TECHNICAL DRAWINGS REFURBISHMENT OF RADIOLOGY UNITS AT SELECTED DISTRICT HOSPITALS – LOT 2 (ADJUMANI GENERAL HOSPITAL, GENERAL HOSPITAL AND BULIISA GENERAL HOSPITAL)

Client:

MINISTRY OF HEALTH GOVERNMENT OF

Project:

TECHNICAL ASSISTANCE TO MOH UGANDA IN PROCUREMENT OF SIX (6) X-RAY MACHINES, AND REFURBISHMENT OF RADIOLOGY ROOMS AT DISTRICT HOSPITALS

PROJECT NO: #20849-0001 AUGUST 2018 TENDER DRAWINGS

GSPublisherVersion 0.0.100.100 Min 1.0m deep base 1000MM FROM GROUND LEVEL 1500

40 260 30 260 30 260 30 260 30 260 40 IMPLEMENTING FUNDING PROJECT LOCATION CONTRACTOR AGENCY AGENCY PROJECT SIGNBOARD HOSPITALS OF RADIOLOGYUNITATSELECTEDDISTRICT OF X-RAYMACHINESANDREFURBISHMENT TECHNICAL ASSISTANCEFORPROCUREMENT UNITED NATIONSOFFICEFORPROJECT SERVICES MINISTRY OFHEALTH GOVERNMENT OFUGANDA [ [ HOSPITAL NAME] CONTRACTOR DETAILS] 1120 1200 40 Wording textsize50mm NOTES: Board tobewhiteincolourandletter Board tohave2coatsundercoatforrust MS sheetplate2mmthickness black andwithclientagencylogos protection paintand2topcoatsofacrylic 30 x3mmsteelhollowsection as appropriate oil paint 40 x3mmsteelhollowsection Wording textsize40mm 40 x3mmsteelhollowsection DRAWN BY: DRAWING NUMBER: CHECKED BY: SCALE: APPROVD BY: 1. NO 3. PROJECT SIGNBOARD 2. 4. DRAWING TITLE: PROJECT: CLIENT: MINISTRY OFHEALTH HOSPITALS ROOMS ATSELECTEDDISTRICT REFURBISHMENT OFRADIOLOGY GOVERNMENT OFUGANDA exclusive propertyoftheUNOPS-ESAHandcan This designanddetailsare,atalltimesthe proceeding; promptly toobtainclarificationorconfirmationbefore before commencement; stated; time scaledfromdrawing; thus alldimensionsaretobereadandnotatany Written dimensionsoverridescaleddimensions, Any discrepancytobereportedtheEngineer All dimensionstobecheckedandconfirmedonsite All dimensionsareinmillimetersunlessotherwise not beusedorreproducedwithoutanywritten AS SHOWN MOH-UNOPS-000 REVISION Operational ExcellenceforResultsthatMatter UNOPS CountryOffice-Uganda Plot 15,Mackenzieclose,Kololo GENERAL NOTES TENDER DRAWINGS COPYRIGHT RESERVED East andSouthernAfricaHub UNOPS Building,UNLane, MWESIGWA B SANDRA D SANDRA D Off AvenueP.OBox783, Village Market,00621 -Uganda Nairobi, Kenya. consent KEY DATE APPR

ADJUMANI GENERAL HOSPITAL

TECHNICAL DRAWINGS: EXISTING FLOOR LAYOUT PLAN DEMOLITION PLAN PROPOSED MODIFICATIONS BARRIER WALL ELEVATION & DETAILS WINDOW AND DOOR DETAILS VIEW WINDOW DETAILS EQUIPMENT LAYOUT PLAN

Operational Excellence for Results that Matter East and Southern Africa Hub UNOPS Building, UN Lane, Off Avenue P.O Box 783, Village Market, 00621 Nairobi, Kenya.

E D C B A UNOPS Country Office - Uganda Plot 15, Mackenzie close, Kololo Kampala - Uganda 2.65 2.65 2.65 2.65 W1 W1 W1 W1 0.90 0.90 0.90 0.90 GENERAL NOTES

4 1. All dimensions are in millimeters unless otherwise stated;

2. All dimensions to be checked and confirmed on site before commencement;

3. Written dimensions override scaled dimensions, thus all dimensions are to be read and not at any time scaled from drawing; 1900 4. Any discrepancy to be reported to the Engineer REPORTING promptly to obtain clarification or confirmation before STORE ROOM ARCHIVE 3350 proceeding; /VIEWING ROOM 2800 ROOM 6600 2580 KEY

4250 2.40

860 D2 EXAMINATION ROOM 3 2.40 2.40 D5 D5 NO REVISION DATE APPR 3080 ELECTRICAL ROOM 1500

2.40 940 D4 880

2.40 2.40 890 D3 D3 2.40 2 D1 1050 1050

890 CHANGING CHANGING CUBICLE CUBICLE

1300 CLIENT: 3130 3800 GOVERNMENT OF UGANDA 1900 1180 2.40 2.40 MINISTRY OF HEALTH D3 D3 WAITING AREA 3100 3000 PROJECT: REFURBISHMENT OF RADIOLOGY 3080 ROOMS AT SELECTED DISTRICT ABOVE FL DARK ROOM GRILL -900mm HOSPITALS 2500 1700

DRAWING TITLE: 1 EXISTING FLOOR LAYOUT PLAN ADJUMANI GENERAL HOSPITAL RADIOLOGY UNIT

2.65 GRILL -900mm GRILL -900mm GRILL -900mm W3 DRAWING NUMBER: ABOVE FL ABOVE FL ABOVE FL 1.20 MOH-ADJ-001

SCALE: AS SHOWN CIRCULATION CIRCULATION

DRAWN BY: MWESIGWA B

CHECKED BY: SANDRA D

APPROVD BY: SANDRA D

TENDER DRAWINGS

EXISTING FLOOR LAYOUT PLAN (RADIOLOGY UNIT - ADJUMANI GENERAL HOSPITAL) COPYRIGHT RESERVED This design and details are, and at all times the SCALE: 1: 50 exclusive property of the UNOPS-ESAH and can not be used or reproduced without any written consent Operational Excellence for Results that Matter East and Southern Africa Hub UNOPS Building, UN Lane, Off Avenue P.O Box 783, Village Market, 00621 Nairobi, Kenya.

E D C B A UNOPS Country Office - Uganda Plot 15, Mackenzie close, Kololo Remove existing Remove existing Remove existing Kampala - Uganda 2.65 casement window 2.65 casement window 2.65 casement window 2.65 W1 W1 W1 W1 0.90 0.90 0.90 0.90 GENERAL NOTES

4 1. All dimensions are in millimeters unless otherwise stated;

2. All dimensions to be checked and confirmed on site before commencement;

Remove existing RC work 3. Written dimensions override scaled dimensions, thus all dimensions are to be read and not at any top and make good wall time scaled from drawing; to match existing finish 4. Any discrepancy to be reported to the Engineer REPORTING promptly to obtain clarification or confirmation before ARCHIVE proceeding; STORE ROOM /VIEWING ROOM ROOM KEY

Cut existing floor to create Existing R.Concrete Wall 2.40 base for barrier wall D2 EXAMINATION Remove existing New Masonry Wall ROOM semi-solid door Demolition 3 2.40 2.40 NO REVISION DATE APPR D5 D5 Remove existing semi-solid door Remove existing ELECTRICAL ROOM semi-solid door 2.40 D4

2.40 2.40 D3 D3 2.40 2 D1 Remove existing semi-solid door CHANGING CHANGING CUBICLE CUBICLE CLIENT: GOVERNMENT OF UGANDA 2.40 2.40 MINISTRY OF HEALTH D3 D3 WAITING AREA

PROJECT: REFURBISHMENT OF RADIOLOGY ROOMS AT SELECTED DISTRICT ABOVE FL DARK ROOM GRILL -900mm HOSPITALS

DRAWING TITLE: 1 DEMOLITION PLAN ADJUMANI GENERAL HOSPITAL RADIOLOGY UNIT

2.65 GRILL -900mm GRILL -900mm GRILL -900mm W3 DRAWING NUMBER: ABOVE FL ABOVE FL ABOVE FL 1.20 MOH-ADJ-002

SCALE: AS SHOWN CIRCULATION CIRCULATION

DRAWN BY: MWESIGWA B

CHECKED BY: SANDRA D

APPROVD BY: SANDRA D

TENDER DRAWINGS

DEMOLITION PLAN (RADIOLOGY UNIT - ADJUMANI GENERAL HOSPITAL) COPYRIGHT RESERVED

SCALE: 1: 50 This design and details are, and at all times the exclusive property of the UNOPS-ESAH and can not be used or reproduced without any written consent Operational Excellence for Results that Matter East and Southern Africa Hub UNOPS Building, UN Lane, Off Avenue P.O Box 783, Village Market, 00621 Nairobi, Kenya. Brick msonry Infill to raise window UNOPS Country Office - Uganda level to 2m Sill level Plot 15, Mackenzie close, Kololo E D C B A Kampala - Uganda

