PAS 79: 2007

Annex A (informative) Model pro-forma for documentation of the fire risk assessment for premises in England and Wales

A . 1 This Annex contains a model pro-forma for documentation of a fire risk assessment in England Wales. I f the pro-forma is completed by a competent person, the format and scope of the fire risk assessment will be suitable and sufficient to satisfy the recommendations of this PAS.

NOTE Enforcement of fire safety legislation is the prerogative of the enforcing authority charged by legislation with the responsibility to do so. Each enforcing authority is autonomous. There is experience to suggest that, at the time of writing, there are inconsistencies between different officers of different enforcing authorities (e.g. different fire and rescue authorities) regarding their interpretation of the term "suitable and sufficient", as used in fire safety legislation in England and Wales to describe the requirement in respect of fire risk assessments; there is also a lack of consistency in respect of the meaning of the term "significant findings", as used in fire safety legislation. There is a lack of case law to assist in this respect. However, the format of the pro-forma contained in this Annex is considered by the Chief Fire Officers' Association to be one suitable format for recording the significant findings of a suitable and sufficient fire risk assessment, although many other formats would also be acceptable.

A.2 The format of a documented fire risk assessment may vary from that shown in this Annex, provided the recommendations of each clause of this PAS are satisfied. For example, in the case of means of escape, compliance with Annex C necessitates that the key factors in Table C.1 are explicitly addressed in the documented fire risk assessment, but not all the specific issues shown in Table C.1 and in the pro-forma contained in this Annex need necessarily be included in all documented fire risk assessments complying with the recommendations of this PAS, as they might not all constitute "significant findings". It is, however, necessary for compliance with this PAS, that the specific issues have, at least, been considered by the fire risk assessor while carrying out the fire risk assessment.

A.3 Equally, the prompt list of fire hazards shown in the pro-forma may be expanded. This might be appropriate, for example, if there are significant fire hazards for which no headings are included in the pro-forma.

A.4 Where description of any fire hazards or fire precautions is considered appropriate, this can be recorded under the relevant “Comments” heading in the pro-forma. The comments sections can also be used to set out

THE OLD MALTHOUSE, LANGTON MATRAVERS

© C.S. Todd & Associates Ltd. 2007 This pro-forma is licensed for use in fire risk assessments only if carried out by a purchaser of PAS 79. PAS 79: 2007 justification for acceptance of standards of any fire protection measures that depart significantly from a prescriptive norm (see 9.2 b)).

A.5 While it might not be essential to record further information in every comments section, care needs to be taken to ensure that the pro-forma does not become a mere ticklist with inadequate supporting information. Such a fire risk assessment is unlikely to satisfy fire safety legislation, nor would it comply with the recommendations of this PAS.

2 PAS 79: 2007

REGULATORY REFORM (FIRE SAFETY) ORDER 2005

FIRE RISK ASSESSMENT

Responsible Person (e.g. Employer) or COTHILL EDUCATIONAL TRUST. Person having control of the premises:

Address of Premises: THE OLD MALTHOUSE LANGTON MATRAVERS SWANAGE DORSET BH9 3HB Person(s) Consulted: MARION LLOYD-JONES (DIRECTOR)

Assessor: ALASTAIR GORDON-FARLEIGH G I Fire E

Date of Fire Risk Assessment: 1st March 2010 – re-assessed 8/5/10

Date of Previous Fire Risk Assessment: N/A

Suggested Date for Review1: WHEN PREMISES IS FULLY FUNCTIONAL – Reviewed 8th May 2010

The purpose of this report is to provide an assessment of the risk to life from fire, and, where appropriate, to make recommendations to ensure compliance with fire safety legislation. The report does not address the risk to property or business continuity from fire.

THE PREMISES WAS, FORMERLY, A PRIVATE PREPARATORY SCHOOL. IT HAS BEEN OUT OF SERVICE FOR APPROX 2 YEARS AND IS CURRENTLY BEING FULLY RENOVATED TO PROVIDE A HIGH QUALITY RESIDENTIAL EDUCATIONAL CENTRE. GROUPS OF UP TO 48 CHILDREN AGED FROM 12 – 13 WILL STAY AT THE PREMISES FOR A WEEK AT A TIME FOR SCIENTIFIC STUDIES.

