MECHANICAL CRITERIA CONTROL SYSTEM AND SEQUENCE OF OPERATIONS MECHANICAL ABBREVIATIONS MECHANICAL SYMBOL LIST 1. BEFORE SUBMITTING A PROPOSAL, THE MECHANICAL CONTRACTOR SHALL VISIT THE SITE OF WORK AND FAMILIARIZE SEQUENCES OF OPERATION HIMSELF WITH ALL SITE CONDITIONS. MECHANICAL CONTRACTOR SHALL CAREFULLY EXAMINE ALL CIVIL, ARCHITECTURAL, AFF ABOVE FINISHED FLOOR SUPPLY AIR UP STRUCTURAL, , MECHANICAL AND ELECTRICAL CONSTRUCTION DOCUMENTS. SUBMISSION OF A BID WILL 1. FCU-1 (GAS HEAT, DX COOLING CONSTANT VOLUME) AHJ AUTHORITY HAVING JURISDICTION ACKNOWLEDGE THE MECHANICAL CONTRACTOR HAS VISITED THE SITE AND EXAMINED ALL CONSTRUCTION DOCUMENTS AHU AIR HANDLING UNIT SUPPLY AIR DUCT DOWN AND BID INSTRUCTIONS. THE MECHANICAL CONTRACTOR'S BID SHALL INCLUDE ALL MECHANICAL WORK IN THE OCCUPIED MODE: A.I.P. ABANDON IN PLACE CONSTRUCTION DOCUMENTS, INCLUDING MECHANICAL WORK RELATED TO EQUIPMENT PROVIDED BY OTHERS. OUTDOOR AIR DAMPER OPEN TO SETPOINT AS SCHEDULED AL ALUMINUM RETURN AIR DUCT UP SUPPLY FAN OPERATES CONTINUOUSLY ALT ALTERNATE 2. MECHANICAL CONTRACTOR SHALL REQUEST CLARIFICATION ON ANY ITEM(S) OF THE CONTRACT DOCUMENTS THAT ARE THERMOSTAT SET FOR 70°F (FIELD ADJUSTABLE), UNLESS OTHERWISE DIRECTED BY OWNER. AP ACCESS PANEL RETURN AIR DUCT DOWN NOT UNDERSTOOD OR WHERE CONFLICTS MAY EXIST. CLARIFICATIONS MUST BE PRESENTED AS A "REQUEST FOR AS AIR SEPARATOR INFORMATION" (RFI) IN WRITING PRIOR TO SUBMITTING A BID. RFI SHALL BE PRESENTED A MINIMUM OF FIVE (5) WORKING COOLING: ATC AUTOMATIC TEMPERATURE CONTROL EXHAUST AIR DUCT UP DAYS BEFORE THE BID DATE. OBTAIN THE RFI FORM AT WWW.GANDWENGINEERING.COM/DOCUMENTS. SUBMISSION OF A UPON SIGNAL FROM 7-DAY PROGRAMMABLE THERMOSTAT; ATR ALL THREAD ROD BID WILL ACKNOWLEDGE THE MECHANICAL CONTRACTOR UNDERSTANDS THE SCOPE OF WORK, MEANS AND METHODS OF IF SPACE TEMPERATURE RISES 2°F OR MORE ABOVE SET POINT COOLING IS ENERGIZED ATU AIR TERMINAL UNIT EXHAUST AIR DUCT DOWN INSTALLATION, EQUIPMENT AND MATERIALS TO BE USED. RFI THAT HAVE NOT BEEN CLARIFIED PRIOR TO BID, WILL BE AV MANUAL AIR VENT PROVIDED BY THE MECHANICAL CONTRACTOR, AS DIRECTED BY THE ENGINEER OF RECORD, AND THE MOST STRINGENT HEATING: BB BASEBOARD HEATER CHANGE IN DUCT SIZE MATERIALS, EQUIPMENT, AND SCOPE OF WORK SHALL APPLY. NO ADDITIONAL COMPENSATION WILL BE MADE FOR THE UPON SIGNAL FROM 7-DAY PROGRAMMABLE THERMOSTAT; BDD BACK DRAFT DAMPER FAILURE OF THE CONTRACTOR TO OBTAIN CLARIFICATIONS PRIOR TO BID. IF SPACE TEMPERATURE DROPS 2°F OR MORE BELOW SET POINT HEATING IS ENERGIZED BES BANKING EQUIPMENT SUPPLIER TURNING VANES BFF BELOW FINISHED FLOOR 3. THE MECHANICAL CONTRACTOR'S BID SHALL BE BASED ON THE SCHEDULED EQUIPMENT, MATERIALS, AND UNOCCUPIED MODE: BMS BUILDING MANAGEMENT SYSTEM FLEXIBLE DUCT CONNECTION MANUFACTURERS WHICH FORM THE "BASIS OF DESIGN". ALL OTHER EQUIPMENT, MATERIALS, AND MANUFACTURERS, ARE OUTDOOR AIR DAMPER CLOSED BOD BOTTOM OF DUCT CONSIDERED SUBSTITUTIONS. CONTRACTOR PROPOSED SUBSTITUTIONS MUST BE SUBMITTED TO THE ENGINEER OF SUPPLY FAN OPERATES UPON CALL FOR COOLING OR HEATING BOE BOTTOM OF EQUIPMENT HORIZONTAL LIFE SAFETY DAMPER RECORD FOR REVIEW AND WITH A COMPLETED SUBSTITUTION REQUEST FORM. OBTAIN THIS FORM AT THERMOSTAT SET FOR 80°F COOLING AND 70°F HEATING BOP BOTTOM OF WWW.GANDWENGINEERING.COM/DOCUMENTS. APPROVALS OF SUBSTITUTIONS ARE CONTINGENT UPON ENGINEER'S BS BRANCH SELECTOR - DAIKIN VERTICAL LIFE SAFETY DAMPER REVIEW. THE MECHANICAL CONTRACTOR SHALL MAKE NO PRIOR ASSUMPTIONS ON SUBSTITUTIONS NOT APPROVED BY COOLING: CH CHILLER THE ENGINEER. IF THE ENGINEER APPROVES A SUBSTITUTION REQUEST, THE MECHANICAL CONTRACTOR WILL BE HELD UPON SIGNAL FROM 7-DAY PROGRAMMABLE THERMOSTAT; CLG CEILING M MOTORIZED AUTOMATIC DAMPER (MAD) RESPONSIBLE FOR ENGINEERING REVISIONS, PHYSICAL SIZE, CAPACITIES, COORDINATION, SUPPLEMENTAL DRAWINGS IF SPACE TEMPERATURE RISES 2°F OR MORE SET POINT COOLING IS ENERGIZED CO CARBON MONOXIDE AND INFORMING OTHER TRADE CONTRACTORS RELATED TO THE INSTALLATION, AS TO ANY SPECIFIED ITEM CHANGES. THE CO2 CARBON DIOXIDE MANUAL DAMPER MECHANICAL CONTRACTOR SHALL BEAR AS PART OF HIS CONTRACT, ANY ADDITIONAL COSTS INCURRED IN HIS WORK OR HEATING: CR CONDENSER WATER RETURN BY THE OTHER CONTRACTORS AS A RESULT OF INSTALLATION FOR OTHER THAN "BASIS OF DESIGN" MATERIALS AND UPON SIGNAL FROM 7-DAY PROGRAMMABLE THERMOSTAT; CRAC COMPUTER ROOM AIR CONDITIONER F CARBON DIOXIDE DETECTOR CO 2 EQUIPMENT. IF SPACE TEMPERATURE DROPS 2°F OR MORE BELOW SET POINT HEATING IS ENERGIZED CRCU COMPUTER ROOM CONDENSING UNIT CS CONDENSER WATER SUPPLY F CARBON MONOXIDE DETECTOR CO 4. SHOP DRAWINGS SHALL BE SUBMITTED ELECTRONICALLY AS PDF FILES. SHOP DRAWINGS SHALL INCLUDE TRANSMITTAL 2. EF-B WITH MOTORIZED DAMPER CSST CORRUGATED STAINLESS TUBING PAGE(S) INDICATING THE NAME OF THE PROJECT, AND THE NAME, ADDRESS, AND PHONE NUMBER OF THE GENERAL AND CT COOLING TOWER H HUMIDISTAT MECHANICAL CONTRACTORS. GENERAL CONTRACTOR AND MECHANICAL CONTRACTOR SHALL REVIEW SHOP DRAWING EXHAUST FAN OPERATES UPON SIGNAL FROM TIMED OVER-RIDE AND/OR CO DETECTOR (FIELD ADJUSTABLE), CU CONDENSING UNIT SUBMITTALS FOR COMPLIANCE, CONTENT AND COMPLETENESS AND PROVIDE A STAMP WITH THE DATE OF REVIEW AND SEE ELECTRICAL DRAWINGS FOR CO AND TIMER INFORMATION. MOTORIZED DAMPERS TO BE WIRED TO BE CUH CABINET UNIT HEATER M MANOMETER SIGNATURE OF THE REVIEWER. TRANSMITTAL PAGE SHALL HAVE INDEX WITH SPECIFICATION SECTION AND DESCRIPTION NORMALLY OPEN (SPRING OPEN, POWER CLOSED). DAMPERS ARE TO BE INTERLOCKED WITH CO DETECTOR DDC DIRECT DIGITAL CONTROL OF SUBMITTED ITEMS. NO EXCEPTIONS WILL BE TAKEN. SHOP DRAWINGS NOT SUBMITTED IN THIS FORMAT WILL BE PS AND SHALL OPEN UPON SIGNAL FROM CO DETECTOR. TIMER SHALL ALSO ENABLE DAMPER AND FAN, BUT DIFF DIFFUSER PRESSURE SWITCH REJECTED AND WILL NOT CAUSE REASON FOR PROJECT DELAYS. EQUIPMENT SHALL NOT BE ORDERED UNTIL ENGINEER SHALL NOT INTERFERE WITH CO MONITORING SYSTEM. DISC DISCONNECT OF RECORD HAS PROCESSED APPLICABLE SHOP DRAWINGS. A MINIMUM OF SEVEN WORKING DAYS WILL BE ALLOWED FOR DLSS DUCTLESS SPLIT SYSTEM F RETURN AIR SMOKE DETECTOR SUBMITTAL PROCESSING BY THE ENGINEER. REFER TO PROJECT MANUAL FOR ADDITIONAL REQUIREMENTS. 3. FAI-1 MOTORIZED DAMPER DN DOWN DPS DIFFERENTIAL PRESSURE SWITCH F REFRIGERANT (Rxxx) DETECTOR 5. MECHANICAL CONTRACTOR SHALL PERFORM WORK IN A SAFE MANNER. COMPLY WITH APPLICABLE OSHA SAFETY REF MOTORIZED DAMPERS TO BE WIRED TO BE NORMALLY OPEN (SPRING OPEN, POWER CLOSED). DAMPERS ARE (E) EXISTING GUIDELINES DURING THE COURSE OF COMPLETING THE WORK DESCRIBED ON THESE CONSTRUCTION DOCUMENTS. EA TO BE INTERLOCKED WITH EF-B AND OPEN WHEN EF-B IS ENABLED. EXHAUST AIR EBB ELECTRIC BASE BOARD T THERMOSTAT 6. PROVIDE ALL REQUIRED INSPECTIONS AND RE-INSPECTIONS. PROVIDE A SIGNED CERTIFICATE OF INSPECTION AT THE EC ELECTRICAL WORK CONTRACTOR PROJECT COMPLETION. EF EXHAUST FAN A PIPE/DUCT IN ATTIC EG EXHAUST GRILLE 7. ALL ITEMS OF WORK AND MATERIALS SHALL BE SPECIFICALLY INSTALLED PER WRITTEN INSTALLATION INSTRUCTIONS AND EMS ENERGY MANAGEMENT SYSTEM B PIPE/DUCT BELOW FLOOR OR GRADE METHODS OF INSTALLATION AS PROVIDED BY THE MANUFACTURER OF THE EQUIPMENT OR MATERIAL PROVIDER. EQPT EQUIPMENT MECHANICAL CONTRACTOR SHALL UNDERSTAND THE PRODUCT AND METHODS OF INSTALLATION. THE CONTRACTOR ER EXHAUST REGISTER C PIPE/DUCT ABOVE CEILING SHALL OBTAIN THE INSTALLATION INSTRUCTIONS AND REQUIREMENTS PRIOR TO BID. ALL REQUESTS FOR ADDITIONAL ERV ENERGY RECOVERY VENTILATOR INFORMATION DURING CONSTRUCTION WHERE THE CONTRACTOR HAS NOT PREVIOUSLY OBTAINED THIS INFORMATION PIPE & TUBING SUPPORT SPACING SCHEDULE ET EXPANSION TANK E EXPOSED DUCT, W/ MILL PHOSPHATIZED FINISH FOR BIDDING PURPOSES WILL NOT BE CAUSE FOR ADDITIONAL COSTS OR CONSTRUCTION DELAY. EUH ELECTRIC UNIT HEATER NOMINAL PIPE SIZE (IN.) < 1/2 1/2 3/4 1 1-1/2 2 3 4 5 6 8 10 12 14 16 18 20 24 EWC ELECTRIC WATER COOLER R PIPE/DUCT ON ROOF 8. SYSTEMS AS SHOWN ARE DIAGRAMMATIC AND GIVE THE GENERAL ARRANGEMENT ONLY. EXACT LOCATIONS SHALL BE MAXIMUM SUPPORT PIPE 7 7 7 9 10 11 12 14 1617 19 2223 25 27 2830 32 EWH ELECTRIC WATER HEATER NEW CONNECTION TO EXISTING (VERIFY SIZE SPACING (FT.) TUBING 56 7 8 8 9 10 12 1314 16 ------DETERMINED IN THE FIELD ON THE BASIS OF DETAIL DRAWINGS, REVIEWED DRAWINGS, AND SUPPLEMENTARY EXH EXHAUST AND LOCATION IN FIELD PRIOR TO BID) INFORMATION. INSTALLATION SHALL PROVIDE FOR OPERATING EFFICIENCY, NEATNESS OF APPEARANCE AND EASE OF NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE. FA FIRE ALARM MAINTENANCE. IT IS EXPECTED THAT THE CONTRACTOR WILL PREPARE DIMENSIONED FIELD ERECTION DRAWINGS AND FAAP FIRE ALARM ANNUNCIATOR PANEL NEW BRANCH DUCT TAP & CONNECTION N WORK SKETCHES FOR USE BY THEIR MECHANICS, TO ENSURE PROPER INSTALLATION AND COORDINATION. THE FACP FIRE ALARM CONTROL PANEL TO EXISTING MECHANICAL CONTRACTOR SHALL TAKE THEIR OWN MEASUREMENTS AT THE BUILDING, AND BE RESPONSIBLE FOR THE FC FLEX CONNECTION # DUCT INSULATION (SEE SCHEDULE) CORRECT INTERPRETATION AND USE OF ALL SIZES AND DIMENSIONS. INSULATION HANGER FCU ROD FAN COIL UNIT FD FIRE DAMPER XX XX XX PLAN NOTE SYMBOL 9. CAST IRON NO-HUB, OR BLACK IRON PIPE IS REQUIRED ABOVE CEILINGS OR IN CAVITIES USED AS PROVIDE INSULATION FPC FIRE PROTECTION CONTRACTOR ENVIRONMENTAL AIR PLENUM; NO PVC WILL BE ALLOWED IN RETURN AIR PLENUM SPACES. REFER TO SHIELD AND INSERT FRT FIRE-RETARDANT-TREATED X REVISION SYMBOL ARCHITECTURAL, MECHANICAL OR PLUMBING DRAWINGS OR VERIFY AT SITE, ALL RETURN AIR PLENUM LOCATIONS. WELD FOR ALL PIPING, 8" FSC ADJUSTABLE, MAXIMUM. FOOD SERVICE CONSULTANT SWIVEL ROLLER XX PIPE FSD FIRE/SMOKE DAMPER EQUIPMENT CALLOUT (SEE SCHEDULE) SADDLE HANGER,. SEE SPECS XX 10. THE CONTRACTOR SHALL KEEP "AS-BUILT" INFORMATION DURING CONSTRUCTION AND FURNISH TO THE OWNER OR INSULATION FSEC FOOD SERVICE EQPT. CONTRACTOR TENANT A RECORD SET OF LEGIBLE BLACK LINE PRINTS AND AN ELECTRONIC COPY OF THESE DOCUMENTS AT THE BAND FTU FAN TERMINAL UNIT XX XX GRILLE/DIFFUSER CALLOUT (SEE SCHEDULE) PROJECT COMPLETION. ADJUSTABLE ROLLER HANGER FV FIELD VERIFY TYPE 43 IN SPECIFICATIONS GC GENERAL WORK CONTRACTOR XX LIFE SAFETY DAMPER CALLOUT (SEE SCHEDULE) 11. ALL MECHANICAL WORK SHALL BE DONE UNDER THE SUPERVISION OF THE MECHANICAL CONTRACTOR, WHO SHALL GF GAS FURNACE PROVIDE A COMPETENT AND SKILLED FOREMAN TO LAYOUT ALL WORK. ALL WORK SHALL BE PROVIDED WITH DUE REGARD HANGER GWH GAS WATER HEATER EXISTING DUCT TO REMAIN FOR THE SPACE REQUIREMENTS OF THE OTHER CONTRACTORS. THE MECHANICAL CONTRACTOR SHALL REPORT ANY ROD 3/8" DIA. HANGER HP HEAT PUMP INSULATION (VAPOR RODS WITH 36" EXISTING TO BE DEMOLISHED CONFLICTS OR DIFFICULTIES IN REGARD TO THE INSTALLATION IMMEDIATELY TO THE GENERAL CONTRACTOR OR BARRIER TYPE MAX. SPACING HP HORSEPOWER CONSTRUCTION MANAGER. WHERE CROWDED LOCATIONS EXIST, OR WHERE THERE IS A POSSIBILITY OF CONFLICT REQUIRED FOR LOW ON EACH. TEMP. PIPE). HRCU HEAT RECOVERY CONDENSING UNIT BETWEEN TRADES, THE MECHANICAL CONTRACTOR SHALL MAKE COMPOSITE SUPPLEMENTARY DRAWINGS SHOWING THE HWCP HOT WATER CIRC. PUMP EXACT LOCATIONS OF PIPES, CONDUIT, DUCTS AND EQUIPMENT. DRAWINGS SHALL BE BASED ON FIELD MEASUREMENTS PROVIDE HIGH COMPRESSIVE HX STRENGTH INSULATION BLOCKS 1" 2 GAGE MECHANICAL PIPING AND, AFTER CONSULTATION AND AGREEMENT AMONG THE TRADES, THE GENERAL CONTRACTOR OR CONSTRUCTION UNDER INSULATION SHIELD. CHANNEL OR IAH INTAKE AIR HOOD 2" x 2" x 1" MANAGER SHALL DIRECT THE SOLUTION BEFORE INSTALLATION OF THE WORK. ANGLE. IOM INSTALLATION & OPERATION MANUAL A COMPRESSED AIR LINE INSULATION SHIELD AT HANGER. 1" MAX. ID INSIDE DIAMETER 12. REVIEW ARCHITECTURAL DRAWINGS FOR ALL FIRE RATINGS AND FIRE RATED ASSEMBLIES PRIOR TO BIDDING THE IR INFRA-RED HEATER (GAS) CD CONDENSATE DRAIN TRAPEZE HANGER FOR UP TO 1000 lb. PROJECT. PROVIDE FIRE STOP AT EACH RATED WALL, FLOOR, ROOF AND CEILING ASSEMBLY PENETRATION. FIRE STOP IV INTAKE VENTILATOR CD CONDENSATE DRAIN BELOW FLOOR OR GRADE ADJUSTABLE CLEVIS HANGER UNIFORM LOAD SYSTEMS SHALL BE MANUFACTURED BY "3M". PROVIDE IN STRICT COMPLIANCE WITH THE MANUFACTURER'S APPLICATION KEF KITCHEN EXHAUST FAN TYPE 1 IN SPECIFICATIONS CR CONDENSER WATER RETURN DETAILS AND INSTRUCTIONS. PROVIDE TAGGED CERTIFICATIONS AT EACH PENETRATION. PROVIDE SHOP DRAWINGS FOR LLSV LINE SOLENOID VALVE REVIEW WITH THE U.L. LISTING AND TEST CRITERIA. PROVIDE FIRE STOPPING WHERE REQUIRED BY THE AUTHORITY LV LOUVER CS CONDENSER WATER SUPPLY HAVING JURISDICTION. EQUAL SYSTEMS AS MANUFACTURED BY "SPEC SEAL" OR "HILTI" WILL BE ACCEPTABLE. REFER TO LPG LIQUIFIED PETROLEUM GAS (PROPANE) CHR CHILLED & HOT WATER RETURN THE PROJECT MANUAL FOR SYSTEMS SPECIFICATIONS. MAX MAXIMUM 1 PIPE HANGER DETAILS MC MECHANICAL WORK CONTRACTOR CHS CHILLED & HOT WATER SUPPLY M0.0 NO SCALE 13. PROVIDE DUCT OR PIPING ASSEMBLY PENETRATIONS OF NON-RATED ASSEMBLIES WITH DRAFT STOPPING, OR SMOKE MCA MINIMUM CIRCUIT AMPERES CWR CHILLED WATER RETURN BARRIER SYSTEMS. THROUGH PENETRATION SEALANT SYSTEMS SHALL BE MANUFACTURED BY "3M". APPLY IN MCC MOTOR CONTROL CENTER STRICT COMPLIANCE WITH THE MANUFACTURER'S APPLICATION DETAILS AND INSTRUCTIONS. PROVIDE DRAFT STOPPING MD MANUAL DAMPER CWS CHILLED WATER SUPPLY OR SMOKE BARRIER TO MEET APPROVAL OF THE AUTHORITY HAVING JURISDICTION. EQUAL SYSTEMS AS MIN MINIMUM D DRAIN LINE MANUFACTURED BY "SPEC SEAL" OR "HILTI" WILL BE ACCEPTABLE. 3/8" A.T.R. WITH VIBRATION MH MOUNTING HEIGHT G GAS LINE ISOLATORS, TYP., ATTACH MOCP MAXIMUM OVER CURRENT PROTECTION 14. HVAC WORK SHALL COMPLY WITH THE LOCAL ADOPTED MECHANICAL CODE AS WELL AS GOVERNING STATE LAW AND TO STRUCTURE MTD MOUNTED HPC HIGH PRESSURE CONDENSATE LOCAL ORDINANCES. ALL NEW MECHANICAL EQUIPMENT, DUCTWORK AND PIPING SHALL BE ANCHORED AND SEISMICALLY MUA MAKE-UP AIR HWR HOT WATER RETURN RESTRAINED WHERE REQUIRED TO COMPLY WITH THE 2015 INTERNATIONAL MECHANICAL CODE AND FUEL GAS CODE. BACKDRAFT DAMPER MUW MAKE UP WATER NC NORMALLY CLOSED HPS HIGH PRESSURE STEAM 15. MECHANICAL CONTRACTOR SHALL CUT AND PATCH ROOF, FLOORS, WALLS, AND CEILINGS WHERE REQUIRED TO INSTALL NIC NOT IN CONTRACT EXTEND TO ROOF HWS HOT WATER SUPPLY NEW MECHANICAL DUCT AND PIPING SYSTEMS. SURFACES SHALL BE PATCHED AND LEFT READY FOR FINAL SCHEDULED VENTILATOR, SEE PLAN NO NORMALLY OPEN FINISH. ROOFING REPAIRS SHALL MAINTAIN THE ROOF WARRANTY AND BE PERFORMED BY A QUALIFIED ROOFING OA OUTDOOR AIR RL REFRIGERANT LIQUID LINE CONTRACTOR WHICH MAINTAINS THE WARRANTY OF THE ROOF. CEILING FAN OD OUTSIDE DIAMETER RS REFRIGERANT SUCTION LINE OX OXYGEN 16. MECHANICAL CONTRACTOR SHALL PROVIDE ALL TEMPERATURE CONTROL WIRING, INCLUSIVE OF ALL VOLTAGES, NO PC PLUMBING WORK CONTRACTOR EXCEPTIONS OR EXCLUSIONS. ALL COMPONENTS SHALL BE NEW UNLESS NOTED OTHERWISE. TYPICAL SPACE DISCHARGE DUCT WITH PCF POUNDS/CUBIC FOOT MECHANICAL PIPING SYMBOLS THERMOSTAT OR SENSOR MOUNTING HEIGHT SHALL BE 48" A.F.F. COORDINATE ACTUAL THERMOSTAT OR SENSOR FLEX CONNECTOR PSG PUMP SUCTION GUIDE MOUNTING WITH FINAL ARCHITECTURAL FLOOR AND FURNITURE PLANS. DO NOT MOUNT THERMOSTATS OR SENSORS IN PT PRESSURE TREATED AUTOMATIC AIR VENT (AAV) DIRECT SUNLIGHT, NEAR HEAT SOURCES, OR ON EXTERIOR WALLS. IF THERMOSTAT MUST BE MOUNTED ON AN EXTERIOR PVC AUTOMATIC FLOW CONTROL VALVE WALL, PROVIDE INSULATED MOUNTING BASE. ALL SYSTEMS SHALL BE COMPLETE INCLUDING, BUT NOT LIMITED TO: CEILING RA RETURN AIR EXPERTISE, DESIGN, EQUIPMENT, CABINETS, BOXES, RELAYS, SWITCHES, CONTACTORS, TRANSFORMERS, WIRING, RAH RELIEF AIR HOOD AUTOMATIC TEMPERATURE CONTROL RACEWAYS, AND ELECTRICAL ACCESSORIES. WIRING EXPOSED IN RETURN AIR PLENUM SHALL BE PLENUM RATED CABLE. GRILLE RF RETURN FAN VALVE (3-WAY) PROVIDE SHOP DRAWINGS FOR REVIEW AND PROCESSING. THE SHOP DRAWINGS SHALL CONTAIN A FLOOR PLAN WITH RG RETURN GRILLE AUTOMATIC TEMPERATURE CONTROL THERMOSTAT LOCATIONS, CONTROL SEQUENCE STATEMENT, AND WIRING DIAGRAM WITH ALL PARTS INDICATED OR A BILL 2 CEILING EXHAUST FAN RL EXISTING DEVICE RELOCATED VALVE (2-WAY) OF MATERIAL. RR RETURN REGISTER M0.0 BALL VALVE (BV) NOT TO SCALE RTU ROOF TOP UNIT 17. THE MECHANICAL CONTRACTOR SHALL PROTECT ALL DUCT SYSTEMS, PIPING AND MECHANICAL EQUIPMENT EXPOSED TO RV RELIEF VENTILATOR CHECK VALVE (CV) CONSTRUCTION, FROM CONSTRUCTION DIRT. PROTECT EACH RETURN AIR DUCT OPENING OF MECHANICAL EQUIPMENT SA SUPPLY AIR CIRCUIT SETTER (CS) OPERATED DURING CONSTRUCTION WITH MERV 8 FILTERS AND INSTALL MERV 8 FILTER(S) IN EQUIPMENT FILTER RACK. SF SUPPLY FAN UPON COMPLETION OF CONSTRUCTION, REMOVE RETURN DUCT FILTERS AND REPLACE EQUIPMENT FILTERS WITH NEW SG SUPPLY GRILLE CONCENTRIC PIPE REDUCER 06-21-2017 FILTERS AS SPECIFIED. SMS SHEET SCREW ECCENTRIC PIPE REDUCER SS TA TRANSFER AIR FLEXIBLE PIPE CONNECTION TEMP TEMPORARY GAS SHUT-OFF VALVE (SOV) TYP TYPICAL UH UNIT HEATER GATE VALVE (GT. V.) UON UNLESS OTHERWISE NOTED GEAR OPERATED BUTTERFLY VALVE UNV UNIVERSAL UTR UP THROUGH ROOF GLOBE VALVE (GL. V.) VAV VARIABLE AIR VOLUME END VALVE VFD VARIABLE FREQUENCY DRIVE VRF VARIABLE REFRIGERANT FLOW MANUAL AIR VENT (MAV) VRV VARIABLE REFRIGERANT VOLUME PRESSURE REDUCING VALVE (PRV) VSD VARIABLE SPEED DRIVE W/ WITH STRAINER (STR) WP WEATHERPROOF STRAINER WITH BLOWDOWN WSHP WATER SOURCE HEAT PUMP XFMR TRANSFORMER TRIPLE DUTY VALVE (TDV) M WATER METER HANGER STRUCTURE * TITUS LOAD RATED GRILLE, REGISTER, AND DIFFUSER SCHEDULE ** HART & COOLEY NOT REQUIRED FOR FASTENERS PAIR SPACING: 10 FT. 8 FT. 5 FT. 4 FT. DUCTWORK WITH LESS PLAN MODEL NO. NECK SIZE FACE SIZE MAX P.D. BORDER PATTERN FINISH NOTES THAN 6 SQ. FT. DUCT PERIMETER, MARK CFM HANGER STRAPS WIRE/ WIRE/ WIRE/ WIRE/ 12" CROSS-SECTIONAL AREA MAXIMUM HALF (SEE CHART) STRAP STRAP STRAP STRAP MAX. ROD ROD ROD ROD SA *301RL 10"x4" 12"x6" 50 0.1 TYPE 1 2-WAY #26 1, 2, 3 60 in. MAX. UNLESS FOOT OF IN. x GA IN. x GA IN. x GA IN. x GA SB *301RL 12"x4" 14"x6" 85 0.1 TYPE 1 2-WAY #26 1, 2, 3 STRAP IS PLACED P/2 = 30" 10 GA 10 GA 12 GA 12 GA UNDER A BOTTOM 1 x 22 1 x 22 1 x 22 1 x 22 SC *301RL 12"x6" 14"x8" 150 0.1 TYPE 1 2-WAY #26 1, 2, 3 36"Ø MAX. (.135") (.135") (.106") (.106") REINFORCEMENT 24"Ø MAX. SD **210 14"x4" 16"x6" 95 0.1 TYPE 1 2-WAY #26 1, 2, 3 P/2 = 72" 1 x 18 3/8" 1 x 20 1/4" 1 x 22 1/4" 1 x 22 1/4" SE **210 12"x6" 14"x4" 150 0.1 TYPE 1 2-WAY #26 1, 2, 3 P/2 = 96" 1 x 16 3/8" 1 x 18 3/8" 1 x 20 3/8" 1 x 22 1/4" P/2 = 120" 1.5 x 16 1/2" 1 x 16 3/8" 1 x 18 3/8" 1 x 20 1/4" SF *S300FS 10"x4" 12"x6" 50 0.1 TYPE 1 2-WAY #26 1, 2, 3 BAND OF SAME SIZE AS P/2 = 168" 1.5 x 16 1/2" 1.5 x 16 1/2" 1 x 16 3/8" 1 x 18 3/8" HANGER STRAP 1 in. SCREWS P/2 = 192" NONE 1/2" 1.5 x 16 1/2" 1 x 16 3/8" 1 x 16 3/8" RA **265 14"x4" 16"x6" 150 - TYPE 1 - #26 2, 3 MIN. P/2 = 193"+ SPECIAL ANALYSIS REQUIRED RB *50F 24"x6" 26"x8" 350 - TYPE 1 - #26 2, 3 BAR JOIST OR OTHER SINGLE HANGER MAXIMUM ALLOWABLE LAP JOINED STRAPS, MINIMUM RC *50F 18"x12" 20"x14" 500 - TYPE 1 - #26 2, 3 STRUCTURAL WOOD STRUCTURAL LOAD FASTENERS (PLACE FASTENERS IN RD *33RS 42x20" 44"x22" 3100 - TYPE 1 - #26 2, 3 COMPONENT FRAMING OR SERIES, NOT SIDE BY SIDE): *50F BLOCKING WIRE/ STRAP FASTENERS RE 42"x18" 44"x20" 3100 - TYPE 1 - #26 2, 3 STRAP WEIGHT ROD WEIGHT IN. x GA (QTY) - SIZE NOTES: 1. PROVIDE WITH OPPOSED BLADE BALANCING DAMPER. IN. x GA LBS. Ø (IN.) LBS. (2) - #10 SMS or GALVANIZED SHEET GYP. BD. 1 x 18, 20, 22 2. MECHANICAL CONTRACTOR TO VERIFY CEILING CONSTRUCTION WITH ARCHITECT AND ENSURE THAT IT IS COMPATIBLE WITH 1 x 22 260 0.106 80 (1) - 1/4"Ø BOLT METAL STRAP GRILLE, REGISTER, AND DIFFUSER FRAMING, INCLUDING BORDER TYPES, T-BARS, AND CROSS NOTCHES. 1 x 20 320 0.135 120 1 x 16 (2) - 1/4"Ø BOLT 3. FACTORY FINISH TO MATCH EITHER FLOORING (BROWN OR GREY), WALL (WHITE), OR CEILING (WHITE) COLOR. STRAP 1 x 18 420 0.162 160 1.5 x 16 (2) - 3/8"Ø WASHER 1 x 16 700 1/4 270 WASHER LOAD RATED NUT SHEET METAL 1.5 x 16 1100 3/8 680 SCREW 1/2 1250 EXHAUST FAN SCHEDULE * LOREN COOK W/WASHER 5/8 2000 WASHERS MAY BE OMITTED WITH 100 1-1/2" x #8 SMS WITH PLAN E.S.P. HP 3/4 3000 CFM RPM DRIVE SONES WEIGHT V/PH/HZ NOTES LB MAX LOAD ON 22 GA STRAP WHEN WASHER MARK MODEL NO. * (IN. WG) (WATT) FOLDED NOTE: TABLE ALLOWS FOR DUCT WEIGHT, 1 LB./SQ. FT. INSULATION WEIGHT, AND NORMAL REINFORCEMENT AND TRAPEZE WEIGHT. EF-A *GC-122 50 .375 (46) 800 DIRECT 1.9 14.0 120/1/60 1 EF-B *150HLC15D 3100 .375 3/4 HP 1550DIRECT 27.0 190.0 120/1/60 2 1 DUCT HANGER DETAILS NOTES: 1. FURNISH FAN WITH FACTORY MOUNTED DISCONNECT, FAN SPEED CONTROLLER, BACKDRAFT DAMPER, ISOLATOR KIT, AND M0.1 NO SCALE ALUMINUM GRILLE. FAN SPEED CONTROLLER FURNISHED BY M.C., INSTALLED BY E.C. COORDINATE PRIOR TO CONSTRUCTION. 2. MOTORIZED BACKDRAFT DAMPER, EXHAUST FAN TO BE INTERLOCKED WITH FAI-1.

