<<

providing insights for today’s hvac system designer Engineers Newsletter volume 47–2

HVAC-related changes in ASHRAE Standard 90.1-2016

down in a digital document (ironically 2013 version. This is the energy Jurisdictions have begun to adopt noted in this three-column document). ASHRAE 90.1-2013. We now look to the consumed by the entire building, 2016 version for ideas on how to save And due to overwhelming hue and cry, including equipment not regulated by energy over the 2013 version—for italics that were removed in the 2013 90.1. participating in above-code programs, version have been restored. Words in preparing for the future, or simply as a italics are defined in Chapter 3 of the The mechanical-related changes include: design preference for energy and energy cost saving. This Engineers Newsletter standard. You'll also find that digital • New climate zone assignments from describes important changes affecting versions have hyperlinks and cross- ASHRAE Standard 169-2013 HVAC systems and related equipment. references. There is also a new interactive tool for 90.1 available on the • Replacement equipment to follow some mandatory and prescriptive Since 1975, ANSI/ASHRAE/IES ASHRAE website. requirements (other than just Standard 90.1 (hereafter referred to as Purchase a copy of Standard 90.1, and efficiency) 90.1 for brevity) has been the basis of the accompanying User’s Manual to many energy codes, and continues to • New coverage in equipment classes better understand the requirements as be adopted directly or by reference in such as DOAS, CRAC and pool they apply to specific systems, climates, the International Energy Conservation buildings and design applications. Code (IECC). It is also the basis for • Upgraded efficiency in packaged DX determining compliance with the rooftops, PTAC and VRF Energy Policy Act of 1992. • fault detection in While harmony is desired and 2016 HVAC Changes packaged DX equipment attempted between 90.1 and IECC, • Variable airflow exhaust- and return- some requirements diverge. This 121 addenda were incorporated in 2016. VFD control for building pressure newsletter identifies some of the areas Of those, only 23 had energy savings control and sections with the most differences which could be captured in any of the between the two model codes, to help nearly 600 energy models created by the • VFD threshold reductions (towers, designers select a preferred path when U.S. Department of Energy to determine pumps, fans) there is a choice. energy saving impacts. Some types of • Fan system control 5 hp threshold equipment are not used in any of the moved to subsections Look for this icon throughout this prototype buildings, some changed the newsletter to indicate significant optional performance path only, and • Chilled-water plant monitoring differences between 90.1-2016 and others simply added clarity to previous • 15°F minimum design delta T for IECC-2018. requirements. cooling coil selections The most obvious change is the new According to these models, the 23 • reset alternative to formatting, which is better suited for addenda save 34 percent energy versus pump pressure reset digital use. More columns in the old the 2004 version, or 6.8 percent version lead to more scrolling up and (weighted average) compared to the Let's review these changes in more detail.

©2018 Trane. All rights reserved. 1

Revised climate classifications. Figure 1. ASHRAE climate zone map. ASHRAE 90.1-2016 updated to the climate classifications published in ASHRAE Standard 169-2013 (Figure1). The methods and data used to develop the classifications are sufficiently arcane that this newsletter will only summarize and illustrate the significance of this change.

Some areas were quite affected (Figure 2). For example, 75 percent of the population of Wisconsin "moved" from climate 6A to 5A and 3 percent moved from 7 to 6A. Other states heavily reclassified are West Virginia (47%), North Carolina (43%), North Dakota (37%), Tennessee (36%), Indiana (30%) and Texas (24%). A few states reclassified as colder, such as Oklahoma (9% from 3A to 4A), New Hampshire (6% from 5A to 6A) and Washington (4% from 4C to 5C). Portions of 169 have been reprinted in the appendices of 90.1 for ease of reference.

These changes have ripple effects Figure 2. Counties where climate zone classification has changed. throughout the Standard. For example, requirements for insulation, glazing, the economizer tradeoff and high limit controls may change, all with potential impacts on energy savings calculations.

Climate zone 1 has been divided to include a new climate zone 0, to allow for more discerning requirements and their justifications for even hotter locations. Several areas outside of North America have begun to use 90.1 as the basis of their own energy RED counties moved to codes—some of which are in climate milder zones Source: zone 0. GREEN counties moved to colder zones

