POCKET FIELD MANUAL

Tables, Formulas & Data for Engineering and T&D Personnel

2019

TABLE OF CONTENTS Formulas Electrical Formulas 1 OHM’S Law 2 Metering CT Metering Determination 4 Meter Type Selection Table 5 Phase Rotation Connection for Meter can 6 Network Connection Single-Phase 7 Net-meter Connection 120 Single-Phase 8 Conductor/Transformer Data Full Load Currents – 1/Ø Transformers 9 Full Load Currents – 3/Ø Transformers 9 Ampacity – Service Conductors 10 Ampacity – Overhead Conductors – Bare 11 Ampacity – Underground Primary 11 Ampacity – Low Voltage Wire 12 Conductor Impedance’s 13 Conductor Code Names 13 Conductor in Conduit 14 Maximum Conductor per Single-Phase Pad mount 15 Voltage Voltage Limits 16 Transformer Sizing Guide 17 Transformer Voltage Drop 18 Voltage Regulator Capacity 18 Secondary Voltage Drops 1/0 Triplex – 120/240 19 4/0 Triplex – 120/240 20 1/0 Quadruplex – 120/208 21 4/0 Quadruplex – 120/208 22 Voltage Flicker and Curves Percent for 1/0 Service Cable 23 Percent for 4/0 Service Cable 23 Flicker Limits 24 Percent for Transformer 24 Motor Starting KVA 25 Motor Amperage 26 Transformer Connections Sizing Open Delta Banks 27 Sizing Closed Delta Banks 28

I Distribution Transformer Connections 3/Ø, 4 wire primary/4 wire delta 120/240 V 29 3/Ø, 4 wire open wye primary/3 wire open 480 V 29 3/Ø, 4 wire primary/4 wire secondary 120/208 V 30 3/Ø, 4 wire primary/4 wire secondary 277/480 V 30 3/Ø, 4 wire open wye primary/4 wire open delta 120/240 V 31 Fusing Transformer Fusing 32 Capacitor Bank Fusing 32 1/Ø Overhead Fusing 33 3/Ø Underground Fusing 33 Fault Current Customer Secondary – Aerial Transformers 34 Customer Secondary – Pad mounted Transformers 35 KEYS Substation 36 Pole Depths & Guys Pole Setting Depths 37 Guy Lead Length 37 Guy Heights & Formula 38 Pole and Transformer Weights and Base Diameter 39 Rope Capacity in Pounds 40 Tension Sag and Tensions – Primary & Secondary 41 Underground Cable Pulling Max Tension 42 Clearances NESC Clearance Reference Guide 43 Service Drop Examples 44 Minimum Working Clearances 45 Utility Underground Clearance Notification 46 ADA Wheelchair Passage Width 47 Transmission Line Line Summary and Circuit Rating 48 Substation Transformer Ratings 49 Keys 138KV Transmission Line Fault Locator Line 4 BCS-US-1 50 Keys 138KV Transmission Line Fault Locator BCS-BPS 51 Keys 138KV Transmission Line Fault Locator Line 6 BPS-BCS 52 Keys 138KV Transmission Line Fault Locator Line 7 BPS-MAR 53 Keys 138KV Transmission Line Fault Locator Line 7 MAR-BPS 54 Keys 138KV Transmission Line Fault Locator Line 9 US-1-BCS 55 Keys 69KV Transmission Line Fault Locator KDS-WSS 56 Keys 69KV Transmission Line Fault Locator WSS-KDS 57 Keys 69KV Transmission Line Fault Locator Line 3 KDS-SIPP 58 Keys 69KV Transmission Line Fault Locator Line 5 US-1-SIPP 59 Keys 69KV Transmission Line Fault Locator US-1-KDS 60 Keys 69KV Transmission Line Fault Locator Line 11 KWD-KDS 61 II

Generation Summary KEYS Generation and SC Ratings 62 Safety American Red Cross First Aid Bleeding – Poisoning – Shock 63 Burns – Electrical Shock – Heat Exhaustion 64 Rescue Breathing – First Aid For Choking 65 Relays IEEE Relay Devices Number & Names 66 SEL Relays Codes 67 Other KEYS Official TEN Signals 68 Hand Signals for Cranes and Cherry Pickers 69 Useful Knots 71 Centigrade and Fahrenheit Scales 72 Standard Phonetic 73 SEL AR360 Fault Indicator 74 GIS/Map Phasing for OMS/Milsoft 75 Notes: Blank Pages

III Electrical Formulas for determining amps, horsepower, kilowatts and kilovolt-amps

Alternating Current To Find Single-phase Three-phase Amps when hp x 746 hp x 746 horsepower is known E x %Eff x pf 1.73 x E x %Eff x pf Amps when kW x 1000 kW x 1000 kilowatts are known E x pf 1.73 x E x pf Amps when kVA x 1000 kVA x 1000 kVA are known E 1.73 x E I x E x pf 1.73 x I x E x pf Kilowatts (kW) 1000 1000 I x E 1.73 x I x E Kilovolt-amp (kVA) 1000 1000 Horsepower- I x E x Eff x pf 1.73 x I x E x Eff x pf (Output) 746 746 kWh to kW kWh kWh (kW average) Time (hr) Time (hr)

Amps = PkW x 1000 = I PkW x 1000 = I

1 Megawatt VL-N 1.73 x VL-L

I = Amperes (current) E = Voltage - L-N (Single Phase) E = Voltage - L-L (Three Phase) %Eff. = Efficiency percent efficiency in decimals pf = Power Factor in decimals kVA = Kilovolt-Amphs (apparent power) kW = Kilowatts (power) hp = horsepower

1 OHM'S LAW

The Rate of the flow of the current is equal to Electromotive force divided by resistance

Electromotive Force = Volts = "E" Volts Amperes = Current = Amperes = "I" OHMS Resistance = OHMS = "R"

Series Circuit Parallel Circuit

A Series Ciruit is a circuit that has A Parallel Circuit is a circuit only one path through which the that has more than one path electrons may flow. through which the electrons Note: "T" stands for total may flow.

ET = E1 + E2 + E3 ET = E1 = E2 = E3 IT = I1 = I2 = I3 IT = I1 + I2 + I3 RT = R1 + R2 + R3 1 1 1 1 RT = R1 + R2 + R3

Note: For a parallel circuit having only two resistors, the following formula may be used.

R1 X R2 RT= R1 + R2

2 OHM'S LAW

A. When VOLTS and OHMS are Known:

Volts E Amps = or I = OHMS R

Example: Find the current of a 120 volt circuit with a Resistance of 60 OHMS. E 120 I = = = 2 Amps R60

B. When WATTS and VOLTS are known:

Watts P Ampers = or I = Volts E

Example: A 120 volt circuit has a 1440 watt load. Determine the current. P 1400 I = = = 12 Amps E 120

C. When OHMS and WATTS are known:

Watts P Ampers = or I = √ OHMS√ R

Example: A circuit consumes 625 watts through a 12.75 OHM resistor. Determine the current.

P 625 = 7 Amps I = √ R= √ 12.75 = √ 49

Notes: A. One electrical horsepower = 746 watts Electric motors are rated in horsepower

B. One Kilowatt = 1000 watts Generators are rated in Kilowatts 3 CT Metering Determination

Purpose: The purpose of the formulas below is to simplify the calculations for determining the current transformer (CT) needs for a project.

Definitions: kW = Estimated peak demand in kilowatts (P) V = Voltage at which the CT's are going to be applied Z = Impedance due to resistance, inductive reactance and capacitive reactance Formulas: Power = (CURRENT) (VOLTAGE) (1.73)

Power Current = (Voltage) (1.73)

kW kW kW I = = = (V) (√3) (V) (1.73) Z

*Remove √3 for single phase

Table: # of phase System Conf. Voltage Z Factor 3 13,800/7970 13.8 23.9 3 277/480 0.48 0.83 3 120/208 0.208 0.36 3 120/240 0.24 0.42 1 7.97 7.97 7.9 1 2.4 2.4 2.4 1 0.24 0.24 0.24 1 0.12 0.12 0.12 Step 1 Obtain the estimated KW peak demand of the customer load. Obtain this from Engineering. Step 2 Obtain the voltage running through the CT's Step 3 From step 2 voltage, get Z factor from table above Step 4 Using the numbers from step 1 & 3 insert into the formula above and calculate. Step 5 Using the number (I) calculated in step 4, find a CT close to this number. Look for a common CT ratio higher than the calculated (I). 4 Meter Type Selection Table

Self Instrument Phase Voltage Contained Meter (CT) 1 120/240 Peak < 82 kW Peak > 82 kW 1 277/480 Peak < 280 kW Peak > 280 kW 3 120/208 Peak < 123 kW Peak > 123 kW 3 240 Peak < 141 kW Peak > 141 kW 3 277/480 Peak < 280 kW Peak > 280 kW

5 Phase Rotation Connection for Three Phase Meter

6 Network Meter Connection Single Phase

7 Net-Meter Connection 120 V Single Phase

8 Full Load Currents Single Phase Amps @ Amps @ Amps @ Amps @ kVA 120 V 240 V 480 V 7970 V 10 83.3 41.7 20.8 1.25 15 125 62.5 31.3 1.88 25 208 104 52.1 3.13 37.5 313 156 78.1 4.7 50 417 208 104 6.27 75 625 313 156 9.41 100 833 417 208 12.5 167 1392 696 348 21 250 2083 1042 521 31.4 333 2775 1388 694 41.8 500 4167 2083 1042 62.7

Three-Phase Banks Amps @ Amps @ Amps @ Amps @ kVA 208 V 240 V 480 V 13800 30 83.3 72.2 36.1 1.26 45 125 108 54.1 1.88 75 208 180 90.2 3.14 112.5 312 271 135 4.71 150 416 361 180 6.28 225 625 541 271 9.41 300 833 722 361 12.5 500 1388 1203 601 20.9 750 2082 1804 902 31.4 1000 2778 2486 1203 41.8

Helpful Hints: 1 MW = 42 amps @ 13.8- 3Ø 1 MW = 13 amps @ 7.97- 1Ø

9 Ampacity - Service Conductors

TYPESIZE AMPACITY Duplex #4 Whippet 90 Triplex #2 150 Triplex 1/0 Leda 205 Triplex 4/0 Lepas 315 Quadruplex 1/0 Shetland 180 Quadruplex 4/0 Walking 275 Quadruplex 336.4 Lippizaner 370

NOTE: Conductor type is Aluminum C3 type NESC

10 Ampacity-Overhead Conductor-Bare

Conductor Size Continuous & Type Rating #2 CU 217 #4 CU Jumper 175 1/0 CU 297 4/0 CU 465 336.4 ACSR 522 #2 AAAC 192 1/0 AAAC 257 394.5 AAAC 536 559.5 AAAC 668 652.4 AAAC 735 927.2 AAAC 915 431 ACCC/TW 780

Above are based on 88° ambient temp, near calm winds & summer sunny day. Calculations are from Southwire software for KEYS area.