PROVIDE A MINIMUM OF 18" FROM GAS METER EXTERIOR RATED STAINLESS SIZE PER PLANS CONDENSING UNIT SCHEDULE (OWNER FURNISHED) * CARRIER STEEL/JACKETED FLEXIBLE GAS COOLING EFFICIENCY SPIN IN WITH NO DAMPER CSST PIPE AS A FINAL PLAN MODEL NO. * VOLTS/ MCA/ WEIGHT NOTES SHUT-OFF TOTAL AMBIENT EER SEER MAIN DUCT CONNECTION TO EQUIPMENT. MARK PH MOCP INSULATED FLEXIBLE DUCT VALVE GAS PIPE SHALL COMPLY WITH (MBH) (°F) (MIN) (8' MAX. LENGTH) NATIONAL FUEL GAS CODE ANSI CU-1 *24VNA960A003 56.71 93.2° 10 16 208/1 40/60 282 1,2,3 PRESSURE TAPS MIN. 10 Z223.1 AND NFPA 54. 90 ADJUSTABLE ELBOW PULL FLEX PIPE DIAMETERS NOTES: 1. REFRIGERANT PIPING SHALL BE INSTALLED PER EQUIPMENT MANUFACTURER'S RECOMMENDATIONS. INSULATION OVER ELBOW TO GRILLE 2. PROVIDE UNIT WITH LOW AMBIENT CONTROL. G CONNECTION, SEAL WITH TIE WRAP. 3. PROVIDE UNIT WITH 50FT PRE-INSULATED LINESET, LIQUID LINE SITE , 3FT SAMPLING TUBE, CONNECT WITH SHEET METAL AND HEAT PUMP FEET. SCREWS 4 LOCATIONS AT COLLAR. 1" 3 PCF DENSITY LINER G

DIRT LEG 6" OPPOSED BLADE DAMPER UNION TO EQUIPMENT FURNACE AND DX COIL SCHEDULE (OWNER FURNISHED) * CARRIER MIN GRILLE NECK SIZE PER SCHEDULE CONNECTION SIZE PER PLAN CFM O.A. E.S.P. COOLING CAP. (MBH) HEATING CAP. (MBH) NOTE: MANUFACTURER'S MODEL NO. * VOLTS/ MCA/ NOTES MARK CFM IN & FITTINGS TO BE DATA TTL/SENS INPUT OUTPUT PH MOCP SURFACE MOUNTED DIFFUSER PER SCHEDULE CAP LOCATED WITHIN 6'-0" OF EQUIPMENT CONNECTION. FCU-1 *59MN7A100V21 / *CNPVP6024ALA 2000 150 0.5 56.71/39.02 100 98 120/1 14.8/20 1 NOTES: 1. PROVIDE AND INSTALL HUMCCLBP24LBP CARRIER HUMIDIFIER WITH HUMIDISTAT, SURFACE MOUNTED CEILING SYSTXCCITCO1-A WIFI THERMOSTAT, SMOKE DETECTOR, AND CONCENTRIC VENT KIT. 2 DIFFUSER AND BRANCH DUCT 3 GAS PIPING CONNECTION DETAIL M0.1 M0.1 NO SCALE NO SCALE INFRARED UNIT HEATER SCHEDULE * RE-VERBER-RAY

HEATING CAP. (MBH) PLAN MODEL NO. * VOLTS/PH MCA NOTES MARK INPUT OUTPUT EXTRUDED ALUMINUM IUH-1 *HL3-40-100 100 80 120/1 4.8 1 ROOF VENTILATOR NOTES: 1. PROVIDE WITH HANGING KIT PER MANUFACTURER'S SPECIFICATIONS.

PIPE FULL SIZE OF UNIT DRAIN CONNECTION INSULATED NOTES: PREFABRICATED INTAKE SCHEDULE * LOREN COOK SLOPED ROOF CURB REMOVABLE CAP 1. LOCATE TRAPS SO AS TO BE BY FAN MANUF. (SECURE NAILER BY CURB MFR. ACCESSIBLE FOR CLEANING. PLAN HOOD AREA HOOD AREA MAX TO PLYWOOD DECK WITH MODEL NO. * THROAT SIZE FINISH P.D. NOTES MARK (SQ. FT.) VEL FPM CFM SCREWS UNDER SHINGLES) 2. HEIGHT SHALL BE EQUAL TO FAN STATIC PRESSURE, PLUS 1". FAI-1 *18X42X3TRE 18"x42" CLEAR ANODIZED 6.42 483 3100 0.17 1,2 REMOVABLE CAP 3. TERMINATE CONDENSATE LINE NOTES: 1. FURNISH AND INSTALL UNIT WITH AN 14" SLOPED ROOF CURB AND BIRDSCREEN. VIA INDIRECT CONNECTION TO 2. PROVIDE MOTORIZED DAMPER INTERLOCKED WITH EF-B. 2" NEAREST: FLOOR DRAIN. 4" BATT INSULATION FLOW PLYWOOD 4. VERIFY MFR. REQUIREMENT ROOF DECK FOR P-TRAP, UNIT MAY CONTAIN KITCHEN HOOD SCHEDULE * BROAN INTERNAL TRAP. SEE DRAWING 4" BATT INSULATION FOR DUCT SIZE SEE PLAN MODEL NO* CFM P.D. FLA VOLTS/PH NOTES MOTORIZED DAMPER 45° NOTE 2 5. PROVIDE MINIMUM 2" AIR GAP @ MARK DRAIN TERMINATION

2" AIR GAP HD-1 AP130 440 0.05 2 120 / 1 1 EQUIPMENT CABINET NOTES: 1. PROVIDE WITH ROOF JACK, COORDINATE COLOR WITH ARCHITECT.

4 INTAKE VENTILATOR DETAIL 5 COOLING EQUIPMENT CONDENSATE DRAIN TRAP M0.1 NO SCALE M0.01 NO SCALE DUCT INSULATION SCHEDULE MATERIAL FIELD VAPOR THICK- NO. OF BTU.IN IB ID TAG K AT 75 F. FORM R-VALUE APPLIED RETARDER H.SQ.FT.F D 3 NESS LAYERS FT ROOF JACKET REQUIRED VENTILATOR MINERAL-FIBER BLANKET N/A 2" ONE FOIL & PAPER YES 2 (0.27/1.0) 7.4

INSULATED PREFABRICATED LINER NAILER BY CURB MFR. 3 N/A 1" 4.2 ONE NONE YES SLOPED ROOF CURB BY (0.24/1.5) VENTILATOR MANUFACTURER VERIFY PITCH WITH (SECURE TO PLYWOOD DECK WITH ARCHITECTURAL PLANS GENERAL NOTE: DUCT SIZES INDICATED ON DRAWINGS ARE SHEET METAL SIZE AND INCLUDE LINER SPECIFIED. SCREWS UNDER SHINGLES) 06-21-2017

4" BATT INSULATION

PLYWOOD ROOF DECK ROOF LINE MOTORIZED DAMPER

6 ROOF VENTILATOR DETAIL M0.1 NO SCALE (ON ROOF) FAI 1 6 GENERAL NOTES - MECHANICAL CLOSET A. OFFSETS AND TRANSITIONS ARE TO BE PROVIDED FOR COORDINATION 119 WITH OTHER SYSTEMS AND THE BUILDING STRUCTURE.

RE B. COORDINATE DUCTWORK DROPS WITH STRUCTURAL COMPONENTS. - C. EQUIVALENT AREA DUCTS AND MODIFICATIONS TO LAYOUT ARE ACCEPTABLE BASED ON FIELD CONDITIONS AND COORDINATION.

6"Ø INTAKE D. PRIOR TO THE START OF CONSTRUCTION, THE MECHANICAL WITH CAP CONTRACTOR SHALL COMPLETELY REVIEW AND CONFIRM THE 5 INTENDED RETURN AIR PATH TO MECHANICAL EQUIPMENT IS OPEN AND WILL BE FUNCTIONAL. CONFIRM AGAIN, PRIOR TO THE AIR BALANCE OF IUH 9 THE MECHANICAL SYSTEM. 1 E. COORDINATE LOCATION AND SUPPORTS OF MECHANICAL UNITS WITH OTHER TRADES. 6"Ø

WITH CAP G CLOSET # PLAN NOTES - MECHANICAL 118 1. VERIFY THERMOSTAT LOCATION WITH OWNER PRIOR TO INSTALLATION.

2. PROVIDE ELECTRIC SOLENOID VALVE ON GAS LINE. COORDINATE WITH CU E.C. 7 1 3. ROUTE DOWN TO RANGE FOR CONNECTION, SEE DETAIL 3/M0.1.

(ON ROOF) 4. ROUTE EXHAUST DUCT UP TO ROOF JACK. EF RLRS B 5. SEE MEP SITE PLAN ON SHEET MEP1.0 FOR PATIO GRILL GAS CONNECTION AND ROUTING.

SD SD SC 6. ROUTE 42"x18" DUCT UP TO FAI-1.

8 G 95 95 150 CLOSET 117 7. PROVIDE CONDENSING AS SCHEDULED AND SPECIFIED. UNIT SHALL 11 SET DEAD LEVEL ON PAD. EXTEND REFRIGERANT PIPING AS SCHEDULED TO CORRESPONDING FAN COIL. COAT REFRIGERANT PIPING INSULATION EXPOSED TO THE ELEMENTS WITH WEATHER PROOF COATING AS SPECIFIED. 8Ø DINING AREA EQUIPMENT ROOM 20x14 8. REFRIGERANT PIPING TO COOLING COIL IN BASEMENT, SEE M2.1 FOR RA 14x4 DN 115 T 120 CONTINUATION. - 1 IUH-1 1" BEDROOM #4 BEDROOM #3 RD RA 9. CONNECT GAS TO IUH-1, SEE DETAIL 3/M0.1. 113 114 SC - - 150 14x4 DN 10. 10"x4" HOOD DUCT THROUGH ROOF TO ROOF JACK.

11. ROUTE 20"x14" DUCT UP TO EF-B. 8Ø SC G SA 6Ø 2 150 SC 50 CORRIDOR 3 RC CLOSET 112 1" 150 - RESTROOM #1 107 2

G G 10x8 G G G 111 6" EF 8Ø 3/4" A 4" 6" 10x10 2 1"

3 G 4 1" EF 2 3 4 6Ø EF A HD A 4" 8Ø 10 1

20x10 3

6Ø KITCHEN IT CLOSET 2 H.C. 116 SA RESTROOM 4" 106

10x10 6Ø 50 108 EF 3 A CLOSET T RESTROOM #2 1 FCU-1 109 110 RC CORRIDOR CLOSET - 102 SA 105 6Ø 2 50 3

RA 14x4 DN 10x8 - 6Ø 2 RA

- SB 6Ø 2 SB 14x4 DN 70 70

BEDROOM #1 BEDROOM #2 103 104 LIVING ROOM 101

SE SE 150 150 6Ø 2 6Ø 2

SB SB 70 70

06-21-2017

N FIRST FLOOR PLAN - MECHANICAL SCALE: 1/4" = 1'-0" GENERAL NOTES - MECHANICAL

A. OFFSETS AND TRANSITIONS ARE TO BE PROVIDED FOR COORDINATION WITH OTHER SYSTEMS AND THE BUILDING STRUCTURE.

B. COORDINATE DUCTWORK DROPS WITH STRUCTURAL COMPONENTS. SUPPLY AND RETURN DUCT TRANSITION TO DUCT SIZE C. EQUIVALENT AREA DUCTS AND MODIFICATIONS TO LAYOUT ARE AS SHOWN ON PLAN ACCEPTABLE BASED ON FIELD CONDITIONS AND COORDINATION. FLOOR STRUCTURE D. PRIOR TO THE START OF CONSTRUCTION, THE MECHANICAL CONTRACTOR SHALL COMPLETELY REVIEW AND CONFIRM THE INTENDED RETURN AIR PATH TO MECHANICAL EQUIPMENT IS OPEN AND WILL BE FUNCTIONAL. CONFIRM AGAIN, PRIOR TO THE AIR BALANCE OF THE MECHANICAL SYSTEM. 3 CEILING OR SOFFIT E. COORDINATE LOCATION AND SUPPORTS OF MECHANICAL UNITS WITH OTHER TRADES. SA DUCT WITH LINER AS SCHEDULED FLEXIBLE CONNECTION # PLAN NOTES - MECHANICAL

1. 1-1/2" GAS PIPE THROUGH EXTERIOR WALL, SEAL AREA AROUND PIPE UNISTRUT OR PAINTED AND WALL SLEEVE, ROUTE PIPE TO MECHANICAL EQUIPMENT AS INSTALL HUMIDIFIER DX ANGLE BRACKET SECURING SHOWN. PAINT GAS PIPE EXPOSED TO THE ELEMENTS, COLOR TO PER MFR COIL UNIT TO WALL WITH (4) 1/4" MATCH BUILDING EXTERIOR. SECTION LAG BOLTS MINIMUM 2. ROUTE GAS PIPING DOWN TO DRYER CONNECTION, SEE DETAIL 3/M0.1.

