Fire Alarm Sequence of Operations

Total Page:16

File Type:pdf, Size:1020Kb

Fire Alarm Sequence of Operations Redmond Fire - Building Information Card Requirements Fire Alarm Sequence of Operations Alarm Cause System System Actions • Permit submittals for new systems or significant changes shall include a zone Annunciation & map that must be posted by FACP before final alarm inspection. Transmission • Label all pages “Building Information Card” and include a description of the geographic zone, such as the floor level. • The building information card must be comprised of two components: 1. Floor plans (example available at www.redmond.gov/934) Show all initiating devices, alarm panels, annunciators, and any other important landmarks. Ensure the plan is legible and allows a reader to ctivate A Fire alarm control control Fire alarm panel Central station notification devices notification devices quickly identify and locate initiating devices. 2. Sequence of operations (example available at www.redmond.gov/934) Sequence of Operations A. Group the matrix inputs by the five RFDS 9.0-required alarm On On Off Alarm programming zones: Alarm Trouble Trouble Trouble Trouble Supervisory Supervisory Supervisory Supervisory i. Alarm, e.g., heat and smoke detectors horn/strobe ctivate exterior Dampers actuate actuate Dampers activated (red) Remote LED locks door electric Release (alter.) to 2nd floor elevator Recall (primary) to 1st floor elevator Recall A ii. Waterflow, not including tampers pressurization SPF-1 stair pressurization SPF-2 stair fire doors Release Level 1 smokes/manual pulls • • • • • • • • • iii. Supervisory Level 2 smokes/manual pulls • • • • • • • • • iv. Trouble Kitchen hood suppression • • • • • • • • • v. Special systems, e.g., hood systems, pre-action systems Level 2 MDF room pre-action smokes • • • • • • • • • B. Alarms and waterflows must be grouped by geographical area or Fire Alarm Elevator lobby smoke detector (1st floor) • • • • • • • • • • floor. Elevator lobby smoke detector (floors 2–8 & base) • • • • • • • • • • C. Devices shall be programmed to come in with specific descriptions Elevator machine room smoke detector • • • • • • • • • • at the fire alarm control panel, e.g., "Floor 4 Smoke Alarm –Corridor P01 west dry waterflow • • • • • • • • • Smoke 4231 by Unit 436". P01 east dry waterflow • • • • • • • • • D. Device descriptions, as received by the central station, shall be P1 dry waterflow • • • • • • • • • brief, e.g., “Floor 4 Smoke Alarm”. Level 1 waterflow • • • • • • • • • Waterflow Level 2 waterflow • • • • • • • • • Level 3 waterflow • • • • • • • • • Level 2 MDF pre-action waterflow • • • • • • • • • Sprinkler tamper • • • Duct smoke detectors • • • • • High/low air supervisory signal • • • each sheet of building information card Generator Running • • • Supervisory Name and address of building shall be noted on ERRS system • • • AC power failure • • • • Initiating device circuit – open, ground, or short • • • Notification appliance circuit, open, ground, or short • • • Communications fault/AES trouble • • • Low battery • • • General Troubles Generator fault • • • FSCP SPF-1 manual on • • • • • • • FSCP SPF-2 manual on • • • • • • • Actions Notes: 1. All events (alarm, trouble, and supervisory) shall be recorded in system memory. 