<<

BUILDING DEPARTMENT 108 Eighth Street, Suite 401, Glenwood Springs, CO 81601 Tel: (970) 945-8212

Fire Separation Requirements at Two-Family Dwellings Including ADUs located within the same structure as Primary Dwelling August 2019

A Secondary or Accessory Dwelling Unit (ADU) located within the same structure as a primary dwelling unit invokes certain provisions that require proper detailing of assemblies on the part of the designer, as well as proper execution at the job site by the builder.

Building Code requirements for “two-family dwellings” include -rated construction assemblies at walls, floors and/or roofs, as well as penetrations occurring in these fire-resistant building elements. Fire separation requirements of two family dwellings are described in detail in Sections R302.3–R302.4 of the 2015 International Residential Code. For more detailed information, refer to the attached requirements as excerpted from I.R.C. Code & Commentary – Volume 1.

Garfield County residential projects with two or more dwelling units in the same structure require a Colorado licensed Architect to wet-seal drawings submitted for building permit. The Architect shall specifically address key fire resistance provisions of the Building Code (as referenced above), and the Architect must wet seal/stamp the drawings submitted along with the building permit application.

Drawings prepared by the Architect and submitted to the Building Department for permit shall include the following:

1. For All Projects – Clearly identify location and extent of all fire-rated assemblies between adjacent dwelling units – as shown on floor plans, building sections, details – and including the following requirements: a. Construction assemblies of both vertical and/or horizontal separations are required to meet a one-hour fire-resistance rating (*Note: Fire sprinklers reduce fire-rating to 30 minutes). b. Floor/ceiling and wall assemblies shall extend to and be tight against exterior walls. Wall assemblies shall extend from foundation up to underside of roof sheathing. c. Where floor assemblies are required to be fire-resistance rated, supporting construction (walls, beams, posts) shall have an equal or greater fire-resistance rating. d. Penetrations (including electrical, recessed lights & mechanical ductwork) located within fire-rated assemblies shall comply with specific requirements.

2. For New Construction Projects – Show detailed drawings or otherwise describe wall, floor, ceiling, and roof fire-rated assemblies. Reference numbers of approved construction assemblies from nationally recognized agencies (for example, Underwriters’ Laboratories, U.S. Association, etc.) may be submitted, but descriptive specifications and/or illustrations must also be included.

3. For Retrofit/Remodel Projects – In lieu of specific documentation for the original structure, the Building Department may accept installation of (2) layers of 5/8” Type X drywall at one side of wall, floor/ceiling, or roof assemblies to provide the required one-hour fire rating between adjacent dwelling units. The Architect may otherwise provide alternative fire resistance rating for assembly components as per Chapter 7 of the 2015 I.B.C.

Attachments:

. “Two-Family Dwellings – Fire Separation Requirements” as excerpted from 2015 I.R.C. Code/Commentary

Two-Family Dwellíngs: Fire Separation Requirements BUILDING PLANNING

ROOF SLOPE MORETHAN 2:1 PAMPET MUST EXTEND TO NOT LESS THAN THE HEIGHT OFANY PORTION OF THE ROOF WITHIN A DISÏANCE OF 3 FT

ROOF SLOPE OF 2:12 OR LESS 30 tN. MIN

(ADJACENT ROOF NOT sHowN FoR CLARTTY)

