Specification Sheet • Single Jacket Mill Hose - 250 • Double Jacket Contractors Hose - 400 • Rubber Lined Visit us on the Web: www.keyfire.com • 1”, 11/2”, 2”, 21/2”, 3”, 4” a Scope a Single Jacket Hydrostatic Testing Quality: The assembly supplied under this spec- Stock Lengths: Standard lengths are 50, 75 and 100 feet. 1 1 ification shall be constructed with superior quality materi- Size 1” 1 /2” 2” 2 /2”3”4” als. NFPA 1961 standards shall be observed in production Part Number SP10-MHH SP15-MHH SP20-MHH SP25-MHH SP30-MHH SP40-MHH of the assembly, in order to ensure its quality and durability. Test 250psi 250psi 250psi 250psi 250psi 250psi Service Life: Hose furnished under these specifications Service Test Pressure 125psi 125psi 125psi 125psi 125psi 125psi will have a potential service life warranty of not less than Elongation 4% 5% 6% 7% 8% 8% one year; barring mistreatment that would render it unfit Burst Test 500psi 500psi 500psi 500psi 450psi 450psi for service. Upon delivery, the hose shall be free from Kink Test 250psi 250psi 250psi 250psi 250psi 250psi defects in workmanship and materials. Any defective hose will be replaced at no charge whatsoever. a Single Jacket Weights and Measures a Jacket Construction Size 1” 11/2” 2” 21/2”3”4” The jackets will be woven evenly and be free of defects, Part Number SP10-MHH SP15-MHH SP20-MHH SP25-MHH SP30-MHH SP40-MHH

including knots, lumps, or unsightly disfigurations that Bowl Size 11/4”13/4” 23/8”213/16”33/8”43/8” Weight per 50’ length could jeopardize the integrity of the hose assembly. The Uncoupled 8 lbs. 12 lbs. 18 lbs. 21 lbs. 29 lbs. 32 lbs. warp yarn shall consist of staple polyester yarn. The use of Weight per 50’ length Coupled 10 lbs. 13 lbs. 20 lbs. 23 lbs. 31 lbs. 41 lbs. filament or entangled yarn is expressly forbidden due to the lack of inherent abrasion resistance. The filler yarns a Double Jacket Contractors Hose shall be constructed of high strength, low elongation, fila- Hydrostatic Testing ment polyester to reduce weight and increase flexibility. Stock Lengths: Standard lengths are 50, 75 and 100 feet.

1 1 a Abrasion Impregnation Size 1 /2” 2” 2 /2” Part Number DP15-MHH DP20-MHH DP25-MHH Hose assemblies are available with polymer impregnation Test Pressure 400psi 400psi 400psi that provide additional abrasion resistance. Colors include: yellow, orange, red, tan, black, blue and green. Color shall Service Test Pressure 200psi 200psi 200psi be pure and even in each hose. Impregnated hose shall meet Elongation 5% 7% 8% the requirements of Mil-H-24606B for abrasion resistance. Burst Test 600psi 600psi 600psi Kink Test 400psi 400psi 400psi a Lining The rubber lining shall be a single-ply extruded of a Double Jacket Contractors Hose synthetic rubber compounded to resist ozone. The fin- Weights and Measures

ished form shall be free of pits or other imperfections and Size 11/2” 2” 21/2” have a smooth finish. No reclaimed rubber shall be used. Part Number DP15-MHH DP20-MHH DP25-MHH

Plastic tubes that sacrifice durability of the hose life for the Bowl Size 115/16” 21/2”3” sake of weight are not acceptable. Weight per 50’ length 17 lbs. 25 lbs. 28 lbs. The backing shall be of adequate thickness to Uncoupled Backing: Weight per 50’ length create a smooth waterway but not greater than .020. The Coupled 18 lbs. 27 lbs. 30 lbs. fire hose constructed under this specification shall be man- ufactured fully backed. Key Fire Hose reserves the right to modify any specification without prior notice to meet or exceed changing standards. Customers are advised that special diameters or construction a Couplings characteristics can be produced on special request. For more As required by purchaser, expansion ring threaded, STORZ information, please contact your Key Fire Hose Corporation clamp ring, etc. authorized distributor.

PHONE 1-800-447-5666 • FAX 1-800-447-5664 • E-MAIL [email protected]

KF-004 02/04 Specification Sheet • Single Jacket 300 Pound Test • Rubber Lined • 11/2”, 2”, 21/2”, 3”, 4” Visit us on the Web: www.keyfire.com a Scope a Hydrostatic Testing Quality: The fire hose assembly supplied under this spec- Stock Lengths: Standard lengths are 50, 75 and 100 feet.

ification shall be constructed with superior quality materi- 1 1 Size 1/2” 2” 2 /2”3”4” als. NFPA 1961 standards shall be observed in production Part Numbers SP15-300 SP20-300 SP25-300 SP30-300 SP40-300 of the assembly, in order to ensure its quality and durability. Test Pressure 300psi 300psi 300psi 300psi 300psi Service Life: Hose furnished under these specifications will have a potential service life warranty of not less than Elongation 5% 6% 7% 8% 8% five years; barring mistreatment that would render it Twist per foot 64° right 64° right 25° right 25° right 20° right unfit for service. Upon delivery, the hose shall be free from Warp 10” 10” 10” 10” 10” defects in workmanship and materials. Any defective hose Rise 3” 2” 1” 0” 0” will be replaced at no charge whatsoever. Burst Test 650psi 650psi 650psi 550psi 500psi Kink Test 300psi 300psi 300psi 300psi 300psi a Jacket Construction The jackets will be woven evenly and be free of defects, a Finished Hose including knots, lumps, or unsightly disfigurations that Markings: Beginning at a point not less than four could jeopardize the integrity of the hose assembly. The feet from the end, each fifty foot section shall be sten- warp yarn shall consist of staple polyester yarn. The use of cilled in indelible ink with letters at least one inch filament or entangled yarn is expressly forbidden due to high stating the name of the manufacturer, month the lack of inherent abrasion resistance. The filler yarns and year of manufacture, and service test to 150 PSI shall be constructed of high strength, low elongation, fila- per NFPA 1962. The ink used will be of a contrasting ment polyester to reduce weight and increase flexibility. color. a Abrasion Impregnation Methods of Testing: All measurements and tests Hose assemblies are available with polymer impregnation necessary to determine compliance of the fire hose spec- that provide additional abrasion resistance. Colors include: ified requirements shall be made with ASTM, UL and yellow, orange, red, tan, black, blue and green. Color shall NFPA 1961 designation, unless otherwise prescribed. be pure and even in each hose. Impregnated hose shall meet a Weights and Measures

the requirements of Mil-H-24606B for abrasion resistance. 1 1 Size 1 /2”* 2”* 2 /2”* 3”* 4”* a Lining Part Numbers SP15-300 SP20-300 SP25-300 SP30-300 SP40-300 The rubber lining shall be a single-ply extruded tube of Bowl Size 113/16”2 3/8”213/16”33/8”43/8” Weight per 50’ length synthetic EPDM compounded to resist ozone. The fin- Uncoupled 11 lbs. 15 lbs. 23 lbs. 25 lbs. 37 lbs. Weight per 50’ length ished form shall be free of pits or other imperfections and Coupled 13 lbs. 16 lbs. 24 lbs. 27 lbs. 41 lbs. have a smooth finish. No reclaimed rubber shall be used. *Available with a UL label add-on. tubes that sacrifice durability of the hose life for the sake of weight are not acceptable. a Couplings Backing: The backing shall be of adequate thickness to As required by purchaser, expansion ring threaded, STORZ create a smooth waterway but not greater than .020. The clamp ring, etc. fire hose constructed under this specification shall be man- Key Fire Hose reserves the right to modify any specification ufactured fully backed. without prior notice to meet or exceed changing standards. Tensile Strength & Ultimate Elongation: Shall Customers are advised that special diameters or construction meet the standards of Underwriters Laboratories, Inc.TM as characteristics can be produced on special request. For more well as all other properties of UL-19 for rubber lined hoses. A valid U.S. Underwriters inspection procedure shall be information, please contact your Key Fire Hose Corporation in force at the time of bid. authorized distributor.

