Grease Duct Enclosures Fire and Smoke Dampers in Grease Ducts

Grease Duct Enclosures Fire and Smoke Dampers in Grease Ducts

506.3.11 CHANGE TYPE: Modification CHANGE SUMMARY: The code specifically prohibits the installation of Grease Duct Enclosures fire and smoke dampers in grease ducts. 2015 CODE: 506.3.11 Grease Duct Enclosures. A commercial kitchen grease duct serving a Type I hood that penetrates a ceiling, wall, floor or any concealed spaces shall be enclosed from the point of penetration to the outlet terminal. In-line exhaust fans not located outdoors shall be enclosed as required for grease ducts. A duct shall penetrate exterior walls only at locations where unprotected openings are permitted by the International Building Code. The duct enclosure shall serve a single grease duct and shall not contain other ducts, piping or wiring systems. Duct enclosures shall be either a shaft enclosure in accordance with Section 506.3.11.1, a field-ap- plied enclosure assembly in accordance with 506.3.11.2 or a factory-built enclosure assembly in accordance with Section 506.3.11.3. Duct enclosures shall have a fire-resistance rating of not less than that of the assembly pen- etrated and not less than 1 hour. Fire dampers and smoke dampers shall not be installed in grease ducts. Duct enclosures shall be as prescribed by Section 506.3.11.1, 506.3.11.2 or 506.3.11.3. 506.3.11.4 Duct enclosure not required. This excerpt is taken from Exception: A duct enclosure shall not be required for a grease duct Significant Changes to the that penetrates only a non-fire-resistance-rated roof/ceiling assembly. International Plumbing/ CHANGE SIGNIFICANCE: It has long been understood that fire and smoke dampers are not compatible with grease ducts, and the duct en- Mechanical/ closure requirements clearly account for the lack of such dampers where Fuel Gas the ducts penetrate walls, floors and ceilings. Fire and smoke dampers Codes, 2015 would be made useless by the severe environment within grease ducts Edition. (e.g. high temperatures, grease, cleaning chemicals and water). The code Significant now prohibits what has been assumed to be prohibited all along. Changes publications take you directly to the most important changes that impact projects. Key changes Fire-resistant construction are identified then followed Duct enclosure by in-depth discussion of ® Grease duct for how the change affects real- Type I hood world application. Photos, tables and illustrations are included to further clarify Fire damper and smoke application. Available for the damper not permitted IBC, IRC, IFC and IPC/IMC/ International Code Council IFGC, the Significant Changes Fire dampers and smoke dampers are not permitted in grease ducts. publications are very useful training and review tools for transitioning to a new code edition. DESIGN SERVICES OF # 152875 Cust: ICC Au: _______ Pg. No. 108 C/M/Y/K S4-CARLISLE Title: PMG (Plumbing, Mechanical and Fuel Gas) Short / Normal Publishing Services.

View Full Text

Details

  • File Type
    pdf
  • Upload Time
    -
  • Content Languages
    English
  • Upload User
    Anonymous/Not logged-in
  • File Pages
    1 Page
  • File Size
    -

Download

Channel Download Status
Express Download Enable

Copyright

We respect the copyrights and intellectual property rights of all users. All uploaded documents are either original works of the uploader or authorized works of the rightful owners.

  • Not to be reproduced or distributed without explicit permission.
  • Not used for commercial purposes outside of approved use cases.
  • Not used to infringe on the rights of the original creators.
  • If you believe any content infringes your copyright, please contact us immediately.

Support

For help with questions, suggestions, or problems, please contact us