EACH GROUP OF CHILDREN WILL BE ACCOMPANIED BY THEIR OWN STAFF. THERE WILL ALSO BE 2 GAP YEAR STUDENTS RESIDENT ON SITE AND THERE ARE, CURRENTLY FOUR EMPLOYEES ON SITE (THESE ARE THE FIRE WARDENS FOR THE SITE)

THE PREMISES COMPRISE THE MAIN BUILDING ON 2 & 3 FLOORS, WHICH WILL HOUSE THE SLEEPING ACCOMMODATION AND GENERAL LIVING & ADMINISTRATION QUARTERS AND TWO FURTHER BUILDINGS PROVIDING THE MAIN HALL AND A TEACHING BLOCK OF 6 CLASSROOMS OVER 2 FLOORS. THE HALL

1 This fire risk assessment should be reviewed by a competent person by the date indicated above or at such earlier time as there is reason to suspect that it is no longer valid, or if there has been a significant change in the matters to which it relates, or if a fire occurs. ______THE OLD MALTHOUSE, LANGTON MATRAVERS 3 © C.S. Todd & Associates Ltd. 2007 This pro-forma is licensed for use in fire risk assessments only if carried out by a purchaser of PAS 79. PAS 79: 2007

ALSO HOUSES A NUMBER OF FORMER MUSIC PRACTICE ROOMS AT BASEMENT LEVEL, AND IS USED AS THE ASSEMBLY POINT FOR THE SITE IN THE EVENT OF FIRE

THIS ASSESSMENT IS LIMITED TO THE MATTERS OBSERVABLE AT THIS CONSTRUCTION STAGE AND SHOULD BE REVIEWED WHEN THE PREMISES IS COMPLETED AND FULLY OCCUPIED – Reviewed 8/5/10 GENERAL INFORMATION

1. THE PREMISES

1.1 Number of floors: 2 &3

1.2 Approximate floor area: 1800m2 gross 650 m² on ground floor. [delete units as appropriate]

1.3 Brief details of construction:

MAIN BUILDING OF TRADITIONAL CONSTRUCTION WITH TIMBER CUT ROOF BEARING SLATES / TILES

1.4 Occupancy:

SPECIALIST, RESIDENTIAL EDUCATIONAL TRAINING UNIT FOR CHILDREN AGED 12-13

2. THE OCCUPANTS

2.1 Approximate maximum number: 52

2.2 Approximate number of employees at any one time: 5

2.3 Maximum number of members of public at any one time: 90

3. OCCUPANTS ESPECIALLY AT RISK FROM FIRE

3.1 Sleeping occupants: 52

3.2 Disabled occupants: 0

3.3 Occupants in remote areas: 0

3.4 Young persons: 0

3.5 Others: 0

______THE OLD MALTHOUSE, LANGTON MATRAVERS 4 © C.S. Todd & Associates Ltd. 2007 This pro-forma is licensed for use in fire risk assessments only if carried out by a purchaser of PAS 79. PAS 79: 2007

______THE OLD MALTHOUSE, LANGTON MATRAVERS 5 © C.S. Todd & Associates Ltd. 2007 This pro-forma is licensed for use in fire risk assessments only if carried out by a purchaser of PAS 79. PAS 79: 2007

FIRE LOSS EXPERIENCE

N/A

OTHER RELEVANT INFORMATION

N/A

6. RELEVANT FIRE SAFETY LEGISLATION

6.1 The following fire safety legislation applies to these premises:

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005

6.2 The above legislation is enforced by:

DORSET FIRE AUTHORITY

6.3 Other legislation that makes significant requirements for fire precautions in these premises (other than the Building Regulations 2000):

PUBLIC ENTERTAINMENT LICENCE

6.4 The legislation to which 6.3 makes reference is enforced by:

PURBECK D.C.

6.5 Comments:

FIRE HAZARDS AND THEIR ELIMINATION OR CONTROL

7. ELECTRICAL SOURCES OF IGNITION

7.1 Reasonable measures taken to prevent fires of Yes X No electrical origin?

7.2 More specifically:

Fixed installation periodically inspected and tested? Yes X No

Portable appliance testing carried out? Yes X No

______THE OLD MALTHOUSE, LANGTON MATRAVERS 6 © C.S. Todd & Associates Ltd. 2007 This pro-forma is licensed for use in fire risk assessments only if carried out by a purchaser of PAS 79. PAS 79: 2007

Suitable policy regarding the use of personal electrical Yes X No appliances? Suitable limitation of trailing leads and adapters? Yes X No

7.3 Comments and hazards observed:

THE MAIN BUILDING HAS BEEN COMPLETELY REFURBISHED AND REWIRED AS NECESSARY. P.A.T. TESTING IS TO BE DONE IN-HOUSE AND WILL INCLUDE PERSONAL ELECTRICAL EQUIPMENT USED IN THE PREMISES

8. SMOKING

8.1 Reasonable measures taken to prevent fires as a result of Yes X No smoking?

8.2 More specifically:

Smoking prohibited in the building? Yes X No

Smoking prohibited in appropriate areas? N/A X Yes No

Suitable arrangements for those who wish to smoke? Yes X No

This policy appeared to be observed at time of inspection? Yes X No

8.3 Comments and hazards observed:

SMOKERS ARE TO RESORT TO NEARBY LANE OFF SITE

9. ARSON

9.1 Does basic security against arson by outsiders appear Yes X No reasonable2?

9.2 Is there an absence of unnecessary fire load in close proximity Yes X No to the premises or available for ignition by outsiders?