Adjustment factors If Ambient temp is 80°-- then multiply above by 1.05. If wind speed is greater than 5 mph -- then multiply above by 1.25.

Ampacity - Underground Primary 15 kV-UG Conductor Size Continuous Continuous & Type Rating 1 - Phase Rating 3 - Phase 1/0 Alum 120 - CU #2 178 - CU 500 - 524 CU 750 - 651 CU 1000 - 753 Calculations are based on KEYS conditions/design from Okonite Co. 11 Ampacities - Low Voltage Wire Insulated Conductors, Rated 0 through 2000 volts, in raceway in free air 60°c 75°c 90°c 60°c 75°c 90°c 140°F 167°F 194°F 140°F 167°F 194°F TypeTypeTypeTypeTypeType THHN, THHN, THHW, THHW, RHW, THW2, THW2, RHW, THHW, THWN2, THWN2 Size THHW, Size TW, THW, RHH, , RHH, (AWG TW THW, (AWG UF THWN, RWH2, RWH2, kcmil) THWN, kcmil) XHHW, USE2, USE2, XHHW ZW XHHW, XHHW, XHHW2, XHHW2 ZW2 ,ZW2 Aluminum or copper-clad Copper aluminum 14 16* 18* 21* ------14 12 20* 24* 27* 16* 18* 21* 12 10 27* 33* 36* 21* 25* 28* 10 83643482833378 64858653845516 46679895161694 3 76 90 102 59 70 79 3 2 88 105 119 69 83 93 2 1 102 121 137 80 95 106 1 1/0 121 145 163 94 113 127 1/0 2/0 138 166 186 108 129 146 2/0 3/0 158 189 214 124 147 167 3/0 4/0 187 223 253 147 176 197 4/0 250 205 245 276 160 192 217 250 300 234 281 317 185 221 250 300 350 255 305 345 202 242 273 350 500 315 378 427 254 303 342 500 600 343 416 468 279 335 378 600 750 387 466 529 321 384 435 750 1000 448 542 617 382 460 521 1000 Correction Factors For ambient temperatures other than 30°C (86°F), multiply Ambient Ambient the ampacities shown above by the appropriate factor Temp (°C) Temp (°F) shown below. 31-35 0.91 0.94 0.96 0.91 0.94 0.96 88-95 36-40 0.82 0.88 0.91 0.82 0.88 0.91 97-104 41-45 0.71 0.82 0.87 0.71 0.82 0.87 106-113 46-50 0.58 0.75 0.82 0.58 0.75 0.82 115-122 Not more than three conductors in race way or cable* (Extracted from the National Electrical Code) 12 Conductor Impedances Type R (ohms/kft) X (ohms/kft) OH #2 tpx 0.262 0.027 OH 1/0 tpx 0.164 0.027 OH 4/0 tpx 0.082 0.024 OH 1/0 quad 0.164 0.033 OH 4/0 quad 0.082 0.031 OH 1/0 AAAC 0.163 ----- OH 394.5 AAAC 0.051 ----- OH 431 ACCC/TW 0.12801 ----- OH 559.5 AAAC 0.036 ----- OH 652.4 AAAC 0.0309 ----- OH 927.2 AAAC 0.0217 -----

Code Names Type Name OH # 4 duplex Whippet OH # 2 tpx Shrimp OH 1/0 tpx Leda OH 4/0 tpx Lepas OH 1/0 quad Shetland OH 4/0 quad Walking OH 336.4 quad Lippizaner OH 1/0 AAAC Azusa OH 394.5 AAAC Canton OH 431 ACCC/TW Linnet OH 559.5 AAAC Darien OH 652.4 AAAC Elgin OH 927.2 AAAC Greely

13 Maximum Number of Conductors in Trade Sizes of Conduit or Tubing

Conduit Trade Size 0.5 0.75 1 1.25 1.5 2 2.5 3 3.5 4 5 56 (Inches) Conduit Size AWG, Type Letters MCM 14 13 24 39 69 94 154 12 10 18 29 51 70 114 164 THWN 10 6 1118324473104 160 8 3 5 9 16 22 36 51 79 106 136 6 1 4 6 11 15 26 37 57 76 98 125 154 FEP (14 thru 2) 4 1 2 4 7 9 16 22 35 47 60 75 94 137 FEPB (14 thru 8) 3 1 1 3 6 8 13 19 19 39 51 64 80 116 PFA (14 thru 4/0) 2 1 1 3 5 7 11 16 15 33 43 54 67 97 Pfah (14 thru 4/0) 1 1 1 1 3 5 8 12182532405072 Z (14 thru 4/0)

0 1 1 3 4 7 10 15 21 27 33 42 61 00 1 1 2 3 6 8 13 17 22 28 35 51 XHHW (4 thru 000 1 1 1 3 5 7 11 14 18 23 29 42 500 MCM) 0000 1 1 1 2 4 6 9 1215192435 250 1 1 1 3 4 7 10 12 16 20 28 300 1 1 1 3 4 6 8 11 13 17 24 350 1112 357 9121521 400 1 1 1 3 5 6 8 101319 500 1 1 1 2 4 5 7 9 11 16 600 111 134 57913 700 11 134 56811 750 11 123 46711 6 1 3 5 9 13 21 30 47 63 81 102 128 185 600 111 134 57913 XHHW 700 11 134 56711 750 11 123 46710

Primary conduit sizes

Single Cable Three Cable Cond %Fill % Fill in Jam Jam Ratio Size Volt Cond. in Type Cond. Type Ratio in in Type (AWG or Class Size DB Size DB Type DB Sch 80 kcmll) kV (In.) Cond. (In) Cond. Cond. Cond. 1/0 15 2 23 4 20 4.13 3.78 750 15 3 27 6 23 3.84 3.58

14 Maximum Conductor Per Phase Single Phase Padmounted Transformer

Max Transformer Max "Per Conductor Secondary KVA Phase" Range Conduits 4 - 4" Max 50 8 8 - 2" Max 4 - 4" Max 8 100 8 - 2" Max 4 - 4" Max 8 #2-4/0 167 8 - 2" Max 4 - 4" Max 8 250 8 - 2" Max 4 - 4" Max 8 333 8 - 2" Max

Three Phase Padmounted Transformer

Max Transformer Max "Per Conductor Secondary KVA Phase" Range Conduits 45 6 - 4" Max 6 75 6 - 4" Max 6 150 8 - 4" Max 8 300 8 - 4" Max 8 #2-750 500 8 - 4" Max 8 750 8 - 4" Max 8 1000 8 - 4" Max 8

15 Voltage Limits

Service Entrance Voltage Variation Limits Applicable at Service Entrance Points Nominal Extreme Operating Conditions System Favorable (Normal) Voltage Operating Conditions Single - Phase 120/240 110/210 114/218 126/252 129/258 240 220 228 252 259 480 440 456 504 518 Three - Phase 4 - conductor 120/208 Y 110/190 114/198 126/218 129/225 277/480 Y 253/440 263/456 291/504 299/518 Three - Phase 3 - conductor 240 220 228 252 259 480 440 456 504 518

16 Transformer Sizing Guide

# of Size Of Home Homes Apt Small Medium Large 1 25 kVA 25 kVA 25 kVA 25 kVA 2 25 kVA 25 kVA 25 kVA 25 kVA 3 25 kVA 25 kVA 25 kVA 50 kVA 4 25 kVA 25 kVA 50 kVA 50 kVA 5 25 kVA 25 kVA 50 kVA 50 kVA 6 25 kVA 50 kVA 50 kVA 50 kVA 7 50 kVA 50 kVA 50 kVA Split load 8 50 kVA 50 kVA 75 kVA Split load 9 50 kVA Split load 10 50 kVA Split load

Apt 500-999 SQ. FT Small 1000-1499 SQ. FT Medium 1500-1999 SQ. FT Large 2000-2499 SQ. FT

Note: 1) The above is a guide as to when to upgrade existing transformers and for new installations.

2) The above should be based on actual known kW loads.

