Power Transformers

Power Transformers

ELG4125: Lecture 2 Power Transformers The Ideal Transformer The Real Transformer Equivalent Circuits for Practical Transformers The Per-Unit System Three-Phase Transformers Autotransformers Transformers in Power Systems • Typically in power systems, voltages get transformed approximately five times between generation and delivery to the users. • Generation in power systems, primarily by synchronous generators, takes place at around 20-kV level. • Transmission voltages of 230 kV, 345 kV, 500 kV, and 765 kV is common. • At the load, these voltages are stepped down to 120/240 V single-phase in residential usage. • Another advantage of transformers in many applications is to provide electrical insulation for safety purposes. Real Transformers Transformer Types Power Transformers Current Transformers Voltage Transformers Transformer Connections Series Transformers Each leg is a single phase transformer Transformer Purchasing Issues Y-Y connections (no phase shift) Efficiency D-D connections (no phase shift) Audible Noise Y-D connections (-30 degrees phase shift) Installation Costs D-Y connections (+30 degrees phase shift) Manufacturing Facilities Performance Record 3 Nameplate Information • kVA is the apparent power. • Voltage ratings for high and low side are no-load values. The symbol between the values indicate how the voltages are related: • Long dash (—) From different windings. • Slant (/) …from same winding: • 240/120 is a 240 V winding with a center tap. • Cross (X) Connect windings in series or parallel. Not used in wye-connected winding: • 240X120 two part winding connected in series for 240 or parallel for 120. • Wye (Y) A wye-connect winding. Basic Principles of Transformer Operation • Transformers consist of two or more coupled windings where almost all of the flux produced by one winding links the other winding. Transformer Exciting Current • Transformers use ferromagnetic materials that guide magnetic flux due to their high permeability, require small ampere- turns to produce the desired flux density. • The magnetising current is that current which flows in the primary winding when the primary voltage is applied with the secondary unloaded. It is the necessary current that satisfies the excitation condition as determined by the fundamental transformer equation. • In modern power transformer of large kVA ratings, the magnetizing currents in their normal operating region are very small, for example, well below 0.2% of the rated current at the rated voltage. Voltage Transformation d d v e N vS eS NS P P P dt dt • The EMF of a transformer at a given flux density increases with frequency. By operating at higher frequencies, transformers can be physically more compact because a given core is able to transfer more power without reaching saturation and fewer turns are needed to achieve the same impedance. However, core loss and conductor skin effect also increase with frequency. • Aircraft and military equipment employ 400 Hz power supplies which reduce core and winding weight. Conversely, frequencies used for some railway electrification systems were much lower (16.7 Hz and 25 Hz) than normal utility frequencies (50/60 Hz) for historical reasons concerned mainly with the limitations of early electric traction systems. • As such, the transformers used to step down the high over-head line voltages (15 kV) were much heavier for the same power rating than those designed only for the higher frequencies. 2π EP f NP φmax 4.44 f NP φmax 2 VP max 4.44 f NP • Where VP is the RMS value of the applied voltage with the assumption that eP = VP. The second Equation shows that the flux is determined by the applied voltage, the frequency of operation, and number of turns in the winding. Example Transformer Equivalent Circuit Viewed from the Primary Side Modeling a Real Transformer Equivalent Circuit with Parameters Moved to the Primary Side Transformer Phasor Diagram Transformer Tests Test to Determine Transformer Parameters, we require to conduct Open Circuit Test: Energize Low voltage winding at rated voltage, leaving other winding open Measure Current (Ioc) and Power (Poc) into energized winding. Calculate parameters Short Circuit Test: Energize Low current (high voltage) winding at rated current with a solid short circuit applied across the other winding Measure Voltage and Power at terminals of energized winding Calculate parameters 15 Transformer Test Open-Circuit Test Short-Circuit Test S S PC I C , and VS S S 2 S 2 I C I e - I C 2 V V S S PSC SC 2 RC , and R X T - RT I S T 2 I C ISC SC S VS X m S Im Example 1 Example 2 The Per unit system • In the per-unit system, the voltages, currents, powers, impedances, and other electrical quantities are expressed on a per-unit basis by the equation: Actual value Quantity per unit = Base value of quantity • It is customary to select two base quantities to define a given per-unit system. The ones usually selected are voltage and power. S S Vb Vrated b rated Then compute base values for currents and impedances S 2 b Vb Vb I b Z V b b I b Sb Vactual Iactual Vp.u. I p.u. Vb Ib S Z S actual actual p.u. Z p.u. Sb Z b Z% Z p.u. 100% Example 1 Example 2 An electrical load is rated 120 volts, 500 watts. Compute the per-unit and percent impedance of the load. Give the per unit equivalent circuit. 