GENERAL NOTES

1. All dimensions are in millimeters unless otherwise 4 stated; 2. All dimensions to be checked and confirmed on site 5100 1200 before commencement;

3. Written dimensions override scaled dimensions, thus all dimensions are to be read and not at any R time scaled from drawing; 4. Any discrepancy to be reported to the Engineer promptly to obtain clarification or confirmation before 2070 proceeding; REPORTING ARCHIVE Q STORE ROOM CONTROL /VIEWING ROOM ROOM 135° CUBICLE KEY 400x400mm view window with 16mm lead glass at Existing R.Concrete Wall 1.2m FFL 800 New lead-lined door 2.40 New Masonry Wall 660 D2 EXAMINATION Demolition ROOM 325 New lead-lined door 325mm thick wall double leaf wall with embedded lead 3 NO REVISION DATE APPR New lead-lined door sheet to min height 2.5m

ELECTRICAL ROOM

2.40 D4

2.40 2.40 D3 D3 2.40 2 D1

CHANGING CHANGING New lead-lined door CUBICLE CUBICLE 600x400 radiation CLIENT: warning signage GOVERNMENT OF UGANDA MINISTRY OF HEALTH

WAITING AREA PROJECT: REFURBISHMENT OF RADIOLOGY ROOMS AT SELECTED DISTRICT HOSPITALS DARK ROOM DRAWING TITLE: PROPOSED RENOVATION WORKS 1 ADJUMANI GENERAL HOSPITAL PROPOSED REFURBISHMENT WORKS

DRAWING NUMBER: MOH-ADJ-003

SCALE: AS SHOWN 600x400 radiation warning signage CIRCULATION CIRCULATION

DRAWN BY: MWESIGWA B

CHECKED BY: SANDRA D

APPROVD BY: SANDRA D

TENDER DRAWINGS

PROPOSED MODIFICATIONS (RADIOLOGY UNIT - ADJUMANI GENERAL HOSPITAL) COPYRIGHT RESERVED This design and details are, and at all times the SCALE: 1: 50 exclusive property of the UNOPS-ESAH and can not be used or reproduced without any written consent Operational Excellence for Results that Matter East and Southern Africa Hub UNOPS Building, UN Lane, Off Avenue P.O Box 783, Village Market, 00621 550 Nairobi, Kenya.

UNOPS Country Office - Uganda Plot 15, Mackenzie close, Kololo New Fixed casement window with Kampala - Uganda 650 normal 6mm clear glazing

GENERAL NOTES

1. All dimensions are in millimeters unless otherwise stated; 3200

1100 Masonry brick infill to raise window 2. All dimensions to be checked and confirmed on site level to 2.0m sill level, plastered and before commencement; paint finish 3. Written dimensions override scaled dimensions, thus all dimensions are to be read and not at any time scaled from drawing; 2mm thick lead sheet 4. Any discrepancy to be reported to the Engineer promptly to obtain clarification or confirmation before Vinyl paint finish to match existing embedded in masonry wall proceeding;

900 Existing FFL wall surfaces (see schedule of finishes) KEY 150mm thick clay brick jointed with cement mortar (1:4mix) ELEVATION R 13mm thick cement plaster SCALE: 1: 20 finished ready for paint Existing FFL 13mm thick cement screed & NO REVISION DATE APPR 12mm thick terrazzo finish

Existing CFL Floor cut line 150 4T10 with R08 links @ 250mm centres 700 Base thickening with 150 150mm thick clay brick masonry wall leaf grade 25 concrete 1 with hoop iron strip every 2 courses

CLIENT:

900 2mm lead sheet pinned and embedded in BARRIER WALL FLOOR GOVERNMENT OF UGANDA masonry wall CONNECTION DETAIL MINISTRY OF HEALTH 150mm thick clay brick masonry wall leaf SCALE: 1: 10 PROJECT: 400 2 with hoop iron strips every 2 courses REFURBISHMENT OF RADIOLOGY 2500 400x400mm view window with lead lined ROOMS AT SELECTED DISTRICT frame & 16mm lead glass (5mm Pb HOSPITALS equivalent); contractor to provide DRAWING TITLE: specs/sample prior to installation 1200 Existing FFL BARRIER WALL ELEVATION & DETAILS 13mm cement plaster and paint finish to 13mm cement plaster and paint ADJUMANI GENERAL HOSPITAL wall finish to wall PROPOSED REFURBISHMENT WORKS

840 400 840 150mm thick clay brick jointed with DRAWING NUMBER: cement mortar (1:4mix) MOH-ADJ-004 SCALE: 400 2070 AS SHOWN

ELEVATION Q DRAWN BY: MWESIGWA B SCALE: 1: 20 CHECKED BY: SANDRA D 2mm thick lead sheet pinned and APPROVD BY: SANDRA D FINISHES SCHEDULE embedded between masonry wall

Element Description Existing Intervention Remark 1. Internal floor Terrazzo files floor Cleaning, polishing and sealing TENDER DRAWINGS 4T10 with R08 links @ 2. Internal wall Plaster and painted wall Sanding, 1 skimming coat, 2 coats emulsion Color to match existing BARRIER WALL DETAIL primer and 2 coat vinyl silk emulsion COPYRIGHT RESERVED SCALE: 1: 10 This design and details are, and at all times the exclusive property of the UNOPS-ESAH and can 3. Ceiling Gypsum panel false ceiling Repair damaged panels Panels to match existing not be used or reproduced without any written consent CODE (1no) (2no) (1no) (1no) CODE (3no) D3 D4 D2 D1

2100 300 W1 NEW LEAD-LINEDDOOR- D2 & D3DETAIL Lead-lined pressedsteelframewith Lead-lined pressedsteelframewith Lead-lined pressedsteelframewith Lead-lined pressedsteelframewith single rebate,doubledoorleafsize single rebate,doorleafsize single rebate,doorleafsize single rebate,doorleafsize 1400 x2050mmandPV300mm 900 x2050mmandPV300mm 820 x2050mmandPV300mm 820 x2050mmandPV300mm FRAME CONSTRUCTION FRAME CONSTRUCTION Steel casementframe;

780 830 x630(fixed) above above above above 860 DOOR SCHEDULE[NewLead-linedDoors] WINDOW SCHEDULE[New] SCALE: Hinged panelswith 1: 10 6mm glazing lead-lined, flushdoor lead-lined, flushdoor lead-lined, flushdoor lead lined,flushdoor Fixed MSlouverpanelabovedoor; 1400 x2050x40mm to bemaintained 900 x2050x40mm 820 x2050x40mm 820 x2050x40mm Door closerunit(providesample for approval) Lead-lined woodenswingdoor installation panels; contractortoprovidespecs PANEL for approvalpriortosupplyand lead lineddoorpanel 4no 100mmheavydutyhingesto base andfloor. max 5mmspacingbetweendoor SHUTTER SILL HEIGHT(mm) hinges, magneticlock 2000 swing hinges,door Lever handle,lock, swing hinges,door Lever handle,lock, swing hinges,door Lever handle,lock, Lever handle,lock, IRON MONGERY door closer,swing closer closer closer Replace existing ACTION Provide samplesfor Provide samplesfor Provide samplesfor Provide samplesfor REMARKS

2100 300 approval approval approval approval DETAIL NEW LEAD-LINEDDOOR- D4

780 880 SCALE: VERTICAL SECTION

1: 10 20 286 20 285 20 Fixed MSlouverpanelabovedoor; to bemaintained Door closerunit(providesample for approval) Lead-lined woodenswingdoor installation panels; contractortoprovidespecs for approvalpriortosupplyand SCALE: lead lineddoorpanel 4no 100mmheavydutyhingesto base andfloor. max 5mmspacingbetweendoor 30 1: 10 15x3mm flatplateweldedto 15x3mm flatplateweldedto 30x20x3mm steelRHSframe 30x20x3mm steelRHSframe with 3mmfilletweld with 3mmfilletweld Approved fixingputty 6mm clearglass

