Liquid Subcooling Reheat (LSRH)

Total Page:16

File Type:pdf, Size:1020Kb

Liquid Subcooling Reheat (LSRH) 62X Air-Cooled DOAS Units Liquid Subcooling Reheat (LSRH) Carrier offers a liquid subcooling reheat (LSRH) option on all 62X dedicated outdoor air units. The liquid subcooling package boosts a unit’s dehumidification capacity to help deliver drier air to the space. AUDITORIUMS Because LSRH does not add to the unit footprint, it is an extremely cost effective way to enhance unit performance. In some cases, LSRH allows you to downsize your unit selection, decreasing unit size and electrical requirements while increasing cost savings. EDUCATION HEALTHCARE HOSPITALITY Reheat Coil Direct Subcooling Coil Expansion (DX) Coil Cut-away rendering shows placement of coils, including the LSRH option, inside a 62X Dedicated Outdoor Air unit. How Liquid Subcooling THREE-WAY THREE-WAY Reheat (LSRH) Works VALVE CONDENSER VALVE LSRH works by passing warm liquid refrigerant that is leaving CHECK the condenser to a full faced coil VALVE following the evaporator coil. Not only does the subcooling process SA help to reheat the supply air, it also HOT GAS reduces the temperature of the REHEAT COIL refrigerant entering the evaporator coil. The 62X unit dehumidification capacity will increase by as much LIQUID SUBCOOLING COMPRESSOR REHEAT COIL as 10% with LSRH, which can help to reduce the mechanical direct CHECK VALVE expansion (DX) capacity and improve unit efficiency. EVAPORATOR The LSRH is accompanied by a hot gas reheat (HGRH) coil to ensure OA that the supply air is reheated to space neutral conditions. EXPANSION DEVICE Carrier® 62X Dedicated Outdoor Air Unit carrier.com/62X | 1.800.CARRIER © 2020 Carrier. Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. .
Recommended publications
  • Subcooling Cryogenic Propellants for Long Duration Space Exploration
    -. Subcooling Cryogenic Propellants for Long Duration Space Exploration Shuvo Mustati1, Edgar Canavan 2 NASA Goddard Space Flight Center, Greenbelt, Maryland, 20771, USA Wesley Johnson3 NASA Kennedy Space Center, Kennedy Space Center, Florida, 32899, USA Bernard Kutter4 United Launch Alliance, Denver, Colorado, 80127, USA and JeffShull5 Barber Nichols> Arvada, Colorado, 80002, USA The use of cryogenic propellants such as hydrogen and oxygen is crucial for exploration of the solar system because of their superior specific impulse capability. Future missions may require vehicles with the flexibility to remain in orbit or travel in space for months, necessitating long-term storage of these cryogens. One powerful technique for easing the challenge of cryogenic fluid storage is to remove energy from tlie cryogenic propellant by isobaricly subcooling them below their normal boiling point prior to launch. The isobaric subcooling of the cryogenic propellant will be performed by using a cold pressurant to maintain the tank pressure while the cryogen's temperature is simultaneously reduced. After launch, even with the use of the best insulation systems, heat will leak into the cold cryogenic propellant tank. However, the large heat capacity available in highly subcooled cryogenic propellants allows them to absorb the energy that leaks into the tank until the cryogen reaches its operational thermodynamic condition. During this period of heating of the subcooled cryogen there will be no loss of the propellant due to venting for pressure control. This simple technique can extend the operational life of a spacecraft or an orbital cryogenic depot many months with minimal mass penalty. Subcooling technologies for cryogenic propellants would thus provide the Exploration Systems Mission Directorate with an enhanced level of mission flexibility.