9.3 Comments and hazards observed:

P.I.R. OPERATED FLOODLIGHTING AROUND THE SITE. 4 x CCTV CAMERAS INSTALLED AROUND THE SITE. KEY PAD ENTRY ON ALL GROUND AND FIRST FLOOR ENTRY DOORS.

10. PORTABLE HEATERS AND HEATING INSTALLATIONS

2 Note: Reasonable only in the context of this fire risk assessment. If specific advice on security (including security against arson) is required, the advice of a security specialist should be obtained. ______THE OLD MALTHOUSE, LANGTON MATRAVERS 7 © C.S. Todd & Associates Ltd. 2007 This pro-forma is licensed for use in fire risk assessments only if carried out by a purchaser of PAS 79. PAS 79: 2007

10.1 Is the use of portable heaters avoided as far as practicable? Yes X No

10.2 If portable heaters are used,

is the use of the more hazardous type (e.g. radiant bar N/A Yes X No fires or lpg appliances) avoided?

are suitable measures taken to minimize the hazard of N/A Yes X No ignition of combustible materials?

10.3 Are fixed heating installations subject to regular N/A Yes X No maintenance?

10.4 Comments and hazards observed:

SOME CONVECTOR HEATERS ARE IN TEMPORARY USE AND HAVE FAULTY ‘FEET’. THESE ARE TO BE REPAIRED OR REMOVED FROM THE PREMISES. ADDITIONAL HEATING IS PROVIDED BY PORTABLE OIL-FILLED ELECTRIC RADIATORS - All portable heaters are now removed.

11. COOKING 11.1 Are reasonable measures taken to prevent fires as a result of N/A Yes No X cooking?

11.2 More specifically:

Filters changed and ductwork cleaned regularly? N/A Yes X No

Suitable extinguishing appliances available? N/A Yes X No

11.3 Comments and hazards observed:

FILTERS WILL BE CLEANED REGULARLY. THE SPECIFICATION INDICATES ADEQUATE PROVISION OF EXTINGUISHERS

12. LIGHTNING 12.1 Does the building have a lightning protection system? Yes No X

12.2 Comments and deficiencies observed:

CONSIDERATION SHOULD BE GIVEN TO THIS PROVISION

13. HOUSEKEEPING

13.1 Is the standard of housekeeping adequate? Yes No X 13.2 More specifically:

Combustible materials appear to be separated from Yes X No ______THE OLD MALTHOUSE, LANGTON MATRAVERS 8 © C.S. Todd & Associates Ltd. 2007 This pro-forma is licensed for use in fire risk assessments only if carried out by a purchaser of PAS 79. PAS 79: 2007

ignition sources?

Avoidance of unnecessary accumulation of combustible Yes No X materials or waste?

Appropriate storage of hazardous materials? N/A X Yes No

Avoidance of inappropriate storage of combustible Yes X No materials?

13.3 Comments and hazards observed:

THERE IS COMBUSTIBLE STORAGE IN MANY AREAS DUE TO THE CONSTRUCTION WORKS BEING CARRIED OUT. ALL EXCESS COMBUSTIBLE MATERIALS SHOULD BE REMOVED FROM THE PREMISES AS SOON AS POSSIBLE TO REDUCE THE RISK – all removed by 8/5/10

14. HAZARDS INTRODUCED BY OUTSIDE CONTRACTORS AND BUILDING WORKS

14.1 Are fire safety conditions imposed on outside contractors? Yes X No

14.2 Is there satisfactory control over works carried out in the Yes X No building by outside contractors (including "hot work" permits)?

14.3 If there are in-house maintenance personnel, are suitable N/A X Yes No precautions taken during "hot work", including use of hot work permits?

14.4 Comments:

POLICIES ON THESE MATTERS ARE BEING PREPARED AND WILL BE ENFORCED FOR FUTURE WORKS

15. DANGEROUS SUBSTANCES

15.1 If dangerous substances are, or could be, used, has a risk N/A X Yes No assessment been carried out, as required by the Dangerous Substances and Explosive Atmospheres Regulations 2002?