2100 300 350 20 NEW LEAD-LINEDDOOR- D1 DETAIL 30 680 20 385

1050 WINDOW -W1DETAIL HORIZONTAL SECTION 1470 385 SCALE: SCALE: 830 SCALE: 385 1: 10 1: 10 385 1: 10

285 285 20

630 20 15x3mm flatplateweldedto 30x20x3mm steelRHSframe approved putty 6mm clearglassfixedwith with 3mmfilletweld base andfloor. max 5mmspacingbetweendoor Fixed MSlouverpanelabovedoor; Magnetic interlockattopofdoor to bemaintained panels Door closerunit(providesample Rebate jointatdoorpanel Radiation warninglight;contractor Lead-lined woodenswingdoor installation panels; contractortoprovidespecs for approval) each lead-lineddoorpanel approval priortoinstallation to providespecs&samplefor 4no 100mmheavydutyhingesto for approvalpriortosupplyand Approved fixingputty 15x3mm flatplateweldedto 30x20x3mm steelRHSframe with 3mmfilletweld 6mm clearglass DRAWN BY: DRAWING NUMBER: CHECKED BY: SCALE: APPROVD BY: 1. PROPOSED REFURBISHMENTWORKS NO 3. 2. 4. ADJUMANI GENERALHOSPITAL DRAWING TITLE: PROJECT: CLIENT: DOOR ANDWINDOWDETAILS MINISTRY OFHEALTH HOSPITALS ROOMS ATSELECTEDDISTRICT REFURBISHMENT OFRADIOLOGY GOVERNMENT OFUGANDA exclusive propertyoftheUNOPS-ESAHandcan This designanddetailsare,atalltimesthe proceeding; promptly toobtainclarificationorconfirmationbefore before commencement; stated; time scaledfromdrawing; thus alldimensionsaretobereadandnotatany Written dimensionsoverridescaleddimensions, Any discrepancytobereportedtheEngineer All dimensionstobecheckedandconfirmedonsite All dimensionsareinmillimetersunlessotherwise not beusedorreproducedwithoutanywritten AS SHOWN MOH-ADJ-005 REVISION Operational ExcellenceforResultsthatMatter UNOPS CountryOffice-Uganda Plot 15,Mackenzieclose,Kololo GENERAL NOTES TENDER DRAWINGS COPYRIGHT RESERVED East andSouthernAfricaHub UNOPS Building,UNLane, MWESIGWA B SANDRA D SANDRA D Off AvenueP.OBox783, Village Market,00621 Kampala -Uganda Nairobi, Kenya. consent KEY DATE APPR Operational Excellence for Results that Matter East and Southern Africa Hub UNOPS Building, UN Lane, Off Avenue P.O Box 783, Village Market, 00621 Nairobi, Kenya.

400 UNOPS Country Office - Uganda Factory set Plot 15, Mackenzie close, Kololo Kampala - Uganda support profile 320

Factory set stop profile GENERAL NOTES Radiation 1. All dimensions are in millimeters unless otherwise NOTES: Control Room side stated; Room side 2. All dimensions to be checked and confirmed on site 16mm lead glass before commencement; 400 400 1. Options for frame material: Stainless 320 3. Written dimensions override scaled dimensions, thus all dimensions are to be read and not at any steel with brushed; or Aluminum Telescopic view time scaled from drawing; brushed and clear anodized finish or 4. Any discrepancy to be reported to the Engineer window frame promptly to obtain clarification or confirmation before MS with gray primer/powder coat proceeding;

finish. 2mm thick lead shielding KEY 2. All sheet lead shall be 99.9% pure. inside wall and frame X-RAY VIEW WINDOW 3. Contractor must verify lead shielding SCALE: 1: 10 equivalency requirement prior to VIEW WINDOW VERTICAL ordering. DETAIL SCALE: 1: 10 NO REVISION DATE APPR 4. Contractor to allow for testing of view window installation 16mm lead glass

Factory set stop profile 400

2mm thick lead shielding CLIENT: inside wall & frame GOVERNMENT OF UGANDA MINISTRY OF HEALTH

PROJECT: REFURBISHMENT OF RADIOLOGY Door Opening width ROOMS AT SELECTED DISTRICT Factory set support profile HOSPITALS Door Panel width DRAWING TITLE: Telescopic aluminum DOOR & VIEW WINDOW DETAILS ADJUMANI GENERAL HOSPITAL view window frame PROPOSED REFURBISHMENT WORKS 2mm thick lead shielding inside frame DRAWING NUMBER: VIEW WINDOW HORIZONTAL. MOH-ADJ-006 SCALE:

Wall thickness Wall thickness SCALE: 1: 10 AS SHOWN Door jamb width Door jamb width DETAIL

max. 5mm max. 5mm

100mm Heavy duty DRAWN BY: MWESIGWA B MS door frame primed hinge CHECKED BY: SANDRA D ready to paint Radiation Room side Solid wood edge trim APPROVD BY: SANDRA D 2mm Lead lining in door panel

20mm veneered wood panel TENDER DRAWINGS

COPYRIGHT RESERVED

DOOR FRAME DETAIL This design and details are, and at all times the exclusive property of the UNOPS-ESAH and can not be used or reproduced without any written SCALE: 1: 10 consent AC external unit fixed min. 200mm from Operational Excellence for Results that Matter East and Southern Africa Hub wall and at 2.4m height; Contractor to UNOPS Building, UN Lane, provide sample of on MS fixing brackets Off Avenue P.O Box 783, for Eng's approval Village Market, 00621 Nairobi, Kenya. drain hose E D C B A UNOPS Country Office - Uganda AC internal unit fixed at to ground Plot 15, Mackenzie close, Kololo min. 2.5m height from FFL Kampala - Uganda

GENERAL NOTES

4 1. All dimensions are in millimeters unless otherwise

H IND H stated;

2. All dimensions to be checked and confirmed on site X-Ray Machine before commencement; Chest X-Ray Acquisition 3. Written dimensions override scaled dimensions, Bucky Generator H Reporting Station thus all dimensions are to be read and not at any Control panel Station time scaled from drawing;

4. Any discrepancy to be reported to the Engineer H REPORTING promptly to obtain clarification or confirmation before

ARCHIVE IND STORE ROOM /VIEWING ROOM proceeding; ROOM X-Ray Bucky Table KEY

Existing Lighting switch 2.40 9kg chemical powder D2 IND

fire extinguishers fixed EXAMINATION Existing 3-Phase Power outlet at 1.2m FFL ROOM H Floor cable trench200mm x DP Existing 1-Phase Power (13A) 100mm deep with chequered 3 metal slot cover (existing) NO REVISION DATE APPR

ELECTRICAL ROOM

2.40

D4 H

2.40 2.40 D3 D3 2.40 2 D1 DP 9kg chemical powder CHANGING CHANGING fire extinguishers fixed CUBICLE CUBICLE at 1.2m FFL CLIENT: GOVERNMENT OF UGANDA MINISTRY OF HEALTH

Wooden wall hung WAITING AREA cassette cabinet fixed PROJECT: 1.35m above FFL REFURBISHMENT OF RADIOLOGY ROOMS AT SELECTED DISTRICT DARK ROOM HOSPITALS

DRAWING TITLE:

EQUIPMENT LAYOUT PLAN H H 1 ADJUMANI GENERAL HOSPITAL RADIOLOGY UNIT

DRAWING NUMBER: Drain to AC internal unit fixed at MOH-ADJ-007 gully pit min. 2.5m height from FFL SCALE: AS SHOWN CIRCULATION AC external unit fixed min. 200mm from CIRCULATION wall and at 2.4m height; Contractor to provide sample of on MS fixing brackets for Eng's approval DRAWN BY: MWESIGWA B

CHECKED BY: SANDRA D

APPROVD BY: SANDRA D

TENDER DRAWINGS EQUIPMENT LAYOUT PLAN (RADIOLOGY UNIT - ADJUMANI GENERAL HOSPITAL) COPYRIGHT RESERVED SCALE: 1: 50 This design and details are, and at all times the exclusive property of the UNOPS-ESAH and can not be used or reproduced without any written consent

KIBOGA GENERAL HOSPITAL

TECHNICAL DRAWINGS: EXISTING FLOOR LAYOUT PLAN DEMOLITION PLAN PROPOSED MODIFICATIONS BARRIER WALL ELEVATION & DETAILS WINDOW AND DOOR DETAILS VIEW WINDOW DETAILS EQUIPMENT LAYOUT PLAN

ENTRANCE

TO WARDS TO OPD / LAB CIRCULATION 3.15 D5 A

3920 3.15 D1 1400 1380 3.95 2.10 WASHROOM W5 1.04 2.70 W2 ARCHIVE ROOM Cement screed Cement screed 2750 B 3.15 D5 EXISTING LAYOUTPLAN(RADIOLOGY UNIT-KIBOGAGENERALHOSPITAL) 1.04 2.70 2.10 2.95 W2 3920 W3 ROOM REPORTING/ VIEWING Cement tiles Cement tiles WAITING AREA 3000 3000 0.95 2.90 W4 3.15 D5 1.04 2.70 W2 3040 2950 SCALE: 3.15 C D5 CIRCULATION 1: 50 2750 WASHROOM 1550 1600 Cement screed STORE ROOM 1.04 2.70 W2