PHONE 1-800-447-5666 • FAX 1-800-447-5664 • E-MAIL [email protected]

KF-003 02/04 Specification Sheet • Single Jacket 500 Pound Test • Rubber Lined Visit us on the Web: www.keyfire.com • 1”, 11/2”, 13/4”, 2”, 21/2”, 3” a Scope A valid U.S. Underwriters inspection procedure shall be in force at the time of bid. Quality: The fire hose assembly supplied under this spec- ification shall be constructed with superior quality materi- a Hydrostatic Testing als. NFPA 1961 standards shall be observed in production Stock Lengths: Standard lengths are 50, 75 and 100 feet. of the assembly, in order to ensure its quality and durability. 1 3 1 Service Life: Hose furnished under these specifications Size 1” 1 /2” 1 /4”2”2/2”3” will have a potential service life warranty of not less than Part Numbers SP10-500 SP15-500SP17-500 SP20-500 SP25-500 SP30-500 five years; barring mistreatment that would render it Test Pressure 500psi 500psi 500psi 500psi 500psi 400psi unfit for service. Upon delivery, the hose shall be free from Elongation 4% 5% 6% 6% 7% 8% Twist per foot 71° right 64° right 64° right 64° right 25° right 25° right defects in workmanship and materials. Any defective hose Warp 10” 10” 10” 10” 10” 10” will be replaced at no charge. Rise 4” 3” 2” 1” 0 0 a Jacket Construction Burst Test 800psi 800psi 800psi 750psi 750psi 750psi Kink Test 500psi 400psi 350psi 350psi 350psi 300psi The jackets will be woven evenly and be free of defects, including knots, lumps, or unsightly disfigurations that a Finished Hose could jeopardize the integrity of the hose assembly. The Markings: Beginning at a point not less than four feet warp yarn shall consist of staple polyester yarn. The use of from the end, each fifty foot section shall be stencilled filament or entangled yarn is expressly forbidden due to in indelible ink with letters at least one inch high stat- the lack of inherent abrasion resistance. The filler yarns ing the name of the manufacturer, month and year of shall be constructed of high strength, low elongation, fila- manufacture, and service test to 250 PSI per NFPA ment polyester to reduce weight and increase flexibility. 1962. The ink used will be of a contrasting color. Methods of Testing: All measurements and tests nec- a Abrasion Impregnation essary to determine compliance of the fire hose specified requirements shall be made with ASTM, UL and NFPA Hose assemblies are available with polymer impregnation 1961 designation, unless otherwise prescribed. that provide additional abrasion resistance. Colors include: yellow, orange, red, tan, black, blue and green. Color shall a Weights and Measures

be pure and even in each hose. Impregnated hose shall meet 1 3 1 Size 1” 1 /2”* 1 /4”* 2”* 2 /2”* 3” the requirements of Mil-H-24606B for abrasion resistance. Part Numbers SP10-500 SP15-500 SP17-500 SP20-500 SP25-500 SP30-500

1 3 15 3 13 3 Bowl Size 1 /4” 1 /4” 1 /16”2/8”2/16”3/8” a Lining Weight per 50’ length 9 lbs. 13 lbs. 18 lbs. 21 lbs. 24 lbs. 32 lbs. Uncoupled The rubber lining shall be a single-ply extruded tube of Weight per 50’ length 11 lbs. 14 lbs. 19 lbs. 22 lbs. 25 lbs. 35 lbs. synthetic EPDM compounded to resist ozone. The fin- Coupled ished form shall be free of pits or other imperfections and *Available with a UL label add-on. have a smooth finish. No reclaimed rubber shall be used. a Couplings Plastic tubes that sacrifice durability of the hose life for the As required by purchaser, expansion ring threaded, STORZ sake of weight are not acceptable. clamp ring, etc. Backing: The backing shall be of adequate thickness to Key Fire Hose reserves the right to modify any specification create a smooth waterway but not greater than .020. The fire hose constructed under this specification shall be man- without prior notice to meet or exceed changing standards. ufactured fully backed. Customers are advised that special diameters or construction Tensile Strength & Ultimate Elongation: Shall characteristics can be produced on special request. For more meet the standards of Underwriters Laboratories, Inc.TM as information, please contact your Key Fire Hose Corporation well as all other properties of UL-19 for rubber lined hoses. authorized distributor.

PHONE 1-800-447-5666 • FAX 1-800-447-5664 • E-MAIL [email protected]

KF-007 02/ 04 Specification Sheet • Double Jacket 600 Pound Test • Rubber Lined • 11/2”, 13/4”, 2”, 21/2”, 3”, 4” Visit us on the Web: www.keyfire.com a Scope a Hydrostatic Testing Quality: The fire hose assembly supplied under this spec- Stock Lengths: Standard lengths are 50, 75 and 100 feet. ification shall be constructed with superior quality materials.

NFPA 1961 standards shall be observed in production of the Size 11/2” 13/4” 2” 21/2” 3” 4” assembly, in order to ensure its quality and durability. Part Number Service Life: Hose furnished under these specifications DP15-600 DP17-600 DP20-600 DP25-600 DP30-600 DP40-600 will have a potential service life warranty of not less than Test Pressure 600psi 600psi 600psi 600psi 600psi 600psi ten years; barring mistreatment that would render it unfit Elongation 6% 6% 6% 6% 7% 8% o o o o o o for service. Upon delivery, the hose shall be free from Twist per foot 15 right 15 right 10 right 10 right 8 right 71/2 right defects in workmanship and materials. Any defective hose Warp 10” 10” 10” 10” 10” 10” will be replaced at no charge whatsoever. Rise 0 0 0 0 0 0 Burst Test 1000psi 1000psi 1000psi 1000psi 1000psi 1000psi a Jacket Construction Kink Test 500psi 500psi 500psi 500psi 450psi 400psi The jackets will be woven evenly and be free of defects, including knots, lumps, or unsightly disfigurations that a could jeopardize the integrity of the hose assembly. The Finished Hose warp yarn shall consist of staple polyester yarn. The use of Markings: Beginning at a point not less than four feet filament or entangled yarn is expressly forbidden due to from the end, each fifty foot section shall be stencilled the lack of inherent abrasion resistance. The filter yarns in indelible ink with letters at least one inch high stat- shall be constructed of high strength, low elongation, fila- ing the name of the manufacturer, month and year of ment polyester to reduce weight and increase flexibility. manufacture, and service test to 300 PSI. The ink will a Abrasion Impregnation be of a contrasting color. Hose assemblies are available with polymer impregnation Methods of Testing: All measurements and tests that provide additional abrasion resistance. Colors include: necessary to determine compliance of the fire hose spec- yellow, orange, red, tan, black, blue and green. Color shall ified requirements shall be made with ASTM, UL and be pure and even in each hose. Impregnated hose shall NDPA 1961 designation, unless otherwise prescribed. meet the requirements of Mill-H-24606B for abrasion Couplings: As required by purchaser, expansion ring resistance. threaded, STORZ clamp ring, etc. a Lining a Weights & Measures The rubber lining shall be a single-ply extruded tube of synthetic EPDM compounded to resist ozone. The finish Size 11/2”* 13/4”* 2”* 21/2”* 3”* 4”* form shall be free of pits or other imperfections and have a smooth finish. No reclaimed rubber shall be used. Plastic Part Number DP15-600 DP17-600 DP20-600 DP25-600 DP30-600 DP40-600 tubes that sacrifice durability of the hose life for the sake Bowl Size 115/16” 21/8” 21/2” 3” 3 9/16” 49/16” of weight are not acceptable. Weight per 50’ 17 lbs. 19 lbs. 25 lbs. 28 lbs. 38 lbs. 53 lbs. Backing: The backing shall be of adequate thickness to length Uncoupled create a smooth waterway but not greater than .020. The Weight per 50’ 18 lbs. 20 lbs. 27 lbs. 30 lbs. 41 lbs. 59 lbs. fire hose constructed under this specification shall be man- length Coupled

ufactured fully backed using a calendered EPDM. The use *Available with a UL label add-on of adhesives of any kind are acceptable and expressly for- bidden. Key Fire hose reserves the right to modify any specification Tensile Strength & Ultimate Elongation: Shall without prior notice to meet or exceed changing standards. meet the standards of Underwriters Laboratories, Inc.TM as Customers are advised that special diameters or construction well as all other properties of UL-19 for rubber lined characteristics can be produced on special request. For more hoses. A valid U.S. Underwriters inspection procedure information, please contact your Key Fire Hose Corporation shall be in force. authorized distributor.

PHONE 1-800-447-5666 • FAX 1-800-447-5664 • E-MAIL [email protected] KF-008 02/ 04 Key-Lite Specification Sheet POTABLE • Double Jacket 600 Pound Test • lined Visit us on the Web: www.keyfire.com • 11/2”, 21/2” and 4” a Scope a Hydrostatic Testing Quality: The fire hose assembly supplied under this speci- Stock Lengths: Standard lengths are 50 and 100 feet.