2. Not all of the matrix is necessarily used for this project. 3. Speakers will be provided a low-frequency (520 Hz) signal by the amplifier in order to produce 75 dBA at the pillow level per NFPA 72 18.4.5. Sample Building Information Card Page 1 of 3 9 8 7 6 5 4 3 2 1 4 ENLARGED TRANSFORMER VAULT HEAT DETECTOR INSTALLATION DETAILS NOT TO SCALE FIRE-2018-01379 SYMBOL KEY 1/2" THREADED CONDUIT WITH WALL SV Sprinkler control valve THREADED COUPLER Standpipe 4 SQUARE BOX Single Contact Monitor Module LC1•S:00 EXPOSED AREA IN VAULT 18/4 SL FPLR S Address S- S+ SLC TO FACP Smoke detector 4" TO 12" FROM CEILING Z NO C PROBE HEAT MP Manual pull station DETECTOR D ANN Remote annunciator D CONDUIT W/ HEAT DETECTOR NEEDS TO BE INSTALLED SO THAT THE TRANSFORMER VAULT HEAT DETECTOR CAN BE REPLACED WITHOUT ENTERING THE TRANSFORMER KH Kitchen hood suppression system VAULT BY SLIDING THE CONDUIT OUT ON THE OPPOSITE SIDE OF THE WALL. FACP Fire alarm control panel FM 200 FM 200 suppression system SLC1•M:025 MM GEN. FAULT SLC1•M:023, 024 DM GEN. RUN/STOP TRANSFORMER TRANSFORMER GENERATOR UP111b UP111a UP101 UP 135° 135° 4 4 FM 200 V V SHORT TERM BICYCLE UC STORAGE 48" x 48" OPENING IN J J Overhead doors providing ELECTRIC METERS UC access to the garage shall MM MM LP104 SLAB PER MECH. W/ open on activation of the UP113 SLC1•M:125 GARAGE FAN TRAFFIC RATED GREAT SLC1•M:124 building's fire alarm system. DELIVERY J SWITCHGEAR & WCF UP106 ELECTRIC METERS UP110 #18/4 FPLR SLC TO UP112 THE FLOORS ABOVE IN CONTINUOUS RACEWAY REFUSE RECYCLE UP102 5 SLC1•M:021 RM GARAGE DOOR TRIGGER 4 STAIR 2 STAIRST-02 2 UC TO LEVEL P02 ONLY ELEV 1 ANN ELEV 1 ANN6 4 SLC1•S:003 SLC1•S:004 B S S C C ELEV 2 MP UC UC UC B LOWER LOBBY STAIR UP PARKING MAIL LEVEL P01 GARAGE DRY P100 LP101 WATERFLOW ZONE 48" x 48" OPENING IN SLAB PER MECH. W/ DN TRAFFIC RATED GREAT BIKE RM B WOMEN MEN STG UP B SCREENING LP103 B each sheet of building information card Name and address of building shall be noted on B KH 32" CMU WALL W/ FENCE LEVEL P01 ABOVE FITNESS WATERFLOWLP102 ZONE UP SLC1•S:002 UC ELEVATOR 3 STAIR 5 S EL-03 BIKE RM ST-05 LP108 DNSTAIR 5 ELEC. RISER (ABOVE) UC UC UC UC FIRE SPRINKLER SUPPLY FROM P02 UP TO CEILING WALLS @ +42" UC 48" x 48" OPENING IN WALL @ +42" 48" x 48" OPENING IN 4 OF P01, SEE CIVIL FOR SLAB PER MECH. W/ SLAB PER MECH. W/ ENTRY POINT. SLC1•M:020 TRAFFIC RATED GREAT TRAFFIC RATED GREAT 5 RM GARAGE DOOR TRIGGER B RAMP DOWN SL S S A RPS2 UTIL MPRPS1FACP F FACP FSCP GAS METER UP107 FACP/SPRINKLER AT GRADE 1 RISERFIRE SPRINKLER ROOM A Overhead doors providing access FA 9.0 to the garage shall open on UP109 activation of the building's fire alarm system. MDF BIKE KITCHEN UP114 SP101 LEVEL P2 BELOW Sample Note: The building information card shall include a symbol key; geographic