Explosion Protection Document Page 1 of 1

Explosion Protection Document Page 1 of 1

<p>Coatings Solutions Explosion Protection Document Page 1 of 5 </p><p>Risk assessment for plant: Oven room R 7</p><p>Plant section Proc. Orig. A-measure1) Rem. Zone Ignition I-measure2)/ Note: Mat’ls temp. zone zone expansion sources C-measure3) Continuous-flow 1 - 5 <160°C 0 AV, 2*) Entire IE1 Floors R<108  *) Operating drier, dilution below vapour Footwear anti- conditions pre-drier 10% LEL space incl. static are outside > 1 m³ exhaust air Metals R<106  zone interior, apart unit Plastic surfaces definition from initiator <100 cm² housing area Plastic containers < 60 l IH1 Drying temperature limited to 160°C (> limit temperature) IH3 Conveyor systems with relative speeds < 1 m/s IH4 Shaft bearings subject to preventive maintenance 1)Measure to limit the probability of an explosive Atmosphere occurring Page 1 of 5 2)Measure to avoid effective Ignition sources 3)Design-based explosion protection measure, where effective ignition sources cannot be reliably ruled out Plant section Proc. Orig. A-measure1) Rem. Zone Ignition I-measure2)/ Note: Mat’ls temp. zone zone expansion sources C-measure3) (cont.) IS1 Electrical Continuous-flow equipment drier, installed outside pre-drier zone > 1 m³ IS2 See IH3/IH4 interior, apart CP not required from initiator because of housing area dilution < 10% LEL Initiator housing 1 - 5 <160°C 0 AD, NEX pre-drier, interior no penetration of atmosphere possible because of cast enclosure UV zone, interior 1 - 5 <160°C 0 AV, 2*) Entire IE1 Floors R<108  *) Operating except dilution below 10% vapour Footwear anti- conditions initiator housing, LEL space incl. static are outside UV lamp housing, exhaust air Metals R<106  zone microwave unit Plastic surfaces definition detector housing <100 cm² and lighting Plastic containers housing < 60 l IH1 Drying temperature limited to 160°C (> limit temperature)</p><p>1)Measure to limit the probability of an explosive Atmosphere occurring Page 2 of 5 2)Measure to avoid effective Ignition sources 3)Design-based explosion protection measure, where effective ignition sources cannot be reliably ruled out Plant section Proc. Orig. A-measure1) Rem. Zone Ignition I-measure2)/ Note: Mat’ls temp. zone zone expansion sources C-measure3) (cont.) IH3 Conveyor UV zone, interior systems with except relative speeds initiator housing, < 1 m/s UV lamp housing, microwave detector housing and lighting CP not required housing because of dilution < 10 % LEL Initiator housing 1 - 5 < 160 0 AD, NEX UV zone, °C no penetration of interior atmosphere possible because of cast enclosure Lighting housing, 1 - 5 <160°C 0 AV, NEX interior dilution below 10% LEL </p><p>AP, forced-ventilated lamp housing with air monitoring</p><p>1)Measure to limit the probability of an explosive Atmosphere occurring Page 3 of 5 2)Measure to avoid effective Ignition sources 3)Design-based explosion protection measure, where effective ignition sources cannot be reliably ruled out Plant section Proc. Orig. A-measure1) Rem. Zone Ignition I-measure2)/ Note: Mat’ls temp. zone zone expansion sources C-measure3) UV lamp housing, 1 - 5 <160°C 0 AV, NEX interior dilution below 10% LEL </p><p>AP, forced-ventilated lamp housing with air monitoring Microwave 1 - 5 <160°C 0 AV, NEX detector housing, dilution below 10% interior LEL </p><p>AP, forced-ventilated lamp housing with air monitoring Final drier, 1 - 5 <160°C 0 AV, 2*) Entire IE1 Floors R<108  *) Operating interior, except dilution below 10% vapour Footwear anti- conditions initiator housing LEL space incl. static are outside exhaust air Metals R<106  zone unit Plastic surfaces definition <100 cm² Plastic containers < 60 l</p><p>1)Measure to limit the probability of an explosive Atmosphere occurring Page 4 of 5 2)Measure to avoid effective Ignition sources 3)Design-based explosion protection measure, where effective ignition sources cannot be reliably ruled out Plant section Proc. Orig. A-measure1) Rem. Zone Ignition I-measure2)/ Note: Mat’ls temp. zone zone expansion sources C-measure3) (cont.) IH1 Drying Final drier, temperature interior, except limited to 160°C initiator housing (> limit temperature) Final drier initiator 1 - 5 <160°C 0 AD, NEX housing, no penetration of interior atmosphere possible because of cast enclosure Oven room 1, 2, 3 <40°C 2 Mechanical NEX surroundings ventilation for 2x air change</p><p>1)Measure to limit the probability of an explosive Atmosphere occurring Page 5 of 5 2)Measure to avoid effective Ignition sources 3)Design-based explosion protection measure, where effective ignition sources cannot be reliably ruled out</p>

View Full Text

Details

  • File Type
    pdf
  • Upload Time
    -
  • Content Languages
    English
  • Upload User
    Anonymous/Not logged-in
  • File Pages
    5 Page
  • File Size
    -

Download

Channel Download Status
Express Download Enable

Copyright

We respect the copyrights and intellectual property rights of all users. All uploaded documents are either original works of the uploader or authorized works of the rightful owners.

  • Not to be reproduced or distributed without explicit permission.
  • Not used for commercial purposes outside of approved use cases.
  • Not used to infringe on the rights of the original creators.
  • If you believe any content infringes your copyright, please contact us immediately.

Support

For help with questions, suggestions, or problems, please contact us