1 1 fication shall be constructed with superior quality materials. Size 1/2” 2 /2” 4” NFPA 1961 standards shall be observed in production of the Test Pressure 600psi 600psi 600psi assembly, in order to ensure its quality and durability. Elongation 6% 6% 8%

Service Life: Hose furnished under these specifications Twist per foot 15˚ right 10˚ right 71/2˚ right will have a potential service life warranty of not less than Warp 10” 10” 10” two years; barring mistreatment that would render it Rise 000 unfit for service. Upon delivery, the hose shall be free from Burst Test 900psi 900psi 900psi defects in workmanship and materials. Any defective hose Kink Test 500psi 500psi 400psi will be replaced at no charge whatsoever. a Finished Hose a Jacket Construction Markings: Beginning at a point not less than four feet The jackets will be woven evenly and be free of defects, from the end, each fifty foot section shall be stencilled in including knots, lumps, or unsightly disfigurations that could indelible ink with letters at least one inch high stating jeopardize the integrity of the hose assembly. The warp yarn the name of the manufacturer, month and year of shall consist of staple polyester yarn. The use of filament or manufacture, and service test to 300 PSI. The ink used entangled yarn is expressly forbidden due to the lack of inher- will be of a contrasting color. ent abrasion resistance. The filler yarns shall be constructed Methods of Testing: All measurements and tests of high strength, low elongation, filament polyester to reduce necessary to determine compliance of the fire hose weight and increase flexibility. specified requirements shall be made with ASTM, UL and NFPA 1961 designation, unless otherwise prescribed. a Abrasion Impregnation Hose assemblies are available with polymer impregnation a Couplings that provide additional abrasion resistance. Colors include: As required by purchaser, expansion ring threaded, yellow, orange, red, tan, black, blue and green. Color shall be STORZ clamp ring, etc. pure and even in each hose. Impregnated hose shall meet the requirements of Mil-H-24606B for abrasion resistance. a Weights and Measures a Lining Size 11/2” 21/2” 4” Part Number DP15-600PU DP25-600PU DP40-600PU The lining shall be a single-ply extruded tube of synthetic Bowl Size 115/16” 3” 4 9/16” polyurethane to resist ozone. The polyurethane tube shall Weight per 50’ length. Uncoupled. 14 lbs. 22 lbs. 40 lbs. adhere to the jacket to prevent delamination. The finished product will meet and exceed all potable water Mil-H-24606B Key Fire Hose reserves the right to modify any specification without standards for the manufacturing of lightweight fire hose. The prior notice to meet or exceed changing standards. Customers are use of the polyurethane lined fire hose is designed to advised that special diameters or construction characteristics can be increase packing ability and applications where lightweight produced on special request. For more information, please contact fire hose is desired. your Key Fire Hose Corporation authorized distributor.

PHONE 1-800-447-5666 • FAX 1-800-447-5664 • E-MAIL [email protected] KF-010 01/ 04 Combat LDH-600 Specification Sheet • Rubber Covered Hose • 4” & 5” Hi-Pressure Attack Hose Visit us on the Web: www.keyfire.com a Hose Construction a Ozone Resistance Hose shall be made from 100 percent high tenacity synthetic Hose shall show no visible signs of cracking to the lin- yarn, circularly woven and completely protected and locked-in ing or cover when tested in accordance to ASTM D518 by tough highly resistant synthetic nitrile rubber, forming a sin- Procedure B, 100pphm/118°F/70 hours. gle homogeneous construction without the use of glues or adhesives of any type. Meeting all requirements of NFPA 1961. a Chemical Resistance Warranty: Hose shall carry a five year written warranty. Exposure to sea water and contamination by most chem- a Lining Properties ical substances, hydrocarbons, oils, alkalis, acids and Ultimate Tensile Strength: greases must have no effect on the short or long term per- Tensile strength of the lining and cover shall not be less formance of the hose. A chemical resistance chart is avail- than 1750 PSI. able and Key Fire Hose will supply specific chemical resist- Ultimate Elongation: ance data on request of purchaser for unique applications. 500 percent minimum. Accelerated Aging Test: a Heat Resistance The tensile strength and ultimate elongation of the vul- The hose, when subjected to a static pressure of 100 PSI, canized rubber compound which has been subjected to shall be capable of withstanding a surface temperature of the action of oxygen at a pressure of 300 PSI (±10 PSI) 1200°F for a minimum of two minutes without rupture and a temperature of 158°(±18°F) for a period of 96 hours or damage to the synthetic reinforcement. shall retain 60 percent of its originally stated properties. a Hose Weight and Coil Diameters a Hydrostatic Pressure Tests The hose shall conform to the following average weights Service Test Acceptance Burst Part # Diameter and diameters. Pressure Test Pressure Pressure

RC40-600G 4” 300psi 600psi 900psi Weight Coil Size Part # Diameter per foot Uncoupled RC50-600G 5” 300psi 600psi 900psi uncoupled 100’ Lengths RC40-600G 4” .93lbs 26” RC50-600G 5” 1.25 lbs 29” a Abrasion Resistance Hose shall withstand 30,000 cycles on the Taber Abrasion a Color Machine (H-22 Wheel: 1 kg). Key Fire Hose Corporation on The color shall be a HI-VISIBILITY keylime green. request will supply written warranties that this hose meets a minimum 30,000 cycles. Other abrasion test results (UL, DIN, etc.) can be supplied on request of purchaser. a Couplings As required by purchaser, expansion ring threaded, a Cold Resistance STORZ clamp ring, etc. Hose shall have a capability of use down to -35°F. Hose shall have no apparent damage to cover, reinforcement or lining Special orders requiring unusual diameters or when subjected to the following cold bending test: a 50 ft. construction characteristics can be produced by length of dry hose is to be firmly coiled and placed in a cold box request. Contact our customer service representatives at -35°F for a duration of 24 hours. Immediately after removal of the hose from the box, hose should be uncoiled and laid out for all your needs. *Key Fire Hose Corp. reserves the by one operator. Following this procedure, the hose shall not right to modify any specification without prior notice to leak nor show any damage to the reinforcement when sub- meet changing NFPA standards. jected to the hydrostatic acceptance test stated above.

PHONE 1-800-447-5666 • FAX 1-800-447-5664 • E-MAIL [email protected]

05/ 03 Dura-Flow Specification Sheet • Rubber Covered Hose • 1”, 11/2”, 13/4”, 2”, 21/2” and 3”

Visit us on the Web: www.keyfire.com a Hose Construction by one operator. Following this procedure, the hose shall not leak nor show any damage to the reinforcement when sub- Hose shall be made from 100 percent high tenacity synthetic jected to the hydrostatic acceptance test stated above. yarn, circularly woven and completely protected and locked-in by tough highly resistant synthetic nitrile rubber, forming a sin- a Ozone Resistance gle homogeneous construction without the use of glues or Hose shall show no visible signs of cracking to the lin- adhesives of any type. Meeting all requirements of NFPA 1961. ing or cover when tested in accordance to ASTM D518 Warranty: Hose shall carry a five year written warranty. Procedure B (100pphm/118°F/70 hours). a Lining Properties a Chemical Resistance Ultimate Tensile Strength: Exposure to sea water and contamination by most chem- Tensile strength of the lining and cover shall not be less ical substances, hydrocarbons, oils, alkalis, acids and than 1500 PSI. greases must have no effect on the short or long term per- Ultimate Elongation: formance of the hose. A chemical resistance chart is avail- 400 percent minimum. able and Key Fire Hose will supply specific chemical resist- Accelerated Aging Test: ance data on request of purchaser for unique applications. The tensile strength and ultimate elongation of the vul- a canized rubber compound which has been subjected to Heat Resistance the action of oxygen of a pressure of 300 PSI (±10PSI) and The hose, when subjected to a static pressure of 100 PSI, a temperature of 158°(±18°)F for a period of 96 hours shall be capable of withstanding a surface temperature of shall retain 60 percent of its originally stated properties. 1200°F for a minimum of two minutes without rupture or damage to the synthetic reinforcement. a Hydrostatic Testing a Hose Weight and Coil Diameters Part Service Test Acceptance Burst Diameter The hose shall conform to the following average weights Number Pressure Test Pressure Pressure and diameters RC10-600 1” 300psi 600psi 900psi Part Weight per Coil Size - Coupled 1 Diameter RC15-600 1/2” 300psi 600psi 900psi Number Length (Coupled) per 50’ Lengths

3 RC17-600 1 /4” 300psi 600psi 900psi RC10-600 1” 10 lbs 16 in.

1 RC20-600 2” 300psi 600psi 900psi RC15-600 1/2” 12 lbs 16 in.

1 3 RC25-600 2 /2” 300psi 600psi 900psi RC17-600 1 /4” 14 lbs 17 in.

RC30-600 3” 300psi 600psi 800psi RC20-600 2” 16 lbs 17 in.

