<<

Redmond - Building Information Card Requirements Fire Alarm Sequence of Operations

Alarm Cause System System Actions • Permit submittals for new systems or significant changes shall include a zone Annunciation & map that must be posted by FACP before final alarm inspection. Transmission • Label all pages “Building Information Card” and include a description of the

geographic zone, such as the floor level. • The building information card must be comprised of two components: 1. Floor plans (example available at www.redmond.gov/934) Show all initiating devices, alarm panels, annunciators, and any other

important landmarks. Ensure the plan is legible and allows a reader to ctivate A Fire alarm control control Fire alarm panel Central station notification devices notification devices quickly identify and locate initiating devices. 2. Sequence of operations (example available at www.redmond.gov/934) Sequence of Operations A. Group the matrix inputs by the five RFDS 9.0-required alarm On On Off Alarm programming zones: Alarm Trouble Trouble Trouble Trouble Supervisory Supervisory Supervisory Supervisory

i. Alarm, e.g., heat and detectors horn/strobe ctivate exterior Dampers actuate actuate Dampers activated (red) Remote LED locks door electric Release (alter.) to 2nd floor elevator Recall (primary) to 1st floor elevator Recall A ii. Waterflow, not including tampers pressurization SPF-1 stair pressurization SPF-2 stair fire doors Release Level 1 /manual pulls • • • • • • • • • iii. Supervisory Level 2 smokes/manual pulls • • • • • • • • • iv. Trouble Kitchen hood suppression • • • • • • • • • v. Special systems, e.g., hood systems, pre-action systems Level 2 MDF room pre-action smokes • • • • • • • • •

B. Alarms and waterflows must be grouped by geographical area or Fire Alarm Elevator lobby (1st floor) • • • • • • • • • • floor. Elevator lobby smoke detector (floors 2–8 & base) • • • • • • • • • • C. Devices shall be programmed to come in with specific descriptions Elevator machine room smoke detector • • • • • • • • • • at the , e.g., "Floor 4 Smoke Alarm –Corridor P01 west dry waterflow • • • • • • • • • Smoke 4231 by Unit 436". P01 east dry waterflow • • • • • • • • • D. Device descriptions, as received by the central station, shall be P1 dry waterflow • • • • • • • • • brief, e.g., “Floor 4 Smoke Alarm”. Level 1 waterflow • • • • • • • • •

Waterflow Level 2 waterflow • • • • • • • • • Level 3 waterflow • • • • • • • • • Level 2 MDF pre-action waterflow • • • • • • • • • Sprinkler tamper • • • Duct smoke detectors • • • • • High/low air supervisory signal • • • each sheet of building information card Generator Running • • • Supervisory Name and address of building shall be noted on ERRS system • • • AC power failure • • • • Initiating device circuit – open, ground, or short • • • Notification appliance circuit, open, ground, or short • • • Communications fault/AES trouble • • • Low battery • • • General Troubles Generator fault • • • FSCP SPF-1 manual on • • • • • • • FSCP SPF-2 manual on • • • • • • • Actions

Notes: 1. All events (alarm, trouble, and supervisory) shall be recorded in system memory. 2. Not all of the matrix is necessarily used for this project. 3. Speakers will be provided a low-frequency (520 Hz) signal by the amplifier in order to produce 75 dBA at the pillow level per NFPA 72 18.4.5.

Sample Building Information Card Page 1 of 3 9 8 7 6 5 4 3 2 1 4 ENLARGED TRANSFORMER VAULT INSTALLATION DETAILS NOT TO SCALE FIRE-2018-01379 SYMBOL KEY 1/2" THREADED CONDUIT WITH WALL SV Sprinkler control valve THREADED COUPLER Standpipe 4 SQUARE BOX Single Contact Monitor Module LC1•S:00 EXPOSED AREA IN VAULT 18/4 SL FPLR S Address S- S+ SLC TO FACP Smoke detector 4" TO 12" FROM CEILING Z NO C

PROBE HEAT MP Manual pull station DETECTOR

D ANN Remote annunciator D CONDUIT W/ HEAT DETECTOR NEEDS TO BE INSTALLED SO THAT THE TRANSFORMER VAULT HEAT DETECTOR CAN BE REPLACED WITHOUT ENTERING THE TRANSFORMER KH Kitchen hood suppression system VAULT BY SLIDING THE CONDUIT OUT ON THE OPPOSITE SIDE OF THE WALL.