zones N Building for fire alarm and sprinkler waterflow; the location of firewalls, standpipes, and N Information sprinkler valves; and special systems (type I hood suppression systems, pre-action N systems, clean agent systems, etc.). Only initiating devices need to be shown. BUILDING INFORMATION CARD LEVELLEVEL P01 P01 Card SCALE : 1/8" = 1' Page 2 of 3 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 FIRE-2018-01379 SYMBOL KEY SV Sprinkler control valve Standpipe LC1•S:00 SL S Smoke detector MP Manual pull station D D #18/4 FPLR SLC TO ELEC. RM UP-133 ON THE FLOOR BELOW IN CONTINUOUS RACEWAY D4 - L1 A1.1 - L1 A1.9 - L1 A1.8 - L1 A1.7 - L1 A1A - L1 102 108 110 112 114 116 B5 - L1 B5.1 - L1 104 106 A3.1 - L1 B3.1 - L1 B3 - L1 A3 - L1 120 122 124 118 2-HR FIREWALL OFFICE LR12 A6 - L1 OPEN OFFICE 100 LR07 BACK OFFICE LR10 OFFICE ISO RPS4 SLC1•S:011 SLC1•S:010 SLC1•S:009 LEVEL 1 SLC LR11 S S S SLC1•S:007 R&R UC UC UC S IDF 2 U102 ZN2•001 U101 MP TS ZN1•001 ZN1•001SVWF TS SLC2•M:001 DH MM SLC2•M:002, 003 DM UC SLC1•S:020 SLC1•S:021 SLC1•S:022 SLC1•S:023 STAIR 1 S S S S S MEETING ROOM SLC1•S:008 UC UC UC UC UC LR09 A6 - L1 STAIRST-01 1 DH 101 2-HR FIRE WALL ANN 6 S ELEVATOR 1 SLC1•S:024 EL-01 4 SLC1•S:030 VESTIBULE S LOBBY LEVEL 1 NORTH V01 C LR08 C5 - L1-5 C WATERFLOW ZONE ELEVATOR 2 109 (2) #16/4 FPLR (SBUS) EL-02 TO THE FACP ON P01 UC MP C4.2 - L1 E1A 115 D4.1 - L1 105 C4 - L1 UC DN 103 151 A4-L1 A4.1-L1 LOUNGE B DN 119 121 L108 SLC1•S:012 C4.1 - L1 S 150 UC 2-HR FIRE WALL S UC SLC1•S:025 #18/4 FPLR SLC TO THE FACP IN CONTINUOUS RACEWAY (SEE RISER WIRING DETAIL) DH UC DH A5.1 - L1 2-HR FIRE WALL 2-HR FIRE WALL 153 B2.2 - L1 152 S 2-HR FIRE WALL B2.1 - L1 SLC1•S:026 C3 - L1 133 136 SLC1•S:013 S ENTRY GATE S3A - L1 155 #18/4 FPLR SLC TO THE FACP IN CONTINUOUS RACEWAY (SEE RISER WIRING DETAIL) UC DN UC A2.1 - L1 A2 - L1 154 135 C1 - L1 138 B E1A SLC1•S:027 169 S B B11A each sheet of building information card D5 - L1-5 B2 - L1 SLC1•S:014 137 175 S 156 B10 - L1 TS MM 157 #18/4 FPLR SLC TO THE ZN1•001 SLC2•M:041 UC FACP IN CONTINUOUS RACEWAY Name and address of building shall be noted on (SEE RISER WIRING DETAIL) B9 - L1 STAIR 4 B C1A - L1 165 IDF 140 U103 UC STAIR 4 LEVEL 1 SOUTH S101 RPS3 RES STRG A2 - L1 ST-04 SLC1•S:029 S B4 - L1-5 WATERFLOW ZONE 158 2 177 ZN1•001 TS SV SC 3 MP MM ELEVATOR 3 SLC2•M:051 UTIL R S STAIR 5 EL-03 U104 SLC1•S:015 S STAIR 5 SLC1•S:028 MP ST-05 B1 - L1-5 SLC1•S:018 SLC1•S:017CORRIDOR SLC1•S:016 UTIL S S S 142 C103 U107 UC UC UC RPS5 SL SLC1•S:019 S S 2 IDF U105 D8 - L1 S1.3 - L1 A DN 141 143 D1 D7 144 S1.1 - L1 S1 - L1 S1 - L1 S1 - L1 S1.2 - L1 160 172 170 168 166 164 LEVEL P2 BELOW A A1.3 - L1 B13 - L1-5 162 174 D6 - L1 SHARED FIRE APPARATUS ACCESS 176 AND DRIVEWAY Sample Note: The building information card shall include a symbol key; geographic zones Building for fire alarm and sprinkler waterflow; the location of firewalls, standpipes, and N sprinkler valves; and special systems (type I hood suppression systems, pre-action Information systems, clean agent systems, etc.).