2820200 Cement screed 2.55 2.55 D3 D3 D 2.20 D2 580 1960 870 200 900 200 1650 580 Terrazzo tiles EXAMINATION ROOM

580 2.10 D4 1.04 2.70 W1 DARK ROOM 4250 Cement screed 2850 TO STORAGE

250 5900 250

2570 E 250 NOTES: · · · · Internal floorfinishis Internal wallfinishispainted Examination roomwallsare plaster walls Ceiling finishissuspended gypsum panel 250mm thickR.Concrete; terrazzo screed 1 3 2 4 DRAWN BY: DRAWING NUMBER: CHECKED BY: SCALE: APPROVD BY: 1. NO 3. 2. 4. DRAWING TITLE: PROJECT: CLIENT: RADIOLOGY UNIT KIBOGA GENERALHOSPITAL EXISTING FLOORLAYOUTPLAN MINISTRY OFHEALTH HOSPITALS ROOMS ATSELECTEDDISTRICT REFURBISHMENT OFRADIOLOGY GOVERNMENT OFUGANDA exclusive propertyoftheUNOPS-ESAHandcan This designanddetailsare,atalltimesthe proceeding; promptly toobtainclarificationorconfirmationbefore before commencement; stated; time scaledfromdrawing; thus alldimensionsaretobereadandnotatany Written dimensionsoverridescaleddimensions, Any discrepancytobereportedtheEngineer All dimensionstobecheckedandconfirmedonsite All dimensionsareinmillimetersunlessotherwise not beusedorreproducedwithoutanywritten AS SHOWN MOH-KIB-001 REVISION Operational ExcellenceforResultsthatMatter UNOPS CountryOffice-Uganda Plot 15,Mackenzieclose,Kololo GENERAL NOTES TENDER DRAWINGS COPYRIGHT RESERVED East andSouthernAfricaHub UNOPS Building,UNLane, MWESIGWA B SANDRA D SANDRA D Off AvenueP.OBox783, Village Market,00621 Kampala -Uganda Nairobi, Kenya. consent KEY DATE APPR Operational Excellence for Results that Matter East and Southern Africa Hub UNOPS Building, UN Lane, Off Avenue P.O Box 783, Village Market, 00621 Nairobi, Kenya.

UNOPS Country Office - Uganda Plot 15, Mackenzie close, Kololo Kampala - Uganda TO WARDS CIRCULATION A B C D TO STORAGE E GENERAL NOTES 3.95 2.90 1. All dimensions are in millimeters unless otherwise W5 W4 stated; 2.10 0.95 2. All dimensions to be checked and confirmed on site 2.10 before commencement; D4 1 3. Written dimensions override scaled dimensions, thus all dimensions are to be read and not at any time scaled from drawing;

4. Any discrepancy to be reported to the Engineer promptly to obtain clarification or confirmation before proceeding;

KEY DARK ROOM Existing R.Concrete Wall STORE ROOM

New Masonry Wall 2.55 WAITING AREA D3 Demolition

3.15

D5 WASHROOM NO REVISION DATE APPR 2

Remove existing 3.15 semi-solid door D1 2.20 D2

2.95 W3 2.10 3.15 D5 CLIENT: 3 GOVERNMENT OF UGANDA MINISTRY OF HEALTH 3.15 D5 Cut existing floor to create base for barrier wall PROJECT: REFURBISHMENT OF RADIOLOGY ROOMS AT SELECTED DISTRICT EXAMINATION HOSPITALS

CIRCULATION ROOM 2.55

D3 DRAWING TITLE: Remove existing REPORTING/ VIEWING FLOOR LAYOUT PLAN ROOM semi-solid door KIBOGA GENERAL HOSPITAL RADIOLOGY UNIT

DRAWING NUMBER:

ARCHIVE ROOM MOH-KIB-002 WASHROOM 3.15 SCALE: D5 AS SHOWN Remove existing casement window

DRAWN BY: MWESIGWA B

4 CHECKED BY: SANDRA D 2.70 2.70 2.70 2.70 2.70 Remove existing W2 W2 W2 W2 W1 extraction fan frame APPROVD BY: SANDRA D 1.04 1.04 1.04 1.04 1.04

TENDER DRAWINGS TO OPD / LAB COPYRIGHT RESERVED DEMOLITION PLAN (RADIOLOGY UNIT - KIBOGA GENERAL HOSPITAL) This design and details are, and at all times the exclusive property of the UNOPS-ESAH and can not be used or reproduced without any written SCALE: 1: 50 consent Operational Excellence for Results that Matter East and Southern Africa Hub UNOPS Building, UN Lane, Off Avenue P.O Box 783, Village Market, 00621 Nairobi, Kenya.

UNOPS Country Office - Uganda Plot 15, Mackenzie close, Kololo

TO WARDS Kampala - Uganda CIRCULATION TO STORAGE A B C D E GENERAL NOTES

1. All dimensions are in millimeters unless otherwise stated;

2. All dimensions to be checked and confirmed on site 1 before commencement; 3. Written dimensions override scaled dimensions, thus all dimensions are to be read and not at any time scaled from drawing;

4. Any discrepancy to be reported to the Engineer promptly to obtain clarification or confirmation before proceeding;

DARK ROOM KEY

STORE ROOM Existing R.Concrete Wall

New Masonry Wall WAITING AREA

Demolition WASHROOM 2 NO REVISION DATE APPR

CONTROL

810 CUBICLE 325mm thick brick wall New lead shielded 325

1480 double leaf wall with door 2.20 embedded lead sheet to 600x400 mm Radiation D2 135° min height 2.5m warning signage 1070 325

CLIENT: 2010 3 GOVERNMENT OF UGANDA 3.15 MINISTRY OF HEALTH 400x400mm view window D5 New lead shielded door Q with 16mm lead glass at 1.2m FFL New lead shielded PROJECT: door REFURBISHMENT OF RADIOLOGY EXAMINATION ROOMS AT SELECTED DISTRICT

CIRCULATION ROOM HOSPITALS 2.55 D3 REPORTING/ VIEWING DRAWING TITLE: ROOM PROPOSED RENOVATION WORKS 4120 KIBOGA GENERAL HOSPITAL PROPOSED REFURBISHMENT WORKS

DRAWING NUMBER: ARCHIVE ROOM

WASHROOM MOH-KIB-003 Brick msonry Infill to close existing window SCALE: R AS SHOWN opening Brick masonry Infill to close existing fan hole 30 2700 1560

DRAWN BY: MWESIGWA B

4 CHECKED BY: SANDRA D

APPROVD BY: SANDRA D NOTES: · Examination room walls are 250mm thick R.Concrete; · Internal wall finish is painted TENDER DRAWINGS TO OPD / LAB plaster walls · Internal floor finish is COPYRIGHT RESERVED terrazzo screed This design and details are, and at all times the PROPOSED MODIFICATION (RADIOLOGY UNIT - KIBOGA GENERAL HOSPITAL) exclusive property of the UNOPS-ESAH and can · Ceiling finish is suspended not be used or reproduced without any written SCALE: 1: 50 gypsum panel consent Operational Excellence for Results that Matter East and Southern Africa Hub UNOPS Building, UN Lane, Off Avenue P.O Box 783,

600 Masonry brick infill to existing Village Market, 00621 extraction fan openings Nairobi, Kenya.

UNOPS Country Office - Uganda Plot 15, Mackenzie close, Kololo Kampala - Uganda 2mm thick lead sheet embedded in masonry wall GENERAL NOTES

1660 Masonry brick infill to blockout 1. All dimensions are in millimeters unless otherwise window, plastered and paint 150mm thick clay brick jointed stated; 3300 finish with cement mortar (1:4mix) 2. All dimensions to be checked and confirmed on site before commencement;

13mm thick cement plaster 3. Written dimensions override scaled dimensions, thus all dimensions are to be read and not at any Vinyl paint finish to match finished ready for paint time scaled from drawing; existing wall surfaces (see Existing FFL 4. Any discrepancy to be reported to the Engineer schedule of finishes) 13mm thick cement screed & promptly to obtain clarification or confirmation before proceeding; 1040 Existing FFL 12mm thick terrazzo finish KEY Floor cut line 150 4T10 with R08 links @ ELEVATION R 250mm centres Base thickening with 150 SCALE: 1: 20 grade 25 concrete

NO REVISION DATE APPR

Existing FFL

13mm cement plaster and paint 800 finish to wall

150mm thick clay brick masonry wall leaf 150mm thick clay brick jointed with 1 with hoop iron strip every 2 courses cement mortar (1:4mix)

CLIENT: 900 2mm lead sheet pinned and GOVERNMENT OF UGANDA embedded in masonry wall MINISTRY OF HEALTH 3300 150mm thick clay brick masonry wall leaf 400 2 with hoop iron strip every 2 courses PROJECT: REFURBISHMENT OF RADIOLOGY 400x400mm view window with lead lined 2mm thick lead sheet pinned and ROOMS AT SELECTED DISTRICT frame & 16mm lead glass (5mm Pb HOSPITALS embedded between masonry wall equivalent); contractor to provide DRAWING TITLE: 1200 specs/sample prior to installation Existing FFL BARRIER WALL DETAIL ELEVATION AND SECTION DETAILS 13mm cement plaster and KIBOGA GENERAL HOSPITAL PROPOSED REFURBISHMENT WORKS paint finish to wall SCALE: 1: 10 1550 400 800 DRAWING NUMBER: MOH-KIB-004