For Sl: 1 inch = 25.4 mm, 304.8 mm. Figure R302.2.3 PARPET REQUIREMENTS

R.302.2.4 Stnrctural independence. Each individual town- that will not structurally affect townhouses should a house shall be structurally independent. problem develop in the adjacent dwelling unit. Excep- Exceptions: tion 1 is based on the norm within the industry for foun- dation construction. ln the code, Section R402 lists 1. Foundations supporting exterior walls ot cornmon only wood and concrete within the foundation materi- walls. als section, although Section R404 accepts 2. Structural roof and wall sheathing from each unit foundation walls. ln general, concrete and masonry fastened to the common wall . are the most common types of foundations;wood foun- dations are viewed as unique. Given the performance 3. Nonstructural wall and roof coverings. of both masonry and concrete, and the fact that these 4. Flashing at termination of roof covering over com- foundation systems must sustain loads from both the mon wall. structure and the adjacent soils, it is reasonable to 5. Townhouses separated by a common wali as pro- assume that the foundation will not be the item that vided in Section R302.2,Item 1 or 2. fails in most situatíons. Permitting a common founda- tion also helps solve other problems that would arise if 4. Each townhouse must be structurally independent and the structural independence issue were taken as an capable removed without adja- of being atfecting the absolute. An example where requiring separate foun- cent dwelling unit. This provision is only to applicable dations would probably create more problems or diffi- townhouses, not two-family dwellings. indepen- This culty is in the dampproofing or waterproofing of below- dence is useful not only in the event of a fire in one unit, grade foundation walls. but also during remodeling alteration. The any or lf a wood foundation is used between adjacent units, objective of this structural independence is that a com- what is the level of that may be needed? plete burnout could occur on one side of the wall with- Because concrete and masonry foundations are the out causing the townhouse. collapse of the adjacent norm, it would be easy to forget or overlook protectíng This condition occurs rarely. The provision also helps if the foundation when it is constructed of wood. ln these there is ever a fire or other problem by creating a clear cases, it would seem appropriate to deal with the foun- separation between the units. With separate owner- dation as any other wall, and protect it on any exposed ship and each owner having a different insurance com- side. The level of fire resistance should be equalto that pany, the ability to gain access or get repairs made can of the wall or walls that the foundation supports. be difficult and time consuming. By having clearly sep- arated units, it is much easier to determine who is R302.3 Two-family dwellings. Dwelling units in two-family responsibie and to make any needed repairs. dwellings shall be separated from each other by wall and The code lists five exceptions that waive the struc- floor assemblies having not less than a l-hour fire-resistance tural independence requirement. A quick review of the rating where tested in accordance with ASTM 8119 or UL exceptions shows that they generally deal with items 263. Fire-resistance-rated floor/ceiiing and wall assemblies

2015 INTERNATIoNAL RËSIDENTIAL coDE@ coMMEhITARY 3-47 BUILDING PLANN]NG

shall extend to and be tight against the exterior wo.ll, and wall neighbor in the adjacent dwelling unit. To accomplish assemblies shali extend from the foundation to the underside this protection, the code addresses separation of the roof sheathing. between the units, structural support and any openings or penetrations of the separation. Exceptions: Depending on the layout of the various dwelling l. A fire-resistauce ratiug of 11, hour shall be permitted in units, Sectlon R302.3 requires that the walls and/or buitdings equipped throughout with an automatic floor assemblies that divide one dwelling unit from the sprinkler system installed in accordance with NFPA adjacent unit be at least 1-hour fire-resistance rated. See Commentary Figure R302.3 for examples of the 2. 'Wall assemblies need not extend through øølc spaces separation. The separation rating is to be determined s/u-inch whcrc thc cciling is protected by not less than by either ASTM E119 or UL 263, which is the normal tested (15.9 nmù Dpe X gypsum board, an øfflc drafT stop test used for determining fire resistance. Many constructed as specified in Section R302'12'1 is pro- assemblies are available for use in these locations. con- vided above and along the wall assembly separating The provisions of the section also address the is the dwellingl and the structt¡ral framing supporling tínuity of the separation, so that one dwelling unit t/r-inch the ceiling i.r protected by not less than ( l2'7 completely divided from the other. The horizontal the mm) gypsum board or equivalent. aspect of the separation, which requires that assemblies extend to and be tight agaínst the exterior gs, * of nation's occur wall, is not difficult to comply with. lt is most likely the particularly one- and two-family dwellings. These fires vertical aspect (continuing a wall assembly to the fire accountfor more than 80 percent of all deaths from underside of the roof sheathing) that will require some in residential uses (including hotels, apartments, dor- detailed planning, careful construction and careful mitories, etc.) and about two-thirds of all fire fatalities in inspection for the units to be separated. dwellings any type of building. One- and two-family Exception 1 grants a reduction in the required sepa- percent also account for more than 80 of residential ration for those cases in which the building is equipped property property losses and more than one-half of all with an automatic sprinkler system. ln these cases, a poor is iosées irom fire, Despite this fire record' there rating of 1/, hour is permitled varsus a 1-hour fire-resis- widespread resistance to mandating much in the way tance rating. The sprinkler system must be "installed in of fre protection systems or methods because of our accordance with NFPA 13," and is to be installed society's belief that people's homes are their castles' "throughout" the building. The type of sprinkler system protection This viewpoint has limited the types of that used must meet NFPA 13 and may not be installed to are imposed on these private homes to the installation either NFPA 130 or 13R, even though those two stan- of smoke alarms and the more recent requirement of dards do address certain types of residentíal uses. The provides dwelling unit separation. Section R302.3 a word "throughout' requires thatthe sprinkler system be separation for protection of the occupants of one dwell- installed in all portions of both dwelling units and any ing unit in a two-family dwelling from the actions of their

