Technical Data TD027002EN Effective March 2014 Modular integrated transportable substation (MITS)

Contents Description Page Voltage regulation with bypassing ...... 2 Mobile MITS application ...... 3 Natural gas extraction ...... 4 Utility substation ...... 5 Portable power application ...... 6 Small substation ...... 7 Residential area substation ...... 8 Lightning damaged substation ...... 9 Rural substation ...... 10 Technical Data TD027002EN Modular integrated (Effective March 2014 transportable substation (MITS

Voltage regulation with bypassing

10 kVA Station Service Transformer W/VFI HV: 34,500V Delta LV: 120/240V FR3 Fluid Filled

34.5 kV Fused 34.5 kV Disconnect Switch Bypass Switch S Regulators (3) Value proposition 345 kVA 34.5 kV, 100A, Single-point contact for project management, plug-and-play FR3 Fluid Filled installation, on-board fluid containment, and resolved voltage L regulation with an aesthetically pleasing design. A waste water treatment facility in the northeast United States found that poor voltage regulation was a significant problem for their equipment. The facility decided to remedy the situation with a voltage regulation MITS, resulting in fewer equipment issues and improved reliability. 34.5 kV Fused Disconnect Switch

Figure 1. System Schematic

8'-11.8"

43'-11.4" 34.5 kV Fused 34.5 kV Fused Disconnect Switch Disconnect Switch and 34.5 kV Bypass Switch Voltage Regulator 34.5 kV, 100A 10 kVA Control Power Transformer FR3 Fluid Volume = 470 Gals. FR3 Fluid Volume = 173 Gals. 34.5 kV, 240/120V

10'-1.0"

4-Inch Containment Wall Above Deck (Typical All Around)

Figure 2. System Layout and Dimensions

2 eaton www.eaton.com Modular integrated Technical Data TD027002EN transportable substation (MITS) Effective March 2014  Mobile MITS application

480V Junction Box for Generator Cable Connection

5 kV Cables on Trailer

Transformer 2400/4160Y/2400–480V Step Up Application 2500 kVA, Value proposition FR3 Fluid, 65°C Improved reaction time in emergency situations, completely mobile, integrated connection interface, and simple design. This application involves a dedicated mobile application for the customer. Fueled by the need to respond and react to potential emergency situations, this mobile MITS provides the customer the ability to transform voltage. Used in conjunction with a mobile genset, voltage is generated at 480V and stepped up to a voltage of either 4160Y/2400 or 2400V delta to supply power on an emergency basis.

Figure 3. System Schematic

5 kV, 350 kcmil Jacketed Cable, 100 Ft Steel Diamond Plate Deck

8'-6"

Spare Tire/Cover, 12" Galvanized Steel Cable 480V 7–500 kcmil Near and Far Side with Turnbuckle Metal-Clad Armor Cables

480V NEMA 4 Ground Cable Junction Box Storage Box Rails, Side 2500 kVA with Transition and Back 2400/4160Y/2400 Busbars 480V 5.73% IZ

11'-4"

Flip Down/Up Ladder

40'-10.0"

Figure 4. System Layout and Dimensions

eaton www.eaton.com 3 Technical Data TD027002EN Modular integrated (Effective March 2014 transportable substation (MITS  Natural gas extraction Source 1 Source 2 VFI Switchgear—Main Metering 25 kV, 900A CTs

VFI Switchgear #1 VFI Switchgear #2 25 kV, 900A, 25 kV, 900A, Four Feeders Four Feeders

Value proposition Fifty percent savings on future relocation costs, 15 percent savings over conventional design, 25 percent savings in space, and increase in cash flow due to a quickly commissioned substation. Primary Metering Primary Metering Compartment Compartment Configured for supplying electrical loads for sites that extract ground 14,400–120V VTs 14,400–120V VTs water embedded with natural gas, this MITS application is a different way of building substations for the mining industry. Using a skid- based platform, the MITS reduces the footprint and can provide a cost savings over a typical installation. Eaton’s modular substation is 50 kVA Station Service Transformer designed to be relocated to a new site after its service is completed HV: 14,440GY at the existing site. The ability to move the entire substation without LV: 240/120V complete disassembly can provide customers with substantial benefits over conventional substation installations. Figure 5. System Schematic Viewing loads and status of equipment in harsh, remote environments often requires a long drive across difficult terrain. Eaton provides RTU cabinets populated with IEDs and SCADA equipment to meet most specifications. This contributes to cost and time savings for maintaining valuable equipment.