15.2 Comments:

16. OTHER SIGNIFICANT FIRE HAZARDS THAT WARRANT CONSIDERATION

16.1 Hazards: 16.2 Comments and deficiencies observed:

FIRE PROTECTION MEASURES ______THE OLD MALTHOUSE, LANGTON MATRAVERS 9 © C.S. Todd & Associates Ltd. 2007 This pro-forma is licensed for use in fire risk assessments only if carried out by a purchaser of PAS 79. PAS 79: 2007

17. MEANS OF ESCAPE FROM FIRE

17.1 It is considered that the building is provided with Yes X No reasonable means of escape in case of fire.

17.2 More specifically:

Adequate design of escape routes? Yes X No

Adequate provision of exits? Yes X No

Exits easily and immediately openable where Yes X No necessary?

Fire exits open in direction of escape where Yes X No necessary?

Avoidance of sliding or revolving doors as fire exits Yes X No where necessary?

Satisfactory means for securing exits? Yes X No

Reasonable distances of travel:

 Where there is a single direction of travel? Yes X No

 Where there are alternative means of escape? Yes X No

Suitable protection of escape routes? Yes X No

Suitable fire precautions for all inner rooms? Yes X No

Escape routes unobstructed? Yes X No

17.3 It is considered that the building is provided with Yes X No reasonable arrangements for means of escape for disabled people.

17.4 Comments and deficiencies observed:

ALL THE HALL EXIT DOORS REQUIRE ATTENTION AS THEY ARE DIFFICULT TO OPEN. SOME ESCAPE ROUTES CONTAIN STORAGE DUE TO CONSTRUCTION WORKS. ALL ISSUES IN THE MAIN BUILDING WILL BE SATISFACTORY ONCE FULLY FUNCTIONAL – all issues addressed by 8/5/10

18. MEASURES TO LIMIT FIRE SPREAD AND DEVELOPMENT

______THE OLD MALTHOUSE, LANGTON MATRAVERS 10 © C.S. Todd & Associates Ltd. 2007 This pro-forma is licensed for use in fire risk assessments only if carried out by a purchaser of PAS 79. PAS 79: 2007

18.1 It is considered that there is: compartmentation of a reasonable standard3. Yes X No

reasonable limitation of linings that may promote fire Yes X No spread.

18.2 As far as can reasonably be ascertained, fire dampers are N/A Yes No X provided as necessary to protect critical means of escape against passage of fire, smoke and combustion products in the early stages of a fire? 4,5

18.3 Comments and deficiencies observed:

19. EMERGENCY ESCAPE LIGHTING

19.1 Reasonable standard of emergency escape lighting system Yes X No provided6?

19.2 Comments and deficiencies observed:

EXCELLENT PROVISION IS BEING INSTALLED CURRENTLY –all provision completed by 8/5/10

20. FIRE SAFETY SIGNS AND NOTICES

20.1 Reasonable standard of fire safety signs and notices? Yes X No

20.2 Comments and deficiencies observed:

THE SPECIFIED NOTICES & SIGNS WILL BE ADEQUATE – all signage completed by 8/5/10

21. MEANS OF GIVING WARNING IN CASE OF FIRE

21.1 Reasonable manually operated electrical fire alarm system Yes X No provided7?

21.2 Automatic fire detection provided? Yes X Yes No (throughout (part of building building) only) 21.3 Extent of automatic fire detection generally appropriate for the N/A Yes X No occupancy and fire risk?

21.4 Remote transmission of alarm signals? Yes No X

3 Based on visual inspection of readily accessible areas, with a degree of sampling where appropriate. 4 Based on visual inspection of readily accessible areas, with a degree of sampling where appropriate. 5 A full investigation of the design of HVAC systems is outside the scope of this fire risk assessment. 6 Based on visual inspection, but no test of illuminance levels or verification of full compliance with relevant British Standards carried out. 7 Based on visual inspection, but no audibility tests or verification of full compliance with relevant British Standard carried out. ______THE OLD MALTHOUSE, LANGTON MATRAVERS 11 © C.S. Todd & Associates Ltd. 2007 This pro-forma is licensed for use in fire risk assessments only if carried out by a purchaser of PAS 79. PAS 79: 2007

21.5 Comments and deficiencies observed?

THE SYSTEM IS NOT FUNCTIONAL YET. IT IS STRONGLY RECOMMENDED THAT THE SYSTEM BE LINKED TO AN ALARM HANDLING CENTRE TO CALL THE FIRE SERVICE AUTOMATICALLY DURING THE HOURS OF DARKNESS – Kentek Syncro 2 Loop Addressable System installation completed April 2010