1.HR FIRE.RESISTANT WALL TO D TO U}{DERSIDE OF ROOF

ATTIC ATTIC

DWELLING DWELLING UNITA UNIT B

DWELLING DWELLING UNITA UNIT B

DWELLING UNITA FLOOFÍCEILING ASSEMBLY WALL t R302.3,1

DWELLING UNIT B

Figure R302.3 DWELLING UNIT SEPARATIONS IN TWO-FAMILY DWELLINGS

3-48 201 5 INTERNATIONAL BESIDENTIAL CODE6 COM¡¡IENTABY BUILDING PLANNING

common spaces. The provisions of NFPA 13 that per- assemblies at penetratíons. lf the penetralion of a mit omitting sprinklers in certain areas, such as small rated assembly is not properly constructed, the assem- concealed spaces, are applicable' Therefore, the pro- bly itself is jeopardized and may not perform as vision requires a complying sprinkler system 'Through- intended. The provisions of this section apply to pene. out" the buildíng (that is, in all areas of the building that trations of fire-resistance-rated walls and fl oor/ceiling must be protected according to the standard), and it assemblies that are a part of the dwelling unit separa- does not accept any partial system, such as one tion in either twô-family dwellings ortownhouses. Pen- installed ín only one dwelling unit or only in the base- etrations of the rated assemblies range from ment level of both units. combustible pipe and tubing to noncombustible wiring Exception 2 addresses separation in the area of the with combustible covering to noncombustible items, attic of two-family dwellings or duplexes. As long as an such as pipe, tube, conduit and ductwork. attic draft stop is prosenl that meets the requirements Each type of penetration requires a specific method in Section R302.12.1, the 1'hourfire separation is per- of protection, which is based on the type ol fire-resis- 5/o-inch mitted to stop at a ceiling constructed of (15'9 tance-rated assembly penetrated and the size and mm)Type X gypsum board. This may be beneficialas, type of the penetrating item. The first step in determin- in many cases, the type of truss or attic rafter and rafter ing the type of penetration protection required is to tie/coliar tie configuration will prohibit continuing con- identiff whether a wall or floorlceiling assembly is struction of the 1-hour separation wall all the way up to being penetrated. The next step is to determine the the roof sheathing. type of penetrating item and whether jt is a membrane or through penetration. Once these factors are known, R302.3.1 Supporting construction.'Where fl oor assemblies then the applicable section must be applied and ihe are required to be fire-¡esistance lated by Secrion R302.3' the applicable method of protection must be decided upon. supporting construction of such assemblies shall have an equal or greater fire-resistance rating. R302.4.1. Through penetrations. Through penetrations of fire-resistance-rated wall or floor assemblies shall comply This provision applies only to walls that support the * with Section R302.4. 1. 1 ot R302.4.L2. fire-¡esistance-rated floor assemblies that form the 'Where separation between dwelling units in a two-family Exception: the penetrating items are steel, ferrous dwelling where the dwelling units are stacked verti- or copper pipes, tubes or conduits, the annular space shall cally. When eiiher all or portions of a dwelling unit sep- be protected as follows: aration are provided by a floor assembly, the code 1. In concrete or masoüy wall or floor assemblies, requires that the structural suppods for the separation concrete, grout or mortar shall be permitted where have a rating equal to or higher than the floor. This is inst¿lled to the full thickness of the wall or floor conceptually similar to the garage separation of Sec- assembly or the thickness required to maintain the tion R302.6. Without the supporting construction beíng fire-resistance rating, provided that both of the fol- protected, a fire on the lower level could lead to an lowing arê complied with: early failure of the dwelling unit separation (see Com- 1.1. The nominal diameter of the penetrating mentary Figure R302.3. 1 ). item is not more than 6 inches (152 mm).