    [Show full text]
  • Sustainable Energy Conversion Through the Use of Organic Rankine Cycles for Waste Heat Recovery and Solar Applications
    ENERGY SYSTEMS RESEARCH UNIT AEROSPACE AND MECHANICAL ENGINEERING DEPARTMENT UNIVERSITY OF LIÈGE Sustainable Energy Conversion Through the Use of Organic Rankine Cycles for Waste Heat Recovery and Solar Applications. in Partial Fulfillment of the Requirements for the Degree of Doctor of Applied Sciences Presented to the Faculty of Applied Science of the University of Liège (Belgium) by Sylvain Quoilin Liège, October 2011 Introductory remarks Version 1.1, published in October 2011 © 2011 Sylvain Quoilin 〈►[email protected]〉 Licence. This work is licensed under the Creative Commons Attribution - No Derivative Works 2.5 License. To view a copy of this license, visit ►http://creativecommons.org/licenses/by-nd/2.5/ or send a letter to Creative Commons, 543 Howard Street, 5th Floor, San Francisco, California, 94105, USA. Contact the author to request other uses if necessary. Trademarks and service marks. All trademarks, service marks, logos and company names mentioned in this work are property of their respective owner. They are protected under trademark law and unfair competition law. The importance of the glossary. It is strongly recommended to read the glossary in full before starting with the first chapter. Hints for screen use. This work is optimized for both screen and paper use. It is recommended to use the digital version where applicable. It is a file in Portable Document Format (PDF) with hyperlinks for convenient navigation. All hyperlinks are marked with link flags (►). Hyperlinks in diagrams might be marked with colored borders instead. Navigation aid for bibliographic references. Bibliographic references to works which are publicly available as PDF files mention the logical page number and an offset (if non-zero) to calculate the physical page number.
    [Show full text]
  • Theoretical Study on a Modified Subcooling Vapor-Compression Refrigeration Cycle Using Hydrocarbon Mixture R290/R600a" (2018)
    Purdue University Purdue e-Pubs International Refrigeration and Air Conditioning School of Mechanical Engineering Conference 2018 Theoretical study on a modified ubs cooling vapor- compression refrigeration cycle using hydrocarbon mixture R290/R600a Qi Chen Xi'an Jiaotong University, China, People's Republic of, [email protected] Jianlin Yu Xi’an Jiaotong University, China, People's Republic of, [email protected] Gang Yan Xi'an Jiaotong University, China, People's Republic of, [email protected] Yunho Hwang [email protected] Follow this and additional works at: https://docs.lib.purdue.edu/iracc Chen, Qi; Yu, Jianlin; Yan, Gang; and Hwang, Yunho, "Theoretical study on a modified subcooling vapor-compression refrigeration cycle using hydrocarbon mixture R290/R600a" (2018). International Refrigeration and Air Conditioning Conference. Paper 2079. https://docs.lib.purdue.edu/iracc/2079 This document has been made available through Purdue e-Pubs, a service of the Purdue University Libraries. Please contact [email protected] for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html 2720, Page 1 Theoretical Study on A Modified Subcooling Vapor-compression Refrigeration Cycle Using Hydrocarbon Mixture R290/R600a Qi Chen1*, Jianlin Yu1, Gang Yan1, Yunho Hwang2 1 Energy and Power Engineering School, Xi’an Jiaotong University, Xi'an, Shaanxi, 710049, China 2Center for Environmental Energy Engineering, Department of Mechanical Engineering, University of Maryland, College Park, MD 20742 (301-405-5247, [email protected]) * Corresponding author: [email protected] ABSTRACT In this study, a modified subcooling vapor-compression refrigeration cycle (MSVRC) using refrigerant mixture R290/R600a was proposed for applications in refrigerator-freezers.
