NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Asset: SOUTH SHORE HS - K, 6565 FLATLANDS AVENUE, New York, 11236 Inspection Id Inspection Type Time In Last Edited SA : K515 Architectural - Senior 2020-01-14 7:28 AM 2020-01-24 12:16 PM AA : K515 Architectural - Associate 2020-01-14 8:31 AM 2020-01-16 4:47 PM Asset Data Question Answer Was the building fully accessible for inspection No Inspection Access Comment 1st Floor - Boys + Girls Shower Rooms - Sealed Off, Completely. Principal(s) Information

Principal Name Louis Garcia Organization X - Brooklyn Did you meet with this Principal? No Did this Principal provide feedback? No

Principal Name Daniela Gafen Organization Uncommon Preparatory Charter High School - Brooklyn Did you meet with this Principal? No Did this Principal provide feedback? No

Principal Name Dr. Max Jean Paul Organization Brooklyn Bridge Academy and Young Adult Borough Center - Brooklyn Did you meet with this Principal? Yes Did this Principal provide feedback? Yes Summary of Principal's Feedback The Principal commented that the Heating System needs to be balanced.

Principal Name Michelle Robinson Organization Pathways of Graduation - Brooklyn Did you meet with this Principal? No Did this Principal provide feedback? No

Principal Name Eugene Mazzola Organization Academy for Conservation and the Environment - Brooklyn Did you meet with this Principal? Yes Did this Principal provide feedback? Yes Summary of Principal's Feedback The Principal commented that the Heating System needs to be balanced.

Principal Name Chaubentz Dieujuste Organization Victory Collegiate High School - Brooklyn Did you meet with this Principal? No Did this Principal provide feedback? No

Principal Name David Ward Organization Brooklyn Theatre Arts - Brooklyn Did you meet with this Principal? No Did this Principal provide feedback? No

Principal Name Dawn Harris Organization Y.A.B.C. - Brooklyn Did you meet with this Principal? No Did this Principal provide feedback? No Custodian Hugh Doherty Fireman Michael Florimonte Building Square Footage 407,000

PB/A&W Page 1 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Comments on the Area None Comments on the Stories (Floors) plus Basements 4+B+PH Comments on the Number of Classrooms 125 Comments on the Year Built 1970 Student Population 2115 Staff Population 303 Weather Fair Facade Photo

Flatlands Avenue - North View

Main Entrance Photo

Facade A - Flatlands Avenue

PB/A&W Page 2 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Roof Photo

Roof 1 - Northwest View Have any Systems/Major Building Components been upgraded? Yes Systems: Student Toilet Rooms HC upgrade Rooms 114, 121, 452, 458. Year: 2020 Systems: Windows replacement; Window Guards refurbishment; New Computer Room 282; Partial Roofing repairs. Year: 2019 Systems: Cafeteria upgrade; 1st Floor Student Toilet Rooms 154, 158 HC Conversion; Partial Roofing repairs. Year: 2018 Systems: Roofing and Flashing replacement at all Roofs except Roofs 2, 4, 5; Partial Exterior Walls repointing; Partial Coping replacement; Parapets repointing; New Roof Barrier. Year: 2012 Systems: 3rd and 4th Floor Shops converted into Classrooms. Year: 2011 Systems: Chimney repairs and reconstruction. Year: 2010 Systems: Science Labs upgrade; Sidewalk replacement. Year: 2008 Systems: Partial Roofing repairs; Partial Exterior Walls repointing. Year: 1998 Have there been any New Building Additions? No Tandem Schools? No Leased Space? No Priority Condition

Priority Priority Condition Component Location Person(s) Person(s) Title PhotoImage Condition Exist Category Description Affected Description Notified Last Year? No Potential Falling Leaning parking DOT Sidewalk Glenwood Road Michael Fireman Debris sign post on Florimonte public sidewalk is a Potential Safety Hazard

PB/A&W Page 3 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 No Protruding Broken coping SITE | Flatlands Michael Fireman Elements stone with RETAINING Avenue - Florimonte exposed rebar is WALLS Parking Lot a Potential Entrance Safety Hazard

No Protruding Broken mirror INTERIOR | Room 295 Michael Fireman Elements with sharp edges CLASSROOMS Florimonte is a Potential /CORRIDORS/ Safety Hazard ADMIN SPACES | Walls

Yes Tripping Hazard Broken and INTERIOR | Stairs D/2, 3, Michael Fireman loose stair treads STAIRS/RAMP E/1, 2, F/2, K/2 Florimonte are a Potential S: INTERIOR | Tripping Hazard Stairs and Landings

Yes Tripping Hazard Severely SITE | PAVING Parking lot at Michael Custodian heaving and | Student Glenwood Florimonte displaced pavers Non-Use | Road, are a Potential Pavers Glenwood Road Tripping Hazard Near Container

Structural Engineer Required

Structural Condition Component Location Person(s) Person(s) Title PhotoImage Condition Type Description Affected Description Notified

No condition recorded Accessibility

Accessibility Status Question Response Is the primary or secondary entrance on an accessible route? Yes Is the building a multi-story building? Yes Are all floors of the building accessible through compliant means? Yes Accessible classrooms exists on each floor? Yes Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes If the following spaces exist, are they ALL accessible? Art Room, Auditorium, Yes Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs

Physical Breakdown Structure Exists Required Complies Deficiency Audio Fire Induction Alarm System Strobe FUNCTIONAL ACCESSIBILITY Exterior Routes Exterior Entrances & Exits Yes Exterior H/C Lifts No No Exterior Ramps and Railings No No

Interior Routes Corridor and Lobby H/C Lifts No No Interior Corridor Doors and Hardware Yes Yes

PB/A&W Page 4 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515

Physical Breakdown Structure Exists Required Complies Deficiency Audio Fire Induction Alarm System Strobe Interior Routes Interior Corridors and Lobbies Yes Interior Elevators Yes Yes Interior Lobby Doors and Hardware Yes Interior Ramps Yes Yes

Rooms & Spaces Art Rooms Rooms 323, 365, 421 Yes Yes Auditorium 1st Floor Yes Yes Yes Yes Cafeteria 1st Floor - Students, 1st Floor - Staff Yes Yes Yes Yes Classrooms 1st-4th Floor Yes Yes Computer Rooms Rooms 210, 371, 467 Yes Yes Gymnasium 2nd Floor - Gymnasium A/B, 2nd Floor - Yes Yes Yes Yes Gymnasium C/D Library Room 101 Yes Yes Main Office Room 201 (Academy for Conservation Yes Yes and the Environment); Room 267 (Brooklyn Theatre Arts); Room 280J (Pathways of Graduation); Room 301 (Uncommon Preparatory Charter High School); Room 373 (Y.A.B.C.); Room 377 (Brooklyn Bridge Academy and Young Adult Borough Center); Room 468 (Brooklyn X); Room 477 (Victory Collegiate High School) Multi-purpose Room No Nurse's Room Room C150 Yes Yes Pool No Science Lab Rooms 326, 327, 330, 427, 430 Yes Yes Toilet Rooms (Boys) 1st-4th Floor Yes Yes Toilet Rooms (Girls) 1st-4th Floor Yes Yes Toilet Rooms (Staff) 1st-4th Floor Yes Yes

PB/A&W Page 5 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Building Template

Inspection Question Response Architectural EXTERIOR Inspected AREAWAY Does not Exist AWNINGS AND CANOPIES Inspected Condition 4 - Between Fair and Poor Deficiency CONCRETE: WATER PENETRATION Roof Plan reference

Deficiency Quantity 100 Quantity Uom S.F. Potential Action REPAIR Urgency of Action PRIORITY 5 Purpose of Action LEVEL 2 Deficiency Photo1

PB/A&W Page 6 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response EXTERIOR AWNINGS AND CANOPIES Facade E Violations No violations recorded.