17 Transformer Voltage Drop

Volts Transformer Transformer Size Loading 15 25 37.5 50 75 100 167 kVA kVA kVA kVA kVA kVA kVA 50% 1.2 1.1 1.0 1.0 0.8 1.0 0.9 60% 1.5 1.3 1.2 1.2 1.0 1.2 1.1 70% 1.7 1.6 1.4 1.4 1.2 1.4 1.3 80% 2.0 1.8 1.5 1.6 1.4 1.6 1.5 90% 2.2 2.0 1.7 1.8 1.5 1.8 1.7 100% 2.5 2.2 1.9 2.0 1.7 2.0 1.9 110% 2.7 2.4 2.1 2.2 1.9 2.2 2.1 120% 3.0 2.7 2.3 2.4 2.0 2.4 2.2

Voltage Regulator Capacity

Amp. Rating -Continuous Emergency Rating Size 10% Reg 5% Reg 10% Reg 167 220 350 310 250 320 525 450 333 440 668 600

NOTE: Emergency Rating is for 2 Hour Loading

18 Secondary Voltage Drops

Voltage Drop for 120/240 V Single-Phase Service

1/0 AL OH Triplex

5 10 15 20 25 30 35 40 45 50 kW kW kW kW kW kW kW kW kW kW Feet Volts 20 0.07 0.14 0.22 0.29 0.36 0.43 0.50 0.58 0.65 0.72 40 0.14 0.29 0.43 0.58 0.72 0.86 1.01 1.15 1.30 1.44 60 0.22 0.43 0.65 0.86 1.08 1.30 1.51 1.73 1.94 2.16 80 0.29 0.58 0.86 1.15 1.44 1.73 2.02 2.30 2.59 2.88 100 0.36 0.72 1.08 1.44 1.80 2.16 2.52 2.88 3.24 3.60 120 0.43 0.86 1.30 1.73 2.16 2.59 3.02 3.46 3.89 4.32 140 0.50 1.01 1.51 2.02 2.52 3.02 3.53 4.03 160 0.58 1.15 1.73 2.30 2.88 3.46 4.03 4.61 180 0.65 1.30 1.94 2.59 3.24 3.89 4.54 200 0.72 1.44 2.16 2.88 3.60 4.32 225 0.81 1.62 2.43 3.24 4.05 250 0.90 1.80 2.70 3.60 4.50 275 0.99 1.98 2.97 3.96 300 1.08 2.16 3.24 4.32 400 1.44 2.88 4.32

19 Secondary Voltage Drops

Voltage Drop for 120/240 V Single-Phase Service

4/0 AL OH Triplex

5 10 15 20 25 30 35 40 45 50 kW kW kW kW kW kW kW kW kW kW Feet Volts 20 0.04 0.08 0.11 0.15 0.19 0.23 0.26 0.30 0.34 0.38 40 0.08 0.15 0.23 0.30 0.38 0.45 0.53 0.60 0.68 0.75 60 0.11 0.23 0.34 0.45 0.56 0.68 0.79 0.90 1.01 1.13 80 0.15 0.30 0.45 0.60 0.75 0.90 1.05 1.20 1.35 1.50 100 0.19 0.38 0.56 0.75 0.94 1.13 1.31 1.50 1.69 1.88 120 0.23 0.45 0.68 0.90 113 1.35 1.58 1.80 2.03 2.25 140 0.26 0.53 0.79 1.05 1.31 1.58 1.84 2.10 2.36 2.63 160 0.30 0.60 0.90 1.20 1.50 1.80 2.10 2.40 2.70 3.00 180 0.34 0.68 1.01 1.35 1.69 2.03 2.36 2.70 3.04 3.38 200 0.38 0.75 1.13 1.50 1.88 2.25 2.63 3.00 3.38 3.75 225 0.42 0.84 1.27 1.69 2.11 2.53 2.95 3.38 3.80 4.22 250 0.47 0.94 1.41 1.88 2.34 2.81 3.28 3.75 4.22 4.69 275 0.52 1.03 1.55 2.06 2.58 3.09 3.61 4.13 4.64 300 0.56 1.13 1.69 2.25 2.81 3.38 3.94 4.50 400 0.75 1.50 2.25 3.00 3.75 4.50

20 Secondary Voltage Drops

Voltage Drop for 120/208 V Three-Phase Service

1/0 AL OH Quadruplex

5 10 15 20 25 30 35 40 45 50 kW kW kW kW kW kW kW kW kW kW Feet Percent 20 0.0% 0.1% 0.1% 0.2% 0.2% 0.3% 0.3% 0.3% 0.4% 0.4% 40 0.1% 0.2% 0.3% 0.3% 0.4% 0.5% 0.6% 0.7% 0.8% 0.9% 60 0.1% 0.3% 0.4% 0.5% 0.6% 0.8% 0.9% 1.0% 1.1% 1.3% 80 0.2% 0.3% 0.5% 0.7% 0.9% 1.0% 1.2% 1.4% 1.5% 1.7% 100 0.2% 0.4% 0.6% 0.9% 1.1% 1.3% 1.5% 1.7% 1.9% 2.1% 120 0.3% 0.5% 0.8% 1.0% 1.3% 1.5% 1.8% 2.0% 2.3% 2.6% 140 0.3% 0.6% 0.9% 1.2% 1.5% 1.8% 2.1% 2.4% 2.7% 3.0% 160 0.3% 0.7% 1.0% 1.4% 1.7% 2.0% 2.4% 2.7% 3.1% 3.4% 180 0.4% 0.8% 1.1% 1.5% 1.9% 2.3% 2.7% 3.1% 3.4% 3.8% 200 0.4% 0.9% 1.3% 1.7% 2.1% 2.6% 3.0% 3.4% 3.8% 225 0.5% 1.0% 1.4% 1.9% 2.4% 2.9% 3.4% 3.8% 250 0.5% 1.1% 1.6% 2.1% 2.7% 3.2% 3.7% 275 0.6% 1.2% 1.8% 2.3% 2.9% 3.5% 4.1% 300 0.6% 1.3% 1.9% 2.6% 3.2% 3.8% 400 0.6% 1.7% 2.6% 3.4%

For line-to-line drop voltage in volts, = (% Voltage Drop) (208 volts) /100 For line-to-ground voltage drop in volts, = (% Voltage Drop) (120 volts) /100

21 Secondary Voltage Drops

Voltage Drop for 120/208 V Three-Phase Service

4/0 AL OH Quadruplex

5 10 15 20 25 30 35 40 45 50 kW kW kW kW kW kW kW kW kW kW Feet Percent 20 0.0% 0.0% 0.1% 0.1% 0.1% 0.1% 0.2% 0.2% 0.2% 0.2% 40 0.0% 0.1% 0.1% 0.2% 0.2% 0.3% 0.3% 0.4% 0.4% 0.5% 60 0.1% 0.1% 0.2% 0.3% 0.4% 0.4% 0.5% 0.6% 0.6% 0.7% 80 0.1% 0.2% 0.3% 0.4% 0.5% 0.5% 0.7% 0.7% 0.8% 0.9% 100 0.1% 0.2% 0.4% 0.5% 0.6% 0.7% 0.8% 0.9% 1.1% 2.1% 120 0.1% 0.3% 0.4% 0.6% 0.7% 0.8% 1.0% 1.1% 1.3% 1.2% 140 0.2% 0.3% 0.5% 0.7% 0.8% 1.0% 1.1% 1.3% 1.5% 1.4% 160 0.2% 0.4% 0.6% 0.7% 0.9% 1.1% 1.3% 1.5% 1.7% 1.6% 180 0.2% 0.4% 0.6% 0.8% 1.1% 1.3% 1.5% 1.7% 1.9% 1.9% 200 0.2% 0.5% 0.7% 0.9% 1.2% 1.4% 1.6% 1.9% 2.1% 2.1% 225 0.3% 0.5% 0.8% 1.1% 1.3% 1.6% 1.8% 2.1% 2.4% 2.3% 250 0.3% 0.6% 0.9% 1.2% 1.5% 1.8% 2.0% 2.3% 2.6% 2.6% 275 0.3% 0.6% 1.0% 1.3% 1.6% 1.9% 2.3% 2.6% 2.9% 3.2% 300 0.4% 0.7% 1.1% 1.4% 1.8% 2.1% 2.5% 2.8% 3.2% 3.5% 400 0.5% 0.9% 1.4% 1.9% 2.3% 2.8% 3.3% 3.7%

For line-to-line voltage drop in volts, = (% Voltage Drop) (208 volts) /100 For line-to-ground voltage drop in volts, = (% Voltage Drop) (120 volts) /100

22 23 Voltage Flicker Limits Visibility and Irritation Curves - for reference only

Residential services should be designed for a maximum voltage dip (flicker) of 3%

24 Motor Starting kVA

NEMA Code Starting kVA NEMA Code Starting Letter per HP Letter kVA per HP A 0.00-3.14 L 9.00-9.99 B 3.15-3.54 M 10.00-11.19 C 3.55-3.99 N 11.20-12.49 D 4.00-4.49 P 12.50-13.99 E 4.50-4.99 R 14.00-15.99 F 5.00-5.59 S 16.00-17.99 G 5.60-6.29 T 18.00-19.99 H 6.30-7.09 U 20.00-22.39 J 7.10-7.99 V 22.40-UP

Air Conditioning Starting Currents Starting Current for Single-Phase 240 Volt Compressor

Air Conditioner Size Starting Current Up to 3 tons 100A 3+ to 3.5 tons 110A 3.5+ to 4.0 tons 120A 4.0+ to 4.5 tons 130A 4.5+ to 5.0 tons 140A

CAUTION Starting Currents can vary considerably depending

on the type of compressor.

25 Motors - Amperage

Induction Motor Full Load Amperes: 85% efficiency, 85% power factor

1/Ø AC 3/Ø AC HP 115 V 240 V 230 V 480 V 1 16 8 3.6 1.8 2 24 12 6.8 3.4 3 34 17 9.6 4.8 5 56 28 15.2 7.6 7 1/2 80 40 22 11 10 100 50 28 14 15 42 21 20 54 27 25 68 34 30 80 40 40 104 52 50 130 65 60 154 77 75 192 96 100 248 124 125 312 156 150 360 180 200 480 240

26 Sizing Delta Banks Open delta transformer bank selection chart

100

FOR LOADS IN THIS AREA INSTALL CLOSED DELTA BANKS 80

60

40 Single Phase Load kVa Load Phase Single 20 167-25

0 20 40 60 80 100 120 140 160 Three Phase Load kVA

120/240V Open Wye/Open Delta Bank For open Wye/Open Delta banks serving 120/240V single-phase load size the transformers as shown below:

Loading the 240V unit = 0.58 X three-phase load (Power Transformer)

Loading the 120/240V unit = (0.58 X three-phase load) + (Lighter Transformer) single-phase load

27 Sizing Delta Banks Delta transformer bank selection chart Three-Phase Load kVA 160 75 167 140 75 100 100 120 7 Load kVA Single Phase 75 100 5 167 25 75 100 75 25 50 75 80 75 75 50 60 50 50 5 50 0 2 40 FOR LOADS IN THIS 25-25-5 AREA INSTALL OPEN 25 DELTA BANKS 20 25

0 20 40 60 80 100 120 140 160 120/208V & 277/480V Banks For 120/208V & 277/480V transformer banks serving 3-phase loads, each transformer shall be large enough to serve 1/3 of the total 120/208/240V Banks For 120/208V banks serving 1-phase 120/240V loads, size the transformer as shown below: Loading of the 120/208V unit = Three-phase load (Power Transformers) 3 Loading of the 120/240 unit = (2/3 X three-phase load) + (Lighter Transformers) signle-phase load

28 Distribution Transformer Connections

Note: For both of the above connections Use two bushing transformers Float primary neutral Install a temporary jumper then energizing or de-energizing the transformer bank to grond Hz 29 Distribution Transformer Connections

30 Distribution Transformer Connections

Note: This connection is for maintenance only, not for new loads.

