Timers, counters, control and analogue interfaces Zelio Time, Count, Control, Analogue Confidence can be measured

Simply Smart! Simply Smart! Leveraging ingenuity and intelligence for ease of use Zelio Time, Cou

Zelio Time

Our complete and high-performance electronic timer conforms to international standards and corresponds exactly to your requirements. It is designed for all hard-wired logic automated systems complementing programmable logic controllers. Ergonomic and configurable Zelio timers are available in 3 versions: modular, industrial, panel-mounted.

Zelio Count

XBK counters, when associated with sensing products, assure a complementary counting function within automation systems. A variety of simple functions, displays and settings are available in two technologies and three product families: ■ XBKH: hour counting ■ XBKT: totalizers ■ XBKP: threshold preselectors

2 nt, Control and Analogue

Zelio Control

Zelio Control covers all monitoring and control requirements. This range is “in phase” with industrial control systems, guaranteeing detection of breakdowns and faults. It enables three-phase network monitoring, AC and DC current and voltage measurement, and handles conducting liquid level control.

Zelio Analogue

Zelio Analogue converters are designed to convert signals emitted by sensors or electrical measurements into standard electrical signals which are compatible with automation platforms and controllers (thermal processes and speed). They also increase the connection distance between a sensor and the measurement acquisition device (eg. between a thermocouple and a programmable controller).

3 Zelio Time Modular Relays

RE11 range

The new timing relay offer presents a major size advantage with its width of 17.5 mm.

■ Compact dimensions – only 17.5 mm wide. ■ Single or multifunction ranges are available. ■ Wide power supply range. ■ Time range: 0.1 s to 100 h. ■ Relay or solid-state output. ■ Settings are protected by a sealable plastic cover. ■ Simple to instal wiring and timing diagrams are located on side of relay.

17.5 mm

Spring terminals and settings are protected by a sealable plastic cover. Wiring and timing diagrams are located on side of relay.

FUNCTIONS POWER SUPPLY TIME RANGEOUTPUT TERMINALS CAT. NUMBERS Multifunction (1) : Timer on-delay 24 VDC & 24 to 240 VAC 0.1 s to 100 h 1 relay 8A screw RE11 RA MU Timer on-delay / Timer on-delay Calibrator 24 VDC & 24 to 240 VAC 0.1 s to 100 h 1 relay 8A screw RE11 RB MU with lock control / Calibrator / Pulse on energization 24 VDC & 24 to 240 VAC 0.1 s to 100 h 1 relay 8A screw RE11 RH MU Timer off-delay with control / Timer off-delay with control 24 VDC & 24 to 240 VAC 0.1 s to 100 h 1 relay 8A screw RE11 RC MU Pulse on energization / Pulse on energization with time control lock / 24 VDC & 24 to 240 VAC 0.1 s to 100 h 1 relay 8A screw RE11 RL MU Asymmetrical flasher Symmetrical flasher starting by 12 VAC / DC 0.1 s to 100 h 1 relay 8A screw RE11 RL JU pause or pulse. Multifunction (1) 24 VDC & 24 to 240 VAC 0.1 s to 10 h 1 relay 8A screw RE11 RME MU 12 to 240 VAC / DC 0.1 s to 100 h 1 relay 8A screw RE11 RM MW Multifunction (2) : Multifunction (1) and timer Multifunction (2) 24 VDC & 24 to 240 VAC 0.1 s to 100 h 1 relay 8A screw RE11 RM MU 12 to 240 VAC / DC 0.1 s to 100 h 1 relay 8A spring RE11 RM MWS on-delay then timer off-delay by 12 VAC / DC 0.1 s to 100 h 1 relay 8A screw RE11 RM JU external control / Externally Multifunction (3) 24 VDC & 24 to 240 VAC 0.1 s to 100 h 1 relay 8A screw RE11 RMX MU controlled differentiator. Timer on-delay 24 to 240 VAC/DC 0.1 s to 100 h static 0.7A screw RE11 LA MW Multifunction (3) : Pulse on energization 24 to 240 VAC 0.1 s to 100 h static 0.7A screw RE11 LH BM Timer on-delay by external control Timer off-delay with control 24 to 240 VAC 0.1 s to 100 h static 0.7A screw RE11 LC BM / Single cycle flasher by control / Asymmetrical flasher 24 to 240 VAC 0.1 s to 100 h static 0.7A screw RE11 LL BM Watchdog / Delayed watchdog / Multifunction (2) 24 to 240 VAC 0.1 s to 100 h static 0.7A screw RE11 LM BM Delayed fixed pulse / Delayed fixed pulse with time lock control / Remote switch / Time delay remote switch / Timer off-delay when Compact size/Accurate settings/Wiring and operating external control disappears. 4 diagrams visible on product/UL, CSA and GL certified Zelio Time Industrial Relays

RE7 range

The 22.5 mm industrial range is perfectly suited to user requirements.