1 RC25-600 2 /2” 24 lbs 18 in.

RC30-600 3” 30 lbs 18 in. a Abrasion Resistance Hose shall withstand 30,000 cycles on the Taber Abrasion a Color Machine (H-22 Wheel: 1 kg). Key Fire Hose Corporation on The color shall be of HI-VISIBILITY yellow or red. request will supply written warranties that DURA-FLOW hose Other color available are: blue, orange and green. meets a minimum 30,000 cycles. Other abrasion test results (UL, DIN, etc.) can be supplied on request of purchaser. a Couplings As required by purchaser, expansion ring threaded, a Cold Resistance STORZ clamp ring, etc. Hose shall have a capability of use down to -35°F. Hose shall Key reserves the right to modify any specification with- have no apparent damage to cover, reinforcement or lining out prior notice to meet or exceed changing standards. when subjected to the following cold bending test: a 50 ft. Customers are advised that special diameters or con- length of dry hose is to be firmly coiled and placed in a cold box struction characteristics can be produced on special at -35°F for a duration of 24 hours. Immediately after removal request and you are requested to contact Key Fire Hose of the hose from the box, hose should be uncoiled and laid out Corporation, Miami, Florida.

PHONE 1-800-447-5666 • FAX 1-800-447-5664 • E-MAIL [email protected] KF-012 01/ 04 Reel-Lite 600/800 Specification Sheet Visit us on the Web: www.keyfire.com • Lightweight Booster Hose

A multi-purpose, lightweight, rigid 1” diameter attack hose ᭤ Characteristics that meets the needs of industrial, municipal and forestry Hose Size 1”(38 mm) market applications. Reel-lite 600 features an abrasion resistant all polyester cover with a polyurethane coating. Part Number RB10-800R/RB10-600R Reel-lite 800 is a uniquely constructed product which fea- Test Pressure 800 PSI tures a nitrile rubber cover for heat and abrasion resistance. Weight 50’ Coupled 10 LBS Both products are constructed with a special helical interior Recommended Reel Size 12” minimum reinforcement to retain its rigid shape. This thin-walled E.P.D.M. rubber lined hose, is the most durable lightweight ᭤ Color booster hose on the market. The color shall be red.

᭤ Hose Construction • Normal service conditions in temperature range from Circular woven, single jacket, combined with a helical interior reinforcement, and a all polyester or nitrile –50°F to 112°F rubber cover. • Heat resistant up to 1200°F *RB10-800R only • UL abrasion test of 15,000 cycles minimum ᭤ Tube • Minimum working pressure of 400 PSI Extruded E.P.D.M. rubber liner for age, ozone and • Service test to 800 PSI chemical resistance. • Maximum burst pressure of 1200 PSI • Pliable and abrasion resistant cover ᭤ Internal Diameter • Lightweight and kink resistant One inch (38 mm) • 1-Year warranty against defects in material and work- manship ᭤ Bowl Size 1 5/16” Reel & available upon special request.

᭤ Length Contact our sales representatives for Available in 50’ to 200’ continuous lengths. more information.

᭤ Couplings Field replaceable coupling with a one inch NH thread standard. Aluminum internal expansion ring coupling available upon request.

PHONE 1-800-447-5666 • FAX 1-800-447-5664 • E-MAIL [email protected] KF-092 06/05 Reel-Lite www.keyfire.com 1” Diameter Attack Hose

• 1 year warranty • Abrasion Resistance Cover • Lightweight and Kink Resistant • Heat Resistance • Single Jacket Construction • Chemical Resistance

Are You Really Ready? Pro-Flow Specification Sheet • Rubber Covered Hose • 11/2”, 13/4”, 2”, 21/2” and 3”

Visit us on the Web: www.keyfire.com a Scope when subjected to the following cold bending test: a 50 ft. length of dry hose is to be firmly coiled and placed in a cold Quality: The fire hose assembly supplied under this spec- box at -35°F for a duration of 24 hours. Immediately after ification shall be constructed with superior quality materials. removal of the hose from the box, hose should be uncoiled NFPA 1961 standards shall be observed in production of the and laid out by one operator. Following this procedure, the assembly, in order to ensure its quality and durability. hose shall not leak nor show any damage to the reinforce- Warranty: Pro-Flow hose shall carry a 5 year warranty ment when subjected to the hydrostatic acceptance test against defects in material and workmanship. Barring any stated above. mistreatment or accidental damage the warranted hose a Ozone Resistance will be replaced at no charge. Hose shall show no visible signs of cracking to the lining a or cover when tested in accordance to ASTM D518 Hose Construction Procedure B (100pphm/118°F/70 hours). Hose shall be made from 100 percent high tenacity syn- thetic yarn, circularly woven and completely protected a Chemical Resistance and locked-in by tough highly resistant synthetic nitrile Exposure to sea water and contamination by most rubber, forming a single homogeneous construction with- chemical substances, hydrocarbons, oils, alkalis, acids out the use of glues or adhesives of any type. and greases must have no effect on the short or long a Lining Properties term performance of the hose. A chemical resistance chart is available and Key Fire Hose will supply specific Ultimate Tensile Strength: Tensile strength of the chemical resistance data on request of purchaser for lining and cover shall not be less than 1500 PSI. unique applications. Ultimate Elongation: 400 percent minimum. Accelerated Aging Test: The tensile strength and a Heat Resistance ultimate elongation of the vulcanized rubber compound The hose, when subjected to a static pressure of 100 PSI, which has been subjected to the action of oxygen at a shall be capable of withstanding a surface temperature of pressure of 300 PSI (±10PSI) and a temperature of 1200°F for a minimum of two minutes without rupture 158°(±18°)F for a period of 96 hours shall retain 60 per- or damage to the synthetic reinforcement. cent of its originally stated properties. a Hose Weight and Coil Diameters a Hydrostatic Pressure Test The hose shall conform to the following average weights and diameters Service Test Acceptance Burst Part # Diameter Pressure Test Pressure Pressure Weight per Coil Size-Coupled 1 Part # Diameter RC15-500 1/2” 250psi 500psi 800psi Length (Coupled) per 50’ Lengths

3 1 RC17-500 1 /4” 250psi 500psi 800psi RC15-500 1 /2” 16 lbs 151/2 in. 3 RC20-500 2” 250psi 500psi 750psi RC17-500 1 /4” 17 lbs 16 in. 1 RC25-500 2 /2” 250psi 500psi 750psi RC20-500 2” 19 lbs 17 in. 1 RC30-500 3” 250psi 500psi 750psi RC25-500 2 /2” 26 lbs 17 in. RC30-500 3” 32 lbs 18 in. Note: Per NFPA, attack hose shall have a minimum design service a Color pressure of 300 psi. See our Dura-Flow line for this type of hose. The stock colors are HI-VISIBILITY yellow or red. a Abrasion Resistance Other colors available upon request. Hose shall withstand 20,000 cycles on the Taber Abrasion a Couplings Machine (H-22 Wheel: 1 kg). Key Fire Hose Corporation on As required by purchaser, expansion ring threaded, request will supply written warranties that PRO-FLOW hose STORZ clamp ring, etc. meets a minimum 20,000 cycles. Other abrasion test results Key reserves the right to modify any specification with- (UL, DIN, etc.) can be supplied on request of purchaser. out prior notice to meet or exceed changing standards. Customers are advised that special diameters or con- a Cold Resistance struction characteristics can be produced on special Hose shall have a capability of use down to -35°F. Hose shall request and you are requested to contact Key Fire Hose have no apparent damage to cover, reinforcement or lining Corporation, Miami, Florida.

PHONE 1-800-447-5666 • FAX 1-800-447-5664 • E-MAIL [email protected]

KF-046 07/03 Pro-Flow www.keyfire.com Rubber Covered Hose • 5 year warranty • Single Homogeneous Construction • Abrasion Resistance • Cold Resistance • Chemical Resistance • Heat Resistance

Are You Really Ready? Pro-Lite Specification Sheet • Rubber Covered Hose • 13/4 ” and 21/2” Hi-Rise Hose

Visit us on the Web: www.keyfire.com a Scope leak nor show any damage to the reinforcement when sub- Quality: The fire hose assembly supplied under this spec- jected to the hydrostatic acceptance test stated above. ification shall be constructed with superior quality materials. a Ozone Resistance NFPA 1961 standards shall be observed in production of the assembly, in order to ensure its quality and durability. Hose shall show no visible signs of cracking to the lining Warranty: Pro-Lite hose shall carry a 5 year warranty or cover when tested in accordance to ASTM D518 against defects in material and workmanship. Barring any Procedure B (100pphm/118°F/70 hours). mistreatment or accidental damage the warranted hose will be replaced at no charge. a Chemical Resistance Note: This hose is specifically designed for high-rise use. Exposure to sea water and contamination by most a Hose Construction chemical substances, hydrocarbons, oils, alkalis, acids Hose shall be made from 100 percent high tenacity syn- and greases must have no effect on the short or long thetic yarn, circularly woven and completely protected term performance of the hose. A chemical resistance and locked-in by tough highly resistant synthetic nitrile chart is available and Key Fire Hose will supply specific rubber, forming a single homogeneous construction with- out the use of glues or adhesives of any type. chemical resistance data on request of purchaser for a Lining Properties unique applications. Ultimate Tensile Strength: Tensile strength of the a Heat Resistance lining and cover shall not be less than 2000 PSI. Ultimate Elongation: 400 percent minimum. The hose, when subjected to a static pressure of 100 PSI, Accelerated Aging Test: The tensile strength and shall be capable of withstanding a surface temperature of ultimate elongation of the vulcanized rubber compound 1200°F for a minimum of two minutes without rupture which has been subjected to the action of oxygen at a pressure of 300 PSI (±10PSI) and a temperature of or damage to the synthetic reinforcement. 158°(±18°)F for a period of 96 hours shall retain 60 per- a cent of its originally stated properties. Hose Weight and Coil Diameters The hose shall conform to the following average weights a Hydrostatic Pressure Test and diameters Service Test Acceptance Burst Part # Diameter Pressure Test Pressure Pressure Coil Size-Coupled 3 RC17-600SO 1 /4” 300psi 600psi 900psi Part # Diameter Weight per Foot per 50’ Lengths 1 RC25-600SO 2 /2” 300psi 600psi 900psi 3 RC17-600SO 1 /4” .2 lbs 10 in.

