Electric Service Rules

Total Page:16

File Type:pdf, Size:1020Kb

Electric Service Rules 2021 Electric Service Rules GENERAL INFORMATION TEMPORARY SERVICES OVERHEAD SERVICES UNDERGROUND SERVICES DISTRIBUTED GENERATION METERING HUD MANUFACTURED HOMES FARM SERVICES UTILITY/CATV SERVICES PRIMARY SERVICES SPECIAL SERVICES AND MOTORS OPTIONAL STANDBY GENERATION CLEARANCES GROUNDING AND BONDING ELECTRIC VEHICLES © 2021 Alliant Energy 885247 11/20 AM Version 17 Updates to this manual may be necessary throughout the year. Please see www.alliantenergy.com/servicemanuals for the most up-to-date information. ELECTRIC SERVICE RULES Issued Jan 2021 C a l l B e f o r e Y o u D i g DIGGERS HOTLINE, Telephone Numbers, Alliant Energy Web Site Information & Cable Locating Services ALLIANT ENERGY IP&L/WP&L TELEPHONE NUMBERS Electric Service: 1-800-862-6222 or 1-800-ALLIANT Outage Reporting: 1-877-740-5050 or 1-800-ALLIANT PRE-EXCAVATION TELEPHONE NUMBERS Pre-Excavation Call Number All Areas - 811 Iowa – Iowa One Call: 1-800-292-8989 Wisconsin – Diggers Hotline: 1-800-242-8511 ALLIANT ENERGY WEBSITE Key in Web Site www.alliantenergy.com/servicemanuals C a l l B e f o r e Y o u D i g Page i ELECTRIC SERVICE RULES Issued Jan 2021 TABLE OF CONTENTS - ESR Revision Date: January 2021 CHAPTER 1 – GENERAL INFORMATION...... UPDATED JULY 2021 Page 100. General ...................................................................................................................... 1-1 101. Purpose ..................................................................................................................... 1-1 102. Scope ........................................................................................................................ 1-1 103. Codes and Rules ...................................................................................................... 1-1 104. Word Application ....................................................................................................... 1-2 105. Continuity of Service ................................................................................................. 1-2 106. Point of Service ......................................................................................................... 1-2 107. Application for Service ............................................................................................... 1-3 108. Service Voltages and Maximum Amperage .............................................................. 1-4 109. Number of Services ................................................................................................... 1-5 110. Short Circuit Duty Requirements ............................................................................. 1-10 111. Inspections and Maintenance .................................................................................. 1-12 112. Service Connections ............................................................................................... 1-12 113. Identification of Conductors ..................................................................................... 1-12 114. Changes to Existing Service-Entrance Equipment .................................................. 1-12 115. Alliant Energy Equipment on Customer Premises .................................................. 1-13 116. Capacity .................................................................................................................. 1-13 117. Sequence of Disconnecting Service and Meter ...................................................... 1-14 118. Customer Installation ............................................................................................... 1-14 119. Communication Tower Installation .......................................................................... 1-15 CHAPTER 2 - TEMPORARY SERVICE 200. General ...................................................................................................................... 2-1 201. Overhead Temporary Service, 1PH, 3-Wire, 120/240V, 200A Max ................ 2-2 & 2-3 202. Underground Temp./Perm. Service, 1PH, 3-Wire, 120/240V, 200A Max.................. 2-4 203. Underground Temporary Service, 1PH, 3-Wire, 120/240V, 200A Max ..................... 2-5 204. Underground Temporary Service, 1PH, 3-Wire, 120/240V, 200A Max ..................... 