■ Standard dimensions: 22.5 mm W, 78 mm H, 80 mm D. ■ Settings are protected by a sealable plastic cover. ■ External control is possible for: v start of time delay v partial stop of time delay v adjustment of time delay ■ Simple and quick installation. Wiring and timing diagrams are located on side of relay. ■ Wide time range (up to 300 hours). ■ Application adaptation (7 time delay choices). ■ Two 8 A outputs (second output instantaneous or time delay). ■ LEDs indicate time delay. ■ Screw or spring connection. Settings are protected by a sealable plastic cover. ■ Wide voltage range (24 to 240 VAC/DC). ■ Mounting on DIN rail or by screw without adapter plate. ■ Compact size. ■ UL, CSA and GL certified.

Wiring and timing diagrams are located on side of relay.

FUNCTIONS POWER SUPPLY TIME RANGEOUTPUT CAT. NUMBERS 24VAC/DC - 110 to 240 VAC 0.05 s to 300 h 1 relay 8 A RE7TL11BU Timer on-delay 24VAC/DC - 110 to 240 VAC - 42 to 48 VAC/DC 0.05 s to 300 h 1 relay 8 A RE7 TM11BU 24VAC/DC - 110 to 240 VAC - 42 to 48 VAC/DC 0.05 s to 300 h 2 relay 8 A* RE7 TP13 BU 24VAC/DC - 110 to 240 VAC - 42 to 48 VAC/DC 0.05 s to 300 h 1 relay 8 A RE7 MA11BU Timer on-delay and off-delay 24VAC/DC - 110 to 240 VAC - 42 to 48 VAC/DC 0.05 s to 300 h 2 relay 8 A* RE7 MA13BU Control by external contact 24VAC/DC - 110 to 240 VAC - 42 to 48 VAC/DC 0.05 s to 300 h 1 relay 8 A RE7 MV11BU Timer off-delay 24 to 240 VAC / DC 0.05 s to 10 m 1 relay 5 A RE7 RB11MW on de-energization 24 to 240 VAC / DC 0.05 s to 10 m 2 relay 5 A* RE7 RB13MW Timer off-delay control opening 24VAC/DC - 110 to 240 VAC - 42 to 48 VAC/DC 0.05 s to 300 h 1 relay 8 A RE7 RA11BU (low level) 24VAC/DC - 110 to 240 VAC - 42 to 48 VAC/DC 0.05 s to 300 h 1 relay 8 A RE7 RM11BU (low level) 24VAC/DC - 110 to 240 VAC - 42 to 48 VAC/DC 0.05 s to 300 h 2 relay 8 A* RE7 RL13BU 24VAC/DC - 110 to 240 VAC 0.05 s to 300 h 1 relay 8 A RE7 PE11BU Pulse on energization 24VAC/DC - 110 to 240 VAC - 42 to 48 VAC/DC 0.05 s to 300 h 2 relay 8 A* RE7 PP13BU Timer off-delay at on removal of 24VAC/DC - 110 to 240 VAC - 42 to 48 VAC/DC 0.05 s to 300 h 1 relay 8 A RE7 PM11BU external control 24VAC/DC - 110 to 240 VAC - 42 to 48 VAC/DC 0.05 s to 300 h 2 relay 8 A* RE7 PD13BU 24VAC/DC - 110 to 240 VAC 0.05 s to 300 h 1 relay 8 A RE7 CL11BU Symmetrical flasher (off start) 24VAC/DC - 110 to 240 VAC - 42 to 48 VAC/DC 0.05 s to 300 h 2 relay 8 A* RE7 CP13BU Multifunction (4) : Asymmetrical flasher 24VAC/DC - 110 to 240 VAC - 42 to 48 VAC/DC 0.05 s to 300 h 1 relay 8 A RE7 CV11BU Timer on-delay / Timer off-delay / Star-delta starting time delay 24VAC/DC - 110 to 240 VAC - 42 to 48 VAC/DC 0.05 s to 300 h 2 relay 8 A RE7 YA12BU Pulse on energization / Pulse on Star-delta starting time delay 24VAC/DC - 110 to 240 VAC - 42 to 48 VAC/DC 0.05 s to 300 h 2 relay 8 A** RE7 YR12BU opening control / Symmetrical flasher starts by pause or pulse. Multifunction (4) 24VAC/DC - 110 to 240 VAC - 42 to48 VAC/DC 0.05 s to 300 h 1 relay 8 A RE7 ML11BU Multifunction (4) 24VAC/DC - 110 to 240 VAC 0.05 s to 300 h 2 relay 8 A* RE7 MY13BU * 1 selectable in instantaneous Star-delta starting time delay 24 to 240 VAC /DC 0.05 s to 300 h 2 relay 8 A* RE7 MY13MW ** with common point

