FLOW RATE INDICATOR / TOTALIZER WITH PULSE SIGNAL OUTPUT

Features Signal output • Displays instantaneous flow rate, total and • Scaled pulse output according to accumulated accumulated total. total. • Large 17mm (0.67") digit selection for flow rate or total. Signal input • Scaled pulse signal output according Flow accumulated total. • Reed-switch. • Ability to process all types of flowmeter • NAMUR. signals. • NPN/PNP pulse. • Auto backup of settings and running totals. • Sine wave (coil). • Operational temperature -40°C up to +80°C • Active pulse signals. (-40°F up to 176°F). • (0)4 - 20mA. • Very compact design for panel mount, wall • 0 - 10V DC. mount or field mount applications. • Rugged aluminum field mount enclosure Applications IP67/NEMA4X. • Flow measurement where re-transmission • Intrinsically Safe - ATEX, IECEx, FM and CSA of the totalizer function is required. approval for gas and dust applications. Alternative basic models: F010 - F011 - F012 • Explosion/flame proof II 2 GD EEx d IIB T5. - F013 or more advanced F016, F110 and • LED backlight option. higher. DATASHEETTOTALIZER INDICATOR / RATE F014 - FLOW • Loop or battery powered, 8 - 24V AC/DC or 115 - 230V AC power supply. • Sensor supply 3.2 / 8.2 / 12 / 24V DC.

1 General information Signal input Introduction The F014 accepts most pulse and analog input The F014 is a local indicator to display the actual signals for volumetric flow or mass flow flow rate, total and accumulated total. The total measurement. The input signal type can be can be reset to zero by pressing the CLEAR selected by the user in the configuration menu button twice. The eleven digit accumulated total without having to adjust any sensitive however can not be reset to zero. Related to the mechanical dip-switches, jumpers or trimmers. acculmulated total, a scaled pulse is generated The analog input version is even available as for re-transmitting the count on the display. 4 - 20mA input loop powered display. A wide selection of options further enhances the capabilities of this model. Power supply Several power supply options are available to Display power the F014 and sensor. Most popular is our The display has large 17mm segments which battery powered version with a long life lithium can be set to show total or flow rate. On-screen battery which will last up to five years. engineering units are easily configured from a For analog sensors, a 4 - 20mA loop powered comprehensive menu, whilst different units for version is available as well. A real sensor supply flow rate and total can be displayed is offered with the 24V AC/DC or 115 - 230V AC simultaneously. The accumulated total can register power supply option. up to 11 digits and is backed-up in EEPROM memory where it is regularly updated. Hazardous area For hazardous area applications, this model Backlight has been ATEX, IECEx, FM and CSA certified For those applications where readability during Intrinsically Safe for gas and dust day and night is an issue, a bi-color backlight is applications, with an allowed operational available. The background color green or amber temperature of -40°C to +70°C (-40°F to and the intensity can be adjusted from the +158°F). A flame proof enclosure with ATEX keyboard. The display is a transflective type, certification offers the rating II 2 GD EEx which means that a high contrast reading is d IIB T5. guaranteed in full sunlight as well as during the night. This backlight option is also available Enclosures Intrinsically Safe. Various types of enclosures can be selected, all ATEX, IECEx, FM and CSA approved. As Configuration standard the F014 is supplied in an GRP panel All configuration settings are accessed via a mount enclosure. Most popular is our simple operator menu which can be pass-code aluminum field mount enclosure with IP67 / protected. Each setting is clearly indicated with NEMA 4X rating. Both European or U.S. cable an alphanumerical description, which avoids gland entry threads are available. confusing abbreviations. Once familiar with one F-series product, you will be able to program all Overview application F014 models in the series without a manual. All settings are safely stored in EEPROM memory in Pulse output the event of sudden power failure.

Pulse output The scaleable pulse output reflects the count on the accumulated display. The pulse length is Flowmeter user defined from 0.001 second up to 10 seconds. input The maximum output frequency is 500Hz. The output signal can be a passive NPN, active PNP or an isolated electro-mechanical relay.