760 2010 SCALE: AS SHOWN ELEVATION Q

DRAWN BY: MWESIGWA B SCALE: 1: 20

CHECKED BY: SANDRA D FINISHES SCHEDULE APPROVD BY: SANDRA D Element Description Existing Intervention Remark 1. Internal floor Terrazzo tiles floor Cleaning, polishing and sealing TENDER DRAWINGS 2. Internal wall Plaster and painted wall Sanding, 1 skimming coat, 2 coats emulsion Color to match existing primer and 2 coat vinyl silk emulsion COPYRIGHT RESERVED

This design and details are, and at all times the 3. Ceiling Gypsum panel false ceiling exclusive property of the UNOPS-ESAH and can Replace damaged panels Panels to match existing not be used or reproduced without any written consent CODE

W1 2200 FRAME CONSTRUCTION NEW LEAD-LINEDDOOR-D2 DETAIL Carefully takedown 730 550 WINDOW SCHEDULE[Modifications] 1580 SCALE: PANEL N/A 1: 10 SILL HEIGHT(mm) N/A Radiation warninglight;contractor Door closerunit(providesample Magnetic interlockattopofdoor Lead-lined woodenswingdoor base andfloor. max 5mmspacingbetweendoor installation panels; contractortoprovidespecs panels each lead-lineddoorpanel to installation to providespecsforapprovalprior 4no 100mmheavydutyhingesto for approvalpriortosupplyand for approval) Fill withbrickmasonry ACTION wall CODE (1no) (2no) (1no) D5 D3 D2 Lead-lined pressedsteelframewith Lead-lined pressedsteelframewith single rebate,doubledoorleafsize single rebate,doorleafsize x2040mm andPV1000mmabove rebate, singledoorleafsize820 1550 x2040mmandPV400mm 820 x2040mmandPV1000mm Pressed steelframewithsingle FRAME CONSTRUCTION above above DOOR SCHEDULE[NewLead-linedDoor] NEW LEAD-LINEDDOOR-D3 DETAIL 2200 450

lead-lined, flushpaneldoor lead-lined, flushpaneldoor lead-lined, flushpaneldoor 780 1550 x2040x40mm 820 x2040x40mm 820 x2040x40mm 870 SHUTTER SCALE: closer, swinghinges, 1: 10 swing hinges,door Lever handle,lock, swing hinges,door Lever handle,lock, IRON MONGERY Pull handle,door Existing fixedglasspanelto Lead-lined woodenswingdoor installation panels; contractortoprovidespecs be maintained magnetic lock for approvalpriortosupplyand Door closerunit(providesample for approval) lead lineddoorpanel 4no 100mmheaveydutyhingesto base andfloor. max 5mmspacingbetweendoor closer closer provided forapproval provided forapproval provided forapproval Samples tobe Samples tobe Samples tobe REMARKS DRAWN BY: DRAWING NUMBER: CHECKED BY: SCALE: APPROVD BY: 1. PROPOSED REFURBISHMENTWORKS KIBOGA GENERALHOSPITAL NO 3. 2. 4. WINDOW &DOORDETAILS DRAWING TITLE: PROJECT: CLIENT: MINISTRY OFHEALTH HOSPITALS ROOMS ATSELECTEDDISTRICT REFURBISHMENT OFRADIOLOGY GOVERNMENT OFUGANDA exclusive propertyoftheUNOPS-ESAHandcan This designanddetailsare,atalltimesthe proceeding; promptly toobtainclarificationorconfirmationbefore before commencement; stated; time scaledfromdrawing; thus alldimensionsaretobereadandnotatany Written dimensionsoverridescaleddimensions, Any discrepancytobereportedtheEngineer All dimensionstobecheckedandconfirmedonsite All dimensionsareinmillimetersunlessotherwise not beusedorreproducedwithoutanywritten AS SHOWN MOH-KIB-005 REVISION Operational ExcellenceforResultsthatMatter UNOPS CountryOffice-Uganda Plot 15,Mackenzieclose,Kololo GENERAL NOTES TENDER DRAWINGS COPYRIGHT RESERVED East andSouthernAfricaHub UNOPS Building,UNLane, MWESIGWA B SANDRA D SANDRA D Off AvenueP.OBox783, Village Market,00621 Kampala -Uganda Nairobi, Kenya. consent KEY DATE APPR Operational Excellence for Results that Matter East and Southern Africa Hub UNOPS Building, UN Lane, Off Avenue P.O Box 783, 400 Village Market, 00621 Factory set Nairobi, Kenya. 320 UNOPS Country Office - Uganda support profile Plot 15, Mackenzie close, Kololo Kampala - Uganda Factory set stop profile Radiation GENERAL NOTES Control Room side 1. All dimensions are in millimeters unless otherwise NOTES: 16mm lead glass Room side stated; 2. All dimensions to be checked and confirmed on site 400 400 320 before commencement; Telescopic view 3. Written dimensions override scaled dimensions, 1. Options for frame material: Stainless thus all dimensions are to be read and not at any steel with brushed; or Aluminum window frame time scaled from drawing; 4. Any discrepancy to be reported to the Engineer brushed and clear anodized finish or promptly to obtain clarification or confirmation before proceeding; MS with gray primer/powder coat 2mm thick lead shielding finish. inside wall and frame X-RAY VIEW WINDOW KEY 2. All sheet lead shall be 99.9% pure. SCALE: 1: 10 3. Contractor must verify lead shielding VIEW WINDOW VERTICAL equivalency requirement prior to DETAIL SCALE: 1: 10 ordering. 16mm lead glass NO REVISION DATE APPR 4. Contractor to allow for testing of view window installation Factory set stop profile 400

2mm thick lead shielding inside wall & frame CLIENT: GOVERNMENT OF UGANDA MINISTRY OF HEALTH

PROJECT: Factory set support profile REFURBISHMENT OF RADIOLOGY ROOMS AT SELECTED DISTRICT Door Opening width HOSPITALS Telescopic aluminum Door Panel width DRAWING TITLE: view window frame VIEW WINDOW DETAILS KIBOGA GENERAL HOSPITAL PROPOSED REFURBISHMENT WORKS

2mm thick lead VIEW WINDOW HORIZONTAL. DRAWING NUMBER: shielding inside frame DETAIL SCALE: 1: 10 MOH-KIB-006 SCALE: AS SHOWN Wall thickness Wall thickness Door jamb width Door jamb width

max. 5mm max. 5mm 100mm Heavy duty DRAWN BY: MWESIGWA B MS door frame primed hinge CHECKED BY: SANDRA D

ready to paint Radiation APPROVD BY: SANDRA D Room side Solid wood edge trim 2mm Lead lining in door panel TENDER DRAWINGS

20mm veneered wood panel COPYRIGHT RESERVED

This design and details are, and at all times the DOOR FRAME DETAIL exclusive property of the UNOPS-ESAH and can not be used or reproduced without any written consent SCALE: 1: 10 Operational Excellence for Results that Matter East and Southern Africa Hub UNOPS Building, UN Lane, Off Avenue P.O Box 783, Village Market, 00621 Nairobi, Kenya.

UNOPS Country Office - Uganda Plot 15, Mackenzie close, Kololo

TO WARDS Kampala - Uganda CIRCULATION TO STORAGE AC external unit fixed on min. 200mm A B C D Drain to E from wall and at 2.4m height; GENERAL NOTES Existing extraction fan gully pit Contractor to provide sample of on MS fixing brackets for Eng's approval 1. All dimensions are in millimeters unless otherwise stated;

2. All dimensions to be checked and confirmed on site 1 before commencement; H H 3. Written dimensions override scaled dimensions, thus all dimensions are to be read and not at any AC internal unit fixed at min. time scaled from drawing; 2.5m height from FFL 4. Any discrepancy to be reported to the Engineer promptly to obtain clarification or confirmation before proceeding;

DARK ROOM KEY STORE ROOM Existing Lighting switch Wooden wall hung WAITING AREA IND

cassette cabinet fixed Existing 3-Phase Power outlet 1.35m above FFL H

WASHROOM Existing 1-Phase Power (13A) H H

2 NO REVISION DATE APPR DP H 9kg chemical powder fire extinguishers fixed

9kg chemical powder at 1.2m FFL Station

fire extinguishers fixed Acquisition at 1.2m FFL 2.20 D2 H Control panel

DP DB 3 CLIENT: X-Ray GOVERNMENT OF UGANDA 3.15 generator MINISTRY OF HEALTH D5

PROJECT: IND REFURBISHMENT OF RADIOLOGY EXAMINATION ROOMS AT SELECTED DISTRICT

CIRCULATION ROOM 2.55 HOSPITALS D3 REPORTING/ VIEWING DRAWING TITLE: ROOM

X-Ray machine EQUIPMENT LAYOUT PLAN X-Ray bucky table KIBOGA GENERAL HOSPITAL RADIOLOGY UNIT

H DRAWING NUMBER: ARCHIVE ROOM

WASHROOM Floor cable trench MOH-KIB-007 Reporting 100x100mm deep SCALE: Station with chequered AS SHOWN metal slot cover

