GPS Time Backup for Power Industry

John Lowe Station Manager NIST Time & Frequency Division WWV Ft. Collins, CO. WWVH , HA. WWV/WWVH Provided Syntonization Frequency Calibration

• Standard Carrier Frequencies • 2.5, 5, 10, 15, 20 & 25 MHz • @10 kW radiated power on 5, 10, and 15 MHz • @2.5 kW radiated on 2.5, 20 and 25 MHz WWV/WWVH Reception

1FH F 1FL Multiple-hop

E 2FL 1EL

Transmit Receive

Ground/surface WWV/WWVH Reception

1FH F 1FL Multiple-hop

E 2FL 1EL

Transmit Receive

Ground/surface

Frequency stability 1 x 10-9 Time Synchronization 1mS WWVB Provided Syntonization Frequency Calibration

• Standard Carrier Frequency • 60 KHz • @70 kW radiated power (upgraded in 99’) WWVB Electron Content Diurnal Maps Sunset Greenbelt, MD Sunrise Greenbelt, MD Sunset Boulder, CO Sunrise Boulder, CO Sunset Sunrise Sunset Sunrise Boulder, CO Boulder, CO Greenbelt, MD Greenbelt, MD WWVB in terms of WWV Controlling Oscillator June 3,4, & 5 Slope +1µsec/24 hrs. (1800-1800 UT) WWVB 10 10 x 10N pts above WWV

50 µsec June 5 June 3 June 4 0000 0600 1200 1200 1800 0000 0600 Time (UTC) Frequency stability 1 x 10-11 1 x 10-12 With averaging Time Synchronization 100 uS (?) Power Grid Application Timing Needs

Application Need

General Purpose < ±100 ms

Time-Stamping SCADA and Operational Data Logs < ±1 ms

Substation Monitoring e.g. phasor measurement units (PMUs) < ±1 μs (IRIG-B Replacement Applications with a local PTP grandmaster )

Extended distance applications < ±1 μs (fault detection, transient suppression) Power Grid Application Timing Needs

Application Need

General Purpose < ±100 ms

Time-Stamping SCADA and Operational Data Logs < ±1 ms

Substation Monitoring e.g. phasor measurement units (PMUs) < ±1 μs (IRIG-B Replacement Applications with a local PTP grandmaster )

Extended distance applications < ±1 μs (fault detection, transient suppression)

What GPS gives you! Proposed Solution To Backup GPS Proposed Solution To Backup GPS Internet Connected “Radio Common View” Radio KNIT Knowledgeable Networked Integrated Time Proposed Solution To Backup GPS Internet Connected “Radio Common View” Radio KNIT Knowledgeable Networked Integrated Time

Proposed Solution Pinch Hitting for GPS Radio KNIT Knowledgeable Networked Integrated Time

Backing up GPS “time” by knitting together: -NIST radio station signals -Common View algorithms -Smart Internet connectivity Field Receiver

GPS

Local clock Field Receiver

GPS NIST Antenna Radio Station Antenna

Local clock Internet Connection Field Receiver

GPS NIST Antenna Radio Station Antenna

Local clock Internet Connection KNITting Field Receiver

GPS NIST Antenna Radio Station Antenna

Local clock Internet Connection KNITting Field Receiver

GPS NIST Antenna Radio Station Antenna

Local clock Internet Connection Field Receiver Field Receiver Field Receiver

GPS NIST Antenna Radio Station Antenna

Local clock Internet Connection New Type Receiver

GPS NIST Antenna Radio Station Antenna

Local clock Internet Connection Add New Type Receiver Better GPS NIST Antenna Radio Station Clock Antenna

Local clock Internet Connection An New Type Receiver Atomic GPS NIST Antenna Radio Station Clock Antenna

Atomic clock Internet Connection An Monitoring Station Atomic GPS NIST Antenna Radio Station Clock Antenna