Distribution Panel

8'-6.0"

38'-0"

Relay Cabinet Specified Metering and SCADA Equipment Feeder Protection Relays 25 kV Padmounted Switchgear Voltage Transformer 50 kVA Station Service Transformer

7'-3"

Feeder Switchgear #2 Main Switchgear Feeder Switchgear #1

1'-9"

Figure 6. System Layout and Dimensions

4 eaton www.eaton.com Modular integrated Technical Data TD027002EN transportable substation (MITS) Effective March 2014  Utility substation

Regulator and Recloser Bypass 15 kV Model 10T Substation RVAC Switchgear Transformer 2 Source / 2 Taps 9375/10,500– with Tie Switch 12,468/13,965 kVA Visible Break on HV: 22.9 kV Delta All Sources and Taps LV: 13.8Y/7.97 kV 55/65°C, ONAN/ONAF

Regulators (3) S 500 kVA 7620V, 656A (Operated at 7970V) L

Value proposition Modular design can be used at many locations, is completely integrated, provides on-board spill containment, and is transportable. 15 kV Recloser (1) Three-Phase NOVA Driven by the need to cut the cost of installed substations and to (Solid Dielectric) 15 kVA Station create a modular design concept, this customer turned to Eaton’s Tamper-Resistant Service MITS solution. The conventional substation consisted of overhead Outdoor Enclosure Transformer distribution, transformation, and feeder protection. In addition, each HV: 13,800GY LV: 120/240V substation required the site to be prepared for oil containment in the event of a leak. In this example, Eaton provided solutions to the customer’s requirements and allowed the use of this modular solution at several sites throughout the electrical grid. Figure 7. System Schematic

15 kVA Locking Pump 120/240V Distribution Panel Station Access for Oil Weep Holes Weep Holes, Typ. Service Removal Located Directly Transformer Access Hatch Under Fins Access Hatch Radiators

Locking Pump 8'-6.0" Access for Oil Removal 13'-1.3" LV HV Cabinet Cabinet 34'-5.9"

Control Box

15'-1.5" Recloser Substation Transformer Regulators 15 kV, 600A 9375 kVA Switchgear 656A, 7.97 kV Tamper-Resistant HV: 22.9 kV Delta 15 kV, 600A CL-6A Controls Enclosure LV: 13.8Y/7.97 kV RVAC Model 10T

10'-11.0" 7'-8.4"

Figure 8. System Layout and Dimensions

eaton www.eaton.com 5 Technical Data TD027002EN Modular integrated (Effective March 2014 transportable substation (MITS  Portable power application Metal-Enclosed Switchgear (3) 5 kV; 1200A Fused Load Interrupter Switches Metal-Clad Switchgear (1) 5 kV, 1200A Drawout Breaker

52

Substation Transformer 5000/6250 kVA HV: 11.0Y/6.35 kV LV: 3.6 kV 55/65°C, KNAN/KNAF

Metal-Clad Switchgear (5) 15 kV, 1200A Drawout Breakers Value proposition 52 Quick delivery, fully integrated, transportable, and a single point of contact for project management. Furnished for the U.S. government, this MITS skid provides quick 52 and reliable portable power for emergency applications. The need 52 for this project was to step up voltage supplied by generators from Notes: 3.6 kV to 11 kV. The application has a variety of self-protecting 1. All Breakers 52 features, and is quick to install and commission. Controlled by: Feeder Protection Relays 52 2. Differential Protection Scheme for Transformer: 52 Relay

Figure 9. System Schematic

H0 H1 X1 8'-2.8" X2 H2 X3 H3

37'-11.4" Substation Transformer 5000/6250 kVA 15 kV Class 5 kV Class Horn HV: 11,000Y/6350V Switchgear Lineup Switchgear Lineup LV: 3600V Delta

73000 Lbs

10'-1.9"

Figure 10. System Layout and Dimensions

6 eaton www.eaton.com Modular integrated Technical Data TD027002EN transportable substation (MITS) Effective March 2014  Small substation

Transformer 5000 kVA DIFF. Protection Relay HV: 34.5Y/19.9 kV 87 LV: 13.2Y/7.62 kV 55°C, ONAN

Primary Metering Compartment PTs and CTs

Recloser (1) 35 kV, 200A Value proposition Three-Phase NOVA (Solid Dielectric) Substantial saving over conventional substation design, 25 to Tamper-Resistant Outdoor Enclosure 30 percent savings in project management, and over 60 percent smaller footprint than conventional substation design. Installed in the western part of the U.S., this application combines two MITS skids that will provide dual functionality. Initially, the skids will step up voltage from 13.2 kV to 34.5 kV, and distribute 15 kVA Station Service Transformer 48 Vdc Battery System voltage onto the transmission lines. At some point in the future, with AC Charger the customer plans to use these skids in the reverse fashion and HV: 34.5GY/19.9 kV step 34.5 kV down to 13.2 kV. Included with each skid is an Eaton LV: 120/240V differential protection relay used to trip the NOVA recloser and an upstream device.