    [Show full text]
  • TB-0037) BITZER Software Guide Version 4, January 2015
    Technical Bulletin (TB-0037) BITZER Software Guide Version 4, January 2015 DEFINITION OF TERMS Terms Found in the BITZER Software Condenser Capacity: The power needed to reject heat from the refrigerant after being compressed to fully condense and achieve specified amount of subcooling at the exit of the condenser. Reference “Total Heat of Rejection” for comparison. Condensing Capacity: The power needed to reject heat from the refrigerant after being compressed to fully condense the refrigerant. Reference “Total Heat of Rejection” for comparison. Cooling Capacity (Qoh): The potential energy transfer rate of the compressor that utilizes the suction gas temperature and the naturally subcooled liquid temp. In the Parallel-compound section of the software, externally subcooled liquid temp can be included in this capacity by checking the box located in Program Options. Compressor cooling capacity includes external subcooling. Evaporator Capacity (Qo): The energy transfer rate taking place inside the evaporator using the final liquid temp before entering the expansion device and the useful superheat. This term is the same as “Net Refrigeration Effect.” Natural Subcooling: The difference in temperature of the liquid refrigerant from the outlet of the condenser to the saturated condensing temp. Suction Gas Superheat: Temperature at the inlet of the compressor minus the saturated suction temp. Suction Gas Temperature (toh): Temperature at the inlet of the compressor. Useful Superheat: Superheat taking place inside of the evaporator (corresponds to the expansion device superheat.) 100% useful superheat indicates that the suction gas superheat and the useful superheat are identical. With Economizer / with Subcooler: When these terms are used in either a two stage or screw section of the software, they indicate a liquid line subcooler that utilizes its own expanded liquid which is fed back to the compressor at an interstage pressure.
    [Show full text]
  • Natural Refrigerant-Based Subcritical and Transcritical Cycles for High Temperature Heating Cycles Souscritiques Et Transcritiqu
    International Journal of Refrigeration 30 (2007) 3e10 www.elsevier.com/locate/ijrefrig Natural refrigerant-based subcritical and transcritical cycles for high temperature heating J. Sarkar, Souvik Bhattacharyya*, M. Ram Gopal Department of Mechanical Engineering, Indian Institute of Technology, Kharagpur 721302, India Received 11 April 2005; received in revised form 31 January 2006; accepted 13 March 2006 Available online 5 June 2006 Abstract Theoretical analyses of subcritical/transcritical heat pumps using four natural refrigerants, carbon dioxide, ammonia, pro- pane and isobutane have been carried out for high temperature heating applications at different heating outlet temperatures and heat sources using computer models. The compressor discharge pressures have been optimized for transcritical and subcrit- ical (with near critical operation of condenser) cycles. Results show that for subcritical heat pumps, use of subcooling is efficient for heating applications with a gliding temperature. Results also show that although propane yields better coefficient of perfor- mance (COP) in low temperature heating applications, ammonia performs the best in high temperature heating applications. Finally, design aspects of major components of all the four heat pumps for high temperature heating have been discussed, par- ticularly with reference to suitability of available lubricants to the newly evolved operating conditions. Ó 2006 Elsevier Ltd and IIR. All rights reserved. Keywords: Heat pump; Carbon dioxide; Ammonia; Propane; Isobutane; Research; Thermodynamic cycle; Transcritical cycle; Performance; COP Cycles souscritiques et transcritiques utilisant des frigorige`nes naturels dans les applications a` tempe´rature e´leve´e Mots cle´s : Pompe a` chaleur ; Dioxyde de carbone ; Ammoniac ; Propane ; Isobutane ; Recherche ; Cycle thermodynamique ; Cycle transcritique ; Performance ; COP 1.
    [Show full text]
  • Economizers in Chiller Systems
    Ekaterina Vinogradova T662KA ECONOMIZERS IN CHILLER SYSTEMS Bachelor’s Thesis Building Services Engineering November 2012 DESCRIPTION Date of the bachelor's thesis 17.12.12 Author(s) Degree programme and option Ekaterina Vinogradova Double Degree Programme in Building Services Engineering Name of the bachelor's thesis Economizers in Chiller Systems Abstract There are many buildings that have cooling demands for different purposes. They can be hospitals, administrative and office buildings, shopping centers, data centers and also industrial buildings. Cooling of processes and products, cool rooms, ice halls, and air-conditioning systems require chiller system application. Chiller system is usually the substantial part of energy consumption of the build- ing. That’s why different ways of increasing of the chiller systems efficiency began to be used more often. Due to the widespread use a lot of schemes to optimize and improve the effectiveness of chiller sys- tems have been developed. One possibility is the installation of an additional low-cost equipment like the economizer systems. They may be applied in the refrigeration cycle of the chiller or in the rest chiller system. In the theoretical part of the thesis measures and methods of the chiller systems efficiency increasing and different types of economizers were described. Influencing on the economizers efficiency factors were noted. Study case contains the simulation of the office building in different modes with IDA Indoor Climate and Energy software. Some results of the simulations are presented in the tables. The benefit from the economizer operation is calculated as compared with traditional chiller system. Also influence of the economizer set-point temperature on its benefits was evaluated.