20"x20" 3 3. ROUTE GAS PIPING DOWN TO WATER HEATER CONNECTION, SEE RETURN DETAIL 3/M0.1. AIR DUCT 4. ROUTE 3/4" GAS PIPING DOWN TO FCU-1 CONNECTION, SEE DETAIL 3/M0.1. FAN/ HEATER 5. ROUTE 1" GAS PIPING UP WITHIN CHASE, SEE M2.0 FOR CONTINUATION. SECTION FILTER ACCESS PANEL, 6. ROUTE REFRIGERANT PIPING DOWN TO COOLING COIL. TRAP CONDENSATE PROVIDE 1" THROW-AWAY PER. MFR. MERV 8 FILTER 7. PROVIDE FCU-1 COMPLETE AS SCHEDULED. UNIT SHALL SET DEAD UP UP LEVEL. PROVIDE WALL MOUNTED THERMOSTAT AS SCHEDULED. 6Ø 6Ø EXTEND VERTICALLY CONFIGURED SUPPLY AND RETURN DUCTS FROM FULL SIZE FLEXIBLE CONNECTIONS AT UNIT AND TRANSITION TO DUCTS RLRS SIZED AS SHOWN. DUCT RETURN INTO OPEN PLENUM AS SHOWN ON G STAIRS 3 20 GA SUPPORT PLENUM FOR RLRS 004 DRAWING AND DETAIL 1/M2.1. CONNECT REFRIGERANT LINES TO UNIT FAN COIL UNIT FROM CORRESPONDING CONDENSING UNIT. M.C. SHALL PIPE CONDENSATE TO CLOSEST FLOOR DRAIN VIA INDIRECT TERMINATION.

10x6 UNIT SHALL SET ON 1" 1" CONDENSATE TO NEOPRENE AND CORK COORDINATE CONTROL WIRING WITH E.C. COMPLETE INSTALLATION NEAREST FLOOR DRAIN VIA VIBRATION ISOLATION PADS PER MANUFACTURER'S PUBLISHED INSTALLATION INSTRUCTIONS. INDIRECT CONNECTION FLOOR 8. PROVIDE IN-O-VATE TECH. INC. EXTERIOR WALL VENT MODEL "DWV-4W". ROUTE 4"Ø DRYER DUCT UP TO ABOVE CEILING, USE LONG RADIUS 4x14 UP ELBOWS, TERMINATE THROUGH WALL VENT. VENT SHALL BE MOUNTED SB 3 1" SB 85 80 1 TYPICAL FCU ELEVATION LEVEL AND SEALED WATER TIGHT. M.C. SHALL COORDINATE COLOR WITH ARCHITECT PRIOR TO ORDERING. FIELD CONNECT TO UNIT M2.1 NO SCALE 6Ø 6Ø PROVIDED BY OWNER. INSTALL PER MANUFACTURERS IOM. LAUNDRY EQUIPMENT PROVIDED BY OWNER, COORDINATE DRYER VENT

WORKOUT 3 LOCATION AND ACTUAL EQUIPMENT PRIOR TO INSTALLATION. ROOM 3 001 9. ROUTE 3"PVC FURNACE FLUE AND INTAKE TO PVC CONCENTRIC KITAT 10x6 RLRS EXTERIOR WALL, SEE DETAIL 2/M2.1. 10x10 SB 6Ø 6Ø SB 10. ROUTE 3" PVC WATER HEATER EXHAUST AND INTAKE TO PVC 11 80 85 FLASHING TO WALL BY G.C. CONCENTRIC KIT AT EXTERIOR WALL, SEE DETAIL 2/M2.1.

GGG 11. 8"Ø FRESH AIR INTAKE SET FOR 150 CFM. ROUTE FROM CONNECTION 5 TO SIDE RETURN DUCT TO EXTERIOR WALL CAP. 6" CONCENTRIC CONCENTRIC KIT VENT 12. ROUTE 4Ø EXHAUST DUCT TO EXTERIOR WALL CAP. 20x10 UP 20x10 UP MINIMUM OF 10'-0" FROM ALL FRESH AIR INTAKES 3 3

1"

RESTROOM 20x12 20x12 002 COMBUSTION AIR AND VENT EXHAUST PIPE RLRS RB - TO GAS FIRED EQUIPMENT, SIZE PER

SA GG EQUIPMENT MANUFACTURER'S WRITTEN INSTRUCTIONS. PROVIDE PVC PIPE. 50 4 8Ø G 6 GWH COMBUSTION AIR & VENT PIPING FCU 3 " 3 EF 7 4 1 12 10x10 1 2 4Ø A WALL CONCENTRIC VENT KIT 3 M2.1 NO SCALE LAUNDRY 10 FROM FCU-1 003 4x14 UP G 9 FROM GWH-1 3 SE RE 50 - 4Ø 1 "

10x10 1 2 SE 2 50 G 8Ø 8Ø G UP UP 8 G G G 1 " 1 " 2 1 2 G 1

06-21-2017

N BASEMENT FLOOR PLAN - MECHANICAL SCALE: 1/4" = 1'-0" GENERAL NOTES - ELECTRICAL

A. COORDINATE ELECTRIC UTILITY WORK WITH UTILITY ENGINEER PRIOR TO START OF CONSTRUCTION.

B. REFER TO RISER DIAGRAM DETAIL 5/E0.1 FOR ADDITIONAL INFORMATION.

# PLAN NOTES - ELECTRICAL

1. PROPOSED LOCATION OF NEW UTILITY PAD-MOUNTED TRANSFORMER.

2. PROVIDE ONE (1) 4" CONDUIT FROM EXISTING UTILITY COMPANY POWER #10 POLE TO NEW UTILITY PAD-MOUNTED TRANSFORMER. VERIFY ALL REQUIREMENTS WITH LOCAL UTILITY COMPANY AND INSTALL PER THEIR REQUIREMENTS. COORDINATE CONDUIT ROUTING WITH OTHER "SE" UNDERGROUND UTILITIES. "SE" 13 13 3. PROVIDE ONE (1) 2" CONDUIT FOR TELEPHONE SERVICE AND ONE (1) 1" CONDUIT FOR CABLE TV. COORDINATE ROUTING WITH OTHER UNDERGROUND UTILITIES. 6 (TYP.) 4. 48 kW EMERGENCY GENERATOR.

5. FLAGPOLE LIGHT FIXTURE, VERIFY FINAL LOCATION WITH OWNER.

6. PROVIDE 1" CONDUIT MINIMUM FOR SITE LIGHTING. #10

GENERAL NOTES - MECHANICAL

A. COORDINATE NEW LOW PRESSURE GAS METER PER THE LOCAL UTILITY 13 COMPANY, MECHANICAL CONTRACTOR AND AUTHORITY HAVING "SE" JURISDICTION REQUIREMENTS. CONFIRM GAS SYSTEM REQUIREMENTS WITH THE LOCAL UTILITY COMPANY. LPA-13 B. GAS COMPANY IS RESPONSIBLE FOR THE METER AND GAS LINES UP TO "SE" (VIA "SLC") 13 METER. CONTRACTOR IS RESPONSIBLE FOR ALL GAS EQUIPMENT AFTER THE METER.

C. GAS LINE SHOWN IS FOR REFERENCE ONLY. COORDINATE EXACT LOCATION WITH GAS COMPANY. 4

# PLAN NOTES - MECHANICAL 4 3 1. GAS MAIN EXTENSION BY LACLEDE GAS COMPANY UP TO THE GAS METER AT THE BUILDING.

2. PROVIDE LOW PRESSURE GAS METER PER THE LOCAL UTILITY COMPANY AND AUTHORITY HAVING JURISDICTION REQUIREMENTS. PROPOSED LOAD TO BUILDING: 1,200 CFH PROPOSED DELIVERY PRESSURE: 10"-14" W.G. COORDINATE GAS SYSTEM REQUIREMENTS WITH THE LOCAL UTILITY COMPANY. PROVIDE ALL PIPING, VALVES, ASSOCIATED MATERIALS AND PRESSURE REDUCING VALVES AS REQUIRED TO PROVIDE THE PROPOSED DELIVERY PRESSURE TO THE BUILDING. PAINT ALL GAS PIPING, VALVES AND MATERIALS EXPOSED TO THE ELEMENTS WITH RUST INHIBITING PAINT TO MATCH THE COLOR OF THE BUILDING EXTERIOR. VERIFY COLOR WITH ARCHITECT PRIOR TO PAINTING. VERIFY AVAILABLE GAS SERVICE DELIVERY PRESSURE WITH UTILITY COMPANY PRIOR TO BID.

3. 3/4" GAS TO SERVE GAS GRILL ON PATIO. COORDINATE FINAL LOCATION WITH OWNER. 2 3 4. 1" GAS TO SERVE GENERATOR, COORDINATE ROUTING IN FIELD.

3 GENERAL NOTES - PLUMBING T 1 A. PRIOR TO CONSTRUCTION OF OR CONNECTION TO ANY , 3 , WATER MAIN, OR ANY OTHER UTILITIES, THE CONTRACTOR SHALL EXCAVATE, VERIFY AND CALCULATE ALL POINTS LPA-3 OF CONNECTION AND ALL UTILITY CROSSING AND INFORM THE (VIA "SLC") OWNER/DEVELOPER OF ANY CONFLICT OR REQUIRED DEVATIONS FROM 1 THE PLAN. #10 2 "SF" "SC" 3 3 # PLAN NOTES - PLUMBING 5 #10 2 5 1. 1-1/2" WATER SERVICE. 6 4 6 EXISTING 2. 4" FIRE SERVICE, SEE CIVIL DRAWINGS FOR CONTINUATION. UTILITY POLE 3. PROVIDE OIL / SAND INTERCEPTOR, INSTALL PER MANUFACTURER'S INSTRUCTIONS. ROUTE (2) TWO 3" VENTS FROM INTERCEPTOR, SEE P2.0 FOR ADDITIONAL INFORMATION.

4. PROPOSED FIRE DEPARTMENT SIAMESE CONNECTION.

5. PROPOSED WATER METER LOCATION.

6. NEW SANITARY , SEE CIVIL DRAWINGS FOR CONTINUATION. 06-21-2017 EXISTING 7 1 TELEPHONE 7. EXISTING 8" WATER LINE, SEE CIVIL DRAWINGS FOR ADDITIONAL PEDESTAL INFORMATION.

N SITE PLAN - MEP SCALE: 1/16" = 1'-0" FAI 1

6" INTAKE

6" FLUE

3" VTR EF B

4" VTR 4" VTR 3" VTR

ROOF JACK 3" VTR ROOF JACK

06-21-2017

N ROOF PLAN - MEP SCALE: 1/4" = 1'-0" PLUMBING CRITERIA: PLUMBING ABBREVIATIONS PLUMBING SYMBOL LIST 1. BEFORE SUBMITTING A PROPOSAL, THE PLUMBING CONTRACTOR SHALL VISIT THE SITE OF WORK AND FAMILIARIZE HIMSELF WITH ALL SITE AD AREA DRAIN CONDITIONS. PLUMBING CONTRACTOR SHALL CAREFULLY EXAMINE ALL CIVIL, ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND PLUMBING FIXTURES BALANCING VALVE (BAL.V.) ELECTRICAL CONSTRUCTION DOCUMENTS. SUBMISSION OF A BID WILL ACKNOWLEDGE THE PLUMBING CONTRACTOR HAS VISITED THE AHJ AUTHORITY HAVING JURISDICTION SITE AND EXAMINED ALL CONSTRUCTION DOCUMENTS AND BID INSTRUCTIONS. ALL PLUMBING WORK IN THE CONSTRUCTION DOCUMENTS, ALL FIXTURES INCLUDED IN THIS PROJECT SHALL BE PROVIDED BY THE PLUMBING CONTRACTOR UNLESS OTHERWISE NOTED. PROVIDE ALL AUTOMATIC SPRINKLER SYSTEM AND REQUIRED BY OTHER DIVISIONS, GENERALLY INSTALLED BY THE PLUMBING CONTRACTOR, WHERE EQUIPMENT IS PROVIDED BY NECESSARY HANGERS, BOLTS, ANCHORS, STEEL ANGLE, AND BRACKETS. ALL FIXTURES SHALL BE PROPERLY CONNECTED TO DWV SYSTEM AP ACCESS PANEL OTHERS, SHALL BE INCLUDED. IT IS EXPRESSLY UNDERSTOOD THAT THIS PROPOSAL IS BASED ON THE ABOVE REQUIREMENTS AND THAT IT AND WATER LINES AND SHALL BE INSTALLED IN AN ABSOLUTELY RIGID AND SUBSTANTIAL MANNER, WITHOUT DAMAGE TO ANY ADJOINING ARVTR ACID RESISTANT VENT THRU ROOF COVERS EVERYTHING NECESSARY TO COMPLETE THE SCOPE OF WORK DESCRIBED. WORK OR FINISH. PROVIDE SPECIFICATION GRADE SEALANT AT ALL WALL AND FLOOR CONNECTIONS COMPATIBLE WITH THE COLOR OF THE GATE VALVE (GT. V.) AND FINISH. COORDINATE WITH ARCHITECT PRIOR TO INSTALLATION. ARV ACID RESISTANT VENT 2. PLUMBING CONTRACTOR SHALL REQUEST CLARIFICATION ON ANY ITEM(S) OF THE CONTRACT DOCUMENTS THAT ARE NOT UNDERSTOOD ARW ACID RESISTANT WASTE GLOBE VALVE (GL. V.) OR WHERE CONFLICTS MAY EXIST. CLARIFICATIONS MUST BE PRESENTED AS A “REQUEST FOR INFORMATION” (RFI) IN WRITING PRIOR TO “ADA” WATER CLOSETS SHALL BE PROVIDED BY THE EQUIPMENT SUPPLIER WITH THE CORRECT FLUSH HANDLE ORIENTATION. THE EQUIPMENT SUBMITTING A BID. RFI SHALL BE PRESENTED A MINIMUM OF FIVE (5) WORKING DAYS BEFORE THE BID DATE. OBTAIN THE RFI FORM AT SUPPLIER AND PLUMBING CONTRACTOR SHALL ASSURE THIS COORDINATION. THE CONTRACTOR IS RESPONSIBLE FOR THIS COORDINATION CB CATCH BASIN CHECK VALVE (C.V.) WWW.GANDWENGINEERING.COM/DOCUMENTS . SUBMISSION OF A BID WILL ACKNOWLEDGE THE PLUMBING CONTRACTOR UNDERSTANDS AND SHOP DRAWING PROCESSING ACKNOWLEDGES THE PLUMBING CONTRACTOR HAS CORRECTLY ORDERED THE CORRECT FLUSH HANDLE THE SCOPE OF WORK, MEANS AND METHODS OF INSTALLATION, AND MATERIALS TO BE USED. RFI THAT HAVE NOT BEEN CLARIFIED PRIOR ORIENTATION, NO EXCEPTIONS OR EXCLUSIONS. CI CAST IRON TO BID, WILL BE PROVIDED BY THE PLUMBING CONTRACTOR, AS DIRECTED BY THE ENGINEER OF RECORD, AND THE MOST STRINGENT CO CLEANOUT GAS SHUT-OFF VALVE (S.O.V.) MATERIALS, EQUIPMENT, AND SCOPE OF WORK SHALL APPLY. NO ADDITIONAL COMPENSATION WILL BE MADE FOR THE FAILURE OF THE ALL FAUCETS SHALL BE FURNISHED AND INSTALLED WITH UNION TAILPIECES FOR CONNECTION TO SUPPLIES. SLIP JOINTS OR GASKETED CONTRACTOR TO OBTAIN CLARIFICATIONS PRIOR TO BID. JOINTS WILL NOT BE PERMITTED. DF DRINKING FOUNTAIN PRESSURE REDUCING VALVE (P.R.V.) DN DOWN 3. THE EQUIPMENT, MATERIALS, AND MANUFACTURERS SCHEDULED IN THE CONTRACT DOCUMENTS SHALL FORM THE BASIS OF DESIGN. THE ALL FIXTURES SHALL BE INDEPENDENTLY VALVED WITH EITHER INTEGRAL STOPS, CONCEALED STOPS OR STOPS BELOW THE FIXTURES. ALL PLUMBING CONTRACTOR SHALL BASE HIS BID ON THE SCHEDULED MATERIALS AND EQUIPMENT. ALL OTHER EQUIPMENT, MATERIALS, AND PLUMBING FIXTURES SHALL HAVE CHROME PLATED TRIM UNLESS OTHERWISE SPECIFIED. DS DOWNSPOUT BALL VALVE (B.V.) MANUFACTURERS, ARE CONSIDERED SUBSTITUTIONS. PROPOSED SUBSTITUTIONS MAY BE SUBMITTED FOR REVIEW AFTER THE ENGINEER HAS RECEIVED A SUBSTITUTION REQUEST FORM. OBTAIN THE SUBSTITUTION REQUEST FORM AT FIXTURES SHALL BE FURNISHED AS INDICATED ON THE DRAWINGS. “BASIS OF DESIGN” IS KOHLER, SIMILAR AND EQUAL CHINA FIXTURES (E) EXISTING STRAINER (STR.) WWW.GANDWENGINEERING.COM/DOCUMENTS . THE PLUMBING CONTRACTOR SHALL MAKE NO PRIOR ASSUMPTIONS ON SUBSTITUTIONS MANUFACTURED BY AMERICAN STANDARD, CRANE, TOTO, AND ELJER WILL BE ACCEPTABLE FOR REVIEW BY THE ENGINEER. THE SUBSTITUTION EC ELECTRICAL CONTRACTOR NOT APPROVED BY THE ENGINEER. APPROVALS OF SUBSTITUTIONS ARE CONTINGENT UPON ENGINEER'S REVIEW. SHOULD THE ENGINEER REQUEST FORM IS NOT REQUIRED FOR ALTERNATE MANUFACTURES UNLESS NOTES SPECIFICALLY STATE “NO SUBSTITUTIONS”. SIMILAR AND F FURNISHED BY OTHERS APPROVE A SUBSTITUTION REQUEST, THE PLUMBING CONTRACTOR WILL BE HELD RESPONSIBLE FOR ENGINEERING COSTS, PHYSICAL SIZE, EQUAL STAINLESS STEEL FIXTURES BY JUST WILL BE ACCEPTABLE FOR REVIEW. SIMILAR AND EQUAL TERRAZZO OR MOLDED STONE EWC ELECTRIC WATER COOLER CAPACITIES, COORDINATION, SUPPLEMENTAL DRAWINGS AND INFORMING OTHER TRADE CONTRACTORS RELATED TO THE INSTALLATION PRODUCTS BY STERN WILLIAMS AND SWAN WILL BE ACCEPTABLE FOR REVIEW. FCO FLOOR C.O. AS TO ANY SPECIFIED ITEM CHANGES. THE PLUMBING CONTRACTOR SHALL BEAR AS PART OF HIS CONTRACT, ANY ADDITIONAL COSTS B PIPING BELOW FLOOR OR GRADE INCURRED IN HIS WORK OR BY THE OTHER CONTRACTORS AS A RESULT OF SUBSTITUTIONS TO THE BASIS OF DESIGN. FAUCETS, SHOWER CONTROLS, TUB AND SHOWER CONTROLS OF SIMILAR DESIGN AND EQUAL QUALITY TO THAT SPECIFIED BY KOHLER, MOEN, FD FLOOR DRAIN CHICAGO FAUCET, T&S BRASS, AND SYMMONS WILL BE ACCEPTABLE FOR REVIEW. THE SUBSTITUTION REQUEST FORM IS NOT REQUIRED FOR C PIPING ABOVE CEILING 4. PLUMBING CONTRACTOR SHALL PERFORM WORK IN A SAFE MANNER. COMPLY WITH APPLICABLE OSHA SAFETY GUIDELINES DURING THE ALTERNATE MANUFACTURES UNLESS NOTES SPECIFICALLY STATE “NO SUBSTITUTIONS” FL FLOWLINE COURSE OF COMPLETING THE WORK DESCRIBED ON THESE CONSTRUCTION DOCUMENTS. FSC FOOD SERVICE CONTRACTOR FIXTURES SHALL BE PROVIDED AS INDICATED ON THE DRAWINGS. PLUMBING FIXTURES, TRIM AND RELATED APPURTENANCES AND FLOOR XX XX XX PLAN NOTE SYMBOL 5. SHOP DRAWINGS SHALL BE SUBMITTED ELECTRONICALLY AS PDF FILES. SHOP DRAWINGS SHALL INCLUDE TRANSMITTAL PAGE(S) DRAINS LISTED IN THE FIXTURE SCHEDULE ARE SELECTED TO ESTABLISH THE BASIS OF DESIGN AND A LEVEL OF QUALITY EXPECTED. FPC FIRE PROTECTION CONTRACTOR INDICATING THE NAME OF THE PROJECT, AND THE NAME, ADDRESS, AND PHONE NUMBER OF THE GENERAL AND PLUMBING CONTRACTORS. GC GENERAL CONTRACTOR XX REVISION SYMBOL GENERAL CONTRACTOR AND PLUMBING CONTRACTOR SHALL REVIEW SHOP DRAWING SUBMITTALS FOR COMPLIANCE, CONTENT AND PLUMBING FIXTURES SHALL BE AS FOLLOWS: COMPLETENESS AND PROVIDE A STAMP WITH THE DATE OF REVIEW AND SIGNATURE OF THE REVIEWER. TRANSMITTAL PAGE SHALL HAVE HB HOSE BIBB SANITARY STACK NUMBER INDEX WITH SPECIFICATION SECTION AND DESCRIPTION OF SUBMITTED ITEMS. NO EXCEPTIONS WILL BE TAKEN. SHOP DRAWINGS NOT L-1 ADA LAVATORY WITH INTEGRAL CULTURED MARBLE TOP AND BOWL, BY ARCH, DELTA #501LF-HGMHDF CENTER SET LAVATORY FAUCET, X SUBMITTED IN THIS FORMAT WILL BE REJECTED AND WILL NOT CAUSE REASON FOR PROJECT DELAYS. EQUIPMENT SHALL NOT BE SINGLE HANDLE, 0.5 G.P.M. FLOW RESTRICTOR, AERATOR, OFFSET GRID STRAINER AND 1-1/4" TAILPIECE, CHROME FINISH. CHROME PLATED 3/8" HD HUB DRAIN ORDERED UNTIL ENGINEER OF RECORD HAS PROCESSED APPLICABLE SHOP DRAWINGS. A MINIMUM OF SEVEN WORKING DAYS WILL BE FLEXIBLE ANGLE SUPPLIES WITH LOOSE KEY STOP VALVES, PVC P-TRAP WITH CLEANOUT AND WALL ESCUTCHEON. INSULATE HOT WATER IW INDIRECT WASTE X DOWNSPOUT LETTER ALLOWED FOR SUBMITTAL PROCESSING BY THE ENGINEER. REFER TO ARCHITECT'S GENERAL REQUIREMENTS FOR ADDITIONAL SUPPLY AND P-TRAP WITH FULLY MOLDED TRUEBRO HANDI LAV-GUARD INSULATION KIT #103 IN WHITE COLOR. REQUIREMENTS. LAV LAVATORY NEW CONNECTION TO EXIST. VENT LINE. L-2 LAVATORY WITH INTEGRAL CULTURED MARBLE TOP AND BOWL, BY ARCH, DELTA #520LF-HGMHDF CENTER SET LAVATORY FAUCET, SINGLE VERIFY SIZE AND LOCATION IN THE FIELD. MB MOP BASIN 6. PROVIDE ALL REQUIRED INSPECTIONS AND RE-INSPECTIONS. PROVIDE A SIGNED CERTIFICATE OF INSPECTION AT THE PROJECT HANDLE, 0.5 G.P.M. FLOW RESTRICTOR, AERATOR, POP-UP DRAIN AND 1-1/4" TAILPIECE, CHROME FINISH. CHROME PLATED 3/8" FLEXIBLE ANGLE NEW CONNECTION TO EX. WASTE OR SAN. SEWER. COMPLETION. SUPPLIES WITH LOOSE KEY STOP VALVES, PVC P-TRAP WITH CLEANOUT AND WALL ESCUTCHEON. MC MECHANICAL CONTRACTOR VERIFY LOCATION, SIZE, AND F.L. IN THE FIELD.