Deficiency CONCRETE: DETERIORATED Roof Plan reference

Deficiency Quantity 50 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 Deficiency Photo1

Facade I Violations No violations recorded.

CHIMNEY Inspected Material Type(s) Masonry Condition 3 - Fair Deficiency BRICK: OPEN JOINTS Roof Plan reference

Deficiency Quantity 20 Quantity Uom S.F. Potential Action REPOINT Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2

PB/A&W Page 7 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response EXTERIOR CHIMNEY Deficiency Photo1

Roof 6 Violations No violations recorded.

Deficiency BRICK: MINOR CRACKS AND SPALLING Roof Plan reference

Deficiency Quantity 10 Quantity Uom S.F. Potential Action RESTITCH Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Roof 6 Violations No violations recorded.

COPING Inspected Condition 3 - Fair Deficiency CAST STONE: OPEN TRANSVERSE JOINTS WITH DAMAGED CAULKING

PB/A&W Page 8 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response EXTERIOR COPING Roof Plan reference

Deficiency Quantity 10 Quantity Uom L.F. Potential Action MAINTENANCE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1 No photo recorded Violations No violations recorded.

Deficiency CAST STONE: CRACKED/BROKEN PIECES Roof Plan reference

Deficiency Quantity 10 Quantity Uom L.F. Potential Action REPLACE-IN-KIND Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 Deficiency Photo1

Roof 1 Violations No violations recorded.

Deficiency METAL: DETERIORATED

PB/A&W Page 9 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response EXTERIOR COPING Roof Plan reference

Deficiency Quantity 30 Quantity Uom L.F. Potential Action REPLACE-IN-KIND Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 Deficiency Photo1

Roof 1 - Bulkhead 3 Violations No violations recorded.

CORNICE Does not Exist DOORS Inspected DOORS AND FRAMES Inspected Condition 3 - Fair Deficiency ROLL-UP DOOR: DETERIORATED DOOR AND FRAME - MAJOR DETERIORATION Roof Plan reference

Deficiency Quantity 1 Quantity Uom EACH Potential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2

PB/A&W Page 10 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response EXTERIOR DOORS DOORS AND FRAMES Deficiency Photo1

Facade I Violations No violations recorded.

Deficiency ROLL-UP DOOR: DETERIORATED DOOR AND FRAME - MINOR DETERIORATION Roof Plan reference

Deficiency Quantity 3 Quantity Uom EACH Potential Action MAINTENANCE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1 No photo recorded Violations No violations recorded.

DOOR HARDWARE Inspected Condition 3 - Fair Deficiency No deficiencies recorded LINTELS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded TRANSOM/SIDE LIGHT Inspected Condition 5 - Poor Deficiency METAL: DENTED, MAJOR RUSTING

PB/A&W Page 11 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response EXTERIOR DOORS TRANSOM/SIDE LIGHT Roof Plan reference

Deficiency Quantity 40 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 Deficiency Photo1

Facade I Violations No violations recorded.

Deficiency METAL: DENTED, MINOR RUSTING Roof Plan reference

Deficiency Quantity 10 Quantity Uom S.F. Potential Action MAINTENANCE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1 No photo recorded Violations No violations recorded.

EXTERIOR WALLS Inspected Material Type(s) Masonry Replacement Quantity 86,000

PB/A&W Page 12 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response EXTERIOR EXTERIOR WALLS Replacement Uom S.F. Instance on All Facades Inspected Instance Condition 2 - Between Good and Fair Instance Quantity 86,000 Instance Quantity Uom S.F. Deficiency BRICK: OPEN JOINTS Roof Plan reference

Elevation

Deficiency Quantity 50 Quantity Uom S.F. Potential Action REPOINT Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Facade K Violations No violations recorded.

Deficiency BRICK: MINOR CRACKS AND SPALLING

PB/A&W Page 13 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response EXTERIOR EXTERIOR WALLS Roof Plan reference

Elevation

Deficiency Quantity 10 Quantity Uom S.F. Potential Action RESTITCH Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Facade I Violations No violations recorded.

Deficiency BRICK: DETERIORATED MASONRY SILLS Roof Plan reference

PB/A&W Page 14 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response EXTERIOR EXTERIOR WALLS Elevation

Deficiency Quantity 10 Quantity Uom L.F. Potential Action REPAIR Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Facade C Violations No violations recorded.

EXTERIOR SOFFITS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded LOADING DOCK Inspected Condition 5 - Poor Deficiency CHEEK WALL/CRACKS, SPALLING - MAJOR Roof Plan reference

Deficiency Quantity 10 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2

PB/A&W Page 15 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response EXTERIOR LOADING DOCK Deficiency Photo1

Facade H Violations No violations recorded.

Deficiency DETERIORATED CONCRETE PLATFORM WITH CRACKED, SPALLED CONCRETE OR EXPOSED REINFORCING Roof Plan reference

Deficiency Quantity 10 Quantity Uom S.F. Potential Action REPAIR Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Facade C Violations No violations recorded.

Deficiency BAD BUMPERS

PB/A&W Page 16 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response EXTERIOR LOADING DOCK Roof Plan reference

Deficiency Quantity 9 Quantity Uom EACH Potential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 Deficiency Photo1

Facade C Violations No violations recorded.

LOUVER Inspected Condition 3 - Fair Deficiency BROKEN/ DENTED BLADES Roof Plan reference

Elevation

PB/A&W Page 17 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response EXTERIOR LOUVER Deficiency Quantity 20 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 Deficiency Photo1

Facade B Violations No violations recorded.

PARAPETS Inspected Material Type(s) Masonry Replacement Quantity 20,000 Replacement Uom C.F. Instance on All Facades Inspected Instance Condition 2 - Between Good and Fair Instance Quantity 20,000 Instance Quantity Uom C.F. Deficiency No deficiencies recorded PLAZA DECK Does not Exist ROOF Inspected Roofing Inspected Replacement Quantity 133,000 Replacement Uom S.F. ROOF HATCH/SMOKE HATCH Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected Condition 3 - Fair Deficiency DAMAGED/MISSING Roof Plan reference

Deficiency Quantity 10 Quantity Uom L.F.

PB/A&W Page 18 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response EXTERIOR ROOF Roofing LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Potential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 Deficiency Photo1

Roof 1 Violations No violations recorded.

ROOF BARRIER Inspected Condition 2 - Between Good and Fair Deficiency RAILINGS/PANELS: DETERIORATED, MINOR RUSTING Roof Plan reference

Deficiency Quantity 40 Quantity Uom S.F. Potential Action MAINTENANCE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1 No photo recorded Violations No violations recorded.