1 a Abrasion Resistance RC25-600SO 2 /2” .4 lbs 14 in. Hose shall withstand 5,000 cycles on the Taber Abrasion a Machine (H-22 Wheel: 1 kg). Key Fire Hose Corporation on Color request will supply written warranties that PRO-LITE hose The color shall be HI-VISIBILITY orange. meets a minimum 5,000 cycles. Other abrasion test results (UL, DIN, etc.) can be supplied on request of purchaser. a Couplings a Cold Resistance As required by purchaser. Key reserves the right to modify any specification with- Hose shall have a capability of use down to -35°F. Hose shall have no apparent damage to cover, reinforcement or lining out prior notice to meet or exceed changing standards. when subjected to the following cold bending test: a 50 ft. Customers are advised that special diameters or con- length of dry hose is to be firmly coiled and placed in a cold box struction characteristics can be produced on special at -35°F for a duration of 24 hours. Immediately after removal of the hose from the box, hose should be uncoiled and laid out request and you are requested to contact Key Fire Hose by one operator. Following this procedure, the hose shall not Corporation, Miami, Florida.

PHONE 1-800-447-5666 • FAX 1-800-447-5664 • E-MAIL [email protected] KF-014 01/04 Pro-Lite www.keyfire.com Rubber Covered Hi-Rise Hose

• 5 year warranty • Abrasion Resistance • Cold Resistance • Chemical Resistance • Heat Resistance • Single Homogeneous Construction

Are You Really Ready? Rack & Reel Hose Single Jacket Specification Sheet • 500 Pound Test Light Weight Visit us on the Web: www.keyfire.com • Polyurethane Lined • 11/2”, 21/2”

a Scope a Features

All polyester single jacket fire hose specifically designed for • FM Approved Standard & UL available upon special interior fire fighting use, pin racks, and/or fire cabinets in request.

buildings and plants. NFPA 1961 standards shall be observed • Stock lengths: Standard lengths are 50, 75 and 100 in production and assembly to insure quality and durability. feet. • Pre-folded for ease of installation. a Jacket Construction • 250 PSI working pressure, hydrostatically tested to

The jackets will be woven evenly and be free of defects, 500 PSI at point of manufacture. including knots, lumps, or unsightly disfigurations that •Available with internal expansion ring brass or alu- could jeopardize the integrity of the hose assembly. The minum couplings. warp and filler yarns shall consist of 100% virgin polyester a to reduce weight and increase flexibility. Physical Properties

Hose Part Coupling Weight per 50’ Working Test Size # Bowl Size foot uncpld. Pressure Pressure a Lining 1-1/2” RR15-500 1-11/16” 6 lbs 250 PSI 500 PSI

The lining shall be a single-ply extruded tube of synthetic 2-1/2” RR25-500 2-11/16” 10 lbs 250 PSI 500 PSI polyurethane to resist ozone and increase tensile strength char- acteristics. The polyurethane tube shall adhere to the jacket to prevent delamination. The use of polyurethane lined fire hose is designed to increase packing ability and interior firefighting applications where lightweight fire hose is desired.

PHONE 1-800-447-5666 • FAX 1-800-447-5664 • E-MAIL [email protected] KF-002 01/04 Rack & Reel Single Jacket

• 5 year warranty • Single Homogeneous Construction • Abrasion Resistance • Cold Resistance • Chemical Resistance

• Heat Resistance www.keyfire.com Rubber-Covered

Visit us on the Web: www.keyfire.com Stock List

Industrial Application Part Number Description Length YELLOW RED BLUE BLACK ORANGE GREEN RC15-500 1-1/2” Pro-Flow x x x x 50 & 100 ft RC15-500 1-1/2” Pro-Flow x x 75 ft RC17-500 1-3/4” Pro-Flow x x 50 & 100 ft RC20-500 2” Pro-Flow x x 50 & 100 ft RC25-500 2-1/2” Pro-Flow x x 50, 75 & 100 ft RC30-500 3” Pro-Flow x x 50 & 100 ft Municipal Application Part Number Description Length YELLOW RED BLUE BLACK ORANGE GREEN RC10-600 1” Dura-Flow x 50 & 100 ft RC15-600 1-1/2” Dura-Flow x x x 50 & 100 ft RC17-600 1-3/4” Dura-Flow x x x x x 50 & 100 ft RC20-600 2” Dura-Flow x x 50 & 100 ft RC25-600 2-1/2” Dura-Flow x x 50 & 100 ft RC30-600 3” Dura-Flow x x 50 & 100 ft LHD - Supply Hose Part Number Description Length YELLOW RED BLUE BLACK ORANGE GREEN RC40-500 4” Pro-Flow x x x x Length to 100 ft RC50-400 5” Pro-Flow x x x x Length to 100 ft RC60-300 6” Pro-Flow x Length to 100 ft LDH - High Pressure Hose Part Number Description Length YELLOW RED BLUE BLACK ORANGE GREEN RC40-600 4” Attack Hose x Length to 100 ft RC50-600 5” Attack Hose x Length to 100 ft Municipal Application Part Number Description Length YELLOW RED BLUE BLACK ORANGE GREEN RC17-600 1-3/4” High Rise x 50, 75 & 100 ft RC25-600 2-1/2” High Rise x 50, 75 & 100 ft

Other Lengths, Colors and Diameters Available by Special Order Please contact our Customer Service Dept. for details. Mailing Address: P.O. Box 530007 Miami, FL 33153-0007 Corporate Office: 1150 N.W. 72 Street, Miami, FL 33150

PHONE 1-800-447-5666 • FAX 1-800-447-5664 • E-MAIL [email protected]

KF-005 02/ 04

Super-Flow Specification Sheet • Nitrile Rubber Covered Hose Black LDH • 4”, 6”, and 8”

Visit us on the Web: www.keyfire.com

᭤ Hose Construction ᭤ Ozone Resistance Hose shall be made from 100 percent high tenacity synthetic Hose shall show no visible signs of cracking to the lin- yarn, circularly woven and completely protected and locked-in ing or cover when tested in accordance to ASTM D518 by tough highly resistant synthetic nitrile rubber, forming a sin- Procedure B, 100pphm/118°F/70 hours. gle homogeneous construction without the use of glues or adhesives of any type. ᭤ Chemical Resistance Exposure to sea water and contamination by most chem- ᭤ Lining Properties ical substances, hydrocarbons, oils, alkalis, acids and Ultimate Tensile Strength: greases must have no effect on the short or long term per- Tensile strength of the lining and cover shall not be less than 1750 PSI. formance of the hose. A chemical resistance chart is avail- Ultimate Elongation: able and Key Fire Hose will supply specific chemical resist- 500 percent minimum. ance data on request of purchaser for unique applications. Accelerated Aging Test: ᭤ The tensile strength and ultimate elongation of the vulcan- Heat Resistance ized rubber compound which has been subjected to the The hose, when subjected to a static pressure of 100 PSI, action of oxygen at a pressure of 300 PSI (±10 PSI) and a shall be capable of withstanding a surface temperature of temperature of 158°(±18°F) for a period of 96 hours shall 300°F for a minimum of two minutes without rupture or retain 60 percent of its originally stated properties. damage to the synthetic reinforcement. ᭤ Hydrostatic Pressure Tests ᭤ Hose Weight and Coil Diameters Part Service Test Acceptance Burst Diameter The hose shall conform to the following average weights Number Pressure Test Pressure Pressure and diameters. RC40-500 4” 250psi 500psi 750psi

RC60-300 6” 150psi 300psi 500psi Part Weight Coil Size Number Diameter per foot Uncoupled RC80-300 8” 150psi 300psi 450psi uncoupled 100’ Lengths

RC40-500 4” .75 lbs 24” ᭤ Abrasion Resistance RC60-300 6” 1.20 lbs 34” Hose shall withstand 30,000 cycles on the Taber Abrasion RC80-300 8” 1.70 lbs 38” Machine (H-22 Wheel: 1 kg). Key Fire Hose Corporation on request will supply written warranties that SUPER-FLOW ᭤ hose meets a minimum 30,000 cycles. Other abrasion test Color results (UL, DIN, etc.) can be supplied on request of purchaser. The color shall be black. Other colors available upon request. ᭤ Cold Resistance ᭤ Hose shall have a capability of use down to -5°F. Hose shall Couplings have no apparent damage to cover, reinforcement or lining Hose is designed for Bower Couplings. when subjected to the following cold bending test: a 50 ft. Key reserves the right to modify any specification with- length of dry hose is to be firmly coiled and placed in a cold box out prior notice to meet or exceed changing standards. at -5°F for a duration of 24 hours. Immediately after removal of Customers are advised that special diameters or con- the hose from the box, hose should be uncoiled and laid out by one operator. Following this procedure, the hose shall not leak struction characteristics can be produced on special nor show any damage to the reinforcement when subjected to request and you are requested to contact Key Fire Hose the hydrostatic acceptance test stated above. Corp. Miami, Florida.

