************************************************************************** USACE / NAVFAC / AFCEC / NASA UFGS-33 52 43.12 (August 2018)

------Preparing Activity: USACE Superseding UFGS-33 52 43.12 (February 2010)

UNIFIED FACILITIES GUIDE SPECIFICATIONS

References are in agreement with UMRL dated July 2021 **************************************************************************

SECTION TABLE OF CONTENTS

DIVISION 33 - UTILITIES

SECTION 33 52 43.12

AVIATION FUEL PANTOGRAPHS

08/18

PART 1 GENERAL

1.1 REFERENCES 1.2 ADMINISTRATIVE REQUIREMENTS 1.3 SUBMITTALS 1.4 QUALITY ASSURANCE 1.4.1 Design Conditions

PART 2 PRODUCTS

2.1 MATERIALS 2.1.1 Piping 2.1.2 Fitting and Bends 2.1.3 Components 2.1.4 2.2 EQUIPMENT AND MATERIAL 2.2.1 Detachable Aircraft Pantograph 2.2.2 High Reach Pantographs 2.2.3 Permanent Pantograph Fabrication - [Hoseless][Hose End] Type 2.2.4 Truck Fill Stand Pantograph Fabrication - (Non-Recessable) 2.2.5 Truck Fill Stand Pantograph Fabrication (Recessable) 2.2.6 Flanged Swivel Joints 2.2.7 Flow Meter 2.2.8 Emergency Dry Breakaway Coupler (EDBC) 2.2.9 Sampling Connection 2.2.10 Pressure gage assembly 2.2.11 Drain and Vent Assemblies 2.2.12 Hydrant Coupler 2.2.13 Shut-Off Valve 2.2.14 Dry Break Quick Disconnect 2.2.15 Pressure Fueling Nozzle 2.2.16 Aviation Fuel Hose 2.2.17 Venturi 2.2.18 Pantograph Control Valve

SECTION 33 52 43.12 Page 1 2.2.19 Fuel Separator 2.2.20 Additive Injector 2.2.21 Nitrogen Powered Deadman Control System

PART 3 EXECUTION

3.1 ASSEMBLY 3.2 TESTING

-- End of Section Table of Contents --

SECTION 33 52 43.12 Page 2 ************************************************************************** USACE / NAVFAC / AFCEC / NASA UFGS-33 52 43.12 (August 2018)

------Preparing Activity: USACE Superseding UFGS-33 52 43.12 (February 2010)

UNIFIED FACILITIES GUIDE SPECIFICATIONS

References are in agreement with UMRL dated July 2021 **************************************************************************

SECTION 33 52 43.12

AVIATION FUEL PANTOGRAPHS 08/18

************************************************************************** NOTE: This guide specification covers the requirements for Pantographs used in aircraft refueling systems or at truck fill stands constructed to the requirements of the DoD Type III/IV/V, and Cut and Cover Hydrant Refueling System Standards.

Adhere to UFC 1-300-02 Unified Facilities Guide Specifications (UFGS) Format Standard when editing this guide specification or preparing new project specification sections. Edit this guide specification for project specific requirements by adding, deleting, or revising text. For bracketed items, choose applicable item(s) or insert appropriate information.

Remove information and requirements not required in respective project, whether or not brackets are present.

Comments, suggestions and recommended changes for this guide specification are welcome and should be submitted as a Criteria Change Request (CCR). **************************************************************************

PART 1 GENERAL

************************************************************************** NOTE: DoD Type III systems must conform to Standard Design AW 078-24-28 PRESSURIZED HYDRANT FUELING SYSTEM TYPE III. DoD Type IV/V systems must conform to Standard Design AW 078-24-29 PRESSURIZED HYDRANT DIRECT FUELING SYSTEM TYPE IV/V. Cut and Cover systems must conform to Standard Design AW 078-24-33 UNDERGROUND VERTICAL STORAGE TANKS CUT AND COVER. Field fabricated ASTs must conform to AW 078-24-27 ABOVEGROUND VERTICAL STEEL TANKS WITH FIXED ROOFS.Standards can be found on the Whole Building

SECTION 33 52 43.12 Page 3 Design Guide at the following location https://www.wbdg.org/ffc/dod/non-cos-standards.

Subject Matter Expert (SME) is defined as Service Headquarters Subject Matter Experts: Air Force - The Air Force Fuels Facilities S