ROOF CAGE Does not Exist ROOF FENCE Does not Exist ROOFING Inspected Instance on Modified Bitumen: Roofs 1, 2, 3, 3A, 4 Inspected Instance Condition 3 - Fair Instance Quantity 93,000 Instance Quantity Uom S.F. Does the roof have major mechanical equipment sitting on No Dunnage Steel less than 18" above the Roofing? Installation Year 2012 Source of Installation Custodial Staff Deficiency MODIFIED BITUMEN: ROOFING: DELAMINATION

PB/A&W Page 19 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response EXTERIOR ROOF Roofing ROOFING Roof Plan reference

Deficiency Quantity 50 Quantity Uom S.F. Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENT REMOVAL Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 Deficiency Photo1

Roof 1 Violations No violations recorded.

Instance on Built-Up: Roofs 5, 6 Inspected Instance Condition 3 - Fair Instance Quantity 24,500 Instance Quantity Uom S.F. Does the roof have major mechanical equipment sitting on No Dunnage Steel less than 18" above the Roofing? Installation Year 1996 Source of Installation Custodial Staff Deficiency BUILT-UP: FLASHING: CAP FLASHING MISSING Roof Plan reference

Deficiency Quantity 10

PB/A&W Page 20 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response EXTERIOR ROOF Roofing ROOFING Quantity Uom L.F. Potential Action INSTALL NEW Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 Deficiency Photo1

Roof 2 Violations No violations recorded.

Deficiency BUILT-UP: ROOFING: BEYOND USEFUL LIFE Deficiency Location/Instance Built-Up: Roofs 5, 6 Deficiency Quantity 24,500 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 1 Purpose of Action LEVEL 2 Deficiency Photo1 No photo recorded Violations No violations recorded.

Instance on IRMA: Roof 7 Inspected Instance Condition 3 - Fair Instance Quantity 15,500 Instance Quantity Uom S.F. Does the roof have major mechanical equipment sitting on No Dunnage Steel less than 18" above the Roofing? Installation Year 1998 Source of Installation Custodial Staff Deficiency IRMA: ROOFING: DAMAGED INSULATION Roof Plan reference

Deficiency Quantity 40 Quantity Uom S.F. Potential Action REPLACE

PB/A&W Page 21 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response EXTERIOR ROOF Roofing ROOFING Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 Deficiency Photo1

Roof 5 Violations No violations recorded.

ROOFING DRAINS Inspected Condition 5 - Poor Deficiency DETERIORATED Roof Plan reference

Deficiency Quantity 2 Quantity Uom EACH Potential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 Deficiency Photo1

Roof 2 Violations No violations recorded.

Deficiency CLOGGED

PB/A&W Page 22 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response EXTERIOR ROOF Roofing ROOFING DRAINS Roof Plan reference

Deficiency Quantity 1 Quantity Uom EACH Potential Action MAINTENANCE Urgency of Action PRIORITY 5 Purpose of Action LEVEL 2 Deficiency Photo1

Roof 3a Violations No violations recorded.

Specialties Inspected BULKHEAD/PENTHOUSE Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded CUPOLA/ SPIRES/ TOWERS Does not Exist DORMER Does not Exist DUNNAGE STEEL Does not Exist SKYLIGHT/ROOF VENT Inspected Material Type(s) Glass Condition 3 - Fair Deficiency DAMAGED GUARDS

PB/A&W Page 23 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response EXTERIOR ROOF Specialties SKYLIGHT/ROOF VENT Roof Plan reference

Deficiency Quantity 25 Quantity Uom S.F. Potential Action MAINTENANCE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Roof 1 Violations No violations recorded.

ROOF/GRAVITY TANK Does not Exist STAIRS/RAMPS: EXTERIOR Inspected BUILDING CHEEK/FLANK WALLS Inspected Condition 3 - Fair Deficiency STONE: OPEN JOINTS Roof Plan reference

Deficiency Quantity 20 Quantity Uom S.F. Potential Action REPOINT Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2

PB/A&W Page 24 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response EXTERIOR STAIRS/RAMPS: EXTERIOR BUILDING CHEEK/FLANK WALLS Deficiency Photo1

Facade A Violations No violations recorded.

RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency RUST - MINOR Roof Plan reference

Deficiency Quantity 10 Quantity Uom L.F. Potential Action MAINTENANCE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1 No photo recorded Violations No violations recorded.

STAIRS/RAMPS Inspected Condition 3 - Fair Deficiency CONCRETE: CRACKS/SPALLING - MINOR Roof Plan reference

Deficiency Quantity 15 Quantity Uom S.F. Potential Action REPAIR

PB/A&W Page 25 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response EXTERIOR STAIRS/RAMPS: EXTERIOR STAIRS/RAMPS Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Facade K Violations No violations recorded.

Deficiency STONE: OPEN JOINTS Roof Plan reference

Deficiency Quantity 10 Quantity Uom L.F. Potential Action REPOINT Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Facade A Violations No violations recorded.

Deficiency STONE: CRACKS, SPALLING

PB/A&W Page 26 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response EXTERIOR STAIRS/RAMPS: EXTERIOR STAIRS/RAMPS Roof Plan reference

Deficiency Quantity 10 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 Deficiency Photo1

Facade A Violations No violations recorded.

WINDOWS Inspected Replacement Quantity 30,000 Replacement Uom S.F. EXTERIOR GUARDS Inspected Condition 3 - Fair Deficiency RUST - MAJOR Roof Plan reference

PB/A&W Page 27 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response EXTERIOR WINDOWS EXTERIOR GUARDS Elevation

Deficiency Quantity 60 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 Deficiency Photo1

Facade E Violations No violations recorded.

Deficiency RUST - MINOR Roof Plan reference

Elevation

Deficiency Quantity 500 Quantity Uom S.F. PB/A&W Page 28 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response EXTERIOR WINDOWS EXTERIOR GUARDS Potential Action MAINTENANCE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1 No photo recorded Violations No violations recorded.

LINTELS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded WINDOWS Inspected Material Type(s) Aluminum Instance on Aluminum - Other: All Facades Inspected Instance Condition 1 - Good Instance Quantity 30,000 Instance Quantity Uom S.F. Installation Year 2019 Source of Installation Custodial Staff Deficiency No deficiencies recorded INTERIOR Inspected

POOLS Does not Exist STRUCTURAL Inspected COLUMNS/BEAMS/BEARING WALLS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded FLOOR STRUCTURE Inspected Condition 3 - Fair Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS Deficiency Location/Instance Basement - Electrical Panel Room Deficiency Quantity 50 Quantity Uom S.F. Potential Action REPAIR Urgency of Action PRIORITY 3 Purpose of Action LEVEL 5 Deficiency Photo1

Basement - Electrical Panel Room Violations No violations recorded.

Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED Deficiency Location/Instance Roof 1 - Penthouse 1, 1st Floor - Loading Areas Deficiency Quantity 150

PB/A&W Page 29 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR STRUCTURAL FLOOR STRUCTURE Quantity Uom S.F. Potential Action REPAIR Urgency of Action PRIORITY 3 Purpose of Action LEVEL 5 Deficiency Photo1

Roof 1 - Penthouse 1 Violations No violations recorded.

FOUNDATION WALLS Inspected Material Type(s) Concrete Condition 2 - Between Good and Fair Deficiency No deficiencies recorded ROOF STRUCTURE Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded VAULTS-BUNKERS Does not Exist AUDITORIUM Inspected Instance on 1st Floor (994 Seats) Inspected Ceiling Instance on 1st Floor (994 Seats) Inspected Condition 2 - Between Good and Fair Deficiency ACOUSTIC TILES ON PLASTER: DAMAGED/MISSING Deficiency Location/Instance 2nd Floor - Right side Deficiency Quantity 20 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

2nd Floor - Right side Violations No violations recorded.