    [Show full text]
  • Performance of a Combined ORC and VCC for Heat Activated
    Performance of a Combined Organic Rankine Cycle and Vapor Compression Cycle for Heat Activated Cooling Hailei Wang*, Richard Peterson, Kevin Harada, Erik Miller, Robbie Ingram-Goble, Luke Fisher, James Yih, Chris Ward School of Mechanical, Industrial, & Manufacturing Engineering 204 Rogers Hall, Oregon State University Corvallis, OR 97331, USA * Corresponding Author Phone: 541-713-1354, Fax: 541-758-9320, Email: [email protected] Abstract Heat activated cooling has the potential of utilizing thermal sources that currently go unused such as engine exhaust heat or industrial waste heat. Using these heat sources can provide enhanced energy utilization and reduced fuel usage in applications where cooling is needed. The concept developed here uses waste heat from stationary and mobile engine cycles to generate cooling for structures and vehicles. It combines an organic Rankine cycle (ORC) with a conventional vapor compression cycle. A nominal 5 kW cooling capacity prototype system was developed based on this concept and tested under laboratory conditions. In order to maintain high system performance while reducing size and weight for portable applications, microchannel based heat transfer components and scroll based expansion and compression were used. Although the system was tested off of its design point, it performed well achieving 4.4 kW of cooling at a measured heat activated COP of 0.48. Both the conversion and 2 nd law efficiencies were close to the model results, proving it to be an attractive technology. The measured isentropic efficiency of the scroll expander reached 84%, when the pressure ratio was close to the scroll intrinsic expansion ratio. The reduced cooling capacity was attributed to off design operation.
    [Show full text]
  • A/C-Heat Pump System Troubleshooting Guide
    A/C-Heat Pump System Troubleshooting Guide Before using this guide: 1) Make sure all filters, blower, and coils are clean. Verify all dampers are open. 2) Identify metering device and refrigerant type. 3) Measure and set required airflow at a nominal 400 CFM/Ton. www.trutechtools.com 4) Determine required suction and liquid pressures using the design temperature difference. (DTD) 1-888-224-3437 5) Test in cooling mode for heat-pumps Typical design Evaporator DTD: (-35 °) @400CFM/Ton (1) Typical design Condenser DTD: 6-8 SEER (+30°), 10-12 SEER (+25°), 13 SEER+ (+20°) Condenser pressures/temperatures will increase with indoor load RA Temp - Evap DTD = Evap Temp Example: 75° RA - 35° DTD = 40° Evap Temp = 68.6 PSIG R22/118 PSIG R410a ODA Temp + Cond DTD = Cond Temp Example: 95° ODA + 25° DTD = 120° Cond Temp = 260 PSIG R22 / 418 PSIG R410a Convert Evap and Cond temps to pressures with Temperature Pressure chart to obtain required pressures System Problem (Fixed) Suction Pressure Liquid Pressure Superheat Subcooling Amps R/H Control Refrigerant