2 F014 Dimensions enclosures Terminal connections power supply Aluminum & GRP panel mount enclosure PB/PC - PD - PL - PX

FLOWMETER INPUT POWER SUPPLY PULSE OUTPUT BACKLIGHT 31 mm 29 mm (1.22") (1.14") 130 mm (5.12")

115 (4.53") 1 2 3 456 78 9 10

P: coil PD: 16 - 30V DC OT: passive trans. ZB: 20 - 30V DC + + + + 120 mm (4.72") 98 (3.86")

P: reed switch / NPN Sensor supply: For pulse input + (type P): 8.2V DC HB & HC enclosures panel cut-out P: active signal + Aluminum & GRP field / wall mount enclosures P: PNP

130 mm (5.12") Ø 7mm (0.27") Ø 7mm (0.27") - +

P: namur -

A: (0)4 - 20mA For analog input (type A): voltage as 120 mm (4.72") I+ connected to terminal 5. 60 mm (2.36") U: 0 - 10V For analog input 75 mm (2.95") 112 mm (4.40") (type U): voltage as U+ connected to terminal 5.

Aluminum GRP A - PL: 4 - 20mA PL: input loop powered. 30mm 30mm I+

22,50 mm HD PX: 8 - 30V DC

PG9 M20 x 1,5 PG9 +

30mm 30mm 30mm 30mm PB / PC: battery powered (PX is also available: if an external supply is connected, the battery supply will be switched off / on automatically.) 22,50 mm 22,50 mm HM HE

M16 x 1,5 M20 x 1,5 M16 x 1,5 Ø16Ø20 Ø16 Terminal connections power supply PF - PM

22,50 mm HN HF 22,50 mm ( 0.9")

7 M20 x 1,5 Ø22 ( /8")

25mm 25mm 25mm 25mm POWER SUPPLY PULSE OUTPUT FLOWMETER INPUT 22,50 mm 22,50 mm HO HG

M20 x 1,5 M20 x 1,5 Ø20 Ø20 GND 1 2 34 5 6 7

12mm 12mm 12mm 12mm PF: 24V AC OA: active 24V DC P: coil + 17 mm 17 mm HP HH

14 mm 14 mm PF: 24V DC OT: passive trans. P: reed switch / NPN 24mm 24mm 6 x M12 24mm 24mm Ø12 36mm 36mm 36mm 36mm - + + + 30mm (1.18") 30mm (1.18") PM: 115 - 230V AC OR: mech. relay P: PNP 0.9" HT HJ = = - + 22,50 mm ( 0.9")

1 7 7 7 P: namur /2"NPT Ø22 ( /8") Ø22 ( /8") Ø22 ( /8")

1.18" 1.18" - +

P: active signal 0.9" HU HK +

1 1 /2"NPT 1/2"NPT /2"NPT Flat bottom, no holes available. A: (0)4 - 20mA 15mm 15mm + + 15 mm HV U: 0 - 10V 16 mm + + 38mm 4 x M20 x 1.5

HZ

F014 3 Typical wiring diagram F014-P-(OT)-PB-(PX)-(ZB) Typical wiring diagram F014-A-OT-PX-ZB

Type PB: Type PX: TERMINAL CONNECTORS BATTERY POWERED TERMINAL CONNECTORS BASIC 8 - 30V DC POWER SUPPLY F0 - series F0 - series (STANDARD)

Backlight option: type ZB Backlight supply 10 Backlight option: type ZB Backlight supply 10 20 - 30V DC 20 - 30V DC (not used in this example)

Common ground 9 Common ground 9 e.g. counter

Pulse output type OT: 87 87 123456 passive transistor Pulse output type OT: (not used in this example)

Common ground Common ground passive transistor +

Power supply type PX: 5 5 Power supply type PX: Main supply 8 - 30V DC Main supply 8 - 30V DC 8 - 30V DC

(not used in this example) Common ground 4 Common ground 4 -

Supply * 3 Signal Flowmeter input Signal type P:

type of signal pulse type of signal

Circuit depends on Circuit depends on Flowmeter input type A: (0)4 - 20mA Common ground 12 Common ground 12

* Sensor supply voltage for pulse flowmeter type P: * Sensor supply voltage for pulse flowmeter type P: Terminal 3: 1.2 / 3.2V DC. Terminal 3: 1.2 / 3.2V DC.

* Sensor supply voltage for analog flowmeter type A / U: * Sensor supply voltage for analog flowmeter type A / U: Terminal 3: not available. Terminal 3: not available.