Door(s)

PB/A&W Page 30 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR AUDITORIUM Door(s) Instance on 1st Floor (994 Seats) Inspected Condition 4 - Between Fair and Poor Deficiency WOOD: DETERIORATED DOOR Deficiency Location/Instance 2nd Floor Entrance on both sides Deficiency Quantity 2 Quantity Uom EACH Potential Action MAINTENANCE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

2nd Floor Entrance Violations No violations recorded.

Fixed H/C Lift Instance on 1st Floor (994 Seats) Does not Exist Fixed Seating Instance on 1st Floor (994 Seats) Inspected Condition 3 - Fair Deficiency DAMAGED/BROKEN/INOPERABLE Deficiency Location/Instance Seats A/2, 3, 9, 108, 102, 104, 2nd Floor - Seats A/104, L/5, and others Deficiency Quantity 62 Quantity Uom EACH Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Seat A/108 Violations No violations recorded.

Floor Finish Instance on 1st Floor (994 Seats) Inspected Condition 2 - Between Good and Fair Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

PB/A&W Page 31 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR AUDITORIUM Floor Finish Deficiency Location/Instance Near the Stage, left and right aisles Deficiency Quantity 30 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Near the Stage Violations No violations recorded.

Sliding-folding Partition Instance on 1st Floor (994 Seats) Inspected Condition 5 - Poor Deficiency MOTOR: INOPERABLE Deficiency Location/Instance Center on both sides Deficiency Quantity 1 Quantity Uom EACH Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1 No photo recorded Violations No violations recorded.

Stage Instance on 1st Floor (994 Seats) Inspected Stage Inspected Instance on 1st Floor (994 Seats) Inspected Condition 3 - Fair Deficiency DAMAGED FLOOR Deficiency Location/Instance Rear Center Deficiency Quantity 15 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2

PB/A&W Page 32 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR AUDITORIUM Stage Stage Deficiency Photo1

Rear Center Violations No violations recorded.

Deficiency DAMAGED STEPS Deficiency Location/Instance Left side of Stage, Right side of Stage Deficiency Quantity 15 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Left side of Stage Violations No violations recorded.

Stage Curtain Rigging Inspected Instance on 1st Floor (994 Seats) Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded Stage Curtains Inspected Instance on 1st Floor (994 Seats) Inspected Condition 3 - Fair Deficiency WORN/DETERIORATED Deficiency Location/Instance Left side of Stage - Center Deficiency Quantity 100 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2

PB/A&W Page 33 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR AUDITORIUM Stage Stage Curtains Deficiency Photo1

Left side of Stage - Center Violations No violations recorded.

Walls Instance on 1st Floor (994 Seats) Inspected Condition 2 - Between Good and Fair Deficiency WOOD PANELING: DETERIORATED Deficiency Location/Instance Left side of Stage, Right side of Stage Deficiency Quantity 40 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Right side of stage Violations No violations recorded.

Window Curtains/Shades/Blinds Instance on 1st Floor (994 Seats) Does not Exist CAFETERIA Inspected Instance on 1st Floor - Students Inspected Instance on 1st Floor - Staff (600SF) Inspected Ceiling Instance on 1st Floor - Students Inspected Condition 2 - Between Good and Fair Deficiency GYPSUM BOARD: DAMAGED/DETERIORATED Deficiency Location/Instance Near Kitchen Deficiency Quantity 15 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 PB/A&W Page 34 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR CAFETERIA Ceiling Purpose of Action LEVEL 2 Deficiency Photo1

Near Kitchen Violations No violations recorded.

Instance on 1st Floor - Staff (600SF) Inspected Condition 3 - Fair Deficiency ACOUSTIC TILES ON PLASTER: DAMAGED/MISSING Deficiency Location/Instance Near Entrance Deficiency Quantity 25 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Near Entrance Violations No violations recorded.

Instance on 1st Floor - Students Inspected Condition 2 - Between Good and Fair Deficiency ACOUSTIC TILES: DAMAGED/MISSING Deficiency Location/Instance Near Serving Area - East side Deficiency Quantity 10 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2

PB/A&W Page 35 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR CAFETERIA Ceiling Deficiency Photo1

Near Serving Area - East side Violations No violations recorded.

Door(s) Instance on 1st Floor - Students Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded Instance on 1st Floor - Staff (600SF) Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded Fixed Equipment Instance on 1st Floor - Students Does not Exist Instance on 1st Floor - Staff (600SF) Does not Exist Floor Finish Instance on 1st Floor - Staff (600SF) Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded Instance on 1st Floor - Students Inspected Condition 1 - Good Deficiency No deficiencies recorded Sliding-folding Partition Instance on 1st Floor - Students Does not Exist Instance on 1st Floor - Staff (600SF) Does not Exist Stage Instance on 1st Floor - Students Does not Exist Instance on 1st Floor - Staff (600SF) Does not Exist Walls Instance on 1st Floor - Staff (600SF) Inspected Condition 3 - Fair Deficiency PLASTER: CRACKS/SPALLING Deficiency Location/Instance Rear Deficiency Quantity 40 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2

PB/A&W Page 36 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR CAFETERIA Walls Deficiency Photo1

Rear Violations No violations recorded.

Window Curtains/Shades/Blinds Instance on 1st Floor - Staff (600SF) Does not Exist Instance on 1st Floor - Students Does not Exist CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected Ceiling Inspected Condition 2 - Between Good and Fair Deficiency GYPSUM BOARD: DAMAGED/DETERIORATED Deficiency Location/Instance Corridor near Room 280J Deficiency Quantity 20 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Corridor near Room 280J Violations No violations recorded.

Deficiency ACOUSTIC TILES ON PLASTER: DAMAGED/MISSING Deficiency Location/Instance Courtyard Vestibule, Corridor near Rooms 420, 432, 468, Corridor near Stair B/4, and others Deficiency Quantity 400 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2

PB/A&W Page 37 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Ceiling Deficiency Photo1

Corridor near Room 468 Violations No violations recorded.

Deficiency PLASTER: CRACKS/SPALLING Deficiency Location/Instance Exit Vestibule 8, Rooms 182, C107, 202, 241, 423, 426, and others Deficiency Quantity 250 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Room 182 Violations No violations recorded.

Door(s) Inspected Condition 3 - Fair Deficiency METAL: DETERIORATED DOOR Deficiency Location/Instance Corridor near Rooms 227, 283 Deficiency Quantity 4 Quantity Uom EACH Potential Action MAINTENANCE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

PB/A&W Page 38 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Door(s) Corridor near Room 227 Violations No violations recorded.

Deficiency WOOD: DETERIORATED DOOR Deficiency Location/Instance Suite 280 Entrance, Rooms 370, 462, 464 Deficiency Quantity 4 Quantity Uom EACH Potential Action MAINTENANCE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Room 464 Violations No violations recorded.

Floor Finish Inspected Condition 2 - Between Good and Fair Deficiency VINYL TILES: DETERIORATED SUBSTRATE Deficiency Location/Instance Rooms 267A, 267C, 267D Deficiency Quantity 400 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Room 267A Violations No violations recorded.