Overcharge ↑ ↑ ↓ ↑ ↑ Poor Refrigerant Undercharge ↓ ↓ ↑ ↓ ↓ ICE/Poor Liquid Restriction (Dryer) ↓ ↓ ↑ ↑ ↓ ICE/Poor Low Evaporator Airflow (low load) ↓ ↓ ↓ ↓ ↓ ICE/Normal Dirty Condenser ↑ ↑ ↓ ↓ ↑ Poor Low Outside Ambient Temperature ↓ ↓ ↑ ↑ ↓ ICE/Normal Inefficient Compressor3 ↑ ↓ ↑ ↑ ↓ Poor Non-Condensables ↑ ↑ ↓ Normal6 ↑ Poor System Problem (TXV) Suction Pressure Liquid Pressure Superheat Subcooling Amps R/H Control Refrigerant Overcharge Normal ↑ Normal ↑ ↑ Normal Refrigerant Undercharge Normal2 /↓ ↓ Normal2 /↑ ↓ ↓ ICE/Normal Liquid Restriction (Dryer) ↓ ↓ ↑ ↑ ↓ ICE/Poor Low Evaporator Airflow (low load) ↓ ↓ Normal4 Normal ↓ ICE/Normal Dirty Condenser Normal ↑ Normal Normal ↑ Normal Low Outside Ambient Temperature Normal4 ↓ Normal4 Normal ↓ Normal Inefficient Compressor3 ↑ ↓ ↑ ↑ ↓ Poor TXV Bulb Loose ↑ ↑ ↓ ↓5 ↑ Poor TXV Bulb Lost Charge ↓ ↓ ↑ ↑ ↓ ICE/Poor TXV Bulb Poorly Insulated ↑ ↑ ↓ ↓ ↑ Poor Non-Condensables Normal ↑ Normal4 Normal6 ↑ Poor/Normal Notes: 1) DTD figures are standard design values.
    [Show full text]
  • Llopis Et Al., 2015)
    Document downloaded from: http://hdl.handle.net/10251/99050 This paper must be cited as: Llopis Doménech, R.; Cabello, R.; Sanchez, D.; Torrella Alcaraz, E. (2015). Energy improvements of CO2 transcritical refrigeration cycles using dedicated mechanical subcooling. International Journal of Refrigeration. 55:129-141. doi:10.1016/j.ijrefrig.2015.03.016 The final publication is available at https://doi.org/10.1016/j.ijrefrig.2015.03.016 Copyright Elsevier Additional Information Energy improvements of CO2 transcritical refrigeration cycles using dedicated mechanical subcooling Rodrigo Llopis1,*, Ramón Cabello1, Daniel Sánchez1, Enrique Torrella2 1Jaume I University, Dep. of Mechanical Engineering and Construction, Campus de Riu Sec s/n E-12071, Castellón, Spain 2 Polytechnic University of Valencia, Department of Applied Thermodynamics, Camino de Vera, 14, E-46022, Valencia, Spain *Corresponding author: R. Llopis ([email protected]), Phone: +34 964 72 8136; Fax: +34 964 728106. ABSTRACT In this work the possibilities of enhancing the energy performance of CO2 transcritical refrigeration systems using a dedicated mechanical subcooling cycle are analysed theoretically. Using simplified models of the cycles, the modification of the optimum operating conditions of the CO2 transcritical cycle by the use of the mechanical subcooling are analysed and discussed. Next, for the optimum conditions, the possibilities of improving the energy performance of the transcritical cycle with the mechanical subcooling are evaluated for three evaporating levels (5, -5 and -30 ºC) for environment temperatures from 20 to 35 ºC using propane as refrigerant for the subcooling cycle. It has been observed that the cycle combination will allow increasing the COP up to a maximum of 20% and the cooling capacity up to a maximum of 28.8%, being both increments higher at high evaporating levels.