PHONE 1-800-447-5666 • FAX 1-800-447-5664 • E-MAIL [email protected] KF-075 04/07 Pro-Flow Specification Sheet • Rubber Covered Hose • 4”, 5”, and 6”

Visit us on the Web: www.keyfire.com a Hose Construction a Ozone Resistance Hose shall be made from 100 percent high tenacity synthetic Hose shall show no visible signs of cracking to the lin- yarn, circularly woven and completely protected and locked-in ing or cover when tested in accordance to ASTM D518 by tough highly resistant synthetic nitrile rubber, forming a sin- gle homogeneous construction without the use of glues or Procedure B, 100pphm/118°F/70 hours. adhesives of any type. Meeting all requirements of NFPA 1961. a Chemical Resistance Warranty: Hose shall carry a five year written warranty. Exposure to sea water and contamination by most chem- a Lining Properties ical substances, hydrocarbons, oils, alkalis, acids and Ultimate Tensile Strength: greases must have no effect on the short or long term per- Tensile strength of the lining and cover shall not be less formance of the hose. A chemical resistance chart is avail- than 1750 PSI. able and Key Fire Hose will supply specific chemical resist- Ultimate Elongation: ance data on request of purchaser for unique applications. 500 percent minimum. Accelerated Aging Test: a Heat Resistance The tensile strength and ultimate elongation of the vul- canized rubber compound which has been subjected to The hose, when subjected to a static pressure of 100 PSI, the action of oxygen at a pressure of 300 PSI (±10 PSI) shall be capable of withstanding a surface temperature of and a temperature of 158°(±18°F) for a period of 96 hours 1200°F for a minimum of two minutes without rupture shall retain 60 percent of its originally stated properties. or damage to the synthetic reinforcement. a Hydrostatic Pressure Tests a Hose Weight and Coil Diameters The hose shall conform to the following average weights Part Service Test Acceptance Burst Diameter Number Pressure Test Pressure Pressure and diameters

RC40-500 4” 250psi 500psi 750psi Part Weight Coil Size RC50-400 5” 200psi 400psi 600psi Diameter per foot Uncoupled Number uncoupled 100’ Lengths RC60-300 6” 150psi 300psi 500psi RC40-500 4” .74 lbs 24” RC50-400 5” 1.04 lbs 27” a Abrasion Resistance RC60-300 6” 1.35 lbs 34” Hose shall withstand 30,000 cycles on the Taber Abrasion Machine (H-22 Wheel: 1 kg). Key Fire Hose Corporation on request will supply written warranties that PRO-FLOW hose a Color meets a minimum 30,000 cycles. Other abrasion test results The color shall be of HI-VISIBILITY yellow or red. (UL, DIN, etc.) can be supplied on request of purchaser Other colors available upon request. a Cold Resistance a Couplings Hose shall have a capability of use down to -35°F. Hose shall As required by purchaser, expansion ring threaded, have no apparent damage to cover, reinforcement or lining STORZ clamp ring, etc. when subjected to the following cold bending test: a 50 ft. Key reserves the right to modify any specification with- length of dry hose is to be firmly coiled and placed in a cold box out prior notice to meet or exceed changing standards. at -35°F for a duration of 24 hours. Immediately after removal Customers are advised that special diameters or con- of the hose from the box, hose should be uncoiled and laid out by one operator. Following this procedure, the hose shall not struction characteristics can be produced on special leak nor show any damage to the reinforcement when sub- request and you are requested to contact Key Fire Hose jected to the hydrostatic acceptance test stated above. Corp. Miami, Florida.

PHONE 1-800-447-5666 • FAX 1-800-447-5664 • E-MAIL [email protected]

KF-031 03/ 03 Forestry-187 Forestry-187 Single Jacket Specification Sheet Single Jacket Specification Sheet • 600 Pound Test Heavy Duty Light Weight • 600 Pound Test Heavy Duty Light Weight Visit us on the Web: www.keyfire.com • Polyurethane Lined Visit us on the Web: www.keyfire.com • Polyurethane Lined • 1”, 11/2” • 1”, 11/2” ᭤ Scope ᭤ Hydrostatic Testing ᭤ Scope ᭤ Hydrostatic Testing Stock Lengths: Standard lengths are 50 and 100 feet. Stock Lengths: Standard lengths are 50 and 100 feet. Quality: The fire hose assembly supplied under this Quality: The fire hose assembly supplied under this Size 1” 1-1/2” Size 1” 1-1/2” specification shall be constructed with superior quality specification shall be constructed with superior quality Test Pressure 600psi 600psi Test Pressure 600psi 600psi materials observing USDA Forestry 5100-187 specifications. Elongation 4% 5% materials observing USDA Forestry 5100-187 specifications. Elongation 4% 5%

o o o o NFPA 1961 standards shall be observed in production of the Twist per foot 71 right 64 right NFPA 1961 standards shall be observed in production of the Twist per foot 71 right 64 right Warp 10” 10” Warp 10” 10” assembly, in order to ensure its quality and durability. Rise 4 3 assembly, in order to ensure its quality and durability. Rise 4 3 Service Life: Hose furnished under these specifications Burst Test 900psi 900psi Service Life: Hose furnished under these specifications Burst Test 900psi 900psi Kink Test 500psi 500psi Kink Test 500psi 500psi will have a potential service life warranty of two years; will have a potential service life warranty of two years; barring mistreatment that would render it unfit for service. barring mistreatment that would render it unfit for service. ᭤ Finished Hose ᭤ Finished Hose Upon delivery, the hose shall be free from defects in Upon delivery, the hose shall be free from defects in Markings: Beginning at a point not less than four feet Markings: Beginning at a point not less than four feet workmanship and materials. Any defective hose will be from the end, each fifty foot section shall be stencilled in workmanship and materials. Any defective hose will be from the end, each fifty foot section shall be stencilled in indelible ink with letters at least one inch high stating the indelible ink with letters at least one inch high stating the replaced at no charge. replaced at no charge. name of the manufacturer, month and year of name of the manufacturer, month and year of manufacture, and service test to 300 PSI. The ink used manufacture, and service test to 300 PSI. The ink used ᭤ Jacket Construction ᭤ Jacket Construction will be of a contrasting color. will be of a contrasting color. The jackets will be woven evenly and be free of defects, Methods Testing: All measurements and tests The jackets will be woven evenly and be free of defects, Methods Testing: All measurements and tests necessary to determine compliance of the fire hose necessary to determine compliance of the fire hose including knots, lumps, or unsightly disfigurations that including knots, lumps, or unsightly disfigurations that specified requirements shall be made with ASTM, UL and specified requirements shall be made with ASTM, UL and could jeopardize the integrity of the hose assembly. The NFPA 1961 designation, unless otherwise prescribed. could jeopardize the integrity of the hose assembly. The NFPA 1961 designation, unless otherwise prescribed. warp yarn shall consist of filament polyester yarn. The warp yarn shall consist of filament polyester yarn. The ᭤ Couplings ᭤ Couplings filler yarns shall be constructed of high strength, low Expansion ring threaded or as required by purchaser. filler yarns shall be constructed of high strength, low Expansion ring threaded or as required by purchaser. elongation, filament polyester to reduce weight and elongation, filament polyester to reduce weight and ᭤ Weights & Measures ᭤ Weights & Measures increase flexibility. increase flexibility. Part # SP10-600-187 SP15-600-187 Part # SP10-600-187 SP15-600-187 Coil Diameter 13” 14” Coil Diameter 13” 14” ᭤ Lining ᭤ Lining Size 1” 1-1/2” Size 1” 1-1/2” The lining shall be a single-ply extruded tube of synthetic Bowl Size 1-1/4” 1-3/4” The lining shall be a single-ply extruded tube of synthetic Bowl Size 1-1/4” 1-3/4” Weight per 100’ length (uncoupled) 8 10 Weight per 100’ length (uncoupled) 8 10 polyurethane to resist ozone. The polyurethane tube shall Weight per 100’ length (coupled) 12 13 polyurethane to resist ozone. The polyurethane tube shall Weight per 100’ length (coupled) 12 13 adhere to the jacket to prevent delamination. The finished adhere to the jacket to prevent delamination. The finished product will meet and exceed all potable water Mil-H-24606B product will meet and exceed all potable water Mil-H-24606B Key reserves the right to modify any specification Key reserves the right to modify any specification standards for the manufacturing of lightweight fire hose. The without prior notice to meet or exceed changing standards for the manufacturing of lightweight fire hose. The without prior notice to meet or exceed changing standards. Customers are advised that special diameters standards. Customers are advised that special diameters use of the polyurethane lined fire hose is designed to increase use of the polyurethane lined fire hose is designed to increase or construction characteristics can be produced on or construction characteristics can be produced on packing ability and applications where lightweight fire hose is special request. For more information, please contact packing ability and applications where lightweight fire hose is special request. For more information, please contact desired. your Key Fire Hose Corporation authorized distributor. desired. your Key Fire Hose Corporation authorized distributor.