Typical wiring diagram F014-A-(OT)-PL-ZB Typical wiring diagram F014-P-OT-PD-ZB

Type PL: Type PD:

TERMINAL CONNECTORS INPUT LOOP POWERED TERMINAL CONNECTORS 16 - 30V DC POWER SUPPLY

F0 - series F0 - series + Backlight option: type ZB 20 - 30V DC

Backlight supply 10 Backlight option: type ZB 20 - 30V DC Backlight supply 10 Common ground 9 - Common ground 9 e.g. counter

Pulse output type OT: 87 87 123456 passive transistor (not used in this example) Pulse output type OT: Common ground Common ground passive transistor

Supply *

6 +

5 Power supply type PD: Main supply 16 - 30V DC

16 - 30V DC Common ground 4 -

Flowmeter input type A - PL: Supply *

Input loop powered 4 - 20mA 3

Signal + Signal Flowmeter input type P:

type of signal type of signal pulse

8 - 30V DC

Circuit depends on Circuit depends on Common ground 12 - Common ground 12

Sensor supply: sensor is externally powered. * Sensor supply voltage for pulse flowmeter type P: Terminal 3: 1.2 / 3.2V DC. Terminal 6 with type PD: 8.2V DC.

* Sensor supply voltage for analog flowmeter type A / U: Terminal 3: not available. Terminal 6 with type PD: voltage as connected to terminal 5 (internally linked).

4 F014 Typical wiring diagram F014-P-OA-PF-ZB Typical wiring diagram F014-A-OT-PF-ZB

Type PF: Type PF: TERMINAL CONNECTORS 24V AC / DC POWER SUPPLY TERMINAL CONNECTORS 24V AC / DC POWER SUPPLY F0 - series F0 - series

Backlight option: type ZB Backlight option: type ZB Internally powered. Internally powered.

Supply * Supply *

7 7 Flowmeter input type A: Signal Flowmeter input Signal (0)4 - 20mA type P:

type of signal pulse type of signal Circuit depends on Circuit depends on

Common ground 56 Common ground 56

e.g. counter + Pulse output type OT:

43

123456 Pulse output type OA: 87 123456 passive transistor - e.g. counter active 24V DC pulse Common ground

2 2 Main supply 24V AC Main supply + 1 1 Power supply type PF: Power supply type PF: 24V DC

8 - 24V AC / DC 8 - 24V AC / DC Common ground 0 Earth Common ground 0 -

* Sensor supply voltage for pulse flowmeter type P: * Sensor supply voltage for pulse flowmeter type P: Terminal 7: 1.2 / 3.2 / 8.2 / 12 / 24V DC. Terminal 7: 1.2 / 3.2 / 8.2 / 12 / 24V DC.

* Sensor supply voltage for analog flowmeter type A / U: * Sensor supply voltage for analog flowmeter type A / U: Terminal 7: 8.2 / 12 / 24V DC. Terminal 7: 8.2 / 12 / 24V DC.

Typical wiring diagram F014-A-OA-PM-ZB Typical wiring diagram F014-P-OR-PM-ZB

Type PM: Type PM: TERMINAL CONNECTORS 115 - 230V AC POWER SUPPLY TERMINAL CONNECTORS 115 - 230V AC POWER SUPPLY F0 - series F0 - series

Backlight option: type ZB Backlight option: type ZB Internally powered. Internally powered.

Supply * Supply *

7 Flowmeter input type A: 7 Signal (0)4 - 20mA Signal Flowmeter input type P:

type of signal type of signal pulse Circuit depends on Circuit depends on

Common ground 56 Common ground 56 +

43

123456 4 123456 - e.g. counter Pulse output type OA: e.g. counter Pulse output type OR: active 24V DC pulse mechanic relay 3

L1 L1 2 2 Main supply Power supply type PM: Main supply Power supply type PM: 115 - 230V AC 115 - 230V AC N N 1 1

Common ground 0 Common ground 0 Earth Earth

* Sensor supply voltage for pulse flowmeter type P: * Sensor supply voltage for pulse flowmeter type P: Terminal 7: 1.2 / 3.2 / 8.2 / 12 / 24V DC. Terminal 7: 1.2 / 3.2 / 8.2 / 12 / 24V DC.

* Sensor supply voltage for analog flowmeter type A / U: * Sensor supply voltage for analog flowmeter type A / U: Terminal 7: 8.2 / 12 / 24V DC. Terminal 7: 8.2 / 12 / 24V DC.