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES Deficiency Location/Instance Main Entrance Lobby, Rooms 241, 247, Corridor near Rooms C102, 181, 339, and others Deficiency Quantity 1,250 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3

PB/A&W Page 39 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Floor Finish Purpose of Action LEVEL 2 Deficiency Photo1

Main Entrance Lobby Violations No violations recorded.

Deficiency TERRAZZO: CRACKS Deficiency Location/Instance Exit Vestibules 8, 9, Main Entrance Lobby Deficiency Quantity 115 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Exit Vestibule 9 Violations No violations recorded.

Walls Inspected Condition 2 - Between Good and Fair Deficiency MIRRORS: BROKEN/DAMAGED Deficiency Location/Instance Room 295 Deficiency Quantity 25 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6

PB/A&W Page 40 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Walls Deficiency Photo1

Room 295 Violations No violations recorded.

Deficiency GLAZED BLOCK: CRACKS/SPALLING Deficiency Location/Instance Corridor near Rooms 181, 308, 333 408, 426, and others Deficiency Quantity 180 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Corridor near Room 408 Violations No violations recorded.

Deficiency PLASTER: CRACKS/SPALLING Deficiency Location/Instance Room 371 Deficiency Quantity 20 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Room 371 Violations No violations recorded.

PB/A&W Page 41 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Specialties Inspected Classroom Locker(s) Inspected Condition 2 - Between Good and Fair Deficiency DAMAGED UNITS Deficiency Location/Instance Total: 1,600 Lockers - Corridor near Room 289, 295, inside Suite C100 Deficiency Quantity 5 Quantity Uom EACH Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Corridor near Room 289 Violations No violations recorded.

Fixed Seating Does not Exist GYMNASIUM Inspected Instance on 2nd Floor - Gymnasium C/D Inspected Instance on 2nd Floor - Gymnasium A/B Inspected Ceiling Instance on 2nd Floor - Gymnasium A/B Inspected Condition 2 - Between Good and Fair Deficiency PLASTER: CRACKS/SPALLING Deficiency Location/Instance Storage Room Deficiency Quantity 60 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Storage Room Violations No violations recorded.

Instance on 2nd Floor - Gymnasium C/D Inspected

PB/A&W Page 42 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR GYMNASIUM Ceiling Condition 2 - Between Good and Fair Deficiency PLASTER: CRACKS/SPALLING Deficiency Location/Instance Small Storage Room Deficiency Quantity 20 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Small Storage Room Violations No violations recorded.

Door(s) Instance on 2nd Floor - Gymnasium A/B Inspected Condition 5 - Poor Deficiency WOOD: DETERIORATED DOOR Deficiency Location/Instance Entrance, Storage Room Deficiency Quantity 4 Quantity Uom EACH Potential Action MAINTENANCE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Storage Room Violations No violations recorded.

Instance on 2nd Floor - Gymnasium C/D Inspected Condition 4 - Between Fair and Poor Deficiency WOOD: DETERIORATED DOOR Deficiency Location/Instance Small Storage Room Deficiency Quantity 2 Quantity Uom EACH Potential Action MAINTENANCE

PB/A&W Page 43 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR GYMNASIUM Door(s) Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Small Storage Room Violations No violations recorded.

Fixed Equipment Instance on 2nd Floor - Gymnasium C/D Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded Instance on 2nd Floor - Gymnasium A/B Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded Floor Finish Instance on 2nd Floor - Gymnasium A/B Inspected Condition 3 - Fair Deficiency CONCRETE: CRACKS Deficiency Location/Instance Storage Room Deficiency Quantity 25 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Storage Room Violations No violations recorded.

Deficiency WOOD: DAMAGED/DETERIORATED Deficiency Location/Instance Near Drinking Fountain, Center Deficiency Quantity 200 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3

PB/A&W Page 44 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR GYMNASIUM Floor Finish Purpose of Action LEVEL 2 Deficiency Photo1

Near Drinking Fountain Violations No violations recorded.

Instance on 2nd Floor - Gymnasium C/D Inspected Condition 2 - Between Good and Fair Deficiency CONCRETE: CRACKS Deficiency Location/Instance Large Storage Room Deficiency Quantity 25 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Large storage room Violations No violations recorded.

Seating Instance on 2nd Floor - Gymnasium C/D Inspected Condition 1 - Good Deficiency No deficiencies recorded Instance on 2nd Floor - Gymnasium A/B Does not Exist Sliding-folding Partition Instance on 2nd Floor - Gymnasium C/D Inspected Condition 2 - Between Good and Fair Deficiency MOVABLE PANELS: DAMAGED Deficiency Location/Instance Center Deficiency Quantity 20 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2

PB/A&W Page 45 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR GYMNASIUM Sliding-folding Partition Deficiency Photo1 No photo recorded Violations No violations recorded.

Instance on 2nd Floor - Gymnasium A/B Inspected Condition 4 - Between Fair and Poor Deficiency MOVABLE PANELS: DAMAGED Deficiency Location/Instance Center, left and right sides Deficiency Quantity 280 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Left side Violations No violations recorded.

Stage Instance on 2nd Floor - Gymnasium C/D Does not Exist Instance on 2nd Floor - Gymnasium A/B Does not Exist Walls Instance on 2nd Floor - Gymnasium A/B Inspected Condition 2 - Between Good and Fair Deficiency MASONRY: CRACKS/SPALLING Deficiency Location/Instance Storage Room Deficiency Quantity 50 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Storage Room Violations No violations recorded.

PB/A&W Page 46 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR GYMNASIUM Walls Instance on 2nd Floor - Gymnasium C/D Inspected Condition 2 - Between Good and Fair Deficiency MASONRY: CRACKS/SPALLING Deficiency Location/Instance Large Storage Room Deficiency Quantity 20 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Large storage room Violations No violations recorded.

Window Curtains/Shades/Blinds Instance on 2nd Floor - Gymnasium C/D Does not Exist Instance on 2nd Floor - Gymnasium A/B Does not Exist INTERIOR DOOR HARDWARE Inspected Condition 3 - Fair Deficiency No deficiencies recorded INTERIOR GUARDS Inspected Condition 2 - Between Good and Fair Deficiency DETERIORATED/TORN-OUT/MISSING Deficiency Location/Instance Stair B/4 Deficiency Quantity 20 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Stair B/4 Violations No violations recorded.

KITCHEN Inspected

PB/A&W Page 47 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR KITCHEN Instance on 1st Floor (2,000SF) Inspected Ceiling Instance on 1st Floor (2,000SF) Inspected Condition 3 - Fair Deficiency METAL PAN: DAMAGED/MISSING Deficiency Location/Instance Near Entrance, Prep area, Serving area, Exit Vestibule Deficiency Quantity 80 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Near Storage Room Violations No violations recorded.

Door(s) Instance on 1st Floor (2,000SF) Inspected Condition 5 - Poor Deficiency METAL: MISSING DOOR Deficiency Location/Instance Staff Serving area Deficiency Quantity 1 Quantity Uom EACH Potential Action MAINTENANCE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Staff Serving area Violations No violations recorded.

Deficiency METAL: DETERIORATED DOOR AND FRAME Deficiency Location/Instance Can wash room Deficiency Quantity 1 Quantity Uom EACH Potential Action MAINTENANCE

PB/A&W Page 48 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR KITCHEN Door(s) Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Can wash Room Violations No violations recorded.

Deficiency WOOD: DETERIORATED DOOR Deficiency Location/Instance Men Locker Room Deficiency Quantity 1 Quantity Uom EACH Potential Action MAINTENANCE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Men Locker Room Violations No violations recorded.

