Tutorial on Shunt Capacitor Banks Design, Application and Protection Considerations Presenter: Pratap Mysore, HDR

Tutorial on Shunt Capacitor Banks Design, Application and Protection Considerations Presenter: Pratap Mysore, HDR

Tutorial on Shunt Capacitor Banks Design, Application and Protection Considerations Presenter: Pratap Mysore, HDR Minnesota Power Systems Conference November 12, 2015 Topics Covered . Power system Considerations, Capacitor Benefits . Capacitor Ratings, Capabilities and Service Conditions Shunt Shunt . Capacitor Unit Construction and failure mode - . Bank Design, Connections and Configuration . Sizing of Capacitor Banks Tutorial Bank Capacitor MIPSYCON_2015 MIPSYCON_2015 . MVAR sizing . Voltage Rating . Insulation requirement 2 Topics Covered .Switching Transients .Single Bank Switching .Back to Back Switching Shunt Shunt .Voltage Magnification - .Resonance Issues Capacitor Bank Tutorial Bank Capacitor .Use of Current Limiting Reactor MIPSYCON_2015 .Sizing .Switching Issues 3 Topics Covered .Switching Devices .Circuit Breaker .Circuit Switcher Shunt Shunt - . Bank Protection Capacitor Bank Tutorial Bank Capacitor .System Protection VS Bank Protection MIPSYCON_2015 .Unbalance Protection Methods 4 Tutorial Reference Materials . IEEE Std. 18-2012* – IEEE Standard for Shunt Power Capacitors. IEEE 1036-2010* – IEEE Guide for the application of Shunt Power Capacitors. PES-TR16*; Technical Report, “Transient Limiting Shunt Shunt Inductor Applications in Shunt Capacitor Banks” - * Document developed under Capacitor Subcommittee of Transmission and Distribution Committee Capacitor Bank Tutorial Bank Capacitor . C37.99 2012# – IEEE guide for the Protection of MIPSYCON_2015 Shunt capacitor Banks # Document developed under IEEE Power Systems Relaying Committee (Will soon be Power Systems Relaying and Control Committee) 5 IEEE Reference Documents . IEEE Std18TM - 2012: IEEE Standard for Shunt Power Capacitors - Revised and approved for publication on 5th December 2012 – Published on 15 February 2013. This standard provides a basis for uniformity in Shunt design, manufacturing and testing of shunt power - capacitors. Capacitor Bank Tutorial Bank Capacitor . The revision included portions of NEMA CP1 MIPSYCON_2015 document. The ratings and capabilities remain the same as 2002 version. 6 IEEE Reference Documents . IEEE 1036TM-2010 – IEEE Guide for the Application Shunt Power- under revision. Provides guidelines for the application, protection, and ratings of equipment for the Shunt Shunt safe and reliable utilization of shunt power - capacitors. Capacitor Bank Tutorial Bank Capacitor MIPSYCON_2015 MIPSYCON_2015 7 IEEE Reference Documents . C37.99 -2012; IEEE Guide for the Protection of Shunt Capacitor Banks . Revisiting analog relays technologies for the application of digital relays technologies for the protection of externally fused, internally fused, fuseless and unfused capacitor Shunt Shunt banks. - . Added theory and analysis of unbalance relaying methods. Massive editorial changes. Capacitor Bank Tutorial Bank Capacitor . Minimized bank grounding section directing references to MIPSYCON_2015 IEEE 1036. 