Recommended publications
  • How to Live with Your Fire Alarm System
    How to Live with Your Fire Alarm System: Smoke detectors are sensitive to a number of items in addition to smoke from fire, including dusts and mists. To prevent nuisance fire alarms: 1. Do not smoke in your residence hall. 2. Do not spray aerosol products (air fresheners, hair spray, spray paint, perfume, mists, insect spray) or use candles, incense, powder, etc.) near smoke detectors or in large amounts. Consider using solid, non-aerosol air fresheners and keep spray paint and dusty projects outdoors in a well ventilated area. 3. Do not spray liquids on or near smoke detectors (cleaning products, water, steam) 4. Do not leave your microwave unattended. Burned food can smoke and does set off smoke detectors. Follow reheating directions and food preparation recommended cooking times, especially popcorn, and stay close by. 5. Do not use prohibited items such as candles, toaster ovens, George Forman Grills, or space heaters in your room. These items can cause nuisance fire alarms or worse - start a fire. Nuisance fire alarms and unnecessary fire department runs are dangerous, expensive, and disruptive for the fire department and create safety hazards for everyone. Your life and the lives of others may depend on your smoke detector. Do not disable or cover it. For more about cooking fires and fire prevention tips, visit NFPA.org @ http://www.nfpa.org/index.asp Fire Prevention Week commemorates the Great Chicago Fire of 1871, the tragic conflagration that killed more than 250 people, left 100,000 homeless, and destroyed more than 17,400 structures. Fire Prevention Week Web site www.firepreventionweek.org .
    [Show full text]
  • Smoke Alarms in US Home Fires Marty Ahrens February 2021
    Smoke Alarms in US Home Fires Marty Ahrens February 2021 Copyright © 2021 National Fire Protection Association® (NFPA®) Key Findings Smoke alarms were present in three-quarters (74 percent) of the injuries from fires in homes with smoke alarms occurred in properties reported homei fires in 2014–2018. Almost three out of five home with battery-powered alarms. When present, hardwired smoke alarms fire deathsii were caused by fires in properties with no smoke alarms operated in 94 percent of the fires considered large enough to trigger a (41 percent) or smoke alarms that failed to operate (16 percent). smoke alarm. Battery-powered alarms operated 82 percent of the time. Missing or non-functional power sources, including missing or The death rate per 1,000 home structure fires is 55 percent lower in disconnected batteries, dead batteries, and disconnected hardwired homes with working smoke alarms than in homes with no alarms or alarms or other AC power issues, were the most common factors alarms that fail to operate. when smoke alarms failed to operate. Of the fire fatalities that occurred in homes with working smoke Compared to reported home fires with no smoke alarms or automatic alarms, 22 percent of those killed were alerted by the device but extinguishing systems (AES) present, the death rate per 1,000 reported failed to respond, while 11 percent were not alerted by the operating fires was as follows: alarm. • 35 percent lower when battery-powered smoke alarms were People who were fatally injured in home fires with working smoke present, but AES was not, alarms were more likely to have been in the area of origin and • 51 percent lower when smoke alarms with any power source involved in the ignition, to have a disability, to be at least 65 years were present but AES was not, old, to have acted irrationally, or to have tried to fight the fire themselves.