Voltage markings on terminal blocks/Accurate Settings 5 Wiring and operating diagrams visible on product/UL, CSA and GL certified Zelio Time Panel-mounted Relays

RE48 Range

The new range of plug-in timing relays in a 48 x 48 is especially designed for integration in machines and equipment, for any application requiring frequent cycle time adjustment or setting.

■ Ergonomic design. ■ Direct reading. ■ Multifunction. ■ Multivoltage: 24 to 240 VAC-DC. ■ Wide time range: 0.02 to 300 h. ■ Mounting spring supplied as standard. ■ Connection sub-bases as option.

Readability: direct reading.

Wiring diagram located on relay side.

Flush-mounted.

Multifunction (5) : Timer on-delay / Pulse on energization

FUNCTIONS POWER SUPPLY TIME RANGEOUTPUT PINS SUB-BASES CAT. NUMBERS Multifunction (6) : Timer on-delay 24 to 240 VAC/DC 0.02 s to 300 h 2 relay 5 A 8 RUZ1D RE48A TM12MW Timer on-delay / Calibrator / Timer off-delay / Symmetrical Asymmetrical flasher 24 to 240 VAC/DC 0.02 s to 300 h 2 relay 5 A 11 RUZ1A RE48A CV12MW flasher Multifunction (5) 24 to 240 VAC/DC 0.02 s to 300 h 2 relay 5 A* 8 RUZ1D RE48A MH13MW Multifunction (6) 24 to 240 VAC/DC 0.02 s to 300 h 2 relay 5 A 11 RUZ1A RE48A ML12MW * 1 selectable to instantaneous mode

Easy to Configure/Accurate settings/Plug-in/UL, CSA and GL Certified 6 Zelio Count Electronic and Electromechanical Counters

Electronic Electromechanical

■ LCD or LED display and fast ■ Mechanical display and slow input counter (≤ 7.5 kHz). input counter (≤ 25 kHz). ■ User-friendly display. ■ Permanent display. ■ Counting frequency. ■ Immunity against electrical ■ Configurable product (input and magnetic interference. type, mode, output…). ■ Economical solution. ■ Internal battery. ■ With or without reset to zero. ■ With or without reset to zero. ■ Two sizes: 24 x 48 mm and ■ Three sizes: 24 x 48 mm, 48 x 48 mm. 48 x 48 mm and 72 x 72 mm.

XBKH Range hour counters*

Counts elapsed time in hours and 1/100 hours and displays / updates values.

DISPLAY POWER SUPPLY FREQUENCYRESET DIMENSIONS CAT. NUMBERS 24 VAC 50 Hz without 48 x 48 mm XBKH70000004M Mechanical 7-digit 230 VAC 50 Hz without 48 x 48 mm XBKH70000002M LCD 8-digit Battery 1/100 h manual* 48 x 24 mm XBKH81000033E

XBKT Range totalizers*

Counts electrical pulses or contact and displays/updates value at each pulse; uni-directional.

DISPLAYPOWER SUPPLY FREQUENCYRESET DIMENSIONS CAT. NUMBERS 5-digit 24 VDC 20 Hz manual 41.5 x 31 mm XBKT50000U10M Mechanical 6-digit 24 VDC 10 Hz without 30 x 20 mm XBKT60000U00M 6-digit 24 VDC 25 Hz manual 60 x 50 mm XBKT60000U10M 8-digit 24 VDC 25 Hz without 60 x 50 mm XBKT80000U00M LCD 8-digit Battery 7.5 kHz manual* 48 x 24 mm XBKT81030U33E

XBKP Range multifunction counters*

Upcounts or downcounts electrical pulses or contact. Displays and updates value and transmits an electrical signal when preselected threshold is reached.

