Subcooling for Increased Compressor Capacity, Efficiency with Solstice

Subcooling for Increased Compressor Capacity, Efficiency with Solstice

Refrigerants Subcooling for Increased Compressor Capacity and Efficiency Technical Bulletin Product: Solstice® N13 (R-450A) Bulletin#: 08 rev 0.0 Application: Refrigeration Background There will be instances when a Chart 1 refrigeration system will need an increase Peak Load Capacity (San Antonio, Texas) in refrigeration capacity due to additional Shows the capacity increase due to subcooling of the R-450A system. refrigeration load or design changes while retrofitting. Percent 140 Problem Replacing an entire system to increase 130 131% capacity is time consuming and costly. 120 The alternative of adding compressors to y (Btuh) increase the refrigeration load results in 110 an increase in energy usage. Capacit 100 100% Resolution 90 Subcooling the main liquid line will 80 increase refrigeration capacity while Base Subcooled improving energy efficiency. Subcooling in this document refers to the use of a separate refrigeration source to lower the temperature of the main liquid line. This separate system operates at a higher evaporator pressure and thereby increases the overall efficiency of the combined systems. As an example, we will review the subcooling effect upon a medium- temperature parallel rack system utilizing Honeywell Solstice N13 (R-450A) refrigerant. System Description • Install a pre-packaged condensing unit Chart 2 to subcool the main liquid line with a Subcooling Performance plate heat exchanger¹. Efficiency for ~100,000 Btuh System (San Antonio, Texas) • Run this condensing unit at 50ºF suction temperature to subcool the 11.00 main system liquid line to 70ºF². EER • Main system peak condensing 10.00 10.0 Average Seasonal Kw* temperature assumed to be 120ºF 9.3 9.00 with a suction temperature of 20ºF³. 8.56 Kw 8.00 7.79 Results EER I 7.00 • Chart 1 shows the capacity increase due 6.00 to subcooling of the R-450A system. 5.00 • Chart 2 indicates an increase in efficiency as well as an overall reduction 4.00 *Includes subcooler load Base Subcooled in operating costs. The addition of a small condensing unit with a plate heat exchanger to subcool the main liquid line will increase the system capacity as much as 31% at peak load conditions while reducing overall energy consumption. Notes: ¹ Capacity control for compressor is recommended due to load fluctuations over operating range. ² Most areas in the United States have a 1% dewpoint lower than 70 degrees. Therefore it is recommended to limit subcooling to 70 degrees to avoid condensation on liquid lines. If liquid lines are insulated lower liquid temperatures are possible. ³ Analysis is done using an independent condenser for subcooling compressor. If it is desired to utilize the existing main system condenser an approximate 6oF increase in condensing temp is expected. This would change the capacity increase from 31% to 25%. Although Honeywell International Inc. believes that the information contained herein is accurate and reliable, it is presented without guarantee or responsibility of any kind and does not constitute any representation or warranty of Honeywell International Inc., either expressed or implied. A number of factors may affect the performance of any products used in conjunction with user’s materials, such as other raw materials, application, formulation, environmental factors and manufacturing conditions among others, all of which must be taken into account by the user in producing or using the products. The user should not assume that all necessary data for the proper evaluation of these products are contained herein. Information provided herein does not relieve the user from the responsibility of carrying out its own For more information: tests and experiments, and the user assumes all risks and liabilities (including, but not limited to, risks relating to results, Technical Support Team patent infringement, regulatory compliance and health, safety and environment) related to the use of the products and/ or information contained herein. 800-631-8138 www.honeywell-refrigerants.com Honeywell Refrigerants Genetron and Solstice are registered 115 Tabor Road trademarks of Honeywell International Inc. 2220 FP Ref v4 | January 2018 Morris Plains, NJ 07950 © 2018 Honeywell International Inc. All rights reserved..

View Full Text

Details

  • File Type
    pdf
  • Upload Time
    -
  • Content Languages
    English
  • Upload User
    Anonymous/Not logged-in
  • File Pages
    2 Page
  • File Size
    -

Download

Channel Download Status
Express Download Enable

Copyright

We respect the copyrights and intellectual property rights of all users. All uploaded documents are either original works of the uploader or authorized works of the rightful owners.

  • Not to be reproduced or distributed without explicit permission.
  • Not used for commercial purposes outside of approved use cases.
  • Not used to infringe on the rights of the original creators.
  • If you believe any content infringes your copyright, please contact us immediately.

Support

For help with questions, suggestions, or problems, please contact us