Effectiveness of Surge Capacitors on Transformer Tertiary Connected

Effectiveness of Surge Capacitors on Transformer Tertiary Connected

Effectiveness of Surge Capacitors on Transformer Tertiary connected shunt reactors in preventing failures - Field measurements and comparison with Transient study results Pratap Mysore Venugopal Tondupally Adi Mulawarman Pratap Consulting Services HDR Xcel Energy Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Shunt Reactor Additions in Xcel Energy Wind Generation Addition . 825 MW wind power generation in Southern MN CAPX 2020 .Joint Initiative of eleven transmission owning utilities in four states in upper Midwest. .800 miles of transmission at 345 kV and 230 kV .Largest transmission project in 40 years to improve reliability of the grid in upper Midwest. .Last line of the project expected to be energized in December 2018. 2 Applicable documents for Operating Voltage Range .System voltage needs to be within the allowable range to prevent connected equipment failures. .ANSI C84.1-2016 “American National Standard for Electric Power Systems and Equipment—Voltage Ratings (60 Hz)”. This standard establishes nominal voltage ratings and operating tolerances for 60 Hz electric power systems above 100V. The latest version includes preferred voltage ratings up to 1200kV which was covered earlier in IEEE 1312-1993. 3 Shunt Reactors Installed to keep system voltage below maximum limit .Installed on Transmission lines .Either at both ends or at only one end. .Middle of the line. .Grounded “Wye” with or without Neutral Reactor .Tertiaries of transmission transformers 4 Transformer Tertiary connected Reactors . Economical Installation at lower voltage .Air core Construction – voltages up to 34.5 kV . Up to 50 MVAR .Ungrounded “Wye” configuration .Frequency of switching – Daily or more frequent 5 Reactor connections and Physical Layout 6 Reactor and Switching Device ratings .34.5 kV, 50 MVAR Reactor; Rated Current 836A .13.8 kV, 50 MVAR Reactor; Rated Current 2091A .72.5 kV, 3000 A, 40 kA SF6 Gas circuit breaker with gas pressure at 65 PSI .34.5 kV Reactor Load current is 2% of the short circuit current interruption rating .13.8 kV reactor current is 5% of the short circuit current interruption rating. .Breaker load current interruption is less than 5% of maximum short circuit rating. 7 Circuit Breaker Characteristics .Circuit breakers are designed to interrupt high short circuit current -40kA .Have no problem interrupting low load currents but, the current is forced to zero before the natural current zero occurs – Phenomenon referred to as current chopping. .C37.015-2017,”IEEE Guide for the Application of Shunt Reactor Switching” assumes low current region to be less than 300A. .Xcel energy 34.5 kV reactors (load current 836A) have failed due to suspected current chopping. .One circuit breaker failure and few 34.5kV reactor failures were attributed to transient voltages due to current chopping 8 Bus Capacitance and Shunt Reactor Inductance • 9 Effect of Current Chopping .If Chopped Current is iCH, the stored energy in the 2 inductor is ½*L*iCH .There is an energy exchange between the bus capacitance (1/2*C*V2) 2 2 2 .Total energy exchange is 1/2CV -1/2CV0 = LiCH Where, V0 is the voltage at which current is chopped. 2 2 .Voltage developed, V = √[V0 +(L/C) * iCH ] √(L/C) is the surge impedance 10 Surge Impedance Transient volta Surge Impedance: Assuming 250 pf capacitance, 13.8 kV Reactor bus: Z = 106√(0.0101/250) = 6.36 kΩ 34.5 kV Reactor bus; Z = 106√(0.063/250) = 15.89 kΩ Transient voltage Peak: 2 + 2 .√[V0 (6.36*iCH) ] kV at 13.8 kV 2 2 .√[V0 +(15.89*iCH) ] kV at 34.5 kV .V0 is the voltage at which contacts interrupted the current. 11 Transient Voltage .The value of current chopped is dependent on: .Capacitance on both sides of the breaker .Chopping number λ, a characteristic value of the circuit breaker .SF6 Puffer type λ = 4x104 to 19x104 .Total current chopped = λ√C; With 250 pf on both sides of the 4 breaker and λ=10x10 , C=250pf/2, iCH = 1.1A; This can vary up to 4A depending on λ and capacitance. .Chopping current is higher at load currents. 