DISPLAY POWER SUPPLY FREQUENCY RESET TYPE DIMENSIONS PRESELECTIONS CAT. NUMBERS 24 VDC 5 kHz manual, electrical, automatic 48 x 48 mm 1 XBKP61130G30E 115 VAC 5 kHz manual, electrical, automatic 48 x 48 mm 1 XBKP61130G31E LCD 6-digit 230 VAC 5 kHz manual, electrical, automatic 48 x 48 mm 1 XBKP61130G32E 24 VDC 5 kHz manual, electrical, automatic 48 x 48 mm 2 XBKP61230G30E 115 VAC 5 kHz manual, electrical, automatic 48 x 48 mm 2 XBKP61230G31E 230 VAC 5 kHz manual, electrical, automatic 48 x 48 mm 2 XBKP61230G32E 24 VDC 5 kHz manual, electrical, automatic 48 x 48 mm 1 XBKP62130G30E LED 6-digit 230 VAC 5 kHz manual, electrical, automatic 48 x 48 mm 1 XBKP62130G32E 24 VDC 5 kHz manual, electrical, automatic 48 x 48 mm 2 XBKP62230G30E 230 VAC 5 kHz manual, electrical, automatic 48 x 48 mm 2 XBKP62230G32E * Not CSA certified. (For export only)

Simple/Rugged/UL listed 7 Zelio Control Monitoring and Control Relays

RM4UA/B Voltage ■ Under/overvoltage ■ DC motor overspeed ■ Network and power ■ Adjustable timing monitoring supply monitoring measurement ■ 50 mV - 500 V ■ Battery monitoring ■ Speed monitoring function

FUNCTIONS RANGESPOWER SUPPLY TIME RANGE OUTPUT CAT. NUMBERS U : 160...220 VAC U : 220...300 VAC 0.05 V... 0.5 V 24 VAC - 1 relay 8 A RM4 UA01B Overvoltage 0.3 V... 3 V 110...130 VAC - 1 relay 8 A RM4 UA01F 0.5 V... 5 V 220...240 VAC - 1 relay 8 A RM4 UA01M 1 V... 10 V 24 VAC - 1 relay 8 A RM4 UA02B Overvoltage 5 V... 50 V 110...130 VAC - 1 relay 8 A RM4 UA02F 10 V...100 V 220...240 VAC - 1 relay 8 A RM4 UA02M 30 V...300 V 24 VAC - 1 relay 8 A RM4 UA03B U Overvoltage 50 V...500 V 110...130 VAC - 1 relay 8 A RM4 UA03F 220...240 VAC - 1 relay 8 A RM4 UA03M 24...240 VAC/DC 0.05 to 30 s 2 relay 8 A RM4 UA31MW 0.05 V... 0.5 V 110...130 VAC 0.05 to 30 s 2 relay 8 A RM4 UA31F Undervoltage or overvoltage 0.3 V...3 V 220...240 VAC 0.05 to 30 s 2 relay 8 A RM4 UA31M 0.5 V...5 V 380...415 VAC 0.05 to 30 s 2 relay 8 A RM4 UA31Q 24...240 VAC/DC 0.05 to 30 s 2 relay 8 A RM4 UA32MW 1 V... 10 V 110...130 VAC 0.05 to 30 s 2 relay 8 A RM4 UA32F Undervoltage or overvoltage 5 V... 50 V 220...240 VAC 0.05 to 30 s 2 relay 8 A RM4 UA32M 10 V...100 V 380...415 VAC 0.05 to 30 s 2 relay 8 A RM4 UA32Q 24...240 VAC/DC 0.05 to 30 s 2 relay 8 A RM4 UA33MW 30 V...300 V Undervoltage or overvoltage 110...130 VAC 0.05 to 30 s 2 relay 8 A RM4 UA33F 50 V...500V 220...240 VAC 0.05 to 30 s 2 relay 8 A RM4 UA33M 380...415 VAC 0.05 to 30 s 2 relay 8 A RM4 UA33Q

RM4J Current ■ Under/overcurrent ■ Measurement of ■ Pump de-energizing ■ 3 mA - 15 A current drawn by a monitoring measurement ■ Adjustable timing 3-phase motor ■ Overtorque monitoring function ■ Heating and lighting ■ Mechanical brake and circuit monitoring clutch monitoring I