2-6 205. Large Temporary Service, 1PH or 3PH ..................................................................... 2-7 Page ii ELECTRIC SERVICE RULES Issued Jan 2021 CHAPTER 3 – OVERHEAD SECONDARY SERVICE Page 300. Scope ........................................................................................................................ 3-1 301. Attachment of Service Drops ..................................................................................... 3-1 302. Service Riser Requirements ...................................................................................... 3-1 303. Service Mast Construction ........................................................................................ 3-2 304. Service Mast Installation ........................................................................................... 3-3 305. Wall or Through-The-Roof Installation ...................................................................... 3-4 306. Pole Mounted Service Entrance – Optional Construction ......................................... 3-5 CHAPTER 4 – UNDERGROUND SECONDARY SERVICE 400. Scope ........................................................................................................................ 4-1 401. General Information ................................................................................................... 4-1 402. Sizing Underground Facilities .................................................................................... 4-1 403. Location of Alliant Energy Secondary Voltage Cables .............................................. 4-2 404. Underground Service Installations ............................................................................ 4-2 405. Outdoor Meter Socket, 1PH &r 3PH .......................................................................... 4-4 406. Outdoor Meter Pedestal Service, Single or Duplex, 1PH & 3PH .............................. 4-5 407. Rigid Conduit ............................................................................................................. 4-6 408A. Concrete Pad Specifications and Layout for 3PH, Pad-Mount Transformers............ 4-8 408B. Concrete Pad Specifications and Layout for 1PH, Pad-Mount Transformers............ 4-9 409. Concrete Specifications and Layout for Foundation Wall for 3PH, PM Trf .............. 4-11 410. Concrete Pad Specifications & Layout for 3PH, PM Trf and Metering TC .............. 4-13 411. Concrete Pad Specifications & Layout for Joint Pad, 3PH, PM Trf & Metering TC.. 4-15 412. Non-Preferred Option: Box Pad Specification for 3PH, Pad-Mount Transformers .. 4-19 413. Box Pad Specification for 1PH, Pad-Mount Transformers ....................................... 4-20 Page iii ELECTRIC SERVICE RULES Issued Jan 2021 CHAPTER 5 – DISTRIBUTED GENERATION Page 500. Scope ........................................................................................................................ 5-1 501. Permission to Interconnect ........................................................................................ 5-1 502. Technical Information ................................................................................................ 5-1 503. Metering Equipment .................................................................................................. 5-2 504. Alliant Energy Distribution System ............................................................................ 5-2 505. Primary Metering Customers with DG ....................................................................... 5-2 506. Optional Standby Generator used with DG ............................................................... 5-2 507. Labeling Requirements ............................................................................................. 5-2 508. Point of Interconnection ............................................................................................. 5-3 509. Interconnection Disconnect Switch Requirements .................................................... 5-3 510. Battery Energy Storage Systems .............................................................................. 5-4 511-523 Drawings ............................................................................................................... 5-4 511. 1PH/3PH, Self-Contained, Single Lug Main + DG Breaker ≤ 120% Of Service Panel Bus Rating .................................................................................... 