This connection is not for susceptible to ferroresonance.

31 Fusing Chart Transformer Single Phase Three Phase kVA Per Installation Installation Phase 7.96 13.8 7.96 / 13.8 5 0.5 0.5 0.75 10 1.5 1 1.5 15 2.5 1.5 2.5 25 5 2.5 5 37 74 7 50 10 5 10 75 15 7 15 100 20 10 20 167 30 15 30 250 50 25 50 Note: Dual element type KS For open Delta banks use: Common Leg - 3-Ø install chart Outside Leg - 1-Ø install chart Capacitor Banks - Use type K fuse 3-Phase Kilovar Volts 300 600 1200 13800 20 40 65 Pad-Mounted Transformer Bayonet fusing Size Phase Bayonet 25 1 C04 50 1 C08 75 1/3 C08/C06 100 1 C10 150 3 C08 167 1 C12 250 1 C14 300 3 C10 500 3 C12 750 3 C14 1000 3 C14 32 Fusing - 7970 system 1-Ø Overhead Suggested Total Transformer kVA Approximate Fuse Initial Design Ultimate Current Amp Size max Allowable Demand 10 50 65 6 20 110 140 10 25 135 175 15 30 160 210 18 35 185 230 20 40 212 250 25 50 265 350 30 65 350 450 35 80 425 550 45-60

kVA for connected transformer per phase 1) Fuse Size= X (L) ( 7.97 )

L = 1.2 for transformers that are below 100% loaded. L = 1.5 for transformers that are loaded between 100-130%.

2) Fuse Size = (Known Amperage During Peak Demand) X (1.7)

Note: 1) If a single phase transformer is connected Delta ( Ø-Ø ) Use only 1/2 of Transformer kVA when developing total. 2) Method #2 is the preferred method. Fusing - UG: Risers 3-Ø Suggested Total Transformer kVA Fuse 3-Ø Connected Size Max Load 25 150 35 300 40 500 50 750 65 1000 80 1500 100 2000 Note: For UG large loop systems, the fuse max not capable of carrying the entire system loop

33 Fault Current Customer Secondary - AERIAL Transformers

Fault Current - Max @ Secondary kVA Total @ Seconday Number Z% KEYS 6500 7.97/13.8Y Voltage of Phases Infinite AMP AMP at at Primary Primary 1-25 kVA 120/240 1 9000 10400 120/208 3 9000 10400 2.0 3-25 kVA 240 delta 3 8000 9000 277/480 3 4000 4500 1-50 kVA 120/240 1 16500 19000 120/208 3 16500 19000 2.2 3-50 kVA 240 delta 3 14500 16500 277/480 3 7000 8200 1-75 kVA 120/240 1 25000 28500 120/208 3 25000 28500 2.2 3-75 kVA 240 delta 3 21500 24500 277/480 3 10500 12000 1-100 kVA 120/240 1 31000 36000 120/208 3 31000 36000 2.3 3-100 kVA 240 delta 3 27500 31500 277/480 3 14000 16000 1-167 kVA 120/240 1 49000 56000 120/208 3 49000 56000 2.5 3-167 kVA 240 delta 3 42000 48000 277/480 3 21000 24000 1-250 kVA 120/240 1 60500 69500 120/208 3 60500 69500 3.0 3-250 kVA 240 delta 3 52000 60000 277/480 3 26000 30000 1-333 kVA 120/240 1 75500 87000 120/208 3 75500 87000 3.2 3-333 kVA 240 delta 3 65000 75000 277/480 3 33000 38000

Note: Based on KEYS fault current study and generation/T-line configuration as of 2011

Upon request, KEYS Field Rep can provide these tables to customer or the electrician 34 Fault Current Customer Secondary - PADMOUNTED Transformers

Fault Current - Max @ Secondary kVA Total @ Seconday Number Z% 7.97/13.8Y Voltage of Phases KEYS 6500 Infinite AMP at AMP at Primary Primary 50 kVA 120/240 1 2.2 16,500 19,000 100 kVA 120/240 1 2.3 31,500 36,200 167 kVA 120/240 1 2.1 50,500 58,000 250 kVA 120/240 1 3.3 27,500 31,200 120/208 23,500 27,000 150 kVA 3 1.5 277/480 10,100 11,600 120/208 34,800 40,000 300 kVA 3 2.1 277/480 14,800 17,000 120/208 53,100 61,000 500 kVA 3 2.3 277/480 22,600 26,000 120/208 34,200 39,300 750 kVA 3 5.3 277/480 14,800 17,000 1000 kVA 277/480 3 5.4 19,900 21,200

Note: Based on KEYS fault current study and generation/T-line configuration as of 2011

Upon request, KEYS Field Rep can provide these tables to customers or the electrician

35 Fault Current At KEYS Distribution Substation

Primary Max - Fault Current Substation Voltage P-P Fault P-G Fault KWD-1 7.97/13.8Y 13,389 15,739 KWD-2 7.97/13.8Y 13,389 15,739 WSS-1 7.97/13.8Y 14,115 16,733 WSS-2 7.97/13.8Y 14,115 16,733 TSS 7.97/13.8Y 7,341 7,927 KDS-1 7.97/13.8Y 15,695 18,312 KDS-2 7.97/13.8Y 15,695 18,312 SSS 7.97/13.8Y 9,822 10,558 US1 7.97/13.8Y 10,214 11,039 BCS 7.97/13.8Y 8,585 9,219 CKS 7.97/13.8Y 8,932 9,594 BPS-1 7.97/13.8Y 15,145 16,795 BPS-2 7.97/13.8Y 15,145 16,795

Note: 1) Based on KEYS fault current study and generation/T-line configuration as of 2017 Upon request, KEYS Field Rep can provide these tables to customer or the electrician

2) The above is KEYS max with T-line in and all of KEYS generation online.

36 Pole Setting Depths and Guy Leads

1-phase Guy Attachment Heights & Guy Leads Average Guy Lead (ft) Pole Height Setting Minimum Preferred Avg. Attachment Height (ft) Depth (ft) Lenght Lenght 40 6.0 32.50 16 20 45 6.5 37.00 19 22 50 7.0 41.50 21 25 55 7.5 46.00 23 28

3-phase Guy Attachment Heights & Guy Leads Average Guy Lead (ft) Pole Height Setting Minimum Preferred Avg. Attachment Height (ft) Depth (ft) Lenght Lenght 45 6.5 36.25 18 22 50 7.0 40.75 20 24 55 7.5 45.25 23 27

37 38 Weights - Poles and Base Diamter Material Size Type Lbs Diameter Concrete 35' III 2,440 Concrete 36' traffic 3,650 Concrete 40' III 3,560 13.2" Concrete 45' HIII 7,000 17.7" Concrete 40' A-storm 5,680 15.7" Concrete 45' A-storm 6,560 16.5" Concrete 45' B-storm 7,600 19.0" Concrete 50' C-storm 9,900 21.3"

Ductile 35 C2 856 11.7" Ductile 40 H1 1,777 15.5" Ductile 45 H3 2,081 16.5" Ductile 45 H5 2,339 19.2" Ductile 50 H5 2,815 20.3" Ductile 55 H6 3,293 23.3"

Wood 35' 4 1,026 10.0" Wood 40' 4 1,272 10.7" Wood 40' 2 1,692 12.3" Wood 45' 2 2,046 12.9" Note: Lbs is approximate

Weights - Transformers Aerial Padmounts Size Lbs Size Lbs 15 kVA 334 50 kVA 1,242 25 kVA 381 100 kVA 1,337 50 kVA 514 150 kVA 3,240 75 kVA 862 167 kVA 1,838 100 kVA 991 250 kVA 2,770 167 kVA 1,506 300 kVA 4,117 250 kVA 2,110 500 kVA 5,530 333 kVA 2,337 750 kVA 8,127 500 kVA 4,088 1000 kVA 9,720 Note: Lbs is approximate 39 Polypropylene Rope Sling, Rated Capacity in Pounds Eye and eye sling Basket Hitch

Angle of rope to horizontal

90° 60° 45° 30°

Angle of rope to vertical Rope Nominal Minimum diameter weight breaking (nominal) per 100 strength, Vertical Choker in. ft, lb lb. hitch hitch 0° 30° 45° 60° 1/2 4.7 3,990 650 350 1,300 1,200 950 650 9/16 6.1 4,845 800 400 1,600 1,400 1,000 800 5/8 7.5 5,890 1,000 500 2,000 1,700 1,400 1,000 3/4 10.7 8,075 1,300 700 2,700 2,300 1,900 1,300 40 Sag and Tensions for Overhead Services

Sag and Tension for service conductors Span Length (ft) Wire Size 100 125 150 175 200 225 250 #2 TPX Sag (ft) 1.5 1.5 2.0 2.5 3.0 3.0 3.0 Tension 200 310 340 370 400 520 630 (lb)

1/0 TPX Sag (ft) 2.0 2.0 2.5 2.5 3.0 3.0 3.5 Tension 240 380 440 600 650 710 880 (lb)

4/0 TPX Sag (ft) 2.0 2.0 2.5 3.0 3.5 4.0 4.0 Tension 440 695 800 910 1000 1140 1400 (lb)