2 Trane Engineers Newsletter volume 47-2 providing insights for today’s HVAC system designer Mandatory Section (6.4) stringency. The table is quite large due to Prescriptive Section (6.5) Changes many different temperature conditions for Changes the various cooling and heating sources. Requirements in this section are Prescriptive requirements may be traded mandatory, meaning they cannot be -plant monitoring and reporting. off using one of the performance or traded off using any of the other Another mandatory requirement is for new alternative compliance paths. If you have a compliance paths. All paths include the chiller plants to have efficiency and energy situation where you can't or don't wish to mandatory sections. use measurement and reporting. This comply with a prescriptive requirement, requirement is invoked based on climate you may switch to the performance path and chiller-plant size (Table 1). Replacement equipment. Previously, (Chapter 11) or the new Energy-Cost- Budget (Appendix G) based compliance like-for-like replacement equipment only Table 1. Chiller-plant monitoring requirements had to meet the minimum efficiency option. requirements, and not all other Climate zone Water-cooled Air-cooled plant plant prescriptive and mandatory Replacement equipment requirements. In the new version, 3C,4C,5,6,7,8 >1500 tons >860 tons prescriptions. In addition to the replacement equipment is now obliged previously mentioned mandatory to also meet several mandatory (as well 0,1,2,3A,3B, >1000 tons >570 tons requirements, the following prescriptive as prescriptive) requirements. This 4A,4B requirements must also be met when includes off-hour controls, demand- replacing like-for-like equipment. controlled ventilation for single-zone • (outdoor units) systems, and setpoint controls. Other The data must be recorded and trended prescriptive requirements for every 15 minutes and graphically displayed • Integrated economizer control replacement equipment will be to include hourly, daily, monthly and annual • Economizer heating impact discussed later. information. The data must be maintained for at least three years. • Fan efficiency DOAS equipment. A new class of • Fan airflow control product has been added for direct- Economizer fault detection and • Ventilation optimization (multiple-zone expansion (DX), dedicated outdoor air diagnostics. This mandatory requirement VAV systems) systems (DOAS). This includes a applies to packaged unitary DX air- reference to the recently created AHRI conditioners and heat pumps, regardless of • Parallel, fan-powered VAV controls Standard 920, which reflects the condensing type, if they have an air • Fractional horsepower fan motors different conditions a 100 percent economizer. The purpose is to identify outdoor-air unit is expected to when sensors and controls on the • Fan speed control (heat rejection experience. The rating is based on equipment are not economizing (bringing in equipment) moisture removal efficiency (MRE) with more than minimum outdoor air) when • Chiller and isolation an off-design rating of ISMRE for cooling outdoor conditions are favorable, or • Boiler turndown and/or ISCOP for heating. Standard 920 conversely if the economizer is active when and its use by 90.1 was the subject of a conditions are unfavorable. Permanent previous Engineers Newsletter. sensors, economizer status, fault Chilled-water reset. This is a new detection, reporting and provisions for test alternative to pump-pressure reset based Pool dehumidifiers and CRAC units modes are specified by 90.1. This on critical valve position. You may now are newly covered in the scope of requirement has been in place for several choose to reset chilled-water temperatures 90.1. The scope of 90.1 is written so years in California; manufacturers have to keep one valve nearly wide open or until that coverage for new equipment can be already developed equipment options that equipment limits are reached. Or, you may added over time. In this case, pool meet the requirements (Figure 3). continue to use pump-pressure reset dehumidifiers and CRAC units now have based on critical valve. Exceptions are minimum efficiency requirements. provided for district cooling, thermal Figure 3. Automatic fault detection implemented storage and process cooling. The Trane in a rooftop unit controller ENL in 2015 included a table comparing the VRF equipment. The 2013 version had energy performance of the two options. the first efficiency requirements for VRF Generally speaking, pump-pressure reset systems with a corresponding AHRI saves more energy at higher load (flow) certification program and test conditions, or when constant-speed procedure. The 2016 version changes are used, and when system design some of the part-load requirements, delta T is less than 15º F. You can also effective either January of 2017 or 2018, choose to do both resets in sequence. That depending on the product. Part of this is is, do one until it reaches a limit and then due to a change in the test procedures the other. and part from an actual improvement in

providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 47–2 3

Table 2. Updated requirements for pump VFD control Chilled-water pumps Heating-water pumps Nameplate hp 0, 1, 2B no requirement ≥ 2 hp 2A, 3B no requirement ≥ 3 hp 3A, 3C, 4A, 4B 7,8 ≥ 5 hp 4C, 5, 6 3C, 5A, 5C, 6B ≥ 7.5 hp 4A, 4C, 5B ≥ 10 hp 7,8 4B ≥ 15 hp 2, 3A, 3B ≥ 25 hp 1B ≥ 100 hp 0, 1A ≥ 200 hp

