Advanced RTU Control Strategies

Advanced RTU Control Strategies

3/4/2014 Advanced RTU Control Strategies Ryan R. Hoger, LEED AP 708.670.6383 [email protected] Environmental Impact of Buildings* • 40% of total U.S. energy consumption • 39% of total U.S. CO2 emissions • 72% of total U.S. electricity consumption *Commercial and Residential 1 3/4/2014 Environmental Energy Impact of Buildings 100% USA Energy Consumption (BTU) 38.2% 28% Transportation 33.4% 32% Industry 28.3% 40% Buildings* Residential & Commercial Buildings 2010 DOE Buildings Energy Data Book 20.26 Quadrillion BTU Site > dropped to 19.99 in 2011 39.29 Quadrillion BTU Primary > means bldgs are about 51-52% efficient in terms of raw energy utilization Commercial HVAC Energy Consumption 27% of all commercial HVAC energy is used by fans!!! 2 3/4/2014 Efficiency Ratings for RTUs • Air-Conditioning, Heating, and Refrigeration Institute RTUs < 65,000 Btuh (~5.4 tons) • Use residential test standards • SEER •AFUE • RTUs >= 65,000 Btuh (~5.4 tons) • EER + IEER • Thermal Efficiency 3 3/4/2014 Industry Movement to IEER Ratings The industry and governing bodies are evolving to Integrated Energy Efficiency Ratio (IEER) values as the leading energy measure: - IEER models building part load profile – EER measures peak unit performance that is typically experienced 3% of the operating time. - Codes now specify both a minimum EER and IEER - Rebate programs generally specify just a part load min IEER - The Department of Energy (DOE) Rooftop efficiency challenge - ONLY specifies IEER @ 18.0 – NO EER ASHRAE 90.1-2010 & IECC 2012 Minimums 4 3/4/2014 ASHRAE 90.1-2013 Minimums Example Manufacture Product Offering High Tier IEER’s Nearly 70% more efficient than entry level Includes: up to 3 stage Nearly 50% more cooling, VFD supply fan, and efficient than mid- ECM condenser fan tier SEER / IEER SEER / High Efficiency Mid-Efficiency Code Tier Tier Minimum RTU Values are averaged 5 3/4/2014 Retro-commissioning Most Common* Improvements *DOE / Lawrence Berkley National Lab Study 2009 Retro-commissioning Savings for Key Improvements** **DOE / Lawrence Berkley National Lab Study 2009 6 3/4/2014 RTU Study Results* *2004 Study by New Buildings Institute 503 RTUs at 181 Sites Example RTU Tune-up Checklist 7 3/4/2014 2013 DOE Study: Advanced Rooftop Control (ARC) Retrofit: Field-Test Results • Pacific Northwest National Labs • Published July 2013 • Purpose was to study combined energy effects of an economizer, demand controlled ventilation, and multi-speed fan control for RTUs • Field testing done on 66 RTUs on 8 different buildings • Various occupancy types (retail, office, food, and healthcare) • Various climates • Mix of Carrier (32), Trane (21), and Lennox (13) units • Range of RTU sizes, but most (43) were 10 to 15 tons • Data collected on 1 minute intervals for 12 months • Controls were alternated between standard (pre-retrofit mode) and advanced control modes on a daily basis 2013 PNNL Study Key Findings • An initial study showed gas/electric units saved between 24 and 35% energy and heat pumps saved 20 to 60% • The field data from the 66 RTUs showed a savings range of 22 to 90%, with a 57% savings average for all RTUs • Fan energy savings was the dominant contributor of the savings • Average payback periods were 6, 3, and 2 years for the 3 utility rates ($0.05, 0.10, and 0.15 / kWh) • Cost included both materials and labor • Larger units and longest runtime units had the shortest paybacks, as expected 8 3/4/2014 Products Reviewed • Available retrofit products: • Transformative Wave’s CATALYST • Enerfit • Bes-Tech’s Digi-RTU Optimizer • All 3 vendors retrofit supply fans with a VFD and generally change speed based on mode (heat, cool, vent, etc.) • All 3 also provide airside integrated economizer controls and CO2-DCV capabilities • Digi-RTU also provides the ability to modulate compressor speed • Based on product maturity and availability, PNNL choose to use the CATALYST product in the field testing PNNL Field Test Settings • Vent mode fan speed = 40% • Cool/heat speed = 75 or 90% (depending on # of stages) • CO2 high setpoint = 1,000 PPM 9 3/4/2014 PNNL Recommendations PNNL Study Runtime Examples 10 3/4/2014 Programmable Thermostats Programmable Thermostats • Stop running heating/cooling 24/7!!! • Relaxes heat/cool setpoints when space not occupied – Only setback about 5º (use 65º for heat and 80º for cooling) – Need to setback minimum of 6 hours to be effective • On average saves 25-30% on heat/cool energy* – If installed in every home would save about 5% of total US energy consumption* *John Hopkins Univ. AICGS Policy Report 11 3/4/2014 Programmable Thermostat Study Results* • Residential stats responsible for 11% of total US energy • What kinds of stats do people have? – 14% have no stat at all – 56% non-programmable – 30% programmable • Of those with programmable stats… – 89% have rarely or never programmed a stat – Only 30% of programmable stats are actually programmed – In winter, 60% use for night setback, only 45% setback during day – In summer, 55% use for night, same for day time – 2003 Carrier study also revealed that 53% of prog stats were in “hold” *2010 - DOE, EPA, and Lawrence Berkley