Setpoint, 18, 31, 73 Supply Fan Hours, 19, 31, 95 Network Discharge Air Heating Setpoint, 19, 31, 73 Temperature Setpoint Input, 27, 52, 95 network variable, 30 Tenant Override Hours, 19, 31, 95 Neuron, 12, 13 Time, 10, 96, 149 Notice, 5 Type Enumeration, 8 Notification, 15 UDP, 10 Notification Class – Events, 21, 32, 109 Under Econo Warning, 105 Notification Class - Faults, 21, 32, 110 Unit State, 14, 17, 25, 30, 96 Notification Class - Problems, 21, 32, 110 Unit Status, 17, 108 Notification Class - Warnings, 21, 32, 111 Unit Support, 20, 31, 97

ED15112-12 153 Unoccupied Cooling Setpoint, 14, 18, 26, 31, 97 Warning Alarms, 104 Unoccupied Heating Setpoint, 14, 18, 26, 31, 98 Water Flow Switch, 23, 33, 100 Variable Compressor Emergency Stop Event, 24, 33, 105, 107, 140 Water Flow Switch Input, 13 Variable Compressor Hours, 20, 31, 99 Water Regulating Valve, 23, 33, 100 Variable Compressor Oil Status, 24, 33, 99, 107 Water Regulating Valve Problem, 23, 33, 107, 141 Variable Compressor Problem, 23, 107, 140 Waterflow Switch Input, 20, 27, 32, 100 VAV Box Output, 18, 25, 30, 98 Waterflow Switch Problem, 23, 33, 107, 140 Warning Alarm, 21, 27, 32, 115 XIF, 13

154 ED15112-9