Pump VFD control by climate zone, Waterside economizer for induction Two changes were made. The word "fan" now includes heating. During the and/or fan-free systems. Aggregating was struck from the threshold, as evaluation of lowering the chilled-water coil capacity rather than looking at the sometimes these units do not have a fan. pump VFD threshold, it was discovered fan-plus-coil terminal size is something Then, when their total cooling load is that the existing requirements were not that's new and starting to affect more large enough, an economizer is required. universally cost justified. The result of codes, but not 90.1. Thresholds based on "Large enough" varies by climate zone. this evaluation prompted a new table, terminal size were used so that chilled- The new requirement applies to chilled- which also creates VFD requirements water systems were not disadvantaged water cooling systems without a fan or on heating-water pumps in many compared to other small-terminal DX that use induced airflow when the sum of climate zones. Unsurprisingly, hot systems, such as PTACs or VRF. Small the cooling loads not served by another climates use drives on smaller pumps units (<54,000 Btu/h) have traditionally type of economizer is in their cooling system and cold been exempt from economizers and still climates use drives on smaller pumps are. However, chilled-beam and induction • ≥ 1,000,000 Btu/h (83 tons) in in their heating systems (Table 2). units now are not. When multiple chilled- climates 0, 1B, 2, 3, and 4 water terminals are connected to the • ≥ 1,400,000 Btu/h (116 tons) in same chiller, especially sensible-cooling- climates 5-8 only terminals using relatively warm water, it's difficult to ignore the potential • Any size in climate 1A savings by using the water-economizer cycle.

Water economizer requirement in IECC. Unlike 90.1, the IECC now has a system size aggregation (not just for induction units but for all chilled-water coils) when water economizers are required (Table 3). The equipment performance exception may be used instead in climates 2A/B, 3A/B and 4A/B (Table 6).

Table 3. Minimum chilled-water system cooling capacity for determining economizer cooling requirements

Total chilled-water system capacity less capacity of cooling units with air economizers Climate zone Local water-cooled chilled-water systems Air-cooled chilled-water systems or district chilled-water systems

1A Economizer not required Economizer not required

1B, 2A, 2B ≥ 960,000 Btu/h ≥ 1,250,000 Btu/h

3A, 3B, 3C, 4A, 4B, 4C ≥ 720,000 Btu/h ≥ 960,000 Btu/h

5A, 5B, 5C, 6A, 6B, 7,8 ≥ 1,320,000 Btu/h ≥ 1,720,000 Btu/h

4 Trane Engineers Newsletter volume 47-2 providing insights for today’s HVAC system designer Ventilation optimization despite Parallel-flow, fan-powered VAV Compliance requires two things: control ERV. The 2010 standard introduced the (PFPVAV) air termination control. This and capability. The return/relief fan control requirement for ventilation optimization new requirement specifies the method of must either directly manage building in multiple-zone VAV systems. It was controlling the fan in a parallel, fan- pressure control or indirectly through thought that systems required to use powered VAV terminal. The fan is only supply-return airflow tracking. The second exhaust air energy recovery should be permitted to run during heating mode, or part of the requirement is for VFDs on exempt from this requirement. if required for ventilation, and as the first fans ½ hp and larger or at least four However, energy use increased with this stage of heat before any heating coil is stages of control. exception, so it has been removed. All activated. Additionally, during warmup or multiple-zone VAV systems must use during setback the controller must either Fan system control threshold moved to ventilation optimization unless their stop the primary air or reverse the logic subsections. Previous versions only exhaust is too high (>70%) relative to so that when the primary air is warmer required compliance with all of Section outdoor-air intake, or if zone-to-zone rather than colder than the zone, the 6.5.3 Air System Design and Control once transfer fans are used, as in fan-powered actuates to open (for more heat) the total system motor nameplate VAV systems. The first exception is rather than close to its minimum as it exceeds 5 hp. This meant that because less turndown of outdoor air is does in cooling mode when the zone is requirements such as the system fan- available, and the second exception is being overcooled. power limit effectively did not apply to because the ventilation effectiveness of small, unitary packaged equipment. systems meeting that exception cannot Variable airflow exhaust- and return- Requirements specifically addressing be easily determined. fan controls. Building pressurization is products below the threshold (such as fan critical for conserving energy, not to control down to 65,000 Btu/h, supply- air- Ventilation design. This new mention moisture control. When exhaust temperature reset, VAV setpoint sensing) requirement sets an upper limit on fans are out of sync with the ventilation perversely did not apply in some cases ventilation of 135 percent of the system, buildings don't perform well. anyway. The system size threshold was minimum outdoor airflow rate using the This can lead to doors that stand open replaced with individual thresholds within prescriptive path. If additional ventilation (positive pressure) or to moisture the specific requirements is part of the design, the building would intruding into the envelope (negative (Table 4). have to comply using one of the pressure). Moisture in the insulation layer performance options. reduces its effectiveness at reducing heat gains or losses across the envelope. Limits on reheating in dedicated Buildings with poor pressurization control outdoor-air systems (DOAS). When are also more likely to have operators zones demand cooling, it doesn't make who disable or limit airside economizer sense for the DOAS to reheat operation. dehumidified air to space neutral dry- bulb temperatures, because zone cooling and fan energy increase. This Table 4. Size thresholds for Section 6.5.3. requirement sets a limit of no higher Section Name Threshold than 60°F supply air from the DOAS 6.5.3.1 Fan System Power and Efficiency > 5 hp when a majority of the zones are in 6.5.3.1.3 Fan Efficiency All, with exceptions cooling mode. Any energy (even site- 6.5.3.2 Fan Control DX >= 65,000 Btu/h sourced or recovered energy) is chilled water >= 1/4 hp prohibited from being used for this purpose. This implies system-level 6.5.3.2.2 VAV Static Pressure Sensor Location All or meet 6.5.3.2.3 instead coordination: the DOAS is operated 6.5.3.2.3 VAV Setpoint Reset > 5 hp and DDC differently, depending on the mode 6.5.3.2.4 Return and Relief Fan Control >1/2 hp in total (exception) or 4+ stages (heating or cooling) of the majority of the 6.5.3.3 Multiple-zone VAV Ventilation Optimization All, with exceptions zones served by the other cooling/ 6.5.3.4 Parallel-flow, Fan-powered VAV Control (new All heating systems. A previous Trane requirement) Engineers Newsletter and application 6.5.3.5 Supply-Air-Temperature Reset All, with exceptions for climate zones 0, 1A, 2A, guide (SYS-APG001-EN) discuss the 3A (and other cases merits of non-neutral DOAS air delivery 6.5.3.6 Fractional Horsepower Fan Motors 1/12 to 1/2 hp motors, exception for heating-only in more detail. fans, others 6.5.3.7 Ventilation Design (new requirement) All

providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 47–2 5

Economizer comfort cooling efficiency Minimum 15°F delta T chilled-water tradeoff. This requirement is not new, cooling coil selections. Chilled-water Where to Learn More but many locations may have switched coils now must be selected for at least a climate zones. The option compares the 15°F delta T with at least a 57°F leaving ASHRAE 90.1-2016 incorporated many efficiency of -bearing coil water temperature. Exceptions changes in this cycle. This newsletter equipment to the minimum requirements include: summarized only the HVAC-related for that same equipment in Section 6.4.1. mandatory and prescriptive changes. In • Sensible-only cooling coils, If the unit meets the full-load efficiency 2017, ASHRAE launched a 90.1 portal which required in Section 6.4.1 and its rated • Fan-cooling units with 5000 cfm or you may find useful for learning more about part-load efficiency is better than the less, these and other changes. It brings together the Standard, the Users' Manual, and a minimum requirement by the fraction in • Constant volume systems, the tradeoff table (Table 5), an redline version that shows changes from economizer is not required. • Coils selected at 50°F or higher one version to the next. Visit https:// entering water or 65°F or lower 901portal..org. This option is quite different in IECC- entering air dry-bulb temperatures, 2018, where it is less stringent but only or coils selected at the maximum The International Code Council (ICC) has covers six climates: 2A/B, 3A/B, 4A/B. temperature difference allowed by also provided free online view-only access The "A" climates are new in the 2018 the chiller. to the IECC Model Code. Chapter 4 version (Table 6). (commercial) can be viewed at https:// An extensive analysis was submitted to codes.iccsafe.org/public/document/ 90.1 showing system energy iecc2018/chapter-4-ce-commercial-energy- Table 5. Eliminate required economizer for consumption and first costs are reduced efficiency. comfort cooling by increasing cooling when chilled-water coils are selected for efficiency (90.1) higher delta Ts (lower water flow rates). climate efficiency The analysis included the impacts on fan, zone improvement pump and chiller energy and costs. The By Susanna Hanson, Trane. To subscribe or view previous issues of the Engineers Newsletter visit 2A 17% rationale is explained in detail in a new trane.com/EN. Send comments to [email protected]. 2B 21% course, ""Fundamentals of Design and 3A 27% Control of Central Chilled-Water Plants," from the ASHRAE Learning Institute. 3B 32% 3C 65%