5-5 512. 1PH/3PH, Self-Contained, Single Lug Main + DG Breaker > 120% Of Service Panel Bus Rating ..................................................................................... 5-5 513. 1PH/3PH, Self-Contained, Approved Alternate Energy Meter Socket, 200 Amp Main, 60-70 Amp DG Breaker (See ESE 106A) ......................................... 5-6 514. 1PH/3PH, Self-Contained, Approved Dual Lug Meter Socket (See ESE 106B) ....... 5-6 515. 1PH/3PH, Self-Contained, Single Lug Main + DG/ Remote Building≤ 120% Of Service Panel Bus Rating Remote Building With DG > 30’ From Meter ............. 5-7 516. 1PH/3PH, Self-Contained, Dual Lug Main + DG/Remote Building > 120% Of Service Panel Bus Rating Remote Building With DG > 30’ From Meter ............. 5-7 517. 1PH/3PH, Metering Transformer Cabinet, Main + DG Breaker, ≤ 120%
Recommended publications
  • New Microsoft Excel Worksheet (2).Xlsx
    Knowledge Assessment ( Written Test) QP Name - Assistant electrician QP Code:CON/Q0602 Total marks: 210 marks Duration: 90 minutes Each NOS carries 30 marks Infrastructure: Classroom, Benches, Pens, pencils Marks CON/N0602: Select and use hand tools, power tools, and electrical devices relevant to construction electrical works 1 Which device is used to measure current in a circuit? 4 a. Voltmeter b. Ammeter c. Tester d. Megger 4 2 Identify the item form the image below? a. Wattmeter b. Digital Multi meter c. Energy meter d. Analog multi meter 3 Which device is used to avoid overload current in a circuit? 4 a. Residual current circuit breaker b. Miniature circuit breaker c. Earth Leakage circuit breaker d. Molded Case circuit breaker 4 Identify the tool form the image below? 4 a. Channel loch plier b. Combination plier c. Nose plier d. Snippers 5 Which of the following is an ideal instrument used to measure the thickness of conduit? 4 a. Vernier Caliper b. Multi meter c. Measuring tape d. Total station 6 Identify the item form the image below? 5 a. Semi enclosed or re-wire able fuse b. Cartridge type fuse c. D type fuse d. Link type fuse 7 Which of the following tools is used to strip the insulation of cable? 5 a. Plier b. Scissor c. Splicer d. Tester CON/N0603: Install temporary lighting arrangement at construction sites Marks 8 What is the maximum number of 1sq.mm wires that can be drawn through a 25mm diameter conduit 4 a. 5 b. 2 c. 4 d.
    [Show full text]
  • Guideline on Through Penetration Firestopping
    GUIDELINE ON THROUGH-PENETRATION FIRESTOPPING SECOND EDITION – AUGUST 2007 SHEET METAL AND AIR CONDITIONING CONTRACTORS’ NATIONAL ASSOCIATION, INC. 4201 Lafayette Center Drive Chantilly, VA 20151-1209 www.smacna.org GUIDELINE ON THROUGH-PENETRATION FIRESTOPPING Copyright © SMACNA 2007 All Rights Reserved by SHEET METAL AND AIR CONDITIONING CONTRACTORS’ NATIONAL ASSOCIATION, INC. 4201 Lafayette Center Drive Chantilly, VA 20151-1209 Printed in the U.S.A. FIRST EDITION – NOVEMBER 1996 SECOND EDITION – AUGUST 2007 Except as allowed in the Notice to Users and in certain licensing contracts, no part of this book may be reproduced, stored in a retrievable system, or transmitted, in any form or by any means, electronic, mechanical, photocopying, recording, or otherwise, without the prior written permission of the publisher. FOREWORD This technical guide was prepared in response to increasing concerns over the requirements for through-penetration firestopping as mandated by codes, specified by system designers, and required by code officials and/or other authorities having jurisdiction. The language in the model codes, the definitions used, and the expectations of local code authorities varies widely among the model codes and has caused confusion in the building construction industry. Contractors are often forced to bear the brunt of inadequate or confusing specifications, misunderstandings of code requirements, and lack of adequate plan review prior to construction. This guide contains descriptions, illustrations, definitions, recommendations on industry practices, designations of responsibility, references to other documents and guidance on plan and specification requirements. It is intended to be a generic educational tool for use by all parties to the construction process. Firestopping Guideline • Second Edition iii FIRE AND SMOKE CONTROL COMMITTEE Phillip E.