Floor Finish Instance on 1st Floor (2,000SF) Inspected Condition 3 - Fair Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES Deficiency Location/Instance Women's Locker Room Deficiency Quantity 10 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2

PB/A&W Page 49 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR KITCHEN Floor Finish Deficiency Photo1

Women’s Locker Room Violations No violations recorded.

Deficiency QUARRY TILE: BROKEN/MISSING TILES Deficiency Location/Instance Near Storage Room Deficiency Quantity 20 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Near Storage Room Violations No violations recorded.

Deficiency CONCRETE: CRACKS Deficiency Location/Instance Storage Room 133 Deficiency Quantity 50 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Storage Room 133 Violations No violations recorded.

PB/A&W Page 50 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR KITCHEN Walls Instance on 1st Floor (2,000SF) Inspected Condition 2 - Between Good and Fair Deficiency CERAMIC TILE: BROKEN/ MISSING Deficiency Location/Instance Near Women's Locker Room, Prep area Deficiency Quantity 30 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Prep area Violations No violations recorded.

LIBRARY Inspected Instance on Room 101 Inspected Built-in Furnishing Instance on Room 101 Does not Exist Ceiling Instance on Room 101 Inspected Condition 1 - Good Deficiency No deficiencies recorded Door(s) Instance on Room 101 Inspected Condition 1 - Good Deficiency No deficiencies recorded Floor Finish Instance on Room 101 Inspected Condition 1 - Good Deficiency No deficiencies recorded Walls Instance on Room 101 Inspected Condition 1 - Good Deficiency No deficiencies recorded LOCKER ROOM Inspected Instance on 1st Floor - Boys (1,708 Lockers) Inspected Alternative use Yes Instance on 1st Floor - Girls (1,446 Lockers) Inspected Alternative use Yes Ceiling Instance on 1st Floor - Boys (1,708 Lockers) Inspected

PB/A&W Page 51 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR LOCKER ROOM Ceiling Condition 2 - Between Good and Fair Deficiency No deficiencies recorded Instance on 1st Floor - Girls (1,446 Lockers) Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded Door(s) Instance on 1st Floor - Boys (1,708 Lockers) Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded Instance on 1st Floor - Girls (1,446 Lockers) Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded Floor Finish Instance on 1st Floor - Boys (1,708 Lockers) Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded Instance on 1st Floor - Girls (1,446 Lockers) Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded Locker Room Lockers Instance on 1st Floor - Boys (1,708 Lockers) Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded Instance on 1st Floor - Girls (1,446 Lockers) Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded Walls Instance on 1st Floor - Boys (1,708 Lockers) Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded Instance on 1st Floor - Girls (1,446 Lockers) Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded MULTI-PURPOSE ROOM Does not Exist SCIENCE DEMO ROOM Inspected Instance on Rooms 332, 421, 423, 429, 432, 440, 441 Inspected Alternative use Yes Instance on Rooms 437, 439 Inspected Alternative use No Instance on Room 340 Inspected Alternative use Yes Fixed Equipment Instance on Room 340 Inspected Condition 2 - Between Good and Fair Deficiency CABINETRY: MISSING/DAMAGED Deficiency Location/Instance Room 340 Deficiency Quantity 2

PB/A&W Page 52 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR SCIENCE DEMO ROOM Fixed Equipment Quantity Uom L.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1 No photo recorded Violations No violations recorded.

SCIENCE LAB Inspected Instance on Rooms 326, 430 Inspected Alternative use Yes Instance on Room 427 Inspected Alternative use Yes Instance on Rooms 327, 330 Inspected Alternative use No Fixed Equipment Instance on Rooms 326, 430 Inspected Condition 3 - Fair Deficiency CABINETRY: MISSING/DAMAGED Deficiency Location/Instance Rooms 326, 430 Deficiency Quantity 12 Quantity Uom L.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1 No photo recorded Violations No violations recorded.

SCIENCE PREP ROOM Inspected Instance on Room 433 Inspected Alternative use Yes Fixed Equipment Instance on Room 433 Inspected Condition 3 - Fair Deficiency CABINETRY: MISSING/DAMAGED Deficiency Location/Instance Room 433 Deficiency Quantity 8 Quantity Uom L.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1 No photo recorded Violations No violations recorded.

SHOWER ROOM Inspected Instance on 1st Floor - Boys Inaccessible Instance on 1st Floor - Girls Inaccessible STAIRS/RAMPS: INTERIOR Inspected Do Letter Stair Signs Exist? Partially Ceiling Inspected

PB/A&W Page 53 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR STAIRS/RAMPS: INTERIOR Ceiling Condition 2 - Between Good and Fair Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK Deficiency Location/Instance Stair C/1 Vestibule Deficiency Quantity 50 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 5 Purpose of Action LEVEL 2 Deficiency Photo1

Stair C/1 Vestibule Violations No violations recorded.

Deficiency PLASTER: CRACKS/SPALLING Deficiency Location/Instance Stairs A/1, B/2, 4, C/3, D/1, L/2 Deficiency Quantity 70 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Stair B/4 Violations No violations recorded.

Door(s) Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded Partition Does not Exist Railings Inspected Condition 5 - Poor Deficiency METAL: BROKEN BRACKET Deficiency Location/Instance Stair H/1 Deficiency Quantity 1 Quantity Uom EACH

PB/A&W Page 54 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR STAIRS/RAMPS: INTERIOR Railings Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Stair H/1 Violations No violations recorded.

Deficiency METAL: DAMAGED Deficiency Location/Instance Stairs A/1, B/1, C/1, D/1, E/1, F/1, G/1, and others Deficiency Quantity 48 Quantity Uom L.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Stair B/1 Violations No violations recorded.

Deficiency METAL: MISSING Deficiency Location/Instance Auditorium - Right side of Stage Entrance Deficiency Quantity 3 Quantity Uom L.F. Potential Action REPLACE Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6

PB/A&W Page 55 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR STAIRS/RAMPS: INTERIOR Railings Inspected Deficiency Photo1

Auditorium - Right side of Stage Entrance Violations No violations recorded.

Stairs and Landings Inspected Condition 3 - Fair Deficiency METAL: RUST - MAJOR Deficiency Location/Instance Stairs B/1, D/1, H/1 Deficiency Quantity 30 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Stair B/1 Violations No violations recorded.

Deficiency TERRAZZO: CRACKS Deficiency Location/Instance Main Entrance Lobby, Stairs A/1, C/1, D/2, 3, F/1, and others Deficiency Quantity 200 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

PB/A&W Page 56 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR STAIRS/RAMPS: INTERIOR Stairs and Landings Inspected Main Entrance Lobby Violations No violations recorded.

Deficiency TERRAZZO: CRACKS Deficiency Location/Instance Stairs D/2, 3, E/1, 2, F/2, K/2 Deficiency Quantity 100 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 Deficiency Photo1

Stair D/3 Violations No violations recorded.

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES Deficiency Location/Instance Stairs B/3, 4, C/2, D/2, F/2, and others Deficiency Quantity 230 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Stair B/4 Violations No violations recorded.

Walls Inspected Condition 2 - Between Good and Fair Deficiency GLAZED BLOCK: CRACKS/SPALLING Deficiency Location/Instance Stairs A/3, B/4, C/4, F/1, K/1, and others Deficiency Quantity 120 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 PB/A&W Page 57 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR STAIRS/RAMPS: INTERIOR Walls Deficiency Photo1

Stair B/4 Violations No violations recorded.