Figure 11. System Schematic

48 Vdc Battery System

8'-6.0"

15 kVA Station Service Transformer 30' Transformer Control Cabinet with Relay Transformer Recloser 5000 kVA 35 kV Three-Phase NOVA Mounted in HV: 34.5Y/19.9 kV Primary Tamper-Resistant Enclosure LV: 13.2Y/7.62 kV Metering Cabinet

8'-6.3"

Figure 12. System Layout and Dimensions

eaton www.eaton.com 7 Technical Data TD027002EN Modular integrated (Effective March 2014 transportable substation (MITS  Residential area substation

13 kV Recloser

25 kVA Transformer Station Service Transformer HV: 13,200GY/7620 LV: 240/120 S Regulators (3) 250 kVA 7620V, 328A

L Value proposition Significantly smaller footprint than conventional substation design, safe and secure design requires no fencing, and one point of contact for entire substation. The heavily wooded terrain of a 13.2 kV to 4 kV metro area provided challenges to the utility that served local estate homes. Unit substations serving the area were several decades old, 4 kV Recloser had become heavily loaded, and lacked needed and overlooked maintenance. A new Eaton MITS was the best option.

Figure 13. System Schematic

Metering Enclosure 3.75 MVA Transformer

Distribution Panel 8'-6"

6" Typ. 40' 15 kVA Station Service Transformer

13 kV Recloser 4 kV Recloser 250 kVA Regulators (3)

8'-6.5"

18.5

Figure 14. System Layout and Dimensions

8 eaton www.eaton.com Modular integrated Technical Data TD027002EN transportable substation (MITS) Effective March 2014  Lightning damaged substation

VFI

Transformer 34,500–12,470Y/7200V 5000 kVA, ONAN 65ºC

SA Regulators (3) 250 kVA SB S 7620V, 328A LB L

LA CL-6 Value proposition Twenty-five percent savings on installed cost, and rapid and efficient H1A/H1B installation and recovery time. Sectionalizing 15 kVA Cabinet This design offers the perfect solution for a customer needing to Station Service replace a 5 MVA storm-damaged substation…fast. Eaton mounted Transformer and pre-wired a 5 MVA transformer, three pad-mounted regulators, Single-Phase a station service transformer, switchgear, and controls on a single HV: 7620GY LV: 240/120V structural steel platform. The customer pre-installed the ground 15 kV Reclosers (3) grid, the MITS foundation, the incoming circuits, and the outgoing circuits. Total field install time of the MITS assembly was less than four hours. Power to a town and surrounding community was restored in record time, and at a total installed cost 25 percent below conventional methods. Figure 15. System Schematic

Sectionalizing Cabinet 15 kVA Service Station Transformer Control Service Enclosure

8'-6"

40'-0"

250 kVA Regulators 15 kV Reclosers 5 MVA Transformer

9'-7.5"

Figure 16. System Layout and Dimensions

eaton www.eaton.com 9 Technical Data TD027002EN Modular integrated (Effective March 2014 transportable substation (MITS  Rural substation

Skid 1

15 kV Recloser

Auto-Transformer 10 MVA HV: 24,940Y/14,400V LV: 13,800Y/7960V

Type PWVE Type RVAC-13A 250 kVA 25 kV Reclosers (2) 25 kV Switchgear Regulators (3)

S SA

LA LB T1 VB2 SW2 SW1 VB1 SB L S

T2 Value proposition VB3 SW3 Quick implementation with minimal disruption to the customer and H1A/H1B

the existing landscape. 25 kVA Station Service A substation was needed to serve a remote industrial load. Because Transformer HV: 24,940Y/14,400V of the unique transformer design, it was acquired through a third LV: 240/120V

party and installed on a separate structural steel platform along with Skid 2 a high-side recloser, which serves as a switch and protection device. To achieve cooling requirements, fans were required on the transformer. (The external transformer cooling fans no longer make Figure 17. System Schematic the assembly tamper-proof; therefore, fencing is required.) A second structural steel platform was used to pre-install and test three single- phase, pad-mounted voltage regulators, switchgear, a control center, and a station service transformer. The platforms were interconnected at the job site and the completed assembly, as an integrated whole, did not affect the integrity of this finished product. Surface grading to level the area would have been required for a concrete foundation. Instead of the concrete foundation, steel pillars were installed at weight-bearing points under the entire MITS assembly to elevate the structure from ground level.

Type PWVE 25 kV Reclosers (2)

8'-6"

37'-0" 25'-0"

25 kVA Station Service Transformer HV: 24,940Y/14,400V LV: 240/120V

Control Service Enclosure 250 kVA Regulators (3) PWE RVAC 13A Recloser 25 kV Switchgear 10'-3"

11'-9.5"

Skid 2 Skid 1

Figure 18. System Layout and Dimensions

10 eaton www.eaton.com Modular integrated Technical Data TD027002EN transportable substation (MITS) Effective March 2014 

eaton www.eaton.com 11 Technical Data TD027002EN Modular integrated (Effective March 2014 transportable substation (MITS 