4A 42% Table 6. Table C403.5 (2) Equipment Efficiency 4B 49% Performance Exception for Economizers (IECC) 4C 64% cooling equipment climate performance improvement 5A 49% zones (EER or IPLV) 5B 59% 2A, 2B 10% efficiency improvement 5C 74% 3A, 3B 15% efficiency improvement 6A 56% 4A, 4B 20% efficiency improvement 6B 65% 772% 877%

6 Trane Engineers Newsletter volume 47-2 providing insights for today’s HVAC system designer A New Level of Building Design Accuracy References Announcing TRACE® 3D Plus! [1] American Society of Heating, Refrigerating, and Air-Conditioning Engineers. 2013 ANSI/ ASHRAE/IESNA Standard 90.1-2013: Energy Standard for Buildings Except Low-Rise Residential Buildings. Atlanta, GA: ASHRAE.

[2] American Society of Heating, Refrigerating, and Air-Conditioning Engineers. 2016. ANSI/ ASHRAE/IESNA Standard 90.1-2016: Energy Standard for Buildings Except Low-Rise Residential Buildings. Atlanta, GA: ASHRAE.

[3] ASHRAE Standard 90.1-2016 User’s Manual. Atlanta, GA: ASHRAE. Available at TRACE 3D Plus is a next generation building design and analysis software www.ashrae.org/bookstore. program that delivers faster, more accurate results through a seamless workflow that closely aligns with today's building process. The latest [4] 2018 International Energy Conservation Code. HVAC systems and controls can be modeled quickly, precisely and with International Code Council, Washington, D.C. IECC. 2018. the intricacies of today's many building applications. TRACE 3D Plus is built on the U.S. Department of Energy's EnergyPlus® engine and [5] Murphy, J., AHRI 920 "Rating Standard for enhanced with Trane's industry leading expertise to help designers Dedicated Outdoor Air Units," Trane Engineers validate and interpret projects with confidence and clarity. All of these Newsletter, vol. 45-4. ADM-APN060-EN. Trane 2016 new features plus a more robust support experience to get you up and running quickly. [6] Hanson, S., M. Patterson and J. Harshaw, "Chilled-Water System Design Trends." Trane For details or to download a trial version visit Trane.com/TRACE3DPlus Engineers Newsletter LIVE. APP-CMC056-EN. Trane. 2015.

[7] Trane. Dedicated Outdoor Air Systems: Trane DX Outdoor Air Unit Application Guide. SYS- APG001-EN. 2012.

[8] Taylor, Steven T, "Fundamentals of Design and Control of Central Chilled-Water Plants", ASHRAE Learning Institute, 2017.

providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 47–2 7

Join your local Trane office for the 2018 Engineers Newsletter LIVE! Mark your calendar!

Demand-Controlled Ventilation. The mobility of a building’s occupants poses a ventilation challenge: To bring enough outdoor air into the building to help ensure good without wasting energy by bringing in (and conditioning) too much. This ENL will discuss various methods used to vary outdoor airflow based on actual demand. It also reviews the related requirements for compliance with ASHRAE Standards 62.1 and 90.1. (November)

Contact your local Trane office for dates and details.

Earn PDH credit - no charge and on-demand! NEW Online Courses Available! View all courses under Training/Continuing Education at www.trane.com

Cooling Towers and Condenser-Water System Design and Operation Sometimes overlooked, the cooling towers and condenser water loop play and important role in the first cost, function, and efficiency of the chilled-water systems. A fundamental understanding of how the affects chiller performance can provide opportunities to reduce both capital cost and operating expense. (Recorded 2005)

Chilled-water System Design Trends This program reviews recent advancements in technology and trends due to these developments, system strategies that can take advantage of the latest technology and when various system strategies should be used. Consideration will be given to: variable primary, primary secondary, constant flow, series chillers, chilled water reset, pump pressure optimization, flow rates and turndown, types, and the components of air- and water-cooled systems.

Trane, the Circle Logo, and TRACE are trademarks of Trane in the United States and other countries. ASHRAE is a regis- tered trademark of the American Society of Heating, , and Air-Conditioning Engineers, Inc. Trane is a brand of Ingersoll Rand, a world leader in creating comfortable, sustainable and efficient environments. Ingersoll Rand's family of brands includes Club Car®, Ingersoll Rand®, Thermo King® and Trane®.

Trane, This newsletter is for informational purposes only and does not constitute legal advice. A business of Ingersoll Rand Trane believes the facts and suggestions presented here to be accurate. However, final design and application decisions are your responsibility. Trane disclaims any responsibility for actions taken on For more information, contact your local Trane the material presented. office or e-mail us at [email protected]

8 Trane Engineers Newsletter volume 47–2 ADM-APN066-EN (June 2018)