7. PLUMBING CONTRACTOR SHALL UTILIZE DIMENSIONED ARCHITECTURAL DRAWINGS AND ELEVATIONS FOR THE LAYOUT OF PLUMBING WC-1 KOHLER HIGHLINE 1.28 GPF ADA FLUSH TANK TOILET, WHITE VITREOUS CHINA, ELONGATED 16-1/2" HIGH BOWL, FLOOR OUTLET WITH MH MANHOLE NEW CONNECTION TO EXIST. WATER LINE. VERIFY SIZE AND LOCATION IN THE FIELD. FIXTURES. REVIEW ARCHITECTURAL LAYOUT AND ELEVATIONS PRIOR TO STARTING CONSTRUCTION. ANY DISCREPANCIES SHALL BE CLOSE COUPLED TANK, AND BOLT CAPS. BEMIS #7850TJDG WHITE OPEN FRONT SEAT WITH COVER WITH CONCEALED CHECK AND OFRD OVERFLOW ROOF DRAIN SUBMITTED TO THE ARCHITECT FOR CLARIFICATION THROUGH AN RFI PRIOR TO STARTING THE WORK. ANTIMICROBIAL AGENT OR EQUAL BY CHURCH OR BENEKE. CHROME PLATED 3/8" SUPPLY PIPE TO WALL WITH LOOSE KEY STOP VALVE, ESCUTCHEON AND FLEXIBLE RISER. RIM HEIGHT SHALL BE 16-1/2" ABOVE FLOOR. PA PIPE ANCHOR 8. ALL EQUIPMENT AND MATERIALS SHALL BE SPECIFICALLY PROVIDED PER WRITTEN INSTALLATION INSTRUCTIONS AS PUBLISHED BY THE PC PLUMBING CONTRACTOR PLUMBING PIPING MANUFACTURER OF THE EQUIPMENT OR MATERIAL PROVIDER. MEANS AND METHODS OF INSTALLATION ARE TO BE PROVIDED BY THE WC-2 KOHLER HIGHLINE 1.28 GPF FLUSH TANK TOILET, WHITE VITREOUS CHINA, ELONGATED HIGH BOWL, FLOOR OUTLET WITH CLOSE COUPLED PLUMBING CONTRACTOR. PLUMBING CONTRACTOR SHALL UNDERSTAND THE PRODUCT, MEANS AND METHODS OF INSTALLATION. THE TANK, AND BOLT CAPS. BEMIS #7850TJDG WHITE OPEN FRONT SEAT WITH COVER WITH CONCEALED CHECK AND ANTIMICROBIAL AGENT OR PD PUMP DISCHARGE SAN SOIL OR WASTE ABOVE FLOOR PLUMBING CONTRACTOR SHALL OBTAIN THE INSTALLATION INSTRUCTIONS AND REQUIREMENTS PRIOR TO BID. ALL RFI AND EQUAL BY CHURCH OR BENEKE. CHROME PLATED 3/8" SUPPLY PIPE TO WALL WITH LOOSE KEY STOP VALVE, ESCUTCHEON AND FLEXIBLE PVC POLYVINYL CHLORIDE PIPE CLARIFICATIONS OF SCOPE DURING CONSTRUCTION WHERE THE CONTRACTOR HAS NOT PREVIOUSLY OBTAINED THIS INFORMATION FOR RISER. SAN SOIL OR WASTE BELOW FLOOR BIDDING PURPOSES WILL NOT BE CAUSE FOR ADDITIONAL COSTS OR CONSTRUCTION DELAY. RCP REINFORCED PIPE ST STORM LINE ABOVE FLOOR S-1 ELKAY #DLRS332210, SINGLE COMPARTMENT STAINLESS STEEL SINK WITH 1-HOLE PUNCHING. DELTA FAUCET #4140-AR-DST. ONE (1) LK-35 RD ROOF DRAIN 9. PLUMBING CONTRACTOR SHALL PROVIDE FIELD COORDINATION WITH OTHER TRADES; SYSTEMS AS SHOWN ARE DIAGRAMMATIC AND GIVE BASKET STRAINER WITH 1-1/2" TAILPIECE AND 1-1/2" PVC P-TRAP WITH ESCUTCHEON AND CLEANOUT. CHROME PLATED ANGLE STOP VALVES ST STORM LINE BELOW FLOOR THE GENERAL ARRANGEMENT AND LOCATIONS ONLY. PLUMBING CONTRACTOR SHALL COMPLETELY REVIEW ARCHITECTURAL DRAWINGS, WITH FLEXIBLE RISERS. PROVIDE AND INSTALL INSINKERATOR 5XP GARBAGE DISPOSAL, 3/4 HP, 120V/1PH. RIO ROUGH-IN ONLY S SUB-SOIL DRAIN TILE STRUCTURAL DRAWINGS, AND SYSTEMS DRAWINGS OF OTHER TRADES FOR DETAILS OF CONSTRUCTION. ROUGH-IN OF PLUMBING FIXTURES, EQUIPMENT, PIPING, ATTACHMENTS, AND HANGERS SHALL BE BASED ON THIS REVIEW. EXACT LOCATIONS AND FINAL LAYOUT S-2 FIAT #FLJD-11 MOLDED STONE LAUNDRY TUB, TWO COMPARTMENT, FOUR WHITE BAKED ENAMEL ANGLE LEGS, SELF LEVELING WITH FLOOR RPBP REDUCED PRESSURE BACKFLOW PREVENTER G KITCHEN GREASE WASTE LINE SHALL BE DETERMINED IN THE FIELD, PROVIDE ALL NECESSARY EQUIPMENT, CLEANOUTS, FITTINGS, HANGERS, SUPPORTS, AND OFFSETS ANCHORS, STRAINER WITH STOPPER SUPPLIED WITH UNIT. CHICAGO FAUCET #527-L12E1ABCP, PVC P-TRAP, 1-1/2" INLET AND OUTLET, WITH S SOIL REQUIRED FOR A COMPLETE INSTALLATION IN ALL RESPECTS. THE PLUMBING CONTRACTOR MEANS AND METHODS OF INSTALLATION CLEANOUT, CHROME PLATED ESCUTCHEON, LOOSE KEY STOPS WITH WALL ESCUTCHEON AND FLEXIBLE RISER. S/O/G SAND/OIL/GREASE WASTE ABOVE FLOOR SHALL PROVIDE FOR OPERATING EFFICIENCY, NEATNESS OF APPEARANCE, AND EASE OF MAINTENANCE. THE PLUMBING CONTRACTOR SD SHOWER DRAIN S/O/G SAND/OIL/GREASE WASTE BELOW FLOOR WILL PREPARE DIMENSIONED FIELD ERECTION DRAWINGS WHERE REQUIRED FOR USE BY THE INSTALLERS, TO ENSURE PROPER WH-1 WOODFORD #67, 3/4" NON-FREEZE WALL HYDRANT WITH VANDAL PROOF INTEGRAL VACUUM BREAKER-BACKFLOW PREVENTER, STRAIGHT SDS SECONDARY DOWNSPOUT INSTALLATION AND COORDINATION. THE PLUMBING CONTRACTOR SHALL TAKE THEIR OWN MEASUREMENTS AT THE BUILDING, AND BE INLET CONNECTION, BRASS CASING AND WITH CHROME PLATED FINISH. VERIFY WALL THICKNESS ON THE ARCHITECTURAL DRAWINGS. VENT LINE RESPONSIBLE FOR THE CORRECT LAYOUT, INTERPRETATION, AND USE OF ALL SIZES AND DIMENSIONS. THE CONTRACTOR SHALL KEEP SIMILAR HYDRANTS BY PRIER, J.R. SMITH OR ZURN WILL BE ACCEPTABLE. SH SHOWER VALVE AR ACID RESISTANT WASTE “AS-BUILT” INFORMATION DURING CONSTRUCTION AND FURNISH TO THE OWNER OR TENANT A RECORD SET OF LEGIBLE BLACK LINE PRINTS AND AN ELECTRONIC COPY OF THESE DOCUMENTS AT THE PROJECT COMPLETION. HR-1 REELCRAFT #CA33112L HOSE REEL WITH HAND CRANK, 3/4” NPTF INLET, ADJUSTABLE SPOOL DRAG, NICKEL PLATED VITON “O” RING SEALS, SS SERVICE SINK AR ACID RESISTANT VENT LINE PERMANENTLY LUBRICATED BEARINGS, POWDER COAT RED FINISH, STEEL DRUM AND 100 FEET OF 3/4” I.D., 1-188” O.D. PVC HOSE RATED FOR SW STREET WASHER 10. REVIEW ARCHITECTURAL DRAWINGS FOR ALL FIRE RATINGS AND FIRE RATED ASSEMBLIES PRIOR TO BIDDING THE PROJECT. PROVIDE FIRE 300 P.S.I. AT 150F. WITH BRASS FITTINGS. PROVIDE WITH CHICAGO FAUCETS #835-SFBCP WALL MOUNT FAUCET WITH EXPOSED BOTTOM INLETS, PD PUMP DISCHARGE STOP AT EACH RATED WALL, FLOOR, AND CEILING-ROOF ASSEMBLY PENETRATION. FIRE STOP SYSTEMS SHALL BE MANUFACTURED BY 3/4” HOSE THREAD OUTLET, VACUUM BREAKER SPOUT WITH PAIL HOOK AND WALL BRACE. TMV THERMOSTATIC MIXING VALVE COLD WATER LINE (C.W.) “3M”. PROVIDE IN STRICT COMPLIANCE WITH THE MANUFACTURER'S APPLICATION DETAILS AND INSTRUCTIONS. PROVIDE INSTALLER TPRV TEMPERATURE AND PRESSURE RELIEF VALVE CERTIFICATION SIGNS AT EACH PENETRATION. PROVIDE SHOP DRAWINGS FOR REVIEW WITH THE U.L. LISTING AND TEST CRITERIA. SH-1 AQUATIC #1423CTC, ACRYLIC PREMOLDED, ONE PIECE SHOWER UNIT WITH SHOWER DRAIN AND STRAINER. 42" X 34" X 76" NOMINAL SIZE HOT WATER LINE (H.W.) PROVIDE FIRE STOPPING WHERE REQUIRED BY THE AHJ. EQUAL SYSTEMS AS MANUFACTURED BY “SPEC SEAL” OR “HILTI” WILL BE WITH LEFT OR RIGHT HAND CONTROL AS REQUIRED BY PLAN VIEW. FINISH SHALL BE WHITE OR AS APPROVED BY ARCHITECT. PROVIDE WITH UR URINAL HOT WATER RETURN LINE (H.W.R.) ACCEPTABLE. COMPATIBLE DOOR SYSTEM, COORDINATE SIZE WITH ARCHITECT. SYMMONS #C-96-1-X "TEMPTROL" PRESSURE BALANCING VALVE WITH INTEGRAL SERVICE STOPS, ADJUSTABLE STOP SCREW TO LIMIT HANDLE TURN, 2.5 G.P.M. FLOW RESTRICTOR, SINGLE-MODE ADJUSTABLE V VENT F FIRE OR SPRINKLER LINE 11. PROVIDE PIPING, AND HANGER PENETRATIONS OF NON-RATED ASSEMBLIES WITH DRAFT STOPPING, OR SMOKE BARRIER SEALANT SHOWER HEAD. PROVIDE REVERSIBLE CORE ON ONE SHOWER ONLY, FOR BACK-TO-BACK INSTALLATIONS. PLUMBING CONTRACTOR SHALL SET VTR VENT THRU ROOF SYSTEMS. THROUGH PENETRATION SEALANT SYSTEMS SHALL BE MANUFACTURED BY “3M”. APPLY IN STRICT COMPLIANCE WITH THE "LIMIT-STOP" FOR 110°F. FCW FILTERED COLD WATER MANUFACTURER'S APPLICATION DETAILS AND INSTRUCTIONS. PROVIDE DRAFT STOPPING OR SMOKE BARRIER SEALANTS TO MEET W WASTE TYPE (E) EXISTING PIPING APPROVAL OF THE AHJ. EQUAL SYSTEMS AS MANUFACTURED BY “SPEC SEAL” OR “HILTI” WILL BE ACCEPTABLE. SH-2 AQUATIC #14834STT, ACRYLIC PREMOLDED, ONE PIECE SHOWER UNIT WITH SHOWER DRAIN AND STRAINER. 48" X 34" X 80" NOMINAL SIZE WC WATER CLOSET WITH LEFT OR RIGHT HAND CONTROL AS REQUIRED BY PLAN VIEW. FINISH SHALL BE WHITE OR AS APPROVED BY ARCHITECT. PROVIDE WITH TYPE PIPE TO BE REMOVED 12. PLUMBING CONTRACTOR SHALL GUARANTEE ALL EQUIPMENT AND MATERIAL INSTALLED UNDER THIS CONTRACT TO BE FREE FROM COMPATIBLE DOOR SYSTEM, COORDINATE SIZE WITH ARCHITECT. SYMMONS #C-96-1-X "TEMPTROL" PRESSURE BALANCING VALVE WITH WCO WALL CLEANOUT DEFECTS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE AND SHALL REPAIR OR REPLACE WITHOUT INTEGRAL SERVICE STOPS, ADJUSTABLE STOP SCREW TO LIMIT HANDLE TURN, 2.5 G.P.M. FLOW RESTRICTOR, SINGLE-MODE ADJUSTABLE COST TO THE OWNER OR TENANT ANY EQUIPMENT WHICH IS DEFECTIVE, OR IMPROPERLY INSTALLED. IN ADDITION THIS CONTRACTOR SHOWER HEAD. PLUMBING CONTRACTOR SHALL SET "LIMIT-STOP" FOR 110°F. WH WALL HYDRANT SHALL ASSUME FULL RESPONSIBILITY FOR ANY DAMAGE TO THE BUILDING AND ITS CONTENTS OR OTHER EQUIPMENT CAUSED BY DEFECTS OR IMPROPER INSTALLATION OF EQUIPMENT OR MATERIALS INSTALLED IN THIS PROJECT. OS-1 STRIEM OS-100 OIL/SAND SEPARATOR, HPDE SEAMLESS MOLDED TANK, WITH FIELD ADJUSTABLE RISER SYSTEM, BUILT-IN FLOW CONTROL, AND VENT CONNECTIONS. SEPARATOR FLOW RATE SHALL BE 100 GPM, WITH CAPACITY OF 147.5 GALLONS OF OIL AND 105 GALLONS OF 13. INSTALL PIPE SLEEVES FOR PIPES PENETRATING FLOORS, PARTITIONS, ROOFS, AND WALLS, EXCEPT CORE DRILLED CONCRETE. INSTALL SEDIMENT. TOTAL TANK CAPACITY SHALL BE 275 GALLONS (36.8 CU.FT.). COVER SHALL PROVIDE WATER/GAS-TIGHT SEAL. SLEEVES IN CONCRETE FLOORS, CONCRETE ROOF SLABS, AND CONCRETE WALLS AS NEW SLABS AND WALLS ARE CONSTRUCTED. SP-1 ZOELLER MODEL 49 , 25 GPM AT 10FT OF HEAD, 1/4 HP, 120V/1PH, PSC MOTOR, WITH INTEGRAL FLOAT SWITCH FOR AUTOMATIC 14. PROVIDE STANDARD WEIGHT CAST IRON SOIL PIPE MANUFACTURED PER “CISPI STANDARDS” AND BEARING THIS TRADEMARK. PROVIDE OPERATION. PROVIDE WITH BASIN, CHECK VALVE, AND SHUT-OFF VALVE. STANDARD NO-HUB FITTINGS FOR ALL CAST IRON DWV PIPING SYSTEMS. SCHEDULE 40 PVC DWV SYSTEM MAY BE INSTALLED WHERE ACCEPTABLE TO THE LOCAL AHJ. PVC PIPE AND DWV FITTINGS SHALL BE SOLVENT WELDED IN ACCORDANCE WITH MANUFACTURER'S WSD-1 SIOUX CHIEF 696-G241 WASHER SUPPLY AND DRAIN BOX, WITH LEVER TYPE BALL VALVE SHUT-OFFS WITH INTEGRAL ARRESTORS INSTALLATION INSTRUCTIONS. INSTALL DWV SYSTEM WITHIN TEMPERATURE CONDITIONS AS SPECIFIED BY THE MANUFACTURER. PROVIDE CERTIFIED TO ASSE 1010. CLEANOUTS IN STRICT ACCORDANCE WITH PLUMBING CODE. PROVIDE CLEANOUT TEE AND CHROME ACCESS COVER IN BASE OF EACH VENT STACK. FLASH VENTS THROUGH ROOF WITH 12LB. SHEET FLASHING OR NEOPRENE RUBBER GROMMET FLASHING. TEST ALL IMB-1 SIOUX CHIEF 696-G101 ICE MAKER SUPPLY BOX, WITH LEVER TYPE BALL VALVE SHUT-OFF WITH INTEGRAL ARRESTOR CERTIFIED TO ASSE DWV AND STORM DRAIN PIPING PER REQUIREMENTS OF THE AHJ OR AS A MINIMUM TO TEN (10) FEET HEAD OF WATER FOR AT LEAST 2 1010. HOURS WITH NO BEFORE COVERING. BACKFILL INSIDE BUILDINGS SHALL BE CLEAN 3 /4” GRANULAR LIMESTONE. RPBP-1 WATTS MODEL LF909 REDUCED PRESSURE ZONE BACKFLOW PREVENTER FOR DOMESTIC WATER USE. PROVIDE WITH QUARTER TURN 15. WATER PIPING SHALL BE COPPER AS SCHEDULED ON THE DRAWINGS. SHUT-OFF VALVES SHALL BE BRONZE BODY NIBCO C-580 BALL BALL VALVES AND BRONZE STRAINER. PROVIDE WITH AIR GAP, PIPE TO NEAREST FLOOR DRAIN. VALVES RATED FOR 125LB.WORKING PRESSURE OR INDUSTRY STANDARD EQUAL. TEST WATER PIPING PER THE AHJ REQUIREMENTS OR AT A MINIMUM TO 125LB. FOR AT LEAST 24 HOURS WITH NO LEAKS BEFORE COVERING. RPBP-2 WATTS MODEL LF909 REDUCED PRESSURE ZONE BACKFLOW PREVENTER FOR FIRE PROTECTION USE. PROVIDE WITH AIR GAP, PIPE TO 16. CPVC PIPE INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURES INSTALLATION INSTRUCTIONS IS ACCEPTABLE. NEAREST FLOOR DRAIN. 17. ABOVE GROUND INTERIOR DOMESTIC WATER PIPING, NPS 2" AND SMALLER, SHALL BE CPVC, ASTM F 441/F 441M, SCHEDULE 40, 2-1/2" AND LARGER SHALL BE SCHEDULE 80 CPVC. FLOOR DRAINS AND FLOOR SINKS SHALL BE AS FOLLOWS: 18. CPVC SOCKET FITTINGS: ASTM F 438 FOR SCHEDULE 40. 19. CPVC PIPING SYSTEM: ASTM D 2846/D 2846M, SDR 11, PIPE AND SOCKET FITTINGS. FD-1 FLOOR DRAIN SHALL BE EQUAL TO JOSAM 30000-A-50 CAST IRON FLOOR DRAIN WITH , INTEGRAL CLAMPING COLLAR AND 20. CPVC TUBING SYSTEM: ASTM D 2846/D 2846M, SDR 11, TUBE AND SOCKET FITTINGS. ADJUSTABLE ROUND NICKEL BRASS STANDARD STRAINER, INSIDE CAULK OUTLET. STRAINER SIZE TO BE 5" FOR 2" OUTLET, 6" FOR 3" OUTLET 21. JOINT CONSTRUCTION FOR SOLVENT-CEMENTED PIPING: CLEAN AND DRY JOINING SURFACES. JOIN PIPE AND FITTINGS TO AND 8" FOR 4" OUTLET. INSTALL IN FINISHED ROOM AREAS. PROVIDE A DEEP SEAL P-TRAP UNDER EACH DRAIN. PROVIDE A TRAP PRIMER AND COMPLY WITH ASTM F 402 FOR SAFE-HANDLING PRACTICE OF CLEANERS, PRIMERS, AND SOLVENT CEMENTS. APPLY PRIMER. JOIN ACCESS PANEL FOR EACH DRAIN. TRAP PRIMER SHALL BE EQUIVALENT TO JOSAM 88250. ACCORDING TO ASTM D 2846/D 2846M APPENDIX. 22. INSTALL VINYL-COATED HANGERS FOR CPVC PIPING WITH THE FOLLOWING MAXIMUM HORIZONTAL SPACING AND MINIMUM ROD DIAMETERS: TD-1 TRENCH DRAIN SHALL BE EQUAL TO ZURN Z882, 12” WIDE TRENCH DRAIN, 8' HDPE CHANNEL, WITH STEEL FRAME, INTEGRAL SLOPE, 23. NPS 1 AND SMALLER: 36 INCHES WITH 3/8-INCH ROD. 4” BOTTOM OUTLET, AND CLASS C VEHICLE RATED SLOTTED GRATE. 24. NPS 1-1/4 TO NPS 2: 48 INCHES WITH 3/8-INCH ROD. 25. NPS 2-1/2 TO NPS 3-1/2: 48 INCHES WITH 1/2-INCH ROD. PROVIDE A TRAP PRIMER FOR FD-1 ONLY. TRAP PRIMER SHALL BE EQUIVALENT TO JOSAM 88250. LOCATE THIS IN A PLUMBING WALL BEHIND AN 26. INSTALL SUPPORTS FOR VERTICAL CPVC PIPING EVERY 60 INCHES FOR NPS 1 AND SMALLER, AND EVERY 72 INCHES FOR NPS 1-1/4 AND ACCESS PANEL PROVIDED BY THE P.C. COORDINATE THE LOCATION WITH THE ACCESS PANEL WITH THE ARCHITECT PRIOR TO STARTING LARGER. CONSTRUCTION. 06-21-2017 27. INSULATE COLD, HOT, AND HOT WATER RETURN PIPING AS SCHEDULED ON THE DRAWINGS. PROVIDE WATER HAMMER ARRESTORS ON THE SIMILAR DRAINS BY J.R. SMITH, ZURN, AND WADE WILL BE ACCEPTABLE. COLD AND HOT WATER SUPPLIES FOR EACH PLUMBING FIXTURE. WATER HAMMER ARRESTORS SHALL BE EQUAL TO “SIOUX CHIEF” HYDRA-RESTER SIZED AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURES INSTALLATION INSTRUCTIONS AND SIZING ALL FLOOR DRAINS SHALL HAVE TOPS SET 1/2" BELOW FLOOR SLAB ELEVATION AND FLATWORK SUB-CONTRACTOR SHALL SLOPE FLOOR TO GUIDELINES. DRAIN TO ASSURE PROPER DRAINAGE.

28. PLUMBING CONTRACTOR SHALL VERIFY THE FLOW LINE OF ALL DRAIN CONNECTION POINTS PRIOR TO STARTING CONSTRUCTION.

29. AFTER INSTALLATION OF PIPING, BACK FILL SHALL BE BROUGHT TO SUB-GRADE ELEVATION AND COMPACTED WITH GRANULAR FILL. FINISH SHALL BE SMOOTH AS REQUIRED TO ACCEPT NEW SCHEDULED FINISH. PLUMBING CONTRACTOR SHALL REMOVE AND LEGALLY DISPOSE ALL EXCAVATION DEBRIS FROM THE CONSTRUCTION SITE.

