<p>CONTACT WALL STATION NON-DIM SWITCH WITH OCCUPANCY SENSOR SPECIFICATION.</p><p>GENERAL.</p><p>A.) Overview.</p><p>1.) The Contact Wall Station Non-Dim Switch with Occupancy Sensor is a designer-style, multiple-detection technology, and universal voltage occupancy sensing wall switch.</p><p>2.) The Contact Wall Station Non-Dim Switch shall be designed to accept and control universal voltage (120VAC to 277VAC, 60Hz.) and rated to control up to 1000VA lighting loads.</p><p>3.) The Non-Dim Switch shall be a two-wire switch capable of handling the following loads:</p><p> a.) Incandescent / Quartz Halogen.</p><p> b.) General Inductive.</p><p> c.) Cold Cathode / Neon.</p><p> d.) Electronic Low-Voltage.</p><p> e.) Magnetic Low-Voltage.</p><p> f.) Fluorescent Non-Dimming Ballasts.</p><p>4.) The Non-Dims integral occupancy sensor shall have a viewing area of not less than one hundred seventy (170°) degrees at an axial distance of forty feet (40'), fifty feet (50') at 0 degrees, and shall have a total coverage area of not less than four- thousand square feet (4,000 Sq. Ft.) with an unobstructed view.</p><p>5.) The non-dim shall be supplied with color-coordinated, self-sticking masking labels that reduce the field of view of the occupancy sensor to 60, 90, or 120 degrees. </p><p>6.) The non-dims integral occupancy sensor shall utilize non-intrusive, passive detection technologies consisting of:</p><p> a.) Passive Infrared (PIR) to read and detect occupants' body heat and movement. b.) Enhanced PIR with Digital Signal Processing (DSP) to read and detect occupancy throughout the entire space.</p><p> c.) Photo detection to sense human motion and help differentiate this signal from other sources such as hot air vents.</p><p>7.) Under no circumstances shall the non-dims integral occupancy sensor emit energy of any type into the space that can potentially interfere with electrical, electronic, or medical devices (i.e. hearing aids).</p><p>8.) Each non-dim shall provide manual on/automatic off or automatic on/ automatic off operation and accept on/off commands from an unlimited number of multi- location 3-way Contact Wall Station Channel Remotes.</p><p>9.) Contact Wall Station Channel Remote stations shall provide multi-location On / Off control of the switch using conventional 3-way wiring.</p><p>10.) Each non-dim shall be capable of 4 time-out methods to adapt to the space:</p><p> a.) Manual fixed time (user definable) from 1 to 30 minutes.</p><p> b.) Auto Time Out Calibration - Conservative Mode.</p><p> c.) Auto Time Out Calibration - Normal Mode.</p><p> d.) Auto Time Out Calibration - Aggressive Mode. In Auto Time Out Calibration Mode the non-dim shall automatically adapt the time out period to the occupancy patterns of the space to maximize energy savings while minimizing distraction to the user.</p><p>11.) The non-dim shall, when manually turned off by the user, continue to monitor the space, but will not turn on the lights. Once the non-dim detects a continuous vacancy for a period of five (5) minutes, the non-dim will rearm itself for automatic on (if so programmed). User shall be able to, at anytime, override this feature by manually turning on the lights.</p><p>12. Each non-dim shall, at the user's discretion, be programmed (at the sensor) to automatically adapt its programming parameters to optimally set time delay according to the space's occupancy/vacancy patterns.</p><p>13.) The non-dim shall, at the user's discretion, be programmed to prevent the automatic turning on of lights, when in automatic on mode, by either:</p><p> a.) Selecting one of eight (8) preset ambient light levels offered by the sensor device. b.) The sensor self-reads and permanently stores a specific ambient light level.</p><p> c.) This programming feature always allows for manual override "On" or "Off" when more or less light is needed or desired by the user.</p><p>14.) The non-dim's operational/parameter programming shall be accomplished with the non-dim installed and operational without the need to remove the non-dim (or its faceplate) from its installed location.</p><p>15.) Each non-dim shall provide a LED indicator to provide indication when the sensor detects movement.</p><p>16.) The non-dim shall offer the selection of three user-programmable warning tones before automatically turning Off. The non-dim shall also offer the ability, to the user, to turn off warning tones.</p><p>17.) The non-dim shall mount in a single gang wallbox and be gangable with other designer-style electrical devices and faceplates.</p><p>18.) Each non-dim shall include a designer-style screwless, detachable color- coordinated faceplate in White, Ivory, or Light Almond.</p><p>19.) The non-dim shall be UL Listed to U.S. and Canadian standards for a 120VAC to 277VAC capacity.</p>
Details
-
File Typepdf
-
Upload Time-
-
Content LanguagesEnglish
-
Upload UserAnonymous/Not logged-in
-
File Pages3 Page
-
File Size-