    [Show full text]
  • Fire Service Features of Buildings and Fire Protection Systems
    Fire Service Features of Buildings and Fire Protection Systems OSHA 3256-09R 2015 Occupational Safety and Health Act of 1970 “To assure safe and healthful working conditions for working men and women; by authorizing enforcement of the standards developed under the Act; by assisting and encouraging the States in their efforts to assure safe and healthful working conditions; by providing for research, information, education, and training in the field of occupational safety and health.” This publication provides a general overview of a particular standards- related topic. This publication does not alter or determine compliance responsibilities which are set forth in OSHA standards and the Occupational Safety and Health Act. Moreover, because interpretations and enforcement policy may change over time, for additional guidance on OSHA compliance requirements the reader should consult current administrative interpretations and decisions by the Occupational Safety and Health Review Commission and the courts. Material contained in this publication is in the public domain and may be reproduced, fully or partially, without permission. Source credit is requested but not required. This information will be made available to sensory-impaired individuals upon request. Voice phone: (202) 693-1999; teletypewriter (TTY) number: 1-877-889-5627. This guidance document is not a standard or regulation, and it creates no new legal obligations. It contains recommendations as well as descriptions of mandatory safety and health standards. The recommendations are advisory in nature, informational in content, and are intended to assist employers in providing a safe and healthful workplace. The Occupational Safety and Health Act requires employers to comply with safety and health standards and regulations promulgated by OSHA or by a state with an OSHA-approved state plan.
    [Show full text]
  • Rules and Regulations for Fire Alarm and Fire Sprinkler Systems
    NORTH ATTLEBOROUGH FIRE DEPARTMENT 50 Elm Street, North Attleborough, Massachusetts 02760 Tel (508) 699-0140 • Fax (508) 643-0296 Issued: January 2020 Revised 02/10/2020 Rules and Regulations for Fire Alarm and Fire Sprinkler Systems The following rules and regulations shall govern the installation, use, and maintenance of all required fire alarm and fire sprinkler systems in the Town of North Attleborough. The rules and regulations are effective January 1, 2020 until otherwise revised or amended. They are intended to cover the most common variables encountered by architects, engineers, fire alarm and fire suppression professionals. These rules and regulations are subject to change and at no time should be considered complete towards all projects and scopes of work. Consult the fire prevention office after reading this document where additional clarification is required. Contents Section 1: General Requirements: ................................................................................................................... 2 Section 2: Engineer/Contractor Submittal and Plan Review ......................................................................... 3 Section 3: Interior System Design and Layout ............................................................................................... 6 Section 4: Sprinkler and Standpipe Systems ................................................................................................ 11 Section 5: Direct Connections to the North Attleborough Fire Department ..............................................
    [Show full text]
  • Fire Department Annual Report 2010
    Borough of Chatham Annual Report 2010 Fire Department February 13, 2011 Mayor V. Nelson Vaughan, III Chatham Borough Council Members Dear Mayor and Council, The following is a report of activities of the Chatham Borough Fire Department for the calendar year 2010. During the year, the fire department responded to a total of three hundred and fourteen (314) incidents, which was an increase of eighty-seven (87) over last year. Fortunately in 2010, there were no significant fires which caused reportable fire loss. During the year however, there were twenty-nine (29) reported fires. This included four (4) building fires, nine (9) cooking related fires, three (3) furnace or boiler fires, four (4) chimney fires, five (5) brush or trash fires, and four (4) passenger vehicle fires. Actual loss was reported for only three (3) months during the year totaling only $8300. This was a very significant decrease of $155,900 over last year in which a loss of $164,200 was posted. The members of the Chatham Fire Department contributed a total of eight thousand seven hundred fifty-three (8753) man-hours of service to the community in 2010. Incident responses accounted for one thousand seven hundred eighteen and three quarters (1718 ¾) man-hours while the remaining seven thousand thirty-four and one quarter (7034 ¼) man-hours were logged for training, work details, and fire duties to facilitate the many programs sponsored by the department throughout the year. This year was a very active year, with an increase of one thousand four hundred and six and three quarters (1406 ¾) man hours compared to the total logged for 2009.
