PLEASANT VALLEY SCHOOL DISTRICT LOS ALTOS MIDDLE SCHOOL 802 EAST COTA STREET. SUITE A SANTA BARBARA, CA 93103 GYMNASIUM ROOF REPLACEMENT TEL (805) 963-1955 ABBREVIATIONS (NOT ALL MAY APPLY) PROVIDE ALL LABOR, MATERIALS, EQUIPMENT, TOOLS, TRANSPORTATION, INSURANCE, AND SERVICES TO REPLACE EXISTING & AND JAN JANITOR 1. ALL WORK SHALL CONFORM TO 2019 EDITION TITLE 24 CALIFORNIA CODE OF REGULATIONS (CCR). ROOF SYSTEM WITH NEW ROOF SYSTEM AT UPPER PORTION OF THE GYMNASIUM BUILDING. ANGLE JT JOINT EXISTING CONTOURS 2. CHANGES TO APPROVED DRAWINGS AND SPECIFICATIONS SHALL BE MADE BY AN ADDENDUM OR A CONSTRUCTION @ AT KIT KITCHEN C CENTERLINE NEW CONTOURS CHANGE DOCUMENT (CCD) APPROVED BY THE DIVISION OF THE STATE ARCHITECT AS REQUIRED BY SECTION 4-338, DIAMETER OR LAB LABORATORY PART 1, T24 CCR. ROUND LAM LAMINATE # POUND OR NUMBER LAV LAVATORY 3. A DSA CERTIFIED INSPECTOR WTIH CLASS 3 SHALL BE EMPLOYED BY THE DISTRICT AND SHALL PROVIDE CONTINUOUS EXISTING SPOT GRADE ACT ACOUSTICAL LKR LOCKER INSPECTION OF THE WORK. THE DUTIES OF THE INSPECTION ARE DEFINED IN SECTION 4-342, PART 1, T24, CCR. THE ACD AMENDED LT LIGHT PROJECT INSPECTOR SHALL BE CERTIFIED BY DSA TO INSPECT. LTG LIGHTING CONSTRUCTION NEW SPOT GRADE DOCUMENT 4. APPARENT DISCREPANCIES ON DRAWINGS AND/OR SPECIFICATIONS SHALL BE REPORTED TO THE ARCHITECT BEFORE MAT'L MATERIAL ACO AREA COMPLIANCE PROCEEDING WITH THE WORK. MAX MAXIMUM EXISTING BUILDING ROOF AREA TO BE REPLACED OFFICER MB MACHINE BOLT DIRECTION OF 5. ANY DIFFERENCE BETWEEN THE EXISTING CONSTRUCTION AS OBSERVED IN THE FIELD AND AS SHOWN ON THE AT GYMNASIUM BUILDING ROOF AREA: 7,700 S.F. AD AREA DRAIN M.C. MEDICINE CABINET DRAINAGE FLOW ADA AMERICANS WITH DRAWING SHALL BE REPORTED TO THE ARCHITECT BEFORE PROCEEDING WITH THE WORK. MECH MECHANICAL DISABILITIES ACT MEOR MECH ENG OF REC 6. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO STARTING WORK. THE ARCHITECT SHALL BE NOTIFIED OF ADJ ADJUSTABLE LEVEL LINE, BENCH MARK, MEMB MEMBRANE ANY DISCREPANCIES OR INCONSISTENCIES. THE CONTRACTOR IS RESPONSIBLE FOR CHECKING AND COORDINATING AFF ABOVE FINISH FLOOR WORK POINT OR CONTROL MTL METAL POINT DIMENSIONS. AGGR AGGREGATE MFG MANUFACTURER ALUM ALUMINUM MH MANHOLE NONE ANNLD ANNEALED 7. IT SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO ENSURE THAT ALL APPLICABLE SAFETY LAWS MIN MINIMUM DIMENSION LINE AND POINT AOR ARCH OF REC ARE STRICTLY ENFORCED AND TO MAINTAIN A SAFE CONSTRUCTION PROJECT. MIR MIRROR APP APPROXIMATE MISC MISCELLANEOUS 8. IT SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO PROVIDE SUPERVISION OF THE CONSTRUCTION 0146* ARCH ARCHITECT/URAL CENTER LINE OR FLOOR LINE M.O. MASONRY WORK TO ENSURE THAT IT IS BUILT IN CONFORMANCE WITH THE APPROVED PLANS AND SPECIFICATIONS. THE ASPH ASPHALT OPENING ARCHITECT WILL PROVIDE ONLY PERIODIC OBSERVATION OF THE WORK. SEE NOTE 3 FOR DSA INSPECTION ASS'Y ASSEMBLY MTD MOUNTED PROPERTY, BOUNDARY OR REQUIREMENTS. MTR MONITOR CUTLINE BD BOARD MULL MULLION 9. ANY DAMAGE DONE TO THE EXISTING CONSTRUCTION DURING THE COURSE OF THIS WORK SHALL BE REPLACED BY BLDG BUILDING (N) NEW THE CONTRACTOR AT THE CONTRACTOR'S EXPENSE WITH NO ADDITIONAL COST TO THE OWNER. BLK BLOCK N NORTH MATCH LINE, SHADED BLK'G BLOCKING SIDE