    [Show full text]
  • Subcooling Methods for CO2 Refrigeration Cycles. a Review. Abstract
    Subcooling methods for CO2 refrigeration cycles. A Review. Rodrigo Llopis*, Laura Nebot-Andrés, Daniel Sánchez, Jesús Catalán-Gil, Ramón Cabello Thermal Engineering Group, Mechanical Engineering and Construction Department, Jaume I University, Spain *Corresponding author: [email protected], +34 964 718136 Abstract CO2 subcooling has resulted a method to upgrade the performance of CO2 refrigeration plants in the recent years, with overall improvements up to 12% with internal heat exchangers, 22% with economizers, 25.6% with thermoelectric systems and 30.3% with dedicated subcooling methods. This paper comprehensively reviews the recent studies that consider subcooling as a way to upgrade the performance of CO2 refrigeration cycles. The review is limited to CO2 refrigeration cycles with accumulation receiver for commercial purposes and does not consider air conditioning or MAC systems. It is organized as follows: first, the thermodynamic aspects of subcooling in CO2 refrigeration cycles are described and discussed; second, the main results and conclusions of the recent investigations are analysed inside two big groups: subcooling internal methods and subcooling external methods. Finally, the review synthesizes the current state of the art and points out the lines of research that deserve future developments. Highlights Research using subcooling as way to improve CO2 refrigeration is analysed. COP improvements up to 37.8% of CO2 base systems have been reported. State-of-the art subcooling systems are presented and discussed New opportunities
    [Show full text]
  • Guide Lines for Checking Super Heat and Sub-Cooling
    Guide Lines for checking Super heat and sub-cooling. These are only for your reference. If you have any questions, or your numbers are off quite a bit please call the Seasons 4 service department. 770-489-0716 and ask for service. Of coarse this is after verifying coils are clean, condenser fans and blowers are operating as they should. And there’s no air restrictions. And keeping in mind the further you get from design conditions, the more the numbers will be affected. All superheat and sub-cooling readings should be taken in the normal AC cycle, hot gas bypass, hot gas reheat coils, compressor unloader(s) should be disabled. **Refrigerant R407C has a large glide pattern. Superheat, pressure to temperature must be read in the vapor or DEW point column, sub-cooling, pressure to temperature must be read in the liquid or BUBBLE column. ** Superheat. Superheat readings are done at the suction filter. Take the pressure at the suction filter, convert to temperature, Measure the temperature at the outlet of the suction filter, subtract the measured temperature from the converted pressure to temperature, the result is superheat at the compressor. We are looking for 20°F at the compressor. With in 5 degrees either way. Sub-Cooling; With out Sub-Cooling coils: Take the pressure at the liquid filter- drier, convert to temperature, and subtract the measured temperature of the liquid line, at the outlet of the drier. We are looking for 10° F. With Sub-Cooling coils located on leaving side of DX coil. Take the pressure at the liquid filter-drier, subtract 5 psig, convert to temperature, and subtract the measured temperature of the liquid line between the sub-cooling outlet, and the inlet to the expansion valve.
    [Show full text]
  • Full Phase Refrigerant Liquid Subcooling As a Mean of Dehumidification & Energy Recovery
    Full Phase Refrigerant Liquid Subcooling as a Mean of Dehumidification & Energy Recovery Marios D. Georgiou, Ph.D. his paper discusses the use of full phase refrigerant liquid subcooling in order Tto meet the dehumidification needs of a conditioned space. The moisture removal efficiency of Addison's new PR series with full phase refrigerant subcooling was esti- mated and presented in the tables that fol- low. The performance with liquid subcooling was also compared against other dehumidifi- cation & energy recovery techniques such as wrap-around heat-pipes. Introduction Liquid refrigerant subcooling is one of the most pop- Figure 1: Full Phase Refrigerant Liquid Subcooling-Air ular and efficient dehumidification design, in a Ded- Reheating icated Outdoor Air System (DOAS), for reducing both sensible and latent loads of the incoming air. The concept is relatively simple, and while in de- • There is no need for a precooling coil. humidification mode the refrigerant exiting the con- denser is rerouted to a reheat coil connected with • The depth of the subcooling coil is less than the condenser and located behind the evaporator as that of the heat pipe. shown in Fig. 1. In this configuration, cooled and dehumidified air This enhanced subcooling results in reducing the exiting the evaporator coil is reheated, and the liquid evaporation temperature and boosting the latent ca- refrigerant is subcooled. The subcooled refrigerant pacity of the system. The system subcooling is only then enters the direct expansion coil, and because it limited by the size of the reheat coil and the air tem- is subcooled the latent and total capacity of the coil perature leaving the evaporator, thus a configuration increases.
    [Show full text]