F014 5 Hazardous area applications Configuration example IIA - IIB and IIC The F014-XI has been certified according F014-P-(OT)-PC-(PX)-XI-(ZB) - Battery powered unit ATEX and IECEx by KEMA and according CSA c-us and FM for use in Intrinsically Safe applications with an ambient temperature of -40°C to +70°C (-40°F to +158°F). • The ATEX markings for gas and dust applications are: II 1 G Ex ia IIC T4 II 1 D Ex iaD 20 IP 65/67 T 100 ¡ C. • The IECEx markings for gas and dust applications are: Ex ia IIC T4 and Ex iaD 20 IP 65/67 T100 ¡ C. • The CSA c-us markings are: Class I/II/III, Division 1, Groups A, B, C, D, E, F, G, Temperature class T4 and Class I, Zone 0, AEx ia IIC T4. • The FM markings are: Class I/II/III, HAZARDOUS AREA SAFE AREA Division 1, Groups A, B, C, D, E, F, G, TERMINAL CONNECTORS Temperature class T4 and Class I, Zone 0, F0 - series AEx ia IIC T4. Supply backlight Backlight option: type ZB 10 It is allowed to connect up to three I.S. power (not used in this example). supplies to power the unit, sensor and back- Common ground 9 light. Consult the certificate for the maximum Pulse output type OT: 8 input and output values of the circuits. The passive transistor (not used in this example).

F014-PD-XI offers a 8.2V DC sensor supply to Common ground 7 power e.g. a Namur sensor or the input voltage to power an analog sensor. An ATEX Basic power supply type PX: approved flame proof enclosure with rating 8 - 30V DC Main supply 5 (not used in this example). II 2 GD EEx d IIB T5 is available as well.

Please contact your supplier for further Common ground 4 details.

Certificate of conformity KEMA 05ATEX1168 X Supply * 3 I.S. flowmeter input type: P • IECEx KEM 08.0006X • CSA.08.2059461 X Signal type of signal pulse Circuit depends on

Common ground 12

* Sensor supply voltage for pulse flowmeter type P : Terminal 3: 1.2 / 3.2V DC. Please note: type PX may be used in combination with the battery (type PC). PX will power the unit; the battery will be disabled automatically till power is disconnected.

6 F014 Configuration example IIA - IIB and IIC - F014-P-OT-PX-XI-(ZB) - Basic power supply 8 - 30V DC

HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F0 - series

Supply backlight Backlight option: type ZB 10 (not used in this example).

Common ground 9 Intrinsically Safe apparatus + Power supply or Uo = max. 30V switch interface 8 123456

Io = max. 200mA For example 123456 - Po = max. 1,2W MTL 5525

Common ground 7 Pulse output type OT: passive transistor MTL 5511 e.g. counter + Uo = max. 30V Power supply

Main supply 5 Power supply type PX: 8 - 30V DC Io = max. 200mA

For example - Po = max. 1,2W MTL 5525 Common ground 4

Supply * 3 I.S. flowmeter input type: P Signal type of signal pulse Circuit depends on

Common ground 12 Note: above values are safety values. Consult the technical specification for operational values. * Sensor supply voltage for pulse type P: Terminal 3: 1.2V / 3.2V DC. Please note: type PX may be used in combination with the battery (type PC). PX will power the unit; the battery will be disabled automatically till power is disconnected.

Configuration example IIA - IIB and IIC - F014-P-OT-PX-XI-ZB - Basic power supply 8 - 30V DC

HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS

F0 - series + Uo = max. 30V Power supply Supply backlight 10 Io = max. 200mA

Backlight option: type ZB For example

- Po = max. 0,75W MTL 5525

Common ground 9 Intrinsically Safe apparatus + Power supply or Uo = max. 30V switch interface 8 123456

Io = max. 200mA For example 123456 - Po = max. 1,2W MTL 5525

Common ground 7 Pulse output type OT: passive transistor MTL 5511 e.g. counter + Uo = max. 30V Power supply

Main supply 5 Power supply type PX: 8 - 30V DC Io = max. 200mA

For example - Po = max. 1,2W MTL 5525 Common ground 4

Supply * 3 + Uo = max. 30V Power supply I.S. flowmeter Signal type of signal input type: P Io = max. 150mA

For example Circuit depends on pulse - Po = max. 0,92W MTL 5525

Common ground 12 Note: above values are safety values. Consult the technical specification for operational values. * Sensor supply voltage for pulse type P: Terminal 3: 1.2V / 3.2V DC. Please note: type PX may be used in combination with the battery (type PC). PX will power the unit; the battery will be disabled automatically till power is disconnected.