FACP Fire alarm control panel

FM 200 FM 200 suppression system

SLC1•M:025 MM GEN. FAULT SLC1•M:023, 024 DM GEN. RUN/STOP TRANSFORMER TRANSFORMER GENERATOR UP111b UP111a UP101

UP 135° 135° 4 4 FM 200 V V SHORT TERM BICYCLE UC STORAGE 48" x 48" OPENING IN J J Overhead doors providing ELECTRIC METERS UC access to the garage shall MM MM LP104 SLAB PER MECH. W/ open on activation of the UP113 SLC1•M:125 GARAGE FAN TRAFFIC RATED GREAT SLC1•M:124 building's . DELIVERY J SWITCHGEAR & WCF UP106 ELECTRIC METERS UP110 #18/4 FPLR SLC TO UP112 THE FLOORS ABOVE IN CONTINUOUS RACEWAY

REFUSE RECYCLE UP102 5 SLC1•M:021 RM GARAGE DOOR TRIGGER 4 STAIR 2 STAIRST-02 2 UC

TO LEVEL P02 ONLY

ELEV 1 ANN ELEV 1 ANN6 4

SLC1•S:003 SLC1•S:004 B S S C C ELEV 2

MP

UC UC UC B

LOWER LOBBY STAIR

UP

PARKING MAIL LEVEL P01 GARAGE DRY P100 LP101 WATERFLOW ZONE

48" x 48" OPENING IN SLAB PER MECH. W/ DN TRAFFIC RATED GREAT BIKE RM B

WOMEN MEN

STG UP

B SCREENING LP103 B each sheet of building information card Name and address of building shall be noted on

B KH 32" CMU WALL W/ FENCE LEVEL P01 ABOVE FITNESS WATERFLOWLP102 ZONE

UP SLC1•S:002 UC ELEVATOR 3 STAIR 5 S EL-03 BIKE RM ST-05 LP108 DNSTAIR 5

ELEC. RISER (ABOVE) UC UC

UC UC SUPPLY FROM P02 UP TO CEILING WALLS @ +42" UC 48" x 48" OPENING IN WALL @ +42" 48" x 48" OPENING IN 4 OF P01, SEE CIVIL FOR SLAB PER MECH. W/ SLAB PER MECH. W/ ENTRY POINT. SLC1•M:020 TRAFFIC RATED GREAT TRAFFIC RATED GREAT 5 RM GARAGE DOOR TRIGGER B

RAMP DOWN SL S S A RPS2 UTIL MPRPS1FACP F FACP FSCP GAS METER UP107 FACP/SPRINKLER AT GRADE 1 RISERFIRE SPRINKLER ROOM A Overhead doors providing access FA 9.0 to the garage shall open on UP109 activation of the building's fire alarm system.

MDF BIKE KITCHEN UP114 SP101

LEVEL P2 BELOW Sample Note: The building information card shall include a symbol key; geographic zones N Building for fire alarm and sprinkler waterflow; the location of firewalls, standpipes, and N Information sprinkler valves; and special systems (type I hood suppression systems, pre-action N systems, clean agent systems, etc.). Only initiating devices need to be shown. BUILDING INFORMATION CARD LEVELLEVEL P01 P01 Card SCALE : 1/8" = 1' Page 2 of 3

9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1

FIRE-2018-01379 SYMBOL KEY

SV Sprinkler control valve

Standpipe

LC1•S:00 SL S Smoke detector

MP Manual pull station

D D

#18/4 FPLR SLC TO ELEC. RM UP-133 ON THE FLOOR BELOW IN CONTINUOUS RACEWAY D4 - L1 A1.1 - L1 A1.9 - L1 A1.8 - L1 A1.7 - L1 A1A - L1 102 108 110 112 114 116

