Project Name: Nortrax Section 26 27 26
Total Page:16
File Type:pdf, Size:1020Kb
Project Name: Nortrax Section 26 27 26
Project No: 13-013 WIRING DEVICES
Page 1
1 General
1.1 SHOP DRAWINGS
.1 Submit shop drawings and product data in accordance with Section 01300 – Administrative Requirements and Section 26 05 01.
2 Products
2.1 WIRING DEVICES
.1 Supply and install wiring devices as indicated complete with coverplates.
.2 Switches: Manually operated, general purpose, AC, specification grade, totally enclosed body, rated 120v, 20 amperes minimum or as required by circuit complete with white decorative designer series toggle. (rocker)
.3 Receptacles: 3 wire, U-Ground type, premium specification grade complete with screw type terminals, double wire contacts, riveted ground contacts, break-off links for split receptacles and white molded housing. Receptacles within 1.5m of a sink to be protected by GFI.
.4 Other receptacles with ampacity and voltage as indicated.
.5 Products: Devices to be Hubbell manufacture, style line series.
.1 Light Switch (Style Line Decorator Series): 20A-120V Single Pole White – DS120W 20A-120V 3-Way White – DS320W 20A-120V 4-Way White – DS420W
.2 Receptacles (Style line Decorator Series): 15A-125V Duplex White – DR15WHI 20A-125V Duplex White – DR20WHI 15A-125V GFCI Duplex – GF15WLA 20A-125V GFCI Duplex – GF20WLA
.3 Tamper Resistant Receptacles (Style Line Decorator Series): 15A-125V Duplex White – DR15WHITR 20A-125V Duplex White – DR20WHITR 15A-125V GFCI Duplex – GFTR15W 20A-125V GFCI Duplex – GFTR20W
.4 Wall Plates (Style Line): Standard Size Stainless; 1-Gang – SS26 3-Gang – SS263 2-Gang – SS262 4-Gang – SS264, ETC.
Project Name: Nortrax Section 26 27 26
Project No: 13-013 WIRING DEVICES
Page 2
Acceptable Manufacturers Pass and & Seymour and Cooper
2.3 SPECIAL WIRING DEVICES
.1 Clock hanger outlets, 15 A, 125 V, 3 wire, grounding type, suitable for No. 10 AWG for installation in flush outlet box. .1 Acceptable materials: Pass & Seymour, Leviton, Arrow Hart .2 Pilot lights as indicated, with neon type 0.04 W, 125 V lamp and red plastic jewel lense flush type.
2.4 COVER PLATES
.1 Cover plates for wiring devices.
.2 Cover plates from one manufacturer throughout project.
.3 Sheet steel utility box cover for wiring devices installed in surface-mounted utility boxes.
.4 Stainless steel, vertically brushed, 1 mm (0.040”) thick cover plates for wiring devices mounted in flush-mounted outlet box.
.5 Sheet metal cover plates for wiring devices mounted in surface-mounted FS or FD type conduit boxes.
.6 Weatherproof double lift spring-loaded cast aluminium cover plates, complete with gaskets for duplex receptacles as indicated.
.7 Weatherproof spring-loaded cast aluminium cover plates complete with gaskets for single receptacles or switches.
3 Execution
3.1 INSTALLATION
.1 Switches: .1 Install single throw switches with handle in "UP" position when switch closed. .2 Install switches in gang type outlet box when more than one switch is required in one location. .3 Mount toggle switches at height specified in Section 16010 - Electrical General Requirements or as indicated.
.2 Receptacles: .1 Install receptacles in gang type outlet box when more than one receptacle is required in one location. .2 Mount receptacles at height specified in Section 26 05 01 – Common Works Electrical.
Project Name: Nortrax Section 26 27 26
Project No: 13-013 WIRING DEVICES
Page 3
.3 Where split receptacle has one portion switched, mount vertically and switch upper portion.
.3 Cover plates: .1 Protect stainless steel cover plate finish with paper or plastic film until painting and other work is finished. .2 Install suitable common cover plates where wiring devices are grouped. .3 Do not use cover plates meant for flush outlet boxes on surface-mounted boxes.
END OF SECTION
Project Name: Nortrax Section 26 27 26
Project No: 13-013 WIRING DEVICES
Page 4
THIS PAGE LEFT INTENTIONALLY BLANK