12 Transient Voltage rate of rise • 13 Addition of Surge Capacitance .Surge Capacitance Csurge = 0.25 µF .Surge Impedance 13.8 kV Reactor bus: Z = 103√(0.0101/0.25) = 200 Ω 34.5 kV Reactor bus; Z = 103√(0.063/0.25) = 502 Ω .Transient Voltage magnitude and Frequency: 10A chopped 13.8 kV bus: 200*10 =2kV; Frequency:3.167 kHz RRRV=25 V/µs 34.5 kV bus: 502*10 =5kV; Frequency:1.26 kHz RRRV=25 V/µs 14 Surge Capacitor .Reduces Peak Transient Voltage .Reduces the frequency of oscillation .Reduces the Rate of rise of transient voltage on the Reactor bus .Reduces the transient recovery voltage rate of rise across the breaker. .Minimizes Breaker reignition 15 Transient Studies • Used Alternate Transient Program (ATP) , a version of Electro-magnetic transient Program(EMTP) • Breaker re-ignition modeled using ‘MODELS’ blocks MOV • High Frequency model of shunt reactor Rp • Hybrid Transformer model-includes Wdg Capacitance CS R L Cg1 Cg2 V V V P P P 15.3kVMCOV MOV S S S Rp CS S V UI V R P V TR_HV EQ-S V X FMR MOV L A A UI Cg1 Cg2 MOV C-Surge-0.25 MOV P P P V Rp S S S CS TR_LV EQ-S V v v + + - - R L Cg1 Cg2 16 Breaker Dielectric Recovery Characteristics • Cold dielectric recovery Characteristic at Low current Interruption • Inherent to the specific breaker (Initial Rate of rise -1.8kV/µs) • Modeled in EMTP_ATP using ‘MODELS’ as an exponential function 1.5996 *10 6 1.3996 1.1997 0.9997 0.7998 0.5998 0.3999 0.1999 0.0000 18 20 22 24 26 28 *10 -3 30 (f ile ADM_ich_10_Bef ore_v 2.pl4; x-v ar t) m:XX0006 -(t-18.03E-3)/(3.55E-3) 17• Cold Dielectric recovery VRecovery = 1600 (1-e ) kV Dielectric Recovery at Load Current Interruption • Arc re-ignites if the voltage across the contacts exceeds • Dielectric Recovery voltage after current interruption. MODEL M reigniti UI ARC_sw I CB2A_1 CB2A_2 1S3_A UI Cstray Cstray 18 Reignition Switch Model Results with 10A Chopping Current 30 3000 *10 3 2000 20 1000 0 10 -1000 -2000 0 -3000 0 10 20 30 40 *10 -3 50 (f ile ADM_TR.pl4; x-v ar t) c:X0001A-X0013A c:X0001B-X0013B c:X0001C-X0013C -10 Reactor Current -20 30 *10 3 -30 20 10 -40 17.98 18.04 18.09 18.15 18.21 18.26 *10 -3 18.32 0 (f ile ADM_ich_10_Bef ore_v 2.pl4; x-v ar t) v :X0001A- -10 -20 -30 -40 18.02 18.03 18.04 18.05 18.06 18.07 *10 -3 18.08 (f ile ADM_ich_10_Bef ore_v 2.pl4; x-v ar t) v :CB2A_1-CB2A_2 19 Bus Voltage -Switching with Surge Capacitor 10.0 10 *10 3 *10 3 7.5 0 5.0 2.5 -10 0.0 -20 -2.5 -5.0 -30 -7.5 -10.0 -40 0 10 20 30 40 *10 -3 50 16.0 16.5 17.0 17.5 18.0 18.5 19.0 *10 -3 19.5 (f ile ADM_ich_10_Bef ore_v 2.pl4; x-v ar t) v :X0001A- (f ile ADM_ich_10_Bef ore_v 2.pl4; x-v ar t) v :CB2A_1-CB2A_2 Bus Voltage Breaker TRV (Voltage Across Breaker) 20 Comparison of ATP simulations with Field Records 3000 2000 1000 0 -1000 -2000 -3000 0.495 0.506 0.517 0.528 0.539 0.550 (f ile ADM01.pl4; x-v ar t) c:X0001A-X0002A c:X0001B-X0002B c:X0001C-X0002C Field Recorded ATP Simulation Shunt Reactor phase Currents 21 Bus Voltage –After Breaker First Pole Opens 12 *10 3 8 4 0 -4 -8 -12 0.49 0.51 0.53 0.55 0.57 0.59 (f ile ADM01.pl4; x-v ar t) v :X0002C Relay Captured –V voltage C ATP Simulation–VC voltage Frequency- 3.03 kHz, RRRV-67V/µs Frequency: 3.11 kHz 22 Reactor Bus Voltage – After next Poles Open 15 *10 3 10 5 0 -5 -10 -15 0.50 0.51 0.52 0.53 0.54 0.55 0.56 0.57 0.58 (f ile ADM01.pl4; x-v ar t) v :X0002B Relay Captured –V voltage B ATP Simulation–V voltage Frequency- 3.03 kHz, Changes to 3.07kHz B Frequency 3.11 kHz After all poles open Calculated Frequency:3.167 kHz C37.015 calculations assume grounded Source with Ungrounded Reactor Configuration -Frequency after first pole opens is lower than the frequency of oscillations after all poles open. This is not true if the source is ungrounded. 23 Conclusions .Addition of Surge Capacitors at the terminals of the reactor mitigates re-ignitions. .At 13.8 kV, 50 MVAR reactor Load current is high enough not to cause current Chopping as seen at 34.5 kV. .34.5 kV installation to be commissioned in the near future will provide the proof of effectiveness of Surge capacitors for lower reactor currents. .Need to have a High sample recording device with Two Voltage inputs to record Breaker TRV 24 Questions? 25.

View Full Text

Details

  • File Type
    pdf
  • Upload Time
    -
  • Content Languages
    English
  • Upload User
    Anonymous/Not logged-in
  • File Pages
    25 Page
  • File Size
    -

Download

Channel Download Status
Express Download Enable

Copyright

We respect the copyrights and intellectual property rights of all users. All uploaded documents are either original works of the uploader or authorized works of the rightful owners.

  • Not to be reproduced or distributed without explicit permission.
  • Not used for commercial purposes outside of approved use cases.
  • Not used to infringe on the rights of the original creators.
  • If you believe any content infringes your copyright, please contact us immediately.

Support

For help with questions, suggestions, or problems, please contact us