B5 - L1 B5.1 - L1 104 106 A3.1 - L1 B3.1 - L1 B3 - L1 A3 - L1 120 122 124

118 2-HR

OFFICE LR12

A6 - L1 OPEN OFFICE 100 LR07

BACK OFFICE LR10 OFFICE ISO RPS4 SLC1•S:011 SLC1•S:010 SLC1•S:009 LEVEL 1 SLC LR11 S S S SLC1•S:007 R&R UC UC UC S IDF 2 U102 ZN2•001 U101 MP TS ZN1•001 ZN1•001SVWF TS SLC2•M:001 DH MM SLC2•M:002, 003 DM UC SLC1•S:020 SLC1•S:021 SLC1•S:022 SLC1•S:023 STAIR 1 S S S S S MEETING ROOM SLC1•S:008 UC UC UC UC UC LR09 A6 - L1 STAIRST-01 1 DH 101

2-HR FIRE WALL ANN 6 S ELEVATOR 1 SLC1•S:024 EL-01 4 SLC1•S:030 VESTIBULE S LOBBY LEVEL 1 NORTH V01 C LR08 C5 - L1-5 C WATERFLOW ZONE ELEVATOR 2 109 (2) #16/4 FPLR (SBUS) EL-02 TO THE FACP ON P01 UC MP C4.2 - L1 E1A 115 D4.1 - L1 105 C4 - L1 UC DN 103 151 A4-L1 A4.1-L1 LOUNGE B DN 119 121 L108 SLC1•S:012 C4.1 - L1 S 150 UC 2-HR FIRE WALL

S UC SLC1•S:025 #18/4 FPLR SLC TO THE FACP IN CONTINUOUS RACEWAY (SEE RISER WIRING DETAIL) DH UC

DH A5.1 - L1 2-HR FIRE WALL 2-HR FIRE WALL 153 B2.2 - L1 152 S 2-HR FIRE WALL B2.1 - L1 SLC1•S:026 C3 - L1 133 136 SLC1•S:013 S

ENTRY GATE S3A - L1 155

#18/4 FPLR SLC TO THE FACP IN CONTINUOUS RACEWAY (SEE RISER WIRING DETAIL) UC DN UC A2.1 - L1 A2 - L1 154 135 C1 - L1 138 B E1A SLC1•S:027 169 S B

B11A each sheet of building information card D5 - L1-5 B2 - L1 SLC1•S:014 137 175 S 156

B10 - L1 TS MM 157 #18/4 FPLR SLC TO THE ZN1•001 SLC2•M:041 UC

FACP IN CONTINUOUS RACEWAY Name and address of building shall be noted on (SEE RISER WIRING DETAIL)

B9 - L1 STAIR 4 B C1A - L1 165 IDF 140 U103 UC STAIR 4 LEVEL 1 SOUTH S101 RPS3 RES STRG A2 - L1 ST-04 SLC1•S:029 S B4 - L1-5 WATERFLOW ZONE 158 2 177 ZN1•001 TS SV SC 3 MP MM ELEVATOR 3 SLC2•M:051 UTIL R S STAIR 5 EL-03 U104 SLC1•S:015 S STAIR 5 SLC1•S:028 MP ST-05 B1 - L1-5 SLC1•S:018 SLC1•S:017CORRIDOR SLC1•S:016 UTIL S S S 142 C103 U107 UC UC UC

RPS5 SL SLC1•S:019 S S 2

IDF U105

D8 - L1 S1.3 - L1 A DN 141 143 D1 D7 144 S1.1 - L1 S1 - L1 S1 - L1 S1 - L1 S1.2 - L1 160 172 170 168 166 164 LEVEL P2 BELOW A A1.3 - L1 B13 - L1-5 162 174 D6 - L1 SHARED FIRE APPARATUS ACCESS 176 AND DRIVEWAY

Sample Note: The building information card shall include a symbol key; geographic zones Building for fire alarm and sprinkler waterflow; the location of firewalls, standpipes, and N sprinkler valves; and special systems (type I hood suppression systems, pre-action Information systems, clean agent systems, etc.). Only initiating devices need to be shown. BUILDING INFORMATION CARD LEVELLEVEL 11 N Card SCALE : 1/8" = 1' Page 3 of 3

9 8 7 6 5 4 3 2 1