TABLE OF CONTENTS TR-XLPE/CN/LLDPE Power, -90 Primary UD, 15kV–35kV Series E9 (Aluminum Solid Conductor)

Product Description The Medium Voltage Primary Underground Distribution (UD) cables consist of an Aluminum Solid conductor, covered with -retardant

LOW VOLTAGE cross-linked polyethylene (TR-XLPE), a concentric neutral of helically applied copper wires, and a linear low-density polyethylene (LLDPE) jacket with 3 extruded red stripes. Applications COMMERCIAL & INDUSTRIAL LLDPE Jacket with 3 Red Stripes • Suitable for underground primary power applications Insulation Shield • For wet or dry locations MEDIUM VOLTAGE • For direct burial or in duct Conductor Shield Features Aluminum Solid Conductor • High dielectric strength TR-XLPE Insulation • Low moisture absorption • Low dielectric loss Copper Wire Concentric Neutral • Excellent resistance to treeing

ARMORED • Jacket is sunlight-resistant • Designed to operate continuously a conductor temperature not exceeding »» 90°C for normal operations »» 130°C for emergency overload »» 250°C for short circuit LOW VOLTAGE Markets UTILITY & RENEWABLES MEDIUM VOLTAGE Specifications Conductor Count 1 conductor Conductor Aluminum 1350 Solid Gauge Sizes Available in 2 AWG through 4/0AWG Conductor Extruded thermoset semi-conducting polymer over the Strand Shield conductor TECHNICAL Insulation Tree-Retardant Cross-linked Polyethylene (TR-XLPE) Extruded thermoset semi-conducting polymer over Insulation Shield the insulation Neutral Helically applied, annealed, solid bare copper wires Jacket Linear Low-Density Polyethylene (LLDPE) 00000 FT CABLE XXAWG (KCMIL) AL SOL 1/C XXKV XXX% INSUL LEVEL XXXMILS TRXLP AA X Jacket Marking #BB LLDPE JKT TYPE MV-90 (UL) MADE IN USA MMDDYYYY (LIGHTNING BOLT) Non-returnable wood reels in a variety of lengths Packaging and dimensions ASTM B-3 ASTM B-230 ASTM B-609 Performance ICEA S-94-649 Compliances AEIC CS8 UL 1072 (MV-90) RUS U1

Product Key Conductor Stranding Voltage Insulation Neutral Options Jacket

or

470.305.1620 All information, content, data, specifications, packaging and part numbers detailed herein are subject to change. For the up-to-date information, please visit lscns.us. Purchase of this product is subject exclusively to the then current LS Cable & System U.S.A., Inc. Terms and Rev 03/19 B-14 lscns.us Conditions of Sale for Energy Cable Products, can be found on our website, lscns.us, or provided to you upon request. 20.1 TR-XLPE/CN/LLDPE Power, Type MV-90 Primary UD (Solid aluminum) Aluminum Solid, 15kV 133% I.L., 220-mils Series E9JK

Part Numbers and Physical Characteristics

Nominal Nominal Nominal Nominal Ampacity OF CONTENTS TABLE Conductor Conductor Insulation Concentric Jacket Overall Nominal Size Diameter¹ Diameter¹ Neutral Thickness¹ Diameter¹ Net Weight¹ Underground Direct Part Number AWG/kcmil in (mm) in (mm) No. x AWG in (mm) in (mm) lbs/kft (kg/km) Duct² Buried² ⅓ Reduced Neutral E9JKT-023S01CA00 2 0.258 (6.6) 0.745 (19.0) 6 x 14 0.055 (1.40) 1.055 (27.0) 485 (721) 126 175 E9JKT-013S01CA00 1 0.289 (7.4) 0.777 (19.9) 6 x 14 0.055 (1.40) 1.087 (27.8) 520 (773) 144 199 E9JKT-1A3S01CA00 1/0 0.325 (8.3) 0.813 (20.8) 6 x 14 0.055 (1.40) 1.123 (28.7) 561 (835) 163 225 VOLTAGE LOW E9JKT-2A3S01CA00 2/0 0.365 (9.3) 0.850 (21.7) 7 x 14 0.055 (1.40) 1.160 (29.7) 622 (925) 186 255 E9JKT-3A3S01CA00 3/0 0.410 (10.4) 0.894 (22.9) 9 x 14 0.055 (1.40) 1.204 (30.8) 704 (1047) 212 286 E9JKT-4A3S01CA00 4/0 0.460 (11.7) 0.948 (24.3) 11 x 14 0.055 (1.40) 1.258 (32.2) 799 (1189) 241 320 Full Neutral E9JKM-023S01CA00 2 0.258 (6.6) 0.745 (19.0) 10 x 14 0.055 (1.40) 1.055 (27.0) 531 (790) 124 170 E9JKM-013S01CA00 1 0.289 (7.4) 0.777 (19.9) 13 x 14 0.055 (1.40) 1.087 (27.8) 602 (895) 143 194