8 IEEE Reference Documents . Technical Report PES-TR16 -2014 As Stated in the document, “The report was written in response to a great amount of confusion in the power industry surrounding the application of Transient limiting Inductors in shunt Shunt Shunt capacitor banks”. - Capacitor Bank Tutorial Bank Capacitor MIPSYCON_2015 MIPSYCON_2015 9 Other IEEE Documents . NEMA CP 1-2000 (R2008), Shunt Capacitors . Portions of this document was incorporated in the Latest revision of IEEE-18. IEEE Std. C37.48-2005 (R2010) IEEE Guide for Shunt Application, Operation, and Maintenance of High- - Voltage Fuses, Distribution Enclosed Single-Pole Air Switches, Fuse Disconnecting Switches, and Tutorial Capacitor Bank Accessories MIPSYCON_2015 10 Reactive Compensation . Allows System voltage levels to stay within the acceptable limits Shunt Shunt .Permits the maximum utilization of - transmission circuits Capacitor Bank Tutorial Bank Capacitor MIPSYCON_2015 MIPSYCON_2015 11 Long Transmission line • Represented as a series of inductor/ Capacitor elements VS VR Shunt Shunt . Voltage and Current at any point x on the - transmission line is given by: Capacitor Bank Tutorial Bank Capacitor .V(x) = VR cos(L-x) +jZ0IRsin (L-x) MIPSYCON_2015 .I(x) = IR cos(L-x) +j[VR/Z0]sin (L-x) 12 Terms used in Transmission wave equations • =(LC) = Phase constant Typically 2.07x 10-3 radians/mile • Z0 = (L/C) = Surge Impedance of the line – ~ 450 Shunt Shunt for single conductor (230 kV and below) and - around ~ 280 for bundled conductor (345 and higher) Capacitor Bank Tutorial Bank Capacitor MIPSYCON_2015 MIPSYCON_2015 • Charging KVAR/ Mile – ~ 900 @ 345 kV; ~ 270 @ 230 kV and around ~ 70 @ 115 kV • Inductive reactance – 0.5-0.8 ohms/mile 13 Receiving End Voltage of an Unloaded Line . VR = VS/Cos L ; . For a 300 mile 500 kV line, the receiving end voltage = 1.0/COS(2.07x10-3x300) Shunt Shunt . Angle = 2.07x10-3x300 radians =0.621radians =35.60 - . VR = 1.229P.U. Remote end voltage is 130% of the nominal. Tutorial Bank Capacitor MIPSYCON_2015 MIPSYCON_2015 14 Line Voltage and Charging Current V X Shunt Shunt - Line Length Capacitor Bank Tutorial Bank Capacitor MIPSYCON_2015 MIPSYCON_2015 IX Line Length 15 Surge Impedance Loading • If the line is terminated with impedance Z0, VR=IRZ0 j(l-x) • V(x) = VR [cos(L-x) +jsin (L-x)] =VRe Shunt Shunt . The magnitudes of voltage at any point of the line - is independent of the position, x Capacitor Bank Tutorial Bank Capacitor MIPSYCON_2015 MIPSYCON_2015 16 Voltage Profile of a Loaded Line P<P0 1.0 P=P0 VR = controlled to 1.0 P.U. P>P0 Shunt Shunt x - 2 Voltage Surge SI Loading [V /Z0] Capacitor Bank Tutorial Bank Capacitor Impedance,Z0 MIPSYCON_2015 345 kV 285 425 MVA (711Amps) 500 kV 285 877 MVA (1013 Amps) 17 P-V, V-Q Curves Operating Point 105% 0.9 Lead Unity PF VR Stable voltage Region Q Shunt Shunt VC - (70%) Unstable voltage Point of voltage Region instability Bus Voltage PCritical Tutorial Bank Capacitor Power MVAR required to Keep MIPSYCON_2015 the bus voltage at a level (ex:1.05) at specified power transfer 18 Shunt Reactor and Shunt Capacitor • Compensate the effect of capacitive/ inductive currents • Shunt Capacitors raise the system voltage – Shunt Reactors lower the bus voltage Shunt Shunt • During light load periods, shunt reactors are used - to control the system voltage • During heavy load periods, shunt capacitors are Tutorial Bank Capacitor used to maintain the system voltage MIPSYCON_2015 19 Application of Shunt Capacitor Banks . To provide local voltage support . Banks are switched when voltage falls below a set value. (15 -20 sec) . To provide system voltage support for higher power transfer Shunt Shunt - . To Provide fast switching to prevent voltage collapse or voltage excursions– (Poor man’s SVC s) (switching Capacitor Bank Tutorial Bank Capacitor time in cycles) MIPSYCON_2015 20 Shunt Capacitor Bank Function . Var support (local Voltage Support). Capacitors supply the reactive power and reduce losses by reducing the current on equipment such as transmission lines. Shunt Shunt - 2000A 2000 +j1000A 0.89 pf Load 2236 A Capacitor Bank Tutorial Bank Capacitor (without capacitor) j1000A MIPSYCON_2015 21 Size and number of capacitor banks . Maximum bank size is influenced by: . Change in system voltage upon capacitor bank switching . Switchgear continuous current limitation . Minimum bank size is influenced by: Shunt Shunt . The type of capacitor bank used: externally fused, - internally fused, fuseless, etc. Capacitor Bank Tutorial Bank Capacitor . The easily available ratings of capacitor units MIPSYCON_2015 . Capacitor bank unbalance considerations . Fuse performance and/or coordination 22 . The cost of the required switchgear and protection Size and Number of Capacitor Banks Capacitor bank sized so that the system voltage will not change more than 3% during switching ( GE flicker curve) I Q M var V C c Shunt Shunt - I SC Ssc Mva It is important to know the application of Capacitor Capacitor Bank Tutorial Bank Capacitor Bank MIPSYCON_2015 - for Local voltage support under contingencies (loss of a source) 23 - for System Support during through flow. Capacitor Unit Ratings As Per IEEE Std. 18 Standard ratings IEEE Std 18-2012 establishes ratings for the following electrical parameters Shunt Shunt . Voltage, rms (terminal-to-terminal) - . Reactive power Capacitor Bank Tutorial Bank Capacitor . Number of phases MIPSYCON_2015 . Frequency . Terminal(s)-to-case (or ground) insulation class 24 Capacitor Unit Ratings . Voltage - RMS (continuous): 110% of the rated value Crest Voltage 120% of the peak value including harmonics . Current - 135% of nominal rating including Shunt Shunt Harmonics - . VAR: -0 to +10% of the rated value ( +15% for units manufactured before the year 2000) Tutorial Bank Capacitor measured at 25 deg.C MIPSYCON_2015 . Temperature - -40 deg. C to +40 deg. C . Max. continuous reactive output - 135% of the 25 rated value Capacitor Unit Overvoltage Limit Reference - NEMA CP1-2000 and IEEE 1036 Voltage Duration (Percentage of Rated) 110% Continuous Shunt - 125% 30 minutes 130% 1 minute Capacitor Bank Tutorial Bank Capacitor 140% 15 seconds MIPSYCON_2015 170% 1 second 200% 15 cycles 220% 6 cycles 26 Capacitor Transient overvoltage Limit Momentary capabilities, transient peak overvoltage 4.0 3.5 3.0 voltage) Shunt Shunt - 2.5 2.0 Capacitor Bank Tutorial Bank Capacitor Peak voltage of voltage rated Peakcrestunit of (Per MIPSYCON_2015 MIPSYCON_2015 1.5 1 10 100 1000 10000 Number of transients per year 27 Source: IEEE 1036 Effect of Geomagnetically Induced Currents . GIC is quasi-DC

View Full Text

Details

  • File Type
    pdf
  • Upload Time
    -
  • Content Languages
    English
  • Upload User
    Anonymous/Not logged-in
  • File Pages
    95 Page
  • File Size
    -

Download

Channel Download Status
Express Download Enable

Copyright

We respect the copyrights and intellectual property rights of all users. All uploaded documents are either original works of the uploader or authorized works of the rightful owners.

  • Not to be reproduced or distributed without explicit permission.
  • Not used for commercial purposes outside of approved use cases.
  • Not used to infringe on the rights of the original creators.
  • If you believe any content infringes your copyright, please contact us immediately.

Support

For help with questions, suggestions, or problems, please contact us