    [Show full text]
  • Fire Alarm and Communication Systems Ioflil Burin of Stndirti
    NBS TECHNICAL NOTE 964 U.S. DEPARTMENT OF COMMERCE / National Bureau of Standards Fire Alarm and Communication Systems ioflil Burin of Stndirti MAY 1 1 1978 Fire Alarm and Communication Systems ^U' ^/ lOc 1w^ Richard W. Bukowski Richard L. P. Custer Richard G. Bright Center for Fire Research National Engineering Laboratory National Bureau of Standards Washington, D.C. 20234 ..< °' ^o, \ U.S. DEPARTMENT OF COMMERCE, Juanita M. Kreps, Secretary Dr. Sidney Harman, Under Secretary Jordan J. Baruch, Assistant Secretary for Science and Technology NATIONAL BUREAU OF STANDARDS, Ernest Annbler, Director Issued April 1978 National Bureau of Standards Technical Note 964 Nat. Bur. Stand. (U.S.), Tech. Note 964, 49 pages (Apr. 1978) CODEN: NBTNAE U.S. GOVERNMENT PRINTING OFFICE WASHINGTON: 1978 For sale by the Superintendent of Documents, U.S. Government Printing OflBce, Washington, D.C. 20434 Price $2.20 Stock No. 003-003-01914-3 (Add 25 percent additional for other than U.S. mailing). 2 CONTENTS Page LIST OF FIGURES v 1. INTRODUCTION 1 2. CONTROL UNITS 2 2.1 Common Features 2 2.2 Local Control Units 3 2.3 Auxiliary Control Units 3 2.4 Remote Station Control Unit 4 2.5 Proprietary Control Units 4 2.6 Central Station Control Units 5 3. INITIATING DEVICES 6 3.1 General 6 3 . Manual 6 3.3 Automatic 7 4. CLASSIFICATION OF DETECTORS 7 4.1 Geometric Classification 7 4.2 Restoration Classification 7 4.3 Alarm Contact Circuit Classification 7 5. HEAT DETECTION 8 5.1 Fixed-Temperature Detectors 8 5.1.1 Eutectic Metal Type 9 5.1.2 Glass Bulb Type 9 5.1.3 Continuous Line Type 9 5.1.4 Bimetal Type 10 5.1.4.1 Bimetal Strip 10 5.1.4.2 Snap Disc 10 5.2 Rate-of-Rise Detectors 11 5.3 Combination Detectors 12 5.4 Thermoelectric Detectors 12 6.
    [Show full text]
  • DS Series Addressable Detector Application Guide K-76-1000
    w w DS Series Addressable Detector Application Guide K-76-1000 K-73-200 Rev AB July 2015 FOREWORD July 2016 -1- K-76-1000 PURPOSE OF THIS GUIDE This guide, K-76-1000, is to be used by qualified and factory-trained personnel, knowledgeable of NFPA standards and any other applicable standards in effect. This guide is intended to provide guidance to qualified technical professionals for the installation and maintenance of the DS Series Addressable Detectors. Any questions concerning the information presented in this guide should be addressed to: Kidde-Fenwal, Inc. 400 Main Street Ashland, MA 01721, USA Phone: (508) 881-2000 Toll Free: (800) 872-6527 Technical Support: (866) 287-2531 Fax: (508) 881-8920 www.kiddefiresystems.com LIMITATION OF LIABILITY Only qualified persons experienced and trained in the installation of this type of equipment should install and configure DS Series Addressable Detectors. Installation in accordance with this guide, applicable codes, and the instructions of the Authority Having Jurisdiction is mandatory. The technical data contained herein is provided for informational purposes only, and should not be used as a substitute for professional judgment. The content of this manual is proprietary in nature and is intended solely for distribution to authorized persons, companies, distributors or others for the sole purpose of conducting business associated with Kidde-Fenwal, Inc. Although, Kidde-Fenwal, Inc. believes this information to be true and correct, it is published and presented without any guarantee or warranty whatsoever. Kidde-Fenwal, Inc. disclaims any liability for any use of the data other than as set out in this manual, foreword included.