30. PLUMBING SCOPE OF WORK SHALL BE PROVIDED TO COMPLY WITH THE CURRENT EDITION OF THE ADOPTED PLUMBING CODE, GOVERNING STATE LAW, FEDERAL LAW, AND ALL LOCAL ORDINANCES. REFER TO THE ARCHITECTURAL CODE BLOCK AND THE MUNICIPALITY WEBSITE FOR THE APPLICABLE CODE AND ADOPTED ORDINANCES PRIOR TO BID. SUBMISSION OF A BID ACKNOWLEDGES YOU HAVE PERFORMED THIS REQUIREMENT AND YOUR BID INCLUDES LABOR AND MATERIAL TO PROVIDE THIS COMPLIANCE. INSULATION MATERIALS SCHEDULE NICKALOY COVER (NOT ALL SYSTEMS MAY BE REQUIRED ON THIS PROJECT) BRONZE PLUG CABINET VENT SINK FLOOR SLAB RISE VENT IN NEAREST WALL

JOSAM #58360 ACCESSIBLE ADJUSTABLE C.O. CLEANOUT (TYP) TYPE OF SERVICE JOSAM 58510 JOSAM 58600 CLEANOUT TEE WALL ACCESS NO-HUB CONNECTION WITH PLUG COVER SAN FROM SINK 4" RISER AS REQUIRED TYPE OF MATERIAL NOTES PIPING IN UNHEATED BUILDING AREAS 5'-0" PIPING EXPOSEDDOMESTICDOMESTIC TO WATER CLIMATICHW WATERPIPING-2-1/2"& HWR HWELEMENTS PIPINGPIPING-2"& HWR & INPIPINGLARGER CIRCULATED& SMALLER ONLY BELOW HOT WATER GROUND SYSTEM MIN 1-1/2" WITH A.S.J. & 0.016 ALUMINUM JACKET, WEATHERPROOF (PIPE ELECTRICALLY TRACED PRIOR TO INSULATING)

1-1/2" FIBERGLASS WITH A.S.J. PRE-FORMED 3 (PIPE ELECTRICALLY TRACED PRIOR TO INSULATING) FITTING COVERS 1/8 BEND ISLAND VENT DETAIL P0.1 NO SCALE 1 INCH FIBERGLASS WITH ALL-SERVICE JACKET WYE WITH 1/8 BEND PRE-FORMED 1 INCH FIBERGLASS WITH ALL-SERVICE JACKET FITTING COVERS NOTES: SET DISCHARGE 1/2 INCH THICK ELASTOMERIC CLOSED CELL INSULATION - ASTM E-84 1. PROVIDE AT BASE OF EACH MULTIPLE FIXTURE STACK. TEMP. AT 120°F. 2. REQUIRED ON STORM DOWNSPOUTS. HW TO FIXTURES 3 " 3. COORDINATE LOCATION WITH ARCHITECT PRIOR TO ROUGH IN. 1 " 1 " 4 1 4 CW 1 4 HW PIPE IN RUN BALL VALVE FULL S PORT (TYP.) 3 " HOT WATER RETURN PUMP 4 B&G NRF-22, 115 V. 2 GPM @ 10 1 PLUMBING MATERIALS SPECIFICATION INTERIOR C.O. DETAIL 2 WALL CLEANOUT DETAIL HEAD (NOT ALL SYSTEMS MAY BE REQUIRED ON THIS PROJECT) P0.1 NO SCALE P0.1 NO SCALE AMTROL ST-5 (STORM AND SANITARY) EXPANSION TANK 3"Ø COMBUSTION AIR BY H.C.

DI-ELECTRIC UNION (TYP.)

8"X8" ACCESS PANEL 3"Ø FLUE JOSAM 30000-S-50 WITH TPRV BY H.C. SATIN NICKEL BRONZE TRAP PRIMER TYPE OF SERVICE STRAINER 88250 1/2" CW 2" WIDE, 20GA. PIPE TPRV TO DRAW BAND FLOOR DRAIN ADHESIVE GROUT AFTER AROUND WATER WATER MEMBRANE IS INSTALLED FLOW TO D HEATER SECURE HEATER TYPE OF MATERIAL NOTES FIXTURE BURIED ABOVEBUILDING GRADEDOMESTIC SANITARY SAN.,BURIED WATER &VENT VENTSAN., DOMESTIC &TO STORMVENT 150# &WATER EXCEPTSTORM IN IN INBUILDING AIR AIR PLENUMS PLENUM TO BLOCK WALL WATERTIGHT AIR GAP VACUUM SCHEDULE 40 SOLID WALL PVC with SOLVENT CEMENTED DRAINAGE PATTERN FITTINGS MEMBRANE WHEN BREAKING PORTS ASTM D-2665 USED, SEE ARCH. DWGS. FINISH FLOOR SAFE PAN COPPER PIPE - SOFT DRAWN TYPE "K" ASTM B88 (SEE NOTE "A") PIPE TO FLOOR DRAIN

COPPER PIPE - HARD DRAWN TYPE "L" ASTM B88 1/2" CW REVERSIBLE CLAMPING with CAST ASTM B16.18 OR WROUGHT ASTM B16.22 SOLDERED JOINT COLLAR IN HIGH POSITION STANDARD WEIGHT NO-HUB CAST IRON ASTM-888 5 WATER HEATER DETAIL with HEAVY DUTY TYPE 304 STAINLESS STEEL COUPLINGS FLASHING COLLAR P0.1 NO SCALE CAULKED OUTLET STRUCTURAL CONNECTION WITH PRE-FAB FLOOR SLAB RUBBER WASTE, VENT & WATER CONNECTION SCHEDULE CLAMPING COLLAR SHOWN WATER HEATER SCHEDULE IN LOW POSITION FIXTURE WASTE VENT COLD WATER HOT WATER NOTES NOTE "A": PLAN STORAGE 1 " G.C. SHALL SLOPE FLOOR-1/2" FROM MANUFACTURER MODEL BTU INPUT VOLTS/PH WATER CLOSETS (TANK) 4" 2" 2 NO-HUB CONNECTION MARK (GAL.) 1 FINISH FLOOR ELEVATION A MINIMUM WATER CLOSETS (FLUSH VALVE) 4" 2" 1 4" (CONTRACTORS OPTION) OF 4'-0" BEYOND DRAIN. (1/8"PER FT.) GWH 1 " 1 " 1 " 1 " A.O. SMITH BTX-100 50 100,000 120/1 LAVATORIES 1 4 1 4 2 2 1 3 URINALS 2" 2" 4" 1. RECOVERY 115 G.P.H. @ 100 DEGREE TEMPERATURE RISE. 1 " 1 " 4 NOTES: MOP BASINS 3" 2" 2 2 FLOOR DRAIN "FD-1" (FINISHED AREAS) 2. PIPING CONFIGURATION SHALL BE CONFIRMED WITH MANUFACTURE PRIOR TO 1 " 1 " SINKS 2" 2" 2 2 P0.1 NO SCALE INSTALLATION. NOTES: 3. PROVIDE INSTALLATION OF ALL COMPONENTS PER MANUFACTURES WRITTEN INSTRUCTIONS, COMPLETE AND READY FOR START-UP BY FACTORY REPRESENTATIVE.

18" SQUARE PROVIDE E.J. CONC. PAD. HEAVY DUTY COVER WHEN PAD IS CHECK VALVE MINIMUM OF 4" OF PLACED IN CONC. 1" CLASS C TRAFFIC RATED MANUAL AIR FINISH GRADE (SEE PLAN BEDDING CONC. ALL PAVEMENT DUCTILE IRON SLOTTED VENT (TYP) FOR MATERIAL) AROUND BY G.C. GRATE 1-1/2" GAUGE COCK AND 1 " 1 4 BALL VALVE PRESSURE GAUGE 18" JOSAM 57000-X-CI ZURN Z882 "PERMA- FULL PORT (TYP) 1 " ADJUSTABLE CO. 1 4 PRV REQUIRED IF HOSE END DRAIN VALVE TRENCH" PRE-SLOPED PRESSURE EXCEEDS DRAIN SYSTEM WITH VACUUM BREAKER UNION (TYP) BRONZE PLUG 4" RISER AS REQUIRED 65PSI DOWN STREAM OF RPBP

LOCKDOWN BOLT VARIES BALL VALVE 8" 14" TO NO-HUB CONNECTION 1-1/2" RPZ-1 12" RPZ-130" MIN ABOVE ANCHOR/LEVELING STRAINER FLOOR STRAPS/RODS WATER WATER WATER NOTE: POUR PAD AFTER TANK TANK TANK FINAL GRADE MATERIAL TO SYSTEM 1/8 BEND #3 #2 #1 IS IN PLACE PIPE INDIRECT WASTE AND GWH-1 4" Ø BOTTOM OUTLET MIN 4" CONE TO FLOOR DRAIN CONNECTION NRS GATE WYE WITH 1/8 BEND 1 " VALVE 1 4 PROVIDE LINK-SEAL AT SOIL SUBGRADE PIPE IN RUN WALL PENETRATION 1 " 1 4 1-1/2" DOMESTIC WATER SERVICE NOTE: COORDINATE ALL INSTALLATION PROVIDE DRAIN IF NOT REQUIREMENTS WITH MANUFACTURER PROVIDED WITH TANK (TYP)

6 EXTERIOR C.O. DETAIL 7 WATER SERVICE DETAIL 8 TRENCH DRAIN DETAIL 9 P0.1 NO SCALE P0.1 NO SCALE P0.1 NO SCALE WATER TANK PIPING DIAGRAM 06-21-2017 P0.1 NO SCALE

WATER TANK SCHEDULE PLAN STORAGE MANUFACTURER MODEL MARK (GAL.)

WT LOCHINVAR RJA200 200 # NOTES: 1. INSULATED, GLASS LINED TANK, WITH MAGNESIUM ANODE RODS 4" VTR

3"V

3"V 1 1 2" PUMP DISCHARGE PIPING TO STORM; 3"V COORDINATE WITH 1 " 1 2 V CIVIL 1 " 1 2 W B.V. L-2 BASIN LID 2"V C.V.

2"V 3"V 4" SAN 2"V 2"V WC-2

1 " 1 " 1 2 W 3" VTR 1 2 V 2" L-2 4" SAN

WC-2 GROUT ALL 2"V AROUND 4" W 4" SAN SH-1 4" SN.

BASIN, PROVIDE C.O. WITH SUMP PUMP 4" SUB-SOIL SH-1 DRAIN PIPING 4" VTR 1 " 2"V 1 2 V 2"V 1 " 18" 1 2 W MIN. WC-1 L-2 SUMP PUMP 2"V 2"V UNION 2"V GRAVEL 1 " 1 2 W BACKFILL 2"V 2"V 4" SAN 1 S-1

WSD-1 SH-1 1 " DISPOSAL 4" THICK CONC. F.C.O. 1 " 1 2 V 1 2 V F.C.O. 1 " BOTTOM 4" SAN 1 2 W C.O. 4" SAN L-2 2"V WC-2 1 SUMP PUMP DETAIL FD-1 1 " S-2 1 2 V P0.2 NO SCALE 4" SAN 1 " 1 2 3"FD-1 4" SAN W 4" SAN 4" SAN 2" W 4" SAN 4" W F.C.O. 3"FD-1 1 4" W 4" W 3"FD-1 4" SAN 3" SAN 4" SAN 4" W

3" SAN 4" SAN FD-1 G.C.O. FOUNDATION WALL SEE STRUCTURAL DWGS. 6" SAN 2 SANITARY, WASTE, VENT RISER DIAGRAM 3 SANITARY, WASTE, VENT RISER DIAGRAM P0.2 NO SCALE P0.2 NO SCALE "MIRAFI" #140S FILTER CLOTH (TYP. @ UNDERFLOOR)

3/4" CLEAN GRAVEL BACKFILL 6" MIN. ALL AROUND PIPE BY PLBG. CONTR. (TYP. @ UNDERFLOOR)

RIGID PVC DRAIN PIPING WITH L-2 PERFORATIONS LAYED DOWN ENGINEERED SHOCK ABSORBER (TYP) (TYP. @ UNDERFLOOR)

PERIMETER WC-2 CONCRETE FOOTING SEE STRUCTURAL DWGS. L-2 1 " WC-2 2 1 WH-1 2" UNDERFLOOR 1 2"

1 4 2" SUB SOIL DRAIN DETAIL 1 3 " 2" 4 P.02 NO SCALE 1 " 2 SH-1 3 4" 3 SH-1 4"

3 4" 3 4" 1 2" PROVIDE LINK-SEAL AT 1" WALL PENETRATION WC-1 1 1" S-1 2" L-1 1 2" SET TO 1 3 " 2" 4 DISHWASHER 0.5GPM 1 2" 1 SH-1 TO MAIN 2" 3 " 4 1" WH-1

1 " 2 1" HR-1 1" 1 1" 2" 1 " 1 " 2 2 1 S-2 2" WSD-1 WH-1 3 " BALL VALVE 1 4 IMB-1 1 SET TO 1 " WC-2 2" 2" 1 2 0.5GPM CHECK VALVE SET TO BRANCH L-2 1 IMB-1 BALANCING VALVE 2" 1 " 1 " 1 " 1GPM 1 4 1 4 1 4 TO GWH-1 IMB-1 06-21-2017 3 4"

3 " 1 4 2" 1"

3 4" 1" HR-1 1 " 1 4 TO STORAGE TANKS

5 H.W.R. BRANCH DETAIL WH-1 1" P0.2 NO SCALE

3 4"

6 DOMESTIC WATER RISER DIAGRAM P0.2 NO SCALE WH-1

HR-1 3/4" HW FB 1" CW FB 2

CLOSET 119

8 8 P0.1 P0.1

CLOSET 118

4" SAN F.C.O. 4" SAN

3"V UP TO 3" VTR

WH-1 2"V # PLAN NOTES - PLUMBING

1. ROUTE 6" SANITARY LINE TO OIL / SAND INTERCEPTOR, SEE MEP1.0 FOR 3/4" CW FB CONTINUATION.

CLOSET 2. HR-1 TO BE MOUNTED 40" A.F.F. TO THE CENTERLINE OF THE TOP MOUNTING BOLT ON REEL. VERIFY EXACT LOCATION WITH OWNER. 117

EQUIPMENT ROOM 3. ROUTE 3" VENT FROM OIL / SAND INTERCEPTOR, SEE MEP1.0 FOR CONTINUATION. 120 BEDROOM #4 BEDROOM #3 4. PROVIDE VALVED 1/2" HOT WATER BELOW SINK FOR CONNECTION TO 113 114 DISHWASHER. ROUTE DISHWASHER DISCHARGE HOSE IN APPROVED MANNER AND CONNECT TO AUXILIARY CONNECTION ON DISPOSAL. FD-1

DINING AREA 4" VTR 115 F 4" VTR 3 3" VTR P0.2 4 RESTROOM #1 CORRIDOR 3 1/2" HW FB 1-1/2" L-2 112 S-1 ISLAND VENT S-2 111 P0.2 2"V UP TO 3" VTR 1/2" CW FB 1/2" CW FB 1-1/2" W DN & UP TO 1-1/2" V 2" W CLOSET KITCHEN WC-2 107 116 4" SAN SH-1 1-1/2" V. 4" SAN WC-1 L-1 3/4" HW FB 4" 3/4" CW FB F.C.O. SAN DN. 2" W 4" SAN DN. 2 IT CLOSET H.C. 8 8 106 RESTROOM P0.2 WC-2 CLOSET 108 P0.1 P0.1 IMB-1 IMB-1 IMB-1 1-1/2" V SH-1 109

3" V L-2 RESTROOM #2 FB CORRIDOR 110 105 CLOSET 2"V 102 4" SAN 4" SAN TD-1 TD-1

FD-1

3"V 4" SAN

BEDROOM #2 BEDROOM #1 LIVING ROOM 2 104 103 101 3/4" CW FB 3"V. UP HR-1 3/4" HW FB 1" CW FB WH-1 2"V FB F.D.C. WH-1

3" V.

06-21-2017

3 1

N FIRST FLOOR PLAN - PLUMBING SCALE: 1/4" = 1'-0" 1" CW, 3/4" HW, & HWR UP

GENERAL NOTES - PLUMBING

A. ALL UNDERFLOOR PIPING SHALL BE TYPE K WITH SILVER SOLDERED JOINTS.

B. ALL HW & HWR UNDERFLOOR PIPING SHALL BE INSULATED.

C. PROVIDE 12" MINIMUM SAND ENCASEMENT AND A MINIMUM OF 12" TO DAYLIGHT BELOW FLOOR FOR ALL UNDERFLOOR PIPING. CONFIRM LOCATION 3/4" CW UP

# PLAN NOTES - PLUMBING

1. 6" SANITARY LINE, SEE MEP1.0 FOR CONTINUATION.

2. 4" FIRE SERVICE, SEE MEP1.0 FOR CONTINUATION. STAIRS 3. 1-1/2" WATER SERVICE, SEE MEP1.0 FOR CONTINUATION. 004 4. PLUMBING CONTRACTOR SHALL PROVIDE AND INSTALL RPBP-2 FOR CONNECTION BY THE FIRE PROTECTION CONTRACTOR. COORDINATE RPBP-2 AND ALL ASSOCIATED PIPING, VALVES, ETC. WITH FIRE PROTECTION DESIGNER PRIOR TO INSTALLATION.

5. 1/2" CW DOWN TO HUMIDIFIER CONNECTION.

WORKOUT ROOM 001

1/2" CW, HW, & HWR UP 1/2" CW, HW 3/4" CW UP 1/2" CW & HW UP 1/2" HW UP PROVIDE LINK-SEAL AT WALL PENETRATION B 3/4" CW & HW UP

