Document 484279 Microprocessor Controller for ® Dedicated Outdoor Air System
Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and/or property damage.
DOAS v4.001 Technical Support Call 1-866-478-2574
Introduction Program Features digital output is reserved for remote alarm indication. The microprocessor controller offers control through Alarms are also communicated via BMS (if equipped). easy monitoring and adjustment of unit parameters by Occupancy Modes way of a lighted graphical display and an integral push- The microprocessor controller offers three modes of button keypad. determining occupancy: a digital input, occupancy Pre-Programmed Operating Sequences schedule or the BMS. If in the unoccupied mode, the The controller has been pre-programmed to offer unit will either be shut down, continue normal operation multiple control sequences to provide tempered air. utilizing adjustable unoccupied set points, recirculate Factory default settings allow for easy setup and with unoccupied set points or will cycle on to maintain commissioning. The sequence parameters are fully adjustable unoccupied space temperature and humidity adjustable. Refer to the Sequence of Operation for set points (space temperature and humidity sensor is details. optional). BMS Communication Remote Unit Access (if equipped) The user can remotely adjust set points, view unit The WebUI and Remote Display are two ways to gain status points and alarms. The microprocessor access to the unit controller allowing monitoring of the controller is capable of communicating over several unit and parameter adjustment without being at the protocols: unit. • BACnet® MSTP • Modbus RTU The WebUI can be accessed via a building network • BACnet® IP • Modbus TCP and is included with every unit controller. The Remote • LonWorks® Display is an LCD to be panel mounted in a remote location and is an option available for purchase. Reference Points List for a complete list of BMS points. Built-In Occupancy Schedule WARNING The controller has an internal programmable time clock, allowing the user to set occupancy schedules for each Electrical shock hazard. Can cause personal injury or day of the week. The controller option also has morning equipment damage. Service must be performed only warm-up and cool down capability for improved by personnel that are knowledgeable in the operation comfort at the time of occupancy. of the equipment being controlled. Alarm Management WARNING The microprocessor controller will monitor the unit’s Mechanical high static protection cutoffs must status for alarm conditions. Upon detecting an alarm, be installed by others to protect the system and the controller will record the alarm description, time, equipment from over-pressurization when using date, and input/output status points for user review. A factory provided control sensors. The manufacturer does not assume responsibility for this.