1 .2. The area of the opening through the wall does DWELLING UNIT not exceed 144 square inche.s (92 900 mrn2). SEPARATION 2. The material used to fill the arnular space shall pre- vent the passage offlame and hot gases sufficient to DWELLING UNITA ignite cotton waste where subjected to ASTM 8119 or UL 263 time temperature fire conditions under a positive pressure differential of not less than 0.01 DWELLING inc.h of wâter (3 Pa) at the location of the penetratíon UNIT B for the time period equivalent to the fire-¡esistance rating of the construction penetrated, SUPPORTING REAUIRES EQUAL OR {. This section contains the general requiremenls for FIRE-RESISTANCE RATING through penetrations, which are penetrations that pass through an entíre assembly. A penetration in Figure R302.3.1 through ¡s SUPPORT OF DWELLING UNIT SEPARATION contrast to a membrane penetration, wtrich creates a penetration through only one side of an asssmbly, Membrane penetrations are addressed in R302.4 ftwclling unit rated peletrations. Penetrations r:f fater Section R302.4.2. See Commentary Figure R302.4.1 for an wall or floor-ceiling asse¡übliss required to be fire-resistance illustration of these two types of penetrations. rirtecl in accordance with Scction R302.2 ur R302.3 shall be Through penetrations must be protected to maintain protected in accordance with this section. the fire resistance of the penetrated assembly, The '& This section addresses the specific requirements for code states two methods, found in Sections maintainíng the integrity of fire-resistance-rated R302.4,1.1 and R302.4.1.2, which can be used to

2015 INTERNATIoNAL HES¡DENTTAL coDgo couMENTAHY g-49 BUILDING PLANNING

and penetration protection. Because it assure the adequacy of the penetraiion protec-tion. The tant assèmblies in the actual fire will be differehce betwben ihese two is the test methodology ls verv llkelv that the i¡enetration positiúe pressure, this ssqtlon speclfies used, but they both provìde essentially the same expoéed to a include a positive pressure resulis. The cómmentary for those is addi- thát the test-liie exposure 'seçtions (0.25 mm) of waler column äs a further tional discussion of the differences. of 0.01 inch performance of this protoction Based on the history of these provisions and on the msans to verify the protection will not bs blown out or wealth of daia that exists concerning items method, Thus'the during a fire' such as conduit, water plping and other similar pene- moved from its Place fat¡óns, the coqle prov¡de's two exceptions that permit R302.4.1.1 Flre-resistance-rsted assembly. Penetrations proteotion by meihods olhet thal those. generally shall be instalted as tested in the appraved fire-resistance' iequired. thé firs! permits the useof colcrete, grout or raûed asseurbly, protect penetratiqrs of coñorete and mortar to dertain s This section addresses situations in which the penetra- floor assemblies' cg¡crete, grout mâsonry wall of lhg tisn is tested as a part of the regular full-scala,Test for be applied for the full thickness of the or mortår muÊt the wafl or floor/ceiiing assembly. The ponotration and can be produced demon- assombiy unless evidenee proposed of pr,otee-tion are evaluated as a.part of fire-rssistance rating can be bpe strating if'at t¡re required itrelregutaiÄSTM Ë119 test, which evaluates the wall with a lesdçrdepth. Concrete, grout and mor- achievéo or flooi/ceiling rating. This seetion and the opJion ¡t pr&' been used as protection for the tar hâve traditionally are no[ usedtrequently because of the cost of penelrations of concrete and vìdes ánnular space in' conducting such full-scal€ tests and the limitations has shown this form *ãàãnry aisemþlies.'Experience olaced oñ the application of the tested assembly' However, caution must be Ot-proteu¡on to þe viablå. b"cause of these'ibsues, penÈtrâtion$ arê most often such as awatêr pipe or con- usåd any time something, protecled in accordance with one oT the exceptions in masonry- Sections duit, is'"place-d in concrete ol becüon R3û2.4,'t or the provisions of Section cantain examples of protection Þäooe"s ãno- Þzoos,s R302.4.1.2. of plumbing sYstems. system. Pçnctrations shall Èxceotion ã addresses the space between ihe pen- R.302,4.1,2 Penetration penetrarion firertop system etratins item and the oríginal assembly construction' be protected by an approuerl ace-'otdance with ASTM EBl4 or UL This gãp is catled the annular space,.and this excep- ínstalled as tesie