F.C.O. 1/2" CW UP

3" V. UP 4" B 4" SAN FROM 4" SAN FROM ABOVE ABOVE 1/2" CW UP 2 SH-2 P0.2 1/2" CW 1/2" CW UP & HW UP RESTROOM 2 002

WC-2 1 " 2 FD-1 GWH 1 L-2 4 FD-1

F.C.O. WT 3

LAUNDRY WT SP 003 4" B 2 1

FD-1 WT WSD-1 RPBP-1 1 1" CW & 3/4" HW UP RPBP-2 4 FOUNDATION DRAIN PERFORATED PVC PIPE, SEE DETAIL. G.C.O. 3/4" CW UP

6" SAN

06-21-2017 3 2 1

N BASEMENT PLAN - PLUMBING SCALE: 1/4" = 1'-0" ELECTRICAL CRITERIA LOW VOLTAGE SYMBOL LIST ELECTRICAL SYMBOL LIST ELECTRICAL ABBREVIATIONS 1. BEFORE SUBMITTING A PROPOSAL, THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE OF WORK 16. TOGGLE SWITCHES SHALL BE 20 AMP, 120/277 VOLT, SPECIFICATION GRADE, SILENT ACTION, SINGLE OUTLETS AND FAMILIARIZE THEMSELVES WITH ALL SITE CONDITIONS. ELECTRICAL CONTRACTOR SHALL POLE OR THREE-WAY. DUPLEX RECEPTACLES SHALL BE 20 AMP, 125 VOLT, GROUNDING TYPE, VOICE OUTLET BOX 1PH SINGLE PHASE (LINE-LINE) CAREFULLY EXAMINE THE ENTIRE SET OF CONSTRUCTION DOCUMENTS. SUBMISSION OF A BID WILL SPECIFICATION GRADE. GROUND FAULT INTERRUPTING RECEPTACLES SHALL BE 20 AMP, 125 VOLT, 3PH 3 PHASE (L1-L2-L3) DATA OUTLET BOX SINGLE RECEPTACLE (+18") ACKNOWLEDGE THE ELECTRICAL CONTRACTOR HAS VISITED THE SITE AND EXAMINED ALL SPECIFICATION GRADE, WITH 5MA TRIP RESET AND TEST SWITCH IN FACE. ALL DEVICES SHALL BE A 3PL THREE POLE 3PSN 3 POLE SOLID NEUTRAL CONSTRUCTION DOCUMENTS AND THE BID INSTRUCTIONS. ALL ELECTRICAL WORK IN THE STANDARD COLOR. DEVICE COVER PLATES IN FINISHED AREAS SHALL BE SPECIFICATION GRADE, VOICE/DATA OUTLET BOX DUPLEX RECEPTACLE (+18") CONSTRUCTION DOCUMENTS, INCLUDING THAT REQUIRED BY OTHER DIVISIONS, GENERALLY PHENOLIC SMOOTH PLASTIC, OF COLOR MATCHING DEVICE, AND WITH CONFIGURATION REQUIRED BY (60/50/3) AMP SIZE/FUSE SIZE/POLES INSTALLED BY THE ELECTRICAL CONTRACTOR, WHERE EQUIPMENT IS FURNISHED BY OTHERS, SHALL DEVICE AND ARRANGEMENT. DEVICE COVER PLATES IN UNFINISHED AREAS SHALL BE ANODIZED T CATV OUTLET BOX QUADPLEX RECEPTACLE (+18") A AMPERE(S) BE INCLUDED. IT IS EXPRESSLY UNDERSTOOD THAT THIS PROPOSAL IS BASED ON THE ABOVE ALUMINUM OR STEEL. COORDINATE COLOR OF DEVICES AND COVER PLATES WITH THE OWNER PRIOR WP AIC AMPERES INTERRUPTING CAPACITY WEATHERPROOF RECEPTACLE REQUIREMENTS AND THAT IT COVERS MATERIAL AND LABOR NECESSARY TO COMPLETE THE SCOPE TO ORDERING. DEVICES AS MANUFACTURED BY HUBBELL, LEVITON, PASS AND SEYMOUR, COOPER OR CCTV CAMERA AFCI ARC FLASH CIRCUIT INTERRUPTER OF WORK DESCRIBED HEREIN. EAGLE ARE ACCEPTABLE. WEATHERPROOF RECEPTACLES SHALL BE PROVIDED WITH “IN USE” TYPE GFI TYPE RECEPTACLE AFF ABOVE FINISHED FLOOR COVER TO COMPLY WITH NEC SECTION 406.8 (B) (1) FOR 15 AND 20 AMP RECEPTACLES IN A WET F MANUAL PULL STATION AHJ AUTHORITY HAVING JURISDICTION 2. ELECTRICAL CONTRACTOR SHALL PERFORM WORK IN A SAFE MANNER. COMPLY WITH APPLICABLE LOCATION. AUDIO/VISUAL ALARM HORN (+80") ISOLATED GROUND TYPE D.R. AHU AIR HANDLING UNIT OSHA SAFETY GUIDELINES DURING THE COURSE OF PERFORMING THE WORK DESCRIBED IN THESE F TR AL ALUMINUM CONSTRUCTION DOCUMENTS. 17. TEST ELECTRICAL SYSTEM AND BRANCH CIRCUIT WIRING FOR SHORT CIRCUITS. MEGGER TEST TAMPER RESISTANT RECEPTACLE H AUDIO/VISUAL MINI ALARM HORN ALT ALTERNATE FEEDERS AND ENSURE LOW IMPEDANCE GROUND SYSTEM. USB ATS AUTOMATIC TRANSFER SWITCH USB CHARGER RECEPTACLE 3. ELECTRICAL WORK SHALL BE PROVIDED TO COMPLY WITH NFPA 70, THE 2014 NATIONAL ELECTRICAL STROBE LIGHT ONLY (+80") AWG AMERICAN WIRE GAUGE CODE (NEC), AS WELL AS ALL APPLICABLE LOCAL ORDINANCES, STATE LAWS AND FEDERAL LAWS. 18. SERVICE AND PANEL FEEDER WIRING: USE TYPE THWN CABLE IN A RACEWAY. PROVIDE THHN/THWN SWITCHED RECEPTACLE BB BASEBOARD HEATER CABLE FOR INTERIOR BRANCH CIRCUIT WIRING UNLESS OTHERWISE NOTED. DESIGN IS BASED ON F SMOKE DETECTOR (CEILING MTD.) S BFF BELOW FINISHED FLOOR 4. PROVIDE ALL REQUIRED INSPECTIONS AND RE-INSPECTIONS. PROVIDE A CERTIFICATE OF INSPECTION COPPER CONDUCTORS AND THE MINIMUM SIZE OF #12 AWG. EXCEPTION: ALUMINUM MAY BE USED FOR F THERMAL DETECTOR (CEILING MTD.) D.R. - TOP HALF SWITCHED BMS BUILDING MANAGEMENT SYSTEM AT THE PROJECT COMPLETION. CONDUCTORS #1 AWG AND LARGER. SEE FEEDER SCHEDULE ON DRAWINGS. PROVIDE INCREASED T CKT CIRCUIT WIRE SIZES, PER THE NEC, TO COMPENSATE FOR NO GREATER THAN A 3% VOLTAGE DROP WHEN THE FLUSH FLOOR BOX. SEE PLANS. F CARBON MONOXIDE DETECTOR F CLG CEILING 5. ELECTRICAL CONTRACTOR SHALL UNDERSTAND THE PRODUCT, MEANS AND METHODS OF FARTHEST OUTLET IS GREATER THAN 100' FROM THE PANEL TERMINATION. WIRING SHALL BE IN CO C/B CIRCUIT BREAKER INSTALLATION. ALL CONDUCTORS AND EQUIPMENT SHALL BE APPROVED AND LISTED BY A NRTL CONDUIT SYSTEMS. SPLICE WIRES #6 AWG AND LARGER WITH APPROVED SOLDERLESS CONNECTORS SURFACE FLOOR RECEPTACLE. SEE PLANS. F SMOKE DETECTOR WITH SOUNDER BASE S CCTV CLOSED CIRCUIT TELEVISION (NATIONALLY RECOGNIZED TESTING LABORATORY). LISTED AND LABELED EQUIPMENT SHALL BE TAPED AND INSULATED. SPLICE SMALLER WIRES WITH MECHANICAL CONNECTORS SUCH AS SS COND CONDUCTOR INSTALLED AND USED IN ACCORDANCE WITH ANY INSTRUCTIONS INCLUDED IN THE LISTING AND "SCOTCHLOCK". TYPE “MC” CABLE MAY ONLY BE USED FOR BRANCH CIRCUITS WHERE APPROVED BY F SUPPLY AIR SMOKE DETECTOR SPECIAL PURPOSE OUTLET. SEE PLANS. LABELING IN ADDITION TO THE WRITTEN INSTALLATION INSTRUCTIONS AND METHODS OF INSTALLATION THE NEC AND ACCEPTABLE TO THE AHJ BUT SHALL NOT BE USED FOR FEEDERS TO PANELS OR SA C CONDUIT (SEE RACEWAYS AND CONDUCTORS) VOICE OUTLET BOX AS PUBLISHED BY THE MANUFACTURER OF THE EQUIPMENT OR MATERIAL PROVIDER. THE ELECTRICAL TRANSFORMERS, FOR HOME RUNS OR AT ANY THROUGH-WALL PENETRATIONS. “TYPE NM” CABLE MAY F RETURN AIR SMOKE DETECTOR w/ SAMPLING TUBE CP CONTROL PANEL RA CONTRACTOR SHALL OBTAIN THE INSTALLATION INSTRUCTIONS AND REQUIREMENTS PRIOR TO BID. BE USED IN WOOD STRUCTURE BUILDINGS AND WHERE APPROVED BY THE NEC AND ACCEPTABLE TO CU COPPER F R.T.U./A.H.U. SHUTDOWN RELAY DATA OUTLET BOX CUH CABINET UNIT HEATER ALL RFI AND CLARIFICATIONS OF SCOPE PRESENTED DURING CONSTRUCTION WHERE THE THE AHJ. SR CONTRACTOR HAS NOT PREVIOUSLY OBTAINED THIS INFORMATION FOR BIDDING PURPOSES WILL NOT R.A. DUCT MTD. SMOKE DETECTOR CT CURRENT TRANSFORMER F VOICE/DATA OUTLET BOX BE CAUSE FOR ADDITIONAL COSTS OR PROJECT DELAY. 19. PROVIDE EMT CONDUIT FOR INTERIOR WIRING WHERE PHYSICAL DAMAGE IS NOT A CONSIDERATION. RTS REMOTE TEST STATION w/ KEY LOCK DC DIRECT CURRENT MINIMUM CONDUIT SIZE IS 3/4" EXCEPT FOR FLEXIBLE CONDUIT TO FIXTURES, MOTORS, EQUIPMENT, POWER POLE. SEE PLANS. DDC DIRECT DIGITAL CONTROL F CONTROL MODULE 6. PROVIDE SERVICE AND EQUIPMENT GROUNDING SYSTEMS IN ACCORDANCE WITH THE NEC. THE ETC., WHICH MAY BE 1/2". CONDUIT SHALL BE CONCEALED WHEREVER POSSIBLE AND SHALL BE RUN CM DISC DISCONNECT CONDUIT SYSTEM SHALL FORM A CONTINUOUS PATH FOR GROUND AND SHALL BE SAFETY GROUNDED PARALLEL OR PERPENDICULAR TO BUILDING WALLS, CEILINGS AND STRUCTURE. EMT CONDUIT MAY BE J JUNCTION BOX - WALL MTD. DN DOWN F MONITOR MODULE AT THE DISTRIBUTION AND BRANCH CIRCUIT PANELS. PROVIDE GROUNDING CONDUCTORS WHERE USED FOR PANEL FEEDERS ABOVE THE FLOOR UNLESS OTHERWISE NOTED. HWC OR GRS SHALL BE MM DPST DOUBLE POLE SINGLE THROW J JUNCTION BOX - CEILING MTD. INDICATED. PROVIDE A NEUTRAL AND GROUND WIRE AT EACH TOGGLE SWITCH ROUGH-IN. PROVIDE USED FOR CONDUIT EXPOSED TO WEATHER. SCHEDULE 40 PVC CONDUITS MAY BE USED BELOW F DUAL MONITOR MODULE DR DUPLEX RECEPTACLE GROUNDING CONDUCTORS FOR PHONE UTILITY DEMARCATION AND UTILITY METERING EQUIPMENT. GRADE OR BELOW THE FLOOR. FMC SHALL BE USED FOR CONNECTIONS TO EQUIPMENT SUBJECT TO DMM P MODULAR FURNITURE WHIP - POWER E EMERGENCY COORDINATE WITH UTILITY COMPANIES PRIOR TO STARTING WORK. VIBRATION, 36” MAXIMUM IN LENGTH, EXCEPT FOR EXTERIOR, DAMP AND WET LOCATIONS WHERE LFMC F FLOW SWITCH (E) EXISTING FS SHALL BE USED. ALL OUTLET, SPLICE, PULL, AND DEVICE BOXES SHALL BE PROVIDED TO COMPLY WITH T MODULAR FURNITURE WHIP - VOICE/DATA EBB ELECTRIC BASE BOARD 7. PRIOR TO BIDDING THIS PROJECT, THE ELECTRICAL CONTRACTOR SHALL CONTACT THE ELECTRICAL THE NEC FILL REQUIREMENTS. THE MINIMUM CONCEALED SIZE ELECTRICAL BOX IS A METALLIC F PRESSURE SWITCH PS EC ELECTRICAL WORK CONTRACTOR UTILITY COMPANY. ELECTRICAL CONTRACTOR SHALL CONFIRM THE PROPOSED ELECTRICAL SERVICE 4”X4”X2” WITH THE REQUIRED FLUSH FRAME FOR ANY POWER OR LOW VOLTAGE DEVICE - NO (+XX") MOUNTING HEIGHT TO CENTERLINE F SUPERVISORY VALVE EF EXHAUST FAN TO THE BUILDING WITH THE UTILITY COMPANY. ELECTRICAL CONTRACTOR SHALL PROVIDE, BUT IS NOT EXCEPTIONS. SV EMS ENERGY MANAGEMENT SYSTEM LIMITED TO, CONDUIT, CABLE, CONNECTIONS, GROUNDING EQUIPMENT, METER BASE, POTENTIAL SWITCHES C C SUBSCRIPT - DENOTES CEILING MOUNTED EMT ELECTRICAL METALLIC TUBING TRANSFORMERS, CURRENT TRANSFORMERS, HARDWARE, CABINETS AND RELATED EQUIPMENT 20. PROVIDE FRAMEWORK, STRUT SYSTEMS, THREADED HANGING RODS, BRACES, X S SINGLE POLE SWITCH (+42") EUH ELECTRIC UNIT HEATER REQUIRED FOR A COMPLETE ELECTRICAL SERVICE FROM THE UTILITY COMPANY SECONDARY AND ACCESSORIES WHERE REQUIRED TO HOLD EQUIPMENT IN FINAL POSITION. PROVIDE STEEL F.A.A.P. FIRE ALARM ANNUCIATOR PANEL EWC ELECTRIC WATER COOLER TERMINATION TO THE MAIN SERVICE EQUIPMENT BUS. IT SHALL BE THE RESPONSIBILITY OF THIS SHAPES AND FRAMES TO SUPPORT WALL MOUNTED EQUIPMENT WHERE NORMAL WALL STRENGTH x3 3-WAY SWITCH (+42") S EWH ELECTRIC WATER HEATER CONTRACTOR TO COORDINATE SERVICE ENTRANCE ELECTRICAL WORK WITH THE UTILITY COMPANY MAY BE INADEQUATE. ELECTRICAL DEVICES, MOTOR STARTERS, DISCONNECT SWITCHES, ETC., SHALL F.A.C.P. FIRE ALARM CONTROL PANEL x4 EXIST EXISTING PRIOR TO THE START OF CONSTRUCTION. SUBMIT SHOP DRAWINGS AND COORDINATE WITH THE BE SUPPORTED INDEPENDENT OF AND ISOLATED FROM EQUIPMENT VIBRATION. S 4-WAY SWITCH (+42") F FLUORESCENT UTILITY COMPANY FOR THE INSTALLATION OF THE METER, CURRENT TRANSFORMERS, POWER TRANSFORMERS, METERING CIRCUIT, MAIN SWITCH, AND INCLUDE ALL REQUIREMENTS OF THE UTILITY 21. PROVIDE LIGHT FIXTURES AS LISTED ON LIGHTING FIXTURE SCHEDULE. PROVIDE NECESSARY S SWITCH WITH PILOT LIGHT FA FIRE ALARM COMPANY'S RULES AND REGULATIONS IN THE BID THAT ENSURES A COMPLETE, APPROVED MOUNTING HARDWARE FOR A COMPLETE INSTALLATION. ASSEMBLE ALL LIGHT FIXTURES SHIPPED TO FAAP FIRE ALARM ANNUNCIATOR PANEL x COMB. SWITCH/DUPLEX RECEPTACLE ELECTRICAL SERVICE INSTALLATION. SUBMISSION OF A BID ACKNOWLEDGES YOU HAVE PERFORMED THE PROJECT SITE. PROVIDE LAMPS, BALLASTS, AND NOTED SPECIAL CONTROLS. PROVIDE A NEUTRAL S FACP FIRE ALARM CONTROL PANEL FCU FAN COIL UNIT THIS CONTRACT REQUIREMENT AND HAVE INCLUDED ALL NECESSARY MATERIALS AND LABOR FOR A AND GROUND WIRE AT EACH TOGGLE SWITCH ROUGH-IN. ALL LIGHTING FIXTURES SHALL BE PROVIDED TO x S THERMAL OVERLOAD SWITCH COMPLETE AND OPERABLE ELECTRICAL SERVICE. WITH CODE APPROVED MEANS OF SUPPORT, EARTHQUAKE CLIPS AND/OR INSTALLED IN ACCORDANCE FDR FEEDER M x WITH THE BUILDING CODE TO MEET SEISMIC RESTRAINT REQUIREMENTS. REFER TO THE STRUCTURAL S MANUAL MOTOR SWITCH FPC FIRE PROTECTION CONTRACTOR 8. ELECTRICAL CONTRACTOR SHALL PROVIDE FIELD COORDINATION WITH OTHER TRADES; SYSTEMS AS CRITERIA FOR DESIGN CONSIDERATIONS CONCERNING SEISMIC SWAY BRACING AND ANCHORING. CABINET - BACK OF BOX FSD FIRE/SMOKE DAMPER L x SHOWN ARE DIAGRAMMATIC AND GIVE THE GENERAL ARRANGEMENT AND LOCATIONS ONLY. S LOW-VOLTAGE SWITCH FSC FOOD SERVICE CONSULTANT ELECTRICAL CONTRACTOR SHALL COMPLETELY REVIEW THE ENTIRE SET OF CONSTRUCTION 22. ELECTRICAL CONTRACTOR SHALL CUT AND PATCH ROOF, FLOORS, WALLS, AND CEILINGS WHERE FTU FAN TERMINAL UNIT K x DRAWINGS FOR DETAILS OF CONSTRUCTION PRIOR TO STARTING WORK. ROUGH-IN OF ELECTRICAL REQUIRED TO INSTALL NEW ELECTRICAL BOXES, FIXTURES, AND RACEWAY SYSTEMS. SURFACES S KEYED SINGLE POLE SWITCH (+42") FV FIELD VERIFY

FIXTURES, EQUIPMENT, CONDUIT, CABLES, ATTACHMENTS, AND HANGERS SHALL BE BASED ON THIS SHALL BE PATCHED AND LEFT READY FOR FINAL SCHEDULED FINISH. ROOFING WORK SHALL BE K x3 GC GENERAL WORK CONTRACTOR S KEYED THREE-WAY SWITCH (+42") REVIEW. EXACT LOCATIONS AND FINAL LAYOUT SHALL BE DETERMINED IN THE FIELD. PROVIDE ALL PERFORMED BY A QUALIFIED ROOFING CONTRACTOR THAT MAINTAINS THE ROOF WARRANTY. ALL GF GAS FURNACE NECESSARY EQUIPMENT, FITTINGS, HANGERS, BOXES, SUPPORTS, OFFSETS AND ACCESS PANELS REQUIRED ROOFING WORK DUE TO ELECTRICAL SCOPE OF WORK SHALL BE INCLUDED IN THE WP S WEATHERPROOF SWITCH GFI GROUND FAULT INTERRUPTER REQUIRED FOR A COMPLETE INSTALLATION IN ALL RESPECTS. THE ELECTRICAL CONTRACTOR'S MEANS ELECTRICAL CONTRACTOR'S BID. GRD GROUND T AND METHODS OF INSTALLATION SHALL PROVIDE FOR OPERATING EFFICIENCY, NEATNESS OF S TIME SWITCH GRS GALVANIZED RIGID STEEL CONDUIT APPEARANCE, EASE OF MAINTENANCE, AND NEC COMPLIANCE. THE ELECTRICAL CONTRACTOR SHALL 23. ELECTRICAL CONTRACTOR SHALL PROVIDE A FULLY FUNCTIONAL NFPA 72 COMPLIANT FIRE ALARM EACH FACTORY MOUNTING HOLE - GWH GAS WATER HEATER S MOTION DETECTOR SWITCH PREPARE DIMENSIONED FIELD ERECTION DRAWINGS, WHERE REQUIRED, FOR USE BY THE INSTALLERS, SYSTEM. PROVIDE NEW FACP, DIGITAL COMMUNICATOR, CONTROL RELAYS, MONITORING RELAYS, PROVIDE 3/8" DIA ANCHOR ROD HP HORSEPOWER TO ENSURE PROPER INSTALLATION AND COORDINATION. THE ELECTRICAL CONTRACTOR SHALL TAKE DETECTION DEVICES, WIRING, REMOTE TEST STATIONS, AND APPLICABLE ADA COMPATIBLE SIGNALS. IMBEDDED 4" DEEP, WITH HILTI HWC HEAVY WALL RIGID CONDUIT THEIR OWN MEASUREMENTS AT THE BUILDING, AND BE RESPONSIBLE FOR THE CORRECT LAYOUT, D DIMMER SWITCH PROGRAM AND TEST THE SYSTEM FOR CORRECT OPERATION AND NOTIFY THE INSPECTION HIT-HY 150 ADHESIVE, NUT AND HWRCP HOT WATER RETURN CIRCULATING PUMP INTERPRETATION, AND USE OF ALL SIZES AND DIMENSIONS . AUTHORITIES FOR WITNESS TO THE TEST AT PROJECT COMPLETION. WIRING SHALL BE RUN OPEN WASHER OR PROVIDE LAG SCREW FIXTURES HZ HERTZ ABOVE CEILINGS IN AN APPROVED SUPPORT SYSTEM WITH PLENUM-RATED CABLES.PHONE LINES WILL IN STUD OR BLOCKING IG ISOLATED GROUND 9. REVIEW ARCHITECTURAL DRAWINGS FOR ALL FIRE RATINGS AND FIRE RATED ASSEMBLIES PRIOR TO BE PROVIDED BY THE OWNER AT THE DEMARCATION POINT, EC SHALL EXTEND TO THE RECESSED DOWN LIGHTING FIXTURE IMC INTERMEDIATE METALLIC CONDUIT BIDDING THE PROJECT. PROVIDE FIRE STOP AT EACH RATED WALL, FLOOR, AND CEILING-ROOF COMMUNICATOR LOCATION. JB JUNCTION BOX ASSEMBLY PENETRATION. FIRE STOP SYSTEMS SHALL BE MANUFACTURED BY “3M”. PROVIDE IN WALL MOUNTED LIGHT FIXTURE kVAR KILOVAR(S) STRICT COMPLIANCE WITH THE MANUFACTURER'S APPLICATION DETAILS AND INSTRUCTIONS. PROVIDE 24. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL VOICE SYSTEM WIRING, RJ45 JACKS, RACEWAYS AND TYPICAL FOR WALL MOUNTED EQUIPMENT (FIRE ALARM PENDANT LIGHT FIXTURE kVA KILOVOLT AMPERE(S) TAGGED CERTIFICATIONS AT EACH PENETRATION. PROVIDE SHOP DRAWINGS FOR REVIEW WITH THE CABLE TESTING. ALL VOICE WIRING SHALL TERMINATE AT THE MAIN TEB. CABLE TERMINATION SHALL CONTROL PANELS, PANELBOARDS, METER BASE, DISCONNECT KW KILOWATT(S) U.L. LISTING AND TEST CRITERIA. PROVIDE FIRE STOPPING WHERE REQUIRED BY THE AHJ. EQUAL BE PROVIDED BY THE ELECTRICAL CONTRACTOR UNDER DIRECTION OF THE EQUIPMENT SUPPLIER. SWITCHES, TRANSFER SWITCHES, ETC.) 2x2 / 2x4 LIGHT FIXTURE SYSTEMS AS MANUFACTURED BY “SPEC SEAL” OR “HILTI” WILL BE ACCEPTABLE. ALL VOICE WIRING SHALL BE CATEGORY 6 WITH A SEPARATE HOMERUN FOR EACH VOICE OUTLET LCP LIGHTING CONTROL PANEL SHOWN AND SHALL BE A DIFFERENT COLOR THAN THE DATA SYSTEM WIRING. WIRING SHALL BE RUN LIGHT FIXTURE WITH EMERGENCY BATTERY LC LIGHTING CONTACTOR 10. PROVIDE CONDUIT, CABLES, AND ELECTRICAL ASSEMBLY PENETRATIONS OF NON-RATED ASSEMBLIES OPEN ABOVE CEILINGS IN AN APPROVED SUPPORT SYSTEM WITH PLENUM-RATED CABLES. PANELBOARD MAX MAXIMUM WITH DRAFT STOPPING, OR SMOKE BARRIER SEALANT SYSTEMS. THROUGH PENETRATION SEALANT EXIT SIGN WITH FACES & ARROWS MC MECHANICAL WORK CONTRACTOR SYSTEMS SHALL BE MANUFACTURED BY “3M”. PROVIDE IN STRICT COMPLIANCE WITH THE 25. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL DATA SYSTEM WIRING, RJ45 JACKS, RACEWAYS AND 1 SEISMIC ANCHORAGE DETAIL MIC MICROPHONE MANUFACTURER'S APPLICATION DETAILS AND INSTRUCTIONS. PROVIDE DRAFT STOPPING OR SMOKE CABLE TESTING. ALL DATA WIRING SHALL TERMINATE AT THE MAIN TEB. CABLE TERMINATION SHALL BE EMERGENCY EGRESS LIGHT W/ BATTERY MIN MINIMUM E0.0 NO SCALE BARRIER SEALANTS TO MEET APPROVAL OF THE AHJ. EQUAL SYSTEMS AS MANUFACTURED BY “SPEC PROVIDED BY THE ELECTRICAL CONTRACTOR UNDER DIRECTION OF THE EQUIPMENT SUPPLIER. ALL SOUND AND SIGNAL MCA MINIMUM CIRCUIT AMPERES SEAL” OR “HILTI” WILL BE ACCEPTABLE. DATA WIRING SHALL BE CATEGORY 6 WITH A SEPARATE HOMERUN FOR EACH DATA OUTLET SHOWN MCB MAIN CIRCUIT BREAKER AND SHALL BE A DIFFERENT COLOR THAN THE VOICE SYSTEM WIRING. WIRING SHALL BE RUN OPEN S CEILING SPEAKER MCC MOTOR CONTROL CENTER 11. ELECTRICAL CONTRACTOR SHALL GUARANTEE WORK INSTALLED UNDER THE CONTRACT TO BE FREE ABOVE CEILINGS IN AN APPROVED SUPPORT SYSTEM WITH PLENUM-RATED CABLES. MLO MAIN LUGS ONLY S WALL MOUNTED SPEAKER FROM DEFECTIVE WORKMANSHIP AND MATERIALS, USUAL WEAR EXPECTED, AND SHOULD ANY SUCH BUSHING MOCP MAXIMUM OVERCURRENT PROTECTION DEFECTS DEVELOP WITHIN A PERIOD OF ONE YEAR AFTER ACCEPTANCE OF THE BUILDING BY THE 26. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL PAGING SYSTEM WIRING, EQUIPMENT, SPEAKERS, LONG RADIUS ELBOW V VOLUME CONTROL MTD MOUNTED OWNER OR TENANT, THE ELECTRICAL CONTRACTOR SHALL REPAIR AND/OR REPLACE ANY DEFECTIVE RACEWAYS AND CABLE TESTING. ALL PAGING SYSTEM WIRING SHALL TERMINATE AT THE MAIN TEB. NF NON FUSED ITEMS, AND DAMAGE RESULTING FROM FAILURE OF THESE ITEMS, AT NO COST TO THE OWNER OR CABLE TERMINATION SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR UNDER DIRECTION OF B BELL/BUZZER NIC NOT IN CONTRACT TENANT. THE EQUIPMENT SUPPLIER. ALL PAGING SYSTEM WIRING SHALL BE PLENUM-RATED MULTI-CONDUCTOR CABLING (OR NL NIGHT LIGHT CABLES AND SHALL BE A DIFFERENT COLOR THAN THE VOICE AND DATA SYSTEMS WIRING. WIRING PULL STRING) T CATV OUTLET P POLE 12. ELECTRICAL CONTRACTOR SHALL PROVIDE TEMPORARY POWER AND LIGHTING FOR THE DURATION OF SHALL BE RUN OPEN ABOVE CEILINGS IN AN APPROVED SUPPORT SYSTEM. PC PLUMBING WORK CONTRACTOR THE PROJECT. ALL TEMPORARY LIGHTING AND POWER SHALL BE PROVIDED TO MEET OSHA I INTERCOM OUTLET PF POWER FACTOR STANDARDS, STATE LAW, LOCAL ORDINANCES AND AHJ REQUIREMENTS. 27. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL CATV SYSTEM WIRING, OUTLETS, RACEWAYS, PH PHASE CONNECTORS, AND CABLE TESTING PER INDUSTRY STANDARD. ALL CATV SYSTEM WIRING SHALL M MICROPHONE OUTLET ACCESSIBLE CEILING PRI PRIMARY 13. PROVIDE POWER WIRING AND CONNECTIONS FOR EACH HVAC EQUIPMENT ITEM. COORDINATE POWER TERMINATE AT THE CATV AMPLIFICATION/SWITCHING EQUIPMENT. CABLE TERMINATION SHALL BE SERVICE AND EQUIPMENT REQUIREMENTS AND ROUGH-IN WITH THE EQUIPMENT SUPPLIER OR CONTRACTOR PRIOR TO PROVIDED BY THE ELECTRICAL CONTRACTOR UNDER DIRECTION OF THE EQUIPMENT SUPPLIER. ALL PVC POLYVINYL CHLORIDE STARTING CONSTRUCTION AND ORDERING ELECTRICAL EQUIPMENT. OBTAIN A COPY OF EQUIPMENT CATV SYSTEM WIRING SHALL BE WHITE, PLENUM-RATED RG-6/U QUAD SHIELD HOMERUN CABLES WITH R RELAY REC RECEPTACLE RF RETURN FAN SUPPLIER INSTALLATION DRAWINGS PRIOR TO SUBMITTING A BID. CONNECT ALL EQUIPMENT A MAXIMUM LENGTH OF 250' . DISTRIBUTION CABLES SHALL BE WHITE, PLENUM-RATED RG-11/U QUAD DRYWALL OR FINISH SURFACE COMPLETE AND READY FOR OPERATION. SHIELD. COORDINATE WITH THE CATV SIGNAL PROVIDER TO PROVIDE ADDITIONAL AMPLIFIERS AS N/F DISCONNECT SWITCH RL EXISTING DEVICE RELOCATED NECESSARY SUCH THAT NO HOMERUNS ARE GREATER THAN 250' . WIRING SHALL BE RUN OPEN ABOVE RT RAIN TIGHT (NEMA 3R) F FUSED DISCONNECT SWITCH 14. ELECTRICAL CONTRACTOR SHALL PROVIDE SAFETY DISCONNECT SWITCHES WHERE REQUIRED BY THE CEILINGS IN AN APPROVED SUPPORT SYSTEM. RTU ROOF TOP UNIT NEC AND AS SHOWN ON THE DRAWINGS. SAFETY DISCONNECT SWITCHES SHALL BE “GENERAL 1" CONDUIT (WITH PULL STARTER SD SMOKE DAMPER DUTY” TYPE IN NEMA 1 ENCLOSURE. EQUIPMENT AS MANUFACTURED BY SQUARE D, SIEMENS, STRING IF NO CABLING) SF SUPPLY FAN GENERAL ELECTRIC OR CUTLER HAMMER IS ACCEPTABLE. SWITCHES SHALL BE QUICK-MAKE, COMBINATION STARTER/DISC. SW. SW SWITCH QUICK-BREAK, EXTERNALLY OPERATED AND INTERLOCKED WITH PROVISIONS FOR LOCK-OUT. SWBD SWITCHBOARD PROVIDE NEMA 3R ENCLOSURES FOR ALL SWITCHES IN EXTERIOR LOCATIONS. PROVIDE ANGLE OR FLAT STRAP PUSHBUTTON OR CONTROL STATION T TELEPHONE TO STUD DUAL-ELEMENT TIME DELAY FUSES SUITABLE FOR APPLICATION AND LOAD SERVED WHERE INDICATED. TC TIMECLOCK PHOTOCONTROL 277/480 VOLT SYSTEMS REQUIRE “HEAVY DUTY” TYPE SAFETY DISCONNECTS TO BE PROVIDED. TEB TELEPHONE EQUIPMENT BOARD MOTOR TEF TOILET EXHAUST FAN 15. ELECTRICAL CONTRACTOR SHALL PROVIDE PANELBOARD(S) AS SHOWN AND/OR SCHEDULED ON THE TEMP TEMPORARY DRAWINGS. PANELBOARDS SHALL BE FLUSH OR SURFACE MOUNTED CABINETS, WITH NEMA 250, TYPE 1 SINGLE GANG REDUCER ENCLOSED CIRCUIT BREAKER TV TELEVISION WITH FLUSH FRAME FOR INDOOR APPLICATIONS AND TYPE 3R FOR OUTDOOR APPLICATIONS. PHASE, NEUTRAL AND TYP TYPICAL AND BLANK PLATE (U.O.N.) GROUND BUSES SHALL BE HARD-DRAWN COPPER OF 98 PERCENT CONDUCTIVITY. MAINS, NEUTRAL, MAIN DISTRIBUTION PANEL UH UNIT HEATER GROUND LUGS AND FEED-THROUGH LUGS SHALL BE MECHANICAL TYPE. PROVIDE OPTIONS FOR EACH UNV UNIVERSAL PANEL AS SHOWN ON SCHEDULE. PANELS SHALL BE FULLY RATED TO INTERRUPT SYMMETRICAL BRANCH CIRCUIT PANELBOARD UON UNLESS OTHERWISE NOTED 06-21-2017 SHORT-CIRCUIT CURRENT AVAILABLE AT TERMINALS. DISTRIBUTION PANELBOARDS SHALL BE NEMA XX V VOLT(S) PB1, POWER AND FEEDER DISTRIBUTION TYPE WITH SECURED DOORS WITH VAULT-TYPE LATCH AND XX EQUIPMENT CALLOUT VA VOLTAMP(S) TUMBLER LOCK, KEYED ALIKE. BRANCH PANELBOARDS SHALL BE NEMA PB1, LIGHTING AND APPLIANCE 1 " 4" SQ x 2 8 DEEP BOX X X X PLAN NOTE SYMBOL VAV VARIABLE AIR VOLUME BRANCH CIRCUIT TYPE WITH CONCEALED HINGE DOORS, SECURED WITH FLUSH LATCH AND TUMBLER 1'-6" (U.O.N.) VFD VARIABLE FREQUENCY DRIVE LOCK, KEYED ALIKE. PANELS SHALL HAVE MAINS (EITHER BREAKER OR LUGS) AS NOTED ON THE X REVISION SYMBOL SCHEDULE. BRANCH BREAKERS SHALL BE BOLT-ON TYPE, AND OVERCURRENT PROTECTION DEVICES VOIP VOICE OVER IP SHALL BE MCCB'S, COMPLYING WITH UL 489, WITH INTERRUPTING CAPACITY TO MEET AVAILABLE FAULT CIRCUITRY AND RACEWAYS VSD VARIABLE SPEED DRIVE W WATT(S) CURRENTS. PROVIDE IDENTIFICATION LABELS PER NEC FOR EQUIPMENT AND TYPED CIRCUIT STUD FRAMING BY CONCEALED CONDUIT W/ WITH DIRECTORIES. EQUIPMENT AS MANUFACTURED BY SQUARE D, SIEMENS, GENERAL ELECTRIC OR OTHERS (2 #12 AWG & APPROVED GROUND MIN. - TYP.) CUTLER HAMMER IS ACCEPTABLE. WP WEATHERPROOF CONDUIT BELOW FLOOR OR GRADE WSHP WATER SOURCE HEAT PUMP FLOOR CONDUIT EXPOSED WT WATERTIGHT XFMR TRANSFORMER GROUND WIRE