22. MANUAL FIRE EXTINGUISHING APPLIANCES 22.1 Reasonable provision of portable fire extinguishers? Yes X No

22.2 Hose reels provided? Yes No X

22.3 Are all fire extinguishing appliances readily accessible? Yes X No

22.4 Comments and deficiencies observed:

CONTRACTORS EXTINGUISHERS IN USE UNTIL FINAL FIT-OUT. ADEQUATE PROVISION IS SPECIFIED – no longer applicable

‡ 23. RELEVANT AUTOMATIC FIRE EXTINGUISHING SYSTEMS 23.1 Type of system:

N/A

23.2 Comments:

24. OTHER RELEVANT‡ FIXED SYSTEMS AND EQUIPMENT 24.1 Type of fixed system:

N/A

24.2 Comments:

24.3 Suitable provision of fire-fighters switch(es) for high voltage N/A X Yes No luminous tube signs, etc

N/A

24.4 Comments: MANAGEMENT OF FIRE SAFETY

25. PROCEDURES AND ARRANGEMENTS

25.1 Fire safety is managed by8:

‡ ‡ Relevant to life safety and this risk assessment (as opposed purely to property protection). ‡ ______THE OLD MALTHOUSE, LANGTON MATRAVERS 12 © C.S. Todd & Associates Ltd. 2007 This pro-forma is licensed for use in fire risk assessments only if carried out by a purchaser of PAS 79. PAS 79: 2007

MRS MARION LLOYD-JONES

25.2 Competent person(s) appointed to assist in undertaking the Yes X No preventive and protective measures (i.e. relevant general fire precautions)?

Comments:

4 TRAINED FIRE WARDENS ON SITE – March’10

25.3 Is there a suitable record of the fire safety arrangements? N/A Yes No X

Comments:

25.4 Appropriate fire procedures in place? Yes X No More specifically:

Are procedures in the event of fire appropriate and properly N/A Yes X No documented?

Are there suitable arrangements for summoning the Yes X No fire and rescue service?

Are there suitable arrangements to meet the fire and N/A Yes X No rescue service on arrival and provide relevant information, including that relating to hazards to fire-fighters?

Are there suitable arrangements for ensuring that the N/A Yes X No premises have been evacuated? Is there a suitable fire assembly point(s)? N/A Yes X No

Are there adequate procedures for evacuation of any N/A Yes X No disabled people who are likely to be present?

Comments:

FIRE WARDENS WILL SUPERVISE EVACUATION OF ALL OCCUPANTS AND ‘SWEEP’ THE PREMISES TO CHECK ALL AREAS CLEAR

25.5 Persons nominated and trained to use fire extinguishing appliances? N/A Yes X No

Comments:

FIRE WARDENS ONLY

8 This is not intended to represent a legal interpretation of responsibility, but merely reflects the managerial arrangement in place at the time of this risk assessment. ______THE OLD MALTHOUSE, LANGTON MATRAVERS 13 © C.S. Todd & Associates Ltd. 2007 This pro-forma is licensed for use in fire risk assessments only if carried out by a purchaser of PAS 79. PAS 79: 2007

25.6 Persons nominated and trained to assist with evacuation, including N/A Yes X No evacuation of disabled people?

Comments:

FIRE WARDENS, ACCOMPANYING STAFF & GAP STUDENTS WILL ASSIST WITH EVACUATION

25.7 Appropriate liaison with fire and rescue service (e.g. by fire N/A Yes X No and rescue service crews visiting for familiarization visits)?

Comments:

CURRENT LIAISON WITH FIRE SAFETY OFFICER PRIOR TO OPENING THE PREMISES

25.8 Routine in-house inspections of fire precautions (e.g. in the N/A Yes No X course of health and safety inspections)?

Comments:

26. TRAINING AND DRILLS

26.1 Are all staff given adequate fire safety instruction and training on Yes X No induction?

Comments:

ALL STAFF GIVEN INDUCTION TRAINING IN-HOUSE

26.2 Are all staff given adequate periodic "refresher training" at suitable Yes X No intervals? Comments:

ALL CURRENT STAFF ARE TRAINED AS FIRE WARDENS AND WILL RECEIVE IN-HOUSE REFRESHER TRAINING IN INTERVENING YEARS BETWEEN QUALIFICATION PERIODS

26.3 Does all staff training provide information, instruction or training on the following:

Fire risks in the premises? Yes X No

The fire safety measures in the building? Yes X No

Action in the event of fire? Yes X No

Action on hearing the fire alarm signal? Yes X No

Method of operation of manual call points? Yes X No ______THE OLD MALTHOUSE, LANGTON MATRAVERS 14 © C.S. Todd & Associates Ltd. 2007 This pro-forma is licensed for use in fire risk assessments only if carried out by a purchaser of PAS 79. PAS 79: 2007

Location and use of fire extinguishers? Yes No X

Means for summoning the fire and rescue service? Yes X No

Identity of persons nominated to assist with evacuation? Yes X No

Identity of persons nominated to use fire extinguishing Yes X No appliances?