    [Show full text]
  • Commercial Conduit Rules and Regulations
    Exhibit C – Commercial Conduit Rules and Regulations Electric Engineering Division COMMERCIAL CONDUIT RULES AND REGULATIONS S:\COO_ACM_US_Electric_Telecommunications\COO_ET_Engineering\Conduit Policies C-1 Exhibit C – Commercial Conduit Rules and Regulations 1805 NE 30th Ave., Bldg. 400 Ocala, FL 34470-4875 Phone: (352) 351-6620 Fax: (352 ) 401-6961 Electric Engineering Division Dear Developer: Over the next few months, the City of Ocala Utility Services (OUS) will be working closely with you and your contractors to install the electrical conduit system for your project. We in the Electric Engineering Division are looking forward to working with your contractors and want the installation to proceed as smooth as possible. Attached, please find the OUS Commercial Conduit Rules and Regulations for use by your electrical conduit contractor. If the contractor has any questions that are not addressed in this guide, please contact the OUS representative responsible for the project. Respectfully Ocala Utility Services Engineering Division C-2 Exhibit C – Commercial Conduit Rules and Regulations TABLE OF CONTENTS i. LETTER TO DEVELOPER ........................................................................................... 2 I. RULES AND REGULATIONS A. TABLE OF CONTENTS ....................................................................................... 3 B. TERMS AND DEFINITIONS ............................................................................... 4 C. DEVELOPER’S RESPONSIBILITIES ...............................................................
    [Show full text]
  • Section 16050 - Basic Electrical Materials and Methods
    Revised 10/03/19 SPECIFICATIONS - DETAILED PROVISIONS Section 16050 - Basic Electrical Materials and Methods C O N T E N T S PART 1 - GENERAL ............................................................................................................................. 1 1.01 SCOPE ........................................................................................................................................ 1 1.02 RELATED SECTIONS ................................................................................................................... 1 1.03 STANDARDS AND CODES ......................................................................................................... 1 1.04 SUBMITTALS ............................................................................................................................. 3 1.05 COORDINATION OF WORK AND TRADES ................................................................................ 4 1.06 DELIVERY, STORAGE, AND HANDLING……………………………………………………………………………….. 5 PART 2 - PRODUCTS .......................................................................................................................... 5 2.01 GENERAL ................................................................................................................................... 5 2.02 CONDUCTORS AND CABLES ..................................................................................................... 6 2.03 CONDUCTOR AND CABLE CONNECTORS ................................................................................
    [Show full text]
  • Specification 270528 Interior Communications Pathways
    GUIDELINES HAS/PDC/Design Division Project Title Houston, Texas Proj./CIP No. (These Guidelines are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer/Contractor/Installation Team.) SECTION 270528 INTERIOR COMMUNICATION PATHWAYS (REV.01-23-2020-SJS) PART 1 GENERAL 1.01 PROJECT SCOPE SUMMARY Designer shall provide a detailed narrative/scope of the tasks to be performed under this specification sections. 1.02 SECTIONS INCLUDES A. This section includes specifications for the installation of interior communications pathways. B. Related Documents: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division - 1 Specification sections, apply to the work of this section. C. Interior Communication Pathways are defined to include, but are not limited to innerduct, flexible multi-cell innerduct, conduit, pull boxes, cable/j-hooks, cable trays, supports, accessories, associated hardware and fire stopping materials. 1.03 REFERENCES A. Related Sections: Use these Specifications for all related work not specifically covered in this specification. 1. Section 270526: Telecommunication Grounding and Bonding 2. Section 270543: Exterior Communication Pathways 3. Section 270553: Identification and Labeling of Communication Infrastructure 4. Section 271100: Communication Cabinets and Equipment Rooms 5. Section 271300: Backbone and Riser Media Infrastructure 6. Section 271500: Horizontal Media Infrastructure 7. Section 272100: Data Communication Network Equipment 8. Section 272200: PC, Laptop, Servers and Equipment 9. Section 275113: Audio Communication System 10. Section 281300: Access Control System 11. Section 232313: Video Surveillance Control and Management System B. American National Standards Institute / Telecommunications Industry Association / Electronic Industries Alliance (ANSI/TIA/EIA): Most current standard revision 1.