Chest bucky H DRAWN BY: MWESIGWA B

4 CHECKED BY: SANDRA D

APPROVD BY: SANDRA D AC external unit fixed on min. 200mm from wall and at 2.4m AC internal unit fixed at min. height; Contractor to provide 2.5m height from FFL sample of MS fixing brackets for Drain to TENDER DRAWINGS TO OPD / LAB Eng's approval ground COPYRIGHT RESERVED

This design and details are, and at all times the exclusive property of the UNOPS-ESAH and can EQUIPMENT LAYOUT PLAN (RADIOLOGY UNIT - KIBOGA GENERAL HOSPITAL) not be used or reproduced without any written consent SCALE: 1: 50

BULIISA GENERAL HOSPITAL

TECHNICAL DRAWINGS: EXISTING FLOOR LAYOUT PLAN DEMOLITION PLAN PROPOSED MODIFICATIONS BARRIER WALL ELEVATION & DETAILS VIEW WINDOW DETAILS EQUIPMENT LAYOUT PLAN

PROJECT SIGN BOARD TYPICAL CASSETTE CABINET DETAILS 1.50 2.15 W3 1.50 1.50 2.15 W3 2.15 W3 E WC 2.15 D4 1570 2410 OFFICE/REPORTING STORE 1880 CH./RM 800 0.95 2.15 W1 3320 3500 Existing concretebench E 2.15 D4 230 230 EXISTING LAYOUTPLAN(RADIOLOGY UNIT-BULIISAGENERALHOSPITAL)

2170 3000 2200 2170 2.30 2.90 W2 E

1500 3180 WAITING AREA 2660 5520 2.15 D1 EXAMINATION ROOM 2.15 D2 SCALE: 3350 CIRCULATION 2.15 D3 1: 50 E 2.15 D4 2.30 2.90 W2 CH./RM 3950 900 1.50 2.15 W3 2100 230 230 WC Existing concretebench E 2.15 D4 2.15 D4 STORE 1380 2.15 3110 D4 890 1400 2.15 D4 230 0.95 2.15 W1 E ULTRASOUND SCAN 900 DARK ROOM 4000 3020 0.95 2.15 W1

3110 660 900 3600 E 1.50 2.15 W3 NOTES: · · · · Internal floorfinishiscement Internal wallfinishispainted Examination roomwallsare plaster walls Gypsum panels Ceiling finishissuspended screed 230mm thickbrickmasonry; 1 1 1 2 DRAWN BY: DRAWING NUMBER: CHECKED BY: SCALE: APPROVD BY: 1. NO 3. 2. 4. DRAWING TITLE: PROJECT: CLIENT: MINISTRY OFHEALTH HOSPITALS ROOMS ATSELECTEDDISTRICT REFURBISHMENT OFRADIOLOGY GOVERNMENT OFUGANDA exclusive propertyoftheUNOPS-ESAHandcan This designanddetailsare,atalltimesthe proceeding; promptly toobtainclarificationorconfirmationbefore before commencement; stated; time scaledfromdrawing; thus alldimensionsaretobereadandnotatany Written dimensionsoverridescaleddimensions, Any discrepancytobereportedtheEngineer All dimensionstobecheckedandconfirmedonsite All dimensionsareinmillimetersunlessotherwise not beusedorreproducedwithoutanywritten RADIOLOGY UNIT BULISA GENERALHOSPITAL AS SHOWN MOH-BUL-001 EXISTING FLOORLAYOUTPLAN REVISION Operational ExcellenceforResultsthatMatter UNOPS CountryOffice-Uganda Plot 15,Mackenzieclose,Kololo GENERAL NOTES TENDER DRAWINGS COPYRIGHT RESERVED East andSouthernAfricaHub UNOPS Building,UNLane, MWESIGWA B SANDRA D SANDRA D Off AvenueP.OBox783, Village Market,00621 Kampala -Uganda Nairobi, Kenya. consent KEY DATE APPR Operational Excellence for Results that Matter East and Southern Africa Hub UNOPS Building, UN Lane, Off Avenue P.O Box 783, Village Market, 00621 Nairobi, Kenya. CIRCULATION UNOPS Country Office - Uganda Plot 15, Mackenzie close, Kololo Kampala - Uganda E E E E E E E GENERAL NOTES 2.15 2.15 2.15 2.15 W1 W3 W1 Existing concrete bench Existing concrete bench W1 1. All dimensions are in millimeters unless otherwise 0.95 1.50 0.95 0.95 stated;

2.15 1 2. All dimensions to be checked and confirmed on site D1 before commencement; 3. Written dimensions override scaled dimensions, thus all dimensions are to be read and not at any time scaled from drawing; WC 4. Any discrepancy to be reported to the Engineer promptly to obtain clarification or confirmation before 2.15 proceeding; D4

OFFICE/REPORTING ULTRASOUND KEY SCAN Existing Brick Masonry Wall 2.15 2.15 D3 New Masonry Wall W3 1.50 WAITING AREA Demolition 2.15 2.15 W3 D4 1.50 NO REVISION DATE APPR 2.15 D4 CH./RM

2.15 D4 2 2.15 W3 2.15 1.50 D4

2.15 2.15 D4 D2 1 CLIENT: GOVERNMENT OF UGANDA WC MINISTRY OF HEALTH Carefully takedown existing lead sliding door, to allow for 2.15

repair of sliding rail track and D4 PROJECT: 2.15 door handles reinstall W3 REFURBISHMENT OF RADIOLOGY 1.50 ROOMS AT SELECTED DISTRICT CH./RM HOSPITALS EXAMINATION ROOM DRAWING TITLE: STORE DARK ROOM DEMOLITION PLAN BULISA GENERAL HOSPITAL RADIOLOGY UNIT Cut existing floor to create base for barrier wall DRAWING NUMBER: MOH-BUL-002

SCALE: AS SHOWN STORE

DRAWN BY: MWESIGWA B 1 CHECKED BY: 2.90 2.90 SANDRA D W2 W2 2.30 2.30 APPROVD BY: SANDRA D

TENDER DRAWINGS

COPYRIGHT RESERVED

DEMOLITION PLAN (RADIOLOGY UNIT - BULIISA GENERAL HOSPITAL) This design and details are, and at all times the exclusive property of the UNOPS-ESAH and can SCALE: 1: 50 not be used or reproduced without any written consent Operational Excellence for Results that Matter East and Southern Africa Hub UNOPS Building, UN Lane, Off Avenue P.O Box 783, Village Market, 00621 Nairobi, Kenya. CIRCULATION UNOPS Country Office - Uganda Plot 15, Mackenzie close, Kololo Kampala - Uganda E E E E E E E GENERAL NOTES Existing concrete bench Existing concrete bench 1. All dimensions are in millimeters unless otherwise stated; 1 2. All dimensions to be checked and confirmed on site before commencement;

3. Written dimensions override scaled dimensions, thus all dimensions are to be read and not at any WC time scaled from drawing; 4. Any discrepancy to be reported to the Engineer promptly to obtain clarification or confirmation before proceeding;

OFFICE/REPORTING ULTRASOUND KEY SCAN Existing Brick Masonry Wall

New Masonry Wall

WAITING AREA Demolition

NO REVISION DATE APPR

CH./RM 2 600x400 mm Radiation warning signage Re-adjust level of existing lead lined door sliding track & repair broken handles

2.15 D2 1 CLIENT: WC New lead-lined privacy GOVERNMENT OF UGANDA screen with sliding rail MINISTRY OF HEALTH 1080 2.15 D5 PROJECT: 325mm thick wall double REFURBISHMENT OF RADIOLOGY ROOMS AT SELECTED DISTRICT CH./RM 325 leaf wall with embedded HOSPITALS lead sheet to min height 800 420 2.5mEXAMINATION ROOM DRAWING TITLE: 4000 STORE DARK ROOM PROPOSED RENOVATIONS WORKS CONTROL BULIISA GENERAL HOSPITAL ROOM Q PROPOSED REFURBISHMENT WORKS D1.1 2880 DRAWING NUMBER:

400x400mm view window 2mm lead sheet Additional lead sheet lining with 16mm lead glass at shielding up to 2.0m MOH-BUL-003 1220 1.2m FFL FFL SCALE: AS SHOWN STORE

DRAWN BY: MWESIGWA B 1 CHECKED BY: SANDRA D

Install new vinyl sheet flooring to APPROVD BY: SANDRA D x-ray examination room

TENDER DRAWINGS

COPYRIGHT RESERVED PROPOSED MODIFICATIONS (RADIOLOGY UNIT - BULIISA GENERAL HOSPITAL) This design and details are, and at all times the exclusive property of the UNOPS-ESAH and can SCALE: 1: 50 not be used or reproduced without any written consent 2500