Comments:

26.4 Are staff with special responsibilities (e.g. fire wardens) given N/A Yes X No additional training? Comments:

WARDENS TRAINED LAST MONTH – March 2010-valid 3 yrs

26.5 Are fire drills carried out at appropriate intervals? Yes X No

Comments:

THIS WILL BE CARRIED OUT FOR EACH WEEKLY STUDENT INTAKE

26.6 When the employees of another employer work in the premises:

Is their employer given appropriate information (e.g. on fire N/A Yes No X risks and general fire precautions)?

Is it ensured that the employees are provided with adequate N/A Yes X No instructions and information?

Comments:

POLICY BEING PREPARED CURRENTLY – information sent to contractors

27. TESTING AND MAINTENANCE 27.1 Adequate maintenance of premises? Yes X No

Comments and deficiencies observed:

IN-HOUSE MAINTENANCE TEAM TAKES RESPONSIBILITY FOR ALL MATTERS

27.2 Weekly testing and periodic servicing of fire detection and Yes X No alarm system?

Comments and deficiencies observed:

______THE OLD MALTHOUSE, LANGTON MATRAVERS 15 © C.S. Todd & Associates Ltd. 2007 This pro-forma is licensed for use in fire risk assessments only if carried out by a purchaser of PAS 79. PAS 79: 2007

WHEN THE NEW SYSTEM IS FUNCTIONING THIS WILL BE CARRIED OUT AND DULY RECORDED – testing now recorded

27.3 Monthly and annual testing routines for emergency escape lighting? Yes X No

Comments and deficiencies observed:

WHEN THE NEW SYSTEM IS FUNCTIONING THIS WILL BE CARRIED OUT AND DULY RECORDED – testing now recorded

27.4 Annual maintenance of fire extinguishing appliances? Yes X No

Comments and deficiencies observed:

EXTINGUISHERS IN THE SATELLITE BUILDINGS ARE OUT OF TEST DATE AND MUST NOT BE USED UNTIL FULLY SERVICED OR REPLACED. THE CONTRACT WILL BE RENEWED WHEN THE PREMISES IS FULLY EQUIPPED AND FUNCTIONING –all extinguishers are now fully compliant

27.5 Periodic inspection of external escape staircases and N/A Yes X No gangways?

Comments and deficiencies observed:

ALGAE ON STAIRS & WALKWAYS TO BE KEPT UNDER CONTROL

27.6 Six-monthly inspection and annual testing of rising mains? N/A X Yes No

Comments and deficiencies observed:

27.7 Weekly and monthly testing, six monthly inspection and N/A X Yes No annual testing of fire-fighting lifts?

Comments and deficiencies observed:

27.8 Weekly testing and periodic inspection of sprinkler N/A Yes No X installations?

Comments:

27.9 Routine checks of final exit doors and/or security fastenings? N/A Yes X No Comments:

MOST IN DAILY USE BUT SOME LESS-USED DOORS REQUIRE ATTENTION AND REGULAR CHECKING – checking system implemented

27.10 Annual inspection and test of lightning protection system? N/A X Yes No

______THE OLD MALTHOUSE, LANGTON MATRAVERS 16 © C.S. Todd & Associates Ltd. 2007 This pro-forma is licensed for use in fire risk assessments only if carried out by a purchaser of PAS 79. PAS 79: 2007

Comments:

27.11 Other relevant inspections or tests:

Comments:

28. RECORDS

28.1 Appropriate records of:

Fire drills? N/A Yes No X

Fire training? Yes X No

Fire alarm tests? N/A Yes X No

Emergency escape lighting tests? N/A Yes No X

Maintenance and testing of other fire protection systems? N/A X Yes No

28.2 Comments:

______THE OLD MALTHOUSE, LANGTON MATRAVERS 17 © C.S. Todd & Associates Ltd. 2007 This pro-forma is licensed for use in fire risk assessments only if carried out by a purchaser of PAS 79. PAS 79: 2007

FIRE RISK ASSESSMENT

The following simple risk level estimator is based on a more general health and safety risk level estimator of the type contained in BS 8800:

Potential consequences of fire Slight harm Moderate harm Extreme harm

Likelihood of fire

Low Trivial risk Tolerable risk Moderate risk

Medium Tolerable risk Moderate risk Substantial risk

High Moderate risk Substantial risk Intolerable risk

Taking into account the fire prevention measures observed at the time of this risk assessment, it is considered that the hazard from fire (likelihood of fire) at these premises is:

Low X Medium High

In this context, a definition of the above terms is as follows:

Low: Unusually low likelihood of fire as a result of negligible potential sources of ignition.