IS BEING CONSIDERED NEG PRES NEGATIVE 10. GRADING PLANS, DRAINAGE IMPROVEMENTS, ROAD & ACCESS REQUIREMENTS AND ENVIRONMENTAL HEALTH BM BEAM PRESSURE CONSIDERATIONS SHALL COMPLY WITH ALL LOCAL ORDINANCES. BOT BOTTOM NIC NOT IN CONTRACT OUTLINE OF HIDDEN OBJECT, GENERAL NR NON RATED NIC ITEMS, REMOVED MATERIAL 11. CUTTING, BORING, SAWCUTTING OR DRILLING THROUGH THE NEW OR EXISTING STRUCTURAL ELEMENTS TO BE DONE PARTIAL LIST OF APPLICABLE CODES AS OF January 1, 2020 CAB CABINET NO. NUMBER ONLY WHEN SO DETAILED IN THE DRAWINGS OR ACCEPTED BY THE ARCHITECT AND THE STRUCTURAL ENGINEER WITH G-001 TITLE SHEET/ GENERAL INFORMATION/ VICINITY MAP/ SITE PLAN CB CATCH BASIN NOM NOMINAL THE APPROVAL OF DSA REPRESENTATIVE. ALL WELDING SHALL BE SPECIALLY INSPECTED BY AN AWS-CWI QUALIFIED 2019 California Building Standards Administrative Code, Title 24 C.C.R. FENCE LINE G-002 SPECIFICATIONS CEM CEMENT NTS NOT TO SCALE INSPECTOR APPROVED BY DSA. ALL BRACING OF DUCTS AND PIPING SHALL BE INSTALLED IN ACCORDANCE WITH 2019 California Building Code (CBC), Title 24 C.C.R. CER CERAMIC OA OVERALL SMACNA GUIDELINES AS APPROVED BY DSA. WHERE BRACING DETAILS ARE NOT SHOWN ON THE DRAWINGS OR IN THE (2018 International Building Code of the International Code Council, with California Amendments) CI CAST IRON O/ OVER BREAK LINE 2019 California Electrical Code (CEC), Title 24 C.C.R. GUIDELINES, THE FIELD INSTALLATION SHALL BE SUBJECT TO THE APPROVAL OF THE ARCHITECT, MECHANICAL ARCHITECTURAL CG CORNER GUARD OC ON CENTER ENGINEER AND FIELD ENGINEER. A COPY OF THE GUIDELINES PUBLISHED BY SMACNA AND APPROVED BY DSA SHALL (2017 National Electrical Code of the National Fire Protection Association, NFPA) CLG CEILING NOTE SYMBOL, 2019 California Mechanical Code (CMC), Title 24 C.C.R. OD OUTSIDE DIAMETER BE PROVIDED BY THE CONTRACTOR AND KEPT ON THE JOB AT ALL TIMES. A-221 ROOF PLAN & DEMOLITION PLAN CAUK'G CAULKING/CHALKING OFF OFFICE 22 SEE NUMBERED (2018 Uniform Mechanical Code of the International Association of Plumbing and Mechanical Officials, IAPMO) A-701 ROOF DETAILS CLO CLOSET OPN'G OPENING NOTES COLUMN 12. SHOULD ANY EXISTING CONDITIONS SUCH AS DETERIORATION OR NON COMPLYING CONSTRUCTION BE DISCOVERED 2019 California Plumbing Code (CPC), Title 24 C.C.R. CLR CLEAR OPP OPPOSITE WHICH IS NOT COVERED BY THE DSA APPROVED DOCUMENTS WHEREIN THE FINISHED WORK WILL NOT COMPLY WITH (2018 Uniform Plumbing Code of the International Association of Plumbing and Mechanical Officials, IAPMO) CO CASED OPENING 2019 California Energy Code (CEC), Part 6, Title 24 C.C.R. OSHPD OFFICE OF STATE HEALTH 1 TITLE 24, C.C.R., OR SEPARATE SET OF PLANS AND SPECIFICATIONS, DETAILING AND SPECIFYING THE REQUIRED ARCHITECT STAMP CONSULTANT STAMP COR CONTR OF REC PLANNING & DEVELOPMENT REPAIR WORK SHALL BE SUBMITTED TO AND APPROVED BY DSA BEFORE PROCEEDING WITH THE REPAIR WORK.. 2019 California Fire Code, Title 24 C.C.R. COL COLUMN PRCST PRECAST COLUMN GRID REFERENCE, (2018 International Fire Code of the International Code Council) CONC CONCRETE PL PROPERTY LINE POINT OF HEXAGON 13. A DSA ACCEPTED TESTING LABORATORY DIRECTLY EMPLOYED BY THE SCHOOL DISTRICT SHALL CONDUCT ALL THE 2019 California Green Building Standards Code (CALGreen Code), Title 24 C.C.R. TOWARDS COLUMN LINE CONN CONNECTION PLAM PLASTIC LAMINATE REQUIRED TESTS AND INSPECTIONS FOR THE PROJECT. 