FUNCTIONS RANGESPOWER SUPPLY TIME RANGE OUTPUT CAT. NUMBERS 3 ... 30 mA 24 VAC - 1 relay 8 A RM4 JA01B Overcurrent 10 ... 100 mA 110 ... 130 VAC - 1 relay 8 A RM4 JA01F 0.1... 1A 220 ... 240 VAC - 1 relay 8 A RM4 JA01M 24... 240 VAC/DC 0.05 to 30 s 2 relay 8 A RM4 JA31MW 3 ... 30 mA Over or undercurrent 110 ... 130 VAC 0.05 to 30 s 2 relay 8 A RM4 JA31F 10 ... 100 mA 220 ... 240 VAC 0.05 to 30 s 2 relay 8 A RM4 JA31M 0.1... 1 A 380 ... 415 VAC 0.05 to 30 s 2 relay 8 A RM4 JA31Q 24... 240 VAC/DC 0.05 to 30 s 2 relay 8 A RM4 JA32MW 0.3 ...1.5 A 110 ... 130 VAC 0.05 to 30 s 2 relay 8 A RM4 JA32F Over or undercurrent 1 ... 5 A 220 ... 240 VAC 0.05 to 30 s 2 relay 8 A RM4 JA32M 3 ...15 A 380 ... 415 VAC 0.05 to 30 s 2 relay 8 A RM4 JA32Q

Simplicity/Performance/Compact Size/Safety/UL, CSA and GL Certified 8 Zelio Control Monitoring and Control Relays

RM4T Network ■ Phase sequence ■ Connection of mobile ■ Protection against risk ■ Phase loss equipment of a driving load monitoring ■ Unbalance ■ Protection of persons (phase loss) function ■ Voltage measurement and equipment against ■ Normal/emergency ■ Adjustable timing reverse operation source switching ■ 160 - 480 VAC ■ Sensitive networks

FUNCTIONS RANGESPOWER SUPPLY TIME RANGE OUTPUT CAT. NUMBERS Phase loss and sequence 220 - 440 VAC Self-powered - 2 relay 8 A RM4 TG20 Phase loss, sequence and undervoltage 160 - 220 VAC Self-powered 200...240 VAC - 2 relay 8 A RM4 TU01 300 - 430 VAC Self-powered 380...440 VAC - 2 relay 8 A RM4 TU02 < 198 V (fixed) Self-powered 220 VAC 0.1 to 10 s 2 relay 8 A RM4 TR33 > 242 V (fixed) < 360 V (fixed) Self-powered 400 VAC 0.1 to 10 s 2 relay 8 A RM4 TR34 Phase loss, sequence and undervoltage / > 440 V (fixed) overvoltage U : 220...300 VAC U : 420...480 VAC 5...15% Self-powered 200...240 VAC 0.5 s fixed 1 relay 8 A RM4 TA01 Phase loss, sequence and voltage 5...15% Self-powered 380...440 VAC 0.5 s fixed 1 relay 8 A RM4 TA02 unbalance 5...15% Self-powered 220...240 VAC 0.1 to 10 s 2 relay 8 A RM4 TA31 5...15% Self-powered 380...440 VAC 0.1 to 10 s 2 relay 8 A RM4 TA32

MPS and MPD relays (120 - 600 VAC)

FUNCTIONS RANGESPOWER SUPPLY MOUNTING OUTPUT CAT. NUMBERS 240V, 60Hz Self powered 240V, 60Hz 1 Relay, 5A 8430MPSV24 Phase loss, Voltage unbalance, Socket Mounted sequence, undervoltage 480V, 60Hz Self powered 480V, 60Hz 1 Relay, 5A 8430MPSV29 120V, 60Hz Self powered 120V, 60Hz 2 Relays 5A 8430MPDV20 Phase loss, Voltage unbalance, 240V, 60Hz Self powered 240V, 60Hz 2 Relays 5A 8430MPDV24 Surface Mounted sequence, undervoltage 480V, 60Hz Self powered 480V, 60Hz 2 Relays 5A 8430MPDV29 600V, 60Hz Self powered 600V, 60Hz 2 Relays 5A 8430MPDV32