Medium: Normal fire hazards (e.g. potential ignition sources) for this type of occupancy, with fire hazards generally subject to proper controls (other than minor shortcomings).

High: Lack of adequate controls applied to one or more significant fire hazards, such as to result in significant increase in likelihood of fire.

Taking into account the nature of the building and the occupants, as well as the fire protection and procedural arrangements observed at the time of this fire risk assessment, it is considered that the consequences for life safety in the event of fire would be:

Slight harm Moderate X Extreme harm harm

______THE OLD MALTHOUSE, LANGTON MATRAVERS 18 © C.S. Todd & Associates Ltd. 2007 This pro-forma is licensed for use in fire risk assessments only if carried out by a purchaser of PAS 79. PAS 79: 2007

In this context, a definition of the above terms is as follows:

Slight harm: Outbreak of fire unlikely to result in serious injury or death of any occupant (other than an occupant sleeping in a room in which a fire occurs).

Moderate Outbreak of fire could foreseeably result in injury (including serious injury) of harm: one or more occupants, but it is unlikely to involve multiple fatalities.

Extreme harm: Significant potential for serious injury or death of one or more occupants.

Accordingly, it is considered that the risk to life from fire at these premises is:

Trivial Tolera X Moder Substa Intoler ble ate ntial able

Comments:

THE RISK IS LIKELY TO REDUCE ONCE THE PREMISES IS FULLY EQUIPPED AND FUNCTIONAL, WITH THE FIRE ALARM & DETECTION SYSTEM OPERATING THROUGHOUT. ALL ESCAPE ROUTES WILL THEN BE CLEARED AND KEPT SO – The risk is now reduced to trivial

A suitable risk-based control plan should involve effort and urgency that is proportional to risk. The following risk-based control plan is based on one advocated by BS 8800 for general health and safety risks:

Risk Level Action and timescale

Trivial No action is required and no detailed records need be kept.

Tolerable No major additional controls required. However, there might be a need for improvements that involve minor or limited cost.

______THE OLD MALTHOUSE, LANGTON MATRAVERS 19 © C.S. Todd & Associates Ltd. 2007 This pro-forma is licensed for use in fire risk assessments only if carried out by a purchaser of PAS 79. PAS 79: 2007

It is essential that efforts be made to reduce the risk. Risk reduction measures should be implemented within a defined Moderate time period.

Where moderate risk is associated with consequences that constitute extreme harm, further assessment might be required to establish more precisely the likelihood of harm as a basis for determining the priority for improved control measures.

Considerable resources might have to be allocated to reduce Substantial the risk. If the building is unoccupied, it should not be occupied until the risk has been reduced. If the building is occupied, urgent action should be taken.

Intolerable Building (or relevant area) should not be occupied until the risk is reduced.

(Note that, although the purpose of this section is to place the fire risk in context, the above approach to fire risk assessment is subjective and for guidance only. All hazards and deficiencies identified in this report should be addressed by implementing all recommendations contained in the following action plan. The fire risk assessment should be reviewed regularly.)

ACTION PLAN

It is considered that the following recommendations should be implemented in order to reduce fire risk to, or maintain it at, the following level:

Trivial Tolerable X

Definition of priorities (where applicable):

______THE OLD MALTHOUSE, LANGTON MATRAVERS 20 © C.S. Todd & Associates Ltd. 2007 This pro-forma is licensed for use in fire risk assessments only if carried out by a purchaser of PAS 79. PAS 79: 2007

Priority. Comments.

Actioned 1. ALL PACKAGI Removed NG AND Removed WASTE MATERIA Removed LS SHOULD Actioned BE REMOVE D FROM Actioned THE PREMISE S DAILY 2. GAS Actioned CYLINDE RS USED ON TEMPOR ARY Actioned SPACE Actioned HEATING UNITS ETC., SHOULD Removed BE REMOVE D FROM Actioned THE PREMISE This is a private area. All equipment is switched off at night & doors to kitchen & office are closed/ locked at night. On hearing the automatic fire alarm, the teacher in Room 3 can exit into a sterile escape route. S AFTER Actioned USE Swept June’10 3. GAS (no wood fires at present) SPACE HEATERS Removed ARE NOT Sign on wall TO BE LEFT ON UNATTE NDED 4. THE SKIP SHOULD BE COVERE D AT ______NIGHT IF THE OLD MALTHOUSE, LANGTON MATRAVERS 21 © C.S. Todd & Associates Ltd. 2007 This pro-forma is licensed for use in fire risk assessments only if carried out by a purchaser of PAS 79. PAS 79: 2007

Priority.