National Labs Study Programmable Thermostats • Easy to retro-fit • Adaptive Intelligent Recovery • 2-stage stat for integrated economizer as 1st stage • Shut off ventilation during unoccupied hours • Internet accessible • Payback less than 6 months *John Hopkins Univ. AICGS Policy Report 12 3/4/2014 Internet Thermostats • Low cost alternative to BAS • Ethernet or Wi-Fi • No PC software – uses standard web browser • No access fees • Text/email alerts Internet Thermostats 13 3/4/2014 Internet Thermostats Phone Apps for Thermostats 14 3/4/2014 Economizers Outdoor Air Economizers • Use outside air for “free cooling” instead of compressors • 3 main types of control – Dry-bulb Temperature (enable when OA < 60º) – Enthalpy (enable when OA < 70º and humidity low) – Differential Enthalpy (is OA better than RA?) 15 3/4/2014 Outdoor Air Economizers • Integrated economizer – Economizer assists compressors on certain days • Building pressure relief needed • Occupancy control – Open to ventilation position only when building occupied (interlock to time clock of stat) instead of whenever fan on • Payback less than 6 months Barometric Relief Outdoor Air Intake Barometric Relief Section 11 – Options and Accessories 16 3/4/2014 Powered Exhaust Remote Duct Mounted Powered Exhaust Outdoor Air Intake Unit Mounted Powered Exhaust Section 11 – Options and Accessories IECC 2012: Commercial Economizers IECC 2012 already required by 8 states Also additional requirements for relief/exhaust, integrated economizer, types of economizer control, water-side economizers, etc. 17 3/4/2014 Existing Economizer Optimization • Many systems have never been commissioned at all – Perform functional performance tests • Economizer dampers and controls inoperative or in poor condition – Test bi-annually - repair or replace • Sensors not recalibrated on regular basis (especially enthalpy and CO2 sensors) – Recalibrate sensors bi-annually • Other issues: – Systems have been locked out by operator – Scheduling is not optimized (sometime running 24/7) – Economizer control not optimal (too high of OA setpoint) Insuring Proper Economizer Operation • Eliminate outside air for ventilation during unoccupied periods by closing OA dampers • OA damper operation should be monitored and recorded to verify actual operation of economizer • Percent OA can be used to verify that the economizer is properly operating • Percent of OA is calculated using a formula or graph 18 3/4/2014 OA% Calculation OA% = (MAT – RAT) (OAT – RAT) Example: OAT = 10° RAT = 70° MAT = 50° OA% = (50 – 70) = 33% (10 – 70) “Typical” Honeywell W7459 M7415 Economizer Economizer Logic Module Actuator Depending on sensors used, it is capable of dry-bulb changeover, enthalpy changeover, or differential enthalpy. Not capable of demand controlled ventilation (DCV). 19 3/4/2014 Honeywell W7212 Also capable of Demand Controlled Ventilation (DCV) Honeywell W7212 20 3/4/2014 Honeywell Logic Modules Honeywell Economizer Simulator customer.honeywell.com/economizertools 21 3/4/2014 Outdoor Air Dry-Bulb Economizer 60° F Outdoor AAir Temp 75° F db / 50% rh Compressor OFF Compressor ON Economizer ON Economizer OFF Modulate OA / RA / Exh. Outdoor Air Damper Section 11 – Options and Accessories at Ventilation Position Outdoor Air Enthalpy Economizer 65° F Outdoor AAir Temp 75° F db / 50% rh h = 25 Compressor OFF Compressor ON Economizer OFF Economizer ON Outdoor Air Damper Modulate OA / RA / Exh. Section 11 – Options and Accessories at Ventilation Position 22 3/4/2014 Integrated Economizer Compressor OFF Compressor ON Compressor ON Economizer ON Economizer OFF Economizer ON Outdoor Air Damper Outdoor Air Damper SectionModulate 11 – Options OA /and RA Accessories / Exh. Fully OPEN at Ventilation Position A, B, C, and D Enthalpy Curves Above Curves: Compressor ON Economizer OFF Outdoor Air Damper at Ventilation Position 75° F db / 50% rh Below Curves: Compressor OFF Economizer ON Modulate OA / RA / Exh. Section 11 – Options and Accessories 23 3/4/2014 CO2-based Demand Controlled Ventilation (DCV) Ventilation Control How is ventilation provided in buildings today? The same way it was in 1930. With Fixed Ventilation! 24 3/4/2014 Minimum Ventilation Rates Fixed Ventilation Building codes require ventilation rates based on cfm/person: (typically 20 cfm/person) MaxActual Occupancy: Occupancy: 25 51 people peopleperson = == 500cfm 500cfm500cfm Inefficient!

View Full Text

Details

  • File Type
    pdf
  • Upload Time
    -
  • Content Languages
    English
  • Upload User
    Anonymous/Not logged-in
  • File Pages
    89 Page
  • File Size
    -

Download

Channel Download Status
Express Download Enable

Copyright

We respect the copyrights and intellectual property rights of all users. All uploaded documents are either original works of the uploader or authorized works of the rightful owners.

  • Not to be reproduced or distributed without explicit permission.
  • Not used for commercial purposes outside of approved use cases.
  • Not used to infringe on the rights of the original creators.
  • If you believe any content infringes your copyright, please contact us immediately.

Support

For help with questions, suggestions, or problems, please contact us