1/0 Quad Sag (ft) 2.0 2.0 2.5 3.0 3.5 4.0 Tension 360 570 650 740 830 910 (lb)

4/0 Quad Sag (ft) 2.0 2.5 3.0 3.5 4.0 Tension 690 840 1000 1170 1350 (lb)

Dead-end tensions for primary conductors (lbs) Conductor Size Bare CU. AAAC ACSR # 1/0 ---- 560 ---- # 2/0 1390 ---- 1600 # 4/0 2183 1080 2525 336.4 kcmil ------2600 394.5 kcmil ---- 2600 ---- 559.5 kcmil ---- 2723 ---- 927.2 kcmil---- 4860 ----

41 Underground Cable Max Pulling Tension* (pull Via conductor) Wire Size One Conductor Three Conductors #2 531 1,593 1/0 846 2,539 500 4,000 10,000 750 6,000 10,000 1000 6,000 10,000

Underground Cable Max Pulling Tension* (pull Via a basket grip) Wire Size One Conductor Three Conductors #2 531 1,593 1/0 846 2,593 500 1,000 3,000 750 1,000 3,000 1000 1,000 3,000

*Based on Industry Standards and Okonite Cable Technical Data Pulling Lubricant Recommended--Polywater Lubricant Type J

42 NESC Clearance Reference Guide

Pole Midspan House Comm-Neutral 30" ① 30" ----- Comm-Sec (insul) 30" ① 30" 12" Comm-Sec (Open) 40" 40" ----- Comm-X-Former 40" ------Comm-St. Light 12" ② ------Non- Adj- NESC Rule 232 Driveway Street Vehicle Road Neutral 9.5' 15.5' 15.5' 15.5' Sec (Insulated) 12' ⑤ 16' ③ 16' 16' Sec (Open) 12.5' 16.5' 16.5' 16.5' Primary 14.5' 18.5' 18.5' 18.5' Bldg/ Bldg- Sign & Balcony NESC Rule 232 Balcony Pool Vert Anten Vert Hort Neutral 3' 4.5' 22' 4.5' 10.5' Sec (Insulated) 3.5' ④ 5' 22.5' 5' 11' Sec (Open) 10' 5.5' 23' 5.5' 11.5' Primary 12.5' 7.5' 25' 7.5' 13.5' Note: ① 40" if communication not grounded ② 12" from drip loop if light not grounded ③ Reduce to 12.5' for difficult installation ④ Reduce to 3' if drop is to bldg (non-prefered) May be reduced to 18" if riser is within 4' from roof edge and drop limited to 6' over roof. ⑤ Insulated service drops limited to 300 V to ground can be reduce to 10.5' residential building only. 43 Service Drop Clearance

Notes: 1. NESC required vertical clearance over pedestrian way. - 12' ft 2. NESC required vertical clearance for service over residential driveway not subjet to truck traffic. - 16' ft 3. NESC required vertical clearance for service over nonresidential driveway subject to truck traffic. - 16' ft 4. Reuired vertical clearance of service drip loop, over roof where less than 6' of conductors overhang the roof. - 18" in EXCEPTIONS TO NOTES 1 & 2 Prior approval by KEYS representive is reuired before exceptions are used. Where height of installation does not permit service drops to meet these vales they may be reduced to the following: 1. Over pedestrian traffic way. - 10' ft 2. Over residential driveway. - 12' ft 44 Minimum Working Clearances

Voltage Minimum Working and Phase to Phase Clear Hot Stick Distance KV Feet/Inches 1.1 - 15 2' - 1" 15 - 36** 2' - 4" 36.1 - 46 2' - 7" 46.1 - 72.5** 3' - 0" 72.6 - 121 3' - 2" 138 - 145** 3' - 7"

** Applicable to KEYS

Minimum Clearances Between Conductors

Voltage Range Phase to Phase to Phase to Phase Ground Ground KV Meters Ft/in Meters Ft/in 30 - 35 0.7 2' - 4" 0.7 2' - 4" 35.1 - 46 0.8 2' - 6" 0.8 2' - 6" 46.1 - 72.5** 0.9 3' - 0" 0.9 3' - 0" 72.6 - 121 1.0 3' - 4" 1.4 4' - 6" 138 - 145** 1.1 3' - 6" 1.5 5' - 0"

Note: From AB chance index card & Lineman Hand Book

45 Utility Underground Clearance

Color Utility Name Red Electric KEYS Orange Telephone/Cable TV AT&T/COMCAST Blue Water FKAA Green Sewer OMI Purple reclaimed FKAA

Any digging within 24 inches of either side of the location markings must be done by hand.

Call Sunshine (UG Clearance Company)

Ph # 1-800-432-4770 Ph # 811 Key West Pipeline Ph# 305-522-9926

46 ADA Wheelchair Passage Width

The U.S. Access Board's ADA Accessibility Guidelines (ADAAG) requires that a minimum clear width for a single wheelchair passage shall be 36" minimun. An exception for a wheelchair width of 32" minimun for the maximum length of 24" (see figure).

Sidewalk width is measured from the back of the curb to the back of the sidewalk; the curb is not included in any width measurements.

47 Transmission Line Summary CBA Phasing

Curcuit Distance Conductor Location Voltage No. (miles) Size & Type

1 WSS - Kennedy Drive 69 kV 2.71 431 ACCC/TW 2 WSS - KW Diesel 69 kV 1.41 927 ACAR 10,11 KW Diesel - Kennedy Drive 69 kV 3.43 927 ACAR Stock Island Steam - 3 69 kV 3.2 927 ACAR Kennedy Drive 5 Stock Island Steam - US-1 69 kV 1.27 927 ACAR 8 US-1 - Kennedy Drive 69 kV 3.05 927 AAAC 4 US-1 - Big Coppitt 138 kV 7.85 559 AAAC 6 Big Coppitt - Big Pine 138 kV 20.87 927 AAAC 7 Big Pine - Marathon 138 kV 16.44 927 AAAC 9 US-1 - Big Coppitt 138 kV 5.51 927 AAAC Total Miles 69 kV 15.07 65.74 Total Miles 138 kV 50.67

Transmission Circuit Ratings

Normal Curcuit Conductor Type Voltage MVA No. Rating 1 431 ACCC/TW 69 kV 93 2,3,5, 927 ACAR 69 kV 92 10,11 8 927 AAAC 69 kV 88 4 559 AAAC 138 kV 141 6 927 AAAC 138 kV 174 7 927 AAAC 138 kV 174 9 927 AAAC 138 kV 239

Note: Rating per FAC-008-3 dated 12-2013 (138kv only) and LIDAR NERC derating

48 Substation Transformer Ratings

Transformer Ratings, MVA Sub Voltage Continuous (65°C) Summer Station Nameplate Emergency

KWD 69-13.8kV13.4/17.9/22.4(OA/FA/FOA) 24.6 (T1) KWD 69-13.8kV25/33.3/41.7 (OA/FA/FA) 45.9 (T2) WSS 69-13.8kV25/33.3/41.7 (OA/FA/FA) 45.9 (T1) WSS 69-13.8kV25/33.3/41.7 (OA/FA/FA) 45.9 (T2) TSS 69-13.8kV20.2/26.9/33.6 (OA/FA/FA) 37.0 (T1) KDS 69-13.8kV25/33.3/41.7 (OA/FA/FA) 45.9 (T1) KDS 69-13.8kV25/33.3/41.7 (OA/FA/FA) 45.9 (T2) SSS 69-13.8kV25/33.3/41.7 (OA/FA/FA) 45.9 (T1) US1 69-13.8kV25/33.3/41.7 (OA/FA/FA) 45.9 (T1) US1 138-69kV 62.8/83.8/104.7 (OA/FA/FA) 104.7 * (A1) US1 138-69kV 50.4/67.1/83.9 (OA/FA/FA) 94* (A2) BCS 138-13.8kV16.8/22/28 (OA/FA/FA) 30.8 (T1) CKS 138-13.8kV25/33.3/41.7 (OA/FA/FA) 45.9 (T1) BPS 138-13.8kV18/24/30 (OA/FA/FA) 33.0 (T1) BPS 138-13.8kV18/24/30 (OA/FA/FA) 33.0 (T2)

Note: * 4hr emergengy rating per FAC-008-3 date 12-2013

Effect of Ambient Temperatures on kVA Capacity

% of rated kVa decrease in % of kVa increase in Type of Cooling capacity of each °C increase capacity for each °C over 30°C air decrease under 30°C air

Self-cooled-OA 1.5 1.0 Forced-air-cooled- 1.0 0.75 OA/FA, OA/FA/FA Forced-air-cooled- OFOA, 1.0 0.75 OA/FOA/FOA

49 Transmission Line #4 (138KV) Fault Locating Looking from Big Coppitt Substation Fault KEYS Distance Landmarks T-Pole From SEL Number 0 Miles BCS BC26 0.4 Crosses US 1 To The North BC12 1 Leaving Land Ave F Big Coppitt BC12-1-3-27 1.1 Dredge Pitts Toppinos T4-79 3.3 North End of Rockland Key (In Water) T4-54 6.3 3 pole Structure behind Key Haven T4-19 7.7 US 1 T4-1

Transmission Line #4 (138KV) Fault Locating Looking from US 1 Substation

Fault KEYS Distance Landmarks T-Pole From SEL Number 0 Miles US 1 T4-1 1.3 3 pole Structure behind Key Haven T4-19 4.3 North end of Rockland Key (In Water) T4-54 5 Dredge Pitts Toppinos T4-79 6.8 On land Ave F Big Coppitt BC12-1-3-27 Corner of 1st Street and Ave F 7.3 BC12-1-3 Big Coppitt 7.7 BCS BC26