F014 7 Configuration example IIA - IIB and IIC - F014-P-OT-PD-XI-ZB - Power supply 16 - 30V DC

HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS

F0 - series + Uo = max. 30V Power supply Supply backlight 10 Io = max. 200mA

Backlight option: type ZB For example

- Po = max. 0,75W MTL 5525

Common ground 9 Intrinsically Safe apparatus + Power supply or Uo = max. 30V switch interface 8 123456

Io = max. 200mA For example 123456 - Po = max. 1,2W MTL 5525 Common ground 7 Pulse output type OT: passive transistor MTL 5511 e.g. counter

Supply * 6 + Uo = max. 30V Power supply

Main supply 5 Power supply type PD: 16 - 30V DC Io = max. 200mA

For example - Po = max. 1,2W MTL 5525 Common ground 4

Supply * 3 I.S. flowmeter input type: P Signal type of signal pulse Circuit depends on

Common ground 12 Note: above values are safety values. Consult the technical specification for operational values. * Sensor supply voltage for pulse type P: Terminal 3: 1.2V / 3.2V DC. Terminal 6: 8.2V DC. Please note: type PD may be used in combination with the battery (type PC). PD will power the unit; the battery will be disabled automatically till power is disconnected.

Configuration example IIA - IIB and IIC - F014-A-OT-PD-XI-ZB - Power supply 16 - 30V DC

HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS

F0 - series + Uo = max. 30V Power supply Supply backlight 10 Io = max. 200mA

Backlight option: type ZB For example

- Po = max. 0,75W MTL 5525

Common ground 9 Intrinsically Safe apparatus + Power supply or Uo = max. 30V switch interface 8 123456

Io = max. 200mA For example 123456 - Po = max. 1,2W MTL 5525 Common ground 7 Pulse output type OT: passive transistor MTL 5511 e.g. counter

Supply * 6 + Uo = max. 30V Power supply

Main supply 5 Power supply type PD: 16 - 30V DC Io = max. 200mA

For example - Po = max. 1,2W MTL 5525 Common ground 4

I.S. flowmeter input - type A: (0)4 - 20mA

Signal type of signal Circuit depends on

Common ground 12 Note: above values are safety values. Consult the technical specification for operational values. * Sensor supply voltage for analog flowmeter type A / U: Terminal 6: as input voltage terminal 5 (internally linked). Please note: type PD may be used in combination with the battery (type PC). PD will power the unit; the battery will be disabled automatically till power is disconnected.

8 F014 Configuration example IIA - IIB and IIC - F014-A-OT-PL-XI-ZB - Input loop powered

HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS

F0 - series + Uo = max. 30V Power supply Supply backlight 10 Io = max. 200mA

Backlight option: type ZB For example

- Po = max. 0,75W MTL 5525

Common ground 9 Intrinsically Safe apparatus + Power supply or Uo = max. 30 V switch interface 8 123456

Io = max. 200 For example 123456 - Po = max. 1,2 W MTL 5525

Common ground 7 Pulse output type OT: passive transistor MTL 5511 e.g. counter I.S. flowmeter input - type A-PL: 4-20mA input loop powered. + Uo = max. 30V Power supply Signal type of signal Io = max. 93mA

For example Circuit depends on - Po = max. 0,92W MTL 5525

Common ground 12 Note: above values are safety values. Consult the technical specification for operational values. Sensor supply is not available: unit is input loop powered (type PL). Please note: type PL may be used in combination with the battery (type PC). PL will power the unit; the battery will be disabled automatically till power is disconnected.

Configuration example IIA - IIB and IIC - F014-A-OT-PX-XI-ZB - Basic power supply 8 - 30V DC

HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS

F0 - series + Uo = max. 30V Power supply Supply backlight 10 Io = max. 200mA

Backlight option: type ZB For example

- Po = max. 0,75W MTL 5525

Common ground 9 Intrinsically Safe apparatus + Power supply or Uo = max. 30V switch interface 8 123456

Io = max. 20