RM4LA/G Liquid ■ 0.25 - 500 K ohms ■ Conduction liquid level ■ Overfill sensing ■ Adjustable timing regulation ■ Filling/emptying level ■ 24 - 240 VDC ■ Protection of pumps function ■ 25 - 415 VAC and heaters against running dry

FUNCTIONS RANGESPOWER SUPPLY TIME RANGE OUTPUT CAT. NUMBERS 24 VAC - 1 relay 8 A RM4 LG01B Filling or emptying 5...100 K 110 ... 130 VAC - 1 relay 8 A RM4 LG01F 220 ... 240 VAC - 1 relay 8 A RM4 LG01M 24 ... 240 VAC/DC - 2 relays 8 A RM4 LA32MW 0.25... 5 K 110 ... 130 VAC 0.1 to 10 s 2 relays 8 A RM4 LA32F Filling or emptying 2.5... 50 K 220 ... 240 VAC 0.1 to 10 s 2 relays 8 A RM4 LA32M 25... 500 K 380 ... 415 VAC 0.1 to 10 s 2 relays 8 A RM4 LA32Q Suspended probe 1 electrode + 1 réf - by RM4 L.... - - LA9 RM201 Protected suspended probe - by RM4 L.... - - RM79 696 043

Simplicity/Performance/Compact Size/Safety/UL, CSA and GL Certified 9 Zelio Analogue Analogue Interfaces

Zelio Analogue Converter and Transmitter

■ Pre-calibration of input and output ranges facilitate installation. ■ High repeatability of output signals as a function of input signal. ■ Outputs protected against polarity inversion, short-circuit and overvoltage. ■ Loop breakdown protection. ■ Sealable protective cover. ■ Conforms to UL/CSA/GL/EC standards. ■ DIN rail or screw mounted.

IP1 IP2 2-Wire PT100 RMPT Converters for PT 100 probes IP3 IP4 2mA 19..30VDC IP1 IP1 A1 IP2 IP2 V0 ■ 3-Wire PT100 Converts the ohmic resistance 2, 3 or 4 wire PT 100 IP3 IP3 IP4 IP4 OPG A2 probes to standard. IP1 0VDC ■ A preset temperature range for the inputs depending on IP2 PT100 4-Wire IP3

IP4 the model. ■ Switchable output of 0 - 10V, 0 - 20mA and 4 - 20mA. ■ Optimum Pt100 converters have an output of 0-10V only.

Universal INPUT / SCALE (Temp. Range) OUTPUT (Output Range)DIMENSIONS (H/W/D - mm) POWER SUPPLY (Voltage) CAT. NUMBERS -40°…40° 0…10 V / 0…20 mA / 22.5 / 80 / 80 24 V DC Non Isolated RMPT10BD PT 100 -40°…104°F 4…20 mA Switchable -100°…100°C 0…10 V / 0…20 mA / 22.5 / 80 / 80 24 V DC Non Isolated RMPT20BD -148°…212°F 4…20 mA Switchable 0°…100°C 0…10 V / 0…20 mA / 22.5 / 80 / 80 24 V DC Non Isolated RMPT30BD 32°…212°F 4…20 mA Switchable 0°…250°C 0…10 V / 0…20 mA / 22.5 / 80 / 80 24 V DC Non Isolated RMPT50BD 32°…482°F 4…20 mA Switchable 0°…500°C 0…10 V / 0…20 mA / 22.5 / 80 / 80 24 V DC Non Isolated RMPT70BD 32°…932°F 4…20 mA Switchable

Optimum INPUT / SCALE (Temp. Range) OUTPUT (Output Range)DIMENSIONS (H/W/D - mm) POWER SUPPLY (Voltage) CAT. NUMBERS -40°…40°C 0…10 V 22.5 / 80 / 80 24 V DC Non Isolated RMPT13BD PT 100 -40°…104°F -100°…100°C 0…10 V 22.5 / 80 / 80 24 V DC Non Isolated RMPT23BD -148°…212°F 0°…100°C 0…10 V 22.5 / 80 / 80 24 V DC Non Isolated RMPT33BD 32°…212°F 0°…250°C 0…10 V 22.5 / 80 / 80 24 V DC Non Isolated RMPT53BD 32°…482°F 0°…500°C 0…10 V 22.5 / 80 / 80 24 V DC Non Isolated RMPT73BD 32°…932°F

10 Compact/Simple/Choice of outputs/UL, CSA and GL certified Zelio Analogue Analogue Interfaces

RMT Converters for J & K type thermocouple 19..30VDC A1 V0 Type K IP1 (+) ■ Converts the voltage signal from J & K type thermocouple to IP2 (-) OPG standard signals. These converters have cold junction A2 compensation to allow detection of errors induced by 0VDC connection to the device itself. The converters have a preset temperature range for the inputs depending on the model and a switchable output of 0 - 10 V, 0 - 20 mA and 4 - 20 mA.