Phasing CBA

50 Transmission Line #6 (138KV) Fault Locating Looking from Big Coppitt Sub to Big Pine Sub (North)

Fault KEYS D.O.T Distance Landmarks T-Pole MM From SEL Number 0 Miles 10.6Big Coppitt Substation BCS 1 11.6Shark Channel 15 2 12.6Saddle Bunch #5 Channel 28 3 13.6N/A 42 4 14.6Saddle Bunch #2 Channel 54 5 15.6North of Lower Sugarloaf Channel 70 6 16.6Entrance to South Point 82 7 17.6North Harris Channel 97 8 18.6Park Channel 110 9 19.6North of Sugarloaf Elementary 123 10 20.6N/A 136 11 21.6North of FL Keys Realty 150 12 22.6Animal Hospital 163 13 23.6Kemp Channel 177 14 24.6South of ACE Hardware 191 15 25.6Niles Channel Bridge 204 16 26.6Radio Tower/Island Auto Sales 214 17 27.6North of Torch Ramrod Channel 229 18 28.6South Pine Channel 243 19 29.6North of Entrance to Big Pine 257 20 30.6Tom Thumb 271 20.6 30.8 1 Big Pine Substation BPS

Note: 1. Mile Marker 30.8 is at the intersection of US1 and County Road, Big Pine Substation sets in 0.4 miles from Mile Marker 30.8 Phasing CBA 51 Transmission Line #6 (138KV) Fault Locating Looking from Big Pine Sub to Big Coppitt Sub (South)

Fault KEYS D.O.T Distance Landmarks T-Pole MM From SEL Number 0 Miles 30.8 2 Big Pine Substation BPS 1 30.2South of Flea Market 263 2 29.2South of North Pine Channel 252 3 28.2King Coves Road 238 4 27.2Looe Key Chevron 222 5 26.2North of Niles Channel Bridge 209 6 25.2South of Niles Channel Bridge 200 7 24.2N/A 185 8 23.2South of Kemp Channel 171 9 22.2N/A 158 10 21.2Colson Drive on Cudjoe 144 11 20.2Bow Channel 131 12 19.2South of Sugarloaf Elementary 118 13 18.2N/A 103 14 17.2Sugarloaf Fire Department 90 15 16.2N/A 75 16 15.2South of Lower Sugarloaf Channel 62 17 14.2South of Saddle Bunch #3 Channel 48 18 13.2Saddle Bunch #4 Channel 34 19 12.2N/A 21 20 11.2South of Entrance to Shark Key 8 20.6 10.6Big Coppitt Substation BCS

Note: 2. Mile Marker 30.8 is at the intersection of US1 and County Road, Big Pine Substation sets in 0.4 miles from Mile Marker 30.8 Phasing CBA 52 Transmission Line #7 (138KV) Fault Locating Looking from Big Pine Sub to Marathon Sub (North) Fault KEYS D.O.T Distance Landmarks T-Pole MM From SEL Number 0 Miles 30.8 1 Big Pine Substation BPS 1 31.4Just South of Beach Drive 18 2 32.4N/A 31 3 33.4Spanish Harbor Channel 44 4 34.4West Summerland 57 5 35.5Bahia Honda Bridge 72 6 36.4Bahia Honda Bridge 86 7 37.4Just North of Bahia Honda Bridge 100 8 38.4Entrance to Sunshine Key 114 9 39.4Little Duck Channel 126 10 40.4Seven Mile Bridge 140 11 41.4Just North of Line Crossover 154 12 42.4Seven Mile Bridge 167 13 43.4South of Hump on Seven Mile Bridge 179 14 44.4North of Hump on Seven Mile Bridge 187 15 45.4Seven Mile Bridge 199 16 46.4Seven Mile Bridge 213 17 47.87 Mile Grill (Marathon) 1414 18 48.4Florida D.O.T. 1391A 18.2 48.6Marathon Substation MS

Note: 1. Mile Marker 30.8 is at the intersection of US1 and County Road, Big Pine Substation sets in 0.4 miles from Mile Marker 30.8 Phasing CBA 53 Transmission Line #7 (138KV) Fault Locating Looking from Marathon Sub to Big Pine Sub (South) Fault KEYS D.O.T Distance Landmarks T-Pole MM From SEL Number 0 Miles 48.6Marathon Substation MS 1 47.6Vaca Key Marina 1409A 2 46.6Seven Mile Bridge 215 3 45.6Seven Mile Bridge 202 4 44.6North of Hump on Seven Mile Bridge 189 5 43.6South of Hump on Seven Mile Bridge 178 6 42.6Seven Mile Bridge 167 7 41.6Just North of Line Crossover 154 8 40.6Seven Mile Bridge 141 9 39.6Just South of Seven Mile Bridge 130 10 38.6Sunshine Key 116 11 37.6N/A 103 12 36.6Entrance to Bahia Honda Park 89 13 35.6Bahia Honda Bridge 76 14 34.6Just South of Bahia Honda Bridge 60 15 33.6Spanish Harbor Channel 46 16 32.6Entrance to Big Pine Key 33 17 31.6Just North of Beach Drive 20 18 30.8 2 County Road 4 18.2 30.8 3 Big Pine Substation BPS

Note: 2. KEYS Pole Number 4 sets in 0.2 miles from Mile Marker 30.8 3. Mile Marker 30.8 is at the intersection of US1 and County Road, Big Pine Substation sets in 0.4 miles from Mile Marker 30.8 Phasing CBA 54 Transmission Line #9 (138KV) Fault Locating Looking from US 1 Substation Fault KEYS Distance Landmarks T-Pole From SEL Number 0 Miles US 1 0.1 Entrance to Key Haven T9-5 0.8 West end Boca Chica Bridge T9-14 1.3 East end Boca Chica Bridge T9-21 2.9 Entrance to Boca Chica Base T9-45 West End Rockland Key Channel 4.3 T9-69 Bridge 5.4 BCS

Transmission Line #9 (138KV) Fault Locating Looking from Big Coppitt Substation Fault KEYS Distance Landmarks T-Pole From SEL Number 0 Miles BCS BCS to East end Rockland Channel 0.85 T9-73 Bridge BCS to West end Rockland Channel 1.09 T9-69 Bridge 2.5 Entrance to Boca Chica Base T9-45 4 East end Boca Chica Bridge T9-21 4.5 West end Boca Chica bridge T9-14 5.2 Entrance to Key Haven T9-5 5.4 US 1 Phasing CBA 55 Transmission Line #1 (69KV) Fault Locating Looking from Kennedy Dr (KDS) Substation Fault KEYS Distance Landmarks T-Pole From SEL Number 0 Miles KDS G9-16 0.89 KDS to Sigsbee Causeway T1-33 Causeway to Garrison Bight 2.1 T1-24 Channel Bight Channel to Garrison Bight 2.2 T1-20 Bridge 2.65 Spencers Boat yard T1-18 WSS D1-3

Transmission Line #1 (69KV) Fault Locating Looking from White St (WSS) Substation Fault KEYS Distance Landmarks T-Pole From SEL Number 0 Miles WSS D1-3 0.48 Spencers Boat yard T1-18 Bight Channel to Garrison Bight 0.97 T1-20 Bridge Garrison Bight Bridge to Sigsbee 1.86 T1-24 Causeway 2.65 Sigsbee Causeway to KDS T1-33 KDS G9-16 Phasing CBA 56 Transmission Line #2 (69KV) Fault Locating Looking from White St (WSS) Substation

Fault KEYS Distance Landmarks T-Pole From SEL Number 0 Miles WSS A40-2 0.26 WSS to Southard St. D2-34 0.76 Southard St. to Simonton St. A57-5 1.25 KWD B5-6 1.31 Fort St & Truman (Line 10) NS28 1.51 Fort St & Truman (Line 10) NS28 Truman Ave and Whitehead 1.74 B24-7 (Line 10) Whitehead and United St 1.97 H2-1 (Line 10) 2.68 United and White (Line 10) H2-1 2.98 TSS (Line 10) J3-4A

Transmission Line #2 (69KV) Fault Locating Looking from Key West Diesel (KWD) Substation

Fault KEYS Distance Landmarks T-Pole From SEL Number 0.47 KWD to Simonton & Southard A57-5 0.99 Simonton/Southard to White D2-34 1.25 Southard/White to WSS

Phasing CBA 57 Transmission Line #3 (69KV) Fault Locating Looking from Kennedy Dr (KDS) Substation Fault KEYS Distance Landmarks T-Pole From SEL Number 0 Miles KDS G9-15 0.34 KDS to Duck Ave/14th St M2-13 0.85 14th St/Duck Ave to 18th St/Duck Ave M7-6 1.21 Duck Ave/18th St to S. Roosevelt/US1 M14-6 1.91 US1/S. Roosevelt to Cross St/US1 SK26-13 2.36 Cross St/US1 to 3rd St/3rd Ave SK54-13 2.75 3rd Ave/3rd St to Front St/4th Ave SK54-17.5 3.25 4th Ave/Front St to SIPP SK55-18 3.25 SIPP SK55-18

Transmission Line #3 (69KV) Fault Locating Looking from Stock Island Plant (SIPP) Substation Fault KEYS Distance Landmarks T-Pole From SEL Number

0 Miles SIPP SK55-18 0.5 SIPP to Front/4th Ave SK55-18 0.66 Front St/4th Ave to 3rd St/3rd Ave SK54-17.5 1.21 3rd St/3rd Ave to Cross St/US1 SK54-13 1.86 Cross St/ US1 to US1 /S. Roosevelt SK26-13 2.39 US1/S. Roosevelt to 18th St/Duck Ave M14-6 2.89 18th St/Duck Ave to Duck Ave/14th St M7-6 3.25 Duck Ave/14th St to KDS M2-13 3.25 KDS G9-15 Phasing CBA 58 Transmission Line #5 (69KV) Fault Locating Looking from US-1 Substation

Fault KEYS Distance Landmarks T-Pole From SEL Number

0 Miles US1 US1-S1 0.49 SIPP to Front St/4th Ave SK54-17.5 1 4th Ave/US1 to 3rd/US1 SK54-13 1.26 3rd/US1 to US1 Sub SK24-1

Transmission Line #5 (69KV) Fault Locating Looking from Stock Island Substation

Fault KEYS Distance Landmarks T-Pole From SEL Number 0 Miles SIPP 0.26 US1 Sub to 3rd/US1 SK24-1 0.75 3rd/US1 to 4th Ave/Front SK54-17.5 1.26 4th Ave/Front to SIPP T-8