TOILET ROOMS - STAFF Inspected Ceiling Inspected Condition 2 - Between Good and Fair Deficiency PLASTER: CRACKS/SPALLING Deficiency Location/Instance Kitchen Women’s Toilet Room Deficiency Quantity 10 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Kitchen Women’s Toilet Room Violations No violations recorded.

Door(s) Inspected Condition 5 - Poor Deficiency WOOD: DETERIORATED DOOR Deficiency Location/Instance Kitchen Men’s Toilet Room, Rooms 170A, 270A, 236, 370A, 470B Deficiency Quantity 6 Quantity Uom EACH Potential Action MAINTENANCE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2

PB/A&W Page 58 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR TOILET ROOMS - STAFF Door(s) Deficiency Photo1

Kitchen Men’s Toilet Room Violations No violations recorded.

Floor Finish Inspected Condition 3 - Fair Deficiency CERAMIC TILE: BROKEN/MISSING TILES Deficiency Location/Instance Kitchen Women’s Toilet Room, Rooms 238, 270A, 270B Deficiency Quantity 60 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Kitchen Women’s Toilet Room Violations No violations recorded.

Stalls Inspected Condition 5 - Poor Deficiency RUST - MAJOR Deficiency Location/Instance Kitchen Men’s Toilet Room, Women’s Toilet Room, Rooms 238, 370B, 470A, 470B, and others Deficiency Quantity 10 Quantity Uom EACH Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2

PB/A&W Page 59 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR TOILET ROOMS - STAFF Stalls Deficiency Photo1

Room 470B Violations No violations recorded.

Walls Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded TOILET ROOMS - STUDENTS Inspected Ceiling Inspected Condition 2 - Between Good and Fair Deficiency PLASTER: CRACKS/SPALLING Deficiency Location/Instance Auditorium Girls’ Toilet Room, Rooms 152, 350, 414, 420, and others Deficiency Quantity 90 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Auditorium Girls’ Toilet Room Violations No violations recorded.

Door(s) Inspected Condition 5 - Poor Deficiency WOOD: DAMAGED LOUVER Deficiency Location/Instance Room 252 Deficiency Quantity 1 Quantity Uom EACH Potential Action MAINTENANCE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2

PB/A&W Page 60 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR TOILET ROOMS - STUDENTS Door(s) Deficiency Photo1

Room 252 Violations No violations recorded.

Deficiency WOOD: DETERIORATED DOOR Deficiency Location/Instance Rooms 220, 350, Auditorium Dressing Room Deficiency Quantity 3 Quantity Uom EACH Potential Action MAINTENANCE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Room 350 Violations No violations recorded.

Floor Finish Inspected Condition 2 - Between Good and Fair Deficiency CERAMIC TILE: BROKEN/MISSING TILES Deficiency Location/Instance Inside Boys Locker Room, Girls Locker Room Deficiency Quantity 20 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

PB/A&W Page 61 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR TOILET ROOMS - STUDENTS Floor Finish Inspected Inside Boys Locker Room Violations No violations recorded.

Stalls Inspected Condition 2 - Between Good and Fair Deficiency RUST - MAJOR Deficiency Location/Instance Auditorium Boys’ Toilet Room Deficiency Quantity 1 Quantity Uom EACH Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Auditorium Boys’ Toilet Room Violations No violations recorded.

Deficiency BROKEN/MISSING Deficiency Location/Instance Room 220 Deficiency Quantity 1 Quantity Uom EACH Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Room 220 Violations No violations recorded.

Walls Inspected Condition 2 - Between Good and Fair Deficiency PLASTER: CRACKS/SPALLING Deficiency Location/Instance Auditorium Boys’ Toilet Room, Room 414 Deficiency Quantity 20 Quantity Uom S.F. Potential Action REPLACE PB/A&W Page 62 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response INTERIOR TOILET ROOMS - STUDENTS Walls Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Auditorium Boys’ Toilet Room Violations No violations recorded.

Deficiency CERAMIC TILE: BROKEN/ MISSING Deficiency Location/Instance Inside Girls Locker Room, Rooms 220, 414, 420, Auditorium Boys’ Toilet Room, Boys’ Toilet Room Near Gymnasium C/D, and others Deficiency Quantity 110 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Auditorium Boys’ Toilet Room Violations No violations recorded.

LIFE SAFETY Inspected F.D. HOLDING AREA Does not Exist STEEL STAIRS Does not Exist SITE Inspected CONTAINERIZATION Inspected Condition 5 - Poor Deficiency FENCING MISSING Deficiency Location/Instance Glenwood Road Deficiency Quantity 1,200 Quantity Uom S.F. Potential Action INSTALL NEW Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1 No photo recorded Violations No violations recorded.

PB/A&W Page 63 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response SITE CONTAINERIZATION Deficiency CONTAINER DAMAGED Deficiency Location/Instance Glenwood Road Deficiency Quantity 6 Quantity Uom EACH Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Glenwood Road Violations No violations recorded.

Drainage System for Asphalt Inspected Catch Basins/Manhole - Surrounded by asphalt Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded Culverts - Asphalt Covering Does not Exist Drainage System for Concrete Inspected Catch Basins/Manhole - Surrounded by concrete Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded Culverts - Concrete Covering Does not Exist Drainage System for Soil Inspected Catch Basins/Manhole - Surrounded by Soil Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded Culverts - Soil Covering Does not Exist DRINKING FOUNTAINS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded FENCES Inspected Condition 4 - Between Fair and Poor Deficiency CHAIN LINK: DAMAGED POST/RAIL Deficiency Location/Instance Flatlands Avenue Walkway toward Athletic Field House, Flatlands Avenue Parking Lot Entrance Deficiency Quantity 50 Quantity Uom L.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2

PB/A&W Page 64 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response SITE FENCES Deficiency Photo1

Flatlands Avenue parking lot entrance Violations No violations recorded.

Deficiency CHAIN LINK: DAMAGED/DETERIORATED Deficiency Location/Instance Ralph Avenue, Glenwood Road Deficiency Quantity 150 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 5 Purpose of Action LEVEL 3 Deficiency Photo1

Glenwood Road Violations No violations recorded.

Deficiency CHAIN LINK: DAMAGED POST/RAIL Deficiency Location/Instance Flatlands Avenue, Ralph Avenue, Glenwood Road, Parking Lot at Glenwood Road Deficiency Quantity 160 Quantity Uom L.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Parking lot at Glenwood Road Violations No violations recorded.

PB/A&W Page 65 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response SITE FENCES Deficiency WROUGHT IRON: DAMAGED/DETERIORATED Deficiency Location/Instance Glenwood Road, Parking Lot Near Glenwood Road Deficiency Quantity 240 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Glenwood Road Violations No violations recorded.

Deficiency CHAIN LINK: DAMAGED/DETERIORATED Deficiency Location/Instance Flatlands Avenue, Ralph Avenue Deficiency Quantity 200 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Ralph Avenue Violations No violations recorded.

Deficiency CHAIN LINK: RUST - MAJOR Deficiency Location/Instance Flatlands Avenue Deficiency Quantity 250 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2

PB/A&W Page 66 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response SITE FENCES Deficiency Photo1

Flatlands Avenue Violations No violations recorded.