2015 INTERNATIONAL RESIDENTTAL CODE6 COMMENTARY 3-50 BUILDING PLAI.¡NINGI

is reported as an "F" (flame) rating and a "Ï'(tempera- L.2. By a horizontal distance of not less than the ture) rating. The code requires only an F rating. The F depth of the wall eavity where the wall cav- rating indicates the period of time, in hours, that the ity is filled with cellulose loose-fiIl, rock- through-penetration flrestop system remained in place wool or slag insulation. the passage of fire during the fire expo- without allowing 1.3. tsy solid lireblocking in accordance with sure test, or the passage of water during the hose Spction R302.11. stream portion of the test. The required F rating must be 1.4. protecting equal to the fire-resistance rating of the wall or floor/ceil- By both boxes with lísted ing assembly that is being penetrated. This means pads. either a 1- or 2-hour rating, depending on the dwelling 1.5. By othet listed materials and methods. unit seParation. 2. Membrane penetrations by listed electrical boxes of the most common materials used in through- Two of any materials provided that tåe boxes have been and penetration flrestop systems are tested for use in fire-resistance-rated assemblies and materials. lntumescent malerials expand endothermic are installed in accordaqce with the instructions to 10 times their original volume when approximately I included in the lísting. The annular space between the exceeding 250'F (121"C). 1l, exposed to temperatures wall memb¡ane and the box shall not exceed inch of the materialfills the voids or openings The expansion (3.1 mm) unless /isred otherwise. Such boxes on panetration to resist the passage of flame, within the opposite sides of tle wall shall be separated by one of while the outer layer of the expanded intumescent the following: materialforms an insulating chared layerthatassists ín limiting the transfer of heat. The expansion properties of 2.1. By the horizontal distance specified in the intumescent materials altow them to seal openings left /istln6 ofthe electrical boxes. by combustible penetrating items that burn away durlng 2.2. By solid fireblocking in accordance with a fire, but they do not retard heat as well as endothermic Section R302.11. materials, lntumescent materials are typically used with 2.3. By protecting both boxes with listed putty combustible penetrating items or where a higher T rat- pads, ing is not required. Endothermic materials provide protection through 2.4- By other listed materials and methods. chemically bound water released ín the form of steam 3. The annular space created by the penetralion of a when exposed to temperatures exceeding 600'F fire sprinkler provided that it is covered by a metai (316"C). This released water cools the penetration and escutcheon plate. retards heat transfer th rough the penetration. Endother- .1. This section deals with instances mic materíals tend to be superior in heat-transfer resis- where only a single side of the fire-resistance-rated pene- tance and have higher T ratings, but they do not expand assembly is trated. This would to fill voids left by combustible penetrating items that be the situation for items such as electrical outlet boxes or plumbing on burn away during a fire. Therefore, endothermic mate- fixtures located one side of the wall only. Commentary rials are typically used with noneombustible penetrating Figure R302.4.1 shows this penetration. part, items and where a hígher T rating is required. type of For the most a nrembrane penetration is to be protected by one of the R302.4.2 Membrane penetrations. Membrane penetations previously described methods established for through rffhere shall cornply with Sestion R302.4.1. walls are required penetrations. However, there are some penetrations to have be a fire-resistance rating, recessed fixtures shall that are allowed without a specific firestopping material installed so that fhe required fire-resistance rating will aot be in the annular space around them. These are reduced. addressed by the exceptions. This section also deals Exceptions: with the installalion of recessed luminaires in fire-resis- tance-rated assemblies and states 1. Membrane penetrations of not more than 2-hour fire- that their installation may not r€duce the assembly's protection. resistance-rated walls and partitions by steel electri- Although these fixtures åre common, they do reprosent a pene- cal boxes that do ¡rot exceed 1 6 sqtrare inches (0.0103 tration of the assembly's protection must be mzS in area provitled that the aggregate area of the snd installed so that the assembly is not openings through the membrane does not exceed 100 compromisod. Exception 1 allows penetrations square inches (0.0ú45 m?¡ in any 100 square f'eet of steel olectrical outlet boxes under certaín conditions. The criteria of (9.29 m2) of wall area. The annular space between the this section limitthe síze of wall membrane and the box shall not exçeed llu inch the box to 16 square inches (0.01 03 m2) or less in area and (3.1 mm). Such boxes on opposite sides sl ths wall to an aggregate aroa not to exceed 100 squaro ínches (64 shall be sepamted by rrrre of the fi-rlluwirrg: 500 mm?) in eacì 100 squ€re foot (9.3 mJ area. Commentary Figure 1.1. By a honzontal distance of not less than 24 R302.4.2(U shows some of the requirements of this inches (610 mm) where the wall or partition section. The area limitations are consistent with the cri- is constructed with individual noncommuni- teria from fire tests, which have shown thatwithín these cating stud cavities. limitations, these penetratlons will not adversely affect the fire-resistence rating of lhe assembly. However, the