    [Show full text]
  • Installation Guide
    Installation Preparation of the hood for installation: To facilitate the installation it is recommended to remove the panel before installing the hood. Attention! Keep both hands on the panel when disassembling or reassembling it into place to prevent it from falling and causing damage to persons or property. Disassembly: - Pull the panel (FRONT SIDE) firmly down, - Push the small lever, located in the right side of the panel, to the left, - Unhook it from the rear joints. 8 Installation - Ducting version 1. Pre-installation calculations 2. Preparation of mounting surface K = Kitchen Height Installing supports above ceiling drywall. C = Counter Height (36" standard) P = Prefered Height of Hood Bottom above counter (Recommended 24”-30”) H = Hood height your installation H = K – C – P a) Select a hood preference height P that is comfortable for the user. (from 24” to 30“). b) Calculate Hood height your installation H = K-C-P. c) Confirm that H is within the range of min to max H found for your model (See “Dimensions and clearances” paragraph). If not adjust your installation. Note: Take into consideration the hood depth; the hood could be much deeper than the cooktop. a. Mark center lines of cooktop or range on ceiling above. Use centerlines marked on ceiling to position the mounting template. Note location of hood front (that indicated with a printed arrow), side, and mounting holes indicated on template. Note: Remember that printed arrow on template corresponds to front of the hood and consequently to side where control panels will be located at the end of installation) b.
    [Show full text]
  • Electrical Conduits
    Electric Level 5 Electrical Conduits What’s it all About? Electrical conduits refer to an electrical system used to protect and provide route of electrical wiring. Electrical conduits are made of metal, plastic, or fiber and could be rigid or flexible. Conduits must be installed by following standard regulations, as those provided by the manufacturer and the National Electrical Code (NEC). Keys to Remember • The 2017 NEC covers 12 types of conduits. Articles 342 through 362 specify use, installation, and construction specifications. • Fill rates, or how many wires can be put in the conduit, is covered in the 2017 NEC Annex C. • Sizing - Conduit tubing uses Outside Dimensions (OD); conduit piping uses Nominal Pipe Size (NPS). Sizes range from 3/8” to 6”. • With any wiring project, safety for people and property is most important. Any metallic conduit should be grounded/bonded to the electrical grounding system. For the Project • Material List with Costs • References • Diagrams • Planning and Research • Dimensions • Title and Labels • Pictures (if exhibiting a report or poster) • Record Sheet Nine Common Types of Electrical Conduit 1. Galvanized Rigid Conduit A conduit made from galvanized steel tubing is commonly referred to as a rigid conduit. The thickness of a galvanized rigid (GR) conduit protects the electrical wiring from being hit and allows it to be threaded. 2. Electrical Metallic Tubing An electrical metallic tubing (EMT) conduit is made of steel; in some cases aluminum is also used. EMT is cheaper than a galvanized rigid conduit and lighter than a GR conduit. EMT is also a very popular material because it can be bent to specific radius and directions.
    [Show full text]
  • Answer the Purpose: 4
    Page 26 1. CONDUCTORS Conductors are defined as materials that easily allow the flow of _________. Metals are _______ conductors while insulators are ______ . The 2 common metals used for conductors in the electrical trade are: ___________ and ______________. Aluminium has become more prevalent for larger C.S.A. conductors as it is cheaper and lighter but more brittle than copper. Current/ Copper/ Aluminium Thermoplastic-sheathed cable (TPS) consists of an outer toughened sheath of polyvinyl chloride (PVC) (the thermoplastic element) covering one or more individual cables which are PVC insulated annealed copper conductors. It is a commonly used type of wiring for residential and light commercial construction in many countries. The flat version of the cable with two insulated conductors and an uninsulated earth conductor all within the outer sheath is referred to as twin and earth. In mainland Europe, a round equivalent is more common. Flat cables (or festoon cables) are made in PVC and Neoprene and are used as trailing cables for cranes, open filed conveyors and shelve service devices. Flat cables offer the advantages of extremely small bending radius’s, high flexibility and minimum wastage of space. Thermoplastic-sheathed cable (TPS) consists of an outer toughened sheath of polyvinyl chloride (PVC) (the thermoplastic element) covering one or more individual cables which are PVC insulated annealed copper conductors. It is a commonly used type of wiring for residential and light commercial construction in many countries. The flat version of the cable with two insulated conductors and an uninsulated earth conductor all within the outer sheath is referred to as twin and earth.