Deficiency CONCRETE CURB: DAMAGED/DETERIORATED Deficiency Location/Instance Flatlands Avenue, Ralph Avenue Deficiency Quantity 60 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Ralph Avenue Violations No violations recorded.

IRRIGATION SYSTEM Does not Exist PAVING Inspected Student Non-Use Inspected Gravel Exists? No Asphalt Inspected Condition 5 - Poor Deficiency LOCALIZED SINK AREA Deficiency Location/Instance Ralph Avenue Parking Lot Deficiency Quantity 50 Quantity Uom S.F. Potential Action REPAIR Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2

PB/A&W Page 67 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response SITE PAVING Student Non-Use Asphalt Deficiency Photo1

Ralph Avenue parking lot Violations No violations recorded.

Deficiency HEAVING Deficiency Location/Instance Along Glenwood Road Deficiency Quantity 100 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 Deficiency Photo1

Road Glenwood Road Violations No violations recorded.

Deficiency POTHOLES Deficiency Location/Instance Ralph Avenue Parking Lot, Glenwood Road Parking Lot Deficiency Quantity 30 Quantity Uom S.F. Potential Action REPAIR Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Glenwood Road Parking Lot

PB/A&W Page 68 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response SITE PAVING Student Non-Use Asphalt Violations No violations recorded.

Deficiency CRACKS - MAJOR Deficiency Location/Instance Parking Lot Near Athletic Field, Ralph Avenue Parking Lot, Glenwood Road Parking Lot Deficiency Quantity 5,000 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Ralph Avenue Parking Lot Violations No violations recorded.

Concrete Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded Pavers Inspected Condition 3 - Fair Deficiency HEAVING Deficiency Location/Instance Parking lot at Glenwood Road, Glenwood Road Near Containers Deficiency Quantity 100 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 Deficiency Photo1

Parking Lot at Glenwood Road Violations No violations recorded.

Student Use Inspected Gravel Exists? No Asphalt Does not Exist

PB/A&W Page 69 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response SITE PAVING Student Use Concrete Does not Exist Pavers Inspected Condition 2 - Between Good and Fair Deficiency HEAVING Deficiency Location/Instance Courtyard Entrance Deficiency Quantity 25 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 Deficiency Photo1

Courtyard Entrance Violations No violations recorded.

Deficiency HEAVING Deficiency Location/Instance Courtyard Deficiency Quantity 20 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Courtyard Violations No violations recorded.

Site Sidewalks & Walkways Inspected Asphalt Inspected Condition 4 - Between Fair and Poor Deficiency DAMAGED CURBS Deficiency Location/Instance Ralph Avenue Parking Lot Deficiency Quantity 20 Quantity Uom L.F. Potential Action REPLACE PB/A&W Page 70 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response SITE PAVING Site Sidewalks & Walkways Asphalt Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Ralph Avenue parking lot Violations No violations recorded.

Deficiency CRACKS - MINOR Deficiency Location/Instance Flatlands Avenue Parking Lot Entrance Deficiency Quantity 50 Quantity Uom S.F. Potential Action MAINTENANCE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1 No photo recorded Violations No violations recorded.

Deficiency CRACKS - MAJOR Deficiency Location/Instance Flatlands Avenue Parking Lot Entrance, Flatlands Avenue Walkway toward Athletic Field House Deficiency Quantity 500 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Flatlands Avenue Parking Lot Entrance Violations No violations recorded.

Concrete Inspected Condition 4 - Between Fair and Poor Deficiency DAMAGED CURBS Deficiency Location/Instance Flatlands Avenue Deficiency Quantity 10

PB/A&W Page 71 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response SITE PAVING Site Sidewalks & Walkways Concrete Quantity Uom L.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Flatlands Avenue Violations No violations recorded.

Deficiency HEAVING Deficiency Location/Instance Ralph Avenue Deficiency Quantity 50 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Ralph Avenue Violations No violations recorded.

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS Deficiency Location/Instance Flatlands Avenue, Ralph Avenue Deficiency Quantity 500 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2

PB/A&W Page 72 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response SITE PAVING Site Sidewalks & Walkways Concrete Deficiency Photo1

Ralph Avenue Violations No violations recorded.

Pavers Does not Exist DOT Sidewalk Inspected Asphalt Does not Exist Concrete Inspected Condition 4 - Between Fair and Poor Deficiency DAMAGED CURBS Deficiency Location/Instance Flatlands Avenue, Ralph Avenue, Glenwood Road Deficiency Quantity 80 Quantity Uom L.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Flatlands Avenue Violations No violations recorded.

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS Deficiency Location/Instance Flatlands Avenue, Ralph Avenue, Glenwood Road Deficiency Quantity 1,000 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2

PB/A&W Page 73 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response SITE PAVING DOT Sidewalk Concrete Deficiency Photo1

Flatlands Avenue Violations No violations recorded.

Pavers Does not Exist PLAYGROUNDS Does not Exist PLAYING SURFACE Does not Exist RETAINING WALLS Inspected Are there any Retaining Walls 6' OR higher facing public No street/sidewalk? Condition 3 - Fair Deficiency BRICK: DETERIORATED COPING STONE Deficiency Location/Instance Flatlands Avenue Deficiency Quantity 120 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Flatlands Avenue Violations No violations recorded.

Deficiency BRICK: DETERIORATED COPING STONE Deficiency Location/Instance Flatlands Avenue Parking Lot Entrance Deficiency Quantity 10 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6

PB/A&W Page 74 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response SITE RETAINING WALLS Deficiency Photo1

Flatlands Avenue Parking Lot Entrance Violations No violations recorded.

Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR Deficiency Location/Instance Parking Lot at Southeast side of Building, Glenwood Road Deficiency Quantity 40 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Parking Lot at Southeast side of Building Violations No violations recorded.

SEATING Inspected Benches Inspected Concrete Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded Metal/Wood/Plastic Does not Exist Bleachers Does not Exist SITE WALLS (NOT RETAINING WALLS) Inspected Condition 3 - Fair Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR Deficiency Location/Instance Southeast Parking Lot Near Athletic Field Deficiency Quantity 20 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2

PB/A&W Page 75 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response SITE SITE WALLS (NOT RETAINING WALLS) Deficiency Photo1

Southeast Parking Lot Near Athletic Field Violations No violations recorded.

Deficiency CAST IN PLACE CONCRETE: DETERIORATED EXPANSION JOINT Deficiency Location/Instance Glenwood Road Parking Lot Deficiency Quantity 20 Quantity Uom L.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2 Deficiency Photo1

Glenwood Road Parking Lot Violations No violations recorded.

STAIRS/RAMPS: EXTERIOR Inspected Railings Does not Exist Site Cheek/flank Walls Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies recorded Stairs/ramps Inspected Condition 2 - Between Good and Fair Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR Deficiency Location/Instance Southeast Parking Lot Deficiency Quantity 20 Quantity Uom S.F. Potential Action REPLACE Urgency of Action PRIORITY 3 Purpose of Action LEVEL 2

PB/A&W Page 76 of 77 Print Date: 9/13/2020 NYC Department of Education Building Condition Assessment Survey 2019 - 2020 Architectural Inspection K515 Question Response SITE STAIRS/RAMPS: EXTERIOR Stairs/ramps Deficiency Photo1

Southeast parking lot Violations No violations recorded.

PB/A&W Page 77 of 77 Print Date: 9/13/2020