E9JKM-1A3S01CA00 1/0 0.325 (8.3) 0.813 (20.8) 16 x 14 0.055 (1.40) 1.123 (28.7) 675 (1004) 162 220 MEDIUM VOLTAGE COMMERCIAL & INDUSTRIAL COMMERCIAL E9JKM-2A3S01CA00 2/0 0.365 (9.3) 0.850 (21.7) 20 x 14 0.055 (1.40) 1.160 (29.7) 788 (1172) 186 251 E9JKM-3A3S01CA00 3/0 0.410 (10.4) 0.894 (22.9) 25 x 14 0.055 (1.40) 1.204 (30.8) 904 (1345) 212 284 E9JKM-4A3S01CA00 4/0 0.460 (11.7) 0.948 (24.3) 32 x 14 0.055 (1.40) 1.258 (32.2) 1091 (1623) 243 323 ARMORED

Aluminum Solid, 25kV 100% I.L., 260-mils Series E9KK

Part Numbers and Physical Characteristics Nominal Nominal Nominal Nominal Ampacity LOW VOLTAGE LOW Conductor Conductor Insulation Concentric Jacket Overall Nominal Size Diameter¹ Diameter¹ Neutral Thickness¹ Diameter¹ Net Weight¹ Underground Direct Part Number AWG/kcmil in (mm) in (mm) No. x AWG in (mm) in (mm) lbs/kft (kg/km) Duct² Buried² ⅓ Reduced Neutral E9KKT-013S01CA00 1 0.289 (7.4) 0.857 (21.9) 6 x 14 0.055 (1.40) 1.167 (29.9) 579 (861) 146 196 E9KKT-1A3S01CA00 1/0 0.325 (8.3) 0.893 (22.8) 6 x 14 0.055 (1.40) 1.203 (30.8) 622 (926) 166 222 UTILITY & RENEWABLES E9KKT-2A3S01CA00 2/0 0.365 (9.3) 0.930 (23.8) 7 x 14 0.055 (1.40) 1.240 (31.7) 685 (1018) 189 283

E9KKT-3A3S01CA00 3/0 0.410 (10.4) 0.974 (24.9) 9 x 14 0.055 (1.40) 1.304 (33.3) 790 (1175) 216 317 MEDIUM VOLTAGE E9KKT-4A3S01CA00 4/0 0.460 (11.7) 1.028 (26.3) 11 x 14 0.055 (1.40) 1.358 (34.7) 888 (1321) 245 343 Full Neutral E9KKM-013S01CA00 1 0.289 (7.4) 0.857 (21.9) 13 x 14 0.055 (1.40) 1.157 (29.6) 657 (977) 146 194 E9KKM-1A3S01CA00 1/0 0.325 (8.3) 0.893 (22.8) 16 x 14 0.055 (1.40) 1.193 (30.5) 731 (1088) 166 219 E9KKM-2A3S01CA00 2/0 0.365 (9.3) 0.930 (23.8) 20 x 14 0.055 (1.40) 1.250 (32.0) 848 (1261) 190 250

E9KKM-3A3S01CA00 3/0 0.410 (10.4) 0.974 (24.9) 25 x 14 0.055 (1.40) 1.304 (33.3) 977 (1454) 217 283 INFO TECHNICAL E9KKM-4A3S01CA00 4/0 0.460 (11.7) 1.028 (26.3) 32 x 14 0.055 (1.40) 1.398 (35.8) 1180 (1756) 248 322 ¹The dimensions and weights shown are nominal and subject to industry standards and manufacturing tolerances. Other designs available upon request. ²Ampacities: ⅓ Reduced Neutral, triplexed - based on ICEA Standards. Full Neutral, single phase - based on 90°C conductor, 20°C ambient, 100% load , 36" burial depth, and earth RHO 90.

All information, content, data, specifications, packaging and part numbers detailed herein are subject to change. For the most up-to-date 470.305.1620 Rev 03/19 information, please visit lscns.us. Purchase of this product is subject exclusively to the then current LS Cable & System U.S.A., Inc. Terms and Ed 20.1 Conditions of Sale for Energy Cable Products, which can be found on our website, lscns.us, or provided to you upon request. lscns.us B-15