Phasing CBA

59 Transmission Line #8 (69KV) Fault Locating Looking from Kennedy Drive Substation Fault KEYS Distance Landmarks T-Pole From SEL Number 0 Miles KDS G9-17 0.35 KDS to Flagler Ave L43-7 0.83 Flagler Ave to 17th St M32-1 1.33 17th St/Flager to S. Roosevelt Blvd M36-11 1.62 S. Roosevelt to Triangle/US-1 G19-8 2.14 Triangle/US-1 to Cross St US1-S20 2.82 Cross St/US-1 to US-1 Sub US1-S1

Transmission Line #8 (69KV) Fault Locating Looking from US-1 Substation Fault KEYS Distance Landmarks T-Pole From SEL Number 0 Miles US-1 0.7 US-1 Sub to Cross St/US-1 US1-S1 1.24 Cross St/US-1 to Triangle US1-S20 1.53 Triangle to Flagler Ave/S. Roosevelt G19-8 2.03 Flagler Ave/S. Roosevelt to 17th/Flagler M36-11 2.51 17th St/Flagler to Kennedy/Flagler M32-1 2.82 Kennedy Dr/Flagler Ave to KDS L43-7

Phasing CBA 60 Transmission Line #11 (69KV) Fault Locating Looking from Thompson Substation Fault KEYS Distance Landmarks T-Pole From SEL Number 0 Miles TSS J3-6.5 0.16 VonPhister and Thompson J18-1 0.39 Staples Ave and 1st St K35-1 0.76 Staples Ave and 6th St L33-1 Staples Ave and 6th St to 1 L35-2.5 Salt Run Channel 1.4 Salt Run Channel to Kennedy Dr L32-1 1.71 Luani Plaza to KDS L47-8 Transmission Line #11 (69KV) Fault Locating Looking from Kennedy Drive Substation Fault KEYS Distance Landmarks T-Pole From SEL Number 0 Miles KDS L47-8 0.31 Kennedy Dr in front of Luani Plaza L32-1 0.71 Kennedy Dr to Salt Run Channel L36-1 0.95 Staples Ave to 6th St L33-1 1.32 Staples Ave and 1st St K35-1 1.55 VonPhister and Thompson J28-1 1.71 TSS J3-4A 2.03 United St and White St (line 10) H12-1 2.74 United St and Whitehead (line 10) H2-1 2.97 Whitehead and Truman (line 10) B24-7 3.2 Truman Ave and Fort St (line 10) NS28 3.3 KWD NS25

Phasing CBA 61 KEYS Generation

MW Name Capacity Capacity Max. Min. SI - CT-1 18 5 SI - CT-2 16 5 SI - CT-3 16 5 SI - CT-4 44 5 SI - EP-2 2 1 SI - MSD-1 7.5 4 SI - MSD-2 7.5 4

Note: The above may vary, for actual rating, call the Generation Department.

62

General Directions for First Aid: While help is being summoned, do the following: 1) Minimize further injury – move victim if necessary for safety reasons 2) Control severe bleeding 3) Maintain an open airway and give Rescue Breathing or CPR if necessary 4) Treat for shock Urgent Care: BLEEDING-WOUNDS First Aid: 1) Direct Pressure and Elevation:  Place dressing and apply direct pressure directly over the wound, then elevate above the level of the heart. Unless evidence of fracture. 2) Apply pressure bandage:  Wrap bandage snugly over the dressing. 3) Pressure Point:  If bleeding doesn’t stop after direct pressure, elevation, and pressure bandage. Compress the pressure point.  Arm: Use the brachial artery – pushing the artery against the upper arm bone.  Leg: Apply pressure on femoral artery – pushing it against the pelvic bone. 4) Nosebleed:  To control a nosebleed, have the victim lean forward and pinch the nostrils together until the bleeding stops. POISONING Signals: Vomiting, heavy labored breathing, sudden onset of pain or illness, burns or odor around the lips or mount, unusual behavior. First Aid:  If you think someone has been poisoned, call your poison control center or local emergency number and follow their directions. If conscious:  Call Poison Control and try to identify the poison – be prepared to inform poison control of the type of poison, when incident occurred, victim’s age, symptoms, and how much poison may have been ingested, inhaled, absorbed, or injected. If unconscious or nauseous: 1) Position victim on side and monitor vital signs (pulse and breathing) 2) Call Poison Control and identify poison. 3) DO NOT give anything by month. SHOCK Signals: Cool, moist, pale, bluish skin, weak rapid pulse (over 100), nausea, rate of breathing increased, apathetic. First Aid: 1) Maintain open airway, have victim lie down 2) Maintain normal body temperature (98.6). If too hot, cool down, and if too cold, use blankets, over and under, to warm the victim.

63

BURNS

Signals: Small, thin (surface) burns or large, thin burns: redness, pain, and swelling. Deep burns: blisters, deep tissue destruction, charred appearance. First Aid: 1) Stop the burning – put out flames or remove the victim from the source of the burn. 2) Cool the burn – run or pour cool water on burn. Immerse if possible. Cool until pain is reduced. 3) Cover the burn – use dry, sterile dressing and bandage. 4) Keep victim as comfortable as possible from being chilled or over heated.  Chemical burn – must be flushed with large amounts of water until EMS arrives.  Electrical burn – make sure power is turned off before touching the victim.

ELECTRICAL SHOCK Signals: Unconsciousness, absence of breathing & pulse First Aid: 1) TURN OFF THE POWER SOURCE – Call EMS (DO NOT approach victim until power has been turned off). 2) DO NOT move a victim of electrical injury unless there is immediate danger. 3) Administer rescue breathing or CPR if necessary. 4) Treat for Shock. 5) Check for other injuries and monitor victim till medical help arrives.

HEAT EXHAUSTION/HEAT STROKE Signals: Heat Exhaustion: Pale clammy skin, profuse perspiration, weakness, nausea, and headache. Heat Stroke: Hot dry red skin, no perspiration, rapid & strong pulse. High body temperature (105°+) this is an immediate life threatening emergency. First Aid: 1) Get the victim out of the heat. 2) Loosen tight clothing or restrictive clothing. 3) Remove perspiration soaked clothing. 4) Apply cool, wet cloths to the skin. 5) Fan the victim. 6) If victim is conscious give cool water to drink. 7) Call for an ambulance if victim refuses water, vomits, or starts to lose consciousness.

64 RESCUE BREATHING

1) Check the victim. Tap and shout, “Are you okay?” to see if the person responds. 2) CALL EMS 911 3) CARE FOR THE VICTIM Step1: Look, listen and feel for breathing for about 5 seconds If the person is not breathing or you can’t tell …. Step 2: Position victim on back, also supporting head and neck Step 3: Tilt head back and lift chin. Step 4: look, listen, and feel for breathing for about 5 seconds. If not breathing …. Step 5: Give two slow gentle breaths Step 6: Check pulse for 5 to 10 seconds Step 7: Check for severe bleeding 4) GIVE RESCUE BREATHING If pulse is present but person is still not breathing … Step 1: Give one slow breath about every 6 to 8 seconds. Do this for about 1 minute (12 breaths) Step 2; Recheck pulse and breathing about every minute Continue rescue breathing as long as pulse is present but person is not breathing 5) BEGIN CARDIOPULMONARY RESUSCITATION (CPR) If there is no pulse and no breathing.

FIRST AID FOR CHOKING

1) Check the victim When an adult is choking: Step 1: Ask, “Are you choking?” If victim cannot cough, speak, or breathe, is coughing weakly or is making high-pitched noises…. Step 2: Shout, “HELP!” Step 3: Phone EMS for help – Send someone to call for ambulance Step 4: Do abdominal thrusts: A. Wrap your arms around victim’s waist. Make a fist. Place thumb side of fist against middle of abdomen just above the navel. Grasp fist with other hand. B. Give quick, upward thrusts. Repeat until object is coughed up or person becomes unconscious IF VICTIM BECOMES UNCONSCIOUS, LOWER TO THE FLOOR Step 5: Do a finger sweep- Lift jaw and tongue, do a finger sweep to remove any obstruction Step 6: Open Airway – tilt head back and lift chin Step 7: Attempt to give breaths. With head tilted back and chin lifted, pinch nose shut. Give two breaths for 1 ½ - 2 seconds each IF AIR WON’T GO IN …. Step 8: Give up to 5 abdominal thrusts – If air won’t go in … Place heel of one hand against middle of victim’s abdomen just above the navel. Place other hand on top of first hand. Press into abdomen with up to five quick upward thrusts. Repeat breaths, thrusts, and sweeps until breaths go in or victim starts to breathe. 65 Relay Devices Number / Names

1 Master Element 48 Incomplete sequence relay 2 Time-delay starting or closing relay 49 Machine or transformer, thermal relay 3 Checking or interlocking relay Instantaneous overcurrent, 50 4 Master contactor or rate-of-rise relay 5 Stopping device 51 Ac time overcurrent relay 6 Starting circuit breaker 52 Ac Circuit breaker 7 Anode circuit breaker 53 Exciter or dc generator relay 8 Control power disconnecting 54 Reserved for future application 9 Reversing device 55 Power factor relay 10 Unit sequence switch 56 Field application relay 11 Reserved for future application 57 Short-circuiting or grounding device 12 Over-speed device 58 Rectification failure relay 13 Synchronous-speed device 59 Overvoltage relay 14 Under-speed device 60 Voltage or current balance relay 15 Speed or frequency, matching device 61 Reserved for future application 16 Reserved for future application 62 Time-delay stopping or opening relay 17 Shunting or discharge switch 63 Pressure switch 18 Accelerating or decelerating device 64 Ground protective relay 19 Starting-to-running transition contactor 65 Governor 20 Electrically operated valve 66 Notching or jogging device 21 Distance relay 67Ac directional overcurrent relay 22 Equalizer circuit breaker 68 Blocking relay 23 Temperature control device 69 Permissive control device 24 Volts per hertz relay 70 Rheostat Synchronizing 71 Level switch 25 or synchronism check device 72 Dc circuit breaker 26 Apparatus thermal device 73 Load-resistor contactor 27 Undervoltage relay 74 Alarm relay 28 Flame detector 75 Position changing mechanism 29 Isolating contactor 76 Dc overcurrent relay 30 Annunciator relay 77 Pulse transmitter 31 Separate excitation device 78 Phase angle measuring 32 Directional power relay 79 Ac reclosing relay 33 Position switch 80 Flow switch 34 Master sequence device 81 Frequency relay 35 Brush-operating 82 Dc reclosing relay Polarity Automatic selection control 36 83 or polarizing voltage device or transfer relay 37 Undercurrent or underpower relay 84 Operating mechanism 38 Bearing protective device 85 Carrier or pilot-wire receiver relay 39 Mechanical condition monitor 86 locking-out relay 40 Field relay 87 Differential protective relay 41 Field circuit breaker Auxiliary motor 88 42 Running circuit breaker or motor generator 43 Manual transfer or selector device 89 Line switch 44 Unit sequence starting relay 90 Regulating device 45 Atmospheric condition monitor 91 Voltage directional relay Reverse-phase, 92 Voltage and power directional relay 46 or phase-balance, current relay 93 Field changing contactor 47 Phase-sequence voltage relay 94 Tripping or trip-free relay 66 SEL COMMAND SUMMARY