    [Show full text]
  • Johns Hopkins Enterprise Low Voltage Cabling Standards - Unabridged
    JOHNS HOPKINS INSTITUTIONS Johns Hopkins Enterprise Low Voltage Cabling Standards - Unabridged Approved by the ICSC, Revisions from Standard from 2005 May 2015 JOHNS HOPKINS UNIVERSITY Shelly Hoffmaster, RCDD Johns Hopkins Medicine Network Project Manager Greg Asman, RCDD Network Project Manager IT@JH-Enterprise Networking To: Architects and Consultants Re: Use of Johns Hopkins Cable Plant Design and Construction Specification Date: March 2, 2015 Intended Use This is a general specification for use in developing project construction documents for the information transport systems infrastructure for the Johns Hopkins Institutions. The specification as presented here includes all possible elements for an ITS installation. Designers and Architects will need to select and modify sections of this specification as required for their project. Not all divisions and sections will be applied to every project. Not all paragraphs of any given section may apply to a given project. System variables (e.g. copper pair counts, fiber backbone size) may be displayed as an example within this general specification. When generating a project specification: Designers and Architects will need to submit specifications based on this document to the appropriate Johns Hopkins group for approval of options selected from this specification. Designers and Architects shall not add language to this specification when generating a project- specific specification without approval of Johns Hopkins. When issuing to Contractors for Installation: The Contractor shall be aware of but not focus on the “Design Requirements” section within each specification section used. Contractors are to provide bid proposals per the “Products” sections and install per the “Execution” sections. Errors and omissions within this document shall be reported for correction in the general specification.
    [Show full text]
  • 2017 NATIONAL ELECTRICAL ESTIMATOR by Mark C
    Buy this complete title here: https://goo.gl/JQUG6D $87.75 ® 2017 NATIONAL ELECTRICAL ESTIMATOR By Mark C. Tyler SAMPLE Download all of Craftsman’s most popular costbooks for one low price with the Craftsman Site License. http://CraftsmanSiteLicense.com Turn your estimate into a bid. Turn your bid into a contract. ConstructionContractWriter.com ® Craftsman Book Company 6058 Corte del Cedro, Carlsbad, CA 92011 Buy similar Craftsman Book Co. titles here: https://www.Craftsman-Book.com Buy this complete title here: https://goo.gl/JQUG6D Acknowledgments The author wishes to thank the following individuals and companies for providing materials and information used in this book. George H. Booth, Vice President Sales — Graybar Electric Company, Inc. Steve Koundouriotis — P-W Western, Inc. Don Geibel — Walker Division of Butler Manufacturing Company. The tables on pages 439 and 440 are reprinted with permission from NFPA 70®-2017, the National Electrical Code®, Copyright 2016, National Fire Protection Association, Quincy, MA 02169. This reprinted material is not the complete and official position of the National Fire Protection Association on the referenced subject, which is represented only by the standard in its entirety. National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association, Inc. Quincy, MA 02169. Looking for Other Construction Reference Manuals? Craftsman has the books to ll your needs. Call toll-free 1-800-829-8123 or write to Craftsman Book Company, 6058 Corte del Cedro, Carlsbad, CA 92011 for a FREE CATALOG of over 100 books, including how-to manuals, annual cost books, and estimating software. Visit our Web site: http://www.craftsman-book.com SAMPLE Cover design: Jennifer Johnson ©2016 Craftsman Book Company ISBN 978-1-57218-326-1 Published December 2016 for the year 2017.