INPUT / SCALE (Temp. Range) OUTPUT (Output Range)DIMENSIONS (H/W/D - mm) POWER SUPPLY (Voltage) CAT. NUMBERS 0°…150°C 0…10 V / 0…20 mA / 22.5 / 80 / 80 24 V DC Non Isolated RMTJ40BD 32°…302°F 4…20 mA Switchable 0°…300°C 0…10 V / 0…20 mA / 22.5 / 80 / 80 24 V DC Non Isolated RMTJ60BD 32°…572°F 4…20 mA Switchable 0°…600°C 0…10 V / 0…20 mA / 22.5 / 80 / 80 24 V DC Non Isolated RMTJ80BD 32°…1112°F 4…20 mA Switchable 0°…600°C 0…10 V / 0…20 mA / 22.5 / 80 / 80 24 V DC Non Isolated RMTK80BD 32°…1112°F 4…20 mA Switchable 0°…1200°C 0…10 V / 0…20 mA / 22.5 / 80 / 80 24 V DC Non Isolated RMTK90BD 32°…2192°F 4…20 mA Switchable

RMC voltage/current converters

■ Allows adaptation of electrical values (voltage/current). Four products are available: a cost effective converter will convert 0...10 V signal to a 4...20 mA signal or vice-versa; a universal voltage/current converter converts the most common signals; 19..30VDC 4..20mA A1 V0 I1 and two universal voltage/current converters for the IPG OPG A2 conversion of AC as well as DC power signals. 0VDC 19..30VDC A1 I0 0..10V V1 IPG OPG 19..30VDC A2 A1 A2 0VDC

0VDC V1 V0 V2 19..30VDC V3 OPG A1 A2 IPG INPUT / SCALE OUTPUT (Output Range)DIMENSIONS (H/W/D - mm) POWER SUPPLY (Voltage) CAT. NUMBERS 0VDC I1 V0 I2 I01 0…10 V or 4…20mA 0…10 V or 4…20 mA 22.5 / 80 / 80 24 V DC Non Isolated RMCN22BD I3 I02 0…10 V / 0…20 mA / 0…10 V / -10…+10 V / 22.5 / 80 / 80 24 V DC Non Isolated RMCL55BD 4…20 mA 0…20 mA / 4…20 mA Switchable 19..30VDC A2 0…50 V / 0…300 V / 0…10 V / 0…20 mA / A1 22.5 / 80 / 80 24 V DC Non Isolated RMCV60BD 0VDC 0…500 V 4…20 mA Switchable

V1 V0 0…1.5 A / 0…5 A / 0…10 V or 0…20 mA I I1 V 45 / 80 / 80 24 V DC Non Isolated RMCA61BD OPG IPG 0…15 A or 4…20 mA

Compact/Accurate/Universal/UL, CSA and GL certified 11 Simply Smart!

The efficiency of Telemecanique branded solutions

Used in combination, Telemecanique products provide quality solutions, meeting all your automation and control applications requirements.

Software tools Operator dialog Motion control Networks & Communication

Interfaces & I/O Automation Motor control

Detection Power supplies

Mounting systems

A unique partner and a worldwide presence

Worldwide availability ■ More than 5,000 points of sale in 130 countries. ■ You can be sure to find a range of products that meets your needs and fully complies with the standards in the country in which they are used.

Schneider Electric’s regional focus ■ 200 dedicated sales engineers operate from 22 regional sales centres and 13 technical service centres across Canada. ■ Our sales engineers are skilled at assessing individual requirements. Combined with the expert support of our product specialists, they will develop the most effective and economical solution for you, taking relevant regulations and standards into account.

Schneider Electric Head Office 19 Waterman Avenue Toronto, Ontario M4B 1Y2 www.schneider-electric.ca Tel: (416) 752-8020

Fax: (416) 752-8944 © 2005 Schneider Canada Inc., All Rights Reserved Customer Service: 1-800-565-6699 T9050BR0501EP R0 July 2005