Comments.

18. THE FIRE BLANKET IN THE KITCHEN REQUIRES REPLACING – IT IS REPLACED TOO LARGE FOR SAFE USE AND IT IS OUT OF DATE 19. EMERGENCY BLANKETS WILL NEED TO BE STORED IN THE HALL M TO PROTECT NIGHT EVACUEES DURING INCLEMENT WEATHER 20. THE OPENING IN THE WALL NEAR THE ENTRANCE TO THE L CLASSROOM BLOCK PRESENTS A VULNERAABILITY TO THE SECURITY OF THE SITE – IT IS RECOMMENDED THAT A SECURED GATE BE INSTALLED AND KEPT LOCKED AT NIGHT 21. IT IS RECOMMENDED THAT THE LOCAL FIRE CREWS BE M ENCOURAGED TO VISIT THE PREMISES, ONCE READY FOR OCCUPATION, TO FAMILIARISE THEM WITH THE RISK 22. MANDATORY FIRE ACTION NOTICES ARE REQUIRED BY EACH ACTIONED STOREY EXIT FROM EACH BUILDING 23. THE ELECTRICAL WIRING TO THE BASEMENT AREA WITHIN H THE HALL IS SUBJECT TO CONSIDERABLE DAMP AND MOULD. IT SHOULD BE CHECKED FOR SAFETY AND INTEGRITY AND DISCONNECTED OR REPLACED AS NECESSARY 24. FIRE WARDENS ARE TO BE PROVIDED WITH FLUORESCENT AVAILABLE ARMBANDS, OR TABARDS, MARKED ‘FIRE WARDEN’ 25. A SUITABLE COURSE FIRE SAFETY INDUCTION DOCUMENT PROCEDURES SHOULD BE PREPARED FOR USE IN BRIEFING NEW GROUPS CIRCULATED 26. CONSIDERATION SHOULD BE GIVEN TO THE PROVISION OF L LIGHTNING PROTECTION FOR THE MAIN BUILDING 27. A FIRE SAFETY LOGBOOK IS TO BE PROVIDED FOR RECORDING IN FIRE PANEL ALL FIRE SAFETY ISSUES

______THE OLD MALTHOUSE, LANGTON MATRAVERS 22 © C.S. Todd & Associates Ltd. 2007 This pro-forma is licensed for use in fire risk assessments only if carried out by a purchaser of PAS 79. PAS 79: 2007

FIRE RISK ASSESSMENT (RA) REVIEW 26TH JUNE 2012

Reviewed March 2014 by NRB

This review was carried out in conjunction with Dorset Fire and Rescue Service.

The Risk Assessment and records kept by OMH are considered to be good.

The following recommendations were made:

 The RA needs to say how the fire brief works for visiting groups

 The RA should state that the Fire Briefing Pack is kept by the exit

 Any further staff training should include a confirmation question sheet and signatures that staff have undertook fire training.

 When investigating a fire post evacuation, two people should carry out the search.

 At night a phone call should ALWAYS be made to the Fire and Rescue services when evacuating, even if a false alarm is suspected.

 Only a “responsible adult” (over the age of 18 years) can take a roll call.

 The sofa and chairs should be removed from the landings.

______THE OLD MALTHOUSE, LANGTON MATRAVERS 23 © C.S. Todd & Associates Ltd. 2007 This pro-forma is licensed for use in fire risk assessments only if carried out by a purchaser of PAS 79. PAS 79: 2007

Amendments to RA:

1. The Fire Plan, RA and Drill are sent out to schools prior to their visit.

2. On arrival all pupils and staff are briefed in the following fashion: a) The fire bell is sounded for familiarisation b) All are escorted to their rooms and shown primary and secondary escape routes c) All are shown the assembly area d) all are asked to go and sit on their beds and then practise the evacuation on hearing the alarm

3. A Fire Briefing Pack is kept by the exit door.

4. When investigating a fire post evacuation, two people should carry out the search.

5. At night a phone call should ALWAYS be made to the Fire and Rescue services when evacuating, even if a false alarm is suspected.

6. Only a “responsible adult” (over the age of 18 years) can take a roll call.

______THE OLD MALTHOUSE, LANGTON MATRAVERS 24 © C.S. Todd & Associates Ltd. 2007 This pro-forma is licensed for use in fire risk assessments only if carried out by a purchaser of PAS 79.