Atomic clock Internet Connection Monitoring Station

GPS NIST Antenna Radio Station Antenna

Atomic clock Internet Connection Field Receiver Monitor Monitor Station Station

Monitor Station

Monitor Station

Field Monitor Receiver Station

Monitor Station

Monitor Station Monitor Station

Field Receiver Good Clock Monitor Station Wants to be Field A Good Clock Receiver Without GPS CHU

WWV Monitor Station WWVB Field Receiver

WWVH Monitor Station WWVB Field Receiver Monitor Station WWVB Field Receiver GPS

Monitor Station WWVB Field Receiver GPS

Monitor Station WWVB Internet Field Connection Receiver Monitoring Station

GPS NIST Antenna Radio Station Antenna

Atomic clock Internet Connection Monitoring Station

GPS NIST Antenna Radio Station Antenna

Posts Path Delay

Atomic clock Internet Connection Field Receiver

GPS NIST Antenna Radio Station Antenna

Local clock Internet Connection Field Receiver

GPS NIST Antenna Radio Station Antenna

Local clock Internet Connection Reads Monitor’s Path Delay Field Receiver

GPS NIST Antenna Radio Station Antenna

Reads Monitor’s Path Delay

Local clock Internet Compares Connection To Field Path Delay Field Receiver

GPS NIST Antenna Radio Station Antenna

Reads Monitor’s Path Delay

Local clock Internet Compares Connection To Field - = ε Path Delay Monitor Station WWVB Field ε Receiver Field Receiver

GPS NIST Antenna Radio Station Antenna

Reads Monitor’s Path Delay

Local clock Internet Compares Connection To Field Path Delay Field Receiver

GPS NIST Antenna Radio Station Antenna

Reads Monitor’s Path Delay

Local clock Internet Compares Connection To Field Path Delay Field Receiver

_ GPS NIST = Antenna Radio Station Corrects Antenna Local Clock Common View ε Reads Monitor’s Path Delay

Local clock Internet Compares Connection To Field Path Delay Field Receiver

_ GPS NIST = Antenna Radio Station Corrects Antenna Local Clock Common View ε Reads Monitor’s Path Delay

Local clock Internet Compares Connection To Field Path Delay Maintains Synch Monitoring Station Clock We want a clock that can hold <1 µs timing accuracy for >7 days…

A synchrophasor is defined as the magnitude and angle of a cosine signal as referenced to an absolute point in time.

Monitor Station

Field How Far? Receiver Differential WWVB Error (over 24 hrs) as a function of Distance from Reference Receiver (Maryland) 10.0 ) [us]

1.0 Unmodeled (

0.1 10 100 RMS Differential Differential RMS Timing Error Distance of WWVB Receiver relative to Reference [Miles] How Far? North/South East/West Joint Proposal Assured Timing for Critical Infrastructure Request for Proposal Other things NIST is working on…

GPS All in View GPS All in View NIST Disciplined Oscillator NIST Disciplined Oscillator NIST Disciplined Oscillator

Frequency stability 5 x 10-14 Time Synchronization 10 nS NIST Disciplined Oscillator

FMAS Frequency Measure & Analysis Service -14 TMAS Frequency stability 5 x 10 Time Measure Time Synchronization 10 nS & Analysis Service SIM Sistema Interamericano de Metrologia (SIM). This time scale, known as the SIM time scale, or SIMT, was developed to complement the official world time scale, Coordinated Also Precision Time Protocol Setup Precision Time Protocol Setup Average Time Offset 13.6 us Calibrate the Client

Specification for LTE 1.5 us Ideally: < 1 us Average Time Offset 13.6 us Calibrate the Client

Specification for LTE 1.5 us Ideally: < 1 us

300 nS RMS Chip-scale Atomic Clocks Chip-scale Atomic Clocks

1 mm Monitoring Station Clock <1 µs timing error over a week and 1×10-12 fundamental accuracy NIST-on-a-Chip Passively Pumped Design:

Actively Pumped Prototype:

MEMS Beam-Clock Design: The End