2 2 V V (120)2 P R 28.8 R P 500 Power factor = 1.0 Z 28.80 23 Select base quantities S 500VA b Vb 120V Compute base impedance V 2 (120)2 b Zb 28.8 Sb 500 The per-unit impedance is Z 28.80 Z p.u. 10p.u. Zb 28.8 24 Percent impedance: Z% 100% Per-unit equivalent circuit: Z 10p.u. VS 10p.u. 25 Per-unit System for Single Phase Circuits One-phase circuits Sb S1- V I where V Vline-to-neutral I Iline-current VbLV VLV VbHV VHV Sb Sb IbLV IbHV VbLV VbHV 26 2 2 VbLV (VbLV ) VbHV (VbHV ) ZbLV ZbHV IbLV Sb IbHV Sb S * S pu VpuI pu Sb P Ppu VpuI pu cos Sb Q Qpu VpuI pu sin Sb 27 Transformation Between Bases Sb1 SA Vb1 VA 2 Vb1 Z L Zb1 Z pu1 Sb1 Zb1 And second Sb2 SB Vb2 VB 2 Vb2 Z L Zb2 Z pu2 Sb2 Zb2 28 Transformation Between Bases 2 Z pu2 ZL Zb1 Zb1 Vb1 Sb2 2 Z pu1 Zb2 ZL Zb2 Sb1 Vb2 2 V S b1 b2 Z pu2 Z pu1 Vb2 Sb1 “1” – old “2” - new 2 V S Z Z b,old b,new pu,new pu,old Vb,new Sb,old 29 Transformation Between Bases Generally per-unit values given to another base can be converted to new base by the equations: Sbase1 (P,Q, S) pu_on_base_ 2 (P,Q, S) pu_on_base_1 Sbase2 Vbase1 Vpu_on_base_ 2 Vpu_on_base_1 Vbase2 2 (Vbase1) Sbase2 (R, X , Z) pu_on_base_ 2 (R, X , Z) pu_on_base_1 2 (Vbase2 ) Sbase1 When performing calculations in a power system, every per-unit value must be converted to the same base. 30 Per-unit System for Single Phase Transformer Consider the equivalent circuit of transformer referred to LV side and HV side shown below: RS X S 2 j 2 RS jX S a a VLV VHV V N N1 N2 Define a LV 1 1 S VHV N2 Referred to LV side Referred to HV side 31 Per-unit System for Single Phase Transformer Choose Vb1 VLV ,rated Sb Srated Compute VHV 1 Vb2 Vb1 Vb1 VLV a 2 2 Vb1 Vb2 Zb1 Zb2 Sb Sb 2 2 Zb1 Vb1 Vb1 2 2 a Z V 1 2 b2 b2 ( V ) 32 a b1 Per-unit System for Single Phase Transformer Per-unit impedances are RS jX S Z p.u.1 Zb1 R jX R jX S S S S 2 2 2 2 R jX Z a a a a S S p.u.2 Z Zb2 b1 Zb1 a2 Z p.u.1 Z p.u.2 33 Voltage Regulation Voltage regulation is defined as V - V VR no-load full-load 100% V full-load In per-unit system V - V VR pu,no-load pu, full-load 100% Vpu, full-load Vfull-load: Desired load voltage at full load. It may be equal to, above, or below rated voltage. Vno-load: The no load voltage when the primary voltage is the desired voltage in order the secondary voltage be at its desired value at full load. 34 Example A single-phase transformer rated 200-kVA, 200/400-V, and 10% short circuit reactance. Compute the voltage regulation when the transformer is fully loaded at unity power factor and rated voltage 400-V. Vb2 400V VP j0.1 VS Sb 200kVA X S Sload Sload, pu 10pu X S, pu j0.1pu 35 Rated voltage VS, pu 1.00pu * * Sload, pu 1.00 I 1.00pu load, pu VS, pu 1.00 VP, pu VS, pu I puX S, pu 1.00 1.00 j0.1 1 j0.1 1.0015.7o pu 36 Secondary side Vpu, full-load VS, pu 1.00pu o Vpu,no-load VP, pu 1.0015.7 pu Voltage regulation V - V VR pu,no-load pu, full-load 100% Vpu, full-load 1.001-1.0 100% 0.1% 1.0 37 Problem j100 G 20 kV 22kV/220kV 220kV/20kV 50MVA 80MVA 50MVA 0.8 PF 14% 10% lagging Select Vbase in generator circuit and Sb=100MVA, compute the per unit equivalent circuit. 38 Residential Distribution Transformers Single phase transformers are commonly used in residential distribution systems.

View Full Text

Details

  • File Type
    pdf
  • Upload Time
    -
  • Content Languages
    English
  • Upload User
    Anonymous/Not logged-in
  • File Pages
    54 Page
  • File Size
    -

Download

Channel Download Status
Express Download Enable

Copyright

We respect the copyrights and intellectual property rights of all users. All uploaded documents are either original works of the uploader or authorized works of the rightful owners.

  • Not to be reproduced or distributed without explicit permission.
  • Not used for commercial purposes outside of approved use cases.
  • Not used to infringe on the rights of the original creators.
  • If you believe any content infringes your copyright, please contact us immediately.

Support

For help with questions, suggestions, or problems, please contact us