    [Show full text]
  • Section 16130 Conduit and Fittings
    Caltrain Standard Specifications SECTION 16130 CONDUIT AND FITTINGS PART 1 – GENERAL 1.01 DESCRIPTION A. Section includes requirements for conduit and conduit fittings. Conduit types shall be as shown on the Contract Drawings and as specified herein. 1.02 REFERENCE STANDARDS A. American National Standards Institute (ANSI): 1. C80.1 Electrical Rigid Steel Conduit (ERCS) B. ASTM International (ASTM): 1. A153 Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware 2. D2564 Specification for Solvent Cements for Poly (Vinyl Chloride) (PVC) Plastic Piping Systems C. American Welding Society (AWS): 1. D1.1 Structural Welding Code - Steel D. California Code of Regulations (CCR): 1. Title 24, Part 3, California Electrical Code E. Institute of Electrical and Electronics Engineers (IEEE): 1. IEEE C2 National Electrical Safety Code (NESC) F. National Electrical Manufacturers Association (NEMA): 1. TC2 Electrical Polyvinyl Chloride (PVC) Conduit 2. TC3 Polyvinyl Chloride (PVC) Fittings for Use with Rigid PVC Conduit and Tubing G. National Fire Protection Association (NFPA): 1. NFPA 70 National Electrical Code (NEC) H. Underwriters Laboratories Inc. (UL): 1. UL 6 Electrical Rigid Metal Conduit - Steel 16130-1 September 30, 2011 CONDUIT AND FITTINGS Caltrain Standard Specifications 2. UL 651 Schedule 40 and 80 Rigid PVC Conduit and Fittings 1.03 DESIGN REQUIREMENTS A. In addition to requirements specified in Section 16000, Basic Electrical Requirements, design supports to support the following loads. 1. Support load equal to sum of weights of conduits and wires, and weight of hanger plus 200 pounds. 2. Stress at root of thread of hanger rods: Not more than 9475 psi at design load.
    [Show full text]
  • PVC Electrical Conduit Product Brochures
    ELECTRICAL CONDUIT MEETS ANSI/UL 651 AND NEMA TC-2, TC-6 AND TC-8 Building essentials for a better tomorrow ELECTRICAL CONDUIT PVC Rigid Non-Metallic Conduit for Electrical Systems Schedule 40 and Schedule 80 Power and Communication Duct 0.5"- 6" Schedule 40 Utility PVC “Gas Sleeve” Pipe Eagle Loc Electrical Conduit ELECTRICAL CONDUIT CONTENTS 01 PRODUCT DesCRIPtiON ....................................2 SHORT FORM SPECIFICATION 02 ELECTRICAL CONDUIT AND POWER DUCT .....................4 SHORT FORM SPECIFICATION 03 POWER AND COMMUNICATION DUCT ..........................6 DimensiOns anD WeiGhts ................................8 04 PVC SCHEDULE 40 AND SCHEDULE 80 CONDUIT . 8 POWER AND COMMUNICATION DUCT..........................9 POWER AND COMMUNICATION DUCT FOR DIRECT BURIAL . 10 TELEPHONE DUCT ..........................................11 SCHEDULE 40 UTILITY ......................................12 PVC “GAS SLEEVE” PIPE ....................................13 05 EAGLE LOC ELECTRICAL CONDUIT .............................14 06 LOADinG ChaRts .........................................16 07 WARRANTY ...............................................19 01 PRODUCT DESCRIPTION ELECTRICAL CONDUIT FOR USE IN POWER, TELEPHONE AND OTHER ELECTRICAL DUCT SYSTEMS DESCRIPTION QUALITY CONTROL JM Eagle™ offers a complete line of Electrical Conduit JM Eagle™ pipe is tested in accordance with the provi- and Power Duct pipe products that includes: Schedule sions of the appropriate listed standard(s) and subject 40 and 80 Conduit (NEMA TC-2, ANSI/UL651), Encased to inspection by its quality control inspectors through- and Direct Burial Conduit (ASTM F512, NEMA TC-6 & 8 out the manufacturing process. JM Eagle’s Quality and/or ANSI/UL 651A), and Type C Telephone Duct. Management System is ISO 9001:2000 registered.* Copies of the registration certificates are available on its website at http://www.jmeagle.com. * JM Eagle™ is has achieved the ISO 9001-2000 registra- tion of Quality Management System for all locations.
    [Show full text]