ISOLATED GROUND WIRE 2 VOICE / DATA / CATV OUTLET DETAIL HOMERUN: NUMBER OF WIRES, PANEL E0.0 NO SCALE P1-2,4,6 DESIGNATION, CIRCUIT NUMBERS TO MAIN WATER PIPE. CONNECT LIGHTING FIXTURE SCHEDULE PANELBOARD SCHEDULE AHEAD OF MAIN SHUT OFF VALVE. TYPE "VN" EXOTHERMIC WELD OR PLAN LUMENS INPUT DESIGNATION/I.D: LP TYPE OF PANEL: CIRCUIT BREAKER ** MOUNTING: SURFACE LISTED GROUND CLAMP. MOUNTING MANUFACTURER MODEL NO. VOLTAGE FINISH NOTES MARK (LAMPS) WATTS VOLTAGE: 120 / 240 /1PH-3W BUS SIZE (AMPS): 200 MAIN SWITCH: M.L.O. MAIN RATING AIC 10k A W/S METALUX 2BCLED-LD4-20SL-F-UNV-L830-CD1-U 2000 120 23 WHITE POLES: 2PSN LUGS: STANDARD TOTAL SPACE REQUIRED: 42 NOTES: B C/R HALO SLD606830WHUNVJB 760 120 13 WHITE FEEDER: SEE RISER DIAGRAM POWER SOURCE: "ATS" C C/S METALUX 4SNLED-LD4-27SL-LW-UNV-L830-CD1-U 2732 120 25 WHITE C C C C K LOAD (WATTS) L L LOAD (WATTS) K GROUNDING BUS A A D C/S LITHONIA UN2-96T8-120-GEB 8550 120 118 WHITE C/B LOAD DESCRIPTION LOAD DESCRIPTION C/B T LOCATED IN MAIN T S S TO BUILDING # F C/R METALUX 22CZ-LD4-24-UNV-L830-CD1-U 2220 120 23 WHITE # AØ BØ S S AØ BØ STEEL. TYPE "VS" PANEL EXOTHERMIC #1/0 G W/R GM LIGHTING STLS-LT-W LED 120 2 WHITE 1 20/1 1080 R REC - BEDROOM #1 REC - KITCHEN R 1080 20/1 2 WELD. H C/R METALUX 24CZ-LD4-40-UNV-L830-CD1-U 3941 120 34 WHITE 3 20/1 1080 R REC - BEDROOM #2 REC - MICROWAVE R 1200 20/1 4 #1/0 5 20/1 1080 R REC - BEDROOM #3 REC - FRIDGE R 1000 20/1 6

SA W/S LUMARK XTOR3B-W-BZ-PC1 2710 120 26 BRONZE 7 20/1 1080 R REC - BEDROOM #4 REC - FRIDGE R 1000 20/1 8 TYPE "GR" SB W/S LUMARK XTOR6BRL-W-BZ-PC1 6133 120 58 BRONZE 9 20/1 720 R REC - RRs, CORRIDOR REC - FRIDGE R 1000 20/1 10 EXOTHERMIC WELD. #6 #4 11 20/1 900 R REC - RR, CORRIDOR REC - DINING, EXTERIOR R 1080 20/1 12 SC UNIV GREENLEE RDB-175MH-120-SPV-BLR (175W MH) 120 175 BLACK FOUNDATION CONTRACTOR 13 720 R REC - STORAGE REC - DISHWASHER R 1200 SD C/R HALO H750ICAT-ML5612835-692SC 1570 120 18 SPEC-CLEAR 20/1 20/1 14 COPPER CLAD SHALL STUB-UP RE-BAR FROM 15 20/1 900 R REC - GARAGE REC - DISPOSAL R 500 20/1 16 GROUND ROD FOUNDATION FOR USE BY THE SE G/PL LEOTEK AR13-10M-MV-NW-4-DB-530 7380 120 65 DARK BRONZE 2 TYPICAL, 5/8"x10'. E.C. TYPE "VS" CONNECTION 17 20/1^ 720 R REC - GARAGE SHORELINE REC - HOOD R 500 20/1 18 SF G/PL LEOTEK AR13-10M-MV-NW-3-DB-530 7380 120 65 DARK BRONZE 2 UFER OR APPROVED CONNECTOR. 19 20/1 1000 R REC - GARAGE DOOR REC - CLOSET R 360 20/1 20 E.C. SHALL COORDINATE WITH 21 20/1 1000 R REC - GARAGE DOOR REC - CLOSET R 360 20/122 FOUNDATION CONTRACTOR. EM W/S SURE-LITES LEM2 - 120 - WHITE NOTE: 23 20/1 900 R REC - GARAGE, EXTERIOR REC - LIVING AREA R 900 20/1 24 X UNIV SURE-LITES LPXH7 - 120 - WHITE 1. EXOTHERMIC WELD DESIGNATION INDICATED ABOVE ARE ERICO "CADWELD". ALL CONNECTIONS SHALL BE 25 20/1 900 R REC - WORKOUT ROOM REC - LIVING AREA R 540 20/126 EXOTHERMIC WELD OR UL LISTED MECHANICAL CONNECTIONS. XR UNIV SURE-LITES SRP-25-BK - 120 - WHITE 1 27 20/1 720 R REC - BSMT RR, LAUNDRY REC - LIVING AREA R 900 20/1 28 GENERAL NOTES: 2. ALL GROUND BUS CONNECTIONS TO BE MADE WITH 2-HOLE COMPRESSION TYPE CONNECTORS. BUS 29 20/1 1000 R F-1 F.A.C.P. R 180 20/130 SHALL BE INSULATED FROM ITS SUPPORT AND SHALL MAINTAIN A 2" SPACING FROM WALL. A. ORDERING INFORMATION: THE ELECTRICAL CONTRACTOR SHALL REVIEW THE CONSTRUCTION DRAWINGS, BRANCH CIRCUIT VOLTAGE AND SUBMITTED LIGHTING FIXTURE SHOP DRAWINGS. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ORDERING THE CORRECT VOLTAGE FOR LIGHTING FIXTURES - NO EXCEPTIONS. INCORRECTLY SUBMITTED SHOP 31 50/2 3000 R CU-1 PAGING SYSTEM R 180 20/1 32 DRAWINGS AND FIXTURE ORDERS WITH THE INCORRECT FIXTURE VOLTAGE WILL NOT BE CAUSE FOR CONSTRUCTION DELAYS OR ADDITIONAL COSTS. 3. ALL WIRING SHALL BE COPPER AND TYPE THHN/THWN GREEN INSULATION WHERE REQUIRED.. 33 - 3000 R -- LTG - GARAGE L 1925 20/134 ORDERING NOTES: 35 20/1 L LTG - LIVING, DINING AREA LTG - BEDROOMS, CORR, RRs L 950 20/1 36 4. GROUND RODS ARE TO BE LOCATED AT SERVICE ENTRANCE WITH SIZE AS NOTED. 1. PROVIDE FINISH TO MATCH EXTERIOR COLOR OF BUILDING; VERIFY FINISH WITH OWNER. 37 20/1 R SPARE LTG - BASEMENT L 750 20/138 2. PROVIDE 15'-0" SQUARE STRAIGHT STEEL POLE 5. ALL GROUNDING AND BONDING SHALL BE INSTALLED IN ACCORDANCE WITH ARTICLE 250 OF NFPA 70 THE 39 20/1 R SPARE LPA SF 6290 100/2 40 "NATIONAL ELECTRICAL CODE". ABBREVIATIONS: 41 20/1 R SPARE LPA SF 6280 -42 C/AC CEILING AIR-CRAFT CABLE, C/CV CEILING COVE, C/P CEILING PENDANT, C/R CEILING RECESSED, C/S CEILING SURFACE, C/SP CEILING SUSPENDED, C/TK TRACK MOUNTED, F/S FLOOR TOTALS 10220 9580 0 14815 13360 0 TOTALS SURFACE, G/P GRADE PAD, G/PL GRADE POLE, R/S ROOF SURFACE, TBD TO BE DETERMINED, U/C UNDER COUNTER, UNIV. UNIVERSAL, W/R WALL RECESSED, W/S WALL SURFACE NOTES: * PROVIDE LOCK ON DEVICE ** 10,000 A.I.C. RATING UNLESS OTHERWISE SPECIFIED CALC. DEMAND 1 GROUNDING ELECTRODE SYSTEM CONNECTED LOAD: 47,975VA ^ GROUND FAULT BREAKER 142A (VOLT-AMPERE) LOAD AMPERE: E0.1 NO SCALE

CLASS: M1=SINGLE PH MOTOR, M3=3PH MOTOR, M2=2PH MOTOR, L=LIGHTING, R=RECEPTACLE, A1=1PH A/C LOAD, A2=2PH A/C LOAD, A3=3PH A/C LOAD, H=HEATING, K=KITCHEN; XF=TRANSFORMER-PANEL; SF=SUB-FEED HILTI CC27 CLIP (OR EQUAL) STRUCTURE

#12 GA. SAFETY WIRE TIED TO SAFETY WIRE SUPPORT HOLES & FASTENED TO PANELBOARD SCHEDULE BLDG. STRUCTURE. MINIMUM (1) SAFETY DESIGNATION/I.D: LPA TYPE OF PANEL: CIRCUIT BREAKER ** MOUNTING: SURFACE WIRE AT CENTER OF FIXTURE FOR LIGHT VOLTAGE: 120 / 240 /1PH-3W BUS SIZE (AMPS): 100 MAIN SWITCH: M.L.O. MAIN RATING AIC 10k HOUSING + 12" FIXTURES LESS THAN 10 LBS. MINIMUM (2) SAFETY WIRES PLACED AT DIAGONAL POLES: 2PSN LUGS: STANDARD TOTAL SPACE REQUIRED: 30 NOTES: CORNERS FOR LIGHT FIXTURES WEIGHING 10 LBS. OR MORE BUT LESS THAN 56 LBS. FEEDER: SEE RISER DIAGRAM POWER SOURCE: "LP" PANEL RE TU IX C C C C F L L HT K LOAD (WATTS) LOAD (WATTS) K IG C/B A LOAD DESCRIPTION LOAD DESCRIPTION A C/B L T S S T # # XØ YØ S S XØ YØ

LIGHT FIXTURE 1 20/1 1000 R GEN - BATTERY CHARGER WASHER R 1000 20/1 2 HOUSING + 12" SAFETY WIRE SUPPORT HOLE, 3 20/1 500 L LTG - EXTERIOR DRYER R 2500 30/2 4 TYPICAL 5 20/1 1000 L EXTERIOR SIGNAGE -- R 2500 - 6

SEISMIC RESTRAINT CLIP 7 20/1 1610 M1 EF-B SP-1 R 180 20/1 8 MINIMUM (4) PER LIGHT SWAY BRACED GRID CEILING 9 20/1 600 H IUH-1 WH-1 R 180 20/1 10 3 " FIXTURE, SECURELY AND 3 32 11 20/1 180 R HW RECIRC PUMP GEN - BLOCK HEATER R 1500 20/1 12 POSITIVELY ATTACHED TO (6) 5/8" Ø EXPANSION ANCHORS (MINIMUM), HILTI 7Z WITH 4-1/2" CEILING GRID, TYPICAL 13 20/1 500 L LTG - SITE POLES SPARE R 20/1 14 EMBEDING. COORDINATE WITH GENERATOR SHOP DRAWINGS. 15 20/1 R SPARE SPARE R 20/1 16

17 20/1 R SPARE SPARE R 20/1 18 5/8" Ø EXPANSION #5 REBAR, AT 12" O.C. EA WAY, NOTES: ANCHORS PLACED IN CENTER OF 8" 1. SUPPORT WIRES FOR FIXTURES WEIGHING LESS THAN 56 LBS. MAY BE INSTALLED SLACK. ALL OTHER 19 20/1 R SPARE SPARE R 20/1 20 SLAB 6" MIN. 8" SUPPORT WIRES SHALL BE INSTALLED TAUT WITH A MINIMUM OF 3 TIGHT TURNS AROUND ITSELF. 21 20/1 R SPARE SPARE R 20/1 22 23 20/1 R SPARE SPARE R 20/1 24 GRADE 2. LIGHT FIXTURES WEIGHING 56 LBS. OR MORE SHALL BE INDEPENDENTLY SUPPORTED DIRECTLY FROM THE STRUCTURE ABOVE, BY APPROVED HANGERS. 25 20/1 R SPARE SPARE R 20/1 26 27 20/1 R SPARE SPARE R 20/1 28 36" EXCEPTION: 29 20/1 R SPARE SPARE R 20/1 30 LIGHT FIXTURES THAT ARE NOT COMPONENTS OF A STANDBY OR EMERGENCY LIGHTING SYSTEM AND WEIGH 2 LESS THAN 20 POUNDS AND ARE POWERED USING FLEXIBLE CABLE CONNECTIONS NOT LESS THAN 3 FT. LONG TOTALS 3100 2290 0 3680 4180 0 TOTALS 1 CONNECTED TO THE FIXTURES, ARE NOT REQUIRED TO HAVE THE ADDITIONAL SUPPORT WIRE(S) DESCRIBED * PROVIDE LOCK ON DEVICE NOTES: ** 10,000 A.I.C. RATING UNLESS OTHERWISE SPECIFIED ABOVE. SUCH FIXTURES ARE REQUIRED TO BE POSITIVELY ATTACHED TO THE CEILING GRID AS DESCRIBED CALC. DEMAND CONNECTED LOAD: 13,250VA 57A 12" ABOVE. (VOLT-AMPERE) LOAD AMPERE:

CLASS: M1=SINGLE PH MOTOR, M3=3PH MOTOR, M2=2PH MOTOR, L=LIGHTING, R=RECEPTACLE, A1=1PH A/C LOAD, A2=2PH A/C LOAD, A3=3PH A/C 2 GENERATOR CONCRETE PAD DETAIL 3 RECESSED LIGHTING FIXTURE SUPPORT DETAIL LOAD, H=HEATING, K=KITCHEN; XF=TRANSFORMER-PANEL; SF=SUB-FEED E0.1 NO SCALE E0.1 NO SCALE

EXISTING POWER POLE # PLAN NOTES - RISER DIAGRAM "TC" "SLC" 3 4 1. PROVIDE 4" SCHEDULE 40 PVC CONDUIT FOR UTILITY COMPANY'S PRIMARY CABLES ET C TERMINAL FROM EXISTING POWER POLE TO UTILITY TRANSFORMER AS DIRECTED BY UTILITY CO. (TYP.) REPRESENTATIVE. FURNISH ADDITIONAL 30 FEET OF CONDUIT TO POWER COMPANY TO HOT 5 INSTALL ON POLE PER THEIR SPECIFICATIONS AND REQUIREMENTS. PROVIDE A PULL 120V WIRE IN EACH CONDUIT. REFER TO SITE PLAN FOR ADDITIONAL INFORMATION. NEUTRAL 2. 3 #3/0 & 1 #6 GRD, 2"C. PROVIDE "PC" (SPARE) LOCK-ON 3. AMEREN APPROVED NEMA 3R METERING ENCLOSURE. REFER TO AMEREN ELECTRIC UTILITY XFMR DEVICE FOR C.B. M SERVICE MANUAL FOR SPECIFICATIONS. FROM PANEL - SEE GENERATOR PLANS FOR 3 4. 200A/2PSN FUSIBLE SWITCH, 200A FUSES, NEMA 1 ENCLOSURE AND GROUNDING KIT. CIRCUITS 11 TO LOADS - SEE PLANS 5. PROVIDE AUTOMATIC TRANSFER SWITCH (ATS), RATED AT 200A, 240/120V, 1Ø, 3W, 06-21-2017 2-POLE WITH SOLID NEUTRAL IN NEMA 1 ENCLOSURE. KOHLER #: RDT-CFNA-0200 OR FOR CIRCUITS ("PC" - ON, GRADE "TC" - OFF) EQUAL. LAUNDRY 003 "PC" - PHOTOCONTROL: INTERMATIC #K4121C. 1 2 6. PANELBOARD "LP": 200A M.L.O.