Access Level 0 ACCESS Enter Access Level HELP Lists all commands available at the current access level ID Displays SEL-2020 current ID, as set in the global settings QUIT Causes the SEL-2020 to return control to Access Level 0 from Level 1 or 2

Access Level 1 DATE Displays the date stored by the internal calendar/clock PORT n Establishes transparent communication between the master port issuing the command and the designated printer or IED port SHOWSET n Displays settings for the specified class or port number STATUS Shows SEL-2020 self-test and the configuration, communication, and data performance of each port TARGET n m Displays global element or port-specific element information TIME Displays and sets time for the internal clock VIEW m:n Shows data stored in a port’s database WHO Gives a table showing of what is connected to each port

Access Level 0 Command ACC Enter Access Level 1. Enter password if main board password jumper is not in place

Access Level 1 Commands BAC Enter Breaker Access Level (Access Level B) DAT Show date EVE n Show event report number n with ¼ -cycle resolution EVE L n Show event report number n with 1/16-cycle resolution EVE R n Show raw event report number n with 1/16-cycle resolution EVE C n Show compressed event report number n for use with SEL-5601 Analytic Assistant HIS n Show brief summary of the n latest event reports HIS C Clear the brief summary and corresponding event reports MET k Display instantaneous metering data. Enter k for repeat count MET D Display demand and peak demand data. Select MET RD or MET RP to reset MET M Display maximum/minimum metering data. Select MET RM to reset QUI Quit. Returns to Access Level 0 SER n Show the latest n rows in the Sequential Events Recorder (SER) event report SER m n Show rows m through n in the SER event report SER d1 Show rows in the SER event report from date d1 SER d1 d2 Show rows in the SER event report from date d1 to d2 SHO n Show relay settings (overcurrent, reclosing, timers, etc.) for Group n SHO L n Show SELOGIC Control Equation settings for Group n SHO G Show global settings SHO P n Show Port n settings SHO R Show Sequential Events Recorder (SER) settings SHO T Show text label settings STA Show relay self-test status TAR R Reset the front-panel tripping targets TAR n k Display Relay Word row. If n=0 through 45, display row n. Enter k for repeat count TIM Show or set time (24-hour time) TRI Trigger an event report Access Level B Commands

BRE n Enter BRE W to preload breaker wear. Enter BRE R to reset breaker monitor data CLO Assert the CLOSE Relay Word bit GRO n Change active group to group n OPE Assert the TRIP Relay Word bit PUL n k Pulse output contact n (OUT1 – OUT11, ALARM) for k (1-30) seconds. Parameter n must be specified; k defaults to 1 if not specified 67 OFFICIAL TEN SIGNALS OF KEYS COMMUNICATION

PROCEDURE AND DETAILS GENERAL USE

10-1 Unable to copy 10-41 Beginning tour of duty 10-2 Signals good 10-42 Ending tour of duty 10-3 Affirmative-Will do 10-44 Message received by all 10-4 Message Received 10-45 Run service to 10-5 Relay 10-46 Ready for meter 10-6 Busy, Stand by 10-7 Out of Service ACCIDENT & VEHICLE HANDLING 10-8 In Service 10-9 Repeat 10-50 Accident – personal injury 10-10 On minor detail 10-51 Accident 10-11 Remain in service 10-52 Ambulance for 10-50 10-12 Personnel present 10-13 Weather conditions SERVICE HANDLING 10-14 Correct time 10-15 Have in possession 10-60 Unseal 10-16 Pick up 10-61 Seal 10-17 Urgent, rush detail 10-62 Change of name 10-18 Anything for us 10-63 Meter change 10-19 Nothing for you 10-64 Reread 10-20 Location 10-65 Install 10-21 Call by phone 10-66 Remove 10-22 Report in person to 10-67 Voltage check 10-23 Arrived at scene 10-68 Repeat address 10-24 Finished with assignment 10-80 Pole number 10-25 Disregard last information 10-87 Meter number 10-26 Service man on duty 10-88 Name 10-27 Duty man – trouble 10-28 Call lineman by phone NAME

EMERGENCY OR UNUSUAL 10-70 Fire 10-79 Report progress of fire 10-30 Does not conform to rules 10-31 Wires down Technical 10-32 Transformers out 10-33 Call – 30 or other truck 10-90 All vehicles – 10-34 Trouble at location Await instructions 10-35 Major Trouble, alert 10-91 Too weak, closer to mic 10-36 Confidential information 10-92 Too loud, farther from mic 10-37 Lights out in area 10-94 Give a test 10-39 No inspection

68 HAND SIGNALS FOR CRANES AND CHERRY PICKERS

STOP DOG EMERGENCY EVERYTHING STOP

TRAVEL TRAVEL TRAVEL BOTH TRACKS ONE TRACK (CRAWLER CARNES ONLY) (CRAWLERS)

RETRACT EXTEND SWING BOOM BOOM BOOM

69

HAND SIGNALS FOR CRANES AND CHERRY PICKERS

RAISE LOAD LOWER LOAD MAIN HOIST

MOVE SLOWLY RAISE BOOM AND LOWER LOWER BOOM AND LOAD (FLEX FINGERS) RAISE LOAD (FLEX FINGERS)

USE BOOM UP BOOM DOWN WHIP LINE

70 USEFUL KNOTS

BOWLINE RUNNING BOWLING BOWLINE ON THE BIGHT

CLOVE HITCH SHEEPSHANK ROLLING HITCH

SINGLE CATSPAW DOUBLE BLACKWALL BLACKWALL HITCH HITCH

SQUARE KNOT TIMBER HITCH SINGLE WITH HALF HITCH SHEET BEND

71 Centigrade and Fahrenheit Thermometer Scales

DEG-C DEG-F DEG-C DEG-F DEG-C DEG-F DEG-C DEG-F 032 1 33.8 26 78.8 51 123.8 76 168.8 2 35.6 27 80.6 52 125.6 77 170.6 3 37.4 28 82.4 53 127.4 78 172.4 4 39.2 29 84.2 54 129.2 79 174.2 5 41 30 86 55 131 80 176 6 42.8 31 87.8 56 132.8 81 177.8 7 44.6 32 89.6 57 134.6 82 179.6 8 46.4 33 91.4 58 136.4 83 181.4 9 48.2 34 93.2 59 138.2 84 183.2 10 50 35 95 60 140 85 185 11 51.8 36 96.8 61 141.8 86 186.8 12 53.6 37 98.6 62 143.6 87 188.6 13 55.4 38 100.4 63 145.4 88 190.4 14 57.2 39 102.2 64 147.2 89 192.2 15 59 40 104 65 149 90 194 16 60.8 41 105.8 66 150.8 91 195.8 17 62.6 42 107.6 67 152.6 92 197.6 18 64.4 43 109.4 68 154.4 93 199.4 19 66.2 44 111.2 69 156.2 94 201.2 20 68 45 113 70 158 95 203 21 69.8 46 114.8 71 159.8 96 204.8 22 71.6 47 116.6 72 161.6 97 206.6 23 73.4 48 118.4 73 163.4 98 208.4 24 75.2 49 120.2 74 165.2 99 210.2 25 77 50 122 75 167 100 212

1 Temp.C°=5/9 X (Temp. F° - 32)

2 Temp.F°=9/5 X (Temp. C° + 32)

3 Ambient temperature is the temperature of the surrounding cooling medium

4 Rated temperature rise is the permissible rise in temperature above ambient when operating under load

72 Standard Phonetic Spelling Alphabet A – Alpha N – November B – Bravo O – Oscar C – Charlie P – Papa D – Delta Q – Quebec E – Echo R – Romeo F – Foxtrot S – Sierra G – Golf T – Tango H – Hotel U – Uniform I – India V – Victor J – Juliet W – Whiskey K – Kilo X – X-Ray L – Lima Y – Yankee M – Mike Z - Zulu

73 SEL AR360 Fault Indicator

All Events the Indicator will flash Red/Amber sequence for the first two minutes (This is so the unit can determine it is Temporary or Permanent fault)

 Temporary Faults  Flashes for 8 hours  Flashing color - Amber

 Permanent Fault  Flashes for 4 hours  Flashing color - Red/Amber sequence

 Other Helpful Information  At nighttime, photocell dims flashing intensity  Battery life of units 10years from install date  Autoranging units - detects and adjust for load current  The units have Inrush restraint  The units can be reset in the field with a magnetic tool

74 Map Phasing for OMS/Milsoft

Phasing is always read from left to right if horizontal. If vertical it is read from top to bottom, both with your back to source A B C

Map phasing for Partner IOS & Field Engineering Primary Phasing 3-Ø - Black 2-Ø - Orange 1-Ø - A-Green, B-Red, C-Blue

75 NOTES

NOTES

NOTES