PHONE 1-800-447-5666 • FAX 1-800-447-5664 • E-MAIL [email protected] PHONE 1-800-447-5666 • FAX 1-800-447-5664 • E-MAIL [email protected] KF-085 06/05 KF-085 06/05 Forestry Single Jacket Specification Sheet • 600 Pound Test Heavy Duty Light Weight

Visit us on the Web: www.keyfire.com • Polyurethane Lined • 1”, 11/2” a Scope a Hydrostatic Testing Quality: The fire hose assembly supplied under this Stock Lengths: Standard lengths are 50 and 100 feet. specification shall be constructed with superior quality Size 1” 1-1/2” materials. NFPA 1961 standards shall be observed in Test Pressure 600psi 600psi production of the assembly, in order to ensure its quality and Elongation 4% 5% durability. Service Life: Hose furnished under these Twist per foot 71o right 64o right specifications will have a potential service life warranty of Warp 10” 10” two years; barring mistreatment that would render it unfit Rise 4 3 Burst Test 900psi 900psi for service. Upon delivery, the hose shall be free from defects Kink Test 500psi 500psi in workmanship and materials. Any defective hose will be replaced at no charge. a Finished Hose a Jacket Construction Markings: Beginning at a point not less than four feet from the end, each fifty foot section shall be stencilled in The jackets will be woven evenly and be free of defects, indelible ink with letters at least one inch high stating the including knots, lumps, or unsightly disfigurations that name of the manufacturer, month and year of could jeopardize the integrity of the hose assembly. The manufacture, and service test to 300 PSI. The ink used warp yarn shall consist of staple polyester yarn. The use of will be of a contrasting color. filament or entangled yarn is expressly forbidden due to Methods Testing: All measurements and tests the lack of inherent abrasion resistance. The filler yarns shall necessary to determine compliance of the fire hose be constructed of high strength, low elongation, filament specified requirements shall be made with ASTM, UL and NFPA 1961 designation, unless otherwise prescribed. polyester to reduce weight and increase flexibility. a Couplings a Abrasion Impregnation Expansion ring threaded or as required by purchaser. Hose assemblies are available with polymer impregnation that provide additional abrasion resistance. Colors include: yellow, a Weights & Measures orange, red, tan, black, blue and green. Color shall be pure Part # SP10-500PU SP15-500PU and even in each hose. Impregnated hose shall meet the Coil Diameter 13” 14” requirements of Mil-H-24606B for abrasion resistance. Size 1” 1-1/2” Bowl Size 1-1/4” 1-3/4” a Lining Weight per 50’ length (uncoupled) 7 10 Weight per 50’ length (coupled) 8 11 The lining shall be a single-ply extruded tube of synthetic polyurethane to resist ozone. The polyurethane tube shall adhere to the jacket to prevent delamination. The finished Key reserves the right to modify any specification product will meet and exceed all potable water Mil-H-24606B without prior notice to meet or exceed changing standards for the manufacturing of lightweight fire hose. The standards. Customers are advised that special diameters use of the polyurethane lined fire hose is designed to increase or construction characteristics can be produced on special request. For more information, please contact packing ability and applications where lightweight fire hose is your Key Fire Hose Corporation authorized distributor. desired.

PHONE 1-800-447-5666 • FAX 1-800-447-5664 • E-MAIL [email protected] KF-001 02/ 04 KEY INDUSTRIAL PRODUCTS

Part Inlet Size Outlet Size Key Fire Hose Part Inlet Size Outlet Size Key Fire Hose Part Inlet Size Outlet Size Key Fire Hose Description & thread & thread Part # Description & thread & thread Part # Description & thread & thread Part # 1.5” CAP 1.5” NST N/A Cap-15NH Brass Hose Plug 1.5” NST N/A PLUG-15NH 2.5” x 1.5” Reducer 2.5” NST 1.5” NPSH Reducer-25Hx15I 2.5” CAP 2.5” NST N/A Cap-25NH Brass Hose Plug 2.5” NST N/A PLUG-25NH 2.5” x 1.5” Reducer 2.5” NST 1.5” NST Reducer-25Hx15H 2.5” x 5/8” Reducer 2.5” NST 5/8” GHT Reducer-25Hx16G 2.5” x 2” Reducer 2.5” NST 2” NPSH Reducer-25Hx20I

Part Inlet Size Outlet Size Key Fire Hose Part Inlet Size Outlet Size Key Fire Hose Part Inlet Size Outlet Size Key Fire Hose Description & thread & thread Part # Description & thread & thread Part # Description & thread & thread Part # Hydrant Gate Valve 2.5” NST 2.5” NST Valve-HydGat25H Brass Shut Off 1.5 x 10” Brass Siamese Ball Type 2.5”NST 1.5” NST Valve-SI25Hx15H Plain Nozzle 1.5” NPSH N/A Nozzle-PL 15Ix10

Part Inlet Size Outlet Size Key Fire Hose Part Inlet Size Outlet Size Key Fire Hose Part Inlet Size Outlet Size Key Fire Hose Description & thread & thread Part # Description & thread & thread Part # Description & thread & thread Part # Double Male Adapter 2.5” NPSH 2.5” NST Adapt-M25IxM25H Double Female Adapter 1.5” NPSH 1.5” NPSH Adapt-F15IxF15I 1.5” Brass Fog Nozzle 1.5” NST N/A Nozzle-BN15 Double Male Adapter 2.5” NST 2.5” NST Adapt-M25HxM25H 2.5” Brass Fog Nozzle 2.5” NST N/A Nozzle-BN25 Double Male Adapter 1.5” NPSH 1.5” NST Adapt-M15IxM15H

P.O. BOX 530007 • Miami, FL 33153 Ph: 305.696.1680 • Fax: 305.696.1316 www.keyfire.com KF-051 Combat Ready Specifications Combat-Ready 1 3/4” and 2 1/2” Visit us on the Web: www.keyfire.com www.keyfire.com Aggressive Interior Attack Fire Hose Factory Mutual Abrasion – A sample of coupled hose is ᭤ Hose Construction submitted to the procedure listed in FM Standard 2111 This hose is designed specifically for aggressive interior • 10 year warranty or MIL-H-24606B, there shall be no signs of leakage • Low Friction Loss fire attack operations. The outer jacket is woven from staple polyester yarns over an inner liner consisting after 20,000 cycles of abrasion. • High Flow Capability of a one-piece extruded through-the-weave tube. Cold Resistance Safety Factor – Hose shall be capable • Modern Fiber Technology Combat-Ready is manufactured in a high-visibility white of safe use down to –50 degrees F. The hose shall have • Unique Construction with one red and one blue stripe running the length of the no apparent damage to cover reinforcement or lining hose. This heat resistant, drag resistant and kink resistant • Added Protection hose shall have superior friction loss characteristics. when subjected to the following cold bending test: A Warranty: Hose shall carry a 10 year written warranty. 50 ft. length of dry hose is coiled and placed in a cold box at –50 degrees for 24 hours. The hose shall not ᭤ Inner Hose Properties show any damage to the reinforcement when subjected When the hose is tested in accordance with NFPA 1961, to hydrostatic acceptance test pressure. the liner or cover shall have the following properties: Flashover Resistance Safety Factor – Heat resistance is Ultimate Tensile Strength – shall not be less than 1500 PSI of the utmost importance when evaluating interior Ultimate Elongation – shall not be less than 400% attack hose. This hose shall meet the safety factors for Permanent Set – shall not exceed 20% heat resistance without exceeding the normal fire hose Accelerated Aging Test – shall meet requirements of UL 19 for accelerated aging weight. The hose shall be subjected to a static pressure Adhesion – between reinforcement and liner shall be a of 100 PSI and be capable of withstanding a surface minimum of 20 pounds temperature of 1200 degrees F for a minimum of 45 Ozone Resistance – shall show no signs of visible seconds without bursting. cracking of the cover of liner when tested in accordance Water Pick-up Weight – The tendency for a hose to with ASTM D1149-91 and ASTM D518-86 (R91), absorb water while in a wet environment can create Procedure B. Chemical Resistance – Exposure to seawater and significant handling difficulties. When tested against contamination by most chemicals will have no effect on the procedure listed in MIL-H-24606B, the maximum the short or long term performance of the hose. weight gain shall not exceed 3 lbs. per 50 foot length. Burst Resistance Safety Factor – Hose failure due to ᭤ Safety Factors bursting is the single most important safety concern. Abrasion Resistance – bears a direct relationship to the Hose shall have the capability of passing a 500 PSI safe performance of the fire hose. The UL abrasion test service test with a 1/4” diameter hole through both most closely resembles the fire ground use of fire hose and jacket and liner. Only a through-the-weave design liner as such, is considered of prime importance. Hose meeting will be acceptable. Hose shall have a minimum burst all of the abrasion resistance safety factors below shall do so without exceeding average weights. pressure of 1500 PSI. UL Abrasion – The hose shall pass a burst test after 5000 Hydrostatic Pressure Tests – The hose shall comply AreYou Really Ready? cycles on a reciprocating abrasion tester – as specified in with the National Fire Protection Association Standard UL Standard 19. NFPA 1961.