    [Show full text]
  • Emergency Management: Smoke Detectors & Fire Extinguishers
    s SMOKE DETECTORS es dn re and pa re P 7 FIRE EXTINGUISHERS Taking it one step Ever Vigilant Sentries That May at a time. SAVE YOUR LIFE Half of the home fires and three-fifths of fire deaths occur in homes without smoke detectors. Hundreds of people die each year in homes with smoke detectors that don’t work. It’s important that you not only have a smoke detector, but that you check and maintain it frequently. You Need To Know What Kind Important Information Of Smoke Detector You Have & About Smoke Detectors How To Maintain It •Battery-Powered Make Placement a Priority Battery-powered smoke detectors operate on •At a minimum, there should be a smoke alkaline batteries. Unlike the bunny, they won’t detector in the hallways and corridors keep going forever. The battery should be checked between the sleeping areas and the rest of weekly and replaced twice a year. A good time to the house, and/or a smoke detector in the do this is when you change your clock in the fall and center of the ceiling directly above each spring. stairway. •Hard-Wired without Battery Back-up • Additional measures include installing smoke This type of smoke detector operates on household detectors on a wall or the ceiling in each current. As long as you have electricity, it will sleeping room. function; but if your house loses power, it will no • Because smoke rises, smoke detectors longer function. If you have this type, you should should be mounted high on the wall or also install battery-operated models for back-up.
    [Show full text]
  • NFPA 72 Fire Alarm System
    Fire Alarm System Plan Review Checklist 2010 OFC and 2007 NFPA 72 This checklist is for jurisdictions that permit the use of the 2007 NFPA 72 in lieu of IFC’s referenced 2002 NFPA 72. Date of Review: ______________________________ Permit Number: _____________________________ Business/Building Name: _______________________ Address of Project: __________________________ Designer Name: ______________________________ Designer’s Phone: ___________________________ Contractor: ________________________________ __Contractor’s Phone: __________________________ FA Manufacturer: ___________________ FA Model: ____________ Occupancy Classification: _________ Reference numbers following checklist statements represent an NFPA code section unless otherwise specified. Checklist Le gend: v or OK = acceptable N = need to provide NA = not applicable 1. ____ Three sets of drawings are provided. 2. ____ Equipment is listed for intended use and compatible with the system, specification data sheets are required, 4.3.1, 4.4.2. Drawings sh all detail t he follo wing items, OFC 907.1.2 and NFPA 72 4.5.1.1: 3. ____ Scale: a common scale is used and plan information is legible. 4. ____ Rooms are labeled and room dimensions are provided. 5. ____ Equipment symbol legend is provided. 6. ____ Class A or B system is declared, alarms zones do not exceed 22,500 sq. ft. (unless sprinklered then limit is set by NFPA 13, and each floor is a separate zone, OFC 907.7.3. 7. ____ When detectors are used, device locations, mounting heights, and building cross sectional details are shown on the plans. 8. ____ The type of devices used. 9. ____ Wiring for alarm initiating and alarm signaling indicating devices are detailed. 10.