2019 California Referenced Standards Code, Title 24 C.C.R. CONSTR CONSTRUCTION PLSTR PLASTER A Title 19 C.C.R., Public Safety, State Fire Marshal Regulations. CONT CONTINUOUS PLYWD PLYWOOD 14. ALL WORK (AS APPLICABLE) MUST MEET THE MANDATORY MEASURES OF THE 2019 CALIFORNIA GREEN BUILDING CONTR CONTRACTOR PR PAIR STANDARDS (CAL GREEN) CODE (TITLE 24, PART II). PARTIAL LIST OF APPLICABLE STANDARDS CORR CORRIDOR PT POINT NFPA 13 Automatic Sprinkler Systems 2019 Edition CTSK COUNTERSUNK PTD PAPER TOWEL DISPENSER LOBBY ROOM NAME NFPA 14 Standpipe Systems (CA Amended) 2013 Edition CNTR COUNTER PTD/R COMBINATION PAPER 125 ROOM NUMBER NFPA 17A Wet Chemical Extinguishing Systems 2013 Edition 2B5 CTR CENTER TOWEL DISPENSER & ROOM MATERIAL CODE * NFPA 20 Stationary Pumps 2019 Edition 10'-0" CEILING HEIGHT RECEPTACLE NFPA 24 Private Fire Service Mains (CA Amended) 2019 Edition DBL DOUBLE PTN PARTITION NFPA 72 National Fire Alarm and Signaling Code (CA Amended) 2019 Edition DEPT DEPARTMENT * SEE ROOM MATERIAL AGENCY APPROVAL PTR PAPER TOWEL CODE SHEET NFPA 80 Fire Door and Other Opening Protectives 2019 Edition DF DRINKING FOUNTAIN RECEPTACLE NFPA 253 Critical Radiant Flux of Floor Covering 2019 Edition DET DETAIL QT QUARRY TILE NFPA 2001 Clean Agent Fire Extinguishing Systems 2018 Edition DIA DIAMETER A WINDOW MARK & TYPE DIM DIMENSION R RADIUS Reference code section for NFPA standards - 2019 CBC (SFM) Chapter 35. DISP DISPENSER RD ROOF DRAIN See Chapter 35 for State of California amendments to NFPA standards. DN DOWN REC RECORD 101A DOOR MARK DO DOOR OPENING REFR REFERENCE DR DOOR REF REFRIGERATOR DWR DRAWER RGTR REGISTER EQUIPMENT SCHEDULE DS DOWNSPOUT REINF REINFORCED EQUIPMENT MARK DSP DRY STANDPIPE REQ'D REQUIRED DWG DRAWING RB RESILIENT BASE RM ROOM (E) EXISTING ELEVATION SYMBOL, RO ROUGH OPENING 52 ELEVATION NUMBERS E EAST RWD REDWOOD A422 EA EACH RWL RAIN WATER LEADER ELEVATION DIRECTION EEOR ELEC ENG OF REC SHEET WHERE DRAWN EJ EXPANSION JOINT S SOUTH EL ELEVATION SC SOLID CORE ELEC ELECTRICAL SCD SEAT COVER DISPENSER ELEV ELEVATOR SCH SCHEDULE EMER EMERGENCY SD SMOKE DETECTOR SECTION ENCL ENCLOSURE SECT SECTION SHEET WHERE DRAWN ENG ENGINEER SEOR STRCT ENG OF REC AREA OF EP ELECTRICAL PANEL SFD SMOKE / FIRE DAMPER WORK EQ EQUAL SFM STATE FIRE MARSHALL EQP EQUIPMENT SHF SHELF 3 DETAIL MULTI-PURPOSE/ FM No. xxxxxxxx ES EDGE STRIP SHWR SHOWER A601 EVS ENVIRONMENTAL SHEET WHERE DRAWN GYMNASIUM BUILDING SHT SHEET REVISIONS SERVICES SHTHG SHEATHING EWP END WALL PROTECTOR SIM'L SIMILAR # EXPO EXPOSED SND SANITARY NAPKIN DISPENSER ENLARGED DETAIL NO. DATE DESCRIPTION EXP EXPANSION SNR SANITARY NAPKIN EXTR EXTERIOR RECEPTACLE SHEET WHERE DRAWN S.D. SOAP DISPENSER FA FIRE ALARM SPEC SPECIFICATION/S FB FLAT BAR SQ SQUARE FLR DRN FLOOR DRAIN S.S. STAINLESS STEEL FD FIRE DAMPER SSK SERVICE SINK REVISION NUMBER FDN FOUNDATION STA STATION REVISION CLOUD, OPTIONAL FE FIRE EXTINGUISHER STD STANDARD BLDG C BLDG F BLDG D THE ARCHITECT DOES NOT REPRESENT THAT FEC FIRE
Details
-
File Typepdf
-
Upload Time-
-
Content LanguagesEnglish
-
Upload UserAnonymous/Not logged-in
-
File Pages4 Page
-
File Size-