"TC" - TIME CLOCK: INTERMATIC #ET-1725 WITH TWO SPST LOADS 7. 3 #3 & 1 #8 GRD, 1-1/4"C. * PROGRAM TIME CLOCK PER OWNER'S DIRECTIONS 5 "ATS" 8. PANELBOARD "LPA": 100A M.L.O. "SLC" - SITE LIGHTING CONTACTOR: ASCO #918-4-20-31, 47L, C 2 4 POLES, 20 AMPS, MECHANICALLY-HELD, 120 VOLT/2-WIRE CONTROL, NEMA 1 ENCLOSURE "LP" "LPA" 9. PROVIDE AND ROUTE 3 #3/0 & 1 #6 GRD, 2"C FROM "ATS" TO GENERATOR. 4 6 8 7 10. ROUTE CONTROL WIRING FROM GENERATOR TO "ATS". 4 5 LIGHTING CONTROL DIAGRAM RISER DIAGRAM 2 11. GENERATOR SPEC: KOHLER MODEL # 48RCL WITH ALERNATOR "4Q7BX". 48 KW, 2 120/240V, 1PH, 3W WEATHERPROOF HOUSING, FUEL. INTEGRAL BATTERY, E0.1 NO SCALE E0.1 NO SCALE BASEMENT BATTERY CHARGER, MUFFLER, 200 AMP C/B. MOUNT GENERATOR/TANK ON CONCRETE PER DETAIL 2/E0.1. COORDINATE EXACT SIZE OF PAD WITH GENERATOR HOUSING 1 9 APPROVED SUBMITTALS. E0.1 10 yblLblQYCtlgNme ecito Lamp Description Number Catalog QTY Label Symbol E1.0 6'-0" 30" 1

2'-0" NO SCALE STANDARD DETAIL LIGHT SB SE SD SA SF 1'-6" DIA.1'-6" 11 XTOR6BRL-W CROSSTOUR WALL CROSSTOUR XTOR6BRL-W 11 AR13-10M-MV-NW-3-DB- 1 AR13-10M-MV-NW-4-DB- 4 ML56 LEDINCH 6 HALO ML5612835-692SC 3 26W WALL CROSSTOUR XTOR3B-W 1 -530 FROM L12134102 FROM -530 L01140502 FROM -530 1" MINIMUM PVC CONDUITPVC FORMINIMUM 1" INSTALLED BY E.C.BY INSTALLED ELECTRIC ELECTRIC HANDHOLE FURNISHED & INSTALLED BY INSTALLED E.C.& FURNISHED BASE SHALL BE POURED BE IMMEDIATELYSHALL BASE ININSTALLED MUST FULLYBE BASE TO GROUND #10 WIRE LUG ANDBOND LUG ON LIGHTINGGROUND POLEPROVIDE PROVIDE 4-#6 REBARS VERT. WITHREBARS 4-#6 PROVIDE GROUND WIRE WITH BRANCH CIRCUIT. WIRE BRANCH WITH GROUND CONC. BASE FURNISHED CONC. &BASE SPECIFICATIONS. ORIGINAL OR SOIL AS COMPACTED PER CHAMFER, & TROWEL TOP. TROWEL REMOVE& FINISH CHAMFER, (OR EQUAL) FORM, SONOTUBE SLOPE, 25'-0" LIGHTING POLE WITHPOLE LUMINAIRE(S)LIGHTING 25'-0" WIRING BY E.C.WIRINGBY TIES 12" O.C. #4 ANCHOR BOLTS ANCHOR ACCUMULATION. TOWATER DRILLING PREVENT AFTER AND PAINT TO MATCH POLE COLOR - TOPOLE MATCHE.C. BY PAINT AND akn rv . c2. c00f / N/A N/A fc 0.0 fc 26.0 fc 1.7 Drive / Parking ecito yblAgMxMnMxMnAvg/Min Max/Min Min Max Avg Symbol Description Statistics OPTIC LENSOPTIC FIXTURE LED 1/4"H. X 13-1/2"W. X 8-26"L. OPTICS LEDS WITH LUMINAIRE LED 8-3/4"H. 13-1/2"W. X X 25-3/4"L. SPECULAR REFLECTOR SPECULAR WITH DOWNLIGHT LEDMOUNT REFRACTIVE LENS REFRACTIVE LED MOUNT WITH FEET OF 28.75DISTANCE TEST WITH GONIOPHOTOMETER IN STANDARDS LABUSING LUMEN CREATED FACTORS CALIBRATION IS BASED ON PHOTOMETRY ABSOLUTE CCT 3500K / LEDLUMEN 80CRIHIGH (1) 25.5 0.9 2708.738 4000K LED EATON AO E 00 13180958 0.9 6123.138 4000K LED EATON GRADE per Lamp per 29680965 0.9 7249.608 68 0.9 7459.111 59630917.3 0.9 1559.613 Lumens Lumens L Wattage LLF

PROPERTY LINE E1.0 1 N "SE" "SE" "SB" "SB" SCALE: 1/16"= 1'-0" SCALE: LIGHTING PHOTOMETRIC SITE "SE" E1.0 1 "SC" S""D "SD" "SD" "SD" "SA" "SA" "SB" "SB" "SB" "SB" E1.0 1 "SF" "SE" "SB" "SB" "SB" "SB" "SB" E1.0 1 PROPERTY LINEPROPERTY

PROPERTY LINE 06-21-2017 (+48") 15 (+48") 15

FAI 1 5 GENERAL NOTES - POWER & SYSTEMS CLOSET 17 17 A. ALL BRANCH CIRCUIT CONDUIT AND WIRING ARE NOT SHOWN. ONLY 119 F HOMERUNS AND CIRCUIT NUMBERS ARE SHOWN ADJACENT TO 5 DEVICES AND EQUIPMENT. THE REMAINING BRANCH CIRCUIT CONDUIT LP-17 AND WIRING SHALL BE INSTALLED PER THE SPECIFICATIONS, SUPPLEMENTAL CONDITIONS AND ALL APPLICABLE CODES. 15 B. ELECTRICAL CONTRACTOR SHALL CONNECT ALL EQUIPMENT 19 4 21 4 WP COMPLETE AND READY FOR OPERATION. THIS INCLUDES, BUT IS NOT LIMITED TO, ALL ELECTRICAL EQUIPMENT, ALL ELECTRICALLY-DRIVEN OR OPERATED MECHANICAL EQUIPMENT, AND ALL ELECTRICAL-RELATED EQUIPMENT WHICH MAY BE FURNISHED BY 10 VARIOUS EQUIPMENT SUPPLIERS. (+48") 15 11 C. COORDINATE ALL EQUIPMENT CONNECTIONS WITH THE GENERAL IUH CONTRACTOR, ALL EQUIPMENT SUPPLIERS AND OTHER TRADE 1 CONTRACTORS.

LPA-1,12 D. COORDINATE ELECTRICAL INSTALLATION REQUIREMENTS FOR CLOSET LPA-9 EQUIPMENT WITH SUPPLIER AND/OR TRADES PRIOR TO START OF 118 CONSTRUCTION. COORDINATE LOCATIONS AND INSTALLATION REQUIREMENTS FOR MECHANICAL EQUIPMENT WITH M.C. AND P.C. PRIOR TO ROUGH-IN. CONNECT EQUIPMENT COMPLETE AND READY FOR OPERATION.

CU E. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS. SEE 1 ARCHITECTURAL PLANS FOR ANY SPECIAL MOUNTING HEIGHTS AND (+48") LOCATIONS. COORDINATE THE FINAL LOCATION WITH THE 15 ARCHITECT/OWNERS REPRESENTATIVE PRIOR TO ROUGH-IN. 15 F 7 WP WP 12 WP RT S F. PROVIDE RG-6 QUAD SHIELDED CABLE TO TERMINAL BOARD IN BASEMENT FOR EACH TELEVISION OUTLET. LPA-7 #8 VC F G. PROVIDE 4 PAIR CAT 5e CABLE TO TERMINAL BOARD IN BASEMENT FOR 7 5 F LP-13 EF EACH TELEPHONE OUTLET AND TERMINATE AT EACH END. 16 7 9 7 5 B LP-31,33 (+84") (+84") CLOSET T T 8 8 117 9 F # 13 CO PLAN NOTES - POWER & SYSTEMS

USB USB 12 1. SWITCH UNDER COUNTER TO SERVE GARBAGE DISPOSAL. INSTALL 7 5 12 EQUIPMENT ROOM COMPLETE AND READY FOR OPERATION. COORDINATE THE ROUGH-IN 7 BEDROOM #4 BEDROOM #3 120 WITH THE P.C. AND G.C. 113 114 7 5 F LP-7 LP-5 18 2. CONNECT DISHWASHER COMPLETE AND READY FOR OPERATION. S LP-15 (+48") F F 14 COORDINATE THE ROUGH-IN WITH THE P.C. AND G.C. S S 12 USB 15 S DINING AREA 3. VERIFY MICROWAVE RECEPTACLE MOUNTING HEIGHT WITH OWNER 14 14 12 115 2 (+54") 20 PRIOR TO INSTALLATION. S S LP-14 7 5 J (+42") LP-4 4 23 4. CONNECT OVERHEAD DOOR COMPLETE AND READY FOR OPERATION. (+48") S LP-16 (+60") 2 LP-9 11 5. SINGLE 20A RECEPTACLE FOR SHORELINE POWER. F CORRIDOR LP-12 14 S S 1 3 8 IT CLOSET 112 T 6. JUNCTION BOX FOR FUTURE SIGN MOUNT J-BOX IN BRICK 8" BETWEEN RESTROOM #1 (IN SOFFIT) CO 106 12 BOXES. (+42") 111 F F 2 9 LP-2 USB CLOSET (+42") KITCHEN (+42") 7. CONNECT SOLENOID VALVE VIA PUSH BUTTON COMPLETE AND READY 107 17 11 116 FOR OPERATION PER EQUIPMENT SUPPLIER SPECIFICATIONS. EF 11nb COORDINATE INSTALLATION WITH M.C. 9pb 12 (+42") EF A 12 F A LP-18 8. PROVIDE RECESSED TV OUTLET BOX (P&S TV1WMTVSSWCC2, OR LP-20 J 19 T.E.B. EQUAL) FOR FLAT SCREEN PER EQUIPMENT SUPPLIER SPECIFICATIONS. H.C. LP-10 LP-8 LP-6 VERIFY MOUNTING HEIGHT WITH OWNER PRIOR TO INSTALLATION. 9 (+42") 22 RESTROOM 2 EF (+42") 9ob 12 108 9. INTERLOCK MOTOR OPERATED LOUVER FAI-1 AND CARBON MONOXIDE A 14 CLOSET LP-19 LP-21 (CO) MONITOR WITH EXHAUST FAN EF-B. CO MONITOR SPEC: MACURCO 109 S 2 2 2 INC. MODEL #CM-6. PROVIDE INTERMATIC 30 MINUTE TIMER TO LP-32 (+42") (+42")(+42") (+42") (+42") 9 RESTROOM #2 10 8 6 (+42") OVERRIDE CO DETECTOR MANUALLY. (+42") F F LP-22 110 CO 9 LP-11 11 24 24 10. 48kW EMERGENCY GENERATOR. REFER TO RISER DIAGRAM DETAIL CORRIDOR (+48") 24 24 24 24 5/E0.1 FOR ADDITIONAL INFORMATION. F USB USB 14 S 105 4 4 11 CLOSET (+30") (+30") S 11. PROVIDE CONCRETE PAD PER DETAIL 2/E0.1. 102 F 3 S S 1 LP-24 12. EXHAUST FAN TO BE TURNED ON VIA SWITCH LOCATED IN RESTROOM. 11 20 SEE SHEET E3.0 FOR ADDITIONAL INFORMATION. 14 14 (+48") 23 13. PROVIDE AND INSTALL VIKING MODEL: E-1600A-EWP WEATHERPROOF S 14 17 17 F F F EMERGENCY PHONE COMPLETE AND READY FOR OPERATION. LP-3 S S LP-1 S 3 1 5 5 USB 21 LP-26 (+48") 14. ATLAS MODEL SD72WV SPEAKER WITH AT100A IVORY FACE PLATE. USB F 3 1 23 PROVIDE VOLUME CONTROL AT SPEAKER. PROVIDE 2 #16 SHIELDED F CABLE TO AMPLIFIER. FLUSH WALL MOUNT 7'-0" A.F.F. 21 F 3 15. ATLAS 8" WEATHERPROOF SPEAKER. PROVIDE 2 #16 SHIELDED CABLE (+84") LP-23 TO AMPLIFIER. T 1 BEDROOM #2 8 BEDROOM #1 LIVING ROOM 28 (+84") 15 16. VOLUME CONTROL FOR EXTERIOR SPEAKER. 104 T 103 101 WP 8 S F 16 17. PROVIDE 3/4" FIRE RATED PLYWOOD TERMINAL BOARD TO COVER 3 1 LP-28 23 (+48") ENTIRE WALL SPACE WITH #66 PUNCH DOWN BLOCKS FOR SPEAKER 21 (+48") 23 VC F CABLES AND DATA CABLE PATCH PANEL.

28 F FIRE ALARM F WP 18. ALL EQUIPMENT ROOM WALL MOUNTED RECEPTACLES TO BE S 28 23 5 5 BELL J J WEATHERPROOF GFCI TYPE. (+48") T F.A.C.P. 8 19. HOOD POWER CONNECTION COORDINATE ROUGH-IN WITH SUPPLIER. F 28 28 6 CONNECT COMPLETE AND READY FOR OPERATION. LP-30 F 20. GARAGE DOOR OPERATORS, CONNECT PER EQUIPMENT SUPPLIER F WP WIRING DIAGRAMS INCLUDING SAFETY SENSORS. 06-21-2017 23 J LPA-5 DOORBELL WP 5 (VIA "SLC") 21. PROVIDE NON-METALLIC FLOORBOX WITH DUPLEX RECEPTACLE. 13 WIREMOLD: 880MP/827B/828R. PROVIDE 1" CONDUIT FOR POWER WIRING BETWEEN BOXES AND TO PANELBOARD. COORDINATE LOCATION WITH FURNITURE. FIELD VERIFY FINAL LOCATION WITH G.C. PRIOR TO START OF CONSTRUCTION.

22. PROVIDE 48"x96"x3/4" FIRE RETARDANT TREATED EQUIPMENT BOARD FOR EQUIPMENT MOUNTING. N FIRST FLOOR PLAN - POWER & SYSTEMS SCALE: 1/4" = 1'-0" GENERAL NOTES - POWER & SYSTEMS

A. ALL BRANCH CIRCUIT CONDUIT AND WIRING ARE NOT SHOWN. ONLY HOMERUNS AND CIRCUIT NUMBERS ARE SHOWN ADJACENT TO DEVICES AND EQUIPMENT. THE REMAINING BRANCH CIRCUIT CONDUIT AND WIRING SHALL BE INSTALLED PER THE SPECIFICATIONS, SUPPLEMENTAL CONDITIONS AND ALL APPLICABLE CODES.

B. ELECTRICAL CONTRACTOR SHALL CONNECT ALL EQUIPMENT COMPLETE AND READY FOR OPERATION. THIS INCLUDES, BUT IS NOT LIMITED TO, ALL ELECTRICAL EQUIPMENT, ALL ELECTRICALLY-DRIVEN OR OPERATED MECHANICAL EQUIPMENT, AND ALL ELECTRICAL-RELATED EQUIPMENT WHICH MAY BE FURNISHED BY VARIOUS EQUIPMENT SUPPLIERS.

C. COORDINATE ALL EQUIPMENT CONNECTIONS WITH THE GENERAL CONTRACTOR, ALL EQUIPMENT SUPPLIERS AND OTHER TRADE CONTRACTORS.

D. COORDINATE ELECTRICAL INSTALLATION REQUIREMENTS FOR EQUIPMENT WITH SUPPLIER AND/OR TRADES PRIOR TO START OF CONSTRUCTION. COORDINATE LOCATIONS AND INSTALLATION REQUIREMENTS FOR MECHANICAL EQUIPMENT WITH M.C. AND P.C. PRIOR TO ROUGH-IN. CONNECT EQUIPMENT COMPLETE AND READY FOR OPERATION.

E. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS. SEE ARCHITECTURAL PLANS FOR ANY SPECIAL MOUNTING HEIGHTS AND LOCATIONS. COORDINATE THE FINAL LOCATION WITH THE ARCHITECT/OWNERS REPRESENTATIVE PRIOR TO ROUGH-IN.

# PLAN NOTES - POWER & SYSTEMS

1. REFER TO ELECTRICAL RISER DIAGRAM DETAIL 5/E0.1 FOR ADDITIONAL INFORMATION. STAIRS 25 004 2. PROVIDE DUAL MONITOR MODULE FOR SPRINKLER ZONE FLOW & TAMPER SWITCH. COORDINATE EXACT LOCATION WITH FIRE ALARM 25 F CONTRACTOR. S F 3. EXHAUST FAN TO BE TURNED ON VIA SWITCH LOCATED IN RESTROOM. SEE SHEET E3.1 FOR ADDITIONAL INFORMATION.

4. ATLAS MODEL SD72WV SPEAKER WITH AT100A IVORY FACE PLATE. PROVIDE VOLUME CONTROL AT SPEAKER. PROVIDE 2 #16 SHIELDED CABLE TO AMPLIFIER. FLUSH WALL MOUNT 7'-0" A.F.F. WORKOUT 25 ROOM 5. CONNECT POWER TO GAS WATER HEATER AND HOT WATER 001 RECIRCULATING PUMP COMPLETE AND READY FOR OPERATION PER EQUIPMENT SUPPLIER SPECIFICATIONS. COORDINATE INSTALLATION WITH P.C.

25

4 S 25

F S

RESTROOM 002 25 4 4 S

EF 3 F S 10 A 4 FCU WH HWRCP 5 27bb 1 LP-25 1

E0.1 S LPA-10 1 27 (+44")

27 LPA-11 ATS "LP" "LPA" LP-27 LP-29

#10 F F LP-4,6 S CO LAUNDRY LPA-8 003 2 LPA-2 SP F F (+44") FS SV 1 F F 27 MM DMM

06-21-2017

N LOWER LEVEL PLAN - POWER & SYSTEMS SCALE: 1/4" = 1'-0" (+138") (+138") (+138") "SB" 3 "SB" 3 "SB" 3

"SB" 3 (+120")

"X" "XR" 2 "C" 34 34 GENERAL NOTES - LIGHTING CLOSET "C" A. SEE DETAIL 4/E0.0 FOR WIRING OF SWITCHED LIGHTING FIXTURES 34 119 CONTAINING EMERGENCY BATTERY BALLASTS. 2 D D D D 36DJ B. PROVIDE AN UNSWITCHED BRANCH CIRCUIT CONNECTION TO FIXTURES WITH AN EMERGENCY BALLAST, TO EMERGENCY, AND TO EXIT 3 DJ S FIXTURES. CONNECTION SHALL BE TO THE SAME BRANCH CIRCUIT SERVING THE LIGHT FIXTURES IN AREA AHEAD OF ANY CONTROLS.

34u 34u 34v 34v C. PROVIDE AN UNSWITCHED BRANCH CIRCUIT CONNECTION TO FIXTURES "SA" DENOTED "NL" FOR NIGHT LIGHT OPERATION. REVIEW AND CONFIRM 3 FIXTURES SELECTED FOR NIGHT LIGHT OPERATION WITH OWNER AND (+80") ARCHITECT PRIOR TO CONSTRUCTION.

D. FIELD CONFIGURE UNIVERSAL EXIT SIGN DIRECTIONAL CHEVRONS, FACES, AND MOUNTING PER PLAN. 2 "C" E. PROVIDE A SEPARATE GROUNDED CONDUCTOR (NEUTRAL) FOR EACH NEW BRANCH CIRCUIT. CLOSET 118 F. PRIOR TO START OF CONSTRUCTION, COORDINATE ROUGH-IN LOCATIONS FOR SWITCHES WITH ARCHITECT. 36DJ 3 DJ S G. ALL BRANCH CIRCUIT CONDUIT AND WIRING ARE NOT SHOWN. ONLY HOMERUNS AND CIRCUIT NUMBERS ARE SHOWN ADJACENT TO FIXTURES. THE REMAINING BRANCH CIRCUIT CONDUIT AND WIRING SHALL BE INSTALLED PER THE ELECTRICAL CRITERIA AND ALL APPLICABLE CODES.

(+80") D DD D "XR" "SA" 3 # PLAN NOTES - LIGHTING

S "C" 2 1. THOMAS FAN MODEL # T96-1/T89-1/G3028 WITH LIGHT KIT, BRONZE aa4 "X" 35 FINISH. E.C. TO PROVIDE LUTRON MODEL MA-LFQM WITH 3-WIRE "B"35aa "B"35aa "B" CLOSET 34u 34u 34v 34v CONNECTION TO FAN-MOUNTED CANOPY MODULE FOR FAN/LIGHT "B" "B" "B" "B" 117 CONTROLS. 35aa 36s 36s 36t 36t 3 2. MOUNT LIGHT FIXTURE ON WALL 6" ABOVE DOOR FRAME. DJ S 36DJ 3. PROVIDE LEGRAND CANOPY SWITCH MODEL 1200 - DOOR JAMB SWITCH (+120") "SB" EQUIPMENT ROOM TO OPERATE CLOSET LIGHT FIXTURE(S). CONNECT COMPLETE AND 36fe 1 36ff 1 READY FOR OPERATION . 3 120 3 "SB" (+80") BEDROOM #4 BEDROOM #3 "B" "B" 35fb 4. MOUNT LIGHT FIXTURE ABOVE MIRROR, REFER TO ARCHITECTURAL 113 114 1 35aa 35aa DETAILS. "B" "B" "B" "B" DINING AREA 1 1 36s 36s 36t 36t 115 5. MOUNT LIGHT FIXTURE 1'-0" A.F.F. 5 5 5 fb 1 aa4 u3 fe s ff b4 v3 t aa4 D D b4 "G"36r "G"36r "G" 36r S S r3 q3 CORRIDOR "B" "B" "B" "A" "B" "B" "B" "B" 36pa 36q 4 112 35b 35b 35b D DD D pb pa r3 q3 36q 36q 36pa S S S S DJ 3 RESTROOM #1 36DJ CLOSET KITCHEN 111 H.C. "B" "B" 107 RESTROOM "A" 36na 116 "C" 36pb 108 4 34u 34u 34v 34v "B" "B" "B" "B" IT CLOSET CLOSET 35b 35b 35b 106 36na 109 "B" 36it 36ob "B" it nb na RESTROOM #2 36DJ S S S 110 DJ S S S Sg3 3 aa4 "A" ob oa h3 b4 4 "B" "B" "B" "B" CLOSET CORRIDOR c4 D "B" "B" "B" 36oa 36g 102 36oa 36g 105 36g h3 g3 35d 35d 35d "G"36h "G" 36h "G" 36h S S

D D fd m k fc d u3 5 5 5 "EM" v3 35 "B" "B" "B" c4 D "B" "B" "B" "B" 1 1 35c 35c 35c 36m 36m 36k 36k D D D D LIVING ROOM "SB" "SB" 101 3 3 (+80") (+120") 36fd 1 36fc 1 "B" "B" 34u 34u 34v 34v "X" "XR" BEDROOM #2 "B" 104 "B" "B" BEDROOM #1 "B" 35c 35fa 1 35c 34 34 103 "C" 36m 36m 36k 36k 2 34

(+138")

"B" "B" "B" "SB" 3 "SB" 3 "SB" 3 (+138") (+138") 35c1 35c 35c

c4 e fa #10 "X" 35 D S LPA-3 (VIA "SLC") 06-21-2017 "XR"

"SD" "SD" "SD" 35e 35e 35e

N FIRST FLOOR PLAN - LIGHTING SCALE: 1/4" = 1'-0" GENERAL NOTES - LIGHTING

A. SEE DETAIL 4/E0.0 FOR WIRING OF SWITCHED LIGHTING FIXTURES CONTAINING EMERGENCY BATTERY BALLASTS.

B. PROVIDE AN UNSWITCHED BRANCH CIRCUIT CONNECTION TO FIXTURES WITH AN EMERGENCY BALLAST, TO EMERGENCY, AND TO EXIT FIXTURES. CONNECTION SHALL BE TO THE SAME BRANCH CIRCUIT SERVING THE LIGHT FIXTURES IN AREA AHEAD OF ANY CONTROLS.

C. PROVIDE AN UNSWITCHED BRANCH CIRCUIT CONNECTION TO FIXTURES DENOTED "NL" FOR NIGHT LIGHT OPERATION. REVIEW AND CONFIRM FIXTURES SELECTED FOR NIGHT LIGHT OPERATION WITH OWNER AND ARCHITECT PRIOR TO CONSTRUCTION.

D. FIELD CONFIGURE UNIVERSAL EXIT SIGN DIRECTIONAL CHEVRONS, FACES, AND MOUNTING PER PLAN.

E. PROVIDE A SEPARATE GROUNDED CONDUCTOR (NEUTRAL) FOR EACH NEW BRANCH CIRCUIT.

F. PRIOR TO START OF CONSTRUCTION, COORDINATE ROUGH-IN LOCATIONS FOR SWITCHES WITH ARCHITECT.

G. ALL BRANCH CIRCUIT CONDUIT AND WIRING ARE NOT SHOWN. ONLY HOMERUNS AND CIRCUIT NUMBERS ARE SHOWN ADJACENT TO FIXTURES. THE REMAINING BRANCH CIRCUIT CONDUIT AND WIRING SHALL BE INSTALLED PER THE ELECTRICAL CRITERIA AND ALL APPLICABLE CODES.

# PLAN NOTES - LIGHTING

1. MOUNT FIXTURE ABOVE MIRROR, REFER TO ARCHITECTURAL DETAILS. "C" 38a "X" STAIRS 004 38 "EM" 38 a3

F F F 38a 38a 38a

LP-38

F F F 38a 38a 38a

"EM" WORKOUT 38 ROOM 001

F F F 38a 38a 38a

S S bb ba "B" 38bb

"B" 38ba RESTROOM S 002 "X" c 38

"A" 38ba

1 LAUNDRY 003

HHH

38c 38c 38c

06-21-2017

N LOWER LEVEL PLAN - LIGHTING SCALE: 1/4" = 1'-0"