2015 INTERNATIONAL BESIDENTIAL CODEO COMMENTARY 3,51 SUILDI}¡G PLANNING

boxes are assumed to be installed as they were durlng many differenttypes of nonmetallic boxes are available, used the f¡re tests. ln general, the test requirements match it is importanttodeterminethatthe boxes being i¡ tested' the limitations shown by the code regarding their size the raied dwelling unit separation have been and the need to be offset. An additional requirement, Although the exception applies to nonmetiallic electrical to eteel one that does not appear in the code, regulates the size outlet boxes, the same concopt would apply 1' of the annular spacf, created around the outlet boxes. boxes that exceed the sizes spocified in Exception Both the Undenilriters Laboratory's (UL) Fire-Restls- Exception 3 provides an altemative to the annular pen- tanæ Dlrectory and the Gypsum Association's Ffe- space protection provisions for a llro sprinkler that is available rcsrìslance Design Manualspeciff a maximum over-cut etrates a single membrane. This exception completely of 1/. inch (S mm) for the annular space around the out- if the annulai space around the sprinkler is plate noncombustible let boxes. R¿On¡ónaUy, Article 314 of the Natlonal Elec- covsred by an escutcheon of posed îÍcal Aode (NEC) (also known as NFPA 70) includes material. The nature of the hazard by single- bythe the size limitation of the over-cut. Thereforo, the excep membrane penetratíons of the sprinkler ls limited openings tion applies only whên the boxes are installed as they size of the opening, the potential number of system. The were dirring the original fire têsts, including the limited present and the presence of a sprinkler provides annular spãce. Becãuse outlet bsxes on both sides of a installation of a noncombustible escutcheon passage fire through the wall create penetrations of boür layers of a wall assem- protection against the free of bly's protection, the code provides five methods to annular spaõe and allows for the movement of the during a seismic event adOrebs this problem. This gives code users several sprinkler piping without breaking options and does not limit ihem to the usual 24-inch [see Commentary Figure R302.4.2(2)l' (610' mm)offset. Excepúon 2 permits using outletboxes of nonmetallic materials if they have been specificallytested. Because

FIRE-RESISTANCE. RATED WALL

MIN 24 lN. SËPARATION BOX SIZE: 5 16 SQ lN. WITH MAX OF lOO SO IN, PER 1OO SO FT OF WALL

*rrrr rr. J#äff8Jf?Èro5#E*,,*,o* m¡' For Sl: 1 inch = 25.4 mm, 1 square inch = 645 mm2, 1 square foot = 0'0929 Flguro R302.4'2(t) MEMBRANE PENETRATION BY OUTLET BOX

CEILINO MEMBRANE

ESCUTCHEOTI PLAÍE

PENDENT SPRINKLER Flgurc R302.4.2(2) EXCEPTION TO ANNUI.AR SPACE PROTECTION

3{2 2015 INTERNATIONAL HESIDENNAL CODEI COTìIMENTÀRY