Physical Data

SERVICE ACCEPTANCE KINK SHORT CURVED AVERAGE WEIGHT COIL SIZE DIAMETER PRESSURE PRESSURE PROOF PRESSURE LENGTH BURST LENGTH BURST 50– COUPLED 50– COUPLED

1 3/4” 500 PSI 1000 PSI 750 PSI 1500 PSI 1500 PSI 18 LBS 16.5” 2 1/2” 500 PSI 1000 PSI 750 PSI 1500 PSI 1500 PSI 26 LBS 18.5”

PHONE 1-800-447-5666 • FAX 1-800-447-5664 • E-MAIL [email protected] KF-011 06/05 Combat Ready Specifications Combat-Ready 1 3/4” and 2 1/2” Visit us on the Web: www.keyfire.com www.keyfire.com Aggressive Interior Attack Fire Hose Factory Mutual Abrasion – A sample of coupled hose is ᭤ Hose Construction submitted to the procedure listed in FM Standard 2111 This hose is designed specifically for aggressive interior • 10 year warranty or MIL-H-24606B, there shall be no signs of leakage • Low Friction Loss fire attack operations. The outer jacket is woven from staple polyester yarns over an inner liner consisting after 20,000 cycles of abrasion. • High Flow Capability of a one-piece extruded through-the-weave tube. Cold Resistance Safety Factor – Hose shall be capable • Modern Fiber Technology Combat-Ready is manufactured in a high-visibility white of safe use down to –50 degrees F. The hose shall have • Unique Construction with one red and one blue stripe running the length of the no apparent damage to cover reinforcement or lining hose. This heat resistant, drag resistant and kink resistant • Added Protection hose shall have superior friction loss characteristics. when subjected to the following cold bending test: A Warranty: Hose shall carry a 10 year written warranty. 50 ft. length of dry hose is coiled and placed in a cold box at –50 degrees for 24 hours. The hose shall not ᭤ Inner Hose Properties show any damage to the reinforcement when subjected When the hose is tested in accordance with NFPA 1961, to hydrostatic acceptance test pressure. the liner or cover shall have the following properties: Flashover Resistance Safety Factor – Heat resistance is Ultimate Tensile Strength – shall not be less than 1500 PSI of the utmost importance when evaluating interior Ultimate Elongation – shall not be less than 400% attack hose. This hose shall meet the safety factors for Permanent Set – shall not exceed 20% heat resistance without exceeding the normal fire hose Accelerated Aging Test – shall meet requirements of UL 19 for accelerated aging weight. The hose shall be subjected to a static pressure Adhesion – between reinforcement and liner shall be a of 100 PSI and be capable of withstanding a surface minimum of 20 pounds temperature of 1200 degrees F for a minimum of 45 Ozone Resistance – shall show no signs of visible seconds without bursting. cracking of the cover of liner when tested in accordance Water Pick-up Weight – The tendency for a hose to with ASTM D1149-91 and ASTM D518-86 (R91), absorb water while in a wet environment can create Procedure B. Chemical Resistance – Exposure to seawater and significant handling difficulties. When tested against contamination by most chemicals will have no effect on the procedure listed in MIL-H-24606B, the maximum the short or long term performance of the hose. weight gain shall not exceed 3 lbs. per 50 foot length. Burst Resistance Safety Factor – Hose failure due to ᭤ Safety Factors bursting is the single most important safety concern. Abrasion Resistance – bears a direct relationship to the Hose shall have the capability of passing a 500 PSI safe performance of the fire hose. The UL abrasion test service test with a 1/4” diameter hole through both most closely resembles the fire ground use of fire hose and jacket and liner. Only a through-the-weave design liner as such, is considered of prime importance. Hose meeting will be acceptable. Hose shall have a minimum burst all of the abrasion resistance safety factors below shall do so without exceeding average weights. pressure of 1500 PSI. UL Abrasion – The hose shall pass a burst test after 5000 Hydrostatic Pressure Tests – The hose shall comply AreYou Really Ready? cycles on a reciprocating abrasion tester – as specified in with the National Fire Protection Association Standard UL Standard 19. NFPA 1961.

Physical Data

SERVICE ACCEPTANCE KINK SHORT CURVED AVERAGE WEIGHT COIL SIZE DIAMETER PRESSURE PRESSURE PROOF PRESSURE LENGTH BURST LENGTH BURST 50– COUPLED 50– COUPLED

1 3/4” 500 PSI 1000 PSI 750 PSI 1500 PSI 1500 PSI 18 LBS 16.5” 2 1/2” 500 PSI 1000 PSI 750 PSI 1500 PSI 1500 PSI 26 LBS 18.5”

PHONE 1-800-447-5666 • FAX 1-800-447-5664 • E-MAIL [email protected] KF-011 06/05 KEY FIRE HOSE CORPORATION WATER FLOW LOSS (PSI PER 100 FEET OF HOSE) FLOW OF WATER IN US GAL. ACTUAL INTERNAL DIAMETER INCHES PER MIN. 1" 1-1/2" 1-3/4" 2" 2-1/2" 3" 3-1/2" 4" 5" 40 44.7 45 55.0 50 67.5 60 94.3 8.7 4.9 2.2 0.73 70 126.0 11.9 6.6 2.9 0.98 80 15.4 8.6 3.9 1.3 90 19.5 10.9 4.9 1.7 100 24.1 13.5 6.1 2.0 110 29 16.3 7.3 2.4 120 34.6 19.4 8.6 2.9 130 40.6 22.8 10.2 3.5 140 47.0 26.5 11.8 4.0 150 54.0 30.4 13.5 4.5 160 61.4 34.6 15.4 5.1 180 77.8 43.7 19.4 6.5 200 54.0 24.1 8.1 3.3 220 65.3 29.0 9.7 4.0 240 77.8 34.6 11.5 4.6 250 84.4 37.5 12.6 5.0 280 105.8 47.0 15.7 6.4 300 54.1 18 7.2 320 61.4 20.5 8.2 340 69.4 23.1 9.3 350 77.9 24.5 9.9 380 86.6 28.9 11.6 400 96.1 32.1 12.9 6.3 3.2 1.1 450 35.4 16.3 7.9 4.1 1.3 500 20.0 9.6 5.0 1.7 550 24.2 11.6 6.0 2.0 600 28.8 13.5 7.3 2.3 650 33.9 15.5 8.6 2.9 700 39.3 17.7 9.7 3.2 750 45.0 20.2 11.5 3.7 800 51.2 22.7 12.4 4.2 850 57.8 25.4 14.3 4.8 900 64.8 28.2 15.9 5.4 950 72.2 31.3 17.6 6.1 1000 34.1 19.2 6.6 1050 37.6 21.2 7.4 1100 41.1 23.3 8.0 1150 45.0 25.4 8.7 1250 53.1 30.0 10.3 1300 57.1 32.4 11.2 1400 66.7 37.7 12.9 1500 76.5 43.2 15.0 1750 58.8 20.2

NOTE: The pressure loss experienced by a flowing The pressure loss is directly proportional to the through a hose depends on the rate of flow , the viscosity of length of the hose, therefore the data shown can the liquid, the hose I.D..the smoothness of the tube and the be easily extended by use of proportions , e.g., hose length. This chart shows the relationship between rate the pressure drop for 50 feet of hose length is half that of flow,I.D., and the pressure loss for 100 ft. NOTE:To find cubic ft/min. multiply GPM x .13380