1200 400 900 700 Existing FFL

150 150 1220 Existing CFL 150 BARRIER WALLFLOOR CONNECTION DETAIL Existing FFL ELEVATION Q SCALE: SCALE: 2850 400 1: 20 1: 10 1220 150 150mm thickclaybrickjointed with cementmortar(1:4mix) embedded inmasonrywall 2mm thickleadsheet 13mm thickcementplaster finished readyforpaint 12mm thickterrazzofinish 13mm thickcementscreed& 230 Base thickeningwith grade 25concrete 250mm centres 4T10 withR08links@ Floor cutline equivalent); contractortoprovide specs/sample priortoinstallation 400x400mm viewwindowwithleadlined frame &16mmleadglass(5mmPb 13mm cementplasterand 150mm thickclaybrick 150mm thickclaybrick paint finishtowall masonry wallleaf2 masonry wallleaf1 embedded inmasonrywall 2mm leadsheetpinnedand BARRIER WALLDETAIL 1. 3. 2. 13mm cementplasterandpaint finish towall Internal wall Internal floor SCALE: Element Description Ceiling FINISHES SCHEDULE 1: 10 150mm thickclaybrickjointedwith cement mortar(1:4mix) embedded betweenmasonrywall 2mm thickleadsheetpinnedand Plaster andpaintedwall Existing Gypsum panelfalseceiling Cement screed WALL SHIELDINGDETAIL-D1.1 and leadplug existing masonrywallwithscrew 2mm thickleadsheetpinned Install vinylsheetflooring Repair damagedpanels Intervention primer and2coatvinylsilkemulsion Sanding, 1skimmingcoat,2coatsemulsion with approvedbondingglue plaster finishedwall(existing) 230mm thickclaybrick& SCALE: 1: 10 Panels tomatchexisting Remark Color tomatchexisting Sample tobeprovidedfor approval 12.5mm thickMRgypsumboard approval) adhesive (providespecfor over leadsheetfixedwithmastic DRAWN BY: DRAWING NUMBER: CHECKED BY: SCALE: APPROVD BY: 1. NO 3. 2. 4. DRAWING TITLE: PROJECT: CLIENT: PROPOSED REFURBISHMENTWORKS BULIISA GENERALHOSPITAL MINISTRY OFHEALTH HOSPITALS ROOMS ATSELECTEDDISTRICT REFURBISHMENT OFRADIOLOGY GOVERNMENT OFUGANDA exclusive propertyoftheUNOPS-ESAHandcan ELEVATIONS &SECTIONDETAILS This designanddetailsare,atalltimesthe proceeding; promptly toobtainclarificationorconfirmationbefore before commencement; stated; time scaledfromdrawing; thus alldimensionsaretobereadandnotatany Written dimensionsoverridescaleddimensions, Any discrepancytobereportedtheEngineer All dimensionstobecheckedandconfirmedonsite All dimensionsareinmillimetersunlessotherwise not beusedorreproducedwithoutanywritten AS SHOWN MOH-BUL-004 REVISION Operational ExcellenceforResultsthatMatter UNOPS CountryOffice-Uganda Plot 15,Mackenzieclose,Kololo GENERAL NOTES TENDER DRAWINGS COPYRIGHT RESERVED East andSouthernAfricaHub UNOPS Building,UNLane, MWESIGWA B SANDRA D SANDRA D Off AvenueP.OBox783, Village Market,00621 Kampala -Uganda Nairobi, Kenya. consent KEY DATE APPR 2230 CODE D5 D2 D5 DETAIL NEW LEAD-LINEDSCREEN- closing end,slidingdooropening closing end,slidingdooropening Steel anglesupportframeonthe Steel anglesupportframeonthe FRAME CONSTRUCTION size 1050x2150mm size 1450x2150mm 1050 1250 SCALE: 1: 20 DOOR SCHEDULE Solid lead-linedslidingpanel solid lead-linedslidingpanel Lead-lined woodenslidingdoor Sliding railtrackcoverfixedtowall installation panels; contractortoprovidespecs for approvalpriortosupplyand 100mm leadlineddooroverlapon door opening base andfloor. max 5mmspacingbetweendoor Sliding railsecurelyfixedtowall End profilefixedsecurelytowall Line ofdoorstructuralopening. 1250 x2230x40mm 1650 x2230x40mm SHUTTER door door pull handle,lock,track pull handle,magnetic IRON MONGERY lock, trackrail rail Repair existingtrack Re-install existingslidingrail& fix securelytowall Radiation warninglight Re -installdoor Re-install brokendoorpullhandles on existingleadlinedslidingdoor REMARKS Install new handles rail and CROSS SECTIONDETAILX Public side SCALE: 1: 20 Room side Radiation CODE W2 FRAME CONSTRUCTION Steel casementframe;

2150 660 1500 x600 EXISTING LEAD-LINEDDOOR - D2DETAIL X WINDOW SCHEDULE 4mm clearglazing Fixed panelswith 1450 PANEL SCALE: SILL HEIGHT(mm) 1: 20 2300 re-djusted andfixedsecurelytowall Sliding trackrailleveltobe Magnetic interlockattopofdoor panels 100mm leadlineddooroverlapon door opening Line ofdoorstructuralopening. Lead-lined woodenslidingdoor base andfloor. max 5mmspacingbetweendoor installation panels; contractortoprovidespecs for approvalpriortosupplyand Sliding railtrackcoverfixedtowall Radiation warninglight;contractor to installation to providespecsforapprovalprior Maintain, window,paint finish tomatchexisting ACTION Sliding doorstop DRAWN BY: DRAWING NUMBER: CHECKED BY: SCALE: APPROVD BY: 1. NO 3. 2. 4. DRAWING TITLE: PROJECT: CLIENT: PROPOSED REFURBISHMENTWORKS BULIISA GENERALHOSPITAL MINISTRY OFHEALTH HOSPITALS ROOMS ATSELECTEDDISTRICT REFURBISHMENT OFRADIOLOGY GOVERNMENT OFUGANDA exclusive propertyoftheUNOPS-ESAHandcan DOOR &SCHEDULEDETAILS This designanddetailsare,atalltimesthe proceeding; promptly toobtainclarificationorconfirmationbefore before commencement; stated; time scaledfromdrawing; thus alldimensionsaretobereadandnotatany Written dimensionsoverridescaleddimensions, Any discrepancytobereportedtheEngineer All dimensionstobecheckedandconfirmedonsite All dimensionsareinmillimetersunlessotherwise not beusedorreproducedwithoutanywritten AS SHOWN MOH-BUL-006 REVISION Operational ExcellenceforResultsthatMatter UNOPS CountryOffice-Uganda Plot 15,Mackenzieclose,Kololo GENERAL NOTES TENDER DRAWINGS COPYRIGHT RESERVED East andSouthernAfricaHub UNOPS Building,UNLane, MWESIGWA B SANDRA D SANDRA D Off AvenueP.OBox783, Village Market,00621 Kampala -Uganda Nairobi, Kenya. consent KEY DATE APPR CODE D5 D2

2230 closing end,slidingdooropening closing end,slidingdooropening Steel anglesupportframeonthe Steel anglesupportframeonthe D5 DETAIL NEW LEAD-LINEDSCREEN- FRAME CONSTRUCTION size 1050x2150mm size 1450x2150mm 1050 1250 SCALE: DOOR SCHEDULE 1: 20 Solid lead-linedslidingpanel solid lead-linedslidingpanel Lead-lined woodenslidingdoor Sliding railtrackcoverfixedtowall installation panels; contractortoprovidespecs for approvalpriortosupplyand 100mm leadlineddooroverlapon door opening base andfloor. max 5mmspacingbetweendoor Sliding railsecurelyfixedtowall End profilefixedsecurelytowall Line ofdoorstructuralopening. 1250 x2230x40mm 1650 x2230x40mm SHUTTER door door pull handle,lock,track pull handle,magnetic IRON MONGERY lock, trackrail rail Re-install existingslidingrail& fix securelytowall Radiation warninglight Re-install brokendoorpullhandles on existingleadlinedslidingdoor Repair existingtrack CROSS SECTIONDETAILX Re -installdoor REMARKS Install new handles rail and Public side SCALE: CODE W2 1: 20 Room side Radiation FRAME CONSTRUCTION Steel casementframe; 1500 x600

