Measuring Air Handler Flow Accurately

Measuring Air Handler Flow Accurately

Measuring Air Handler Flow Accurately Paul Morin The Energy Conservatory © Copyright 2014 The Energy Conservatory Presentation Housekeeping • If you do not hear anything from your computer’s speaker system you will need to dial in and listen to the presentation over the phone • If you have a question for the presenter, please type it in the question box at the right of the screen • The webinar will be available on The Energy Conservatory website and our YouTube site within a week Agenda • Why measuring air handler flow is important • Advantages of using the TrueFlow® • TrueFlow system components • Gauge options • Basic TrueFlow test procedures • TrueFlow procedure with two returns • The Duct Blaster® Pressure matching method Why measuring air handler flow is important • Insufficient airflow is a common problem • Low airflow can lead to: • Decreased heating and cooling capacity • Increased energy usage • Comfort problems • Optimize the performance of heat pump and air conditioner Advantages of using the TrueFlow® • Widely used methods are problematic or time consuming • Simple and accurate method • Proven success over years of field testing • Can be used with any manometer with a resolution of 1 Pascal (0.005 inches H₂O) TrueFlow® Specs • Flow Accuracy: • +/- 7% when using gauge w/1% accuracy • +/- 9% when using a Magnehelic gauge • Flow Range: • #14 TrueFlow Plate 365 – 1565 CFM • #20 TrueFlow Plate 485 – 2100 CFM • System Weight: • 13 lbs. TrueFlow System Components • Carrying Case • Flow Conversion Tables • 10’ blue and 30’ clear tubing • Operations Manual 2 Calibrated TF Plates 8 spacers for sizing adjustments 1 static pressure probe Gauge options Gauge with a resolution of 1 Pa. (0.005 inches H₂O) • DG-700 or DG-500 • DG-2 or DG-3 • Other digital manometers • Magnehelic gauge (+/- 9%) Basic TrueFlow test procedures Choose a location closest to the airhandler Basic TrueFlow test procedures Basic Test Procedure • With AH on and filter in place, measure NSOP • Replace filter with TF • Measure TFSOP • Measure airflow • Calculate a Flow Resistance Correction factor • Use Correction factor to calculate adjusted flow Setup • Replace dirty filters • Open all registers • Open a window • Open AH zone / outside Setup • Insert static probe: • Point the probe into the airflow • Side of supply plenum • Dead end corner of supply plenum • Side of return plenum w/o trunk line, return register or return duct connected to it • 24” from TrueFlow plate • 24” from 90° corners • 24” from return trunk line connections • TrueFlow plate at remote filter grille? • Don’t put probe in return plenum Enter NSOP using DG-700 • The process is simplified • Instead of: • Recording NSOP • Recording TFSOP • Use a chart to determine Flow Resistance Correction factor • You can: • Enter the NSOP into the DG-700 • DG-700 will adjust the flow Enter NSOP using DG-700 • Connect tubing from probe to gauge • Turn on the air handler • Set DG-700 to PR / AH mode • NSOP will begin flashing With AH on and filter in place, measure NSOP • Press the START button • Press the ENTER button Install the TrueFlow Plate • Remove the existing filter • Choose appropriate TrueFlow Plate • Install spacers on top & side • Face the front into airflow Install the TrueFlow Plate • All of airflow must pass through the plates (not around) • Air must pass over all of the plate • Obstructions 6” upstream or 2” downstream affect accuracy • Can be installed inside the AH cabinet (taped in place) Measure the Adjusted Total Air Handler Flow • Connect 2 tubes from the TrueFlow Plate to Channel B • Change the Device to TF • Change CONFIG to match the Plate being used • Turn on the air handler • If numbers fluctuate, switch to LONG term averaging • Record the adjusted flow reading TrueFlow procedure using other gauges • Same as with DG-700 except: • You need to convert pressure at TrueFlow Plates to flow using a chart • You need to adjust flow based on pressure differences between NSOP and TFSOP using a chart TrueFlow with other gauges • You need to convert pressure at TrueFlow Plates to flow using a chart TrueFlow with other gauges • You need to adjust flow based on pressure differences between NSOP and TFSOP: • Record NSOP • Record TFSOP • Use chart to determine multiplier TrueFlow with other gauges TrueFlow with other gauges TrueFlow procedure with two returns • If returns share a trunk, measure at air handler cabinet (if possible) • If returns enter cabinet from different sides, use both Metering Plates: • If second return is smaller than 14x20, use a transition (example: 14x14 to 14x20 transition) • Long tube for Channel A • Measure flows separately and add together Air Density Correction Charts Volumetric Flow • Cooling Air Flow Requirements • 350 – 400 CFM per Ton Humid • 400 – 425 CFM per Ton Dry • 450 CFM per Ton @ 7000’ elevation Air Density Correction Charts Measuring Total System Air Flow (Pressure Matching Method) Measuring Total System Air Flow (Pressure Matching Method) • Measure the Normal System Operating Pressure (NSOP) • Connect the Duct Blaster® Fan to the Duct System • All return air must be flowing through the Duct Blaster fan • Match the Normal System Operating Pressure (NSOP) Measure the NSOP • Replace dirty filters • Open all registers • Open a window • Open AH zone / outside Setup • Insert static probe: • Point probe into the airflow • Side of supply plenum • Dead end corner of supply plenum • Side of return plenum w/o trunk line, return register or return duct connected to it • 24” from TrueFlow plate • 24” from 90° corners • 24” from return trunk line connections • TrueFlow plate at remote filter grille? • Don’t put probe in return plenum Measuring Total System Air Flow (Pressure Matching Method) • Measure the NSOP: • Turn on the airhandler • Turn on gauge and write down the NSOP Measuring Total System Air Flow (Pressure Matching Method) • Connect the Duct Blaster® Fan to the Duct System Measuring Total System Air Flow (Pressure Matching Method) • Match the Normal System Operating Pressure (NSOP): • Connect tubing from DB fan to the DG-700 • Set DG-700 to PR/ FL mode • Turn on the air handler • Turn up the Duct Blaster fan to match the NSOP • Record the Total System Air Flow Measuring Total System Air Flow (Pressure Matching Method) • Unable to match the NSOP? • Turn Duct Blaster fan all of the way up • Record the CFM flow from the DG-700 • Record the operating pressure you were able to achieve • Use the Flow Resistance Correction Factor from Appendix B of the True Flow manual Unable to match the NSOP? • Use the Flow Resistance Correction Factor from Appendix B of the True Flow manual Measuring Air Handler Flow Accurately Questions? Paul Morin The Energy Conservatory (612) 827-1117 phone (612) 254-2162 direct Email: [email protected] website: www.energyconservatory.com.

View Full Text

Details

  • File Type
    pdf
  • Upload Time
    -
  • Content Languages
    English
  • Upload User
    Anonymous/Not logged-in
  • File Pages
    43 Page
  • File Size
    -

Download

Channel Download Status
Express Download Enable

Copyright

We respect the copyrights and intellectual property rights of all users. All uploaded documents are either original works of the uploader or authorized works of the rightful owners.

  • Not to be reproduced or distributed without explicit permission.
  • Not used for commercial purposes outside of approved use cases.
  • Not used to infringe on the rights of the original creators.
  • If you believe any content infringes your copyright, please contact us immediately.

Support

For help with questions, suggestions, or problems, please contact us