    [Show full text]
  • Life Safety Dampers Selection and Application Manual • Ceiling Radiation Dampers • Fire Dampers • Combination Fire Smoke Dampers • Smoke Dampers
    Life Safety Dampers Selection and Application Manual • Ceiling Radiation Dampers • Fire Dampers • Combination Fire Smoke Dampers • Smoke Dampers August 2016 1 Table of Contents HOW TO USE THIS MANUAL DAMPER APPLICATION 3 • Fire Damper Application • Smoke Damper Application • Combination Fire Smoke Damper Application • Corridor Ceiling Combination Fire Smoke Damper Application DAMPER SELECTION 5 • Selection Process • Key Points to Remember ACTUATOR SELECTION 7 • Selection Process • Actuator Mounting Options • Key Points to Remember SLEEVE REQUIREMENTS 9 • Sleeve Thickness • Sleeve Length • Key Points to Remember SPACE REQUIREMENTS FOR PROPER INSTALLATION 10 • Key Points to Remember DAMPER OPTIONS 11 • Control Options • Security Bar Options • Transition Options • Key Points to Remember INSTALLATION REQUIREMENTS 15 • Combination Fire Smoke Damper Installation • Smoke Damper Installation • Actuator Installation • Damper and Actuator Maintenance • Key Points to Remember SPECIAL INSTALLATION CASES 17 • Maximum Damper Size Limitations • Horizontal Fire Smoke Damper in a Non-Concrete Barrier • AMCA Mullion System • What if a Damper Cannot be Installed per the Manufacturer’s Installation Instructions? • What if a Damper Cannot be Installed in the Wall? • Steps to Take When an Unapproved Installation Must be Provided CEILING RADIATION DAMPERS 20 • Ceiling Radiation Damper Application • Key Points to Remember CODES AND STANDARDS 21 • Compliance with the Applicable Building Codes • The National Fire Protection Association • Code and Standard Making
    [Show full text]
  • Fire Service Guide to Reducing Unwanted Fire Alarms
    Copyright 2012 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on September 11, 2012 to CLACKAMAS FIRE for designated user Clackamas Fire. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected]. Fire Service Guide to Reducing Unwanted Fire Alarms R {B7E6D5AF-0C04-40A9-AAE0-C5CA227E42F0} Copyright 2012 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on September 11, 2012 to CLACKAMAS FIRE for designated user Clackamas Fire. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected]. Fire Service Guide to Reducing Unwanted Fire Alarms Fire Service Guide to Reducing Unwanted Fire Alarms www.nfpacatalog.org/redgd 1 {B7E6D5AF-0C04-40A9-AAE0-C5CA227E42F0} 8444-FM.pdf 1 7/27/12 1:13 PM Copyright 2012 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on September 11, 2012 to CLACKAMAS FIRE for designated user Clackamas Fire. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected]. Copyright © 2012 National Fire Protection Association® All or portions of this work may be reproduced, displayed or distributed for personal or non-commercial purposes. Commercial reproduction, display or distribution may only be with permission of the National Fire Protection Association. About NFPA®: NFPA has been a worldwide leader in providing fire, electrical, building, and life safety to the public since 1896.
    [Show full text]
  • Requirements for Certificate of Smoke Detector, Carbon Monoxide and Fire Extinguisher Compliance
    REQUIREMENTS FOR CERTIFICATE OF SMOKE DETECTOR, CARBON MONOXIDE AND FIRE EXTINGUISHER COMPLIANCE Per New Jersey Statutes, the seller is responsible for this test unless otherwise provided. This certificate is required and applies to any structure used or intended for use for residential purposes by not more than two households, or the structure is rented, sold or otherwise made subject to a change of occupancy BEFORE such change takes place. REQUIREMENTS A smoke detector is required on every level of the home. On the levels where there are bedrooms, in addition to a smoke detector, you are required to have a carbon monoxide detector**. Battery powered or electric dual units- (both smoke and carbon monoxide in one housing) 10 year sealed units are required. If you have a basement or crawl space over four (4) feet high, or an attic which has a permanent staircase (not a pull down type) it is considered a level and must have a smoke detector. Portable fire extinguisher: One (1) 2A10BC portable fire extinguisher; 5 pounds to 10 pounds, rated minimum: 2-A:10-B:C is required. It is important to note the extinguisher MUST carry the ABC rating, not just B-C. MOUNTING Smoke detectors and carbon monoxide alarm(s) are required to be mounted outside the bedroom(s), within ten (10) feet of the bedroom door. Battery powered detectors are acceptable. Smoke detectors*: shall be mounted (screwed) to the ceiling or wall. If you choose to mount the smoke detector on the wall, follow the manufacturer’s instructions. In no case shall the top edge of the detector be less than four (4) nor more than twelve (12) inches from the ceiling.
    [Show full text]