2150 660 EXISTING LEAD-LINEDDOOR - D2DETAIL X WINDOW SCHEDULE 4mm clearglazing Fixed panelswith 1450 PANEL SCALE: 1: 20 SILL HEIGHT(mm) 2300 re-djusted andfixedsecurelytowall Sliding trackrailleveltobe Magnetic interlockattopofdoor panels 100mm leadlineddooroverlapon door opening Line ofdoorstructuralopening. Lead-lined woodenslidingdoor base andfloor. max 5mmspacingbetweendoor installation panels; contractortoprovidespecs for approvalpriortosupplyand Sliding railtrackcoverfixedtowall Radiation warninglight;contractor to installation to providespecsforapprovalprior Maintain, window,paint finish tomatchexisting Sliding doorstop ACTION DRAWN BY: DRAWING NUMBER: CHECKED BY: SCALE: APPROVD BY: 1. NO 3. 2. 4. DRAWING TITLE: PROJECT: CLIENT: PROPOSED REFURBISHMENTWORKS BULIISA GENERALHOSPITAL MINISTRY OFHEALTH HOSPITALS ROOMS ATSELECTEDDISTRICT REFURBISHMENT OFRADIOLOGY GOVERNMENT OFUGANDA exclusive propertyoftheUNOPS-ESAHandcan VIEW WINDOW&DOORDETAILS This designanddetailsare,atalltimesthe proceeding; promptly toobtainclarificationorconfirmationbefore before commencement; stated; time scaledfromdrawing; thus alldimensionsaretobereadandnotatany Written dimensionsoverridescaleddimensions, Any discrepancytobereportedtheEngineer All dimensionstobecheckedandconfirmedonsite All dimensionsareinmillimetersunlessotherwise not beusedorreproducedwithoutanywritten AS SHOWN MOH-BUL-005 REVISION Operational ExcellenceforResultsthatMatter UNOPS CountryOffice-Uganda Plot 15,Mackenzieclose,Kololo GENERAL NOTES TENDER DRAWINGS COPYRIGHT RESERVED East andSouthernAfricaHub UNOPS Building,UNLane, MWESIGWA B SANDRA D SANDRA D Off AvenueP.OBox783, Village Market,00621 Kampala -Uganda Nairobi, Kenya. consent KEY DATE APPR Operational Excellence for Results that Matter East and Southern Africa Hub UNOPS Building, UN Lane, Off Avenue P.O Box 783, Village Market, 00621 400 Nairobi, Kenya. Factory set UNOPS Country Office - Uganda 320 Plot 15, Mackenzie close, Kololo support profile Kampala - Uganda

Factory set stop profile GENERAL NOTES Radiation NOTES: Control Room side 1. All dimensions are in millimeters unless otherwise stated; Room side 16mm lead glass 2. All dimensions to be checked and confirmed on site before commencement; 400 400 1. Options for frame material: Stainless 320 3. Written dimensions override scaled dimensions, steel with brushed; or Aluminum thus all dimensions are to be read and not at any Telescopic view time scaled from drawing; brushed and clear anodized finish or window frame 4. Any discrepancy to be reported to the Engineer promptly to obtain clarification or confirmation before MS with gray primer/powder coat proceeding; finish. 2mm thick lead shielding KEY 2. All sheet lead shall be 99.9% pure. inside wall and frame X-RAY VIEW WINDOW 3. Contractor must verify lead shielding SCALE: 1: 10 equivalency requirement prior to VIEW WINDOW VERTICAL ordering. DETAIL SCALE: 1: 10 4. Contractor to allow for testing of view NO REVISION DATE APPR window installation 16mm lead glass Factory set stop profile 400 100mm door over lap 2mm thick lead

shielding inside CLIENT: wall & frame GOVERNMENT OF UGANDA MINISTRY OF HEALTH

PROJECT: 100mm door 100mm door REFURBISHMENT OF RADIOLOGY over lap Door Opening width over lap Factory set support profile ROOMS AT SELECTED DISTRICT HOSPITALS

Door Panel width Telescopic aluminum DRAWING TITLE: VIEW WINDOW & DOOR DETAILS view window frame BULIISA GENERAL HOSPITAL PROPOSED REFURBISHMENT WORKS

DRAWING NUMBER: VIEW WINDOW HORIZONTAL. MOH-BUL-005

DETAIL SCALE: 1: 10 SCALE: AS SHOWN Wall thickness

DRAWN BY: MWESIGWA B MS angle section frame CHECKED BY: SANDRA D (existing) Radiation APPROVD BY: Room side SANDRA D

Existing lead-lined TENDER DRAWINGS sliding door panel COPYRIGHT RESERVED

This design and details are, and at all times the exclusive property of the UNOPS-ESAH and can not be used or reproduced without any written DOOR FRAME DETAIL consent SCALE: 1: 10 Operational Excellence for Results that Matter East and Southern Africa Hub UNOPS Building, UN Lane, Off Avenue P.O Box 783, Village Market, 00621 Nairobi, Kenya. CIRCULATION UNOPS Country Office - Uganda Plot 15, Mackenzie close, Kololo Kampala - Uganda E E E E E E E GENERAL NOTES

Existing concrete bench Existing concrete bench 1. All dimensions are in millimeters unless otherwise stated; 1 2. All dimensions to be checked and confirmed on site before commencement;

3. Written dimensions override scaled dimensions, thus all dimensions are to be read and not at any time scaled from drawing; WC 4. Any discrepancy to be reported to the Engineer promptly to obtain clarification or confirmation before proceeding;

OFFICE/REPORTING ULTRASOUND KEY SCAN Existing Brick Masonry Wall

New Masonry Wall Reporting Station WAITING AREA Demolition

9kg chemical powder fire extinguishers NO REVISION DATE APPR fixed at 1.2m FFL DP CH./RM 2

2.15 D2 1 CLIENT: DP GOVERNMENT OF UGANDA WC 9kg chemical powder MINISTRY OF HEALTH fire extinguishers 2.15 fixed at 1.2m FFL D5 PROJECT: REFURBISHMENT OF RADIOLOGY ROOMS AT SELECTED DISTRICT CH./RM HOSPITALS EXAMINATION DRAWING TITLE: ROOM Wooden wall hung STORE EQUIPMENT LAYOUT PLAN X-Ray Bucky Table DARK ROOM cassette cabinet fixed 1.35m above FFL BULISA GENERAL HOSPITAL RADIOLOGY UNIT

DRAWING NUMBER: Chest MOH-BUL-007 SCALE: Acquisition Control panel Bucky AC internal unit fixed Station AS SHOWN X-Ray Machine at min. 2.5m height STORE X-Ray from FFL Generator

DRAWN BY: MWESIGWA B 1 CHECKED BY: SANDRA D

APPROVD BY: SANDRA D AC internal unit fixed at min. 2.5m height from FFL Drain to Drain to AC external unit fixed on MS brackets min. ground ground 200mm from wall and at 2.4m height; Contractor to provide sample for Eng's AC external unit fixed on min. 200mm TENDER DRAWINGS from wall and at 2.4m height; Contractor approval to provide sample of on MS fixing brackets COPYRIGHT RESERVED for Eng's approval This design and details are, and at all times the exclusive property of the UNOPS-ESAH and can EQUIPMENT LAYOUT PLAN (RADIOLOGY UNIT - BULIISA GENERAL HOSPITAL) not be used or reproduced without any written consent SCALE: 1: 50 STANDARD RADIATIONWARNING SIGN 600 SCALE: 1: 20 6mm veneeredboard 6mm veneeredboard 25mm veneeredblockboard 25mm veneeredblockboard 25mm veneeredblockboard shutter withrecessedhinges 25mm veneeredblockboard 25mm veneeredblockboardon 25mm veneeredblockboard

400 Black White Yellow Yellow Red 1.2m aboveFFL Fixing towallwithscrewabaseheightmin. NOTE: The radiationwarningsignagematerialisperspex All backgroundcoloursarereflectivepaint 800 25 450 1350 25 360 25 360 25 25 180 WALL SHELVINGCABINETELEVATION 6 598 180 560 6 PLAN VIEW Existing FFL SCALE: 180 25 SCALE: 1200 1200 1: 20 5 1: 20 X X 560 598 25 10 SECTION X-X SCALE: Existing FFL Fixing brackets 450 440 1: 20

Fixed 1.35m from FFL 25 365 360 25 DRAWN BY: DRAWING NUMBER: CHECKED BY: SCALE: APPROVD BY: 1. NO 3. 2. 4. CABINET DETAILS WARNING SIGNAGE&CASSETTE DRAWING TITLE: PROJECT: CLIENT: MINISTRY OFHEALTH HOSPITALS ROOMS ATSELECTEDDISTRICT REFURBISHMENT OFRADIOLOGY GOVERNMENT OFUGANDA exclusive propertyoftheUNOPS-ESAHandcan This designanddetailsare,atalltimesthe proceeding; promptly toobtainclarificationorconfirmationbefore before commencement; stated; time scaledfromdrawing; thus alldimensionsaretobereadandnotatany Written dimensionsoverridescaleddimensions, Any discrepancytobereportedtheEngineer All dimensionstobecheckedandconfirmedonsite All dimensionsareinmillimetersunlessotherwise not beusedorreproducedwithoutanywritten AS SHOWN MOH-TOR-006 REVISION Operational ExcellenceforResultsthatMatter UNOPS CountryOffice-Uganda Plot 15,Mackenzieclose,Kololo GENERAL NOTES TENDER DRAWINGS COPYRIGHT RESERVED East andSouthernAfricaHub UNOPS Building,UNLane, MWESIGWA B SANDRA D SANDRA D Off AvenueP.OBox783, Village Market,00621 Kampala -Uganda Nairobi, Kenya. consent KEY DATE APPR